Lightning Protection Calculation
Calculation for Evaluating Need for Protection - by BS6651 1. Collection Area, Ac (sqm) 1.1. Rectangle Building Lengthm Width m 50 14 1.2. Tower Radius m 10 Height m 30 Collection Area Ac sqm 5026.6 Formula: Ac=(H+R)2 Height m 15 Collection Area Ac (sqm 3326.9 Formula: Ac=LW+2LH+2WH+H2
1.3. Sloping Roof (Here pitch 45,if pitch <45,adopt 1.1) Collection Lengthm Height Area Ac m sqm Formula: Ac=H2+2LH 20 30 4027.4 2. Flash density, Ng (per/sqkm) Thunderstor m days per year Td 20 Note: adopt for north Africa 3. Risk of being struck, p 4. Overall risk factor Page 1/of 6 Flash density, Ng (per/sqkm) 1.10 3.7E-03
From Curve of Table 6
Formula: p=AcNg10-6
Lightning Protection Calculation
1 Risk of being struck, p A 2 3 4 5 6 7 8 Overall Overall risk multiplying factor (product factor of columns 1 (product of and 7) columns 2 to 6) 9 Recommendations
Use of structure (Table 8)
Weighting factors B C D Type of Contents or Degree of construction consequential isolation (Table 9) effects (Table 11) (Table 10) 0.4 0.3 1.0
E Type of country (Table 12)
3.7E-03
0.3
0.3
0.011
3.95E-05
protection recommended
Note: Risk less than 110-5 do not generally require protection; risk between 110-5 and 110-4 protection is recommended; risk greater than 110-4 require protection.
Page 2/of 6
Lightning Protection Calculation
Page 3/of 6
Lightning Protection Calculation
Page 4/of 6
Lightning Protection Calculation
Page 5/of 6
Lightning Protection Calculation
Note: This curve is made from Table 6 of BS 6651
Page 6/of 6