Educational Institute for Equipment and Process Design
2.PSV-1031
1.Determine the scenario, using API-521
Since it is R-1001 and exposed to fire then a fire scenario is defined
Parameters Value Parameters Value
Diameter 4.45 m M 16.54
Height 3.1 m Set Pressure 55 barg
Fluid Natural Gas Relieving Pressure 67.55 bara
Z 1.01 Accumulation 0.21
Cp/Cv 1.18 Material CS
2.Calculate the relief load, using API-520 Part1
Educational Institute for Equipment and Process Design
Educational Institute for Equipment and Process Design
Calculation
Parameters Value Parameters Value
Aw 65 m2 KD 0.975
C9 0.2772 116
C10 0.0395 Relief Load 3874 kg/hr
C 0.0254
Note : Relieving Temperature Calculation
since the ratio between operating pressure and PSV relieving pressure is very high, the relieving
temperature calculated is not consistent (it would exceed the maximum vessel wall temperature
for carbon steel, &o). The relieving temperature for PSV design has been assumed equal to 400°C
(considered the max allowable value for carbon steel). The actual relieving mass flow has been
calculated keeping the discharge capacity of the valve (volumetric flow rate) constant and scaling
the temperature down to 400°C.