0% found this document useful (0 votes)
13 views3 pages

BMS Specification

The Building Management System (BMS) features a server/client architecture with Microsoft SQL Server, offering functionalities such as visualization, event handling, real-time reporting, and long-term data storage. It supports various communication protocols and interfaces, including BACnet and Modbus, and integrates with hospitality systems and access control. Hardware requirements include a 32-bit microprocessor, specific memory and power supply specifications, and the ability to operate within a defined temperature and humidity range.

Uploaded by

Hưng Ngọc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views3 pages

BMS Specification

The Building Management System (BMS) features a server/client architecture with Microsoft SQL Server, offering functionalities such as visualization, event handling, real-time reporting, and long-term data storage. It supports various communication protocols and interfaces, including BACnet and Modbus, and integrates with hospitality systems and access control. Hardware requirements include a 32-bit microprocessor, specific memory and power supply specifications, and the ability to operate within a defined temperature and humidity range.

Uploaded by

Hưng Ngọc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Building Management System (BMS)

PART 1: SOFTWARE
 Origin: EU/G7.
 Software Structure: Server/Client and Web, database built on Microsoft SQL
Server.
 IT Security Level: SAL2 (SL2).

Core Features:

1. Graphics (Visualization):
o Vector Graphics supports 2D and 3D graphics.
o Capability to import files from AutoCAD.
2. Events and Warnings:
o Support summary bar, event list, quick processing, and investigation.
3. Connection and Report:
o Real-time display, rotate/ zoom in&out, record status.
o Support report planning (reports forms are set up according to needs)
4. Scheduling:
o Plans for operational stations, view timelines.
5. Trends Graph:
o Historical dynamic trend data and comparison functionality.
6. Reactions:
o Supports event triggers by time via COV/COS or macros.
7. Data Storage:
o Long-term storage and archiving are supported.

Compatibility and Interfaces:

1. AutoCAD Import.
2. Interfaces Supported:

o BACnet, OPC, ONVIF, Modbus TCP, SNMP, IEC 61850, KNX, M-


Bus.

3. Communication Protocols:

o Email: POP3/IMAP/SMTP with SSL/TSL.


o Mobile: ESPA 4.4.4, Ascom, SMS.

Additional Software Support:

1. Hospitality Integration:
o Oracle Hospitality Opera, Fidelio Suite.
2. Access Control:
o Notification systems (via gmail), web access and mobile app support.
3. Script Editor:
o JavaScript supported.

Certifications and Compliance

 BMS Software Certification:


o B-AWS (BACnet Advanced Operator Workstation).
o BIM-3D Support.
 Environmental Standards:
o FDA 21CFR Part 11, GMP Annex 11.
 Pharma Support:
o Pharma format reports, MKT reports.

o Audit trail, validation reports


o Backup and Mounted Without disrupting the system.
o SQL Database Support with long-term storage.
o Active Directory Support

 Applicable Standards:
o UL, ULC, EN, BTL, AMEV.

PART 2: HARDWARE
Hardware Requirements: System Level DDC Controller

1. Processor and Storage:


o 32-bit Multi-tasking microprocessor (Texas Instruments AM335x, 300
MHz).
o Memory: 128 MB DDR3 SDRAM, 512 MB NAND Flash.
o Data retention: 7+ days
2. Power Supply:
o Operating voltage: 24V AC ±15% / ±20%.
3. Communication Ports:
o At least 2 RJ45 ports with the same BACnet IP communication function,
1 KNX PL-link port, 1 COM port
o Modbus RTU/IP integration.
4. WLAN Support:
o IEEE 802.11b/g/n compatible.
5. Ambient during operation
o Acceptable range of temperature from -5°C to 50°C
o Humidity 5% to 95% non-condensing
Functionality:

 Alarms and Scheduling: Integrated for operational processes


 Graphs and access protection
 Web-Based Monitoring: Cloud-based functionality and control remotely via
cloud
 BACnet/IP Communication: Capable of connecting to all network standards
BACnet on UDP/IP.

You might also like