Ib 0600777 Engc
Ib 0600777 Engc
INVERTER
Plug-in option
FR-A8AVP
INSTRUCTION MANUAL (FOR INVERTER/CONVERTER SWITCHING)
Changeover between inverter and
high power factor converter
Compatible inverters: FR-A842-07700(315K) to 12120(500K)
OUTLINE
1
INVERTER-TO-
CONVERTER 2
CONVERSION
INSTALLATION AND
WIRING 3
Safety instructions 1
WARNING CAUTION
Usage
Usage Do not repeatedly start or stop the inverter/converter with a
Stay away from the equipment when the retry function is set as magnetic contactor on its input side. Doing so may shorten the
the inverter/converter will restart suddenly after its output shutoff.
life of the inverter/converter.
Depending on the function settings, the inverter/converter does
Use a noise filter or other means to minimize the
not stop its output even when the STOP/RESET key on the electromagnetic interference with other electronic equipment
operation panel is pressed. To prepare for it, provide a separate
used nearby the inverter/converter.
circuit and switch (to turn OFF the power or to take other
As all parameters return to their initial values after the Parameter
actions) for an emergency stop. clear or All parameter clear is performed, the parameters must
Be sure to turn OFF the start (STF/STR) signal before clearing
be set again as required before the operation is started.
the fault as the inverter/converter will restart the motor suddenly
Before running an inverter/converter which have been stored
after a fault is cleared. and not been operated for a long period, perform an inspection
Use only the specified inverters for the connection with the
and a test operation.
converter. Connection of any other electrical equipment to the
To avoid damage due to static electricity, static electricity in your
output of the converter may damage the equipment. body must be discharged before you touch the inverter/
Do not modify the inverter/converter.
converter.
Do not remove any part which is not instructed to be removed in
Emergency stop
the Instruction Manual. Doing so may lead to a failure or A safety backup such as an emergency brake must be provided
damage. for devices or equipment in a system to prevent hazardous
conditions in case of failure of the inverter/converter or its
external controller.
If the breaker installed on the input side of the inverter/converter
trips, check for wiring faults (short circuits etc.) and damage to
internal parts of this product.
When any fault occurs, take an appropriate corrective action,
then reset the inverter/converter, and resume the operation.
Maintenance, inspection and parts replacement
Do not carry out a megger (insulation resistance) test on the
control circuit of the inverter/converter.
Disposal
This product must be treated as industrial waste.
General instruction
For clarity, illustrations in this Instruction Manual may be drawn
with covers or safety guards removed. Ensure all covers and
safety guards are properly installed prior to starting operation.
2 Safety instructions
CONTENTS
1 OUTLINE 7
1.1 Pre-operation instructions 8
1.1.1 Unpacking and checking the product................................................................................................................9
1.1.2 Component names .........................................................................................................................................10
2 INVERTER-TO-CONVERTER CONVERSION 13
2.1 Conversion flowchart 14
2.3 Troubleshooting 18
CONTENTS 3
3.8 Earthing (Grounding) precautions 47
5 PARAMETERS 79
5.1 Operation panel (FR-DU08) 80
5.1.1 Components of the operation panel ............................................................................................................... 80
5.1.2 Basic Operation of the Operation Panel......................................................................................................... 81
5.1.3 Digital characters and their corresponding printed equivalents...................................................................... 82
5.1.4 Changing the parameter setting value ........................................................................................................... 82
4 CONTENTS
5.4.10 Retry function (Pr.65, Pr.67 to Pr.69) ...........................................................................................................102
5.4.11 Reset selection / disconnected PU detection / PU stop selection (Pr.75) ....................................................104
5.4.12 Parameter write disable selection (Pr.77).....................................................................................................106
5.4.13 Current control (Pr.82 and Pr.83) .................................................................................................................107
5.4.14 Power factor adjustment function (Pr.84 and Pr.85).....................................................................................107
5.4.15 Wiring and configuration of PU connector ....................................................................................................108
5.4.16 Wiring and configuration of RS-485 terminals ..............................................................................................110
5.4.17 Initial setting of operation via communication ...............................................................................................113
5.4.18 Initial settings and specifications of RS-485 communication ........................................................................113
5.4.19 Mitsubishi inverter protocol (computer link communication) .........................................................................115
5.4.20 PU display language selection......................................................................................................................126
5.4.21 Disabling the setting dial and keys on the operation panel...........................................................................126
5.4.22 Input terminal function selection (Pr.178 to Pr.189)......................................................................................127
5.4.23 Operation selection for the RDY signal and the RSO signal (Pr.190 and Pr.191)........................................128
5.4.24 Output terminal function selection (Pr.192 to Pr.194, Pr.196) ......................................................................129
5.4.25 Cooling fan operation selection ....................................................................................................................131
5.4.26 Converter parts life display (Pr.255 to Pr.257)..............................................................................................132
5.4.27 Maintenance timer alarm ..............................................................................................................................134
5.4.28 Detection of control circuit temperature ........................................................................................................135
5.4.29 Adjustment of terminal FM/CA and terminal AM...........................................................................................136
5.4.30 Free parameter .............................................................................................................................................139
5.4.31 Beep control..................................................................................................................................................140
5.4.32 PU contrast adjustment ................................................................................................................................140
5.4.33 Initiating a protective function .......................................................................................................................140
5.4.34 Simple clock function ....................................................................................................................................141
5.5 Parameter clear / All parameter clear on the operation panel 142
5.7 Checking parameters changed from their initial values (initial value change list) 146
CONTENTS 5
7.1.4 Continuity test............................................................................................................................................... 166
7.1.5 Cleaning ....................................................................................................................................................... 166
7.1.6 Replacement of parts ................................................................................................................................... 167
7.1.7 Removal and reinstallation of the control circuit terminal block ................................................................. 170
8 SPECIFICATIONS 175
8.1 Converter rated specifications 176
APPENDIX 189
Appendix 1 Instruction code list............................................................................................................... 190
Appendix 2 Instructions for compliance with the EU Directives........................................................... 192
Appendix 3 Instructions for UL and cUL ................................................................................................. 194
Appendix 4 Instructions for EAC.............................................................................................................. 195
Appendix 5 Restricted Use of Hazardous Substances in Electronic and Electrical Products ........... 196
Appendix 6 Referenced Standard (Requirement of Chinese standardized law).................................. 196
6 CONTENTS
1 OUTLINE
<Abbreviations>
DU ........................... Operation panel (FR-DU08) 1
PU ........................... Operation panel (FR-DU08) or parameter unit (FR-PU07)
Inverter .................... Mitsubishi Electric inverter
Converter ................ High power factor converter converted from the inverter by using the FR-A8AVP
Pr. ........................... Parameter number (Number assigned to function of the inverter or the converter)
<Trademarks>
• Ethernet is a registered trademark of Fuji Xerox Corporation in Japan.
• Microsoft and Visual C++ are registered trademarks of Microsoft Corporation in the United States and other
countries.
• Other company and product names herein are the trademarks and registered trademarks of their respective
owners.
OUTLINE 7
Pre-operation instructions
NOTE
• To use the phase-synchronized bypass switching function, refer to the other instruction manual which is included with the FR-
A8AVP which is dedicated to the function (manual number: IB-0600809ENG).
8 OUTLINE
Pre-operation instructions
Product confirmation
Check the enclosed items.
Plug-in option: 1 Mounting screw (M3 × 8 mm): 2 Spacer: 2 • Converter sticker sheet: 1
(Refer to page 11.) (Refer to page 11.) (Refer to page 16 and page 187.)
Not used.
OUTLINE 9
Pre-operation instructions
SERIAL 6(5,$/;;;;;;;;;
NOTE
• Ethernet communication is not available when the FR-A802-E inverter has been converted to the high power factor converter.
(f) SERIAL
(e)
Ver.
(a) (a)
RS2
TS2
RSO
SE2
RYA
R2
T2
(b) (b)
(a)
Refer to
Symbol Name Description
page
a Mounting hole Fix the option to the inverter (converter) with the screws, or insert spacers. 11
Used to connect the converter (converted from the inverter) to the phase detection
b Terminal block 49
transformer box and to an inverter.
Switch (SW1) for
c Do not change from the initially-set status (OFF: O
). —
manufacturer setting N
10 OUTLINE
Pre-installation instructions for the FR-A8AVP
CAUTION
Do not install or remove the FR-A8AVP while the inverter power is ON. Doing so may damage the
inverter or plug-in option.
To avoid damage due to static electricity, static electricity in your body must be discharged before
you touch the product.
Connector 3
OUTLINE 11
Installing the FR-A8AVP
NOTE
• When installing/removing an option, hold the sides of the circuit board. Do not press on the parts on the circuit board. Stress
applied to the parts by pressing, etc. may cause a failure.
• Take caution not to drop screws during installation and removal of the option.
• Two or more of the same plug-in options cannot be connected. When multiple options are installed, priority is given to option
connectors 1, 2 and 3 on the inverter in this order, and options having a lower priority do not function.
• When the inverter cannot recognize the FR-A8AVP due to improper installation or any other reason, the protective function
(E.1 to E.3) is activated and the inverter cannot be operated. The indication to be shown depends on the position (option
connector 1 to 3) used.
Option connector 2
Option connector 3
• When removing the plug-in option, remove the two screws on the left and right, then pull it straight out. Pressure applied to
the connector and to the option board may break the option.
12 OUTLINE
2 INVERTER-TO-
CONVERTER
CONVERSION
This chapter explains how to convert the inverter into a high power factor
converter.
Always read the instructions before use.
INVERTER-TO-CONVERTER CONVERSION 13
Conversion flowchart
Preparation
(main circuit: power-OFF, (a)
control circuit: power-ON)
Conversion (b)
(Pr.328 setting change)
Refer to
Symbol Description
page
Preparation for the inverter-to-converter conversion.
(a) Be sure to turn OFF the main circuit power of the inverter, and turn ON the control circuit power of the inverter 15
(supplied via terminals R1/L11 and S1/L21 from a separate power source).
(b) Change the setting of Pr.328 in the inverter to convert the inverter into a high power factor converter. 16
(c) Turn OFF the control circuit power. 16
(d) Connect an inverter and the converter options to the converter. 40
(e) After the wiring is completed, turn ON the main circuit power of the converter. —
14 INVERTER-TO-CONVERTER CONVERSION
Conversion procedure
Check the following while the control circuit power of the inverter is OFF.
• The FR-A8AVP is installed in one of the option connectors (1 to 3). (Refer to page 11.)
• All of the main circuit terminals are left open.
• Terminals R1/L11 and S1/L21 are used to supply power to the control circuit of the inverter.
• No USB memory device is connected.
Check the following while the control circuit power of the inverter is ON.
• The inverter is in the PU operation mode (not in the External/PU combined operation mode 1 or 2).
• The PLC function is disabled (Pr.414 = "0").
• The inverter is in normal state and its operation is stopped (its output is shut off). (No protective function is activated.)
NOTE
• When terminal +24 is used to supply power to the control circuit of the inverter, the conversion to the converter is disabled.
• Sequence programs stored in the inverter for the PLC function will be cleared after the conversion. Be sure to back up the
programs before conversion.
INVERTER-TO-CONVERTER CONVERSION 15
Conversion procedure
1 Enter "3100".
Check that "3100" is displayed for Pr.328.
2 Enter "5010".
Check that "5010" is displayed for Pr.328.
3 Enter "1000".
The inverter-to-converter conversion starts when "1000" is entered. The communication status LED indicator
starts blinking. (The following figure shows the location of the LED indicator.)
The LED indicator stays ON after the conversion is completed.
(It takes about 300 seconds to complete the conversion.)
NOTE
• After entering "1000", do not operate the PU until the LED indicator stays ON.
6 Press the setting dial on the operation panel (FR-DU08) and check that "CNV" (converter) is
displayed.
NOTE
• If the control circuit power is turned OFF once and then turned ON again, conversion may restart depending on the timing of
power OFF.
16 INVERTER-TO-CONVERTER CONVERSION
Conversion procedure
CONVERTER
• Check that the power of the converter is OFF and open the terminal block cover. Attach the main circuit terminal stickers
over the existing "U", "V", and "W" stickers as shown in the following figure.
INVERTER-TO-CONVERTER CONVERSION 17
Troubleshooting
2.3 Troubleshooting
Condition Possible cause Countermeasure
Preparation for the conversion has not been Complete the preparation.
Pr.328 cannot be overwritten.
completed. (Refer to page 15.)
Follow the procedure from step 1 to step 3
The Pr.328 setting returns to "0 (initial The procedure from step 1 to step 3 was not
properly.
value)". followed properly.
(Refer to page 16.)
The inverter is in the process of the Contact your sales representative if the
The communication status LED will not conversion (the conversion takes 300 communication status LED indicator remains
change from blinking to constantly lit. seconds after Pr.328 has been set to blinking (does not become solid) even after a
"1000"). lapse of 300 seconds.
• Press the setting dial on the operation
panel (FR-DU08) and check the indication.
Checking of the current state (inverter or
— (Refer to page 16.)
converter) is required.
• Check the Pr.328 setting. (Refer to page
16.)
"11" is displayed for Pr.328 after the
— Please contact your sales representative.
conversion.
18 INVERTER-TO-CONVERTER CONVERSION
3 INSTALLATION AND
WIRING
This chapter explains the installation and the wiring of the converter.
Always read the instructions before use.
Fuse
Phase detection transformer box Install the MC to ensure safety.
(FR-A8VPB) Select a fuse according to the
Check that its capacity is appropriate connected motor capacity.
for the capacity of the converter. (Refer to page 21.)
(Refer to page 8 and 30.)
Inverter
Check that the inverter is
compatible with the high power
factor converter. (Refer to page 22
for compatible inverter.)
Select an inverter according to the
Reactor 1 (FR-A8BL1) capacity of the converter.
Check that its capacity is appropriate The control logic (sink logic/source
for the capacity of the converter. logic) of the converter and the
(Refer to page 8 and 29.) inverter must be matched.
(Refer to page 53.)
Reactor 2 (FR-A8BL2)
Check that its capacity is appropriate Earth
Devices on the inverter's output side
for the capacity of the converter. (ground)
Do not install a power factor correction
(Refer to page 8 and 29.) capacitor or surge suppressor on the inverter's
output side.
When installing a molded case circuit breaker
on the output side of the inverter, contact the
manufacturer of the molded case circuit
breaker.
Earth (ground)
Always earth (ground) the converter, converter
options, inverter, and motor.
NOTE
• When the breaker installed at the converter's input line is shut off, check for the wiring fault (short circuit), damage to internal
parts of the converter, etc. The cause of the trip must be identified and removed before turning ON the power of the breaker.
Fuse
Installation of a fuse is recommended between the converter and an inverter. Select a fuse according to the capacity of the
connected motor. When using a motor, of which the capacity is smaller than the inverter capacity by two ranks or more, select
the fuse with the capacity that is one rank lower than the inverter capacity. (For the details, refer to page 45.)
• Fuse selection table
Motor capacity (kW) Fuse rating (A) Model 3
6.9 URD 232 TDF 1600 or
315 1600
6.9 URD 31 TTF 0800 × 2 (parallel connection)
6.9 URD 232 TDF 1800 or
355 1800
6.9 URD 32 TTF 0900 × 2 (parallel connection)
6.9 URD 232 TDF 1800 or
400 1800
6.9 URD 32 TTF 0900 × 2 (parallel connection)
450 2500 6.9 URD 33 TTF 1250 × 2 (parallel connection)
500 2700 6.9 URD 32 TTF 0900 × 3 (parallel connection)
NOTE
• Install fuses across terminals P/+ and P/+, and across terminals N/- and N/- of the converter and an inverter.
• Fuses are not required when the converter is used in combination with a FR-A842-07700(315K) to 12120(500K) inverter,
which has internal fuses.
Estimated lifespan for when the yearly average surrounding air temperature is 50°C (without corrosive gas, flammable gas, oil mist, dust and dirt etc.).
NOTE
• If the fuse melts down, wiring failure such as a short circuit may be the cause. Find out the cause and remove it before replacing the fuse.
NOTE
• For details of the inverter capacity, refer to the rating specifications in the Instruction Manual of the inverter.
Example: FR-A820
00046 00077 00105
Model FR-A820-[]
0.4K 0.75K 1.5K
SL D 0 .7 5 1 .5 2 .2
When the inverter capacity and the applicable motor capacity are equal
(FR-A800 (ND rating), FR-F800 (LD rating), and 700 series inverters)
Inverter capacity
132K
Converter capacity
or 160K 185K 220K 250K 280K 315K 355K 375K 400K 450K 500K 530K 560K
lower
FR-A842-07700(315K) - -
FR-A842-08660(355K) - -
FR-A842-09620(400K) - - -
FR-A842-10940(450K) - - - -
FR-A842-12120(500K) - - - -
When the applicable motor capacity is higher than the inverter capacity
(FR-A800 (LD rating), FR-A800 (SLD rating), and FR-F800 (SLD rating))
Refer to the table above to check the applicability of the converter. When the capacity of a motor to be installed is larger than
the converter capacity, read the "inverter capacity" in the table above as the applicable "motor capacity".
When the applicable motor capacity is lower than the inverter capacity
(FR-A800 (HD rating))
Inverter capacity
132K
Converter capacity
or 160K 185K 220K 250K 280K 315K 355K 400K 450K 500K 560K
lower
FR-A842-07700(315K) - -
FR-A842-08660(355K) - -
FR-A842-09620(400K) - - -
FR-A842-10940(450K) - - - -
FR-A842-12120(500K) - - - -
Temperature
The permissible surrounding air temperature of the converter is between -10 and +50°C. Always operate the converter within
this temperature range. Operation outside this range will considerably shorten the service lives of the semiconductors, parts,
capacitors and others. Take the following measures to keep the surrounding air temperature of the converter within the
specified range.
(a) Measures against high temperature
• Use a forced ventilation system or similar cooling system. (Refer to page 26.)
• Install the enclosure in an air-conditioned electric chamber.
• Block direct sunlight.
• Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat source.
• Ventilate the area around the enclosure well.
(b) Measures against low temperature
• Provide a space heater in the enclosure.
• Do not power OFF the converter. (Keep the start signal of the inverter OFF.)
(c) Sudden temperature changes
• Select an installation place where temperature does not change suddenly.
• Avoid installing the converter near the air outlet of an air conditioner.
• If temperature changes are caused by opening/closing of a door, install the converter away from the door.
Humidity
Operate the converter within the ambient air humidity range of 45 to 90% (up to 95% with circuit board coating). Too high
humidity will pose problems of reduced insulation and metal corrosion. On the other hand, too low humidity may cause a
spatial electrical breakdown. The humidity conditions for the insulation distance defined in JEM 1103 standard "Insulation
Distance from Control Equipment" is 45 to 85%.
Countermeasure
• Place the converter in a totally enclosed enclosure.
Take measures if the in-enclosure temperature rises. (Refer to page 26.)
• Purge air.
Pump clean air from outside to make the in-enclosure air pressure higher than the outside air pressure.
High altitude
Use the converter at an altitude of within 2500 m. For use at an altitude above 1000 m, consider a 3% reduction in the rated
current per 500 m increase in altitude.
If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air pressure will deteriorate dielectric
strength.
Vibration, impact
The vibration resistance of the converter is up to 2.9 m/s2 at 10 to 55 Hz frequency and 1 mm amplitude for the directions of
X, Y, Z axes. Applying vibration and impacts for a long time may loosen the structures and cause poor contacts of connectors,
even if those vibration and impacts are within the specified values.
Especially when impacts are applied repeatedly, caution must be taken because such impacts may break the installation feet.
Countermeasure
• Provide the enclosure with rubber vibration isolators.
• Strengthen the structure to prevent the enclosure from resonance.
• Install the enclosure away from the sources of the vibration.
Natural
Being a totally enclosed type, this system is the most
Natural ventilation (totally appropriate for hostile environment having dust, dirt, oil mist,
enclosed type) etc. The enclosure size increases depending on the converter
Converter
capacity.
Heat sink This system has restrictions on the heat sink mounting
Heat sink cooling Converter position and area. This system is for relatively small
capacities.
Heat pipe
This system is a totally enclosed type, and is appropriate for
Heat pipe
Converter enclosure downsizing.
20 cm or more
3
5 cm
or
more
10 cm 10 cm ∗1
Converter
or or
more more
Vertical
For replacing the cooling fan, 30 cm of space is necessary in front of the converter. Refer to page 167 for fan replacement.
NOTE
• To remove or reinstall the front cover or the operation panel (FR-DU08) of the converter, refer to the FR-A802 Instruction
Manual (Hardware) as the procedure is the same as that for the inverter.
DANGER CAUTION
Clearances
As the reactors generate heat, leave sufficient space around them.
5 cm or more
5 cm or more 5 cm or more
Installation place
Install the reactors on nonflammable material. Installing them directly on flammable material will cause a fire.
Surrounding environment
Avoid places where the reactors are subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Choose a clean place for installation, or protect it from suspended substances using a dust filter or the like.
Installation orientation
To prevent looseness, install the reactors on a horizontal surface securely with screws or bolts.
Do not install them on a vertical surface. Install them on a mounting stand which can withstand its weight.
NOTE
• As the charged sections of the reactors are uncovered, fully protect them to prevent ground fault and electric shock.
• Intrusion of wire offcuts or dust into the cooling fan of the reactors can cause a failure or malfunction.
Keep clean environment for the reactors.
Clearances
10 cm or more
10 cm or more
Installation place
Install the transformer box on nonflammable material. Installing it directly on flammable material will cause a fire.
Surrounding environment
Avoid places where the transformer box is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the transformer box in a clean place or protect it from suspended substances.
Installation orientation
Install the transformer box in a vertical position.
Vertical
Front cover
Front cover
Reinstallation
• Align the screw holes on the cover with the holes • Fix the cover with the mounting screw
on the transformer box, and place the cover back (tightening torque: 1.7 N m).
into position.
NOTE
• Fully make sure that the front cover has been reinstalled securely. Always tighten the mounting screws of the cover.
• The capacity plate is placed on the cover, and the rating plate is on the remainder of the transformer box. For reinstallation,
check the serial number on the capacity plate against the one on the rating plate to make sure they are identical with each
other.
Wiring method
Cut small slits in the rubber grommets mounted on the underside of the transformer box, and pass the cables through the slits.
NOTE
• To satisfy IP20 protection requirements, note the following points for wiring of the transformer box.
- Do not cut slits in the rubber grommets which are not used for wiring.
- Do not use the transformer box with the rubber grommets removed.
10 cm or more
10 cm or more 10 cm or more
Installation place
Install the filter capacitor on nonflammable material. Installing it directly on flammable material will cause a fire.
Surrounding environment
Avoid places where the filter capacitor is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the filter capacitor in a clean place or protect it from suspended substances.
Fixing bracket
3
Mounting hole
Installation orientation
To prevent looseness, install the filter capacitor on a horizontal surface securely with screws or bolts.
Do not install it on a vertical surface. Install it on a mounting stand which can withstand its weight.
NOTE
• As the charged sections of the filter capacitor is uncovered, fully protect it to prevent ground fault and electric shock.
3 cm or more
3 cm or more 3 cm or more
Installation place
Install the resistor on nonflammable material. Installing directly on or near a flammable material will cause a fire.
Surrounding environment
Avoid places where the resistor is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the resistor in a clean place or protect it from suspended substances.
Do not place a flammable material near the resistor.
Installation orientation
To prevent looseness, install the resistor on a horizontal or vertical surface securely with screws or bolts.
10 cm or more
10 cm or more 10 cm or more
Installation place
Install the stepdown transformer on nonflammable material. Installing it directly on flammable material will cause a fire.
Surrounding environment
Avoid places where the stepdown transformer is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the stepdown transformer in a clean place or protect it from suspended substances.
Installation orientation
To prevent looseness, install the stepdown transformer on a horizontal or vertical surface securely with screws or bolts.
NOTE
3
• As the charged sections of the stepdown transformer is uncovered, fully protect it to prevent ground fault and electric shock.
Reactor 2
Terminal symbol Description
Connected to the reactor 1. Between two reactors, the filter capacitor and the dedicated circuit parts for inrush
R3/L13, S3/L23, T3/L33
current protection must be installed.
R4/L14, S4/L24, T4/L34 Connected to the converter.
R5, S5 Connected to the cooling fan power output terminals on the stepdown transformer for power source of MC.
If reactor 2 overheats, the circuit will open (thermostat output) between TP3 and TP4.
• TP3:
TP3, TP4 Connected to terminal TP2 of the reactor 1.
• TP4:
Connected to terminal SD of the converter.
Filter capacitor
Terminal symbol Description
R2/L12, S2/L22, T2/L32 Connected to the output terminals of the reactor 1 and the input terminals of the inrush current limit resistor.
For earthing (grounding) of the converter chassis. This must be earthed (grounded). 47
Jumper
P/+ S4/L24
3
To inverter
To reactor 2
• Reactor 1 (FR-A8BL1)
Cable gauge
HIV cables, etc. PVC cables, etc.
AWG/MCM
(mm2) (mm2)
Tightening
Terminal R/L11, R/L11, R/L11,
Model torque Crimp
screw S/L21, S/L21, S/L21,
FR-A8BL1-[] N·m terminal
size T/L31, T/L31, T/L31,
R2/L12, R2/L12, R2/L12,
S2/L22, S2/L22, S2/L22,
T2/L32 T2/L32 T2/L32
H315K M12 (M8) 46 (24) 150-12 2 × 150 2 × 300 2 × 150
H355K M12 (M8) 46 (24) C2-200 2 × 200 2 × 350 2 × 185
H400K M12 (M8) 46 (24) C2-200 2 × 200 2 × 400 2 × 185
H450K M12 (M8) 46 (24) C2-250 2 × 250 2 × 500 2 × 240
H500K M12 (M8) 46 (24) C2-250 2 × 250 2 × 500 2 × 240
• Reactor 2 (FR-A8BL2)
Cable gauge
HIV cables, etc. PVC cables, etc.
AWG/MCM
(mm2) (mm2)
Tightening
Terminal R3/L13, R3/L13, R3/L13,
Model torque Crimp
screw S3/L23, S3/L23, S3/L23,
FR-A8BL2-[] N·m terminal
size T3/L33, T3/L33, T3/L33,
R4/L14, R4/L14, R4/L14,
S4/L24, S4/L24, S4/L24,
T4/L34 T4/L34 T4/L34
H315K M12 (M8) 46 (24) 150-12 2 × 150 2 × 300 2 × 150
H355K M12 (M8) 46 (24) C2-200 2 × 200 2 × 350 2 × 185
H400K M12 (M8) 46 (24) C2-200 2 × 200 2 × 400 2 × 185
H450K M12 (M8) 46 (24) C2-250 2 × 250 2 × 500 2 × 240
H500K M12 (M8) 46 (24) C2-250 2 × 250 2 × 500 2 × 240
It is the gauge of the cable with the continuous maximum permissible temperature of 90°C or higher (LMFC (heat resistant flexible cross-linked
polyethylene insulated cable), etc.). It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.
It is the gauge of the cable with continuous maximum permissible temperature of 90°C (THHN cable). It assumes a surrounding air temperature
of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to page 194.)
It is the gauge of the cable with continuous maximum permissible temperature of 90°C (XLPE cable). It assumes a surrounding air temperature
of 40°C or lower and in-enclosure wiring.
(Selection example mainly for use in Europe.)
Screw size for earthing (grounding) is indicated in parenthesis. (Refer to page 47 for earthing (grounding).)
If a cable thinner than the recommended cable size is used, it may not be protected by the DC fuse. (Refer to page 21 for the fuse selection.)
(d) (f)
Reactor1 Reactor2
(FR-A8BL1) (FR-A8BL2) Converter Inverter
Thermostat Thermostat
∗9 ∗7 (NC) × 3 (NC) × 3 (c)
TP1 TP2
(b)
Inrush current limit MCs TP3 TP4 (e) (h)
MCCB MC Fuse ∗10 (a) R/L1 R2/L12 MC1 R3/L13 R4/L14 R4/L14 P+ P+
U
Power
S/L2 S2/L22 MC2 S3/L23 S4/L24 S4/L24 ∗4 ∗5 V M
T/L3 T2/L32 MC3 T4/L34 N- N-
T3/L33 T4/L34 W
Fan power Fan power R1/L11
FAN FAN terminals FAN FAN
terminals S1/L21
(100 to 240 VAC) R5 S5 (100 to 240 VAC)
R5 S5 R5 S5 R5 S5
∗8
∗8
Inrush current limit resistor
Filter capacitor with thermostat (3, NC)
(FR-A8BC) ∗8
R1/L11
S1/L21
Coils for
MC2
inrush current limit MCs LOH ∗2
SD
Stepdown transformer MC3 ROH ∗3
for power source of MC SD
(400 to 220 V)
R/L1 Buffer relay for MCs
S/L2 380V R5/L15 MC4 A1
S/L2 400V Bu1 C1 ∗8
S/L2 420V
S/L2 440V ∗12 S5/L25
S/L2 460V
S/L2 480V
S/L2 500V
Phase detection transformer box
(FR-A8VPB)
Plug-in option
∗8 (FR-A8AVP) ∗8
R
S ∗4 ∗6
T
R2
RS2
R2
RS2 RYA
∗11 X10∗1
TS2 TS2 RSO RES
(f) T2 T2 SE2 SD
∗8
Use the Input terminal function selection to assign the X10 signal to a terminal. The signal is assigned to terminal MRS in the initial status. (Refer
to the Instruction Manual of the inverter.)
The LOH signal function is assigned to terminal RT in the initial status. Set "33" in any of Pr.178 to Pr.189 (Input terminal function selection)
to assign the LOH signal to another terminal.
The ROH signal function is assigned to terminal AU in the initial status. Set "34" in any of Pr.178 to Pr.189 (input terminal function selection)
to assign the ROH signal to another terminal.
Confirm the correct voltage phase sequence between the converter (terminals R4/L14, S4/L24, and T4/L34) and the phase detection
transformer box (terminals R, S, and T).
Do not install any MCCB between the inverter and the converter (P to P and N to N). Connecting opposite polarity of terminals P and N will
damage the converter and the inverter.
Always connect terminals R2, RS2, TS2, and T2 of the FR-A8AVP installed on the converter and the identically-named terminals of the phase
detection transformer box. If the inverter is operated without connecting between the terminals, the converter will be damaged.
Do not install an MCCB or MC between the reactor 1 input terminals (R/L1, S/L2, and T/L3) (a) and the converter input terminals (R4/L14, S4/
L24, and T4/L34) (c) except for those specified in the connection diagram. Doing so disrupts proper operation.
Securely perform grounding (earthing) by using the grounding (earthing) terminal.
Install an MC for each phase.
Install the UL listed fuse (refer to page 194) on the input side of the converter to meet the UL/cUL standards.
Always connect terminal RYA on the FR-A8AVP (installed on the converter) and the inverter terminal to which the X10 signal is assigned, and
connect terminal SE2 on the FR-A8AVP and the inverter terminal SD (terminal PC in the source logic). Failure to do so may lead to damage of
the converter.
Select a terminal S/L2 according to the input voltage.
• Symbols shown in the connection diagram on page 40 correspond to the symbols shown in the following table. For the
details of wiring of each section, refer to the page shown in the following table.)
Refer to
Symbol Wiring
page
(a) Wiring between the power supply and reactor 1 42
(b) Wiring between the reactor 1, filter capacitor, inrush current limit resistor, inrush current limit MC, and reactor 2 43
(c) Wiring between the reactor 2 and converter 44
(d) Wiring between the thermostats of the reactors 1 and 2 and the converter 44
(e) Wiring between the converter and inverter 45
Wiring between the reactor 1, stepdown transformer for power source of MC, phase detection transformer
(f) 45
box, and converter
(g) Wiring between the fans of the reactors 1 and 2 and the stepdown transformer for power source of MC 46
(h) Wiring between the converter and the control circuit power terminal on the inverter 46
NOTE
• The control logic (sink logic (initial setting) /source logic) of the converter and the inverter must be matched. The converter
does not operate properly if the control logic is not consistent with each other.
(Refer to page 53 for the switching of the control logic of the converter. Refer to the Instruction Manual of the inverter for the
switching of the control logic of the inverter.)
• Keep the wiring length between terminals as short as possible.
• When the power is distorted or falls off sharply, the reactors may generate abnormal acoustic noise. This acoustic noise is
caused by the power supply fault and not by the damage of the converter.
• Do not connect the DC reactor to the inverter when using a high power factor converter.
• When using a sine wave filter for the converter, use the MT-BSL-HC reactor.
CAUTION
Refer to the connection diagram on page 40 to check that the reactor 1 and reactor 2 are connected
in the right places. Incorrect connection may damage the converter and reactors.
Always connect terminal RYA of the FR-A8AVP installed on the converter and the inverter terminal to
which the X10 signal is assigned, and connect terminal SE2 of the FR-A8AVP and inverter terminal
SD (terminal PC in the source logic). Failure to do so may lead to damage of the converter.
Reactor 1
MCCB (FR-A8BL1)
MC
R/ R2/
L1 L12
MC
Power S/ S2/
L2 L22
MC T/ T2/
L3 L32
(b) Wiring between the reactor 1, filter capacitor, inrush current limit
resistor, inrush current limit MC, and reactor 2
∗1
Reactor 1 Reactor 2
(FR-A8BL1) (FR-A8BL2) Converter
Inrush current
TP1 limit MC1 TP3
TP2 TP4
R5 R5 R5 R5
S5 S5 S5 S5
Inrush current
limit MC2
LOH
SD
ROH
SD
Inrush current
limit MC3
3
Inrush current limit resistor
Resistor (with thermostat)
Connect the following devices to the inrush current limit MC used for each phase of the BKO-CA2573H11
converter: one BKO-CA2573H01 (resistor without thermostat) and one BKO-CA2573H11
Thermostat output
(resistor with thermostat) for FR-A842-08660(355K) converters or lower, and two BKO-
CA2573H01 (resistor without thermostat) and one BKO-CA2573H11 (resistor with
thermostat) for FR-A842-09620(400K) converters or higher.
Filter capacitor
Connect the filter capacitor to the output terminals of the reactor 1 and to the input terminals of the inrush current limit
MCs.
The following table shows the recommended specifications of the cables used for connection of the filter capacitor.
The following table shows the recommended specifications of the cables used for connection of each phase between the
reactors 1 and 2.
Model Cable gauge (mm2) Total wiring length
FR-A8BL1-H315K
2 × 150 10 m or less
FR-A8BL2-H315K
FR-A8BL1-H355K
2 × 200 10 m or less
FR-A8BL2-H355K
FR-A8BL1-H400K
2 × 200 10 m or less
FR-A8BL2-H400K
FR-A8BL1-H450K
2 × 250 10 m or less
FR-A8BL2-H450K
FR-A8BL1-H500K
2 × 250 10 m or less
FR-A8BL2-H500K
(d) Wiring between the thermostats of the reactors 1 and 2 and the
converter
Connect the thermostat output terminals on the reactor 1 (terminals TP1 and TP2) and reactor 2 (terminals TP3 and TP4) and
the converter terminals (terminal to which the LOH signal is assigned and terminal SD) in series, as shown in the connection
diagram on page 43.
The following table shows the recommended cable specifications.
Cable gauge (mm2) Total wiring length
0.75 to 1.25 10 m or less
For inverters other than the separated converter type of the FR-A802/F802
Conveter Inverter
∗1 inverters, installation of a fuse on each cable is recommended to prevent
R4/L14 P/+ P/+ the spread of damage caused by an inverter failure. Select a fuse
∗3
S4/L24 N/- N/- according to the motor capacity. When using a motor, of which the capacity
is smaller than the inverter capacity by two ranks or more, select the fuse
T4/L34
with the capacity that is one rank lower than the inverter capacity. Refer to
FR-A8AVP the fuse selection tables on page 21.
For connection of multiple inverters, use the same gauge cable as the
RYA X10 ∗2
inverter's power cable for wiring between the inverter main circuit terminal
Control
RSO RES (P/+ or N/-) and a junction terminal. (Refer to the Instruction Manual of the
circuit
SE2 SD inverter.)
The function needs to be assigned to an inverter terminal to be connected
to terminal RYA of the FR-A8AVP.
Refer to the Instruction Manual of the Inverter. Do not install any MCCB
Control circuit cable gauge 0.75 to 1.25 mm2 between the inverter and the converter (P to P and N to N).
NOTE
• Do not connect anything to power input terminals (R/L1, S/L2, and T/L3) of the inverter. Incorrect power input connection will
damage the inverter. Connecting opposite polarity of terminals P/+ and N/- will damage the inverter and the converter.
• Do not connect a DC reactor to the inverter when using the converter.
(f) Wiring between the reactor 1, stepdown transformer for power source
of MC, phase detection transformer box, and converter
As shown in the connection diagram on page 43, connect the output cables of the phase detection transformer box to the FR-
A8AVP's terminals R2, RS2, TS2, and T2 for power detection.
Select a terminal S/L2 on the stepdown transformer according to the input voltage.
Connect the output cables from the MC start command terminals (A1, C1) on the converter to the inrush current limit MCs (for
three phases) through the buffer relay for driving MCs. 3
The following table shows the recommended cable specifications.
Item Cable gauge (mm2) Total wiring length
Input cable for the stepdown transformer 2 10 m or less
Output cable for the stepdown transformer 2 10 m or less
Cable between the phase detection transformer box and
0.75 to 1.25 5 m or less
converter
NOTE
• The terminals R2, RS2, TS2, and T2 on the FR-A8AVP are control terminals used to detect power phases of the power
supply. Confirm the correct voltage phase sequence between the reactor 1 (terminals R/L1, S/L2, and T/L3) and the phase
detection transformer box (terminals R, S, and T). If these terminals are not connected correctly, the converter does not
operate properly.
• If the inverter is operated while the converter terminals R2, RS2, TS2, and T2 are not connected to the power supply, the
converter will be damaged.
(g) Wiring between the fans of the reactors 1 and 2 and the stepdown
transformer for power source of MC
The reactors 1 and 2 have an AC cooling fan. As shown in the connection diagram on page 43, connect the output cables
from the stepdown transformer terminals (R5/L15, S5/L25) in parallel to the fan power terminals (R5, S5) of the reactors 1 and
2.
The following table shows the recommended cable specifications.
Cable gauge (mm2) Total wiring length
2 10 m or less
NOTE
• Be sure to connect cables to the reactor cooling fans. Otherwise, the reactors may be overheated, resulting in output shutoff
or malfunction of the converter.
(h) Wiring between the converter and the control circuit power terminal
on the inverter
Connect the control power supply to the inverter terminals P/+ and N/-. The terminals R1/L11 and S1/L21 are initially
connected to the terminals P/+ and N/- with a jumper respectively.
Inverter
P/+
N/-
R1/L11
S1/L21
NOTE
• To use inverters equipped with terminals R1/L11 and S1/L21 other than the separated converter type of the FR-A802 or FR-
F802 inverters, remove jumpers across main circuit terminals R/L1 and R1/L11 and across S/L2 and S1/L21 on the inverter
(refer to the Instruction Manual of the inverter).
• Terminals R1/L11 and S1/L21 on the inverter are control power input terminals. If the terminals are left open, the inverter
output may be shut off by an activation of a protective function, or the inverter may be damaged.
• If the FR-A842/F842 inverters are connected to the converter, and the inverter control power is supplied via terminals P/+ and
N/- (initial setting), a protective function (E.P24) may be activated in the inverter at the occurrence of a power shutoff.
(I) Separate earthing (grounding): Good (II) Common (single-point) earthing (grounding): OK (III) Inadequate common (single-point) earthing (grounding): Bad
Converter
Power Dedicated
circuit parts M Motor
Reactor 1
Reactor 2
supply
Inverter
for inrush
current (e)
protection
(d)
(b)
(a)
Symbol Description
Make the separate earth (ground) connection for the converter and the converter options from any other devices and
a
equipment wherever possible.
The earthing (grounding) cable should be as close as possible to the power cables, and all these cables should be wired in
b
parallel.
The converter and the converter options are allowed to have the common (single-point) earth (ground) system (unless the
c
reactors 1 and 2 are earthed (grounded) by being mounted on a panel of the enclosure).
If the inverter and the converter are installed far apart and the main circuit cables between them (P to P and N to N) are too
long to store in an enclosure, the inverter earthing (grounding) cable is allowed to be connected to the converter and run as
d close as possible to the main circuit cables in parallel.
When the cables are short enough to store in an enclosure, the inverter is allowed to join in the common (single-point) earth
(ground) connection (c).
e The motor earthing (grounding) cable is allowed be connected to the inverter earth (ground) terminal.
Input signal
Converter
Terminal
Type terminal function Signal name Terminal function description Rated specification
symbol
(initial status)
No function is assigned in the initial setting.
STF — (No function) —
Use Pr.178 to assign a function to the terminal.
No function is assigned in the initial setting.
STR — (No function) —
Use Pr.179 to assign a function to the terminal.
When the SOF signal is turned ON, the converter
STP SOF Converter stop stops. The RDY signal turns OFF, and the inrush
current limit resistor MC turns ON.
No function is assigned in the initial setting.
RH — (No function) —
Use Pr.182 to assign a function to the terminal.
No function is assigned in the initial setting.
RM — (No function) —
Use Pr.181 to assign a function to the terminal.
No function is assigned in the initial setting.
RL — (No function) —
Use Pr.180 to assign a function to the terminal.
No function is assigned in the initial setting.
JOG — (No function) —
Use Pr.185 to assign a function to the terminal.
Reactor
Connected in series with all the thermostat
RT LOH overheat
output terminals on the reactors 1 and 2.
protection
Input resistance: 4.7 kΩ,
The External thermal relay input (OH) signal is
voltage when contacts
used when using the external thermal relay or
are open: 21 to 27 VDC,
External the thermal protector built into the motor to
current when contacts
MRS OH thermal relay protect the motor from overheating. When the
are short-circuited: 4 to 6
input thermal relay is activated, the inverter output is
mADC
shut off by the external thermal relay operation
Contact input
Converter
Terminal
Type terminal function Signal name Terminal function description Rated specification
symbol
(initial status)
Connect this terminal to the power supply
External
common terminal of a transistor output (open
transistor
collector output) device, such as a
common
programmable controller, in the sink logic to
Contact input
Analog output
Common terminal for the analog output terminals
5 5 terminal ―
AM and CA. Do not earth (ground).
common
Power supply input
10E,
10,
2, Not used.
4,
1
Sink logic is initially set for the FM-type converter.
Source logic is initially set for the CA-type converter.
Output signal
Converter
Terminal
Type terminal function Terminal name Terminal function description Rated specification
symbol
(initial status)
A1 A1 MC connection Used for the control of the inrush current limit
―
C1 C1 terminal MC.
1 changeover contact output that indicates
Relay
Converter
Terminal
Type terminal function Terminal name Terminal function description Rated specification
symbol
(initial status)
Permissible load
FM For indication on current: 2 mA.
Pulse
Communication
Terminal
Type Terminal name Terminal function description
symbol
RS-485 communication can be made through the PU connector (for connection on a 1:1 basis
only).
Conforming standard: EIA-485 (RS-485)
— PU connector
Transmission format: Multidrop link
Communication speed: 4800 to 115200 bps
Wiring length: 500 m
RS-485
TXD+
RS-485 terminals
Converter send
The RS-485 terminals enable the communication by RS-485.
TXD-
RXD+
Conforming standard: EIA-485 (RS-485) 3
Transmission format: Multidrop link
Converter receive
RXD- Communication speed: 300 to 115200 bps
GND Earthing Overall length: 500 m
(SG) (grounding)
Mini B connector (receptacle) Interface: conforms to USB1.1
— USB B connector The USB connection with a personal computer can be (USB2.0 full-speed compatible)
USB
signal is ON.)
The open collector
transistor is ON
RSO Converter reset Output during a converter reset. (conductive) in LOW state.
The transistor is OFF (not
conductive) in HIGH state.
SE2 Open collector output common Common terminal for terminals RYA and RSO. —
CAUTION
Always connect terminal RYA on the FR-A8AVP (installed on the converter) and the inverter terminal
to which the X10 signal is assigned, and connect terminal SE2 on the FR-A8AVP and the inverter
terminal SD (terminal PC in the source logic). Failure to do so may lead to damage of the converter.
SOURCE
SINK
Jumper connector
For sink logic
NOTE
• Make sure that the jumper connector is installed correctly.
• Never change the control logic while power is ON.
●Current flow for the I/O signal in the sink logic ●Current flow for the I/O signal in the source logic
Current
Sink
Current
RES connector
R
RES R Source
connector
SOF
R
SOF
R
SD
Converter Inverter
Converter Inverter PC
Sink
RES connector
R
RDA X10 Source
R
connector
RDA X10
R
SE
RES
R
SE SD
Current flow
Current flow
voltage PC voltage
circuit circuit Fuse TB17
TB18
TB18 SD
24 VDC SD
Wiring method
• Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the
sheath of the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
(1) Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with
neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Cable sheath stripping length
10 mm
(2) Crimp the blade terminal. 3
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is inappropriate,
or the face is damaged.
Unstranded wire
ble
Ca
Flathead screwdriver
NOTE
• When using stranded wires without a blade terminal, twist enough to avoid short circuit with a nearby terminals or wires.
• Never change the control logic while power is ON.
• Wire removal
Pull the wire while pushing the open/close button all
the way down firmly with a flathead screwdriver. NOTE
Open/close button • Pulling out the wire forcefully without pushing the open/close
button all the way down may damage the terminal block.
• Use a small flathead screwdriver (tip thickness: 0.4 mm / tip
Flathead screwdriver width: 2.5 mm).
If a flathead screwdriver with a narrow tip is used, terminal
block may be damaged.
Commercially available product (as of February 2016.)
PC
+24 V
SOF, etc.
Converter
SOF, etc.
SD R
External signal input using transistor External signal input using transistor
(sink logic) (source logic)
[Wiring example]
3
Rubber bush
(viewed from inside)
Connection method
When the protection circuit is activated, opening of the electromagnetic contactor (MC) on the input side of the converter
results in power loss in the control circuit of the converter, disabling the fault output signal retention. Terminals R1/L11 and S1/
L21 of the control circuit are provided to hold a fault signal. To use these terminals, add the node points joined to the control
circuit power supply terminals R1/L11 and S1/L21 on the MC power cable.
Terminals R1/L11 and S1/L21 are connected to terminals P/+ and N/- with a jumper respectively. Do not connect the power
cable to incorrect terminals. Doing so may damage the converter.
[Connection diagram]
R1/L11
S1/L21
Remove
the jumper. P/+
N/-
(c)
Power terminal
block for control
Power terminal block circuit
for control circuit
R1/L11
S1/L21
(a)
(b)
(d)
(a) Remove the upper screws.
(b) Remove the lower screws.
(c) Pull the jumper toward you to remove.
(d) Connect the separate power supply cable for the control circuit to the upper terminals (R1/L11, S1/L21).
NOTE
• When using separate power supplies, always remove the jumpers connected to terminals R1/L11 and S1/L21. Failure to do
so may lead to damage of the converter.
• The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than
the input side of the MC.
• When using a separate power supply connected to terminals R1/L11 and S1/L21, the necessary power capacity is 80 VA.
• If the main circuit power is switched OFF (for 0.1 seconds or more) then ON again, the converter is reset and a fault output
will not be held.
or
OMRON Corporation
S8VS-06024
Specifications: Capacity 60 W, output voltage 24 VDC, output current 2.5 A
Installation method: DIN rail installation
For the latest information about OMRON power supply, contact OMRON corporation.
NOTE
• When the 24 V external power is supplied while the main circuit power supply is OFF, the converter operation is disabled. 3
• In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is
performed in the converter, then the power supply changes to the main circuit power supply.
POWER ALARM
• During the 24 V external power supply operation, the 24 V external power supply operation (EV) signal is output. To use the
EV signal, set "68 (positive logic) or 168 (negative logic)" in any of Pr.192 to Pr.194 or Pr.196 (Output terminal function
selection) to assign the function to the output terminal.
NOTE
• Inrush current equal to or higher than the 24 V external power supply specification may flow at power-ON. Confirm that the
power supply and other devices are not affected by the inrush current and the voltage drop caused by it. Depending on the
power supply, the inrush current protection may be activated to disable the power supply. Select the power supply and
capacity carefully.
• When the wiring length between the external power supply and the converter is long, the voltage often drops. Select the
appropriate wiring size and length to keep the voltage in the rated input voltage range.
• In a serial connection of several inverters, the current increases when it flows through the inverter wiring near the power
supply. The increase of the current causes voltage to drop further. Use the converter and inverters after confirming that the
input voltage of each inverter is within the rated input voltage range. Depending on the power supply, the inrush current
protection may be activated to disable the power supply. Select the power supply and capacity carefully.
• "E.P24" may appear when the power supply start-up time is too long for the 24 V external power supply operation.
• "E.P24" may appear when the 24 V external power supply input voltage is low. Check the external power supply input.
• Do not touch the control circuit terminal block (circuit board) during the 24 V power supply operation (when conducted). Doing
so may cause an electric shock or burn.
Parameter unit
Operation panel
(FR-PU07) (option)
(FR-DU08)
STF FWD PU
NOTE
• Refer to the following table when fabricating the cable on the user side. Keep the total cable length within 20 m.
3
• Commercially available products (as of February 2015)
Name Model Manufacturer
SGLPEV-T (Cat5e/300 m)
Communication cable Mitsubishi Cable Industries, Ltd.
24AWG × 4P
RJ-45 connector 5-554720-3 Tyco Electronics
Communication operation
• Using the PU connector as a computer network port enables communication operation from a personal computer, etc.
When the PU connector is used for connection between the converter and a personal, FA, or other computer with a
communication cable, a user program can run to monitor the inverter or read and write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation).
(For the details, refer to page 108.)
USB host
(A connector) ∗1
Communication status
Insert a flathead screwdriver LED indicator
to the slot, and push up
USB device
the cover to open.
(mini B connector)
Not used.
The RS-485 terminals enable communication operation from a personal computer, etc. When the PU connector is connected
with a personal, FA or other computer by a communication cable, a user program can run to monitor the converter or read and
write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation).
For details, refer to the Instruction Manual (Detailed) of the FR-A800 inverter.
NOTE 3
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
• Lead the wires on the left side of the plug-in option for wiring of the RS-485 terminals.
• The FR-A802-E converters do not have the RS-485 terminal block.
Converter INV1
RYA X10
RSO RES
FR-A842 FR-A842
-12120 -07700
(500K) (315K)
SE2 SD
INV2
X10
RES
FR-A840
-04320
(160K)
SD
INV3
X10
RES
FR-A840
-00620
(22K)
SD
66
4 PRECAUTIONS FOR
USE OF THE
CONVERTER
NOTE
• Inverter parameters must be set. The parameter settings differ by the inverter series. Refer to page 23.
● Power supply harmonic suppression effect
(Condition) Load: 100%
Power factor: 1
[When high power factor converter is not connected] [When high power factor converter is connected]
NOTE
• It does not mean that any harmonic components completely disappear.
• When the load is light, harmonic suppression effect declines.
• When the power supply voltage is unstable, power harmonics flow in, making the harmonic current increase.
• The power factor decreases when the setting of Pr.84 or Pr.85 is changed from the initial setting. (Refer to page 107.)
Calculation of equivalent
capacity total
• Conversion coefficient
Classification Circuit type Conversion coefficient Ki
6-pulse converter K11 = 1
1 Three-phase bridge 12-pulse converter K12 = 0.5
24-pulse converter K13 = 0.25
Without reactor K31 = 3.4
Three-phase bridge With reactor (AC side) K32 = 1.8
3
(Capacitor smoothing) With reactor (on DC side) K33 = 1.8
With reactors (AC, DC sides) K34 = 1.4
Single-phase bridge (capacitor Without reactor K41 = 2.3
smoothing, double voltage
With reactor (AC side) K42 = 0.35
4 rectification)
Single-phase bridge (capacitor Without reactor K43 = 2.9
smoothing, full-wave rectification) With reactor (AC side) K44 = 1.3
When a high power factor converter is
5 Self-excitation three-phase bridge K5 = 0
used
P0 = Σ (Ki × Pi) [kVA] Rated capacity: Determined by the capacity of the applied
motor and found in Table 5. The rated capacity used here
Ki: Conversion factor (Refer to page 69.)
is used to calculate the generated harmonic amount and
Pi: Rated capacity of harmonic generating is different from the power supply capacity required for
equipment[kVA] actual inverter drive.
Rated Fundamental
Outgoing harmonic current converted from 6.6 kV (mA)
Applicable current wave current Rated
(With a DC reactor, 100% operation ratio)
motor (A) converted capacity
(kW) from 6.6 kV (kVA)
400 V 5th 7th 11th 13th 17th 19th 23rd 25th
(mA)
75 123 7455 87.2 2237 969 626 373 350 239 224 164
90 147 8909 104 2673 1158 748 445 419 285 267 196
110 179 10848 127 3254 1410 911 542 510 347 325 239
132 216 13091 153 3927 1702 1100 655 615 419 393 288
160 258 15636 183 4691 2033 1313 782 735 500 469 344
220 355 21515 252 6455 2797 1807 1076 1011 688 645 473
250 403 24424 286 7327 3175 2052 1221 1148 782 733 537
280 450 27273 319 8182 3545 2291 1364 1282 873 818 600
315 506 30667 359 9200 3987 2576 1533 1441 981 920 675
355 571 34606 405 10382 4499 2907 1730 1627 1107 1038 761
400 643 38970 456 11691 5066 3274 1949 1832 1247 1169 857
450 723 43818 512 13146 5696 3681 2191 2060 1402 1315 964
500 804 48727 570 14618 6335 4093 2436 2290 1559 1462 1072
560 900 54545 638 16364 7091 4582 2727 2564 1746 1636 1200
Basic techniques
• Do not run the power cables (I/O cables) and signal cables of the converter in parallel with each other and do not bundle
them.
• Use shielded twisted pair cables for the detector connecting and control signal cables and connect the sheathes of the
shielded cables to terminal SD.
• Ground (earth) devices such as the reactor 1, reactor 2, phase detection transformer box, and converter at one point.
(Refer to page 47.)
• Install the recommended noise filter on the converter (refer to page 76). The noise filter is effective against the noises that
enter the converter and the noises that are radiated from the converter.
• Do not earth (ground) the shields of the communication or control cables of the converter or inverter.
Noise
Measure
propagation path
When devices that handle low-level signals and are liable to malfunction due to electromagnetic noises, e.g.
instruments, receivers and sensors, are contained in the enclosure that contains the converter or when their signal
cables are run near the converter, the devices may malfunction due to by air-propagated electromagnetic noises.
The following measures must be taken:
• Install the easily affected devices as far away from the converter and the inverter as possible.
• Place the easily affected signal cables as far away from the converter and the inverter as possible.
(a), (b), (c) • Do not run the signal cables and power cables (converter I/O cables) in parallel with each other and do not bundle
them.
• Install the recommended noise filters (refer to page 76) or the radio noise filters (FR-BIF) on the input side of the
converter, and install the line noise filters (FR-BLF, or non-Mitsubishi product RC5128 or FINEMET® FT-3KM F/
FT-3KL F ) on the output side of the inverter to suppress radiated noises from the cables.
• Use shielded cables as signal cables and power cables and run them in individual metal conduits to produce
further effects.
When the signal cables are run in parallel with or bundled with the power cables, magnetic and static induction
noises may be propagated to the signal cables to cause malfunction of the devices. The following measures must
be taken:
Converter
Dedicated
Power supply ∗1 ∗2 Motor
Reactor 1
M
Inverter
circuit parts for
Reactor 2
inrush current
Refer to page 47 for earthing (grounding) FR- protection Use 4-core cable for motor power
of the converter and peripheral devices. BIF cable and use one cable as
earth (ground) cable.
It is preferred that the inverter, the converter,
and power cables are separated from
sensor circuit by 30 cm or more Use a twisted pair shielded cable.
(at least 10 cm). Sensor
Power supply
Control power
for sensor
Do not connect earthing (grounding) Do not earth (ground) shield but
cables directly to the enclosure. connect it to signal common cable.
R1/L11
S1/L21
Install the filter on the input side of Terminals R, S, and T of the converter.
RC5128: manufactured by Soshin Electric Co., Ltd.
Do not earth (ground) the shield but connect it to the signal common.
Refer to page 76 for the installation method of the recommended noise filter.
The FINEMET® FT-3KM F / FT-3KL F is available on the market, manufactured by Hitachi Metals, Ltd.
FINEMET is a registered trademark of Hitachi Metals, Ltd.
4
NOTE
• Configure a system where the magnetic contactor at the converter input side shuts off the power supply at a failure of the
converter or the connected inverter. (The converter does not shut off the power supply by itself.)
Failure to do so may overheat and burn the resistors in the converter and the connected inverter.
• Connection diagram
Install a noise filter composed of common mode chokes (ring cores) and damping resistors on the input side of the high power
factor converter.
Use the FINEMET® common mode chokes (manufactured by Hitachi Metals, Ltd.) for the zero-phase reactors and the
inverter option brake resistor FR-ABR for the damping resistors.
FINEMET is a registered trademark of Hitachi Metals, Ltd.
The noise filter installed on the input side of the converter is effective in suppressing noises arising from a leakage current
flowing along the path shown in the following figure.
Recommended
noise filter∗1
Detecting phase /
Zero-phase reactor Supplying control power
Molded case Magnetic
circuit breaker contactor Reactor 1 Filter capacitor Reactor 2 Converter Cable shield or the like
(FR-A8BC) Inverter Motor
Power (MCCB), (MC) (FR-A8BL1) (FR-A8BL2)
䚷 Mechanical
supply earth leakage and dedicated load
circuit breaker circuit parts
(ELB), or fuse for inrush
current
protection
(FR-A8MC)
Damping resistor
Stray
capacitance
Suppression effectiveness of the recommended noise filter remains the same wherever it is installed between the power supply and the reactor
1 (FR-A8BL1).
Observe the following precautions for installation of the recommended noise filter.
• As a guide, the total length of cable between the noise filter and the converter should be short enough to fit into an enclosure (about 4 m or shorter).
• Do not divert some of the current from bus cables between the noise filter and the reactor 1.
• Components
FR-A842-[]
Item
07700(315K) 08660(355K) 09620(400K) 10940(450K) 12120(500K)
Model FT-3KM F200160PB FT-3KM F200160PB
Zero-phase reactor
Quantity 4 pcs (penetrated)
Model FR-ABR-H22K
Damping resistor
Quantity 4 pcs in parallel (combined resistance: 13 Ω)
5.5 mm2 or more (when using HIV cable, etc.)
Wire diameter AWG 10 or less (when using THHW cable, etc.)
6 mm2 or more (when using PVC cable, etc.)
Damping resistor cable
Cable length As short as possible within 10 m.
Voltage
Equal voltage resistance to the main circuit cables.
specifications
NOTE
• Observe the instructions given in the Instruction Manual of each component.
• The damping resistor (FR-ABR) requires 5 cm clearance or more around it for directions. Besides, the distance between the
damping resistors should be 1 cm or more.
• As a reference, the surface temperature increase of the damping resistor (FR-ABR) is about 30°C and the total resistance
loss is about 300 W (dependent on the environment).
• For the converters not shown in the table above, installing the recommended noise filter is not required.
If leakage current from the inverter and/or the converter flows along the path shown in the following figure, installing a line
noise filter between the inverter and the motor is effective in suppressing noises arising from the leakage current.
Detecting phase /
Recommended Supplying control power
noise filter ∗2
Zero-phase reactors Line noise
(ring cores) filter∗3
Molded case Cable shield or
Reactor 1 Filter capacitor Reactor 2 Converter Inverter the like
circuit breaker Motor Mechanical
Power Magnetic (FR-A8BL1) (FR-A8BC) (FR-A8BL2) load
(MCCB), 䚷
earth leakage contactor
supply (MC) and dedicated
circuit breaker circuit parts
(ELB), or fuse for inrush current
protection
(FR-A8MC)
Damping resistor
Stray
capacitance
Devices ∗1
The leakage current can cause a malfunction of devices placed over the leakage current path.
Suppression effectiveness of the recommended noise filter remains the same wherever it is installed between the power supply and the reactor
1 (FR-A8BL1).
Observe the following precautions for installation of the recommended noise filter.
• As a guide, the total length of cable between the noise filter and the converter should be short enough to fit into an enclosure (about 4 m or shorter).
• Do not divert some of the current from bus cables between the noise filter and the reactor 1.
Recommended noise filter
Zero-phase reactor Filter capacitor
Molded case
circuit breaker Reactor 1 (FR-A8BC) Reactor 2 Converter
Magnetic and dedicated (FR-A8BL2)
Power (MCCB), (FR-A8BL1) 䚷
contactor circuit parts for
supply earth leakage (MC)
circuit breaker inrush current
(ELB), or fuse protection
(FR-A8MC) Detecting phase /
Supplying control power
4
Damping resistor Devices
Recommended line noise filters include the FR-BLF, RC5128, FINEMET® FT-3KM F or FT-3KL F series.
RC5128: manufactured by Soshin Electric Co., Ltd.
FINEMET® FT-3KM F / FT-3KL F series: manufactured by Hitachi Metals, Ltd.
120 2. 0
Leakage current (mA)
NOTE
• Install the earth leakage circuit breaker (ELB) on the input side of the converter.
• In the connection earthed-neutral system, the sensitivity current is blunt against a ground fault in the inverter output side.
Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes. (NEC
section 250, IEC 61140 class 1 and other applicable standards)
• Do not install the breaker on the output side of the inverter. Doing so may cause unnecessarily operations by harmonics even
if the effective value is within the rating, since the eddy current and hysteresis loss will increase, leading to temperature rise.
• The following models are standard breakers: BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA, and NV-2F earth leakage relay
(except NV-ZHA) and the NV class earth leakage circuit breaker with AA neutral wire open-phase protection.
The other models are designed for harmonic and surge suppression: NV-C/NV-S/MN series, NV30-FA, NV50-FA, BV-C2,
earth leakage alarm breaker (NF-Z), NV-ZHA, and NV-H.
PARAMETERS 79
Operation panel (FR-DU08)
MON: ON when the operation panel is in the monitor mode. Quickly blinks twice
Operation panel mode
(b) intermittently while the converter protective function is activated.
LED indicator
PRM: ON when the operation panel is in the parameter setting mode.
Frequency unit
(d) ON to indicate frequency.
indicator
Shows a numeric value, a parameter number, etc.
(e) Monitor (5-digit LED)
(The monitor item can be changed according to the Pr.52 setting.)
(h) STOP/RESET key Used to reset the converter when the protective function is activated.
Turn the setting dial to select a parameter or change the parameter setting.
Press the setting dial to perform the following operations:
(i) Setting dial
• To display the "CNV" (converter) indication.
• To display a fault history number in the fault history mode.
Switches the operation panel to a different mode.
(j) MODE key Holding this key for 2 seconds locks the operation of the operation panel. The key
inoperable function is invalid when Pr.161 = "0 (initial setting)". (Refer to page 126.)
Used to confirm each selection. When the initial setting is set
Switches the monitor screen in the
Power supply frequency Input current Input voltage
(k) SET key monitor mode.
(The monitor item can be changed
according to the Pr.52 setting.)
Goes back to the previous display.
(l) ESC key
Holding this key for a longer time changes the display back to the monitor mode.
80 PARAMETERS
Operation panel (FR-DU08)
The present
setting displayed.
(Example) Alternating
Parameter clear All parameter clear Fault history clear Parameter copy
Hold down
The monitor item can be changed. (Refer to page 123.)
For the details of fault history, refer to page 149.
Parameter setting mode The set value of the displayed parameter number is read or changed. 82
Initial value change list Identifies the parameters that have been changed from their initial settings. 146
PARAMETERS 81
Operation panel (FR-DU08)
Operating procedure
Turning ON the power of the converter
1.
The operation panel is in the monitor mode.
Selecting the parameter setting mode
2.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Turn to change the set value to " ". Press to enter the setting. " " and " " are displayed
alternately.
• Press three times to return the monitor display to the indication of the power
supply frequency.
NOTE
• If a parameter write condition is not satisfied, a parameter write error appears. (Refer to page 153.)
Error code Error description
Parameter write error
82 PARAMETERS
Parameter unit (FR-PU07)
Monitor
I In ●Liquid crystal display
10.0 A (16 characters × 4 lines, with backlight)
STF FWD PU
●Parameter setting in an interactive manner
●Help function
●Troubleshooting guide
●Monitoring (current, voltage, etc.)
ALARM lamp
ON when a converter fault
occurs.
Operation keys
FR-PU07
Used to clear the "PS" indication which appears when the converter is stopped by pressing (by the PU stop
function).
• Press either of these keys on the parameter setting mode screen to change the parameter setting value sequentially.
• On the selecting screen, these keys are used to move the cursor.
5
/
• Hold down and press either of these keys to advance or return the display screen one page.
NOTE
• Do not operate the keys with sharp tools.
• Do not press the LCD part.
PARAMETERS 83
Parameter unit (FR-PU07)
Select an item from the monitoring list and press to monitor the selected item.
The following items can be monitored.
Hz In : Power supply frequency (Hz)
I In : Input current (A)
V In : Input voltage (V)
Alarm His : Fault history (the last 8 faults)
Dc Bus : Bus voltage (V)
THT % : Electronic thermal O/L relay load factor (%)
Cum Pwr : Cumulative power (kW)
Cum Opr : Cumulative energization time (h)
Pwr In : Input power (kW)
I/P Signal : Input signal
O/P Signal : Output signal
When the converter is used as an inverter before conversion, fault records are displayed for both before and after the conversion (the indication
can be switched for up to eight records).
(After the eighth fault occurs in the converted converter, only the converter's fault records will be displayed.)
NOTE
• If setting Pr.52 has changed the monitor item for the first or the second monitor screen, the monitoring list does not recognize
that the monitor item for the first or the second monitor screen has been changed until the monitoring list is read (displayed).
If a monitor item change has been performed while the monitoring list is displayed, the monitoring list does not recognize the
change and the target item displayed does not turn to the new item.
(b) Connection phase sequence indication
The following phase sequence is displayed.
STF : Positive
STR : Negative
--- : Power supply not detected
(c) Operating status indication
The operating status of the converter is displayed.
STOP : Stop state
FWD : Power driving
REV : Regenerative driving
ALAR : Fault state
(d) Operation mode indication
"EXT" (External operation mode) is always indicated.
(e) Unit indication
The unit of the main monitor item is indicated.
(f) Warning indication
The following is indicated when the converter outputs a warning.
Nothing is indicated when there is no warning output.
For the details, refer to page 153.
OL : Overload signal detection
TH : Electronic thermal relay function pre-alarm
PS : PU stop
MT1 to MT3 : Maintenance signal output
SL : Power supply not detected
CP : Parameter copy
84 PARAMETERS
Parameter unit (FR-PU07)
NOTE
• There are menus in which some functions are not available.
Not used.
5
PARAMETERS 85
Parameter unit (FR-PU07)
3 Pr.List
1 Setting Mode SETTING MODE 1 Appl.Grp
2 Pr.List 0~9:Ser Pr.No. 2 Pr.List
3 Set Pr.List 3 User List
4 Def.Pr.List Select Oper 4 Param Copy
key
0 Pr Mode
1
2
1 3
2
3 Pr.List
4 Pr.Clear SET Pr.LIST 8
5 Alarm His 1 60.00 0
6 AlarmClear 2 50.00
7 INV.Reset 8 0 0, 1
8 T/Shooting
9 S/W DEF.Pr.LIST
10 Selectop 1 60.00
11 Option 2 50.00
12 PRCpy set 8 0
4 Pr.Clear
1 Clear Pr. Clear Pr. Clear Pr.
2 Clear All Exec<WRITE>
Cancel<ESC> Completed
INV.RESET
Exec<WRITE> An indication "INV.RESET" appears, but this is the function to reset the converter.
7 INV.Reset Cancel<ESC>
8 T/Shooting
Not used.
<S/W>
9 S/W
8888*
10 Selectop ON
RL : 0
RM : 1 OFF
RH : 2
RT : 3
<option>
OP1: 8AVP
11 Option OP2: ----
OP3: ----
1 Copy area 1 ∗1
2 Copy area 2
3 Copy area 3 000 Param Copy
12 PRCpy set Name:000
:Select Char Overwrite area 1
READ:Decide Char WRITE:Executing Reading
WRITE:DecideName ESC:Cancel Completed
Copy area 1
1 Read VFD
2 Write VFD
3 Verifing 000 Param Copy
Area 1 to VFD Writing
WRITE:Executing Completed
ESC:Cancel Please Reset
Only the copy area 1 is available to store a parameter setting of the converter. Do not use the copy area 2 for any other product to preserve the
converter parameter setting stored in the copy area 1. Doing so will delete the converter parameter setting stored in the copy area 1.
86 PARAMETERS
Parameter List
NOTE
• The setting of parameters in highlighted cells is changeable during operation even if "1" (write disabled) is set in Pr.77
Parameter write selection.
5
83 Current control integral gain 0 to 200% 1% 100% 107
84 Power factor command value 0.8 to 1 0.001 1 107
85 Power factor lead/lag setting 0, 1 1 0 107
117 PU communication station number 0 to 31 1 0 113
48, 96, 192, 384, 576, 768,
118 PU communication speed 1 192 113
1152
119 PU communication stop bit length 0, 1, 10, 11 1 1 113
120 PU communication parity check 0, 1, 2 1 2 113
121 PU communication retry count 0 to 10, 9999 1 1 113
123 PU communication waiting time setting 0 to 150 ms, 9999 1 ms 9999 113
124 PU communication CR/LF selection 0, 1, 2 1 1 113
145 PU display language selection 0 to 7 1 0 126
157 OL signal output timer 0 to 25 s, 9999 0.1 s 0s 92
158 AM terminal function selection 1 to 3, 8, 10, 13, 14, 21, 98 1 1 100
161 Key lock operation selection 0, 10 1 0 126
168
Parameter for manufacturer setting. Do not set.
169
170 Watt-hour meter clear 0, 10, 9999 1 9999 96
PARAMETERS 87
Parameter List
88 PARAMETERS
Parameter List
PARAMETERS 89
Parameter details
Initial
Pr. Name Setting range Description
value
R-S turns ratio 95.0 to 105.0% Compensates for fluctuations in the input voltage.
1344 9999
compensation 9999 Compensation disabled.
T-S turns ratio 95.0 to 105.0% Compensates for fluctuations in the input voltage.
1345 9999
compensation 9999 Compensation disabled.
The setting is applied after converter reset.
• Set the values specified on the rating plate of the FR-A8VPB in Pr.1344 and Pr.1345. (If the Pr.1344 and Pr.1345 settings
are not consistent with the values specified on the rating plate of the FR-A8VPB, protective functions for overcurrent or
overvoltage may not be activated when the input voltage suddenly changes according to the load, or the converter's
performance specifications such as the power factor or harmonic suppression characteristics may not be satisfied.)
MODEL FR-A8AVPB-H
NOTE
• Stop the converter operation before setting Pr.1344 and Pr.1345. When inverters or other peripheral devices are connected
to the converter, be sure to stop their operation.
90 PARAMETERS
Parameter details
Initial Setting
Pr. Name Description
value range
The parameter shows that the upper limit of allowable range
1 Maximum frequency 60 Hz 60 Hz of the power frequency is 60 Hz.
(Read only)
The parameter shows that the lower limit of allowable range
2 Minimum frequency 50 Hz 50 Hz of the power frequency is 50 Hz.
(Read only)
Initial Setting
Pr. Name Description
value range
NO contact: Turning ON of the SOF signal stops the
0
converter operation.
8 SOF input selection 0
NC contact: Turning OFF of the SOF signal stops the
2
converter operation.
NO contact: Turning ON of the OH signal activates a
0
protective function of the converter to shut off its output.
9 OH input selection 0
NC contact: Turning OFF of the OH signal activates a
1
protective function of the converter to shut off its output.
• Converter operation determined by the SOF signal input status and the Pr.8 setting
SOF signal input Converter operation
status Pr.8 = "0" (NO contact) Pr.8 = "2" (NC contact)
OFF Operation continues. Operation stops.
ON Operation stops. Operation continues.
• Converter operation determined by the OH signal input status and the Pr.9 setting
OH signal input Converter operation
status Pr.9 = "0" (NO contact) Pr.9 = "1" (NC contact)
Operation stops due to the
OFF Operation continues.
5
fault.
Operation stops due to the
ON Operation continues.
fault.
PARAMETERS 91
Parameter details
Initial
Pr. Name Setting range Description
value
22 Current limit level 150% 0 to 220% Set the current limit where the current limit operation starts.
Set the current limit where the current limit operation starts
Current limit level 0 to 220%
(during regenerative driving).
23 9999
(regenerative)
9999 The same setting in Pr.22 is applied.
Set the OL signal output start time at the activation of torque
157 OL signal output timer 0s 0 to 25 s, 9999
limit operation.
Set the proportional gain for the voltage control.
Voltage control
80 100% 0 to 1000% Increasing the setting value reduces the DC voltage
proportional gain fluctuation caused by external disturbance.
Set the integral gain for the voltage control.
Voltage control integral
81 100% 0 to 1000% Increasing the setting value shortens the recovery time from
gain the DC voltage fluctuation caused by external disturbance.
NOTE
• Setting Pr.80 too large makes the operation unstable.
• Setting only Pr.81 makes the operation unstable.
Pr.22
Pr.157 Pr.157 Output current
Pr.157
Time
OL signal ON ON
NOTE
• When the output current reaches the current limit level, DC voltage decreases during power driving, and DC voltage
increases during regeneration.
92 PARAMETERS
Parameter details
Initial Setting
Pr. Name Description
value range
Instantaneous power 0
Turns OFF the Instantaneous power failure detection hold
44 failure detection signal 9999 (Y16) signal.
clear 9999 Function disabled.
• The Instantaneous power failure detection hold (Y16) signal turns ON when the Instantaneous power failure (IPF) signal
turns ON during the converter operation. The Y16 signal turns OFF when a converter reset is performed or Pr.44 is set to
"0".
• For the terminal used for the Y16 signal, set "16 (positive logic)" or "116 (negative logic)" to any of Pr.192 to Pr.194, and
Pr.196 (Output terminal function selection).
NOTE
• Pr.44 always reads "9999".
• Changing the terminal assignment using Pr.192 to Pr.194, and Pr.196 (Output terminal function selection) may affect the
other functions. Set parameters after confirming the function of each terminal.
PARAMETERS 93
Parameter details
2400
1440
0 Hz 45 Hz 60 Hz 65 Hz
(initial value)
20 mA
0A
0 Hz 45 Hz 60 Hz 65 Hz
(initial value)
• Enter the full-scale value of the meter corresponding to a voltage of 10 VDC output via terminal AM.
Enter the frequency value at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal 5.
The output voltage is proportional to the frequency. (The maximum output voltage is 10 VDC.)
Output voltage
10 VDC
0V
0 Hz 45 Hz 60 Hz 65 Hz
(initial value)
94 PARAMETERS
Parameter details
Reference for input power monitor (Pr.51), input voltage monitor (Pr.53),
bus voltage monitor (Pr.55), and current monitor (Pr.56)
• For the FM type converter, enter the full-scale value of the meter corresponding to a pulse train of 1440 pulses/s output via
terminal FM.
Enter the power (kW), voltage (V), or current (A) value at full scale of the meter (1 mA analog meter) installed between
terminal FM and terminal SD.
The pulse speed is proportional to the monitored value. (The maximum pulse train output is 2400 pulses/s.)
Pulse speed (pulse/s)
2400
1440
Setting range
• For the CA type converter, enter the full-scale value of the meter corresponding to a current of 20 mA output via terminal
CA. Enter the current value at full scale of the meter (20 mA ammeter) installed between terminal CA and terminal 5.
The output current is proportional to the power (kW), voltage (V), or current (A). (The maximum output current is 20 mADC.)
Output current
20 mADC
Setting range
• Enter the full-scale value of the meter corresponding to a voltage of 10 VDC output via terminal AM.
Enter the power (kW), voltage (V), or current (A) value at full scale of the meter (10 VDC voltmeter) installed between
terminal AM and terminal 5.
The output voltage is proportional to the monitored value. (The maximum output voltage is 10 VDC.)
5
Output voltage
10 VDC
Setting range
Setting range
-10 VDC
When the input power monitor (with regenerative driving indication) is selected as the monitor item, monitor values during regenerative driving
are displayed with a minus sign.
PARAMETERS 95
Parameter details
RS-485
Minus (-)
Increment Pr.52 dedicated
Monitor item display Description
and unit setting monitor
(hexadecimal)
Power supply
0.01 Hz 0 H01 The power supply frequency is monitored.
frequency
Input current 0.1 A 0 H02 The input current to the converter is monitored.
The effective value of input voltage to the converter is
Input voltage 0.1 V 0 H03
monitored.
Bus voltage 0.1 V 8 H08 The converter output voltage is monitored.
Fault indication — 0 — Each of the last 8 faults is displayed individually.
The cumulative value of the electronic thermal O/L relay
Electronic thermal O/
0.1% 10 H0A is displayed as a percentage of the thermal O/L relay trip
L relay load factor
level.
Input power 0.1 kW 13 H0D The input power to the converter is monitored.
Input power (with The input power to the converter is monitored.
regenerative driving 1 kW 14 H0E Negative values with a minus sign (-) are displayed
indication) during regenerative driving.
The counter of cumulative energization time since the
converter shipment is displayed.
Cumulative
1h 20 H14 The number of times an integrated value has reached
energization time
the maximum value of 65535 hours can be checked in
Pr.563.
The counter of cumulative power calculated from the
Cumulative power 0.1 kWh 25 H19 input power monitor value is displayed.
Use Pr.170 to clear the counter. (Refer to page 98.)
96 PARAMETERS
Parameter details
RS-485
Minus (-)
Increment Pr.52 dedicated
Monitor item display Description
and unit setting monitor
(hexadecimal)
Input terminal status — H0F
ON/OFF status of the I/O signals is displayed on the
Output terminal 55
— H10 operation panel. (Refer to page 98.)
status
The temperature of the control circuit board is
Control circuit monitored. (Refer to page 135)
°C 98 H62
temperature Terminal FM/CA: 0 to 100°C
Terminal AM: -20 to 100°C
The cumulative energization time is accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
On the parameter unit (FR-PU07),"kW" is displayed.
When the value is monitored via communication, the value is displayed in 1-kWh increments.
Only the FR-DU08 supports a signed number indication and a negative value is displayed during regenerative driving. The minus-sign indication
is available only on the FR-DU08. Negative values are displayed during regenerative driving regardless of the setting in Pr.290 Monitor
negative output selection.
Unsigned values are displayed on the FR-PU07 even during regenerative driving.
Parameter setting is not valid to set the item as the main monitor item on the parameter unit (FR-PU07). Use the monitor function of the FR-
PU07 for the setting.
The circle in this column indicates that the indication of negative signed numbers is available.
change the screen displayed at power-ON, display the screen you want to display at power-ON, and hold down for
1 second. (To monitor the power supply frequency at power-ON again, display the screen of power supply frequency, and
Power supply frequency monitoring Input current monitoring Input voltage monitoring
The following is the screen flow diagram when Pr.52 = "20" (cumulative energization time).
● First screen
(initially displayed at power-ON) ● Second screen ● Third screen ● Fault screen
With fault data
5
Power supply frequency monitoring Input current monitoring Cumulative energization time
PARAMETERS 97
Parameter details
OL
FU
ABC2 IPF
Segments corresponding to output terminals
• The decimal point position on the watt-hour meter can be shifted to left. The number of digits to be shifted is equal to the
setting of Pr.891 Cumulative power monitor digit shifted times.
For example, when the cumulative power is 1278.56 kWh and Pr.891 is set to "2", "12.78" is displayed (in 100's of units) on
the operation panel and the communication data is converted into "12".
• When Pr.891 = "0 to 4" and the cumulative value exceeds the upper limit, the decimal point position must be shifted. When
Pr.891 = "9999" and the cumulative value exceeds the upper limit, the meter returns to 0 and the counting starts again.
• Writing "0" in Pr.170 clears the cumulative power monitor.
NOTE
• When Pr.170 is read just after "0" has been written in Pr.170, the setting "9999" or "10" is displayed.
NOTE
• The cumulative energization time does not increase if the power is turned OFF after less than an hour.
• When the converter is used as an inverter before conversion, the total energization time for both before and after the
conversion is displayed.
98 PARAMETERS
Parameter details
NOTE
• When indication with negative numbers is enabled for the output via terminal AM (analog voltage output), the output is within
the range of -10 to +10 VDC. Connect the meter with which output level is matched.
• Parameter unit (FR-PU07) displays only unsigned numbers.
PARAMETERS 99
Parameter details
Output to indicate negative values during regenerative driving regardless of the setting in Pr.290 Monitor negative output selection.
Absolute values are used for indication for terminal FM. (Signed numbers are not available.)
The circle in this column indicates that the output of negative signals is available.
100 PARAMETERS
Parameter details
CAUTION
The motor and machine will start suddenly after occurrence of an instantaneous power failure (after
the reset time has elapsed).
Stay away from the motor and machine when automatic restart after instantaneous power failure has
been selected.
PARAMETERS 101
Parameter details
(Pr.68 × 4) s
Pr.68 (6 s at minimum) Pr.68 Pr.68 Pr.68
Converter
Converter operation
operation
0 Time
0
Time Fist retry Second retry Third retry Retry failed
Retry starts. Counter incremented by 1. (E.RET)
Fault occurred. Fault Fault Fault
occurred. occurred. occurred.
Retry success counter Fault signal (ALM) ON
RTY ON RTY ON ON ON
• When the converter protective function is activated (fault indication is displayed) while the retry function is enabled, the retry
function automatically deactivates (resets) the protective function and restarts the operation after a lapse of the time set in Pr.68.
• The retry function is enabled when the Pr.67 setting is other than "0". Set the number of retries at activation of the
protective function in Pr.67.
RDY signal ON
Pr.67 setting Retry times Fault output
state during retry
0 The retry function disabled. — —
Number of times equal to
1 to 10 No. Not held.
Pr.67 setting.
Number of times calculated
101 to 110 by subtracting 100 from Yes. Not held.
Pr.67 setting.
Number of times calculated
1001 to 1010 by subtracting 1000 from No. Held.
Pr.67 setting.
Number of times calculated
1101 to 1110 by subtracting 1100 from Yes. Held.
Pr.67 setting.
The signal will be held when a protective function with fault indication of E.OCT, E.OVT, or E.CDO occurs.
102 PARAMETERS
Parameter details
• When retries fail consecutively more than the number of times set in Pr.67, the protective function (E.RET) is activated to
shut off the converter output. (Refer to the figure of retry failure example.)
• Use Pr.68 to set the delay from a protective function activation to a retry in the range of 0 to 600 seconds.
• The cumulative number of successful restart times made by retries (retry success counter) can be checked by reading the
Pr.69 value.
The retry counter (Pr.69 value) is incremented by 1 every time a retry succeeds. Retry is regarded as successful when
normal operation restarts and continues with no other faults for the time set in Pr.68 multiplied by four (6 seconds at least.)
(When retry is successful, the cumulative number of retry failures is cleared.)
• Writing "0" in Pr.69 clears the cumulative count.
• During a retry, the RTY signal is ON. For the RTY signal, assign the function by setting "64 (forward action)" or "164
(reverse action)" in any of Pr.192 to Pr.194, or Pr.196 (Output terminal function selection).
• Faults which trigger the retry operation can be selected with Pr.65. The faults not described in the following table do not
enable the retry function. (For the fault details, refer to page 153.)
"●" indicates the fault selected.
NOTE
• Changing the terminal assignment using Pr.192 to Pr.194, or Pr.196 may affect the other functions. Set parameters after
confirming the function of each terminal.
• Only the first fault is recorded in the fault history during retries.
• If a fault that does not trigger a retry occurs during retry operation, the converter output is shut off after the retry operation is
finished.
• The fault reset by the retry function does not reset the accumulated data such as the electronic thermal relay function data.
(The reset result is different from the power-ON reset.)
5
CAUTION
Stay away from the motor and machine when the converter shuts off its output while the retry
function is enabled. Motor and machine will start suddenly (after the reset time has elapsed) after the
shutoff.
PARAMETERS 103
Parameter details
Setting Pr.75 = any of "100 to 103 and 114 to 117" enables the reset limit function.
Reset selection
• The conditions where the reset command can input (using the RES signal or through communication) can be selected.
• When Pr.75 is set to any of "1, 3, 15, 17, 101, 103, 115, and 117", the reset input is enabled only when the protective
function is activated.
NOTE
• When the RES signal is input during operation, the inverter is also reset. The motor coasts since the inverter being reset
shuts off the output. Also, the cumulative value of the electronic thermal O/L relay is cleared.
• The reset input by using the reset key on the parameter unit is enabled only when the protective function is activated,
regardless of the Pr.75 setting.
Disconnected PU detection
• If the PU (FR-DU08/FR-PU07) is detected to be disconnected from the converter for 1 second or longer while Pr.75 = "2, 3,
16, 17, 102, 103, 116, or 117", PU disconnection (E.PUE) is displayed and the converter output is shut off.
NOTE
• When the PU has been disconnected since before power-ON, the output is not shut off.
• To restart operation, make sure that the PU is connected and then reset the converter.
• When RS-485 communication operation is performed through the PU connector, the reset selection / PU stop selection
function is enabled but the disconnected PU detection function is disabled.
• When the operation is stopped by the PU stop, the warning indication "PS" is displayed on the PU. A fault output is not
provided.
104 PARAMETERS
Parameter details
Time
key
PU
key
OFF ON OFF
SOF
• The converter is also restarted after performing the reset by turning OFF and ON the power or inputting the RES signal.
NOTE
• Resetting the converter power (turning OFF the control power) clears the accumulated thermal value.
• When the retry function is set enabled (Pr.67 Number of retries at fault occurrence ≠ "0"), the reset limit function is
disabled.
CAUTION
Do not reset the converter while the inverter start signal is being input. Doing so will cause a sudden
start of the motor, which is dangerous.
PARAMETERS 105
Parameter details
Pr. Name
170 Watt-hour meter clear
178 STF terminal function selection
179 STR terminal function selection
180 RL terminal function selection
181 RM terminal function selection
182 RH terminal function selection
183 RT terminal function selection
184 AU terminal function selection
185 JOG terminal function selection
186 CS terminal function selection
187 MRS terminal function selection
188 STOP terminal function selection
189 RES terminal function selection
190 RDY signal logic selection
191 RSO signal logic selection
192 IPF terminal function selection
193 OL terminal function selection
194 FU terminal function selection
196 ABC2 terminal function selection
328 Inverter/converter switching
106 PARAMETERS
Parameter details
Initial
Pr. Name Setting range Description
value
Set the proportional gain for the current control.
Current control
82 100% 0 to 200% Increasing the setting value reduces the current fluctuation
proportional gain caused by external disturbance.
Set the integral gain for the current control.
Current control integral Increasing the setting value shortens the recovery time
83 100% 0 to 200%
gain from the current fluctuation caused by external
disturbance.
• Adjust the fluctuation range of current by setting Pr.82.
Increasing the setting value reduces the current fluctuation caused by external disturbance.
• Adjust the recovery time to the commanded current after a current fluctuation by setting Pr.83.
Increasing the setting value shortens the recovery time from the current fluctuation caused by external disturbance.
NOTE
• Setting Pr.82 too large makes the operation unstable.
• Setting only Pr.83 makes the operation unstable.
Initial
Pr. Name Setting range Description
value
84 Power factor command value 1 0.8 to 1 Set the power factor command value.
Leading power factor (The phase current leads the
0
phase voltage.)
85 Power factor lead/lag setting 0
Lagging power factor (The phase current lags the
1
phase voltage.)
• To adjust the power factor, set a desired power factor command value in Pr.84.
For example, when "0.8" is set in Pr.84, the applicable inverter capacity of 500 kW will be reduced to 400 kW according to
the following formula.
500 kW (inverter rated capacity) × 0.8 (Pr.84 setting) = 400 kW
• Set Pr.85 = "0 (initial value)" for the leading power factor, and set Pr.85 = "1" for the lagging power factor.
5
NOTE
• Decreasing Pr.84 setting increases the input current, which makes the electronic thermal O/L relay more likely to operate.
PARAMETERS 107
Parameter details
NOTE
• Pins No. 2 and 8 provide power to the operation panel or parameter unit. Do not use these pins for RS-485 communication.
• Do not connect the PU connector to the computer's LAN board, FAX modem socket or telephone modular connector. The
product could be damaged due to differences in electrical specifications.
108 PARAMETERS
Parameter details
Make connection in accordance with the Instruction Manual of the computer to be used with.
Fully check the terminal numbers of the computer since they vary with the model.
NOTE
• Computer-converter connection cable
Refer to the following for the connection cable (RS-232C to RS-485 converter) between the computer with an RS-232C
interface and a converter. Commercially available products (as of February 2015)
Model Manufacturer
Interface embedded cable (for personal computer)
DAFXIH-CAB (D-SUB25P for personal computer) /
DAFXIH-CABV (D-SUB9P for personal computer)
and Diatrend Corp.
Connector conversion cable DINV-485CAB (for converter)
Interface embedded cable dedicated for inverter
DINV-CABV
5
The conversion cable cannot connect multiple inverters. (The computer and inverter are connected in a 1:1 pair.) This is an RS232C-to-RS485
converter-embedded conversion cable. No additional cable or connector is required. For the product details, contact the manufacturer.
• Refer to the following table when fabricating the cable on the user side.
Commercially available products (as of February 2015).
Product name Model Manufacturer
SGLPEV-T (Cat5e/300m)
Communication cable Mitsubishi Cable Industries, Ltd.
24AWG × 4P
RJ-45 connector 5-554720-3 Tyco Electronics
Do not use pins No. 2 and 8 of the communication cable.
PARAMETERS 109
Parameter details
NOTE
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
110 PARAMETERS
Parameter details
RS-485 RS-485
terminals Maximum: terminals
RS-485 interface/terminal ∗ RS-232C cable 15 m ∗
Converter
PARAMETERS 111
Parameter details
Computer
RDA
RDB
SDA
SDB
RSA
∗2
+
+
-
-
RSB
∗1
CSA
SDB1
SDA1
RDB1
RDA1
CSB
SG SG
FG
Computer
RDA
RDB
SDA
SDB
RSA
∗2
+
+
+
+
+
+
+
+
-
-
-
-
-
-
-
-
-
-
RSB
∗1
CSA
SDB1
SDA1
SDB2
SDA2
RDB1
RDA1
RDB2
RDA2
SDB1
SDA1
SDB2
SDA2
RDB1
RDA1
RDB2
RDA2
SDB1
SDA1
RDB1
CSB RDA1
SG SG SG SG SG SG
FG Station No. 0 Station No. 1 Station No. n
Make connection in accordance with the Instruction Manual of the computer to be used with.
Fully check the terminal numbers of the computer since they vary with the model.
On the converter most remotely connected with the computer, set the terminating resistor switch in the ON (100 Ω) position.
NOTE
• For branching, connect the wires as follows.
VCC TXD RXD VCC TXD RXD
Computer Converter
TXD+
TXD-
Transmission enable
RXD+
RXD-
Reception enable Pass a wire.
SG SG
NOTE
• A program should be created so that transmission is disabled (receiving state) when the computer is not sending and
reception is disabled (sending state) during sending to prevent the computer from receiving its own data.
112 PARAMETERS
Parameter details
NOTE
• Turning OFF the converter's power supply clears the modified parameter settings when Pr.342 = "1 (write only to RAM)".
Therefore, parameter settings at next power-ON will be the ones that are last stored to EEPROM.
• The parameter setting written in RAM cannot be checked on the operation panel. (The values displayed on the operation
panel are the ones stored in EEPROM.)
PARAMETERS 113
Parameter details
Initial
Pr. Name Setting range Description
value
Set the permissible number of retries for
unsuccessful data reception. If it is still unsuccessful
0 to 10
PU communication retry after the permissible number of retries, the converter
121 1
stops retrying communication.
count
The converter does not retry communication even
9999
when the communication is unsuccessful.
Set the time delay between data transmission to the
0 to 150 ms
PU communication waiting converter and the response.
123 9999
time setting The time delay is not set in this parameter but in
9999
communication data.
0 Without CR/LF
PU communication CR/LF
124 1 1 With CR
selection
2 With CR/LF
NOTE
• Always reset the converter after making the initial settings of the parameters. After changing the communication-related
parameters, communication cannot be made until the converter is reset.
NOTE
• Always reset the inverter after making the initial settings of the parameters. After changing the communication-related
parameters, communication cannot be made until the converter is reset.
114 PARAMETERS
Parameter details
Communication specifications
• The communication specifications are shown in the following table.
Related
Item Description
parameter
Communication protocol Mitsubishi inverter protocol (computer link communication) —
Conforming standard EIA-485 (RS-485) —
Pr.117
Number of connectable units 1: N (maximum 32 units), the setting range of station number is 0 to 31.
Pr.331
PU connector Selected among 4800/9600/19200/38400/57600/76800/115200 bps. Pr.118
Communication
Selected among 300/600/1200/2400/4800/9600/19200/38400/57600/
speed RS-485 terminals Pr.332
76800/115200 bps.
Control procedure Asynchronous method —
Communication method Half-duplex system —
Pr.119
Character system ASCII (7 bits or 8 bits can be selected.)
Pr.333
Start bit 1 bit —
Pr.119
Stop bit length 1 bit or 2 bits can be selected.
Communication Pr.333
specifications Pr.120
Parity check Check (at even or odd numbers) or no check can be selected.
Pr.334
Error check Sum code check —
Pr.124
Terminator CR/LF (whether or not to use it can be selected)
Pr.341
Pr.123
Time delay setting Availability of the setting is selectable.
Pr.337
Communication procedure
• In communication between the computer and the converter, the following data is exchanged in the order from a to e.
(a) Request data: sent from the computer to the converter. (The converter will not send data unless requested.)
(b) Communication delay time
(c) Reply data: sent from the converter to the computer in response to the computer request (data a)
(d) Converter data processing time
(e) Answer data: sent from the computer in response to the reply data sent from the converter (data c) (Even if (e) is not sent,
subsequent communication is made properly.)
Computer
For data read 5
↓ (Data flow) ∗2
Converter a d e
Time
Converter b c
↓ (Data flow) ∗1
For data write
Computer
If a data error is detected and a retry must be made, perform retry operation with the user program. The converter stops retrying and outputs the
LF signal when the number of consecutive retries exceeds the parameter setting.
On receipt of a data error occurrence, the converter returns reply data (c) to the computer again. The converter stops retrying and outputs the LF
signal when the number of consecutive data errors exceeds the parameter setting.
PARAMETERS 115
Parameter details
In the communication request data from the computer to the converter, the time of 10 ms or more is also required after an acknowledgement
(ACK) signal showing "No data error detected" is sent. (Refer to page 118.)
Reply from the converter to the converter reset request can be selected. (Refer to page 123.)
Number of Characters
Format
1 2 3 4 5 6 7 8 9 10 11 12 13
ENQ Instruction
A Station No. Data Sum check
code
ENQ Instruction
A1 Station No. Data Sum check
code
Data c: Reply data from the converter to the computer (No data error detected)
Number of characters
Format
1 2 3 4
ACK
C Station No.
Data c: Reply data from the converter to the computer (Data error detected)
Number of Characters
Format
1 2 3 4 5
NAK Error
D Station No.
code
A control code.
The converter station number is specified in hexadecimal in the range of H00 to H1F (stations No. 0 to 31).
Set the delay time.
When Pr.123 (time delay setting) ≠ 9999, create a communication request data without "waiting time" in the data format. (The number of
characters decreases by 1.)
CR+LF code
When a computer transmits data to the converter, some computers automatically provide either one or both of the codes CR (carriage return)
and LF (line feed) at the end of a data group. In this case, the same setting is required for data sent from the converter to the computer. Use
Pr.124 (CR/LF selection) for the CR+LF code setting.
116 PARAMETERS
Parameter details
Data c: Reply data from the converter to the computer (No data error detected)
Number of Characters
Format
1 2 3 4 5 6 7 8 9 10 11
STX ETX
E Station No. Read data Sum check
STX ETX
E1 Station No. Read data Sum check
Data c: Reply data from the converter to the computer (Data error detected)
Number of Characters
Format
1 2 3 4 5
NAK Error
D Station No.
code
A control code.
The converter station number is specified in hexadecimal in the range of H00 to H1F (stations No. 0 to 31).
Set the delay time.
When Pr.123 (time delay setting) ≠ 9999, create a communication request data without time delay in the data format. (The number of
characters decreases by 1.)
CR+LF code
When a computer transmits data to the converter, some computers automatically provide either one or both of the codes CR (carriage return)
and LF (line feed) at the end of a data group. In this case, the same setting is required for data sent from the converter to the computer. Use
Pr.124 (CR/LF selection) for the CR+LF code setting.
PARAMETERS 117
Parameter details
Data definitions
• Control code
Signal
ASCII code Description
name
STX H02 Start Of Text (Start of data)
ETX H03 End Of Text (End of data)
ENQ H05 Enquiry (Communication request)
ACK H06 Acknowledge (No data error detected)
LF H0A Line feed
CR H0D Carriage return
NAK H15 Negative acknowledge (Data error detected)
• Station No.
Specify the station number of the converter which communicates with the computer.
• Instruction code
Specify the processing request, for example, operation or monitoring, given by the computer to the converter. Therefore,
the operation or monitoring an item is enabled by specifying the corresponding instruction code. (Refer to page 123.)
• Data
Read/write data such as parameters transmitted from/to the converter. The definition and range of set data are determined
in accordance with the instruction code. (Refer to page 123.)
• Time delay
Specify the delay time (time period between the time when the converter receives data from the computer and the time
when the converter starts transmission of reply data). Set the delay time in accordance with the response time of the
computer in the range of 0 to 150 ms in 10 ms increments. (For example: 1=10 ms, 2=20 ms)
NOTE
• When Pr.123 (time delay setting) ≠ 9999, create a communication request data without "waiting time" in the data format.
(The number of characters decreases by 1.)
• The data check time varies depending on the instruction code. (Refer to page 119.)
• Sum check code
The sum check code is a 2-digit ASCII (hexadecimal) representing the lower 1 byte (8 bits) of the sum (binary) derived from
the checked ASCII data.
∗Delay time
(Example 1) Sum
Instruction
ENQ Station No. check
Computer → Converter code
code
0 1 E 1 1 0 7 A D F 4 ←Binary code
ASCII code→ H05 H30 H31 H45 H31 H31 H30 H37 H41 H44 H46 H34
↓
H30 + H31 + H45 + H31 + H31 + H30 + H37 + H41 + H44
= H1F4
Sum
∗ When the Pr.123 PU communication waiting time setting is other than "9999",
create the communication request data without delay time in the data format.
(The number of characters decreases by 1.)
(Example 2) Sum
Read data
STX Station No. ETX check
Converter → Computer code
0 1 1 7 7 0 3 0 ←Binary code
ASCII code→ H02 H30 H31 H31 H37 H37 H30 H03 H33 H30
↓
H30 + H31 + H31 + H37 + H37 + H30
= H130
Sum
118 PARAMETERS
Parameter details
• Error code
If any error is found in the data received by the converter, its error definition is sent back to the computer together with the
NAK code.
Error
Error item Error Description Converter operation
code
The number of errors consecutively detected in communication
H0 Computer NAK error request data from the computer is greater than the permissible
number of retries.
H1 Parity error The parity check result does not match the specified parity.
The sum check code in the computer does not match that of the
H2 Sum check error
data received by the converter.
The data the converter received has a grammatical mistake. Or, The LF signal is output.
data receive is not completed within the predetermined time. CR
H3 Protocol error
or LF code specification is not the same as the setting of the
parameter.
H4 Framing error The stop bit length differs from the parameter setting.
New data has been sent by the computer before the converter
H5 Overrun
completes receiving the preceding data.
H6 — — —
The converter received an unusable character (other than 0 to 9, The converter does not accept
H7 Character error
A to F, and control codes). the data sent to the converter.
H8 — — —
H9 — — —
Parameter write was attempted when the converter does not
perform computer link communication, when the operation
HA Mode error
commands are not given through communication, or when The converter does not accept
parameter write is set to be disabled. the data sent to the converter.
HB Instruction code error The specified instruction code does not exist.
HC Data range error Invalid data has been specified for parameter write, etc.
HD — — —
HE — — —
HF — — —
Response time
Data transmission time (Refer to the following formula.)
Converter data processing time = Delay time + Data check time
(Data setting (Varies dependingon
Computer → Converter value × 10 (ms)) the instruction code.)
Time
Converter → Computer 10 ms or more required.
Data transmission time (Refer to the following formula.)
[Formula for data transmission time]
1
Number of data
Communication Communication specifications (Total number of bits) = Data transmission time (s)
characters
speed (bps)
Refer to "page 116" 5
Communication specifications
PARAMETERS 119
Parameter details
ENQ
Computer → Converter Illegal Illegal
ACK
NAK
NAK
Converter → Computer
LF OFF ON
ENQ
ENQ
Computer → Converter Illegal Illegal Normal
ACK
NAK
NAK
ACK
Converter → Computer
Reception Reception
error error
LF OFF ON OFF ON OFF
120 PARAMETERS
Parameter details
Programming instructions
• When data from the computer has any error, the converter does not accept that data. Hence, in the user program, always
insert a retry program for data error.
• Data communication starts when the computer gives a communication request to the converter. The converter does not
send any data without the computer's request. Hence, design the program so that the computer gives a data read request
for monitoring, etc. as required.
• Program example
Performing Parameter clear of the converter
Microsoft® Visual C++® (Ver.6.0) programming example
#include <stdio.h>
#include <windows.h>
void main(void){
HANDLE hCom; // Communication handle
DCB hDcb; // Structure for setting communication
COMMTIMEOUTS hTim; // Structure for setting timeouts
nRet = WriteFile(hCom,szTx,nTx,&nTx,NULL);
// Send
if(nRet != 0) {
nRet = ReadFile(hCom,szRx,sizeof(szRx),&nRx,NULL);
// Receive
if(nRet != 0) {
// Display received data
for(i = 0;i < nRx;i++) {
printf("%02X ",(BYTE)szRx[i]);// Output received data to console
// ASCII character code is displayed in hexadecimal. Character "0" is represented as hexadecimal "30".
}
printf("\n\r");
}
}
}
CloseHandle(hCom); // Close communication port
}
}
PARAMETERS 121
Parameter details
General flowchart
Port open
Communication setting
CAUTION
Data communication is not started automatically but is made only once when the computer provides
a communication request. If communication is disabled during operation due to signal cable
breakage etc., the converter/inverter cannot be controlled.
Note that the converter does not detect a fault if communication is broken due to signal cable
breakage, computer fault etc.
122 PARAMETERS
Parameter details
Number of
Read/ Instruction
Item Data description data digits
Write code
(format)
Power supply H0000 to HFFFF: Power supply frequency (hexadecimal) in 0.01 4 digits
Read H6F
frequency Hz increments. (B and E/D)
4 digits
Input current Read H70 H0000 to HFFFF: Input current (hexadecimal) in 0.1 A increments.
(B and E/D)
H0000 to HFFFF: Input voltage (hexadecimal) in 0.1 V 4 digits
Input voltage Read H71
increments. (B and E/D)
H0000 to HFFFF: Data of the monitor item selected with the 4 digits
Special monitor Read H72
instruction code HF3. (B and E/D)
2 digits
Read H73
Special monitor Monitor selection data (Refer to page 96 for details on selection (B and E1/D)
selection No. No.) 2 digits
Write HF3
(A1 and C/D)
H0000 to HFFFF: Two fault records per code.
b15 b8b7 b0
H74 Second latest fault Latest fault
Monitoring
H75 Fourth latest fault Third latest fault
4 digits
Fault record Read H74 to H77
Fault monitor details (example of the instruction code H74) (B and E/D)
PARAMETERS 123
Parameter details
Number of
Read/ Instruction
Item Data description data digits
Write code
(format)
Parameters return to initial values.
Whether to clear communication parameters or not can be
selected according to the data. (: Cleared, ×: Not cleared)
Refer to page 190 for Parameter clear, All parameter clear, and
communication parameters.
Communication
Clear type Data
parameters
Parameter clear H9696 4 digits
Write HFC Parameter clear
All parameter clear H5A5A × (A and C/D)
NOTE
• Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
• For the instruction codes HFF and HF3, their values are held once they are written but cleared to zero when an converter
reset or all clear is performed.
124 PARAMETERS
Parameter details
PARAMETERS 125
Parameter details
Setting
Pr. Name Initial value Description
range
0 The keys are operable.
161 Key lock operation selection 0
10 The keys are inoperable.
• The setting dial and keys on the operation panel can be disabled to prevent unexpected parameter changes.
• Set Pr.161 to "10" and then press for 2 seconds to disable setting dial or key operations.
• When setting dial and key operations are disabled, " " appears on the operation panel. If the setting dial or any key
is used while keys are inoperable, " " appears on the operation panel. (When the setting dial or any key is not
used for 2 seconds, the operation panel switches to the monitor mode.)
• To enable the setting dial and keys again, press for 2 seconds.
NOTE
• Even if setting dial and key operations are disabled, the monitor indication and are enabled.
126 PARAMETERS
Parameter details
PARAMETERS 127
Parameter details
Initial Setting
Pr. Name Description
value range
RDY signal logic 0 ON: Inverter run enable (NO contact)
190 0
selection 100 OFF: Inverter run enable (NC contact)
RSO signal logic 1 ON: Converter reset (NO contact)
191 1
selection 101 OFF: Converter reset (NC contact)
• Converter operation determined by the RDY signal status and the Pr.190 setting
Converter operation
RDY signal output
Pr.190 = "0" (NO contact) Pr.190 = "100" (NC contact)
The converter is faulty or the reset
OFF Inverter operation is enabled.
signal is input.
The converter is faulty or the reset
ON Inverter operation is enabled.
signal is input.
• Converter operation determined by the RSO signal status and the Pr.191 setting
Converter operation
RSO signal output
Pr.191 = "1" (NO contact) Pr.191 = "101" (NC contact)
OFF Operation continues. Converter reset.
ON Converter reset. Operation continues.
NOTE
• For the RDY signal, the initial setting is normally-open contact input specification. To change the RDY signal input
specification to normally-closed, select the normally-open contact input specification for the input logic of the X10 signal of
the inverter.
128 PARAMETERS
Parameter details
Initial
Pr. Name Signal name Setting range
value
IPF terminal function
192 2 IPF (Instantaneous power failure)
selection Open
OL terminal function collector 0 to 5, 7, 8, 16, 25, 26, 32, 64,
193 3 OL (Overload warning)
selection output 68, 90, 95, 98 to 105, 107,
FU terminal function terminal 108, 116, 125, 126, 132, 164,
194 4 CVO (Converter running) 168, 190, 195, 198, 199,
selection
206 to 208, 306 to 308, 9999
Relay
ABC2 terminal
196 output 99 ALM (Fault output)
function selection
terminal
Setting Refer
Signal Related
Positive Negative Function Operation to
name parameter
logic logic page
0 100 RDY Inverter run enable Output when the inverter is ready. Pr.190 128
1 101 RSO Converter reset Output during a converter reset. Pr.191 128
Instantaneous power Output when the protective function for
2 102 IPF Pr.57 101
failure instantaneous power failure is activated.
3 103 OL Overload alarm Output when the current limit function is active. Pr.22, Pr.23 92
4 104 CVO Converter running Output when the converter is running. — —
Output when the detected bus voltage equals to
5 105 Y5 Output voltage match — —
the commanded bus voltage.
Power supply phase Output when a phase is confirmed after a
7 107 PHS — —
detection completion of the power supply phase detection.
Output when the cumulative electronic thermal
Electronic thermal O/L O/L relay value reaches 85% of the trip level.
8 108 THP — —
relay pre-alarm (Electronic thermal relay protection (E.THT) is
activated when the value reaches 100%.
Output when the IPF signal turns ON. This
Instantaneous power signal is held until a converter reset is performed
16 116 Y16 Pr.44 93
failure detection hold or Pr.44 is set to "0".
Output when the converter is running.
25 125 Fan Fan fault output Output when a fan fault occurs.
Output when the heat sink temperature reaches
Pr.244 131
5
Heat sink overheat pre-
26 126 FIN about 85% of the heat sink overheat protection — —
alarm
operation temperature.
Regenerative drive
32 132 Y32 Output during regenerative driving. — —
recognition
Pr.65,
64 164 RTY During retry Output during retry processing. 102
Pr.67 to Pr.69
24 V external power Output while the converter operated with a 24 V
68 168 EV — 59
supply operation power supplied from an external source.
Output when any of the control circuit capacitor,
Pr.255 to
90 190 Y90 Life alarm main circuit capacitor, inrush current limit circuit, 132
Pr.257
or the cooling fan approaches the end of its life.
Output when Pr.503 reaches the Pr.504 setting
95 195 Y95 Maintenance timer Pr.503, Pr.504 134
or higher.
Output when an alarm (fan fault or 108,
98 198 LF Alarm output Pr.121, Pr.244
communication error warning) occurs. 131
Output when the converter's protective function
99 199 ALM Fault is activated to stop the power output (when the — —
Fault occurs).
PARAMETERS 129
Parameter details
Setting Refer
Signal Related
Positive Negative Function Operation to
name parameter
logic logic page
Cooling fan operation Output when the cooling fan operation is
206 306 Y206 Pr.244 131
command signal commanded.
Output when the temperature of the control
Control circuit
207 307 Y207 circuit board reaches the detection level or Pr.663 135
temperature
higher.
208 308 PS PU stopped Output while the PU is stopped. Pr.75 104
9999 — No function. — — —
130 PARAMETERS
Parameter details
Initial Setting
Pr. Name Description
value range
A cooling fan operates at power ON.
0 Cooling fan ON/OFF control is disabled. (The cooling fan is
always ON at power ON.)
Cooling fan operation
244 1 Cooling fan ON/OFF control is enabled.
selection
The fan is always ON while the converter is running. During a
1
stop, the converter status is monitored and the fan switches
ON/OFF according to the temperature.
NOTE
• Changing the terminal assignment using Pr.192 to Pr.194 or Pr.196 (Output terminal function selection) may affect the
other functions. Set parameters after confirming the function of each terminal.
Parameters referred to 5
Pr.192 to Pr.194, Pr.196 (Output terminal function selection) page 129
PARAMETERS 131
Parameter details
Initial Setting
Pr. Name Description
value range
Displays whether or not the parts of the control
(0, 1, 4, 5, 8, 9, circuit capacitor, cooling fan, and inrush current
255 Life alarm status display 0
12, 13) limit circuit have reached the life alarm output
level. Read-only.
Inrush current limit circuit life Displays the deterioration degree of the inrush
256 100% (0 to 100%)
display current limit circuit. Read-only.
Control circuit capacitor life Displays the deterioration degree of the control
257 100% (0 to 100%)
display circuit capacitor. Read-only.
Displays the deterioration degree of the inrush
current limit circuit.
0 to 100% Set "100" after replacing the old FR-A8MC
Inrush current limit circuit life (dedicated circuit parts for inrush current
1202 9999
setting protection) with new one.
No function.
9999
The read value is always "9999".
Pr.255
bit3 bit2 bit0
Decimal Binary
13 1101
12 1100 ×
9 1001 ×
8 1000 × ×
5 0101 ×
4 0100 × ×
1 0001 × ×
0 0000 × × ×
: Alarm output, ×: Alarm not output
• The Life alarm (Y90) signal turns ON when any of the control circuit capacitor, cooling fan, and inrush current limit circuit
reaches the life alarm output level.
• For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of Pr.192 to Pr.194 and
Pr.196 (Output terminal function selection).
NOTE
• Changing the terminal assignment using Pr.192 to Pr.194 or Pr.196 (Output terminal function selection) may affect the
other functions. Set parameters after confirming the function of each terminal.
132 PARAMETERS
Parameter details
Life display and setting of the inrush current limit circuit (Pr.256, Pr.1202)
• The life of the inrush current limit circuit (relay, contactor, and inrush resistor) is displayed in Pr.256.
• The number of times the contacts of relay, contactor, and thyristor turn ON is counted down from 100% (0 times) by 1%
every 1000 times. When the counter reaches 10% (90000 times), bit 3 of Pr.255 turns ON and the life alarm is output by the
Y90 signal turned ON.
• Use Pr.1202 to set the life of the inrush current limit circuit. Set Pr.1202 = "100" after replacing the old FR-A8MC (dedicated
circuit parts for inrush current protection) with new one.
NOTE
• The life alarm and the signal are output when the fan speed of any of the cooling fans reaches the detection level.
• For parts replacement, consult the nearest Mitsubishi Electric FA Center.
PARAMETERS 133
Parameter details
Maintenance timer 1
(Pr.503) Pr.504
Time
NOTE
• The Y95 signal turns ON when any of MT1, MT2 or MT3 is activated. It does not turn OFF unless all of MT1, MT2 and MT3
are cleared.
• If all of MT1, MT2 and MT3 are activated, they are displayed in the priority of "MT1 > MT2 > MT3".
• The cumulative energization time is counted every hour. The energization time of less than 1 hour is not counted.
• Changing the terminal assignment using Pr.192 to Pr.194 or Pr.196 (Output terminal function selection) may affect the
other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.192 to Pr.194, Pr.196 (Output terminal function selection) page 129
134 PARAMETERS
Parameter details
NOTE
• The Y207 signal is turned OFF when the control circuit temperature becomes 5°C or more lower than the Pr.663 setting.
• Changing the terminal assignment using Pr.192 to Pr.194 or Pr.196 (Output terminal function selection) may affect the
other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.54 FM/CA terminal function selection page 100
Pr.158 AM terminal function selection page 100
Pr.192 to Pr.194, Pr.196 (Output terminal function selection) page 129
Pr.290 Monitor negative output selection page 96
PARAMETERS 135
Parameter details
Initial value
Pr. Name Setting range Description
FM CA
867 AM output filter 0.01 s 0 to 5 s Set a filter for output via terminal AM.
869 Current output filter — 0.02 s 0 to 5 s Set a filter for output via terminal CA.
Calibrates the scale of the meter
C0 (900) FM/CA terminal calibration — —
connected to terminals FM/CA.
Calibrates the scale of the analog meter
C1 (901) AM terminal calibration — —
connected to terminal AM.
Set the signal value at the minimum
C8 (930) Current output bias signal 0% 0 to 100%
analog current output.
Set the current value at the minimum
C9 (930) Current output bias current 0% 0 to 100%
analog current output.
Set the signal value at the maximum
C10 (931) Current output gain signal 100% 0 to 100%
analog current output.
Set the current value at the maximum
C11 (931) Current output gain current 100% 0 to 100%
analog current output.
The parameter number in parentheses is the one for use with the parameter unit.
Indicator
1 mA full-scale
(Digital indicator)
analog meter
1 mA 1440 pulses/s (+) ( )
FM FM
( ) ( ) T1
Calibration
resistor ∗1 8 VDC
SD SD
T2
Pulse width T1: Adjust with C0 (Pr.900).
Pulse cycle T2: Set with Pr.49, Pr.51, Pr.53, Pr.55, or Pr.56
Not needed when the operation panel or the parameter unit is used for calibration.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located
far from the converter.
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, perform calibration using
the operation panel or parameter unit.
136 PARAMETERS
Parameter details
NOTE
• When outputting an item such as the input current, which cannot reach a 100% value easily by operation, set Pr.54 to "21"
(reference voltage output) and calibrate. A pulse train of 1440 pulses/s are output via terminal FM.
• The wiring length to terminal FM should be 200 m at maximum.
• The initial value of the calibration parameter C0 (Pr.900) is set to 1 mA full-scale and 1440 pulses/s terminal FM pulse train
output at 60 Hz. The maximum pulse train output of terminal FM is 2400 pulses/s.
• When connecting a frequency meter between terminals FM-SD and monitoring the running frequency, it is necessary to
change Pr.55 to the maximum frequency, since the FM terminal output will be saturated at the initial value when the
maximum frequency reaches 100 Hz or greater.
Selecting a parameter
Turn until " " (C0 (Pr.900) FM/CA terminal calibration) appears. Press to enable the parameter
4.
setting.
The monitored value of the item (initially the power supply frequency) selected by Pr.54 FM/CA terminal function selection
will appear.
Scale adjustment
5.
Turn to move the meter needle to a desired position.
Setting completed
Press to enter the setting. The monitored value and " " are displayed alternately.
NOTE
• Calibration can be performed during operation.
• For the operation from the parameter unit, refer to the Instruction Manual of the parameter unit. 5
PARAMETERS 137
Parameter details
Output signal
0
Signal value at the minimum analog current output
(C8 (Pr.930))
NOTE
• When outputting an item such as output current, which cannot reach a 100% value easily by operation, set Pr.54 to "21"
(Reference voltage output) and calibrate. A current of 20 mADC is output via terminal CA.
• The output via terminal CA is enabled even if C8 (Pr.930) ≥ C10 (Pr.931), C9 (Pr.930) ≥ C11 (Pr.931).
138 PARAMETERS
Parameter details
NOTE
• When outputting an item such as input current, which cannot reach a 100% value easily by operation, set Pr.158 to "21"
(reference voltage output) and calibrate. A voltage of 10 VDC is output via terminal AM.
• Use Pr.290 Monitor negative output selection to enable negative signals output via terminal AM. The output voltage range
is -10 to +10 VDC. Calibrate the maximum positive value output via terminal AM.
Parameters referred to
Pr.54 FM/CA terminal function selection page 100
Pr.55 Bus voltage monitoring reference page 94
Pr.56 Current monitoring reference page 94
Pr.158 AM terminal function selection page 100
Pr.290 Monitor negative output selection page 96
NOTE
• Pr.888 and Pr.889 do not influence the operation of the converter.
PARAMETERS 139
Parameter details
NOTE
• When the buzzer is set to ON, a warning sound will be audible when a fault occurs.
Initial Setting
Pr. Name Description
value range
The setting range is same with the one for fault data codes of
16 to 253 the converter (which can be read through communication).
997 Fault initiation 9999 Written data is not stored in EEPROM.
The read value is always "9999".
9999
The protective function is not activated with this setting.
• To initiate a fault (protective function), set the assigned number of the protective function you want to initiate in Pr.997.
• The value set in Pr.997 is not stored in EEPROM.
• When the protective function is activated, the inverter output is shut off, and the converter displays a fault and outputs the
Fault (ALM) signal.
• While the initiated fault is occurring, the fault is displayed as the latest fault in the fault history. After a reset, the fault history
goes back to the previous status. (The protective function generated by the fault is not saved in the fault history.)
• Perform converter reset to cancel the protective function.
• For the selectable parameter by Pr.997 and the corresponding protective functions, refer to page 151.
NOTE
• If a protective function is already operating, no fault can be activated by Pr.997.
• The retry function is disabled when a protective function has been initiated by the fault initiation function.
• If a fault occurs after a protective function has been activated, the protective function indication does not change. The fault is
not saved in the fault history either.
140 PARAMETERS
Parameter details
Initial
Pr. Name Setting range Description
value
1006 Clock (year) 2000 2000 to 2099 Set the year.
101 to 131, 201 to 228,
(229), 301 to 331, 401 to Set the month and day.
430 , 501 to 531, 601 to 1000 and 100 digits: January to December
101
1007 Clock (month, day) 630, 701 to 731, 801 to 10 and 1 digits: 1 to the end of month (28, 29, 30
(January 1)
831, 901 to 930, 1001 to or 31)
1031, 1101 to 1130, 1201 For December 31, set "1231".
to 1231
0 to 59, 100 to 159, 200
to 259, 300 to 359, 400 to
459, 500 to 559, 600 to
659, 700 to 759, 800 to
859, 900 to 959, 1000 to
Set the hour and minute using the 24-hour clock.
1059, 1100 to 1159, 1200
0 1000 and 100 digits: 0 to 23 hours
1008 Clock (hour, minute) to 1259, 1300 to 1359,
(00:00) 10 and 1 digits: 0 to 59 minutes
1400 to 1459, 1500 to
For 23:59, set "2359".
1559, 1600 to 1659, 1700
to 1759, 1800 to 1859,
1900 to 1959, 2000 to
2059, 2100 to 2159, 2200
to 2259, 2300 to 2359
• When the year, month, day, time and minute are set in Pr.1006 to Pr.1008, the converter unit counts the date and time. The
date and time can be checked by reading Pr.1006 to Pr.1008.
NOTE
• The clock's count-up data is saved in the converter's EEPROM every 10 minutes.
• The clock does not count up while the control circuit power supply is OFF. The clock function must be reset after turning ON
the power supply. Use a separate power supply, such as an external 24 V power supply, for the control circuit of the simple
clock function, and supply power continuously to this control circuit.
• In the initial setting, converter reset is performed if supplying power to the main circuit is started when power is supplied only
to the control circuit. Then, the clock information stored in EEPROM is restored.
• The set clock is also used for functions such as fault history.
PARAMETERS 141
Parameter clear / All parameter clear on the operation panel
Operating procedure
Turning ON the power of the converter
1.
The operation panel is in the monitor mode.
Selecting the parameter setting mode
2.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Selecting a parameter
3. Turn to " " for Parameter clear or turn it to " " for All parameter clear, and press ." (initial
value)" appears.
Parameter clear
Turn to change the set value to " ". Press to enter the setting. " " and " or " are dis-
played alternately after parameters are cleared.
Description
Setting
Pr.CLR Parameter clear ALL.CL All parameter clear
0 Initial display (Parameters are not cleared.)
The settings of parameters except for calibration The settings of all the parameters, including
1 parameters and terminal function selection calibration parameters and terminal function
parameters are initialized. selection parameters, are initialized.
142 PARAMETERS
Copying and verifying parameters on the operation panel
NOTE
• When the copy destination is other than the FR-A842 converter or when Parameter copy is attempted after the parameter
copy reading was stopped, the product series error indication " " appears.
• Refer to the parameter list on page 190 for the availability of parameter copy.
• When the power is turned OFF or an operation panel is disconnected, etc. during parameter copy writing, perform parameter
copy writing again or check the setting values by using parameter verification.
• If parameters are copied from a not-upgraded converter to an upgraded converter that has additional parameters due to
upgrade, out-of-range setting values may be written in some parameters. In that case, those parameters operate as if they
were set to initial values.
Reading the parameter settings in the converter and storing them in the
operation panel
Operating procedure
1. Connect the operation panel to the source converter.
Selecting the parameter setting mode
2.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Selecting a parameter
4. Turn to change the set value to " ". Press to start reading the parameter settings from the converter and stor-
ing them in the operation panel. (It takes about 30 seconds to read and store all the settings. During reading, " " blinks.) 5
End of reading
5.
" " and " " are displayed alternately after the reading is completed.
NOTE
• " " appears... Why?
- Parameter read error. Perform operation from Step 3 again.
PARAMETERS 143
Copying and verifying parameters on the operation panel
Selecting a parameter
Press to start writing the parameter settings stored in the operation panel to the converter. (It takes about 60 seconds to
5.
write all the settings. During writing, " " blinks.)
● Perform this step while the converter is stopped. (Parameter settings cannot be copied during operation.)
End of copying
6.
" " and " " are displayed alternately after copying ends.
7. When parameters are written to the target converter, reset the converter before operation by, for example, turning the power OFF.
NOTE
• " " appears... Why?
- Parameter write error. Perform operation from Step 3 again.
144 PARAMETERS
Copying and verifying parameters on the operation panel
Operating procedure
1. Copy the parameter settings in the verification source converter to the operation panel according to the procedure on page 143.
2. Detach the operation panel from the source converter and attach it to the verification target converter.
Turning ON the power of the converter
3.
The operation panel is in the monitor mode.
Selecting the parameter setting mode
4.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Selecting a parameter
Turn to change the setting value to " " (Parameter copy verification).
Press . Verification of the parameter settings copied to the operation panel and the parameter settings in the verification tar-
6.
get converter is started. (It takes about 60 seconds to verify all the settings. During verification, " " blinks.)
● If there are different parameters, the different parameter number and " " are displayed alternately.
7. " " and " " are displayed alternately after verification ends.
NOTE
• " " blinks... Why?
PARAMETERS 145
Checking parameters changed from their initial values (initial value change list)
Operating procedure
Turning ON the power of the converter
1.
The operation panel is in the monitor mode.
Selecting the parameter setting mode
2.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Selecting a parameter
Turn . The parameter numbers that have been changed from their initial value appear in order.
● When is pressed with a changed parameter displayed, the setting change process of the parameter starts. (Parameter
4.
numbers are no longer displayed in the list when they are returned to their initial values.)
● The indication returns to " " when the last changed parameter is displayed.
NOTE
• The calibration parameters (C0 (Pr.900), C1 (Pr.900), C8 (Pr.930) to C11 (Pr.931)) are not displayed even when these are
changed from the initial settings.
• Parameter setting using the initial value change list is also possible.
146 PARAMETERS
6 PROTECTIVE
FUNCTIONS
OFF
• Turn ON the Reset (RES) signal and keep it ON for more than 0.1
Converter
seconds. (If the RES signal is kept ON, "Err" appears (blinks) to
indicate that the converter is in a reset status.)
RES
SD
Blinking Blinking
Fault record 1∗3
Blinking Blinking
Latest fault
Month Year
6
Eighth latest fault
When there is no fault
history, "E0" is displayed. Press the setting dial.
When an overcurrent trip occurs by an instantaneous overcurrent, the monitored current value saved in the fault history may be lower than the
actual current that has flowed.
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
When the converter is used as an inverter before conversion, fault records are displayed for both before and after the conversion (the indication
can be switched for up to eight records).
(After the eighth fault occurs in the converted converter, only the converter's fault records will be displayed.)
Clearing procedure
POINT
• Set "1" in Err.CL Fault history clear to clear the fault history.
Operating procedure
Turning ON the power of the converter
1.
The operation panel is in the monitor mode.
Parameter setting mode
2.
Press to choose the parameter setting mode. (The parameter number read previously appears.)
Turn to change the set value to " ". Press to start clear.
" " and " " are displayed alternately after the fault history is cleared.
4.
•Turn to read another parameter.
Error message
A message regarding operational troubles is displayed. The
Fault
converter output is not shut off. • When a protective function is activated, the converter
output is shut off and the Fault (ALM) signal is output.
Operation Refer Output of the connected inverters are also shut off.
panel Name to • The data code is used for checking the fault via
indication page
communication or for setting Pr.997 Fault initiation.
Operation panel lock 153
Operation Refer
Parameter write error 153 Data
panel Name to
code
to indication page
Copy operation fault 153
19
Overcurrent trip 156
(H13)
Error 154 35
Overvoltage trip 156
(H23)
Warning Overload trip (electronic 48
156
thermal relay function) (H30)
• Output is not shut off when a protective function is
64
activated. Heat sink overheat 156
(H40)
80
Operation Refer Instantaneous power failure 157
(H50)
panel Name to 81
Undervoltage 157
indication page (H51)
82
Overload signal detection 154 Input phase loss 157
(H52)
Electronic thermal O/L relay pre-alarm 154 External thermal relay 144
157
operation (H90)
Power supply not detected 155 160
Option fault 157
(HA0)
PU stop 155 171
Invalid version 158
(HAB)
SA 155
176
Parameter storage device fault 158
to (HB0)
Maintenance timer 1 to 3 155 177
PU disconnection 158
(HB1)
178
Retry count excess
Alarm (HB2)
158
179
• Output is not shut off when a protective function is Parameter storage device fault 158
(HB3)
activated. An alarm can also be output with a parameter 183
Reactor overheat 158
setting. (HB7)
192
Operation Refer
6
(HC0)
panel Name to 245
indication page (HF5)
CPU fault 159
246
Fan alarm 155 (HF6)
247
(HF7)
Operation panel power supply
193
short circuit / RS-485 terminals 159
(HC1)
power supply short circuit
194
24 VDC power fault 159
(HC2)
197
Inrush current limit circuit fault 159
(HC5)
201
Safety circuit fault 160
(HC9)
Operation Refer
Data
panel Name to
code
indication page
202
(HCA)
Internal circuit fault 160
253
(HFD)
241
(HF1)
242
Option fault 160
(HF2)
243
(HF3)
248
Input power supply fault 160
(HF8)
Others
The fault history or the operation status of the converter is
notified. It is not a fault indication.
Operation Refer
panel Name to
indication page
Fault history 148
Operation panel
HOLD
indication
Name Operation panel lock
Operation panel
Er1
indication
Name Parameter write error
• Parameter setting was attempted while Pr.77 Parameter write selection is set to disable parameter write.
Description • The PU and the converter cannot make normal communication.
• An attempt is made to change the setting of a parameter that cannot be changed during converter operation.
• Parameter write was attempted while Pr.77 Parameter write selection = "1". (Refer to page 106.)
Check point • Check for a connection failure between the PU and the converter.
• Check that the converter is stopped.
• Set Pr.77 Parameter write selection = "2" and retry.
Corrective action • Check the connection of the PU and the converter.
• After stopping the operation, make parameter setting.
Operation panel
rE1
indication
Name Parameter read error
A failure has occurred at EEPROM in the operation panel during reading of the parameter settings for
Description
Parameter copy.
Check point
• Perform Parameter copy again. (Refer to page 143.)
Corrective action
• The operation panel (FR-DU08) may be faulty. Contact your sales representative.
Operation panel
rE2
indication
Name Parameter write error
A failure has occurred at EEPROM in the operation panel during writing of the parameter settings for
Description
Parameter copy.
Check point The [FWD] or [REV] LED indicator on the operation panel (FR-DU08) is blinking.
Corrective action The operation panel (FR-DU08) may be faulty. Contact your sales representative.
Operation panel
indication
rE3 6
Name Parameter verification error
• The data in the converter are different from the data in the operation panel.
Description
• A failure has occurred at EEPROM in the operation panel during parameter verification.
Check point Check the parameter setting of the source converter against the setting of the target converter.
Operation panel
rE4
indication
Name Product series error
• The series of source converter for Parameter copy or the parameter writing/verification is different from that
Description of target converter.
• Parameter copy is attempted after the parameter copy reading was stopped.
• Check that the verifying converter is the same model.
• Check that reading was not interrupted during Parameter copy by switching OFF the power or by
Check point
disconnecting the operation panel.
• Parameter copy was attempted while Pr.77 Parameter write selection = "1".
• Perform Parameter copy or the parameter verification between converters of the same series.
Corrective action • Perform Parameter copy again.
• Set Pr.77 Parameter write selection = "2" and retry.
Operation panel
Err.
indication
• When RES signal is ON.
• When the PU and the high power factor converter cannot make normal communication. (Contact faults of
the connector)
Description • This error may occur when the voltage at the input side of the converter drops.
• When using a separate power source for the control circuit power (R1/L11, S1/L21) from the main circuit
power (R4/L14, S4/L24, T4/L34), this error may appear at turning ON of the main circuit. It is not a fault
indication.
• Turn OFF the RES signal.
Corrective action • Check the connection between the PU and the converter.
• Check the voltage on the input side of the converter.
Warning
Output is not shut off when a protective function is activated.
Operation panel
OL FR-PU07 OL
indication
Name Overload signal detection
Description Appears when the current limit function of the converter activates.
• Check that the acceleration/deceleration time of the inverter is not too short.
• Check that the load is not too heavy.
Check point
• Check for any failures in peripheral devices.
• Check that Pr.22 Current limit level is appropriate. (Refer to page 92.)
• Set the acceleration/deceleration time of the inverter longer.
• Reduce the load.
Corrective action • Check that the peripheral devices are operating properly.
• The limit level of the output current can be set with Pr.22 Current limit level. (Initial value is 150%.) Set the
current limit level higher with Pr.22 Current limit level.
Operation panel
TH FR-PU07 TH
indication
Name Electronic thermal O/L relay pre-alarm
Appears if the cumulative value of the electronic thermal relay reaches or exceeds 85% of the preset level. If
the specified value is reached, the protection circuit is activated to stop the converter control.
Description THP signal can be simultaneously output with the [TH] display. For the terminal used for the THP signal
output, set "8 (positive logic)" or "108 (negative logic)" in any of Pr.192 to Pr.194 or Pr.196 (Output terminal
function selection) to assign the function. (Refer to page 129.)
Check point Check for large load or sudden acceleration.
Corrective action Reduce the load and frequency of operation.
Operation panel
SL FR-PU07 SL
indication
Name Power supply not detected
• Appears when the power supply detection ends incompletely at a power failure.
Description • Appears when power is supplied only to the control circuit through terminals R1/L11 and S1/L12.
• Appears when a fuse is blown in the phase detection transformer box.
• Check the power supply and the wiring.
Check point • Check the wiring for power supply detection.
• Check if the fuse is blown in the phase detection transformer box.
• Perform wiring correctly.
Corrective action
• Contact your sales representative.
Operation panel
PS FR-PU07 PS
indication
Name PU stop
The PU stop (stop of the converter operation by pressing on the PU) is enabled by the setting of Pr.75
Description
Reset selection/disconnected PU detection/PU stop selection. (For the details of Pr.75, refer to page
104.)
Check point Check for a stop made by pressing of the operation panel.
To reset the indication, turn ON the Converter stop (SOF) signal to stop the converter output, and press
Corrective action
.
Operation panel to
MT1 to MT3 FR-PU07 MT1 to MT3
indication
Operation panel
SA FR-PU07 SA
indication
Name SA
Appears when the shorting wire across terminals S1 and PC or terminals S2 and PC is disconnected. (Refer
Description
to page 49.)
Check point Check if the shorting wire across terminals S1 and PC or terminals S2 and PC is disconnected.
• Short across terminals S1 and PC and across S2 and PC with shorting wire to operate the converter.
Corrective action • If " " is indicated when wires across S1 and SIC and across S2 and SIC are both conducted, internal
failure might be the cause. Check the wiring of terminals S1, S2 and SIC and contact your sales
representative if the wiring has no fault.
6
Alarm
Output is not shut off when a protective function is activated. An alarm can also be output with a parameter setting.
(Set "98" in any of Pr.192 to Pr.194 and Pr.196 (Output terminal function selection) (refer to page 129).
Operation panel
FN FR-PU07 FN
indication
Name Fan alarm
Description " " appears on the operation panel when the cooling fan in the converter stops due to a fault, slows
down, or moves differently from the Pr.244 Cooling fan operation selection setting.
Check point Check the cooling fan for a failure.
Corrective action Check for fan failure. Please contact your sales representative.
Fault
When a protective function is activated, the converter output is shut off and the Fault (ALM) signal is output. Output of the
connected inverters are also shut off.
Operation panel
E.OCT FR-PU07 E.OCT
indication
Name Overcurrent trip
Description The converter output is shut off if the input current exceeds the specified level during operation.
• Check for sudden load change.
• Check for a short-circuit in the output circuit.
Check point
• Check that the wiring is performed correctly.
• Check that any power supply failure did not occur.
• Keep the load stable.
• Check the wiring to make sure that output short circuit does not occur.
Corrective action
• Check the wiring.
• Check the power supply.
Operation panel
E.OVT FR-PU07 E.OVT
indication
Name Overvoltage trip
If the converter's internal main circuit DC voltage reaches or exceeds the specified value, the protective
Description circuit is activated to shut off the output of the converter. The circuit may also be activated by a surge voltage
produced in the power supply system.
• Check for sudden load change and excessive regeneration.
Check point
• Check that any power supply failure did not occur.
• Keep the load stable.
Corrective action
• Check the power supply.
Operation panel
E.THT FR-PU07 Inv. Overload
indication
Name Overload trip (electronic thermal relay function)
For the protection of transistor, electronic thermal relay is activated in inverse-time characteristics against the
Description
converter input to shut off the output of the converter.
• Check the motor for the use under overload.
Check point
• Check that the total capacity of the inverters used is not larger than the capacity of the converter.
• Reduce the load.
Corrective action
• Reconsider the configuration of the inverters for the converter.
Resetting the converter initializes the internal cumulative heat value of the electronic thermal O/L relay function.
Operation panel
E.FIN FR-PU07 H/Sink O/Temp
indication
Name Heat sink overheat
When the heat sink overheats, the temperature sensor is activated, and the converter output is shut off.
The FIN signal can be output when the temperature becomes approximately 85% of the heat sink overheat
protection operation temperature.
Description
For the terminal used for the FIN signal output, set "26 (positive logic)" or "126 (negative logic)" in any of
Pr.192 to Pr.194 or Pr.196 (Output terminal function selection) to assign the function. (Refer to page
129.)
• Check for too high surrounding air temperature.
Check point • Check for heat sink clogging.
• Check that the cooling fan is not stopped. (Check that FN is not displayed on the operation panel.)
• Set the surrounding air temperature to within the specifications.
Corrective action • Clean the heat sink.
• Replace the cooling fan.
Operation panel
E.IPF FR-PU07 Inst. Pwr. Loss
indication
Name Instantaneous power failure
• When a power failure occurs (or when power input to the converter is shut off), the instantaneous power
failure protection function is activated to shut off the output of the converter and prevent the control circuit
from malfunctioning. If a power failure persists for 100 ms or longer, the fault output is not provided, and the
converter and the inverter restart if the start signal is ON upon power restoration. In some operating status
Description
(load magnitude, acceleration/deceleration time setting of the inverter, etc.), overcurrent or other protection
may be activated upon power restoration.
The IPF signal is output when a power failure is detected. (Refer to page 129.)
• When a fuse is blown in the phase detection transformer box, the converter output is shut off.
• Find the cause of instantaneous power failure occurrence.
Check point
• Check if the fuse is blown in the phase detection transformer box.
• Remedy the instantaneous power failure.
• Prepare a backup power supply for instantaneous power failure.
Corrective action
• Set the function of automatic restart after instantaneous power failure (Pr.57). (Refer to page 101.)
• If a fuse is blow in the transformer box, contact your sales representative.
Operation panel
E.UVT FR-PU07 Under Voltage
indication
Name Undervoltage
If the power supply voltage of the converter decreases, the control circuit will not perform normal functions. To
Description
prevent this, the converter output is shut off when the power supply voltage drops to about 300 VAC or lower.
Check point Check if a high-capacity motor is driven.
Check the power supply system equipment such as the power supply.
Corrective action
If the problem still persists after taking the above measure, contact your sales representative.
Operation panel
E.ILF FR-PU07 Input phase loss
indication
Name Input phase loss
• This protective function is activated when any of the three phases of power input is lost.
Description
• When a fuse is blown in the phase detection transformer box, the converter output is shut off.
• Check for a break in the cable for the three-phase power supply input.
Check point
• Check if the fuse is blown in the phase detection transformer box.
• Wire the cables properly.
Corrective action • Repair a break portion in the cable.
• If a fuse is blow in the transformer box, contact your sales representative.
Operation panel
E.OHT FR-PU07 OH Fault
indication
Name External thermal relay operation
If an overheat protection device such as a thermostat is activated, the converter output is shut off.
Description This function is available when "7" (OH signal) is set in any of Pr.178 to Pr.189 (input terminal function
selection). This protective function is not available in the initial status. (OH signal is not assigned.)
• Check for the overheat of a thermostat or other similar peripheral devices.
Check point
• Check if the input specification (NO/NC contact) of the OH signal is incorrect.
• Check the wiring.
Corrective action • Use Pr.9 OH input selection to change the input specification. (Refer to page 91.)
• Even if the thermostat restarts automatically, the converter does not restart unless it is reset.
6
Operation panel
E.OPT FR-PU07 Option Fault
indication
Name Option fault
Description When the FR-A8AVP is not installed in the converter, the converter output is shut off.
• Check that the FR-A8AVP is not removed from the converter.
Check point
• Check for a contact fault between the FR-A8AVP and the converter.
Corrective action Install the FR-A8AVP to the converter correctly.
Operation panel
E.VER FR-PU07 Fault
indication
Name Invalid version
Description Appears when an incompatible FR-A8AVP is used for the converter.
Check if the FR-A8AVP installed at the time of conversion to the converter was removed, and another FR-
Check point
A8AVP with a different firmware version has been installed.
Install the correct FR-A8AVP which was used for conversion to the converter. First, convert the converter
Corrective action
back into the inverter, and then convert the inverter into the converter again.
Operation panel
E.PE FR-PU07 Corrupt Memry
indication
Name Parameter storage device fault (control circuit board)
Description The converter output is shut off if a fault occurs in the parameters stored. (EEPROM failure)
Check point Check for too many number of parameter write times.
Contact your sales representative.
Corrective action Set "1" in Pr.342 (write to RAM) for the operation which requires frequent parameter writing via communication,
etc. Note that writing to RAM goes back to the initial status at power OFF.
Operation panel
E.PUE FR-PU07 PU Leave Out
indication
Name PU disconnection
The converter output is shut off if communication between the converter and PU is suspended, e.g. the
operation panel or parameter unit is disconnected, when the disconnected PU detection function is enabled
Description
by Pr.75 Reset selection/disconnected PU detection/PU stop selection. This protective function is not
enabled in the initial setting (Pr.75 = "14").
• Check that the FR-DU08 or the parameter unit (FR-PU07) is connected properly.
Check point
• Check the Pr.75 setting.
Corrective action Install FR-DU08 or the parameter unit (FR-PU07) securely.
Operation panel
E.RET FR-PU07 Retry No Over
indication
Name Retry count excess
If operation cannot be resumed properly within the number of retries set, this function shut off the output of the
converter.
Description
This function is enabled when Pr.67 Number of retries at fault occurrence is set. This protective function is
disabled in the initial setting (Pr.67 = "0").
Check point Find the cause of the fault occurrence.
Corrective action Eliminate the cause of the error preceding this error indication.
Operation panel
E.PE2 FR-PU07 PR storage alarm
indication
Name Parameter storage device fault (main circuit board)
Description The converter output is shut off if a fault occurs in the parameters stored. (EEPROM failure)
Check point ――――
Corrective action Contact your sales representative.
Operation panel
E.LOH FR-PU07 Fault
indication
Name Reactor overheat
When the reactor is overheated, the converter output is shut off. (This function is not available when power is
Description
supplied only to the control circuit.)
• The reactor 1 or 2 is not connected.
• Check the wiring between the overheat detection thermostat of reactor and the terminal to which the LOH
Check point signal is assigned.
• The fan power terminals for the reactors 1 and 2 are not connected to the MC power supply stepdown
transformer.
• Connect the reactors 1 and 2.
• Correct the wiring between the overheat detection thermostat of reactor and the terminal to which the LOH
Corrective action signal is assigned.
• Correct the wiring between the MC power supply stepdown transformer and the fan power terminals for the
reactors 1 and 2.
E. 5 Fault 5
E. 6 Fault 6
Operation panel
FR-PU07
indication
E. 7 Fault 7
Operation panel
E.CTE FR-PU07 E.CTE
indication
Name Operation panel power supply short circuit, RS-485 terminal power supply short circuit
When the operation panel power supply (PU connector) is short circuited, this function shuts off the power
output and stops the converter. The use of the operation panel (parameter unit) and the RS-485
communication via the PU connector are disabled. To reset, enter RES signal, or switch power OFF then ON
again.
Description
When the power supply for the RS-485 terminals are short circuited, this function shuts off the power output.
At this time, the use of the RS-485 communication via the RS-485 terminals are disabled.
To reset, use of the operation panel, enter the RES signal, or switch power OFF then ON again.
Operation panel
E.P24 FR-PU07 E.P24
indication
Name 24 VDC power output short circuit
When the 24 VDC power output from the PC terminal is shorted, this function shuts off the power output.
Description At this time, all external contact inputs switch OFF. The inverter cannot be reset by inputting the RES signal.
To reset it, use the operation panel, or switch power OFF, then ON again.
• Check for a short circuit in the PC terminal output.
Check point
• Check that the 24 V external power supply voltage is correct.
• Repair the short-circuited portion.
• Supply the power at 24 V. (If the power with insufficient voltage is supplied to the 24 V input circuit for a long
Corrective action
time, the inverter internal circuit may heats up. Although it will not damage the inverter, supply power at the
correct voltage .)
Operation panel
E.IOH FR-PU07 Inrush overheat
indication
Name Inrush current limit circuit fault
Stops the converter operation when the inrush current limit contactor does not turn ON or a thermostat of the
Description
inrush current limit resistor is activated. 6
The inrush current limit circuit is faulty.
When the terminal PC and SD are shorted, the ROH signal turns OFF and the converter output is shut off.
• Check the wiring between the resistor thermostat and the terminal to which the ROH signal is assigned.
• Check that the inrush current limit circuit contactor and buffer circuit are not damaged.
Check point • Check that frequent power ON/OFF is not repeated.
• Check that the resistor thermostat is connected with the terminal to which the ROH signal is assigned.
• Check for a short circuit between terminals PC and SD.
• Connect the resistor thermostat with the terminal to which the ROH signal is assigned.
• Configure a circuit where frequent power ON/OFF is not repeated.
Corrective action • Check the wiring between the resistor thermostat and the terminal to which the ROH signal is assigned.
• Check the wiring between terminals PC and SD.
If the problem still persists after taking the above measure, contact your sales representative.
Operation panel
E.SAF FR-PU07 Safety circuit fault
indication
Name Safety circuit fault
• The converter output is shut off when a safety circuit fault occurs.
Description • The converter output is shut off when the shorting wire across terminals S1 and PC or terminals S2 and PC
is disconnected.
Check point Check if the shorting wire across terminals S1 and PC or terminals S2 and PC is disconnected.
• Short across terminals S1 and PC and terminals S2 and PC with shortening wires. (Refer to page 55.)
Corrective action • If this fault occurs even though the shorting wire across the terminals S1 and PC or the terminals S2 and PC
is connected, contact your sales representative.
E.PBT E.PBT
Operation panel
FR-PU07
indication
E.13 Fault 13
Name Internal circuit fault
Description The converter output is shut off when an internal circuit fault occurs.
Corrective action Contact your sales representative.
Operation panel E. 1 to to
FR-PU07 Fault 1 to Fault 3
indication E. 3
Operation panel
E.8 FR-PU07 Fault 8
indication
Name Input power supply fault
• When a fault is detected in the power supply frequency,
• When the phase detection cannot be performed for the normal power supply,
• When an overvoltage occurs during power failure or at an input phase loss.
Description
• When the power supply amplitude changes suddenly,
• When a fuse is blown in the phase detection transformer box,
it is regarded as a power supply fault, and the outputs of the converter and the inverter are stopped.
• Check the power supply and the wiring.
Check point
• Check if the fuse is blown in the phase detection transformer box.
• Perform wiring correctly.
Corrective action
• If a fuse is blow in the transformer box, contact your sales representative.
Others
Indicates the status of the converter. It is not a fault indication.
Operation panel
E.0 FR-PU07 No Alarm
indication
Name No fault history
Appears when no fault records are stored. (Appears when the fault history is cleared after the protective
Description
function has been activated.)
Operation panel
EV FR-PU07 EV
indication
Name 24 V external power supply in operation
Description Blinks when the main circuit power supply is off and the 24 V external power supply is being input.
Check point Power is supplied from a 24 V external power supply.
• Turning ON the power supply (main circuit) of the converter clears the indication.
Corrective action • If the indication is still displayed after turning ON of the power supply (main circuit) of the converter, the
power supply voltage may be low.
NOTE
• If faults other than the above appear, contact your sales representative.
When the phase sequence is correct, check for the short circuit
across terminals SOF and SD and across terminals RES and SD.
Check the following about connection:
● Connection is performed correctly.
The power lamp is OFF. ● Wiring for the main circuit terminals R4/L14, S4/L24, and T4/L34 is performed
correctly.
● The inrush current limit resistor is not damaged.
Check the following about connection:
The charge lamp on the converter does not ● Connection is performed correctly.
come on. ● Wiring for the main circuit terminals R4/L14, S4/L24, and T4/L34 is performed
correctly.
Check the following about connection:
Reactor heats up abnormally.
● Check if the sequence of the reactors 1 and 2 is correct.
Check the following about the setting:
The parameter settings in the inverter are appropriate. (Parameter setting
The inverter does not run.
method differs by the inviter series. For the parameter setting method, refer to
page 23)
Unusual noises are generated from the reactor. The phase sequence is correct.
Check the following about connection:
● Wiring is performed correctly.
A breaker trips. ● Appropriate power supply voltage is applied.
● The phase sequence is correct.
Identify the cause of the trip and remove it before turning ON the power of the breaker.
The converter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any
fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and
vibration, changes in the parts with time, service life, and other factors.
CAUTION
Reactor 1 and reactor 2 are extremely hot. Take caution not to get burned.
(1) Check for unusual vibration and noise. Replace the fan.
Cooling fan (2) Check for loose screws and bolts. Retighten.
(3) Check for stains. Clean.
Cooling
(1) Check for clogging. Clean.
system Heat sink
(2) Check for stains. Clean.
(1) Check for clogging. Clean or replace.
Air filter, etc.
(2) Check for stains. Clean or replace.
(1) Check that indications are correct. Contact the manufacturer.
Indication
(2) Check for stains. Clean.
Display
Meter/counter Check that readouts are correct.
Stop the equipment and
contact the manufacturer. 7
Oil component of the heat dissipation grease used inside the converter may leak out. The oil component, however, is not flammable, corrosive,
nor conductive and is not harmful to humans. Wipe off such oil component.
It is recommended to install a device to monitor voltage for checking the power supply voltage to the converter.
One to two years of periodic inspection cycle is recommended. However, it differs according to the installation environment.
Consult us for periodic inspection.
NOTE
• Continuous use of a leaked, deformed, or degraded smoothing aluminum electrolytic capacitor (as shown in the table above)
may lead to a burst, breakage, or fire. Replace such capacitor without delay.
Checking method
Change the polarity of the tester alternately at a semiconductor device (transistor) on an electrical path between two terminals
among the converter main circuit terminals R4/L14, S4/L24, T4/L34, P/+, and N/- to check the electric continuity.
NOTE
• Before measurement, check that the smoothing capacitor is discharged.
• At the time of electric discontinuity, the measured value is almost ∞. When there is an instantaneous electric continuity, due to
the smoothing capacitor, the tester may not indicate ∞. At the time of electric continuity, the measured value is several Ω to
several tens of Ω. If all measured values are almost the same, although these values are not constant depending on the
module type and tester type, the modules are without fault.
7.1.5 Cleaning
Always run the converter in a clean status.
When cleaning the converter, gently wipe dirty areas with a soft cloth immersed in neutral detergent.
NOTE
• Do not use solvent, such as acetone, benzene, toluene and alcohol, as these will cause the converter surface paint to peel
off.
The display, etc. of the operation panel (FR-DU08) and parameter unit (FR-PU07) are vulnerable to detergent and alcohol.
Therefore, avoid using them for cleaning.
Estimated lifespan for when the yearly average surrounding air temperature is 40°C
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Input current: 80% of the converter rating
NOTE
• For replacement of each part, contact the nearest Mitsubishi Electric FA center.
Fan
3) Fan block
7
2) Fan cover
Fan connector
1)
Hook hole
Hook
Mounting screw
(Tightening torque: 4.4 to 5.9 N·m)
Fan block
Cable clamp
Cable clamp
Fan connector
Fan
Fan block
NOTE
• The fan block has a hook. To remove the fan block from the reactor, first pull the hook-less side of the fan block away from the
reactor, and then disengage the hook from the hole, as shown in the first figure above.
• When fitting the cooling fan into the fan block, first pass the fan cable through the cable clamps if the clamps have been
removed for removal of the fan. Next, fasten the fan to the fan block using the mounting screws (some of them passing
through holes in the clamps). Improper installation may damage the fan. For example, loose fan wires may get caught in the
fan.
AIR FLOW
NOTE
• Installing the cooling fan in the opposite direction may shorten the product life.
• Installing the reactor cooling fan in the opposite direction may cause overheating of the reactor, which results in activation of
the converter protective function (E.LOH).
• Prevent the cable from being caught when installing a fan.
• Switch the power OFF before replacing fans. Since the converter circuits are charged with voltage even after power OFF,
replace fans only when the converter cover is on the converter to prevent an electric shock accident.
Smoothing capacitors
A large-capacity aluminum electrolytic capacitor is used for smoothing in the DC section of the main circuit, and an aluminum
electrolytic capacitor is used for stabilizing the control power in the control circuit. Adverse effects from ripple currents
deteriorate capacitors. Replacement intervals of capacitors vary greatly with surrounding temperatures and operating
conditions. Replace them roughly every 10 years when used in normal air-conditioned environments.
When a certain period of time has elapsed, capacitors will deteriorate more rapidly. Check capacitors at least every year (less
than six months if the life will be expired soon).
Check the following during inspection to determine the end of product life.
• Case: Check that the sides and bottom of the capacitor have not ruptured.
• Rubber seal: Check for any noticeable bulging or severe cracks.
• Top (vent): Check for swollen, open, or exploded vent.
• Others: Check for external cracks, discoloration, and leakage.
2) Be careful not to bend the pins of the converter's control circuit connector, reinstall the control circuit terminal block and fix
it with the mounting screws.
NOTE
• Before starting converter replacement, switch power OFF, wait for at least 10 minutes, and then check the voltage with a
tester and such to ensure safety.
A
Control circuit terminal block
Converter's control
circuit connector
Insert the
terminal block
parallel to the
converter.
NOTE
• Do not tilt the terminal block while tightening the screws or removing it from the converter. (Otherwise, stress applied to the
control circuit terminal block or the control circuit connector may damage the pins.)
• After replacing the control terminal block, connect the jumper connector to the correct position in accordance with the control
logic of input signals. (Refer to page 53.)
Converter
Reactor 1 Reactor 2
R4/L14 P/+
+
Wattmeter
Filter capacitor,
Power inrush current S4/L24 V To inverter
limit resistor,
and MCs -
T4/L34 N/-
7
Earth (ground)
CAUTION
Before performing the insulation resistance test on the external circuit, disconnect the cables from
all terminals of the converter so that the test voltage is not applied to the converter.
For the continuity test of the control circuit, use a tester (high resistance range), and do not use the
megger or buzzer.
174
8 SPECIFICATIONS
SPECIFICATIONS 175
Converter rated specifications
176 SPECIFICATIONS
Common specifications
SPECIFICATIONS 177
Outline dimension drawings
R/L1
4×φ14
S/L2 T/L3
300±2
600±10 2×φ15
190±5 190±5 110±5 110±5
75 6 6
25
Rating plate
690 max
380±10
Model name D
410±2
600±10
2×φ15
190±5 190±5 160±5 160±5
75 6 6
25
Rating plate
770 max
D±10
178 SPECIFICATIONS
Outline dimension drawings
2×φ6
245
260
7.5
16.6 6 1.6
Rating plate
15 80 (15)
110 120
38 34 (38)
(Unit: mm)
74.6
Mass: 3.2 kg
Terminal block
R S T R2 RS2 TS2 T2
8
Terminal screw size
Model Terminals R, S, T, R2, RS2, TS2, and T2 Earth (ground) terminal
FR-A8VPB-H M3.5 M3.5
SPECIFICATIONS 179
Outline dimension drawings
320±3
A
55±1
75±2
90±3
Enlarged view of section A
(Unit: mm)
Mass: 9 kg
B
Attach the fixing brackets to the capacitor (refer to page 33).
FR-A8BC-H500K
433±5
398±3
15
16
80±5 80±5 Screw size: M12
Enlarged view of section B
Rating plate
370±12
305±8
200±3
(Unit: mm)
3.2
Mass: 20 kg
180 SPECIFICATIONS
Outline dimension drawings
8×φ9
9 145
60 136
11.5
26.5
9
A1 A2
243
190
220
31
43
32
2/T1 4/T2 6/T3 44
30 3.2
M12 screw M4 screw (Unit: mm)
55 195
163 Mass: 9.5 kg
SPECIFICATIONS 181
Outline dimension drawings
M4 screw
11
7
Screw size: M6
8.8 134.5 Enlarged view of section A
A
140 max
175 max
2.3
Rating plate
100±1.5 81±1.5
152±2.5 (101)
(Unit: mm)
Mass: 9 kg
A2 A1
23.7
13 23 33 43 53
75
41.6
60 ∗1
50 ∗1
52 ∗1
14 24 34 44 54
8.5 10
7.5 78
(Unit: mm)
43
Mass: 0.27 kg
Screw size: M4
The position of the upper-left mounting hole is selectable. Combinations of the horizontal and vertical dimensions are as follows: 35 and 60, 30
and 60, 34 and 52, 35 and 50-52.
(Unit: mm)
Mass: 35 g
182 SPECIFICATIONS
Outline dimension drawings
33 max 30
70 max
59
B
4
24.5
Screw size: M4
5
200±1.2
Screw size: M5
215±2 500±10
325±15
175±2 6±1 30±1
6±1
(30)
2.5 -0.3
0
60±1.5
(Unit: mm)
Thermostat output Mass: 0.8 kg
(provided for BKO-CA2573H11 only)
SPECIFICATIONS 183
Compatible options
panel
connection cable
(FR-CB2[]) (option)
72.5
78.5
20
72.5
5
22
Hole
(Unit: mm)
40 40
∗1
∗1
Hole
50
51
4-R1
∗1
∗1
135
67
56.8
57.8
(Unit: mm)
184 SPECIFICATIONS
9 CONVERTER-TO-
INVERTER
CONVERSION
This chapter explains how to convert the converter back into the original
inverter.
Always read the instructions before use.
Check the following while the control circuit power of the converter is OFF.
• The FR-A8AVP is installed in one of the option connectors (1 to 3). (Refer to page 11.)
• All of the main circuit terminals are open without wires connecting to them.
• Terminals R1/L11 and S1/L21 are used to supply power to the control circuit of the converter.
• No USB memory device is connected.
Check the following while the control circuit power of the converter is ON.
• The converter is in normal state and its operation is stopping. (Other than E.VER, no protective function is activated.)
NOTE
• When terminal +24 is used to supply power to the control circuit of the converter, the conversion to the inverter is disabled.
1 Enter "3100".
Check that "3100" is displayed for Pr.328.
2 Enter "1080".
Check that "1080" is displayed for Pr.328.
3 Enter "2000".
The converter-to-inverter conversion starts when "2000" is entered. The communication status LED indicator
starts blinking. (The following figure shows the location of the LED indicator.)
The LED indicator stays ON after the conversion is completed.
(It takes about 300 seconds to complete the conversion.)
NOTE
• After entering "2000", do not operate the PU until the LED indicator stays ON.
6 Press the setting dial on the operation panel (FR-DU08) and check that "CNV" (converter) is
not displayed.
NOTE
• If the control circuit power is turned OFF once and then turned ON again, conversion may restart depending on the timing of
power OFF.
188
APPENDIX
APPENDIX 189
Appendix 1 Instruction code list
These instruction codes are used to write or read parameters through RS-485 communication. (Refer to page 113.)
For Parameter copy, Parameter clear, and All parameter clear, indicates the function is available, and indicates the function is not available.
These parameters are communication parameters that are not cleared when Parameter clear (All parameter clear) is executed from RS-485
communication. (Refer to page 113.)
Reading and writing is enabled when commands are sent through communication via the PU connector.
Instruction
Instruction Parameter
Parameter code
code
Extended
Pr. Name
All clear
Extended
Pr. Name
All clear
Copy
Clear
Write
Read
Copy
Clear
Write
Read
PU communication
1 Maximum frequency 01 81 0 120 14 94 1
parity check
2 Minimum frequency 02 82 0
PU communication
8 SOF input selection 08 88 0 121 15 95 1
retry count
9 OH input selection 09 89 0
PU communication
22 Current limit level 16 96 0 123 17 97 1
waiting time setting
Current limit level PU communication
23 17 97 0 124
(regenerative) 18 98 1
CR/LF selection
Instantaneous power PU display language
44 failure detection signal 2C AC 0 145 2D AD 1
selection
clear
157 OL signal output timer 39 B9 1
Power supply
AM terminal function
49 frequency monitoring 31 B1 0 158 3A BA 1
selection
reference
Key lock operation
Input power 161 3D BD 1
51 33 B3 0 selection
monitoring reference
168
DU/PU main display Parameter for manufacturer setting. Do not set.
52 34 B4 0 169
data selection
170 Watt-hour meter clear 46 C6 1
Input voltage
53 35 B5 0 STF terminal function
monitoring reference 178 4E CE 1
selection
FM/CA terminal
54 36 B6 0 STR terminal function
function selection 179 4F CF 1
selection
Bus voltage
55 37 B7 0 RL terminal function
monitoring reference 180 50 D0 1
selection
Current monitoring
56 38 B8 0 RM terminal function
reference 181 51 D1 1
selection
57 Restart selection 39 B9 0
RH terminal function
65 Retry selection 41 C1 0 182 52 D2 1
selection
Number of retries at
67 43 C3 0 RT terminal function
fault occurrence 183 53 D3 1
selection
68 Retry waiting time 44 C4 0
AU terminal function
Retry count display 184 54 D4 1
69 45 C5 0 selection
erase
JOG terminal function
Reset selection/ 185 55 D5 1
selection
disconnected PU
75 4B CB 0 CS terminal function
detection/PU stop 186 56 D6 1
selection
selection
MRS terminal function
Parameter write 187 57 D7 1
77 4D CD 0 selection
selection
STOP terminal
Voltage control 188 58 D8 1
80 50 D0 0 function selection
proportional gain
RES terminal function
Voltage control 189 59 D9 1
81 51 D1 0 selection
integral gain
RDY signal logic
Current control 190 5A DA 1
82 52 D2 0 selection
proportional gain
RSO signal logic
Current control 191 5B DB 1
83 53 D3 0 selection
integral gain
IPF terminal function
Power factor 192 5C DC 1
84 54 D4 0 selection
command value
OL terminal function
Power factor lead/lag 193 5D DD 1
85 55 D5 0 selection
setting
FU terminal function
PU communication 194 5E DE 1
117 11 91 1 selection
station number
ABC2 terminal
PU communication 196 60 E0 1
118 12 92 1 function selection
speed
Cooling fan operation
PU communication 244 2C AC 2
119 13 93 1 selection
stop bit length
190 APPENDIX
Instruction Instruction
Parameter Parameter
code code
Extended
Extended
Pr. Name Pr. Name
All clear
All clear
Copy
Copy
Clear
Clear
Write
Write
Read
Read
Life alarm status C8 Current output bias
255 37 B7 2 1E 9E 9
display (930) signal
Inrush current limit C9 Current output bias
256 38 B8 2 1E 9E 9
circuit life display
(930) current
Control circuit
257 39 B9 2 C10 Current output gain
capacitor life display 1F 9F 9
(931) signal
269 Parameter for manufacturer setting. Do not set.
C11 Current output gain
Monitor negative 1F 9F 9
290 5A DA 2 (931) current
output selection
Inverter/converter 989 Parameter for manufacturer setting. Do not set.
328 1C 9C 3 990 PU buzzer control 5A DA 9
switching
RS-485 PU contrast
991 5B DB 9
331 communication station 1F 9F 3 adjustment
number 997 Fault initiation 61 E1 9
RS-485 1006 Clock (year) 06 86 A
332 20 A0 3
communication speed 1007 Clock (month, day) 07 87 A
RS-485 1008 Clock (hour, minute) 08 88 A
333 communication stop 21 A1 3 Inrush current limit
1202 02 82 C
bit length / data length circuit life setting
RS-485 R-S turns ratio
1344 2C AC D
334 communication parity 22 A2 3 compensation
check selection T-S turns ratio
1345 2D AD D
RS-485 compensation
335 communication retry 23 A3 3 1499 Parameter for manufacturer setting. Do not set.
count
RS-485
337 communication 25 A5 3
waiting time setting
RS-485
341 communication CR/LF 29 A9 3
selection
Communication
342 EEPROM write 2A AA 3
selection
503 Maintenance timer 03 83 5
Maintenance timer
504 warning output set 04 84 5
time
547
Parameter for manufacturer setting. Do not set.
548
Energization time
563 3F BF 5
carrying-over times
Control circuit
663 temperature signal 3F BF 6
output level
686 Maintenance timer 2 56 D6 6
Maintenance timer 2
687 warning output set 57 D7 6
time
688 Maintenance timer 3 58 D8 6
Maintenance timer 3
689 warning output set 59 D9 6
time
867 AM output filter 43 C3 8
869 Current output filter 45 C5 8
888 Free parameter 1 58 D8 8
889 Free parameter 2 59 D9 8
Cumulative power
891 monitor digit shifted 5B DB 8
times
C0 FM/CA terminal
00 80 9
(900) calibration
C1 AM terminal
01 81 9
(901) calibration
APPENDIX 191
Appendix 2 Instructions for compliance with
the EU Directives
The EU Directives are issued to standardize different national regulations of the EU Member States and to facilitate free
movement of the equipment, whose safety is ensured, in the EU territory.
Since 1996, compliance with the EMC Directive that is one of the EU Directives has been legally required. Since 1997,
compliance with the Low Voltage Directive, another EU Directive, has been also legally required. When a manufacturer
confirms its equipment to be compliant with the EMC Directive and the Low Voltage Directive, the manufacturer must declare
the conformity and affix the CE marking.
• The authorized representative in the EU
The authorized representative in the EU is shown below.
Company name: Mitsubishi Electric Europe B.V.
Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
EMC Directive
We declare that this high power factor converter conforms with the EMC Directive and affix the CE marking on the converter.
• EMC Directive: 2014/30/EU
• Standard(s): EN61800-3:2004+A1:2012 (Second environment / PDS Category "C3")
• This converter is not intended to be used on a low-voltage public network which supplies domestic premises. Ensure the
converter is suitable for the environment in which it is to be used when using it in residential areas.
• Radio frequency interference is expected if used on such a network.
• The installer shall provide a guide for installation and use, including recommended mitigation devices.
Note:
First environment
Environment including buildings/facilities which are directly connected to a low voltage main supply which also supplies
residential buildings. Directly connected means that there is no intermediate transformer between these buildings.
Second environment
Environment including all buildings/facilities which are not directly connected to a low voltage main supply which also supplies
residential buildings.
Note
Install the converter with the EMC filter, and perform wiring according to the following instructions.
• Set the EMC Directive compliant EMC filter to the converter. Use a recommended EMC compliant EMC filter shown in
the table below. Insert line noise filters and ferrite cores to the power and control cables as required.
• Recommended EMC compliant EMC filter (Manufactured by: SOSHIN ELECTRIC CO., LTD.)
FR-A842- FR-A842- FR-A842- FR-A842- FR-A842-
Converter model
07700(315K) 08660(355K) 09620(400K) 10940(450K) 12120(500K)
EMC compliant EMC filter NF31000C-SDK NF31000C-SDK NF31000C-SDK NF31000C-SDK NF31000C-SDK
Rated filter current 1000A 1000A 1000A 1000A 1000A
• Connect the inverter and the converter to an earthed (grounded) power supply.
• Install the motor and controller cable found in the EMC Installation Manual (BCN-A21041-204) and Technical News
(MF-S-113, 115) according to the instructions.
• Ensure that the finalized system which includes an inverter and converter unit complies with the EMC Directive.
192 APPENDIX
Low Voltage Directive
We have self-confirmed our converters as products compliant to the Low Voltage Directive (Conforming standard EN 61800-
5-1) and affix the CE marking on the converters.
Outline of instructions
• Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the
earth. Connect the equipment to the earth (ground) securely.
• Wire the earth (ground) terminal independently. (Do not connect two or more cables to one terminal.)
• Use the earth (ground) cable and the cable sizes on page 38 under the following conditions.
• Surrounding air temperature: 40°C maximum
If conditions are different from above, select appropriate wire according to EN60204.
• Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening
the screw, be careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use a PVC cable whose size is indicated on page 38.
• Use the molded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
• DC current may flow from the converter to a protective earth (ground) conductor. When using a residual current device
(RDC) or residual current monitor (RDM), connect a type B RCD or RCM to the power supply side.
• Use the converter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of
the power supply), overvoltage category III (usable with the earth-neutral system power supply, 400 V class only) and
pollution degree 2 or lower specified in IEC60664.
• To use the converter under the conditions of pollution degree 2, install it in the enclosure of IP2X or higher.
• To use the converter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
• On the input and output of the inverter and the converter, use cables of the type and size set forth in EN60204.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30 VDC, 0.3 A. (Relay
output has basic isolation from the internal circuit of the inverter and the converter.)
• Control circuit terminals on page 40 are safely isolated from the main circuit.
• The amount of current leakage from the converter measures 20 mA at maximum (in AC/DC current measuring range
specified in IEC 60990).
• Environment (For the detail, refer to page 24.)
During Operation In Storage During Transportation
Surrounding air temperature -10 to +50°C -20 to +65°C -20 to +65°C
Ambient humidity 95% RH or less 95% RH or less 95% RH or less
Maximum altitude 2500 m 2500 m 10000 m
For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
Wiring protection
Provide the UL and cUL listed fuse in accordance with the table below.
Converter model Fuse type Manufacturer Rating
FR-A842-07700(315K) 170M6111 Bussmann 700 V, 700 A
FR-A842-08660(355K) 170M6112 Bussmann 700 V, 800 A
FR-A842-09620(400K) 170M6113 Bussmann 700 V, 900 A
FR-A842-10940(450K) 170M6114 Bussmann 700 V, 1000 A
FR-A842-12120(500K) 170M6115 Bussmann 700 V, 1100 A
APPENDIX 193
Appendix 3 Instructions for UL and cUL
(Standard to comply with: UL 508C, CSA C22.2 No.274-13)
General precaution
CAUTION - Risk of Electric Shock -
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10
minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
ATTENTION - Risque de choc électrique -
La durée de décharge du condensateur de bus est de 10 minutes. Avant de commencer le câblage ou l’inspection, mettez
l’appareil hors tension et attendez plus de 10 minutes.
Installation
The below types of high power factor converter have been approved as products for use in enclosure.
Design the enclosure so that the surrounding air temperature, humidity and ambience of the converter will satisfy the above
specifications. (Refer to page 24.)
Branch circuit protection
For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical
Code and any applicable provincial codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code
and any applicable provincial codes.
Provide the appropriate fuse in accordance with the table below.
Converter model Fuse type Manufacturer Rating
FR-A842-07700(315K) 170M6111 Bussmann 700 V, 700 A
FR-A842-08660(355K) 170M6112 Bussmann 700 V, 800 A
FR-A842-09620(400K) 170M6113 Bussmann 700 V, 900 A
FR-A842-10940(450K) 170M6114 Bussmann 700 V, 1000 A
FR-A842-12120(500K) 170M6115 Bussmann 700 V, 1100 A
194 APPENDIX
Combination of the converter and the inverter (Back-to-back connection)
Use the converter in combination with the inverter specified in the following table. In addition, it is necessary to use the
peripheral devices specified in the following table for the use of the converter (the peripheral devices are only UL-approved
when used with the converter).
Dedicated
Phase circuit
Applicable
detection parts for Filter
motor Converter Plug-in Reactor 1 Reactor 2 Inverter Applicable
transformer inrush capacitor
capacity option rating
box current
protection
FR-A842- FR-A8MC- FR-A8BL1- FR-A8BL2- FR-A8BC- FR-A842-
315kW FR-A8AVP FR-A8VPB-H ND
07700(315K) H355K H315K H315K H400K 07700(315K)
FR-A842- FR-A8MC- FR-A8BL1- FR-A8BL2- FR-A8BC- FR-A842-
355kW FR-A8AVP FR-A8VPB-H ND
08660(355K) H355K H355K H355K H400K 08660(355K)
FR-A842- FR-A8MC- FR-A8BL1- FR-A8BL2- FR-A8BC- FR-A842-
400kW FR-A8AVP FR-A8VPB-H ND
09620(400K) H500K H400K H400K H400K 09620(400K)
FR-A842- FR-A8MC- FR-A8BL1- FR-A8BL2- FR-A8BC- FR-A842-
450kW FR-A8AVP FR-A8VPB-H ND
10940(450K) H500K H450K H450K H500K 10940(450K)
FR-A842- FR-A8MC- FR-A8BL1- FR-A8BL2- FR-A8BC- FR-A842-
500kW FR-A8AVP FR-A8VPB-H ND
12120(500K) H500K H500K H500K H500K 12120(500K)
The product certified in compliance with the Eurasian Conformity has the EAC marking.
For information on the country of origin, manufacture year and month, and authorized sales representative (importer) in the
CU area of this product, refer to the following:
• Country of origin indication
Check the rating plate of the product. (Refer to page 9.)
Example: MADE IN JAPAN
Symbol Year Month Control number
SERIAL
The SERIAL consists of one symbol, two characters indicating the production year and month, and six characters indicating the control number.
The last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9, X (October), Y (November), or Z (December).
APPENDIX 195
Appendix 5 Restricted Use of Hazardous
Substances in Electronic and
Electrical Products
The mark of restricted use of hazardous substances in electronic and electrical products is applied to the product as follows
based on the "Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic
Products" of the People's Republic of China.
电器电子产品有害物质限制使用标识要求
环境保护使用
期限标识
本产品中所含有的有害物质的名称、含量、含有部件如下表所示。
·产品中所含有害物质的名称及含量
有害物质
部件名称 铅 汞 镉 六价铬 多溴联苯 多溴二苯醚
(Pb) (Hg) (Cd) (Cr(VI)) (PBB) (PBDE)
电路板组件(包括印刷电
路板及其构成的零部件,
× ○ × ○ ○ ○
如电阻、电容、集成电路、
连接器等)、电子部件
金属壳体、金属部件 × ○ ○ ○ ○ ○
树脂壳体、树脂部件 ○ ○ ○ ○ ○ ○
螺丝、电线 ○ ○ ○ ○ ○ ○
上表依据SJ/T11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T26572规定的限量要求以下。
×:表示该有害物质在该部件的至少一种均质材料中的含量超出GB/T26572规定的限量要求。
即使表中记载为×,根据产品型号,也可能会有有害物质的含量为限制值以下的情况。
根据产品型号,一部分部件可能不包含在产品中。
196 APPENDIX
WARRANTY
When using this product, make sure to understand the warranty described below.
197
REVISIONS
*The manual number is given on the bottom left of the back cover.
198 IB(NA)-0600777ENG-C
INVERTER
INVERTER
Plug-in option
FR-A8AVP
INSTRUCTION MANUAL (FOR INVERTER/CONVERTER SWITCHING)
Changeover between inverter and
high power factor converter
Compatible inverters: FR-A842-07700(315K) to 12120(500K)
OUTLINE
1
INVERTER-TO-
CONVERTER 2
CONVERSION
INSTALLATION AND
WIRING 3