Installation Instructions 5014018501
2019-06
G 3 H E
PowerFlex 527 Incremental Encoder Input
Catalog Number: 25-ENC-2
Encoder cover Incremental
Encoder Input
1 L1 L2 L3
I
2
HTL/TTL DIP switches
DC+ DC–
0V
Wait three minutes
0V after shutdown for
capacitors to discharge
Voltage DIP switch to safe voltage levels.
3 Align Tabs of Encoder with the slots on the Control Module
4 Press Down Firmly to Lock Incremental Encoder onto the
Control Module
Publication 520-IN013B-EN-P - July 2019
PowerFlex 527 Incremental Encoder Input
5 How to Remove the Encoder
Hold the top of the Pull out the encoder
encoder firmly as shown
IMPORTANT Do not remove the encoder from the
bottom as it might damage the
encoder and the locking mechanism
on the control module.
6 Wiring the Incremental Encoder
+V Cm Z- Z B- B A- A Maximum Wire Size Minimum Wire Size Torque
12V 5V HTL TTL (ON)
2.08 mm2 (14 AWG) 0.08 mm2 (28 AWG) 0.18...0.22 N•m (1.56...1.9 lb•in)
No. Signal Description I/O Connection Example I/O Connection Example
(1) (2)
+V 5...12V Power Internal power source 250 mA (isolated). Encoder Power +12V DC Encoder Power
– Internal Drive (250 mA) – External
Cm Power Return +V
Common
Power Cm Common Power Source
Z- Marker Z (NOT) Marker pulse Z- to
SHLD
+
Z to SHLD
Z Marker Z External
Internal (drive) B- Power
12V DC, 250 mA B Supply
B- Encoder B (NOT) Quadrature B input. A-
A
B Encoder B
A- Encoder A (NOT) Quadrature A input. Encoder Signal to Power Supply Encoder Signal to SHLD
– Single-Ended, Common – Differential,
+V +V
A Encoder A Dual Channel Cm Marker Dual Channel Cm Marker
Z NOT A NOT
Z- Z-
Marker Z Marker A
Z Z
Output DIP switch selects 12V or 5V power that is
B- B-
B NOT
supplied at terminals “+V” and “Cm” for B B
B B
the encoder. A NOT
A- A-
A A
A A
HTL/TTL DIP Set the position of the DIP switches
switches based on the type of encoder signal used. to SHLD
You must set all switches to the same
position.
(1) When using 12V Encoder power, 24V I/O power, maximum output current at I/O Terminal 11 is 50 mA.
(2) If Encoder requires 24V power, it must be supplied by an external power source.
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, E-mail: support@drives.ra.rockwell.com
Online: https://www.rockwellautomation.com/global/support/overview.page
Rockwell Automation maintains current product environmental information on its website at
https://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
Allen-Bradley, PowerFlex, Rockwell Automation, Rockwell Software, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 520-IN013B-EN-P - July 2019
Supersedes Publication 520-IN013A-EN-P - March 2015 Copyright © 2019 Rockwell Automation, Inc. All rights reserved.