PROJECT :                                                                                           PAGE :
CLIENT :                                                                                     DESIGN BY :
                                             JOB NO. :                                                DATE :                               REVIEW BY :
Wind Analysis for Freestanding Wall & Sign Based on ASCE 7-05
          INPUT DATA
          Exposure category (B, C or D)                                      =             C
          Importance factor, pg 73, (0.87, 1.0 or 1.15)                I     =            1.00       Category II
          Basic wind speed (3 sec. gust wind)                         V      =             90        mph
          Topographic factor (Sec.6.5.7.2, pg 26 & 45)               Kzt     =              1        Flat
          Height of top                                               h      =             35        ft
          Vertical dimension (for wall, s = h)                        s      =              8        ft
          Horizontal dimension                                        B      =            100        ft
          Dimension of return corner                                 Lr      =             2         ft
          DESIGN SUMMARY
          Max horizontal wind pressure                                                           p          =               55   psf
          Max total horizontal force at centroid of base                                         F          =            22.37   kips
          Max bending moment at centroid of base                                                 M          =           693.57   ft-kips
          Max torsion at centroid of base                                                        T          =           447.46   ft-kips
          ANALYSIS
          Velocity pressure
          qh = 0.00256 Kh Kzt Kd V2 I                         =            17.80    psf
          where:      qh = velocity pressure at mean roof height, h. (Eq. 6-15, page 27)
                      Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-3, Case 1,pg 79)                         =     1.01
                      Kd = wind directionality factor. (Tab. 6-4, for building, page 80)                                                   =     0.85
                      h = height of top                                                                                                    =    35.00    ft
          Wind Force Case A: resultant force though the geometric center (Sec. 6.5.14 & Fig. 6-20)
          p = qh G Cf =                                                                    =                28    psf
          F = p As                                                                         =              22.37 kips
          M = F (h - 0.5s) for sign, F (0.55h) for wall                                    =              693.57 ft-kips
          T=                                                                               =               0.00 ft-kips
          where:      G = gust effect factor. (Sec. 6.5.8, page 26).                                                                       =     0.85
                      Cf = net force coefficient. (Fig. 6-20, page 73)                                                                           1.85
                      As = B s                                                                                                             =    800.0    ft2
          Wind Force Case B: resultant force at 0.2 B offset of the geometric center (Sec. 6.5.14 & Fig. 6-20)
          p = Case A                                                        =        28    psf
          F = Case A                                                        =       22.37 kips
          M = Case A                                                        =      693.57 ft-kips
          T = 0.2 F B                                                       =      447.46 ft-kips
          Wind Force Case C: resultant force different at each region (Sec. 6.5.14 & Fig. 6-20)
          p = qh G Cf
          F = S p As
          M = S [ F (h - 0.5s) for sign, F (0.55h) for wall ]
          T = S Ts
              s       Distance         Cf          Pi         Asi           Fi            Mi                Ti
               0          (ft)    (Fig.6-20)      (psf)      (ft2)         (kips)    (ft-kips)        (ft-kips)
   3.63        1          8.0        3.628         55         64            3.51     108.93           161.64
   2.58        2         16.0        2.575         39         64            2.49      77.30            94.76
   1.98        3         24.0        1.975         30         64            1.91      59.29            57.38
   1.41        4         32.0        1.408         21         64            1.36      42.28            30.00
   1.28        5         40.0        1.283         19         64            1.24      38.53            17.40
   0.91       10         80.0        0.908         14         64            0.88      27.27             -8.80
   0.90       B         100.0        0.901         14        160            2.18      67.59            -87.21
                           S                                               13.59     421.19           265.17
                                          PROJECT :                                                                                              PAGE :
                                            CLIENT :                                                                                        DESIGN BY :
                                           JOB NO. :                                          DATE :                                        REVIEW BY :
Wind Analysis for Shade Open Structure Based on ASCE 7-02 / IBC 2003
       INPUT DATA
       Exposure category (A,,B, C or D)                                  =             C
       Importance factor, pg 73, (0.87, 1.0 or 1.15)               Iw    =            1.00   Category II
       Basic wind speed (3 sec. gust wind)                         V     =             90    mph
       Topographic factor (Sec.6.5.7.2, pg 30 & 47)             Kzt      =             1     Flat
       Height of ridge                                           h       =            35     ft
       Roof slope                                                                      4     : 12
       Roof length                                                 L     =            100    ft
       Roof horizontal projected width                             B     =            60     ft
       DESIGN SUMMARY
       Max horizontal force / base shear                                                                     =              31.12   kips
       Max vertical download force                                                                           =               0.00   kips
       Max vertical uplift force                                                                             =              93.84   kips
       Max bending moment at centroid of base                                                                =             948.68   ft-kips
       ANALYSIS
       Velocity pressure
       qz = 0.00256 Kz Kzt Kd V2 Iw                         =           17.17   psf
       where:      qz = velocity pressure at mean roof height, h. (Eq. 6-15, page 31)
                   Kz = velocity pressure exposure coefficient evaluated at height, z, (Tab. 6-3, Case 1,pg 75)                         =         0.97
                   Kd = wind directionality factor. (Tab. 6-4, for building, page 76)                                                   =        0.85
                   z = height of centroid of front roof area                                                                            =        29.29     ft
       Design pressures for wind force acting nomal to the roof
       F = qz G C f A f               =     (   15.64   psf ) Af         =        34.62      kips, (inward at front)
                                      =     (   15.64   psf ) Af         =        34.62      kips, (outward at front)
                                      =     (   15.64   psf ) Af         =        34.62      kips, (outward at back)
                                     = ( 15.64 psf ) Af               =       14.84 kips, (outward at each side)
       where:      F = design wind load on open structural roof. (Eq. 6-25, page 34).
                   G = gust effect factor. (Sec. 6.5.8.1 & 6.5.8.3, page 30).                                                           =        0.85
                   q = roof angle                                                                                                       =        18.43     degree
                   Cf = net force coefficients. (Fig. 6-18, page 68)                                                                    =         1.07     inward at front
                                                                                                                                        =         1.07     outward at front
                                                                                                                                        =         1.07     outward at back
                                                                                                                                        =         1.07     outward at sides
                   Af = roof actual area.                                                                                               =       2213.6     ft2, front / back
                                                                                                                                        =        948.7     ft2, each side
       Horizontal force / base shear                                                                                   H                =          21.90   kips
       Vertical download force                                                                                         V                =           0.00   kips
       Vertical uplift force                                                                                           V                =          93.84   kips
       Bending moment at centroid of base                                                                              M                =          641.3   ft-kips
       Design pressures for wind force acting to horizontal projected area
       F = qz G C f A f                = ( 42.34 psf ) Af             =        31.12 kips, (horizontal)
       where:      F = design wind load on open structural roof. (Eq. 6-25, page 34).
                   G = gust effect factor. (Sec. 6.5.8.1 & 6.5.8.3, page 30).                                                           =         0.85
                   e = ratio of solid area to gross area. (Fig. 6-22 notes 7, page 72)                                                  =         0.22
                   Cf = net force coefficients. (Fig. 6-22, page 72, larger of square & triangle)                                       =         2.90
                   Af = horizontal projected area normal to the wind, included columns area.                                            =        735.0     ft2
       Horizontal force / base shear                                                                    H=F                             =          31.12 kips
       Vertical uplift / download force                                                                 V                               =           0.00 kips
       Bending moment at centroid of base                                                               M=Fz                            =          911.4 ft-kips