Pressuretrol® Controllers
PRODUCT DATA
APPLICATION
L404 Pressuretrol® Controllers are line voltage pressure
controllers that provide operating control, automatic limit
protection, or manual reset limit protection for pressure
systems of up to 300 psi (21.1 kg/cm2 or 2068 kPa).
FEATURES
• Can be used with steam, air, non-combustible gases,
or fluids non-corrosive to the pressure sensing
element.
• Stainless steel diaphragm (except 300 psi [21.1 kg/cm2;
2068 kPa] models) also allows use with ammonia,
oxygen, distilled water and similar media.
• L404B is recommended for supervision of atomizing
medium pressure in oil burner systems.
• Dustproof, trouble-free mercury switches.
• Automatic reset models have adjustable, subtractive
differential (except L404A1651).
• Screw adjustments made on top of case.
• Scaleplates marked in Metric (kg/cm2) and English
(psi) units.
• Clear plastic cover on case to observe pressure
settings and switch action.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Setting and Checkout ....................................................... 6
Service Information .......................................................... 8
SPECIFICATIONS
IMPORTANT Mounting: Hexagonal fitting on diaphragm has 1/4-18 NPT
The specifications given in this publication do not internal threads for mounting on a pipe or steam trap
include normal manufacturing tolerances. Therefore, (siphon loop). Also can be surface-mounted using
this unit may not match the listed specifications screws through two holes (knockouts) in back of case.
exactly. Also, this product is tested and calibrated
under closely controlled conditions, and some minor Dimensions: See Fig. 1. See Fig. 2 for mounting steam trap
differences in performance can be expected if those (siphon loop).
conditions are changed.
Weight: 2 lb. (0.91 kg).
Models: L404A and B Pressuretrol® Controllers. See Table 1.
Finish: Gray.
NOTE: A 14026 Steam Trap (siphon loop) is available,
except where noted in Table 1. The steam trap is Approvals:
necessary for boiler installations. Underwriters Laboratories Inc. Listed (L404A,B,C,D,F;
L604A,L only); file no. MP466, vol. 10, guide no. MBPR.
Switches: Mercury switches in all models. Canadian Standards Association certified (L404A,B,C,D,F;
L604A,L only); file no. LR1620; guide no. 400-E-0.
Pressure Sensing Element: Stainless steel diaphragm
(brass bellows in 300 psi [21.1 kg/cm2 (2068 kPa)] Replacement Parts:
models). 129178 Thermoplastic Cover.
14026 Steam Trap (siphon loop)—1/4 in. black iron pipe;
Ambient Temperature Range: -35°F (-37°C) to +150°F necessary for boiler installations.
(66°C).
Accessories:
NOTE: Also, see the NOTE in the Location and Mounting 33312B Knurled Adjustment Knob—with setscrew; fits on
section. main scale pressure adjusting screw.
4074BWJ Limit Stop Assembly—to limit setpoint ranges;
Adjustment Means: Screws on top of controller case. Scales includes 129564 Range Stop, 107194 Range Stop Screw,
are marked in psi and kg/cm2. and 23466 Wrench.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
95C-10187B—1 2
L404A,B PRESSURETROL® CONTROLLERS
20 to 300c 1.4 to 21.0 138 to 2068 15 to 40 1.04 to 2.76 103 to 276 500 35.2 3445
L404Bd spst, makes 2 to 15b .14 to 1.1 14 to 103 2 to 6 0.14 to 0.41 14 to 41 50 3.5 345
circuit
5 to 50 .35 to 3.5 24 to 345 4 to 12 0.28 to 0.82 27 to 83 85 6.0 586
10 to 150 .66 to 10.6 69 to 1034 8 to 16 0.56 to 1.10 55 to 110 225 15.8 1550
20 to 300c 1.4 to 21.0 138 to 2068 15 to 40 1.04 to 2.76 103 to 276 500 35.2 3445
a
Scaleplates are marked in both psi and kg/cm2.
b
L404A,B models are available with 1 to 6 psi midscale subtractive differential in 2 to 15 psi models.
c Brass bellows replace stainless steel diaphragm. Not suitable for use with ammonia, oxygen, or other corrosive materials.
dAlso recommended for supervision of atomizing medium pressure (air or steam) in an oil burner system.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old control
in the trash. Dispose of properly. This control also
contains mercury in a sealed tube. It must also be
disposed of properly when it is replaced.
3 95C-10187B—1
L404A,B PRESSURETROL® CONTROLLERS
L404A,B
4-1/2 (114.3) (COVER)
2-3/4 (69.9)
4-11/32 (110.3) (CASE)
1-1/16
(27.0)
1-15/16 (49.2) 1-61/64 (49.6)
13/16
3-3/16 (81.0) 1/2 (12.7)
1 (20.6)
1-5/32
(29.4)
1
3-7/8 3-23/32
(98.4) (94.5)
4-31/32
(126.2)
1-13/16
(46.0)
13/16
(20.6)
7/8
3/16 (4.8) X 21/64 (8.3) (22.2) DIA.
KNOCKOUT (2)
1-1/16
2-1/8 (54.0) 1/4-18 NPT (27.0)
1-3/16 (30.2)
1-1/2 (38.1)
1 RESET LEVER (ON MANUAL RESET MODELS ONLY.)
M19534
INSTALLATION
CAUTION
Equipment Damage Hazard.
When Installing This Product… Improper use with a compressor can damage the
1. Read these instructions carefully. Failure to follow them controller.
could damage the product or cause a hazardous When using the controller with a compressor, install a
condition. dampening device (such as a needle valve, header, or
2. Check the ratings given in the instructions and on the surge tank) to dampen pulsations that can damage the
product to make sure the product is suitable for your controller or reduce its life.
application.
3. Installer must be a trained, experienced, flame IMPORTANT
safeguard control technician. 1. Locate the controller where the ambient temperature
4. After installation is complete, check out product will not exceed 150°F (66°C).
operation as provided in these instructions. 2. Use pipe compound sparingly to avoid clogging the
hole in the pipe or diaphragm fitting.
3. Do not tighten the controller by hand by holding the
WARNING case.
4. Accurately level the controller for proper operation.
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before beginning
installation to prevent electrical shock or possible
equipment damage.
95C-10187B—1 4
L404A,B PRESSURETROL® CONTROLLERS
5 95C-10187B—1
L404A,B PRESSURETROL® CONTROLLERS
wire suitable for at lease 167°F (75°C) when you are 24 VOLT POWER
SUPPLY
1
THERMOSTAT
using the controller with a flame safeguard primary 2 L2
control, or at least 194°F (90°C) when using it with a
programming control.
3. For high temperature installations, use
moisture-resistant No. 14 wire, selected for a THERM
temperature rating above the maximum operating
temperature.
4. All models have a terminal block inside the cover (see
Fig. 3) and a 7/8 in. (22 mm) hole in one side for 1/2 in. LOAD
L404A L404B
MAIN SCALE SETPOINT
BREAKS ON MAKES ON (SWITCH BREAKS)
PRESSURE RISE PRESSURE RISE
TO SETPOINT TO SETPOINT
L404A SUBTRACTIVE
DIFFERENTIAL
PRESSURE
M19535 RISE
DIFFERENTIAL SETTING
(SWITCH MAKES)
Fig. 3. L404 terminal blocks and internal schematics.
MAIN SCALE SETPOINT
(SWITCH MAKES)
SPST
L404B SUBTRACTIVE
DIFFERENTIAL
CONTROLLER PRESSURE
RISE
DIFFERENTIAL SETTING
2
L1 (SWITCH BREAKS)
FLAME
(HOT)
SAFEGUARD M19537
POWER CONTROL,
1 MOTOR, OR
SUPPLY
L2
OTHER LOAD Fig. 6. L404 operating points.
L2
Adjust the main scale set point for the desired operating
pressure by turning the main scale adjusting screw (Fig. 7) on
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION the top of the case until the main scale setting indicator is at
AS REQUIRED. the desired value. On an L404A (except the L404A1651,
2 HIGH LIMIT—L404A BREAKS WHEN PRESSURE RISES which has a fixed differential) or L404B, adjust the differential
TO SETPOINT. setting by turning the differential adjusting screw (Fig. 7) until
LOW LIMIT—L404B BREAKS WHEN PRESSURE FALLS TO SETPOINT
MINUS DIFFERENTIAL.
the differential setting indicator is at the desired value. The
OPERATING CONTROLLER—L404A BREAKS WHEN PRESSURE RISES scaleplates are marked psi and kg/cm2.
TO SETPOINT, AND MAKES AGAIN WHEN PRESSURE FALLS TO
SETPOINT MINUS DIFFERENTIAL.
M19536
95C-10187B—1 6
L404A,B PRESSURETROL® CONTROLLERS
DIFFERENTIAL PSI
SETTING
INDICATOR
If a Controller Seems to Operate Improperly
If the controller is suspected of operating improperly, it may be
further checked as follows (Fig. 8):
MAIN SCALE
SETTING
INDEX 1. Disconnect all power to the controller, loosen the cover
INDICATOR
MARK screw, and remove the cover.
POINTER
2. Disconnect the wires from the controller.
DIAPHRAGM
ASSEMBLY
LEVELING 3. Connect an ohmmeter between the switch terminals.
INDICATOR 4. Lower the set point of the controller (simulating a
1 ADJUSTABLE DIFFERENTIAL ON THE L404A,B WITH A 5 TO pressure increase) through a range greater than the
150 PSI (0.34 TO 10.3 kg/cm2 [34 TO 134 kPa] OPERATING RANGE.
M19538
differential. The switch should either make or break,
depending on the model of the controller. (An L404A
should break, an L404B should make.) If it makes, the
Fig. 7. Setting a Pressuretrol® Controller. ohmmeter reads zero; if it breaks, the ohmmeter reads
infinity.
5. Raise the set point of the controller (simulating a
Checkout pressure decrease) through a range greater than the
After the controller has is installed, wired, and set, test it with differential. The switch should break or make, just the
the system in operation. First allow the system to stabilize. opposite of its action in step 4.
Then observe the operation of the controller while raising and 6. An approximation of the differential can be made by
lowering its setpoint. Pressure should increase when the observing the change in set point required for a
setpoint is raised and decrease when the set point is lowered. resistance change from zero to infinity.
7. If the controller operates improperly, replace it.
Also check the make and break points of the controller. If they 8. When the controller is operating properly, reconnect the
do not agree with a separate, accurately calibrated pressure wires to the terminal block, replace the cover and
gauge, a slight adjustment of the scaleplate(s) may be tighten the cover screw, and reconnect the power.
necessary.
7 95C-10187B—1
L404A,B PRESSURETROL® CONTROLLERS
SERVICE INFORMATION
OHMMETER
Calibration
OUTPUT
SETPOINT The controller was carefully calibrated during manufacturing
INPUT
DECREASE and should not require recalibration. Most calibration errors
are caused by improper leveling. The controller should be
0 level when the pointer on the leveling indicator is directly over
W B the index mark (Fig. 7). In some cases, the leveling indicator
may not be accurate enough. The pointer may be over the
index mark, but the controller still may not be operating within
1
R the tolerance of its scale setting. In this case, carefully bend
ZERO
the steam trap (siphon loop) until the controller switches
ADJ properly.
ZERO OHMS
(INFINITY WHEN R-B BREAKS) Maintenance
1 AN L404A, B HAS ONLY TWO TERMINALS (SPST SWITCHING); The cover of the controller should be in place at all times to
AN L404A R C BREAKS AND L404B MAKES WHEN THE SETPOINT IS protect the internal components from dirt, dust, and physical
DECREASED FAR ENOUGH.
damage. Routine maintenance should consist of occasional
M19539
inspection and blowing or brushing away any accumulated dirt
and dust. To ensure proper functioning of the controller at all
Fig. 8. Checking controller operation times, perform an operational check of the entire system
using an ohmmeter. during routine maintenance checks.
APPLICATION
Les régulateurs Pressuretrol L404 tension secteur servent
de dispositif de commande et de limiteur automatique ou à
réarmement manuel dans les systèmes dont la pression peut
atteindre 21, 1 kg/cm2 (300 psi ou 2068 kPa).
CARACTÉRISTIQUES
• Peuvent être utilisés avec de la vapeur, de l'air, des gaz
non combustibles ou avec tout fluide qui ne risque pas
de corroder l'élément sensible.
• Membrane en acier inoxydable (sauf sur les modèles
21,1 kg/cm2 [300 psi ou 2068 kPa]) permettant
également leur utilisation avec de l'ammoniac, de
l'oxygène, de l'eau distillée et d'autres fluides
semblables.
• Le modèle L404B est recommandé pour la surveillance
de la pression d’un agent de pulvérisation dans les
systèmes munis d'un brûleur à mazout.
• Interrupteurs à mercure fiables et antipoussière.
• Différentiel soustractif réglable sur les modèles à
réarmement automatique (sauf sur le modèle
L404A1651).
• Des vis sur le dessus du boîtier permettent d’effecuer
les réglages.
• Échelles de mesure métrique (kg/cm2) et anglaise (psi).
FICHE TECHNIQUE
IMPORTANT Montage : Le raccord hexagonal sur la membrane a un file-
Les caractéristiques énoncées dans la présente tage intérieur de 1/4-18 NPT permettant le montage sur un
notice technique n’englobent pas les tolérances conduit ou un purgeur (siphon). Peut également être
normales de fabrication. Par conséquent, les monté en saillie au moyen de vis dans les deux alvéoles
caractéristiques de l'appareil peuvent ne pas (entrées défonçables) à l'arrière du boîtier.
correspondre exactement à celles mentionnées.
De plus, ce produit est vérifié et étalonné dans des Dimensions : Voir la Fig. 1. Voir également la Fig. 2 pour
conditions étroitement contrôlées qui, modifiées, celles du purgeur (siphon).
peuvent entraîner de légères différences de
rendement. Poids : 0,91 kg (2 lb).
POUR COMMANDER
Au moment d'acheter des produits de modernisation ou de remplacement auprès de votre grossiste ou distributeur
TRADELINE, consulter le catalogue TRADELINE ou les tarifs pour obtenir le numéro de pièce.
Prière d'adresser toute question supplémentaire, demande d'information ou tout commentaires sur les produits et services par
écrit ou par téléphone :
1. Au bureau de vente local des produits de régulation et d’automatisation Honeywell (consulter les pages blanches de l'annuaire
téléphonique).
2. Au Centre des services à la clientèle: 1885 Douglas Drive North, Minneapolis, Minnesota 55422-4386
Au Canada : Honeywell Limited-Honeywell Limitée, 35 Dynamic Dr., Scarborough, Ontario, M1V 4Z9
Points de vente et de service dans toutes les grandes villes du monde. Usines en Allemagne, en Australie, au Canada, en
Espagne, aux États-Unis, en Finlande, en France, au Japon, au Mexique, aux Pays-Bas, au Royaume-Uni et à Taiwan.
95C-10187B—1 2
RÉGULATEURS PRESSURETROL® L404A ET B
3 95C-10187B—1
RÉGULATEURS PRESSURETROL® L404A ET B
L404A,B
98,4 94,5
(3-7/8) (3-23/32)
126,2
(4-31/32)
46,0
(1-13/16)
20,6
(13/16)
22,2
4,8 (3/16) X 8,3 (21/64) (7/8) DIA.
ENTRÉES DÉFONÇABLES (2)
27,0
54,0 (2-1/8) 1/4-18 NPT (1-1/16)
30,2 (1-3/16)
38,1 (1-1/2)
1 LEVIER DE RÉARMEMENT (SUR LES MODÈLES À RÉARMEMENT MANUEL SEULEMENT.)
MF19534
95C-10187B—1 4
RÉGULATEURS PRESSURETROL® L404A ET B
a. à côté du manomètre,
b. dans un raccord sur la chaudière fourni par le
Avant d'installer ce produit… fabricant,
1. Lire attentivement les présentes instructions. Le fait de c. à un endroit assez éloigné (en cas de vibrations
ne pas les suivre pourrait constituer un danger ou excessives),
endommager le produit. d. dans un montage spécial sur un régulateur de
2. Vérifier les caractéristiques nominales spécifiées dans sécurité de bas niveau.
les instructions et celles indiquées sur le produit pour
s'assurer que celui-ci convient à l'usage prévu. MANOMÈTRE
3. L'installateur doit être un technicien spécialisé dans les RÉGULATEUR
dispositifs de commande et de sécurité ayant reçu une DE PRESSION
formation pertinente.
4. Une fois l'installation terminée, vérifier le fonctionne-
ment du produit en suivant les présentes instructions.
RACCORD
AVERTISSEMENT
EN T
CHAUDIÈRE CHAUDIÈRE
MISE EN GARDE
Risque de dommages à l'équipement.
1 CONDUIT DE FER NOIR DE 1/4 PO AVEC FILETAGE EXTÉRIEUR
Un mauvais usage dans une application avec DE 1/4-18NPT AUX EXTRÉMITÉS. PLIER LE PURGEUR (SIPHON)
compresseur pourrait endommager le régulateur. POUR METTRE LE RÉGULATEUR DE NIVEAU.
MF8934A
Lorsque le régulateur est utilisé avec un compresseur,
installer un amortisseur (p. ex. un robinet à pointeau, Fig. 2. Bon et mauvais montage d'un purgeur (siphon),
un collecteur ou un séparateur à liquide) afin avec dimensions approximatives en mm (po).
d'atténuer les oscillations susceptibles de
l'endommager ou d'en réduire la durée de vie. Raccorder les tuyaux selon les normes en vigueur. N'utiliser
qu'une petite quantité de pâte pour étancher les joints. Une
IMPORTANT utilisation excessive de ce produit risque de boucher le petit
1. Placer le régulateur à un endroit où la température trou du raccord et d'empêcher le régulateur de fonctionner
ambiante n'excède pas 66 °C (150 °F). correctement.
2. Utiliser la pâte pour joints de tuyauterie avec
modération pour ne pas boucher les tuyaux et le Pour éviter les fuites et les dommages au boîtier, utiliser une
raccord de la membrane. clé à mâchoire parallèle pour le raccord hexagonal du
3. Ne pas tenir le régulateur par le boîtier pour le serrer. régulateur. Ne pas serrer en tenant le régulateur par le
4. Le régulateur doit être de niveau pour bien boîtier.
fonctionner.
Niveau
Emplacement et montage Un régulateur doté d'un interrupteur à mercure doit être mis
de niveau de façon précise pour bien fonctionner. Pour ce
REMARQUE : Aux endroits où la température descend à faire, plier le purgeur (siphon) avec soin. Lorsque l'indicateur
moins de -29 °C (-20 °F), installer des de niveau (Fig. 7) pend librement et que sa pointe est juste
générateurs de chaleur d'appoint pour assurer au-dessus de l'index au fond du boîtier, le régulateur est de
un fonctionnement précis du régulateur. Ne niveau.
jamais installer ce dernier à des endroits où la
température tombe à moins de -37 °C (-35 °F), Montage à côté du manomètre
car le mercure de l'interrupteur gèlerait.
Pour monter le régulateur à côté du manomètre (Fig. 2),
enlever le manomètre et le remplacer par un purgeur (siphon)
Lorsqu'il est utilisé avec une chaudière à vapeur, le régulateur
surmonté d'un raccord en T. Monter le régulateur et le
doit toujours être monté au dessus du niveau d'eau. Pour
manomètre aux extrémités du raccord au moyen des coudes
prévenir l'entartrage de la chaudière et la corrosion de la
et des mamelons. Mettre le régulateur de niveau après
membrane, toujours installer un purgeur (siphon) entre le
l'installation.
régulateur et la chaudière (Fig. 2). La boucle du purgeur doit
toujours être perpendiculaire au devant du régulateur, sinon
sa dilatation ou sa contraction fera pencher le régulateur et
diminuera la précision de l'interrupteur.
5 95C-10187B—1
RÉGULATEURS PRESSURETROL® L404A ET B
Montage sur chaudière 6. S'assurer que les charges n'excèdent pas les
Si le régulateur ne peut être monté à côté du manomètre, caractéristiques nominales des contacts énumérées à
installer un purgeur (siphon) dans le raccord fourni par le la section FICHE TECHNIQUE.
fabricant de la chaudière. S'il n'y a pas de raccord, monter le 7. Remettre le couvercle en place après le câblage.
purgeur à l'endroit recommandé par le fabricant de la
chaudière. Visser le régulateur directement sur le purgeur et
HAUSSE HAUSSE
le mettre de niveau.
Montage à distance
Lorsque des vibrations trop fortes à la chaudière risquent
d'altérer le fonctionnement du régulateur, celui-ci doit être
monté à distance. Toute la tuyauterie provenant de la
chaudière doit être adéquate et montée solidement. Elle doit
être également assez inclinée pour ramener toute l'eau de
condensation à la chaudière. Un purgeur (siphon) doit être L404A L404B
monté entre le régulateur et le conduit. Mettre le régulateur OUVERTURE SUR FERMETURE SUR
de niveau après l'installation. HAUSSE DE PRESSION HAUSSE DE PRESSION
AU POINT DE CONSIGNE AU POINT DE CONSIGNE
95C-10187B—1 6
RÉGULATEURS PRESSURETROL® L404A ET B
illustrés à la Fig. 6. 12
10
.8
.7
3
2.5
40
8 .6 2 30
.5
6 .4 1.5 20
4 .3 1
.2 10
2 .1 .5
0 0
POINT DE CONSIGNE DE PSI
L'ÉCHELLE PRINCIPALE INDICATEUR
(OUVERTURE) DE RÉGLAGE
DU DIFFÉRENTIEL
L404A DIFFÉRENTIEL
SOUSTRACTIF
HAUSSE DE
PRESSION INDICATEUR
RÉGLAGE DU DIFFÉRENTIEL
DE RÉGLAGE
(FERMETURE) INDEX
DE L'ÉCHELLE
POINT DE CONSIGNE DE PRINCIPALE
POINTE
L'ÉCHELLE PRINCIPALE
(FERMETURE)
MEMBRANE INDICATEUR
DIFFÉRENTIEL DE NIVEAU
L404B
SOUSTRACTIF 1 DIFFÉRENTIEL RÉGLABLE SUR LE L404A ET B AVEC ÉCHELLE DE
HAUSSE DE
PRESSION 0,34 À 10,3 KG/CM2 (5 À 150 PSI) [ 34 TO 134 kPa].
RÉGLAGE DU DIFFÉRENTIEL MF19538
(OUVERTURE)
MF19537
7 95C-10187B—1
RÉGULATEURS PRESSURETROL® L404A ET B
OHMMÈTRE
SORTIE
ABAISSEMENT DU
ENTRÉE
POINT DE CONSIGNE
0
W B
1
R