Barjeel - HVAC Efficiency Compliance Tracker
Enter the number of different ACs 3
Note:
This document must be submitted for all project types except Individual Private Villas & Service Blocks
Result Summary
Compliant
Calculated Selected Unit @ T3 (Chillers @ T1)
Equipment Type Minimum Requirements as per Barjeel Requirements
Cooling Load
Minimum
Cooling
Minimum Cooling Minimum
Rated Energy Seasonal Integrated Minimum
Electric Power Coefficient of Energy Seasonal Integrated
Unit Reference Location Total Quantity Capacity (per Efficiency Performance Part Load Coefficient of Compliance
(per unit) Performance Efficiency Performance Part Load
Cooling System Type unit) Rating Factor (CSPF Value (IPLV) Performance
COP @ T3 Rating Factor (CSPF Value (IPLV)
EER @ T3 Btu/h/W) @ @ T3 (Chiller COP @ T3
(Chiller @ T1) EER @ T3 Btu/h/W) @ @ T3 (Chiller
(Chiller @ T1) T3 (Chiller @ @ T1) (Chiller @ T1)
kW No. kW kW (Chiller @ T1) T3 (Chiller @ @ T1)
T1)
T1)
GAC-1,2,3,4 SHOP-1,2,3,4 DX Decorative 5.6 4 9.38 3.8 8.42 2.47 8.31 2.44 NA NA Compliant
GAC-5 SHOP-5 DX Decorative 7.7 2 7.2 2.5 9.82 2.88 8.31 2.44 NA NA Compliant
GAC-6 ENTRANCE DX Decorative 4.5 1 4.77 1.1 14.79 4.34 8.31 2.44 NA NA Compliant
GAC-7,8 SERVICES DX Decorative 3 2 4.77 1.1 14.79 4.34 8.31 2.44 NA NA Compliant
GAC-9 WATCHMAN DX Decorative 2.6 1 9.38 3.8 8.42 2.47 8.31 2.44 NA NA Compliant
FAC-1…..,9 STUDIOS DX Decorative 5.1 9 7.2 2.5 9.82 2.88 8.31 2.44 NA NA Compliant
FAC-10 STUDIO-10 DX Decorative 7.6 1 9.38 3.8 8.42 2.47 8.31 2.44 NA NA Compliant
RAC-01,02 ROOF DX Decorative 3.5 3 4.77 1.1 14.79 4.34 8.31 2.44 NA NA Compliant