Air Cool
Air Cool
ME-31017
REFRIGERATION AND AIR CONDITIONING I
SEMESTER – I
BY
DR. SU THET MON THAN
ASSOCIATED PROFESSOR
CONTENTS
Chapter Title Page No
1 INTRODUCTION 1
It was in 1834 when an American Engineer, Jacob Perkins introduced the first patent
for a practical ice-making machine in London. These machines were used successfully in
meat-packing plants. Within the next fifty years, ice-makers were manufactured in the United
States, France, Germany, and in other countries. Nowadays, Refrigeration is not only put in
use for the preservation of foods. It is likewise used in chemicals, metals, medicines, gases,
machines, tools and electronic devices.
TH Hot Reservoir
(Heat source)
QH
Heat Engine
Wnet(net work output)
QL
Cold Reservoir
TL
(Heat sink)
Figure 1.2 Work and heat transfer for a heat engine
3
Net Work
Thermal efficiency
Heat supplied
Wnet QH QL Q
th 1 L
QH QH QH
QL
th 1
QH
If all the processes making up the above cycle are reversible, and the heat is
transferred in and out of the cycle reversibly, then the heat engine is a reversible heat engine.
If this reversible heat engine runs backward so that work is input to the cycle and heat
is rejected at the high temperature, that we have a heat pump or a refrigerator.
This occurs inside a pipe or coil of tubing, positioned so that the latent heat required
can be extracted from the space to be cooled.
Hot Reservoir
TH
(Heat source)
QH
TH
Refrigerator
TL
QL = (desired output)
Cold Reservoir
TL
(Heat sink)
(COP)ref = = = =
The same machine could be used for heating. Thus, it will remove heat from a low
temperature ‘source’ at TL, and along with the work W will supply heat Q2 at higher
temperature TH for heating purposes. In this case the machine is termed as heat pump.
Hot Reservoir
TH
(Heat source)
Heat Pump
QL
Cold Reservoir
TL
(Heat sink)
(COP)heat pump = =
= =
It can be seen that the COP of the heat pump is related to the COP of a refrigerator as
below:
(COP)heat pump = = =
= (COP)ref + 1
5
Coefficient of heat pump, (COP)heat pump, is also termed as Energy Performance Ratio,
EPR.
It is evident from the expression for COP that higher the temperature of heat removal,
TL, or lower the temperature of heat rejection, TH , higher will be the COP of the reversed
Carnot cycle working as a refrigerator or as a heat pump.
Example (1.1)
For a refrigerating machine of a heat pump, the ratio of TL to TH is 4:5. If the work done on
the cycle is 32 kW, determine the maximum heating effect. If the cycle is used as a heat
engine, determine the engine efficiency and heat rejected.
Solution:
TH
HP W input
TL
6
TL/TH = 4/5
TL = 0.8 TH
Maximum Heating Effect of Heat Pump = ?
COPHP = QH/ Wnet
COP = TH/ (TH - TL)
=5
QH = COPHP x Wnet = 5 x 32 = 160 kW
Maximum heating effect of heat pump = 160 kW
HE W output
TL
ɳ = Woutput/Qinput
Taking control volume, QH = Wnet + QL
Wnet = QH - QL
Since Q = ʃ Tds
ɳ engine = (TH - TL)/TH
= 1- TL / TH
= 1 – 4/5 = 0.2
7
Tutorial Sheet 1
1. A refrigerator driven by a 0.7457 kW meter removes 21 kJ/min from a cold body. What is
the COP of this refrigeration? At what rate is heat rejected to the hot body?
2. A refrigerator remove an amount of heat equivalent to 1014720 kg of ice/day (latent heat
of fusion of ice is taken as 334 kJ/kg) The COP of this refrigerator is 4. What is the (hp) of
the prime mover driving this refrigerator?
3. Using an engine of 30% thermal efficiency to drive a refrigerator having a COP of 5. What
is the heat input into the engine for each kJ removed from the cold body by the refrigerator?
4. If a refrigerator is used for heating in winter so that the atmospheric becomes the cold body
and the room to be heated becomes the hot body, how much heat would be available for
heating for each kilowatt input into the driving motor? The COP of the refrigerator is 5, and
the electro-mechanical efficiency of the motor is 90%. How dose compare with resistance
heating.
5. A Carnot refrigerator rejects 2500 kJ of heat at 80ºC while using 1100 kJ of work. Find (a)
the cycle low temperature (b) COP (c) Amount of heat absorbed.
6. A Carnot refrigerator operates between temperature limits of -5ºC and 30ºC. The power
consumed is 4 kW and the heat absorbed is 30 kJ/kg. Determine (a) COP (b) Refrigerant flow
rate.
7. A Carnot engine has a thermal efficiency of 25% as a power engine. It is reversed and does
950 kJ/min of refrigeration. Determine: (a) The work and COP
(b) If this system is used for heating. What is the amount of heat delivered and the COP for
heating? Is more work required than (a)?
(c) What is the difference if the heat is added to the system at 4ºC? or at -50ºC
8. Two reversible engines operate in series between a high temperature (TH) and a low
temperature (TC) reservoir. Engine A rejects heat to engine B which in turn rejects heat to the
low temperature reservoir. The high temperature reservoir supplies heat to engine A. Let
TH=1000 K, TC=400 K and the engine thermal efficiency are equal. The heat receives by
engine A is 500 kJ. Determine:
(a) temperature of heat rejection by engine A
(b) work or engine A and B
(c) heat rejected by engine B
9. A carnot refrigerator requires 1.3 kW per tonne of refrigeration to maintain a region at low
temperature of -38 ºC. Determine:
(i) COP of Carnot refrigerator
(ii) Higher temperature of the cycle
8
(iii) The heat delivered and COP when this device is used as heat pump.
Assume 1 tonne of refrigeration = 14000 kJ/hr.
10. A machine works on reversed Carnot cycle between -10 ºC and 24ºC. Find its COP when
working as a (i) heat engine, (ii) refrigerator, (iii) heat pump.
9
CHAPTER 2
VAPOUR COMPRESSION SYSTEM
Absolute
Pressure,
P(Mpa)
Saturated
liquid Saturated vapour
curve curve
Specific Enthalpy,
h(kJ/kg)
This represents the change in phase of the refrigerant between the two saturation lines,
the refrigerant is in the form of a liquid-vapor mixture.
The distance between the two saturations lines along the any constant pressure line, as
read on the enthalpy scale at the bottom of the chart, is the latent heat of vaporization of the
refrigerant at that pressure (hfg). On the chart the change in phase from liquid to vapor phase
takes place progressively from left to right, whereas the change in liquid line, the liquid vapor
mixture is primarily liquid, whereas close to the saturated vapor line, the liquid vapor mixture
is primarily vapor.
The nature of curves for saturated liquid and saturated vapor is dependent on how the
latent heat of vaporization varies with pressure. Both these curves will finally meet tat ta
point and the pressure corresponding to that point is the critical pressure at which liquid
changes to superheated vapor and the latent heat of vaporization is zero.
The lines of constant quality, extending from top to bottom through the center section
of the chart and approximately parallel to the saturated liquid and vapor lines, indicate the
percentage of vapor in the liquid vapor mixture. i.e. The dryness fraction.
For example, at any point along the constant quality line closet to the saturated liquid
line, the quality of the liquid vapor is 10%, (dryness fraction = 0.1) the indicated quality of
the mixture at any point along the constant quality line closet to the saturated vapor line is
90% and the dryness fraction is 0.9. The horizontal lines extending across the chart are lines
of constant pressure and the vertical lines are lined of constant enthalpy.
In the sub cooled region, the constant temperatures lines are nearly vertical and
parallel to the constant enthalpy lines. In the central region, bounded by the saturated liquid
and saturated vapor line, the temperature line is horizontal and parallel to constant pressure
lines, because the refrigerant changes its phase from liquid to vapor at constant pressure and
temperature.
In the superheat region, the temperature lines again change direction and fall sharply
to the bottom of the chart. The lines, very nearly straight, extending diagonally and almost
vertically across the super heated vapor region are constant entropy lines.
In this cycle liquid refrigerant is introduced into an evaporator where it absorbs heat
and boils (evaporates) until it reaches a saturated vapor state. The latent heat, which it
absorbs, causes a cooling effect on its surroundings.
Vapor then passes through the compressor where it is being compressed to a higher
temperature and pressure before entering the condenser, where it is cooled and liquefied. To
complete the cycle the high pressure liquid passes through an expansion valve and returns to
the evaporator at low pressure.
12
called 1 ton machine. It may be noted that 1 ton refrigerating plant will not produce 1 ton ice,
or the quantity in the evaporator that determines the rating.
1 ton of refrigeration = 12000 BTU/hr
= 200 BTU/min
= 50 kcal/min
= 211 kJ/min
= 3.41 kW
2.5 Actual Vapour Compression Refrigeration Cycle
For thermodynamic analysis of the refrigeration systems, we consider the ideal
behaviour of the fluid and neglect any extraneous factors. In actual practice however, these
factors have significant effect on the COP and refrigerating effect of the refrigeration cycle.
In this section, we go for a detailed analysis of these external factors and their influence on
the overall system performance.
The actual vapor compression cycle is shown in Figure 2.3. With the help of a T-s
diagram for the operating pressure limits p1 and p2. The actual compression follows 1 – 2′
instead causing considerable difference due to the irreversibilities associated with the
compression process 1 – 2.
3 2
1
4
clearance V
Effective swept volume
Total volume
ɳ cv = =
ɳ cv = 1 + C – C (Pd/Ps)1/n
ɳv=
3 2' 2
P cond
S1 = S2
P evap 4 1
W1-2/kg = h2 – h1 (Compressor)
Q2-3/kg = h2 – h3 (Condenser)
h3 = h4 = hwet = hf + x hfg = hf + x(hg – hf )
Q4-1 /kg = h1 – h4
3 2' 2
P cond
S1 = S2
P evap 4 1
P cond
3 2
S1 = S2
P evap 4 1
h2 = hg (condenser)
h3 = h4 = hf (evaporator)
h4 = hwet
s2 = s1 = swet = sf + x sfg
= sf + x (sg – sf)
h1 = hwet = hf + x hfg
x= dryness fraction or quality
3 2' 2
S1 = S2
superheat
P evap 4 1' 1
3 3' 2' 2
P cond
S1 = S2
P evap 4 1
Example 2.1
In a vapour compression refrigeration system using R-12, the evaporator pressure is 1.4 bar
and the condenser pressure is 8 bar. The refrigerant leaves the condenser subcooled to 30ºC.
The vapour leaving the evaporator is dry and saturated. The compression process is
isentropic. The amount of heat rejected in the condenser is 13417 kJ/min. Determine
refrigerating effect (kJ/kg), refrigeration load (tons), compressor power input (kW) and COP.
Show the cycle on a p-h diagram.
Solution:
3 2
P cond
S1 = S2
P evap 4 1
h
19
= = = 90.65 kJ/min
-
-
(iv) COP = = = = 3.35 (Ans)
-
Example 2.2
A simple refrigerant 134a (tetrafluroethane) heat pump for space heating, operates between
temperature limits of 15 and 50ºC. The heat required to be pumped is 100 MJ/h. Determine:
(i) The dryness fraction of refrigerant entering the evaporator;
(ii) The discharge temperature assuming the specific heat of vapour as 0.996 kJ/(kg)(K);
(iii) The theoretical piston displacement of the compressor;
(iv) The theoretical power of the compressor
The specific volume of refrigerant 134a saturated vapour at 15ºc is 0.04185 m3/kg.
The other relevant properties of R-134a are given below:
Solution:
20
21
Tutorial Sheet 2
1. A refrigerator uses refrigerant R12 as the working fluid and operates on an ideal vapour-
compression cycle between 0.14 and 0.8 MPa. If the mass flow rate of the refrigerant is 0.05
kg/s, determine (i) the rate of heat removal from the refrigerated space and the power input to
the compressor, (ii) the heat rejection rate to the environment and (iii) the COP of the
refrigerator.
2. A vapor compression refrigeration plant use ammonia and has the pressure limits of 2 bar
and 8 bar. The evaporator outlet temperature is 7ºC. Compression is polytropic with n= 1.2
and compressor has 2% clearance. The mass flow rate of refrigerant is 8.6 kg/min. determine
the refrigerating effect (tons) and volumetric efficiency of the compressor. If this
refrigeration plants is used as a heat pump, determine its COP.
3. In a vapour compression refrigeration system using R-12, the evaporator pressure is 1.4 bar
and the condenser pressure is 8 bar. The refrigerant leaves the condenser subcooled to 30ºC.
The vapour leaving the evaporator is dry and saturated. The compression process is
isentropic. The amount of heat rejected in the condenser is 13417 kJ/min. Determine
refrigerating effect (kJ/kg), refrigeration load (tons), compressor power input (kW) and COP.
Show the cycle on a p-h diagram.
4. A vapour compression system works on a simple saturation cycle with F12 as the
refrigerant while operates between condenser temperature of 40ºC and an evaporator
temperature of -5ºC. For the modified cycle the evaporator temperature is changed to -10ºC,
and other operating conditions are the same as the original cycle. Compare the power
requirements for both cycles. Both systems develops 15 tons of refrigeration.
5. In a small locally- produced paper factory, the heating requirements amount to a total of 6
KW. It is desired to provide this heat from an existing ice plant which was a Freon- 12 vapor-
compression refrigeration system. You are required to determine:
(a) Size of the compressor required
(b) Power of compressor required.
The following design specifications are to be assumed:
Single acting, single cylinder, air-cooled reciprocating compressor speed 500 rpm.
- stroke/ bore ratio is 1.25
- clearance 2%
22
6. A vapor compression refrigeration uses methyl chloride and operates between the pressure
limit of 214 KN/m2 and 852 KN/m2. The compressor which is single acting has a bore of 100
mm and a stroke 125mm. It runs at 5 rev/sec and has a volumetric efficiency of 80%. At the
commencement of isentropic compression, the refrigerant is dry saturated and after
compression it has a temperature of 85ºC. In the condenser, the refrigerant is condensed but
no under cooled. Determine,
(a) The coefficient of performance
(b) The mass of refrigerant
(c) The refrigerant effect
(d) The power of the compressor
The relevant properties of methyl chloride as follows:
7. A vapor compression refrigeration uses methyl chloride. The low pressure suction has a
pressure of 177 KN/m2 and the high pressure section has a pressure of 567 KN/m2. The
compressor is single acting and rates at 240 rev/min. it has two cylinder each of 60 mm bore
and 75 mm stroke. Each cylinder has a volumetric efficiency of 75%. Leaving the
compressor, this refrigerant is dry saturated and its leaves the condenser under cooked by
23
5ºC. Assuming the compression is isentropic and the expension is constant enthalpy.
Determine
(a) the dryness fraction of the refrigerant entering the compressor
(b) The coefficient of performance
(c) ) the mass flow of the refrigerant in kg/min.
The relevant properties of methyl chloride as follows:
CHAPTER 3
REFRIGERATION EQUIPMENTS
3.2 Evaporators
The evaporator in the vapor compression cycle is a heat exchanger which absorbs
heat from the substance to be cooled and transfers it to boiling refrigerant.
3.2.1 Types of Evaporators
Evaporators are also classified as flooded type and Dry type depending upon whether
liquid refrigerant covers all heat transfer surfaces or some portion is having gas being
superheated. The evaporators with thermostatic expansion valve will have some portion of
heat transfer surface where superheating is taking place and can be designated as dry
evaporator; where as evaporators with float valve will be flooded type.
3.2.1.1 Flooded Type
This type consists of a horizontal shell with tubes and removable end covers. The
liquid to be cooled is pumped through the tubes and a series of passes is arranged to increase
the liquid velocity and heat transfer rate by fitting rate of the end cover (the type shown is a
two pass arrangement). Liquid refrigerant is fed into the shell by an expansion valve capable
of maintains a fined liquid level. The balance pipe shown connects to the expansion valve and
assists the flow of liquid out of the valve chamber.
(b) Oil circulating around the system will enter the shell with the liquid refrigerant but not
evaporate. This result in an increase in the dissolved oil concentration, so that an oil
rectifier.
(c) If the evaporating temperature fall below the freezing point of the liquid being cooled,
ice formation will reduce the heat transfer and flow rates. The evaporating
temperature will then fall rapidly and the liquid free in the tube and cause extensive
damage.
These disadvantages can be overcome by using a dry expansion cooler, which is
the type most commonly fitted to modern liquid cooling plants.
3.2.1.2 Dry Expansion Type
HEAT TO RADIATION
HEAT REJECTED AND COOLANT
RRIME COMPRESSOR
WORK
MOVER
HEAT
LOW PRESSURE
AIR COMPRESSED
SOURCE AIR
It serves as the re-claiming agent. The vapours are sucked from the evaporator,
compressed to the pressure corresponding to a saturation temperature, which will be higher
than the coolant available to condense it. The other function is to continuously circulate the
refrigerant through the system. The capacity of the compressor determines the capacity of the
refrigeration system.
The parts of a rotary compressor are the blade, cylinder eccentric, roller, rotor shaft
and the spring.
comparatively high kW power/ton and the fan vibration and noise. The Capacity of an air-
cooled condenser may be calculated using one of the two basic methods.
The total external area of the condenser can be used to compute its heat dissipating
capacity. Computations based upon what is called the frontal area of the condenser. Using the
total external area of the condenser for dissipating heat depends upon the following variables:
External area
Temperature difference
Time
Air velocity
Using these values, the capacity of an air- cooled condenser varies between 20
kJ/hrm2Cto 80 kJ/hrm2C. The effect of air velocity is to increase the condenser capacity
with increase in air velocity. A single tube condenser has a total area approximately 20 times
its frontal area.
From above, it may be concluded that a particular type of condenser may not always
be better for all applications. The selection of condenser depends upon-
(i) System capacity
(ii) Type of refrigerant
(iii) Cooling medium available
3.4.1.4 Evaporative Condenser
An evaporative condenser is essentially a water conservation device and is, in effect, a
condenser and a cooling tower combined into a single unit. A diagram of a typical induced
type evaporative condenser is shown in Figure 3.11.
Both, air and water are employed in the evaporative condenser. The water pumped
from the pump up to the spray header sprays down over the refrigerant coils and returns to
the pump. The air is drawn in from the outside at the bottom of the condenser by action of the
blower and is discharged back to the outside at the top of the condenser. In some cases, both
pump and blower are driven by the same motor. In others, separate motors are used. The
eliminators installed in the air stream above the spray header are to prevent entrained water
from being carried over into the blower.
3.4.1.5 Advantages of Evaporative Condenser (over water-cooled condensers)
The vapour inside the coil is cooled by air as well as by evaporation of spray water.
Therefore, cooling to a temperature below that of ambient air can be achieved. Hence, this
type of condenser reduces the head pressure, and is quite efficient. Plants with capacities of
700 kW cooling (200 tonnes) or above are fabricated using evaporative condensers is less,
36
and are therefore desirable where wate costs are high and also there is acute shortage of
water.
3.5 Expansion Valve
The expansion valve is a device that controls or limit the flow of refrigerant into the
system. It is installed between the condenser and the evaporator.
3.5.1 Types of Expansion Valve
Common Expansion Devices are:
1. High-side Float
2. Low-side Float
3. Thermostatic Expansion Valve
4. Automatic Expansion Valve
5. Fixed-bore (Capillary Tube)
3.5.2 General Applications
Thermostatic Expansion Valve (TEV or TXV): control valve in the refrigeration
system operated by the pressure and temperature in the evaporator. Its sensing bulb
which is installed in the outlet of the evaporator monitors the pressure in the
evaporator.
Automatic Expansion Valve (AEV or AXV): control valve operated by the low-
pressure of the refrigeration system. It is sometimes called “dry” valve due to the fact
that the evaporator is never filled with liquid refrigerant, but just a fog or mist because
of the spraying process that is taking place in it.
Low-side Float Expansion Valve: is a simple but efficient control valve. It maintains
the constant level of liquid refrigerant into the evaporator.
High-side Float Expansion Valve: is similar to a Low-side Float expansion valve
where the liquid refrigerant is sorted in the evaporator which makes it flooded, that is
why the evaporator is called the flooded type.
Capillary Tube: is a control that is made up of small diameter tubes which serves a
constant throttles on the refrigerant.
37
fluorocarbon synthetic fluids. Two chemists from the University of California studied these
fluids. Irvine suggested in 1974 that molecules of Flourocarbons from more than 1-1/2 billion
aerosol cans sold annualy may be rising into the stratosphere. These gas molecules contribute
to break down the earth’s ozone shield that prevents the sun’s most harmful ultraviolet
radiation from reaching the earth. This radiation, if it gets through, would increase cataracts
as well as human skin cancer, and might even cause genetic damage to plant and animal life.
Freon-12 or R-12 (CCL2F2) has a boiling point of -21.6ºF. This refrigerant is usually
use for household refrigerators and freezers. It is also used in automobile air conditioning as
well as in many commercial and industrial systems. Freon-22 or R-22 (CCC1F2) has a
boiling point of -41.4ºF. It is principally used in airconditioning equipment.
Capacitor Start,
Capacitor Run
Motor
Run Capacitor
Current Relay
Potential Relay
capillary tube and the bellows. These three are interconnectely assembled in one which is
charged with a small amount of highly volatile fluid or refrigerant such as the sulfurdioxide.
When the compressor is running and the sensing bulb is gradually cooled, pressure
inside the assembly will decrease, thus opening the contact and cutting the circuit from
electrical source.
Tutorial Sheet 3
1. What is Evaporator? Describe and Explain types of Evaporator in detail with the help of
neat sketches.
2. What are Compressor and Refrigerant Compressor? Make a sketch for general
arrangement of compressor set, types, and general applications.
3. What is Condenser? Describe types of Condenser and Explain any two types with neat
sketches.
4. With the help of neat sketches, Explain the working principle of Air-cooled Condenser?
5. Write down the Water-cooled condenser in detail.
6. Write down the Evaporative condenser in detail.
7. Describe Advantages and Disadvantages of Water-cooled Condenser compare with Air-
cooled Condenser.
8. What is Expansion Valve? Describe Types and and general applications with the help of
neat sketches
9. Explain Terms for Refrigerant and Handaling Refrigerants.
45
CHAPTER 4
ASSEMBLE PARTS OF A DOMESTIC REFRIGERATOR AND
TROUBLESHOOTING
4.1 External View and Dimension of Refrigerator
1. Cabinet 1
2. Case ( VAPORI ) 1
3. Absorber ( VAPORI ) 1
4. Switch relay 1
5. Relay cover 1
6. Pipe service 1
7. Clamp relay cover 1
8. Compressor 1
9. Wire earth 1
10. Base compressor 1
11. Absorber compressor 1
12. Cover cab 1
13. Vibration-roof gum 1
14. Pipe hot 1
15. Pipe suction 1
16. Base cab 1
17. Dryer 1
18. Pipe Connect ( Suction ) 1
19. Pipe Connect ( Deliver ) 1
20. Washer compressor 1
21. Foot adjust 1
22. Fixture compressor bolt 1
4.12 Trouble Shooting Chart
Compressor will not start
Possible Causes Symptoms Remedy
1. Power Failure No voltage on the socket Check power Supply
2. Blown Fuse No voltage on the socket Replace Fuse
3. Open line wire No resistance reading Connect open line
4. Defective Thermostat No resistance reading Replace Thermostat
5. Defective O.L.P No resistance reading Replace O.L.P
6. Open or Burn-out No resistance reading Replace compressor
compressor
7. Open relay No resistance reading Replace relay
54
Low Cooling
Possible Causes Symptoms Remedy
1. Lack or Refrigerant Low pressure Add refrigerant
Sweating evaporator
2. Moisturized Half of evaporator freezing Replace Strainer-Drier
while half is sweating Recharge refrigerant
3. Low setting of Thermostat Compressor will run for a Reset the Thermostat
short time
4. Excessive Food Load Low cooling Remove excess food
5. Frequent door opening Low cooling Minimize door opening
6. Loose door gasket Door will not close tightly Replace door gasket
7. Unit expose to heat Low cooling Re-install unit away from
heat
8. Defective Defrost timer The defrost heating is Replace Defrost timer
energizing as the compressor
is running
55
Compressor Tripping
Possible Causes Symptoms Remedy
1. High head pressure Over heating compressor Replace compressor
High ampere
2. Defective relay High ampere Replace relay
3. Shortage compressor High ampere Replace compressor
4. Stuck-up compressor High ampere Replace compressor
5. Low-voltage High ampere Check voltage reading
56
Tutorial Sheet 4
3. List the possible causes, symptoms and remedy of the following troubles
(i) Compressor will not Start
(ii) No Cooling while Compressor is running
4. Write down the possible causes, symptoms and remedy in Low Cooling.
5. Write down the possible causes, symptoms and remedy in Compressor Runs Continuously
(24 hrs).
6. Write down the possible causes, symptoms and remedy in Compressor Tripping.
REFERENCES