Structural DWG
Structural DWG
GABLE END
11"
GABLE END
2'-0"
EDGE OF HOUSE OF VAULTED
CEILING Residential - Com. Design
14" TRUSS JOISTS
1"
2X6 TREATED
RAFTER TIE
@ 36" O.C.
8'-2"
RE: ARCH
ISSUE DATE:
3/26/2021
DRAWN BY:
30'-0" aba
CHECK BY:
bl
A/S2
3'-0"
1. #3 @ 15" O.C., U.O.N 8x8 GRADE BEAM INCORPORATED HEREIN, AS AN INSTRUMENT
#3 REBAR @ 15" O.C.
1"
32
2. 6 MIL POLYETHLENE VAPOR BARRIER, EXTEND FULL COVERAGE UNDER ENTIRE FLOOR SLAB. @ STAIR BASE OF PROFESSIONAL SERVICE, IS THE PROPERTY
EACH WAY
OF ABA DESIGN STUDIO AND IS NOT TO BE
1'-4"
3. 2" MIN. SAND LEVELING LAYER
USED IN WHOLE OR IN PART, FOR ANY OTHER
2'-8" PROJECT OR PURPOSE WITHOUT THE WRITTEN
4. REINFORCING SUPPORT CHAIR @ 48" ON CENTER EACH WAY.
AUTHORIZATION OF ABA DESIGN STUDIO.
4'-4"
3/4" DOOR
2'-4"
5. 2 - #5 BARS TOP & BOTTOM OF STIRRUPS FOR 12" GRADE BEAMS AND 3 FOR 16" GRADE BEAMS
RECESS
6. #4 DOWEL @ 45° WITH 1'-6" LEGS @ 24" O.C
1'-0"
7. FINISH GRADE: SLOPE PER SITEWORK.
2'-10"
9'-0"
* DESIGN BASED ON ADJACENT SLAB PERFORMANCE AND EXISTING CONDITIONS WHEN ADDING TO EXISTING SLAB. COLUMN BASE
1"
1'-02 1"
32
1'-4" SIMPSON CB66
15'-2"
SUBGRADE PREPARATION AND FILL: FOR WOOD COLUMN
A/S2 SIM
1. STRIP AREAS WITHIN BUILDING LINES TO REMOVE ALL VEGETATION, TOP SOIL AND DEBRIS. 1"
18'-22
D/S2
9'-10"
2. FOLLOWING STRIPPING, PROOF ROLL EXPOSED SUBGRADE TO IDENTIFY WEAK OR SOFT AREAS.
SUCH ZONES SHALL BE REMOVED AND REPLACED WITH SELECT FILL.
slope 1/8" per ft. slope 1/8" per ft.
3"
3. GRADE AREA TO PREVENT PONDING OF WATER. DO NOT ALLOW EXPOSED SUBGRADE TO DRY.
26'-0"
PLASTICITY INDEX (PI) : 7 TO 20% LIQUID LIMIT: 28 TO 40 %
21'-8"
1'-4"
BE DISPOSED OUTSIDE SLAB AREAS.
6. CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS TO AVOID OVER CUTTING AND FILLING THE SLAB AREA
AND TO PROTECT SITE. SITE BUILDING TO SEE WHAT IS ESSENTIAL AND WHAT CAN BE REMOVED.
ABADesign
16'-0"
B/S2
B/S2
SURFACE DRAINAGE: C/S2 #3 REBAR @ 15" O.C.
THE DRAINAGE PRECAUTIONS LISTED BELOW SHOULD BE OBSERVED DURING CONSTRUCTION AND AT ALL TIMES AFTERWARD; EACH WAY Houston, Texas 77064
1"
AFTER THE STRUCTURE HAS BEEN COMPLETED, BUILDER SHALL ADVISE OWNER OF THESE PRECAUTIONS AND
21'-02
8'-10"
CORRECTED MEASURES NEEDED TO ADDRSS ANY REMAINING DRAINAGE ISSUES.
Residential - Com. Design
10'-10"
1. THE GROUND SURFACE SURROUNDING THE EXTERIOR OF THE STRUCTURE MUST BE SLOPED TO DRAIN
AWAY FROM THE STRUCTURE IN ALL DIRECTIONS FOR A MINIMUM DISTANCE OF FIVE (5) FEET WITH A
F/S1 A/S2 SIM M: 832.331.5546
A/S2 SIM
MINIMUM OF SIX (6) INCHES OF VERTICAL FALL. 6"
2. WATER SHOULD NOT BE ALLOWED TO POND NEXT TO THE STRUCTURE & SIDE DRAINAGE SWALES MUST NOT BE BLOCKED. A/S2 B/S2
3. WHERE LANDSCAPING IS TO BE INSTALLED NEXT TO PERIMETER GRADE BEAMS, A MOISTURE BARRIER OR
F/S1
OTHER SUITABLE MEANS IS RECOMMENDED TO PREVENT MOISTURE FROM ENTERING UNDERLYING CLAY ashely.benton@gmail.com
SOILS.
2'-10"
4. ROOF DOWNSPOUTS AND DRAINS SHOULD DISCHARGE WELL AWAY FROM THE LIMITS OF THE FOUNDATIONS
6"
1'-4"
AND AWAY FROM EDGE OF PERIMETER GRADE BEAMS. IF SUCH CANNOT BE PROVIDED, AN UNDERGROUND PIPE
VARIES
DRAINAGE SYSTEM SHALL BE PROVIDED BY BUILDER; ABSENCE OF SUCH PIPE DRAIN SYSTEM CAN CAUSE FUTURE
FOUNDATION SOIL MOVEMENT & FOUNDATION PERFORMANCE ISSUES. ALL DRAIN PIPE SYSTEMS MUST UTILIZE
REVISION DATE:
1"
SOLID PVC PIPES AND PROPERLY SLOPED.
32
COLUMN BASE
2'-2" 6'-10" 9'-0" 7'-6" 6"
CONCRETE: 8" 8"
SIMPSON CB66 -
1'-4" 1'-4" FOR WOOD COLUMN
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE "ACI STANDARD BUILDING CODE REQUIREMENT
11'-0" 11'-0" 8'-0" -
FOR STRUCTURAL CONCRETE: (ACI 318-99)".
2. NORMAL WEIGHT CONCRETE WITH MINIMUM 28 DAY COMPRESSIVE STRENGTH (f'c) = 2500 PSI
-
3. CONCRETE SHOULD BE PLACED IN THE FOOTING EXCAVATIONS AS SOON AS POSSIBLE AFTER EXCAVATION
TO MINIMIZE THE POSSIBILTY OF CAVING OF DRILLED PIERS.
-
4. CLEAN TOPS OF PIERS AND BOTTOM OF GRADE BEAM TRENCHES THOUROUGHLY PRIOR PLACEMENT OF
CONCRETE IN THE GRADE BEAMS.
-
5. INDEPENDENT INSPECTOR SHALL REVIEW DRILLED PIERS PRIOR TO CONCRETE PLACEMENT.
1. Foundation Plan
scale:1/4"=1'-0"
PIPING PENETRATIONS:
1. ALL PIPING PENETRATIONS THROUGH EXTERIOR GRADE BEAMS SHALL BE SLEEVED WITH SCHEDULE 40
PIPE.
6 - #5 REBAR 1"
52
W/ #3 STIRRUPS 1"
1'-12
1/2" ANCHOR BOLTS 4-#5 REBAR
@ 16" O.C., TYP.
@ 4'-0" O.C. AND 8" 1-#4 CONT. NOSING BAR #3 REBAR @ 15" W/ #3 STIRRUPS
#3 REBAR @ 15" OFF END OF SLAB, TYP. @ SLAB RECESSES O.C EACH WAY, TYP. @ 16" O.C., TYP. NEW DRIVEWAY
GREATER THAT 51/2"
3"
O.C EACH WAY, TYP.
FINISHED FLOOR
6"
2'-0"
4"
2'-0"
4"
3"
3"
SAND BASE
4" SAND BASE
6 MIL PLASTIC 2" MIN. SAND BASE
VAPOR BARRIER 6 MIL PLASTIC
VAPOR BARRIER
GRADE AND SELECT FILL
1'-4" 1'-4" NATURAL GRADE
NATURAL GRADE
Garage Addition
scale: 3/4"=1'-0" scale: 3/4"=1'-0"
scale: 3/4"=1'-0"
VARIES
4-#5 REBAR 4-#5 REBAR 4-#5 REBAR
W/ #3 STIRRUPS #3 REBAR @ 15" W/ #3 STIRRUPS #3 REBAR @ 15" W/ #3 STIRRUPS #3 REBAR @ 15"
@ 16" O.C., TYP. O.C EACH WAY, TYP. @ 16" O.C., TYP. O.C EACH WAY, TYP. @ 16" O.C., TYP. O.C EACH WAY, TYP.
4"
ISSUE DATE:
2'-0"
2'-0"
2'-0"
4"
4"
3"
3"
3"
SAND BASE 3/26/2021
6 MIL PLASTIC SAND BASE SAND BASE
VAPOR BARRIER 6 MIL PLASTIC 6 MIL PLASTIC DRAWN BY:
VAPOR BARRIER VAPOR BARRIER aba
1'-4" NATURAL GRADE CHECK BY:
1'-4" 1'-4"
NATURAL GRADE NATURAL GRADE
bl
SHEET NUMBER:
B. FOUNDATION DETAIL
scale: 3/4"=1'-0" D. FOUNDATION DETAILS F. FOUNDATION DETAILS
scale: 3/4"=1'-0" scale: 3/4"=1'-0"
S2
© 2021 ABA DESIGN STUDIO
abastudio.co
ABADesign
Houston, Texas 77064
M: 832.331.5546
ashely.benton@gmail.com
REVISION DATE:
-
-
-
-
-
1. COH Sidewalk detail - Joints 2. COH Driveway Detail @ Street 3. COH Sidewalk Details
Standard Details
ISSUE DATE:
3/26/2021
DRAWN BY:
aba
CHECK BY:
bl
SHEET NUMBER: