Water Demand IPC

The document outlines water demand calculations for domestic plumbing fixtures according to IPC, detailing total Water Supply Fixture Units (WSFU) and water demand in liters for both domestic and flushing needs. It specifies the total water demand for domestic use as 27,896.4 liters and for flushing as 35,721 liters, leading to required tank volumes for underground and overhead storage. The recommended tank sizes are 55,792.8 liters for underground and 13,948.2 liters for overhead for domestic use, and 71,442 liters for underground and 17,860.5 liters for overhead for flushing.

Uploaded by

jhigs amfufu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
559 views11 pages

Water Demand IPC

The document outlines water demand calculations for domestic plumbing fixtures according to IPC, detailing total Water Supply Fixture Units (WSFU) and water demand in liters for both domestic and flushing needs. It specifies the total water demand for domestic use as 27,896.4 liters and for flushing as 35,721 liters, leading to required tank volumes for underground and overhead storage. The recommended tank sizes are 55,792.8 liters for underground and 13,948.2 liters for overhead for domestic use, and 71,442 liters for underground and 17,860.5 liters for overhead for flushing.

Uploaded by

jhigs amfufu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 11

Water Demand Calculation as per IPC - Domestic

# Plumbing Fixture Qty WSFU Total WSFU


1 Lavatories 22 2 44
2 Hose Bib 8 1.5 12
3 Hand Spray 20 1.5 30
4 Kitchen Sink 0 0
5 Service Sink 0 0
0
Total WSFU 86
Total GPM 41
Diversity Factor 30% 12.3
Total Water Demand in Litres 27896.4
Water Demand Calculation as per IPC - Flushing
# Plumbing Fixture Qty WSFU Total WSFU
1 Water Closet 20 5 100
2 Water Bidet 0 0 0
3 Urinal 10 3 30
4 0
5 0
0
Total WSFU 130
Total GPM 52.5
Diversity Factor 30% 15.75
Total Water Demand in Litres 35721
Water Tank Sizing
As per NBC :
Domestic Underground Water Tank Storage = 2-3 Days
Domestic Overhead Water Tank Storage = ½ Day

Domestic Water Demand for One Day = 27896.4 Ltrs


Flushing Water Demand for One Day = 35721 Ltrs

Volume of Domestic Underground water tank ( = 55792.8 Ltrs


Volume of Domestic Overhaed tank (OHT) = 13948.2 Ltrs

Volume of Flushing Underground water tank (U = 71442 Ltrs


Volume of Flushing Overhaed tank (OHT) = 17860.5 Ltrs