DEL and Fatigue
DEL and Fatigue
, 7, 1171–1181, 2022
https://doi.org/10.5194/wes-7-1171-2022
© Author(s) 2022. This work is distributed under
the Creative Commons Attribution 4.0 License.
       Abstract. Present verification of the fatigue life margins on wind turbine structures utilizes damage equivalent
       load (DEL) computations over a limited time duration. In this article, a procedure to determine long-term fa-
       tigue damage and remaining life is presented as a combination of stochastic extrapolation of the 10 min DEL
       to determine its probability of exceedance and computationally fast synthesis of DELs using level crossings
       of a Gaussian process. Both the synthesis of DELs and long-term stochastic extrapolation are validated using
       measured loads from a wind farm. The extrapolation for the blade root flap and tower base fore–aft damage
       equivalent moment is presented using a three-parameter Weibull distribution, whereby the long-term damage
       equivalent load levels are forecast for both simulated and measured values. The damage equivalent load magni-
       tude at a selected target probability of exceedance provides an indicator of the integrity of the structure for the
       next year. The extrapolated damage equivalent load over a year is validated using measured multi-year damage
       equivalent loads from a turbine in the Lillgrund wind farm, which is subject to wakes. The simulation of damage
       equivalent loads using the method of level crossings of a Gaussian process is shown to be able to reconstruct the
       damage equivalent load for both blade root and tower base moments. The prediction of the tower base fore–aft
       DEL is demonstrated to be feasible when using the Vanmarcke correction for very narrow band processes. The
       combined method of fast damage equivalent load computations and stochastic extrapolation to the next year
       allows a quick and accurate forecasting of structural integrity of operational wind turbines.
Published by Copernicus Publications on behalf of the European Academy of Wind Energy e.V.
1172                 A. Natarajan: Damage equivalent load synthesis and stochastic extrapolation for fatigue life validation
seeds) can be taken to repeat over 25 years, a typical wind            The fatigue damage as expressed in terms of the DEL is
farm lifetime. The International Electrotechnical Commis-           strongly dependent on the wakes within wind farms (Gallinos
sion (IEC) 61400-1 standard (IEC, 2019) informally recom-           et al., 2016) due to strong correlation of several load compo-
mends a stochastic extrapolation process to determine the           nents with the wind turbulence in the wake. This implies that
amplitude and cycle count of the largest amplitude loads as         varying atmospheric conditions such as the wind direction
part of the fatigue design process. Moriarty et al. (2004) used     and stability can influence the wake turbulence and thereby
extrapolation of load amplitudes to determine the long-term         also change the DELs on the turbine of interest. Since the
fatigue damage equivalent load, in a manner similar to ex-          turbulence in wakes is a function of a multitude of variables
treme load extrapolation. Since the load amplitude is extrap-       such as the turbine position, the wind direction, upstream tur-
olated, the probability of the load amplitude and number of         bine thrust, and upstream turbine yaw, it is not readily feasi-
cycles is conditional on the joint distribution of turbulence       ble to quantify the cumulative distribution function (CDF)
and mean wind speed. However the DEL is insensitive to iso-         of the wake turbulence. Herein, a novel approach is put for-
lated changes in load amplitudes for fixed wind turbulence,         ward to determine the return period of the DEL magnitudes
and therefore extrapolation using the load amplitudes may           conditional on the mean wind speed, wherein the variation
be conservative as such a process also takes into account iso-      in the DEL is considered to directly correlate to the variation
lated amplitude extremes within 10 min. Load measurements           in the wake turbulence. It is also common that many wind
from wind farms show a wide variation in damage equiva-             farms possess a wind turbine that is instrumented with load
lent loads, much more than seen in the conventional design          sensors and from which only the 10 min load statistics are
process due to varying inflow turbulence. The question then         archived. This usually implies the 10 min mean, standard de-
needs to be addressed as to whether larger damage equiva-           viation, maximum, and minimum are available. The DEL is
lent loads seen in measurements as compared to simulated            often not stored, as its computation requires rainflow count-
values encountered in the design process using limited load         ing or similar procedures to be available on the turbine com-
simulations are indicative of reduced structural reliability and    puter, which is often not the case. In such situations, it is
decreased lifetime.                                                 essential that the DEL can be computed from the measured
   To better quantify fatigue life over a long time, it is needed   standard deviations of the loads. This is not a prevalent prac-
to perform stochastic extrapolation of the short-term DELs          tice but is straightforward to map the standard deviation of
to determine the probability of exceeding the DEL magni-            loads to the DEL if the underlying stochastic process is as-
tude over the long term and thereby determine the life of           sumed to be Gaussian or Poisson. In the following sections,
the structure. In the present work, the DEL itself is extrap-       the 1-year DEL at the blade root and tower base of wind tur-
olated as a stochastic variable and taken to be fully corre-        bines in a farm is predicted both using stochastic extrapola-
lated to the wind turbulence. The DEL being an aggregated           tion of the measured DEL and through synthesis of the DELs
quantity is not affected by isolated changes in load ampli-         using the measured load standard deviations over limited in-
tudes over 10 min, but the change in DEL that is modeled            tervals. The method of synthesis of DELs using 10 min statis-
is due to change in turbulence at a given mean wind speed.          tics also allows the computation of DELs without the need
Therefore, the probability distribution of DEL is conditional       for detailed turbine information to be present, such as is re-
only on the mean wind speed, as is the case with wind turbu-        quired for an aeroelastic model. This allows the wind farm
lence. Extrapolation of extreme loads (Natarajan and Verelst,       owner to simulate DELs quickly without access to detailed
2012) is mandated by IEC 61400-1 to determine the 50-year           turbine information that is possessed only by the wind tur-
ultimate design load level, but there is no mandatory require-      bine manufacturer.
ment presently to extrapolate fatigue DEL. The DEL is an               Some authors refer to extrapolation to imply the prediction
aggregated quantity over a period of 10 min or more, the            of DELs for a future time interval based on measured DELs
value of which is relatively stable and may not change sig-         and wind conditions in the past (Hübler et al., 2018b, a).
nificantly for isolated load excursions resulting from the ran-     In the present work, extrapolation of DEL is defined as a
domness of a stationary process. However, the real condi-           stochastic methodology to determine the return period of
tions on the wind farm have varying wind turbulence inten-          increasing DEL magnitudes outside the domain of present
sities for a given mean wind speed, thus resulting in varying       results. Continuous monitoring and assessment of the tur-
damage equivalent loads. The resulting DEL values from dif-         bine structural life is crucial since the costs of unplanned
ferent 10 min simulations over different wind turbulence at a       downtime and repairs outweigh the cost of monitoring; also,
given mean wind speed can be extrapolated so that the proba-        early correction of wind farm operation ensures safety of
bility of exceeding a target damage equivalent load level over      structures for their intended lifetime and for life extension.
a long-term period can be determined. This is more accurate         Wind farm operational correction can be carried out by der-
and realistic than the conventional process used today of as-       ating upstream wind turbines to reduce the wake turbulence
suming that the same load cycles over a limited set of load         generated by those turbines and thus lower loads on the
simulations are prevalent for the entire life of the turbine.       downstream wind turbines (Dimitrov and Natarajan, 2021;
                                                                    Munters and Meyers, 2018). In the next sections, the abil-
ity to use measured or simulated 10 min load statistics to di-     Here gi is the number of standard deviations, σL , away from
rectly quantify DELs and the use of the stochastic extrapola-      the mean, µL . The number of load cycles with amplitude
tion methodology to forecast the return period of DELs are         greater than Li (upcrossings) is given by (Meirovitch, 2001)
explained, which leads to a criterion to determine if the mea-
                                                                                    L2
sured DELs on a wind turbine are within design limits.                         −     i
                                                                                      2
                                                                                   2σL
                                                                   Nci = νe               ,                                         (4)
2   Methodology
                                                                   where ν is the mean crossing frequency, which here will be
                                                                   assumed to be the first rotational frequency (P ) of the rotor
Given load cycles over 10 min intervals as obtained through
                                                                   for the blade flap loads and the first natural frequency for the
rainflow counting of the output time series of aeroelastic sim-
                                                                   tower base in the loading direction of interest. Based on the
ulations, the annual 10 min damage equivalent load at a given
                                                                   Rayleigh distribution decay rate, a load amplitude bin can be
mean wind speed bin is conventionally computed as
                                                                   determined which provides one load cycle in that amplitude
               Pn                ! m1                             bin; that is the number of upcrossings of level Li minus up-
                  i=1   ni Lm
                            i                                      crossings of Li + 1Li is unity. Equations (3) and (4) assume
Leq|v = 6Nv                              ,                  (1)
                       Neq                                         a Gaussian process with a single mean crossing frequency
                                                                   of interest. For broadband Gaussian processes or Poisson
where Nv is the number of hours in a year at the mean wind         processes, the methods of Cramer–Leadbetter (Cramer and
speed; Neq is the equivalent number of cycles, v; ni is the        Leadbetter, 1967) can be used, which have also been proven
number of load cycles of amplitude, Li ; and m is an expo-         for extreme value analysis (Madsen et al., 1986). However
nent of the SN curve of the material. The load time series         for highly damped structures, the energy in the stochastic re-
used to compute ni and Li in Eq. (1) are conventionally re-        sponse is representative of a very narrow band process, and
sults from rainflow counting of limited aeroelastic simula-        in such cases, Eq. (4) can overly magnify the rate of level
tions performed under conditions important for fatigue dam-        crossings. Vanmarcke (1975) prescribed a correction factor
age. The duration of the load time series over all mean wind       to accurately determine the level crossings of very narrow
speeds and operational conditions simulated is seldom more         band processes, which states that the rate of crossings of such
than a few days, and the same load cycles are assumed equiv-       a process is
alently prevalent for the lifetime of the wind turbine. In prac-
tice, a load measurement campaign will provide a wide scat-                          L2
                                                                                      i
                                                                                −      2
ter in DELs (Barber et al., 2016), so it may be difficult to       Nvi = νv e       2σL
                                                                                              ,                                     (5)
ascertain, based on the limited simulations, the design DEL
value that is to be considered for assuring that the magni-        where
tude of the measured DELs are within acceptable limits to                                  √                   
                                                                                           − 2π(1−α 2 )0.6 Li
ensure structural integrity. Instead of assuming the same lim-                                   σL
                                                                          1 − e
ited number of load cycles repeated for the lifetime of the        νv = ν                                      .                  (6)
                                                                                                                
                                                                                                    L2
turbine in Eq. (1), it is more realistic to determine the prob-                                   − i2
                                                                                                   2σL
ability of exceedance of DELs over a period and thereby de-                               1−e
termine the number of cycles for each DEL magnitude.               α is the Vanmarcke bandwidth parameter, which for a very
   While frequency domain DEL computation methods such             narrow band process will approach unity. The Vanmarcke
as Dirlik’s method (Ragan and Manuel, 2007) have been used         correction regulates the peak crossings of different load lev-
by some, these methods require knowledge of the load spec-         els by conditioning them on the bandwidth parameter α. Thus
trum and may not always be the best choice for design val-         this correction can be directly applied for the computation of
idation due to erroneous spectra. On the other hand, level-        DELs of processes with different bandwidths.
crossing methods need not always require availability of the          For a Gaussian process with a known standard deviation,
process spectrum. If the 10 min statistics of the standard de-     Eq. (1) can also be written as
viation, maxima, and minima of loads are available, then as-
suming the load amplitude can be expressed as a Gaussian                                          Pn               ! m1
                                                                                                   i=1   ni gim
process, the probability of crossing an amplitude level, Li ,      Leq|v = 6Nv σLm                                         .        (7)
follows a Rayleigh distribution (Meirovitch, 2001); that is                                            Neq
                                                                   variety of wind and wake conditions over a year with the re-
                                                                   spective measured DELs.
                                                                      Further time-domain aeroelastic simulations using the
                                                                   HAWC2 software (Larsen and Hansen, 2012) are also made
                                                                   to compute the blade root and tower base damage equivalent
                                                                   moments of the 2.3 MW wind turbine. The DELs obtained
                                                                   from all three methods, that is, Gaussian process analysis,
                                                                   aeroelastic simulations, and field measurements, are extrap-
                                                                   olated to determine the 1-year DEL value. Based on this ex-
                                                                   trapolation, a criterion is established in the following sections
                                                                   that allows lifetime assessment of blades and towers.
4 Results
Figure 3. Measured 10 min (a) blade root flap and (b) tower base fore–aft damage equivalent moments, on the C-08 turbine. The coefficient
of variation (CoV) of blade root flap DELs below rated wind speed is 0.49 and above rated wind speed is 0.17. The CoV of tower base
fore–aft (FA) DELs below rated wind speed is 0.47 and above rated wind speed is 0.29.
Figure 4. Simulated 10 min (a) blade root flap damage equivalent moment and (b) tower base fore–aft damage equivalent moment, over
different mean wind speeds and turbulence. The CoV of blade root flap DELs below rated wind speed is 0.31 and above rated wind speed is
0.22. The CoV of tower base FA DELs below rated wind speed is 0.31 and above rated wind speed is 0.23.
years. This question can be answered only if the probability           be seen that the tail of the extrapolated fitted distribution
of exceedance of the DEL magnitudes is assessed. The wind              corresponding to the 1-year exceedance probability matches
turbine structure is designed to meet a target annual probabil-        the median rank of the measured DELs very well. This pro-
ity of failure in fatigue, and since the DEL is representative         cess can therefore be replicated at all mean wind speeds
of the damage suffered, the probabilities of exceedance of the         and over all turbulence levels to determine DEL magnitudes
DEL magnitudes over a 1-year return period are compared.               with multi-year return periods. The resulting DEL magnitude
    The stochastic extrapolation of the DELs using the three-          probability can be weighted with the probability of mean
parameter Weibull distribution is validated using the mea-             wind speed to determine the DEL over all mean wind speeds.
sured blade root flap DEL. The measured turbulence varia-                 The method proposed is applicable for any number of
tion at each mean wind speed is divided into 50 bins, and              DELs from different load components that are strongly de-
one 10 min DEL is taken from each bin to compute the me-               pendent on wind turbulence. While the influence of the tail
dian rank. The three-parameter Weibull distribution is then            region is greater for larger material exponents such as for
fit to the resulting median rank subset. This stochastic fit is        blades, enabling a longer-term DEL prediction, it is not in-
then extrapolated to a 1-year probability of exceedance and            significant for steel towers. Therefore the methodology pre-
compared with the global median rank of the 1-year mea-                sented herein seeks to use limited load measurements and
sured DELs to validate the approach. The results are shown             load simulation results to enable a comparison of the cor-
in Fig. 5 for two different mean wind speeds, wherein it can           responding estimated 1-year DELs between the field instal-
Figure 5. Validation of the stochastic extrapolation method with the measured 1-year median rank of the DEL.
Figure 6. Comparison of the 10 min (a) extrapolated blade root flap bending damage equivalent moments and (b) the extrapolated tower
base fore–aft damage equivalent moments, using measurements. For the blade root, extrapolated curves begin at the far left (5 m s−1 – lowest
DEL), move to the right with increasing mean wind speed until 11 m s−1 (highest DEL), and then move left again with increasing mean
wind speed. For the tower base, extrapolated curves begin at the middle at 5 m s−1 and move to the right (highest DEL) until 8 m s−1 , before
moving to the left again.
lation and design. The long-term DEL magnitude should be                     The same extrapolation can also be performed using only
bounded with increase in time, and the tail of the DEL should            the simulated DEL values for the same two load sensors, and
be accurately represented, which is what is shown to be the              the results are shown in Fig. 7. The simulated DELs cover
case in Fig. 5. As can be seen, the rate of increase in DEL              all IEC turbulence classes, and these are representative of the
reduces significantly with reduction in the probability of ex-           turbulence levels experienced by the actual turbine. However
ceedance and asymptotically approaches the empirical dis-                the simulated results use the 90 % quantile of turbulence,
tribution from the measured DELs. This implies that the de-              whereas the measured turbulence covers a range of quan-
sired annual or long-term probability of failure can be ac-              tiles. Consequently, it can be compared if the extrapolation
tively measured.                                                         using the simulated DELs in Fig. 7 has a higher 1-year DEL
   Based on the validations shown in Fig. 5, Fig. 6 displays             magnitude at the 1-year probability of exceedance than the
the long-term extrapolated values for the blade root flap dam-           measured 1-year DEL magnitudes over different mean wind
age equivalent moment and tower base damage equivalent                   speeds. The weighted probability of the DEL with the an-
moment to very low probabilities of exceedance, from which               nual probability of mean wind speeds can be quantified to
the DEL magnitude corresponding to the desired exceedance                enable a definite conclusion on a target annual DEL magni-
probability can be determined. It can be seen that extrapo-              tude, above which the turbine structure can be said to possess
lation using the three-parameter Weibull distribution repro-             a diminished annual reliability level.
duces the same trend as the empirical distribution using the                 It should be noted that while the process of verification
measurements while allowing for predicting the DEL mag-                  of the structural integrity in fatigue is presented, the quan-
nitudes asymptotically to lower probabilities of exceedance              tification of the structural reliability or remaining life of the
for the blade root and tower base over various mean wind                 specific operational turbine is not made herein since the ac-
speeds.                                                                  tual design loads of the specific turbine used in its design are
                                                                         not available.
Figure 7. Comparison of the 10 min (a) extrapolated blade root flap bending damage equivalent moments and the (b) extrapolated tower
base fore–aft damage equivalent moment, using simulations.
Figure 8. Comparison of the 10 min blade root flap bending damage equivalent moments between the Gaussian process method and mea-
surement data on the C-08 turbine.
4.2    Extrapolation with Gaussian process analysis (GPA)              Figure 8 compares the resulting blade root flap damage
                                                                    equivalent moment from the GPA with the measured DELs
Since aeroelastic simulation is time-consuming and therefore
                                                                    at two different mean wind speeds. The results in Fig. 8 show
provides limited DEL results, the methods for narrow-band
                                                                    that for all the different wind turbulence variations with var-
and very narrow band processes as explained in previous sec-
                                                                    ious wake angles, the simple Gaussian process analysis pro-
tions are used to directly simulate 1 year of DELs for the
                                                                    vides a similar quantification of the true DEL to that seen
C-08 wind turbine blade root and tower base. The 10 min
                                                                    in measurements. For these blade root flap DELs, Eq. (4)
measured load statistics are used to determine the DEL val-
                                                                    is used directly without the Vanmarcke correction to obtain
ues. Using load levels within the measured minimum and
                                                                    the number of crossings of different levels. However if the
maximum load level and using the measured 10 min stan-
                                                                    same method is used (i.e., without the Vanmarcke correc-
dard deviation as σL , a 1-year DEL simulation is made using
                                                                    tion) for the tower base fore–aft damage equivalent moment,
Eqs. (4)–(7), which requires only a few seconds on a stan-
                                                                    then as seen in Fig. 9a, the tower base fore–aft DELs are
dard laptop computer. Many load measurement statistics of-
                                                                    greatly amplified in comparison to the measured DELs. The
ten do not possess DEL magnitudes, and under such condi-
                                                                    power spectrum of the tower base fore–aft (FA) moment is
tions, the DEL magnitudes can be re-created using Eqs. (4)–
                                                                    compared with the blade root flap in Fig. 9b, from which it
(7). If measured 10 min load statistics are unavailable, then
                                                                    can be seen that the first peak for the tower moment has a
the aeroelastic simulations can be used to determine a range
                                                                    much smaller energy rise relative to its starting point than
of mean and standard deviations relevant for the 10 min load
                                                                    the corresponding first peak in the blade moment, which has
magnitudes as a function of mean wind speed and wind tur-
                                                                    an energy jump of about a 100 on the power spectral density
bulence.
                                                                    (PSD) scale. This is due to significant aerodynamic damping
                                                                    that is not considered in Eq. (4). Therefore the bandwidth of
Figure 9. (a) Comparison of the 10 min tower base fore–aft damage equivalent moment with measurements at 7 m s−1 using the Gaussian
process method without Vanmarcke correction. (b) Comparison of the power spectrum of the tower base moment showing the small increase
in energy at its first peak with the corresponding much larger peak in the blade root flap moment.
Figure 10. Comparison of the 10 min tower base fore–aft bending damage equivalent moments between the Gaussian process method and
measurement data on the C-08 turbine.
the spectrum needs to be provided in the expression for level        on similar turbines. Figure 11 displays the extrapolated 1-
crossings, which is exactly what the Vanmarcke correction            year DEL values for the blade root and tower base with the
applies.                                                             GPA as compared to measurements and the three-parameter
   The Vanmarcke correction in the limit that α → 1 provides         Weibull CDF, where it can be seen that the extrapolation us-
the equivalent bandwidth for a highly damped system, and             ing GPA shows similar trends to using a parametric Weibull
herein α is taken as 0.99 to model the peak crossings of the         fit to data. The empirical DEL using measurements reaches
tower base moment. Figure 10 provides the same compari-              a 1-year probability of exceedance up to 10 m s−1 , beyond
son for the tower base fore–aft damage equivalent moment,            which the measurements have fewer data. Since the results of
with the Vanmarcke correction, and now a very good match             GPA tally well with measured DELs for the blade and tower,
between the DELs computed with this methodology and the              this method can also be used to detect anomalous wind tur-
measured DELs is seen.                                               bine operation, such as if DEL values that are significantly
   The validation of the simulated DELs with the measure-            different from the predictions by GPA are measured. This
ments shown in Figs. 8 and 10 over a year is sufficient justifi-     can happen, for example, if there is tower resonance with the
cation for considering that the underlying stochastic process        rotor rotational speed or if there is a shutdown of the turbine
is Gaussian. The matching comparisons in Figs. 8 and 10              under high turbulence or other uncommon events.
imply that the results from the GPA can be sampled to also               Based on this method, the extrapolated simulated DEL
perform a stochastic extrapolation of the DEL magnitudes             magnitudes (also using simulated standard deviations)
to obtain a 1-year DEL value or values of even higher re-            should display higher DEL values for the same probability of
turn periods. Considering the computation speed of the Gaus-         exceedance as compared to the extrapolated measured DEL
sian process analysis, it is also possible to directly simulate      values, in which case the structural integrity of the turbine
multi-year damage equivalent moments if the correspond-              structure is not compromised. This allows a direct quantifica-
ing standard deviation, minimum, and maximum values of               tion of the life consumption of the turbine structures in a farm
the loads are known, for example from past measurements              if the certification design loads of the turbines in question are
Figure 11. Comparison of the 10 min (a) extrapolated blade root flap damage equivalent moment and (b) tower base fore–aft damage equiv-
alent moment, using the Gaussian process method and measurement data on the C-08 turbine between 7 and 13 m s−1 . Blade: measurement
1-year DEL – between 1.9 and 2.3, Weibull CDF 1-year DEL – between 2 and 2.7, and GPA 1-year DEL – between 1.9 and 3.1. Tower:
measurement 1-year DEL – between 3.3 and 4.4, Weibull CDF 1-year DEL – between 2.9 and 4.4, and GPA 1-year DEL – between 2.8 and
4.4.
available so that the relative difference in the DEL magni-           ment wind farm control methods that either reduce loads or
tudes with the actual inflow conditions is obtained. Without          increase power production, based on the need.
such an extrapolation, the probability of obtaining DEL mag-
nitudes higher than the design DEL magnitudes is not known,
and therefore the extrapolation of DEL is a necessary proce-          Data availability. Measurement data from the wind turbine and
dure.                                                                 the wind farm used in this work are not publicly available due to a
                                                                      non-disclosure agreement between the Technical University of Den-
                                                                      mark and the providers of the data.
5   Conclusions
                                                                      Competing interests. The author has declared that there are no
Methodologies for computing DELs over multiple years and              competing interests.
determining the probability of exceedance of DEL mag-
nitudes were developed and validated using measurements
from the Lillgrund wind farm. The synthesis of DELs using             Disclaimer. Publisher’s note: Copernicus Publications remains
available mean and standard deviation of the loads was pre-           neutral with regard to jurisdictional claims in published maps and
sented and validated for the blade root flap moment and tower         institutional affiliations.
base fore–aft moment. This provides a fast methodology to
simulate the DELs for long durations without loss of accu-
racy. Different approaches for narrow-band processes (blade           Acknowledgements. The author is grateful to Gunner Larsen
flap) and very narrow band processes (tower base fore–aft)            from DTU Wind Energy for his inputs.
were delineated and shown to also be usable as data sets
for stochastic extrapolation to determine probabilities of ex-
ceedance. A suitable indicator to verify structural integrity         Financial support. This research has been supported by the Eu-
of the turbine structure was proposed as the magnitude of the         ropean Union’s Horizon 2020 Framework Programme, H2020 Soci-
DEL at the 1-year probability of exceedance, based on past            etal Challenges – Secure, Clean and Efficient Energy, TotalControl
measurements and compared to the corresponding DEL mag-               Project (grant no. 727680).
nitude in the design basis. The process of structural integrity
verification was shown and quantified through the compari-
                                                                      Review statement. This paper was edited by Amir R. Nejad and
son of extrapolated DELs from measurements obtained from
                                                                      reviewed by three anonymous referees.
a single turbine with the corresponding extrapolated DEL
magnitudes using simulation results. The capability to syn-
thesize DELs from 10 min load statistics also allows ease of
storage of multi-year data, without the need for time-series
analysis. The combined methods of synthesis of DELs and
stochastic extrapolation allow forecasting damage into the
future and can be used as a decision-making tool to imple-
References                                                               Hübler, C., Weijtjens, W., Rolfes, R., and Devriendt, C.: Reliability
                                                                           analysis of fatigue damage extrapolations of wind turbines using
Barber, S., Mechler, S., and Nitschke, M.: The effect of wakes on          offshore strain measurements, J. Phys. Conf. Ser., 1037, 032035,
  the fatigue damage of wind turbine components over their entire          https://doi.org/10.1088/1742-6596/1037/3/032035 2018b.
  lifetime using short-term load measurements, J. Phys. Conf. Ser.,      IEC: International Standard IEC61400-1: Wind Turbines – Part 1:
  753, 072022, https://doi.org/10.1088/1742-6596/753/7/072022,             Design Guidelines, ISBN 978-2-8322-6253-5, 2019.
  2016.                                                                  Larsen, T. J. and Hansen, A. M.: How to HAWC2, the user’s man-
Cramer, H. and Leadbetter, M.: Stationary and Related                      ual, Tech. Rep. R-1597, Technical University of Denmark, De-
  Stochastic Processes, John Wiley & Sons Inc, New York,                   partment of Wind Energy, ISBN 978-87-550-3583-6, 2012.
  ISBN 9780471183907, 1967.                                              Madsen, H. O., Krenk, S., and Lind, N.: Methods of Structural
Dimitrov, N. and Natarajan, A.: Wind farm set point optimiza-              Safety, Prentice Hall, Englewood Cliffs, NJ, ISBN 0-13-579475-
  tion with surrogate models for load and power output targets,            7, 1986.
  J. Phys. Conf. Ser., 2018, 012013, https://doi.org/10.1088/1742-       Meirovitch, L.: Fundamentals of Vibrations, McGraw Hill, New
  6596/2018/1/012013, 2021.                                                York, ISBN 978-1577666912, 2001.
Dimitrov, N. K., Natarajan, A., and Mann, J.: Effects of                 Miner, M. A.: Cumulative damage in fatigue, J. Appl. Mech., 12,
  normal and extreme turbulence spectral parameters on                     159–164, 1945.
  wind turbine loads, Renew. Energ., 101, 1180–1193,                     Moriarty, P. J., Holley, W. E., and Butterfield, S. P.: Extrapolation of
  https://doi.org/10.1016/j.renene.2016.10.001, 2017.                      Extreme and Fatigue Loads Using Probabilistic Methods, Tech.
Gallinos, C., Dimitrov, N., Larsen, T., Natarajan, A., and Hansen,         Rep. NREL/TP-500-34421, https://doi.org/10.2172/15011693,
  K.: Mapping Wind Farm Loads and Power Production – A                     2004.
  Case Study on Horns Rev 1, J. Phys. Conf. Ser., 753, 032010,           Munters, W. and Meyers, J.: Dynamic Strategies for Yaw and In-
  https://doi.org/10.1088/1742-6596/753/3/032010, 2016.                    duction Control of Wind Farms Based on Large-Eddy Simulation
Hoole, J., Sartor, P., Booker, J., Cooper, J., Gogouvitis, X. V., and      and Optimization, Energies, 11, 177–190, 2018.
  Schmidt, R. K.: Systematic statistical characterisation of stress-     Natarajan, A. and Verelst, D. R.: Outlier robustness for wind turbine
  life datasets using 3-Parameter distributions, Int. J. Fatigue, 129,     extrapolated extreme loads, Wind Energy, 15, 679–697, 2012.
  105216, https://doi.org/10.1016/j.ijfatigue.2019.105216, 2019.         Ragan, P. and Manuel, L.: Comparing Estimates of Wind Turbine
Hübler, C., Gebhardt, C. G., and Rolfes, R.: Methodologies for fa-         Fatigue Loads using Time-Domain and Spectral Methods, Wind
  tigue assessment of offshore wind turbines considering scattering        Eng., 31, 83–99, 2007.
  environmental conditions and the uncertainty due to finite sam-        Vanmarcke, E.: On the distribution of the first-passage time for nor-
  pling, Wind Energy, 21, 1092–1105, 2018a.                                mal stationary random processes, J. Appl. Mech., 42, 215–220,
                                                                           1975.