0% found this document useful (0 votes)
23 views37 pages

SOR of Elec

The document is a Bill of Quantities detailing various items related to the supply and erection of overhead equipment and traction sub-station components, including designs, materials, and installation rates. It includes specific item numbers, descriptions, units, and rates for each task involved in the construction and commissioning processes. The document is structured into schedules that categorize different types of work and materials required for the project.

Uploaded by

passionsaurabh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views37 pages

SOR of Elec

The document is a Bill of Quantities detailing various items related to the supply and erection of overhead equipment and traction sub-station components, including designs, materials, and installation rates. It includes specific item numbers, descriptions, units, and rates for each task involved in the construction and commissioning processes. The document is structured into schedules that categorize different types of work and materials required for the project.

Uploaded by

passionsaurabh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

Bill of Quantities

Schedule 16000
RE- General
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Preparation and submission of designs and drawings
for Overhead Equipment, Switching Station,
Sectioning diagram, Power supply diagram,
16001 OHE-1 Schematic diagram of Switching Stations, Traction TKM 2,166 31,401
Working Rule Diagram and Instructions etc. required
for commissioning of OHE.

Supply and Erection of large Span wire (130 sq.mm)


OHE-2
including its fittings with insulators:
16002 (a) With Porcelain Insulators 1050mm CD. Mtr 954 78
(b) With Composite Insulators 1050mm CD. Mtr 901 78
(c) Extra on erection under Power Block . Mtr 0 78
Supply and Erection of materials for Termination of
OHE-3 single conductor of overhead equipment or a
16003 terminating wire:
(a) With Porcelain Insulators 1050mm CD. Each 12,767 1,171
(b) With Composite Insulators 1050mm CD. Each 10,230 1,171
(c) Extra on erection under Power Block . Each 0 1,171
Supply and Erection of materials for Termination of
OHE-4 all aluminium 25 kV feeder conductor single (spider)
16004 including feeder wire:
(a) With Porcelain Insulators 1050mm CD. Mtr 636 257
(b) With Composite Insulators 1050mm CD. Mtr 597 257
(c) Extra on erection under Power Block. Mtr 0 257
Supply and Erection of material for Termination of
OHE-5 copper cross feeder with gantries including cross
16005 feeder wire:
(a) With Porcelain Insulators 1050mm CD. Set 54,092 1,373
(b) With Composite Insulators 1050mm CD. Set 49,016 1,373
(c) Extra on erection under Power Block. Set 0 1,373
Supply and Erection of Terminal Boards in control
16006 OHE-6 Each 13,015 585
cubicles.
Supply and Erection of iron clad 240V AC and 110V
16007 OHE-7 D.C. board with fuse box in control cubicles. Set 8,628 267

Supply, Erection, Testing and Commissioning of low


maintenance Lead Acid Battery set 40 AH, 110 volts
OHE-8 (a) DC as per latest RDSO specifications including Set 87,606 6,286
filling up of electrolyte and initial charging
16008 /discharging etc as required.
Supply, Erection, Testing and Commissioning of
battery charger suitable for 110V, 40 AH low
OHE-8 (b) maintenance lead Acid battery set as per latest Each 85,292 857
RDSO specifications including all accessories.
16009 OHE-9 (a) DELETED
16010 OHE-9 (b) DELETED
16011 OHE-10 Modification to existing Overhead Equipment. Mtr 0 47
Extra for modification to existing Overhead
16011A OHE-10(a) Mtr 0 47
Equipment under power block.
Man-
16012 OHE-11(a) Manning of switching station i.e. SP/SSP and TSS . 0 25,140
month
Man-
16012A OHE-11(b) Manning of anti-theft transformer. 0 23,774
month
Electrification of switching station (SP/SSP) building
16013 OHE-12(a) Each 0 47,102
as per specification.
Supply & Erection of Earthing arrangement at
16013A OHE-12(b) job 22,659 10,768
switching station.
Loading/Unloading, transportation and handing over Metric
16014 OHE-13 of all type of materials etc. (other than contractor Tonne 0 82
material). KM
Schedule-17000
Switching Post Building
Item No. SOR ITEM Description Unit Rate
Construction of Switching Station building, RCC
work, plastering, brick masonry, retaining wall, filling,
17001 OHE-15 compacting and levelling work etc as per RDSO Each 7,66,694
standard drawing and supply and erection of name
board of switching station.
Extra for every 0.3 m or part there of higher plinth
17001A OHE-15(a) over normal plinth height (On ground floor area only). Sq.m 950

Extra for every 0.3 m or part there of deeper


17001B OHE-15(b) foundations over normal depth (On ground floor area Sq.m 950
only).
Extra for open foundation on poor soil having every
17001C OHE-15(c) 0.3 m or part there of higher plinth over normal plinth Sq.m 1,809
height (On ground floor area only).
Schdule 19000
OHE - Ferrous other than steel structures and SPS
Rate
Item No. SOR ITEM Description Unit
Supply Erection
OHE-16 Supply and Erection of a guy rod assembly. Each 9,079 1,409
19001
(a) Extra on erection under Power Block. Each 0 1,409
Supply and Erection of protective screen on
19002 OHE-17 Sq.m 4,701 508
FOBs/ROBs.
Supply and Erection of bracket assembly with
OHE-18
insulators
With Porcelain stay & bracket Insulators 1050mm
(a) Each 21,677 1,214
19003 CD.
With Composite stay & bracket Insulators 1050mm
(b) Each 19,399 1,214
CD.
(c) Extra on erection under Power Block. Each 0 1,214
Supply and Erection of regulating equipment (3
OHE-19 pulley type) with counter weight assembly for Each 71,538 5,251
19004
conventional OHE.
(a) Extra on erection under Power Block. Each 0 5,251
Supply and Erection of material for termination of
OHE-20 double Overhead Equipment conductor
19005 (a) With Porcelain Insulators 1050mm CD. Each 15,197 1,325
(b) With Composite Insulators 1050mm CD. Each 12,918 1,325
(c) Extra on erection under Power Block. Each 0 1,325
Supply and Erection of anti-creep with galvanized
OHE-21
steel wire
(a) With Porcelain Insulators 1050mm CD. Each 35,664 3,725
19006 (b) Extra on provision of extra span in item (a). Each 7,133 745
(c) With Composite Insulators 1050mm CD. Each 31,107 3,725
(d) Extra on provision of extra span in item (c). Each 6,222 745
(e) Extra on erection under Power Block. Each 0 3,725
Supply and Erection of a structure bond/longitudinal
19007 OHE-22 bond/ transverse and special bond. TKM 25,455 8,121
Schedule 20000
OHE - Non Ferrous Part 'A'
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Supply and Erection of Over Head Equipment i.e.
contact & catenary wire (excluding cost of supply of
contact & catenary wires), jumper wire, dropper wire,
contact/catenary clips, fasteners and all other
OHE-23(a) material required at turn out/ overlaps/ diamond TKM 0 62,175
crossings etc. Final checking of OHE and
20001
adjustment, inspection to be done by tower wagon
for commissioning of conventional OHE.

(i) Extra on erection under Power Block. TKM 0 31,087


Extra on manual erection for catenary/contact wire.
(ii) TKM 0 15,543
Supply of contact wire (HDGCC 107/150 Sq.mm)
20002 OHE-23(b) MT 9,60,871 0
only.
Supply of cadmium copper catenary wire
20003 OHE-23(c) MT 9,60,871 0
(65 Sq. mm) only.
Schedule 21000
OHE - Non Ferrous Part 'B'
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Supply and Erection of anti-creep with cadmium
OHE-24
copper catenary wire.
21001 (a) With Porcelain Insulators 1050mm CD. Each 82,419 5,892
(b) With Composite Insulators 1050mm CD. Each 78,954 5,892
(c) Extra on erection under Power Block. Each 0 5,892
Supply and erection of section insulator assembly
OHE-25 and associated fittings & fasteners for OHE with Bar
Insulator:
With Porcelain Insulators 1050mm CD and Bar
21002 (a) Each 95,759 6,295
Insulator.
With Composite Insulators 1050mm CD and
(b) Each 94,027 6,295
Porcelain Bar Insulator.
(c) Extra on erection under Power Block. Each 0 6,295
Supply and Erection of PTFE type short neutral
OHE-26 section assembly as per latest RDSO specification. Each 11,30,077 8,152
21003
(a) Extra on erection under Power Block. Each 0 8,152
21004 OHE-27 DELETED
21005 OHE-28 DELETED
Supply and Erection of all types of copper jumpers.
OHE-29 Each 8,595 475
21006
OHE-29(a) Extra on erection under Power Block. Each 0 475
21007 OHE-30 DELETED
Supply of materials and erection of a large copper
jumper (160sqmm) between aluminium/Copper
OHE-31 busbar and OHE , cross feeder to OHE etc with all Each 11,062 475
21008
associated fittings.
(a) Extra on erection under Power Block. Each 0 475
Supply and Erection of solid copper busbar 18 mm
OHE-32 (a) dia including all connectors, bus splice etc. Mtr 4,280 233
21009
(i) Extra on erection under Power Block. 0 233
Supply and erection of Aluminium Bus Bar
OHE-32 (b) 36mmx28mm size including all connectors, bus Mtr 1,046 64
21010
splice etc.
(i) Extra on erection under Power Block. 0 64
Dismantling of traction structure, portals,TTC and
OHE-34 MT 0 1,777
associated SPS by cutting.
21011 Extra for Dismantling of traction structure,
OHE-34 (a) portals,TTC and associated SPS by cutting under MT 0 1,777
Power Block.
Supply and Erection of safety items i.e. Fire
extinguishers, set of fire bucket with stand and first
21012 OHE-35 aid box, key box with suitable key chain, locks and Set 16,098 2,666
other misc items required for commissioning of
switching station.
Supply and Erection of Retro-reflective type boards -
25kV AC OHE danger board/ danger board for height
OHE-36 gauge, public, staff caution board and special boards Each 451 160
21013
required for commissioning of OHE/SWSs.

(a) Extra on erection under Power Block. Each 0 160


Schedule-24000
TRACTION SUB-STATION
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Design and drawings for 220/27kV or 132/27kV or
24001 TSS-1 110/27kV traction sub-station including feeding post Each 0 1,38,908
and capacitor bank.
24002 TSS-2 DELETED
Construction of baffle wall complete with
24003 TSS-3 Cum 4,189 1,317
reinforcement, brick work, plastering etc.
Supply, erection, testing & commissioning of 132kV
24004 TSS-4(a) double pole SF-6 gas circuit breakers with interlock. Each 10,07,017 8,860

Supply, erection, testing & commissioning of 220kV


24005 TSS-4(b) double pole SF-6 gas circuit breakers with interlock. Each 18,98,354 8,860

Supply and erection of 132kV double pole isolators


24006 TSS-5(a) Each 4,06,836 3,843
(manually operated).
Supply and erection of 220kV double pole isolators
24007 TSS-5(b) Each 4,06,836 3,843
(manually operated).
Supply, erection, testing and commissioning of
24008 TSS-6(a) 132kV current transformer assembly (400- Each 3,41,403 1,982
200/5A).
Supply, erection, testing and commissioning of
24009 TSS-6(b) 220kV current transformer assembly (200-100/5A). Each 3,41,403 7,491

Supply, erection, testing and commissioning of


24009A TSS-6(c) 110kV current transformer assembly (400- Each 2,26,834 1,982
200/5A).
Supply,erection, testing and commissioning of
24009B TSS-6(d) 132kV current transformer assembly (1200- Each 4,26,913 1,982
800-400/5-5-5A).
Supply,erection, testing and commissioning of
24010 TSS-7(a) Each 1,99,770 1,404
120kV lightning arrestors.
Supply,erection, testing and commissioning of 198kV
24011 TSS-7(b) Each 1,99,770 2,448
lightning arrestors.
Supply,erection, testing and commissioning of 96kV
24011A TSS-7(c) Each 83,171 1,404
lightning arrestors.
Supply, erection, testing & commissioning of 25kV
24012 TSS-8(a) single pole Vacuum circuit breaker with interlocking Each 5,25,880 6,222
of rating 1600 Amp.
Supply, erection, testing & commissioning of 25kV
24012A TSS-8(b) single pole Vacuum circuit breaker with interlocking Each 6,22,474 6,222
of rating 2000 Amp.
Supply, erection, testing and commissioning of 25kV
24013 TSS-9(a) Each 95,494 818
current transformers (1500-750/5A).
Supply, erection, testing and commissioning of 25kV
24013A TSS-9(b) current transformers (3000-1500/5 Amp). Each 1,10,367 818
Supply, erection, testing and commissioning of 25kV
24013B TSS-9(c) Each 72,093 4,830
current transformers (200-100/5A).
Supply, erection, testing, and commissioning of
control and numeric relay panel suitable for double
24014 TSS-10(a) transformer traction sub station (two bay) of Each 47,16,651 16,062
220/27kV or 132/27kV or 110/27kV as per latest
RDSO specifications.
Supply, erection, testing, and commissioning of
control and numeric relay panel suitable for Single
24014A TSS-10(b) transformer single bay traction sub station of Each 24,30,609 16,062
220/27kV or 132/27kV or 110/27kV as per latest
RDSO specifications.
Extra payment for provision of indication, metering,
switches etc for additional equipments (BMs, PTs
24014B etc) in main control and numeric relay panel suiting 0 21,137
TSS-10(c) Each
the requirement of 3rd and (or) 4th line works as per
site and as directed by Engineer.

Supply, erection, testing, and commissioning of


24014C TSS-10(d) control numeric relay panel suitable for Single Circuit Each 17,96,537 16,062
breaker as per latest RDSO specification.
Supply, erection, testing and commissioning of
numerical control & relay panel suitable for Shunt
24014D TSS-10 (e) Each 10,72,637 16,062
Capacitor Bank as per latest RDSO specifications.

Supply & erection of tubular aluminium bus bars


24015 TSS-11 50mm x 39mm dia including all connectors, bus Mtr 1,642 66
splice etc.
Supply & erection of ‘Zebra’ ACSR conductor
24016 TSS-12 Mtr 1,137 21
including all connectors etc.
24017 TSS-13 DELETED
Supply & erection of copper jumper with fittings and
24018 TSS-14 Each 4,147 573
fasteners required for TSS.
Supply & erection of 110/132kV support insulators
24019 TSS-15(a) Each 41,671 664
with fittings and fasteners.
Supply & erection of 220kV support insulators with
24020 TSS-15(b) Each 41,671 1,039
fittings and fasteners.
Supply & erection of 110/132kV termination
24022 TSS-17(a) with/without adjuster complete with disc insulators. Each 15,107 345

Supply & erection of 220kV termination with/without


24023 TSS-17(b) adjuster complete with disc insulators. Each 15,107 529

Supply, erection, testing and commissioning of low


maintenance lead acid battery set 200AH, 110V DC
24024A TSS-18(a) as per latest RDSO specifications including filling up set 3,43,606 17,180
of electrolyte and initial charging /discharging as
required.
Supply, erection, testing and commissioning of
Battery Charger (automatic) suitable for 110V,
24024B TSS-18(b) 200AH low maintenance Lead Acid Battery set as each 2,02,205 10,110
per latest RDSO specifications including all
accessories.
Supply, erection testing & commissioning of 240Volt
24025 TSS-19 AC and 110Volt DC Distribution boards in the control Each 39,032 828
room.
24026 TSS-20 Supply and erection of earth electrode. Each 3,263 1,272
Extra payment on TSS-20 for excavation in hard
24026A TSS-20(a) soil/soft rock requiring machine drilling/breaking. Each 0 636

Supply and erection of earth leads 75 x 8mm mild


24027 TSS-21 steel flat laid in the ground or exposed as per site Mtr 232 67
requirement.
Supply and erection of earth leads 50 x 6mm mild
24028 TSS-22 steel flat laid in the ground or exposed as per site Mtr 112 53
requirement.
Supply and erection of 8 SWG GI Wire for earthing.
24029 TSS-23 Mtr 21 22
Supply and erection of 32mm to 40mm dia MS rod
24030 TSS-24 Mtr 265 22
for earth mat.
Supply & erection of earth screen wire including
24031 TSS-25 Mtr 292 14
termination.
Supply, erection, testing & commissioning of
24032 TSS-26(a) 132/27kV, 21.6/30.24MVA, ONAN/ONAF, single Each 2,24,65,190 3,18,607
phase traction power transformers.
supply, erection, testing & commissioning of
24033 TSS-26(b) 220/27kV, 21.6/30.24MVA, ONAN/ONAF, single Each 3,26,10,759 3,18,607
phase traction power transformers.
Supply, erection, testing & commissioning of
24033A TSS-26(c) 110/27kV, 21.6/30.24MVA, ONAN/ONAF, single Each 2,39,14,557 3,18,607
phase traction power transformers.
Supply, erection, testing & commissioning of 132/27
24033B TSS-26(d) kV, 30/42MVA, ONAN/ONAF, single phase traction Each 2,81,70,224 3,18,607
power transformers.
Supply and erection of 25kV double pole isolator
24034 TSS-27 Each 2,31,417 3,682
3150Amp with insulators.
Supply and erection of single pole isolator 3150
24035 TSS-28 Each 1,17,414 3,682
Amp with insulators.
Supply, erection, testing & commissioning of 25kV
shunt capacitor bank of 2400kVAR rating at 25kV
24036 TSS-29 including low loss series reactor, 25kV neutral Each 22,28,416 64,067
current transformer and all other accessories etc
except control and numeric relay Panel.
24037 TSS-30 DELETED
Supply, erection, testing and commissioning of
24038A TSS-31 (a) Each 2,94,283 1,860
110kV Potential Transformer assembly.
Supply, erection, testing and commissioning of
24038B TSS-31 (b) Each 2,35,127 13,048
132kV Potential Transformer assembly
Supply, erection, testing and commissioning of
24038C TSS-31 (c) Each 2,30,901 8,333
220kV Potential Transformer assembly.
Dismantling and shifting of Traction Power
Transformer with associated equipments from the
24039 TSS-32 existing bay and keeping at suitable place in Job 0 92,264
substation as directed by Engineer.
Supply, erection, testing and commissioning of
Special Energy Meter of 0.2s Class accuracy with
ABT, complete feature including software, hardware,
24040 TSS-33 meter cubical etc. as per the latest specification / grid Set 19,74,014 2,59,104
code/ metering regulations / amendments to
regulations of concerned Transmission /Regulatory
Authority.
Note: 1. Provision of cross track, control room building and approach road shall be made in the civil
portion of the Estimate/BOQ.
2. Provision of yard lighting and waterjet pump shall be made in the General Electrical portion of the
estimate/BOQ.
Schedule 27000
TSS Spares
Item No Description Unit Rate
SF-6 Gas Cylinder with filling arrangement
(regulator) -11kg capacity duly filled with SF-6 Gas
27001 of required purity suitable for CBs/interruptors in Set 66,170
TRD. (set = 02 nos of filled cylinders) .

25kV CB Bushing conforming to RDSO


27002 specifications and of make as approved by Engineer. Each 70,502

2kV Interrupter Bushing conforming to RDSO


27003 specifications and of make as approved by Engineer. Each 25,266

Numerical Earth fault Relay suitable for 25KV TSS


27004 and conforming to RDSO specifications and of make Each 16,120
as approved by Engineer.
SINGLE PHASE RELAY TEST SYSTEM FOR
TESTING VARIOUS TYPES OF RELAYS IN TSS
[Single phase relay test system for testing of electro-
mechanical relays, solid state static relays, micro-
processor based relays and numerical relays used in
TSS as per RDSO spec No TI/PSI/SPC/Test-kit/1080
(12/2008) or latest along with suitable
27006 Laptop/Notebook (with minimum configuration of Set 11,13,949
8GB/1TB/2GB GRAPHICS /Window10/ WIFI/BT
/15.6" screen/ Antivirus for atleast 01 years) of
reputed make like Dell/ HP etc with latest software
and antivirus . Model of relay testing kit: - Megger
make SMRT1 or Omricon CMC 356 or Doble F6150
or superior, as approved by Engineer.]

Transformer Oil (Inhibited Mineral Insulating Oil) as


27008 per IS 12463(1988) or latest and RDSO latest Litre 64
instructions.
Capacitor Bank 2400KVAR @25kv
(5500KVAR@40kv) consisting of set of capacitor
27009 units in series/parallel combination as per RDSO Set 12,30,526
spec TI/SPC/PSI/FC&SR/0100 with A&C No-1
(Oct/2016) or latest.
Supply, Testing and commissioning of Transformer
oil filteration plant 3000 LPH, Mobile trolley type
suitable to work on 230 V single phase AC supply,
27010 as per COFMOW specification No: Each 14,53,564
COFMOW/IR/HVTOP/2014 (Rev-1) or latest. (Model
CEEDEE/Pune or equivalent/superior as approved
by Engineer.
SCHEDULE -28000
Tools & Plants (OHE & PSI)
Item No Description Unit Rate
TOOLS & PLANTS (OHE & PSI)
Tirfor 2.5T/1.5T, ISI marked as per IS: 5604/1984 or
28001 latest (Make TRACTEL /TIRFOR or equivalent as Nos 17,032
approved by Engineer).
Tirfor 5T/3T ISI marked as per IS: 5604/1984 or
28002 latest (Make TRACTEL /TIRFOR or equivalent as Nos 23,275
approved by Engineer).
28003 DELETED
Pull lift 0.75T/0.8T ISI mark (Make TRACTEL or
28004 Nos 9,367
equivalent as approved by Engineer).
Fibre/Light Weight Winch Type Ladder Trolley
suitable to move on railway track for maintenance of
28005 25kV AC OHE. (SUMER make or equivalent as Nos 83,571
approved by Engineer) .
Rail Jumpers made of multistrand copper PVC Cable
248/0.457mm size with suitable clamps at both ends
28006 as per RDSO specification no ETI/OHE/3/(2/94) with
A& C slip No. 1(04/95) or latest and as approved by
Engineer-
(a) 3 meter length Each 1,526
(b) 5 meter length Each 2,082
(c) 13 meter length Each 3,217
Earthing discharge rod complete suitable for
working voltage of 25kV AC traction, fibre glass
28007 body screw type in a suitable carry bag as per RDSO Each 17,168
specification no ETI/OHE/51(9/87) or latest and as
approved by Engineer.
Aluminium Straight Ladder Extendable Type (11mtr),
Closed height 6mtr Extended height 11 mtr .(SUMER
28008 Nos 20,163
make Ref-AL100/8809 or equivalent as approved by
Engineer) .
Portable electric drill suitable for drilling holes of 12-
23mm dia, working on single phase, 230V AC supply
alongwith 2 nos suitable spare drill bits. (Make: Railli
28009 (a) wolf model WDH-12 or equivalent model of Nos 17,664
Hitachi/Black & Decker as approved by Engineer).

Portable rail drilling machine, capable of drilling


holes in rail flange upto hole dia 0-36 mm, suitable
for both 52kg & 60kg rail, having petrol start
28009 (b) Kerosene run HONDA engine 100cc alongwith all Nos 1,06,122
accessories. Make Jin Shaa or superior as approved
by Engineer.
First Aid Box made of GI/AL sheet, ISI marked, filled
with medicines as per concerned zonal Railway
28010 standard with suitable locking arrangement and as Nos 2,839
approved by Engineer.
Stretcher two fold type, made of high quality
aluminium alloy tubes. Aprox. Dimensions: unfolded
2100x560x150mm and folded 1100x200x110mm,
28011 max weight 8kg, suitable for load weight upto 150kg, Nos 3,678
to be supplied with sturdy carry case as approved by
Engineer.
Set of 4 Fire buckets (10Ltrs) capacity with one
28012 stand and cover suitable for switching station/TSS set 7,959
and as approved by Engineer.
Portable Fire Extinguisher Dry Chemical powder
Type as per IS:2171, ISI marked (10 kg OR 2 Nos X
28013 Each 2,997
5 kg as required at site and as approved by
Engineer).
Portable Fire Extinguisher Dry Chemical powder
Type, suitably mounted on trolley as per IS:10658,
28014 Each 10,399
ISI marked (25 kg capacity) with minimum discharge
range 6 mtrs.
D Shackeles set of alloy steel consisting one no of
each size (1”, 3/4”, 5/8”, 1/2”) upto 5T load capacity
28015 Set 2,839
as per IS:6132 suitable for use in TRD works.

Set of Steel slings with eye on each end of 8mmX2m


28016 Set 3,548
& 12mmX3m length.
Stainless Steel Digital micro meter suitable for
measuring 0-25mm dia, resolution 0.001mm and
28017 accuiracy of (+/-)1µm. Mitutoyo make or equivalent Nos 11,793
as approved by Engineer.
Bench Vice 6” suitably mounted on steel table as
28018 Nos 20,026
approved by Engineer.
Canvass Tarpaulin 12mx12m with ropes and spikes
28019 of adequate size as approved by Engineer. Nos 5,676

TESTING AND MEASURING EQUIPMENTS


Portable 5kVA Silent Diesel Gen Set with battery
push button start. Make: KOEL/Honda/Mahindra or
28020 Set 2,17,930
as approved by Engineer.

Binoculars Nikon-8252 ACULON A211 10-22x50


28021 zoom Binocular or equivalent as approved by Nos 15,324
Engineer.
Vernier Calipers Digital, range 0-200mm Mitutoyo
28022 make Model 500-197-30 or equivalent as approved Nos 15,246
by Engineer.
Trans-receiver, VHF, hand held walkie–Talkie set
5W (tuned for rated power of 5watts), 16 channels,
synthesized with 2200 mAH, Ni-Mh Battery pack
along with one spare battery pack of capacity
28023 2200mAH and rapid charger suitable to work on Nos 17,212
230V AC as per details enclosed. The VHF Walkie-
Talkie shall be MIL standard compliant for 810.
Make Motorola GP 328/Kenwood TK-2000 as
approved by Engineer.
Digital multi-meter 1000V, 10A Motwane make
28024 (a) model DM352 or superior as approved by Engineer. Nos 15,687

High sensitivity Digital multi-meter for measuring


AC/DC voltage, AC/DC currents, resistance,
28024 (b) frequency, capacitance. Megger make model Nos 38,264
AVO410 or superior as approved by Engineer.
Aluminium self supporting Stool type Magjic pole
28025 ladder-8’ long Make: Sumer or equivalent as Nos 7,217
approved by Engineer.
Drop Out Fuse pull rod made of fibre body, extension
type, suitable for use on 25kV OHE as per RDSO
28026 spec No: ETI/PSI/14(1/86) and CORE/ALD drg No. Nos 6,765
POWER/RLY/1849 as approved by Engineer.

1/2" Square Drive Socket Set containing 22 sockets


with 5 attachments packed in power coated carrying
28027 case. Make Taparia Model S11MXL or equivalent as Set 4,989
approved by Engineer.
Transformer oil Acidity testing Kit with all
28028 Set 14,194
accessories.
Portable arc welding machine 250A capacity, rated
out put current 10-250Amps, rated out put voltage
28V, Rated input power-5kVA, electrode size &
welding thickness 0.5mm to 3.15mm suitable to work
28029 on 230 V ± 15%, 50Hz single phase AC supply, IP23 Each 16,582
protection complete set with copper holder, earth
clamp and PVC copper cable of suitable size of 10m
length.
Digital Tong Tester suitable for measuring AC
28030 current 600Amp, Megger make DCM 340 or FLUKE Nos 11,080
376 or as approved by Engineer.
Portable hand grinding machine to work on 230V,
28031 50Hz, AC supply make MASTER or superior as Nos 4,767
approved by Engineer.
28032 DELETED
Digital breaker time interval meter suitable for
measuring open/close time of CBs/interrupters used
in TSS as per specification given below:-(a) Display:-
4 digital LED display with 7 segment LED (b) Poles:-
Three, (c) Range: 0.1m Sec to 9999 Sec (d) 19,235
28033 Nos
Accuracy :-±0.1%-± 1 count (e) Power:- 220-250V,
AC single phase (Make: NTPL Model: NTT4DSA-5R
or Anuvidyut Pvt Ltd Model : TYPE 1425
or equivalent as approved by Engineer).

28034 DELETED
28035 DELETED
Insulation Megger with voltage selectable range of
250V, 500V, 1000V digital numeric display and IR
measurements upto 999M Ohms in hard carrying 94,387
28036 Nos
case with all standard accessories similar to Megger
make model MIT310 or superior as approved by
Engineer.
Supply of Automatic Transformer Oil BDV Testing Kit
suitable for working on 230V AC single phase supply
in colour display and printer with temperature sensor
to detect oil temperature automatically, HV switch off
28037 time <10us automatically if an established arc of Nos 3,80,714
4mA occurs for 5 ms as per IEC 156 similar to
Megger make model OTS100AF or HV Diagnostic
BA100 or superior, as approved by Engineer.

Transformer oil filtration plant 125Litre per hour


capacity, portable type, suitable to work on 230V
28038 Nos 2,83,856
single phase AC supply, as approved by Engineer .

Auto transformer (Close type dimmer), Input voltage


28039 0-270V AC, out put current 0-10A. AEC make or Nos 11,181
superior as approved by Engineer.
Load cell tester suitable for 40AH and 200AH battery
28040 Nos 2,839
as approved by Engineer.
Supply, installation and commissioning of hydraulic
insulator testing machine for testing tensile load
strength of 25kV, Porcelain and composite insulators
28041 as per RDSO specn.No TI/SPC/OHE/INSTEST/0090 set 3,69,414
(02/2009) with A&C No-1 or latest.

Spanners set consisting of 4 sets of double ended


Ring spanner & 4 sets of double ended Flat type
28042 spanner, 12 pieces in each set (6mm to 42mm size), Set 13,648
Gedore or Taparia make with ISI Mark or as
approved by Engineer.
52 pieces Socket set (box spanners) with storage
28043 case. Cogex make or similar as approved by Set 10,236
Engineer.
Supply, testing and commissioning of primary current
injection test system 3000A, 20kVA burden suitable
for testing protection system of TSS including CT,
CB, interrupters, relays etc and suitable to work on
28044 230 V single phase AC supply. Each 17,93,466
Model:Megger Model ODEN AT/2S or Omicron
CPC100+CPCB2 or Doble M7100 or superior or as
approved by Engineer.

Insulation tester with voltage selectable range of


250V, 500 V, 1000V, 2500V and 5000V digital
numeric display with Insulation (InS), Polarisation
Index (PI) and variable time test modes and IR
28045 Each 2,04,080
measurements upto 1000G Ohms in hard carrying
case with all standard accessories similar to Megger
make model BM 5200 or Fluke 1550C or superior as
approved by Engineer.
Supply of Digital Ground/Earth tester suitable for 2, 3
& 4 point ground rod and soil resistivity testing having
range 0.01Ω to 20kΩ with all standard accessories 2,18,495
28046(a) Each
and carrying case similar to Megger Make Model
DET4TR2 or Fluke 1623 or superior and as
approved by Engineer.
Supply of Digital Ground/Earth tester clamp type
suitable for ground earth electrode earth resistance
measurements without opening earth connections.
Range 0.05 ohm to 1500 ohms, current 0.5mA-35A,
Jaw size: 55X39mm, The meter shall be CATIV600V,
Pollution Degree 2 and IP30 with jaws closed and
28046(b) Each 66,682
256 data storage facility, 4 digit LCD display,
computer interface port, with all standard accessories
and carrying case similar to Megger Model DET14C
or Fluke Model 1630 or superior and as approved by
Engineer.

Thermal Imaging Camera (inclusive of software)


as per RDSO specification No.
TI/SPC/OHE/TIPS/1031 (Dec'2013) or latest, 5,08,683
28047 Each
temperature range from (-20) to (500) degree
centigrade (CEM model DT-9885 or superior as
approved by Engineer).
Supply of fully Automatic Capacitance and TAN
DELTA test set suitable for input power of 240V
single phase, AC and output voltage 0 to 12kV
continuously adjustable, 3.5 kVA, 1-500 Hz, 300 mA
(4 minutes) designed for condition assessment of
electrical insulation in high voltage apparatus such
as transformer bushings, circuit breaker, cables,
28048 lightning arrestor at TSS with built-in temperature Each 15,17,409
correction system, automatic interference
suppression for outdoor switchyards, calibrator box,
data storage and display system on laptop with
associated software (or on board computer system)
similar to Megger make model DELTA 4110A or
Doble M7100 or Omricon Testrano+TD1 or as
approved by Engineer.
Supply, Installation, Testing & Commissioning of
GPS based OHE monitoring & current collection
system Oliver–G as per RDSO spec No
28049(a) Each 3,30,353
TI/SPC/OHE/OLIVER/0051(01/15) or latest along
with all accessories/authentic software as per
mentioned specification necessary for mapping.
Route Mapping of OHE Assets i.e OHE/Pole mast
with Oliver-G with GPS system for current collection
28049(b) test of all the lines of given section of OHE and TKM 1,961
supply/loading of GPS mapping data.
Supply and Commissioning of Fully Automatic
Transformer Turn ratio Analyser, capable of
measuring turn ratio upto 1:10000, micro-controller
operated, with built in printer, LCD screen for display,
IP-54 compatible, single unit design and supplied
28050 with standard accessories, hard carry case, software Each 3,09,017
with touch screen facility etc. Megger Make model
TTRU3 or Omricon Testrano or Doble M7100 or as
approved by Engineer.

Supply of Digital micro-ohm meter capable of


measuring resistance range from 1 micro ohm to
2000 ohms, with 1 micro-ohm resolution for inductive
28051 and resistive loads. Megger Make model MTO210 or Each 68,355
Motwane make model LR 2045-S or superior model
as approved by Engineer.

28052 Furniture for OHI/PSI Depot:


(a) Chairs with cushioned back & Hand rests. Each 1,345
(b) Chairs with cushioned back. Each 1,120
Supervisor's Table (1500mm x 900mm) with sun
(c) Each 7,847
mica top & bottom side drawer with lock.
Ministerial Staff Table (1200mm x 900mm) with sun
(d) Each 6,725
mica top & single side drawer with lock.
(e) Steel Almirah (78x36x22 inch). Each 10,089
(f) File Racks Steel. Each 3,363
(g) 18 Pigeon Holes Locker Steel. Each 11,209
Desktop Computer (Intel Core i3 9100 8GB/1000 GB
(h) Each 52,327
HDD/ Window 10 or superior).
Schedule-29000
SCADA
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Preparation and Supply of Design & Drawing for
29001 SCADA-1 SCADA at RCC,TSS,SP & SSP. Job 0 2,19,752

Supply, Erection, Testing & Commissioning of


29002 SCADA-2 SCADA equipments at Remote Control Centre RCC Job 65,98,433 5,98,288
(as per RDSO latest specification).
SCADA- Supply, Installation & Testing of standard SCADA
29002A Job 35,14,343 3,98,223
2(a) software.
Supply, Erection, Testing & Comissioning of RTU's
29003 SCADA-3
(as per latest RDSO specifications) at -
SCADA-
29003A FP/TSS. Each 13,84,959 1,00,065
3(a)
SCADA-
29003B SP. Each 10,37,669 69,883
3(b)
SCADA-
29003C SSP. Each 10,37,669 69,883
3(c)
Supply, Erection, Testing & Commissioning of
29004 SCADA-4 Maintenance Free/Low Maintenance type 200AH Set 15,29,770 56,378
Lead Acid battery.
Supply, Erection, Testing and Commissioning of 2x5
SCADA- kVA dual redundant hot standby UPS System as per
29004A Set 5,02,470 39,084
4(a) latest RDSO Specification.
29005 SCADA-5 Supply & Erection of Furniture at RCC. Set 4,43,613 33,263
Modification/ Upgradation, Testing & Commissioning
in existing standard SCADA software at RCC
Equipments for configuration, integration/ hooking up
29006 SCADA-6 Job 0 8,29,528
of additional RTUs of adjacent section with master
station i.e. - RCC,TSS,SP and SSP.

Supply, Erection, Testing and Commissioning of


29007 SCADA-7 GPS recevier with 3 nos digital clock at RCC. Job 3,91,172 24,070

Supply, Erection, Testing and Commissioning of


29008 SCADA-8 Hardware & Software for TPC/Head quarter and Job 10,90,496 1,05,062
Railway Board.
Supply of 10% spare cards for operation &
29009 SCADA-9 maintenance as per latest RDSO Specification. Job 14,49,787 0

Supply of Spl. T & P for maintenance as per latest


29010 SCADA-10 Set 3,77,211 0
RDSO Specification.
SCADA- Erection, Integration, Testing & Commissioning for
29011A existing and new equipments for TSS. Job 0 2,32,816
11(a)
SCADA- Erection, Integration, Testing & Commissioning for
29011B existing and new equipments for SSP. Job 0 77,607
11(b)
SCADA- Erection, Integration, Testing & Commissioning for
29011C existing and new equipments for SP. Job 0 1,94,014
11(c)

29012 SCADA-12 Integration of the Energy Data of a TSS from


SCADA-
29012A RCC to SEMC. Job 0 1,26,553
12(a)
SCADA-
29012B SEMC to RCC. Job 0 1,26,553
12(b)
Common Schedule of OHE/TSS
Schedule 30000A
Galvanised Steel Strructures
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Supply and Erection of all types of galvanised Steel
CS-9 Structures, Small Parts Steel etc. MT 1,17,732 3,713
30009
(a) Extra on Erection under Power Block. MT 0 3,713
(b) Extra rate on Manual Erection. MT 0 1,857
Schedule 30000B
Concrete for Fondation
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Providing and laying of concrete for foundation and
plinth in all types of Soils using M-10 grade concrete
for main foundation and M-15 grade concrete for
30006A CS-6 (a) grouting and muffing including nominal reinforcement CUM 5,795 1,875
wherever required as per RDSO drawings.

Providing and laying of concrete for foundation and


plinth in all types of Soils using M-15 grade concrete
for main foundation and M-20 grade concrete for
30006B CS-6 (b) grouting and muffing including nominal CUM 6,846 1,875
reinforcement wherever required as per RDSO
drawings.
Providing and laying of concrete for foundation and
plinth in all types of Soils and Soft/Hard Rock using
M-20 grade concrete for main foundation and M-20
30006C CS-6 (c) grade concrete for grouting and muffing including CUM 7,417 1,875
nominal reinforcement wherever required as per
RDSO drawings.
100% Extra Payment over CS-6(a), (b) and (c) for
foundation and plinth in Hard Rock/heavy concrete
30007A CS-7 (a) requiring chiseling/Blasting/machine breaking. CUM 0 1,875

50% Extra Payment over CS-6(a), (b) and (c) for


foundation and plinth in Soft Rock/Hard soil requiring
30007B CS-7 (b) chiseling/Blasting/machine breaking and in Black CUM 0 938
Cotton Soil.
Extra payment for grouting of masts/portals in yards
30007C CS-7 (c) using M-30 concrete and expansive admixture Each loc 0 423
compound as per RDSO guidelines.
Providing and laying of Reinforced Concrete for
Pier/Column/Pile, Cable Trench and Trench Cover
30008 CS-8 and special designed foundations requiring CUM 0 8,630
reinforcement.
Schedule 30000C
Miscellineous Common Items of OHE/TSS
Rate
Item No. SOR ITEM Description Unit
Supply Erection
Supply, Erection, Testing and Commissioning of
CS-1 25kV, 1600Amp Vacuum Interruptor. Each 4,29,793 4,913
30001
CS-1(a) Extra on erection under Power Block. Each 0 4,913
Supply, Erection, Testing and Commissioning of
CS-2 25kV Potential Transformer Type-I or Type-II. Each 87,580 925
30002
(a) Extra on erection under Power Block. Each 0 925
Supply, Erection, Testing and Commissioning of
CS-3 42kV Lightning Arrestor with surge monitor, counter Each 31,583 648
30003
and cable.
(a) Extra on erection under Power Block. Each 0 648
30004 CS-4 Supply and Installation of cables for SWS/TSS. Mtr 244 19
Supply, Erection, Oil Filtration, Testing and
Commissioning of 25kV/240V, 5kVA Auxilliary (LT)
supply transformer with 25 KV D. O. fuse switch
CS-5(a)
assembly, anti climbing device, Arcing horns, post
30005A insulators, copper jumper and earth electrode etc:

(i) With Porcelain Insulators 1050mm CD. Set 84,592 12,380


(ii) With Composite Insulators 1050mm CD. Set 83,300 12,380
(iii) Extra on erection under Power Block. Each 0 12,380
Supply, Erection, Oil filtration, Testing &
Commissioning of 25kV/240V, 10kVA Auxiliary (LT)
Supply Transformers oil type with DO fuse switch,
CS-5(b)
anti climbing device, Arcing horns, pedestal
30005B insulators, copper jumper and earth electrode etc:

(i) With Porcelain Insulators 1050mm CD. Set 94,300 12,380


(ii) With Composite Insulators 1050mm CD. Set 93,006 12,380
(iii) Extra on erection under Power Block. Each 0 12,380
Supply, Erection, Oil filtration, Testing &
Commissioning of 25kV/240V, 25kVA Auxiliary (LT)
Supply Transformers oil type with DO fuse switch,
CS-5(c)
anti climbing device, Arcing horns, pedestal
30005C insulators, copper jumper and earth electrode etc:

(i) With Porcelain Insulators 1050mm CD. Set 2,38,508 12,380


(ii) With Composite Insulators 1050mm CD. Set 2,37,216 12,380
(iii) Extra on erection under Power Block. Each 0 12,380
Supply and erection of Fencing Panels, Uprights,
30010 CS-10 Mtr 3,488 117
Gate and Anti-Climbing device.
Supply and erection of Aluminium Jumper with
30011 CS-11 Each 2,746 291
Fastners.
Supply and erection of Copper Strips for equipment
30012 CS-12 Mtr 1,657 175
earthing.
30013 CS-13 DELETED
Supply and spreading of gravel/ ballast in the
30014 CS-14 Cum 1,245 9
switching yard (TSS/SP/SSP).
Dismantling of Redundant foundations with
compressor powered machines/manually with
30015A CS-15(a) contractor’s own men and material including Nos 0 5,501
consumables like Diesel Oil etc.
Extra charges for retrieval of OHE masts or
portal/TTC upright from the foundation and stacking Each
30015B CS-15(b) it at nominated place as per the directions of 0 3,067
location
Engineer.
Shifting of mast along with foundation block and un-
Each
30015 (c) CS-15(C) supporting and supporting back the OHE, if required. 0 12,127
location

Monthly charges for one crane operator for full time


operation for one crane including Monthly charges for Man
30016 CS-16 0 27,727
one Watch & Ward for one crane. Month

Supply, Erection, Testing and Commissioning of anti


theft transformer 240Volt/2.2kV, 5kVA with DO Fuse
switch excavation of cable trench, laying of cables, Each
30017 CS-17 earthing, jumpering, DG set including dismantling of location 88,589 61,604
above equipments as per directions of Engineer.

Dismantling of Switching Station (SWS) complete


with building foundation, equipment and gantry
structure with compressor powered
machines/manually with contractor’s own men and Each
30018 CS-18 material and loading, transportation, unloading and 0 83,729
SWS
handing over of released material to nominated
person at specified place as per instructions of the
Engineer.
Hiring charges for semi skilled Labour with proper
tools for working during Non interlocking period. Man-
30019 CS-19 0 433
Days
supply and Laying of dry stone boulder pitching of
30020 CS-20 aprox 300mm thickness in exposed slopes at SWS, cum 976 243
TSS and OHE Foundations etc .
Extra Earthwork in filling at SWS, TSS and OHE
30021 CS-21 Foundations. cum 228 56

Drilling of 50mm dia holes in the existing RCC trestle


beam/pier/mass concrete beam/Flat hard rock/heavy
concrete bed, foundation, structure/ lined or unlined
tunnels to the depth between 450mm to 1250mm
with pneumatic drillers, compressor etc. and making
the hole surface fit for insertion of bolts with all lead
and lift. Supply and grouting of suitable galvanized
MS bolts of size upto 32mm dia of varying length Each
30022 CS-22 including nuts, check nuts, washers etc.Pressure Mast 26,348 6,587
Grouting the drilled holes (50mm dia) by epoxy /Bracket
Loc
grouting of approved quality of epoxy resin hardener
and thinner. Payment includes supply, erection,
grouting with suitable size bolts at regular intervals of
earthing strip and its connection to brackets etc
wherever required in tunnels. (All labour and
materials shall be by the contractor).
Supply and Erection of 25kV, 1250A, Single Ploe
30023 A CS-23(a) Isolators with insulator, with/without earth contact Each 65,036 3,264
assembly and with /without interlock.
Supply and Erection of 25kV, 1250A, Double Pole
30023B CS-23(b) Isolator with insulator, with/without earth contact Each 1,05,517 3,264
assembly and with /without interlock.
Supply and Erection of 25kV Single Pole Isolator
30023C CS-23(c) 1600Amp with insulators, with/without earth contact Each 51,623 3,264
assembly and with /without interlock.
Supply and Erection of 25kV Double Pole Isolator
30023D CS-23(d) 1600Amp with insulators, with/without earth contact Each 97,666 3,264
assembly and with/without interlock.
Supply and Erection of 25kV Single Pole Isolator
30023E CS-23(e) 3150Amp with insulators, with/without earth contact Each 95,883 3,264
assembly and with /without interlock.
Supply and Erection of 25 kV Double Pole Bus
Coupler Isolator 3150Amp with insulators, with
30023F CS-23(f) Each 1,94,486 3,264
/without earth contact assembly and with /without
interlock.
Extra on erection under Power block for Single Pole
30023G CS-23(g) Each 0 3,264
/Double Pole Isolators.
Excavation of Earth, burying of Rail/OHE mast and
connecting it with TSS/SSP/SP and running tracks
30024A CS-24(a) job 0 17,545
including covering back and proper dressing up of
earth (Rail will be supplied by RVNL).
20% Extra payment on CS-24(a) for excavation in
30024B CS-24(b) Each 0 3,163
hard soil.
Supply and erection of earth lead using 75x8mm GI
30024C CS-24(c) flat laid in ground/exposed as per the site Mtr 592 281
requirement.
Watching and guarding of OHE along the track after
30025 CS-25 EIG for 12 hrs each day on administrative reasons. 0 0

Per
(a) Person with arms. Person/ 869 0
day
Per
(b) Person without arms. Person/ 791 0
day
Supply & Erection of 25kV Support/ Post insulators
30026 CS-26 Each 4,923 185
with fittings and fasteners.
SCHEDULE - 33000
ELECTRICAL GENERAL SERVICES WORKS
This schedule shall be read in conjunction with its Explanatory Notes and Technical Specifications for detailed
Rate
Item No. SOR ITEM Description Unit
Supply Erection
SECTIOIN- A : ELECTRIFICATION OF STAFF QUARTERS, GATE MAN
LODGES AT LEVEL CROSSINGS
Electrification of staff quarter complete with point
wirings, circuit wirings, sub main wirings etc. with Fire
Retardant (FR) PVC insulated, multistranded, copper
conductor, single core cable on surface/ in recessed
PVC conduits, along with provision of luminaries with
lamps, call bells, ceiling fans, exhaust fans,
33001 distribution boards, loose wire box, geyser, energy
meters in M.S. box including earthing with G.I. pipe
electrode etc. as per scale of fittings, cable sizes,
nos. of points permissible in each circuit and sub
main/s etc. for each type of quarter as indicated in
Explanatory Notes.
i) Type - I quarter Each 0 42,924
ii) Type - II quarter Each 0 1,16,348
iii) Type - III quarter Each 0 1,39,693
iv) Type - IV quarter Each 0 2,33,439
v) Type - V quarter Each 0 2,76,366
vi) Type - VI quarter Each 0 3,55,025
vii) Type - VII quarter Each 0 4,16,281
viii) Extra for stair case light point controlled with two nos. Each
0 923
two way switches
Electrification of gate man lodge complete with point
wirings, circuit wirings etc. with Fire Retardant (FR)
PVC insulated, multistranded, copper conductor,
single core cable on surface/in recessed PVC
conduits, including provision of luminaries with
33002 lamps, ceiling fan, distribution board, earthing with Each 0 26,707
G.I. pipe electrode etc. as per scale of fittings, cable
sizes, nos. of points permissible in each circuit and
sub mains as indicated in Explanatory Notes.

Electrification of service buildings, passenger shelter,


sheds, pump house, sub-station buildings, offices etc
33003 and additional requirement of points in quarters, LC
gates etc.
Wiring for light/ ceiling fan/exhaust fan/call bell/light
plug/ group etc. points including circuit wiring, sub
main wiring with Fire Retardant (FR), PVC insulated,
multistranded, copper conductor, single core cable
on surface/in recessed PVC conduits, distribution
33003 (i) boards, sub distribution boards, earthing etc. as Point 0 1,666
required. Wiring shall be done as per sizes of cables,
no. of points permissible in each circuit and sub
mains as indicated in Explanatory Notes.
Wiring for power plug point including circuit wiring,
sub main wiring with Fire Retardant (FR), PVC
insulated, multistranded, copper conductor, single
core cable on surface/in recessed PVC conduits,
distribution boards, sub distribution boards, earthing 0 3,059
33003 (ii) Point
with G.I. pipe electrode etc. as required. Wiring shall
be done as per sizes of cables, no. of points
permissible in each circuit and sub mains as
indicated in Explanatory Notes.

Extra for provision of industrial type iron clad plug


33003 (iii) socket with 32A DP MCB in M.S. Box. Point 0 835

Multiplug points (power strip 3 no. 6A socket


33003 (iv) controlled by 16 A switch) similar to Legrand cat no. No. 1,988 98
6745.48 OR as approved by Engineer.
Supply of Light meter measuring up to 200000 lux
with battery and carry case (HTC instruments make
33004 Nos 1,891 0
ref LX-103 or equivalent as approved by Engineer).

SECTION - B : PROVISION OF LUMINARIES, FANS, WATER COOLERS


ETC.
33005 DELETED
Supply, Installation, Testing and Commissioning of
light sensitive street light controller, 25kW for street
light/ High mast complete with infrared sensors,
33006 contactors and MCB, terminal board etc. for 25 KW No. 49,440 2,150
load, Operative Voltage 185-275 V AC. Make: Bajaj
Energy pack or equivalent as approved by Engineer.

33007 DELETED
Supply, Installation, Testing and Commissioning of
230V AC ceiling fan 1400mm with double ball
bearing and suitable capacitor complete with wiring
33008 with 1.5sq.mm FR PVC insulated copper conductor, No. 2,504 393
single/ three core cable as instructed etc. as
required.
Supply and Erection of 1200mm BLDC fan with
33008A No. 2,653 168
remote.
Supply and Fixing of stepped type, electronic fan
regulator with suitable rating for the Ceiling Fan on
the existing phenolic laminated sheet cover plate/
33009 No. 470 105
modular plate of switch box, including connections,
testing and commissioning as required.

Supply, Installation, Testing and Commissioning of


33010 A 11-15W LED lamp as approved by Engineer. No. 246 39

Supply, Erection, Testing and Commissioning of


Recessed type LED luminaries for 2x2 Grid ceiling,
powder coated, CRCA housing, high efficiency
33010B reflector & diffuser cover, system wattage 35-45W No. 4,781 877
suitable to work on 220-240V AC supply.
Supply, Erection, Testing and Commissioning of LED
down lighter having pressure die cast aluminium
33010C housing white powder coated and acrylic cover, No. 1,802 651
system wattage 14-16w suitable to work on 220-240V
AC supply.
Supply, Erection, Testing and Commissioning of LED
Street light fitting, pressure di-cast aluminium
33010D housing with suitable cover, suitable to work on 220-
240V AC supply with system wattage as under :

(i) Fitting 43-48 W No. 6,962 586


(ii) Fitting 35-40 W No. 5,942 586
(iii) Fitting 70-74 W No. 10,778 586
(iv)Fitting 23-27 W No. 2,632 586
Supply and Installation of surface /wall mounted,
LED batten type light fitting complete with LED Lamp
33010E with system wattage 18-22W suitable to work on 220- No. 1,522 141
240V AC supply as approved by Engineer.

Supply and Installation of 7 watts sleek LED mirror


light with diffuser and Led lamp similar to Crompton
33010 F Greaves Ltd Model LINNET LCL-07-CDL complete No. 2,103 37
or superior as approved by Engineer.

Supply, Erection, Testing and Commissioning of LED


flood light fitting, pre die cast aluminium, IP-65 with
33010G high power LED as light source with system wattage No. 24,647 701
140-150W suitable to work on 220-240V AC supply
as approved by Engineer.
Supply, Erection, Testing and Commissioning of LED
flood light fittings pre die cast aluminium IP-65 with
33010H high power LED as light source with system wattage No. 34,755 701
200-210W suitable to work on 220-240V AC supply
as approved by Engineer.
Supply, Erection, Testing and Commissioning of LED
flood light fittings pre die cast aluminium IP-65
33010 I with high power LED as light source with system No. 16,907 701
wattage 90-110W suitable to work on 220-240V AC
supply as approved by Engineer.
Supply, Erection, Testing and Commissioning of
exhaust fan suitable for 1-phase, 230Volts, AC
supply system complete with capacitor, louver
shutters, grouting bolts with nuts, making opening/
modification in the wall to suit the size of the fan,
33011A
making good the damages, connections with
1.5sq.mm FR, PVC insulated, multi stranded copper
conductor, single core/ three cable as instructed,
earthing etc. as required:

AC exhaust fan 300mm, 900 rpm with/ without louver


(i) No. 3,715 581
shutters.
(ii) AC exhaust fan 150mm with louver shutters. No. 2,066 444

(iii) AC exhaust fan 450mm with/ without louver shutters. No. 8,914 444
Supply, Installation, Testing and Commissioning of
wall mounted single phase 230V, 50Hz air
33011B No. 12,141 1,348
circulating fan of 700-750mm sweep including all
accessories.
Supply, Installation, testing and Commissioning of air
33011C curtain single phase 230V, 1000mm size. No. 25,295 1,100

Supply, Installation, testing and Commissioning of


AC bracket fan 400mm similar to Havells Swing
33011D No. 5,098 223
Remote or equivalent as approved by Engineer.

Supply, Erection, Testing and Commissioning of self


contained drinking water cooler 150 liters capacity
complete with all connected standard fittings,
accessories etc. and 5kVA, wall mounted, I.C.
33012 controlled electronic auto-voltage corrector with time Each 69,316 14,978
delay relay, supply and erection of earth electrode
and connection to earthing system etc. as required.

SECTION - C : L.T. SWITCH BOARDS AND FEEDER PILLAR


Supply, Erection, Testing and Commissioning of
33013 cubical type, wall mounted, dust & vermin proof, L.T.
switch board of different capacities.
LT switch board 125Amp comprising of the items
indicated as under
i) incoming MCCB 125A, 4 pole, 35kA, fixed type
(Ics=100%Icu) - 1 No
ii) Outgoing MCCB 63A, 25kA, fixed type (Ics=100%
Icu) - 4 Nos
(a) iii) Outgoing MCB 40A, 4 pole, 10kA - 4 Nos No. 1,02,571 16,110
iv) Outgoing MCB 32A, double pole,10kA-4Nos
v) Outgoing MCB 32A, Single pole, 10kA-4Nos
vi) Sleeved/Epoxy coated copper busbar 250A in bus
bar Chamber
vii) CT's Indication lights.
LT switch board 63 Amp comprising items indicated
as under
i) incoming MCCB 63A, 4 pole, 35kA, fixed type
(Ics=100%Icu) - 1 No
ii) Outgoing MCCB 40A, 4 pole, 25kA, fixed type
(Ics=100%Icu) - 3 Nos
(b) iii) Outgoing MCB double pole, 6-32A, 10kA- No. 93,507 14,688
16 Nos
iv) Outgoing MCB Single pole,6-32A, 10kA-
8Nos
v)Sleeved/Epoxy coated copper bus-bar 200A in bus
bar Chamber
vi) Indication lights.
33014 DELETED
Supply, Installation, Testing & Commissioning of
33015 weather proof, LT. feeder pillar of different capacities:
LT feeder pillar 63Amp comprising of the items
indicated as under ;
(i) incoming MCCB 63A, 4 pole, 35kA, fixed type
(Ics=100%Icu) - 1 No
ii) Outgoing MCCB 40A, 4 pole, 25kA, fixed type
33015A (Ics=100%Icu) - 4 Nos No. 1,06,059 16,655
iii) Outgoing MCB double pole, 40A,10kA-2Nos
iv) Outgoing MCB Single pole, of 40A, 10kA- 4 Nos
v) Sleeved/Epoxy coated copper bus-bar 200 A in
bus bar Chamber
vi) Indication lights.
LT feeder pillar 125Amp comprising of the items
indicated as under
i) incoming MCCB 125A, 4 pole, 35kA (Ics=100%Icu)
- 1 No
ii) Outgoing MCCB 63A, 4 pole, 25kA (Ics=100%Icu) -
4 Nos
iii) Outgoing MCB 40A, 4 pole, 10kA - 4 Nos
33015B iv) Outgoing MCB 32A, DP, 10kA, 4Nos No. 1,26,580 19,882
v) Outgoing MCB Single pole 32A, 10kA-4Nos
vi)Modular digital time switch and 3 phase contactor
63 A - 2 Set
vii) Sleeved/Epoxy coated copper busbar 250A in
bus bar Chamber
viii) Indication lights.
LT feeder pillar 250Amp comprising of the items
indicated as under
i) Incoming MCCB 250A, FP 35kA (Ics=100%Icu)
Fixed Type - 1 No
ii) Outgoing MCCB 125A, FP 35kA (Ics=100%Icu)
Fixed Type - 2 Nos
iii) Outgoing MCCB 63A, FP 25kA (Ics=100%Icu)
33015C Fixed Type - 4 Nos No. 1,96,258 30,824
iv) Outgoing MCB 40 Amps, FP, 10kA - 4 Nos
v) Outgoing MCB 32 Amps DP 10kA - 4 Nos
vi) Outgoing MCB Single pole 32A, 10kA -4 Nos
vii) Modular digital time switch and 3 phase contactor
63 A - 2 Set
viii) Sleeved/Epoxy coated copper bus-bar 400A in
bus bar Chamber.
ix) Indication lights.
33016 DELETED
SECTION - D : EXTERNAL ELCTRIFICATION WORKS
Supply and Erection of different length, swaged type
steel tubular pole complete with the following :
a) Double door, weather proof MS. Junction box
(degree of protection not less than IP54) complete
with MCB 6Amps, copper bus bar for looping 4 -
core, 3 nos. LT cables and clamping with pole, as
33017 required
b) Casting of foundation with concrete of M10 grade
and providing muffing up to 300 mm above ground
levels, as required
c) Erection of GI pipe class 'B' ISI marked up to
junction box for passing cable.
(payment of G.I. pipe shall be made against the
relevant BOQ item).
7 Meter long pole with canopy type single pipe
i) No. 15,931 2,504
bracket ( for one luminary).
7 Meter long pole with canopy type double pipe
ii) No. 16,441 2,583
bracket ( for two luminaries).
iii) DELETED
33018 DELETED
Supply and Erection of GI pipe - class 'B' ISI marked
with accessories including bends etc. for support of
33019 cable with erected pole/ recessing in wall/ floor/
passing earth strip OR passing cable as required:

i) 32mm dia Meter 318 51


ii) 50 mm dia Meter 490 77
iii) 80 mm dia Meter 822 128
iv) 100 mm dia Meter 1,158 183
v) 150 mm dia Meter 1,884 297
Supply, Erection, Testing and Commissioning of
control and distribution panel for colour light
signalling supply in 25kV AC traction system as
33020 perRSDO technical specifications No.
TI/SPC/PSI/CLS/ 0020 (12/02) With A&C slips No. 1
to 4 or latest, connections as required:
i) For 5 -10 kVA AT No. 87,522 13,747
ii) For 25 kVA AT No. 1,86,213 29,247
33021 DELETED

SECTION - E : POWER SUPPLY DISTRIBUTION ARRANGEMENT


Supply, Installation, Testing and Commissioning of
11KV/440V, 50Hz, out door type, Delta/Star
connected, copper wound, DYn11, ONAN cooled,
33022 power distribution transformer (outdoor type)
conforming to IS:1180 (Energy Efficiency level shall
not be less than–II), complete with all accessories
and first filling of oil as required:
i) 100 kVA No. 3,22,036 57,954
ii) 250 kVA No. 6,98,202 93,845
iii) 500 kVA No. 12,67,590 1,20,824
Extra for providing fencing/ enclosure for above item
iv) as indicated in Explanatory Notes. Kg 96 22

Extra for construction of foundation for transformer


v) installation as required. Cu.M 6,131 1,734
Supply, Erection, Testing and Commissioning of 3
33023 pole, 11kV, 400A, gang operated switch complete No. 37,438 6,851
with drop out fuses etc. as required.
Supply, Installation, Testing and Commissioning of
11kV, 350MVA, 630A draw out type manually
33024 operated, 3 panel HT VCB board complete with CTs, Set 20,99,977 3,84,172
PTs etc. as required.
Supply, Installation, Testing and Commissioning of
17 panel LT switch board comprising of following :
i) incoming ACB 800A, 4 pole, 50kA (manual draw
out type ) with CTR 400/5A - 2 Nos
ii) ACB bus coupler 800A, 4 pole, 50kA (fixed type) -
1 No
iii) On load change over switch 400A, 4 pole,
utilisation Cat AC 23 - 1 No.
33025 iv) Outgoing switch fuse unit/ fuse switch unit cat AC No. 14,05,001 1,38,938
23 (TPN) with HRC fuses (250Amp)-4 Nos
v) Outgoing switch fuse unit/ fuse switch unit cat AC
23 (TPN) with HRC fuses 125 Amp -4 Nos.
vi) Outgoing switch fuse unit/ fuse switch unit cat AC
23 (TPN) with HRC fuses 63 Amp -5 Nos.
vii) Sleeved/ epoxy coated copper bus-bar - 800 A for
phase and 400 A for neutral.

Supply, Erection, Testing and Commissioning of 20


panel LT switch board comprising of following:
i) incoming ACB 800A, 4 pole , 50kA (manual draw
out type ) with CTR 800/5A - 2 Nos
ii) ACB bus coupler 1600A, 4 pole, 50kA (fixed type) -
1 No
iii) On load change over switch 800A, 4 pole, Cat AC
23 - 1 No.
iv) Outgoing switch fuse unit/ fuse switch unit cat AC
33026 23 (TPN) with HRC fuses 400 Amp) -3 Nos. No. 21,73,762 2,14,960
v) Outgoing switch fuse unit/ fuse switch unit cat AC
23 (TPN) with HRC fuses 250 Amp) -4 Nos
vi) Outgoing switch fuse unit/ fuse switch unit cat AC
23 (TPN) with HRC fuses 125 Amp -4 Nos.
vii) Outgoing switch fuse unit/ fuse switch unit cat AC
23 (TPN) with HRC fuses 63Amp-5
Nos.
viii) Sleeved/ epoxy coated copper bus-bar - 1600A
for phase and 800A for neutral.
33027 DELETED
33028 DELETED
Supply, Erection/ Fixing of fire extinguishing
equipments (ISI) Marked, Rubber mat (ISI marked),
G.I. fire buckets filled with clean dry sand held on
free standing steel stand, first aid box with medicine
(ISI marked) and associated materials, shock
33029 treatment chart on aluminium frame, schematic Set 83,447 13,105
diagram of HT/LT installation & transformer data on
white hylem sheet with aluminium frame & fixing/
providing in the sub station area as per details in
Explanatory notes.
Supply, installation, testing and commissioning of DG
set with acoustic enclosure, complete with AMF
33030 panel and all other accessories and construction of
plinth etc.
82.5kVA DG set with 160Amp, 4-pole, MCCB 50kA
(i) (Ics=100%Icu), 250Amps copper bus-bars, 4 pole Set 7,39,384 82,154
contactors 250Amp.
160kVA DG set with 250Amp, 4-pole, MCCB 50kA
(ii) (Ics=100%Icu), 400Amps copper bus-bars, 4 pole Set 12,16,626 1,35,180
contactors 400Amp.
250kVA DG set with 400Amp, 4-pole, MCCB 50kA
(iii) (Ics=100%Icu), 600Amps copper bus-bars, 4 pole Set 18,24,565 2,02,729
contactors 600Amp.
500kVA DG set with 800Amp, 4-pole ACB (MDO),
(iv) 800Amps copper bus-bars, 4 pole contactors Set 35,63,988 3,95,999
1000Amp.
Supply, Erection, testing and Commissioning of
125kVAR Automatic power Factor controller panel
33031 (capacitor bank) complete & connection with the No. 6,66,692 65,926
main panel as per site requirement.
SECTION - F : EARTHING ARRANGEMENT
Earthing with 3m long, 50mm dia, G.I. pipe class 'B'
earth electrode, adding the charcoal or coke and salt,
providing concrete enclosure and MS cover plate
33032 with lifting arrangement etc. including connections Job 3,501 550
with 4mm G.I. wire from earth electrode to switch
board / electrical equipment as required.

Earthing with 600mmx600mmx6mm thick G.I earth


plate, adding of charcoal or coke and salt, providing
33033 concrete enclosure and MS cover plate with lifting Job 3,889 609
arrangement, watering pipe etc. as required.

Earthing with 600mmx600mmx3mm thick copper


earth plate, adding of charcoal or coke and salt,
33034 providing concrete enclosure and MS cover plate Job 6,870 1,078
with lifting arrangement, watering pipe etc. as
required.
EARTH CONNECTIONS
Supply and Laying 25mm x6mm G.I. strip at not less
33035(i) than 0.50 meter below ground or in recess as Meter 78 14
required.
Supply and Laying 40mm x 6mm G.I. strip at not less
33035(ii) than 0.50 meter below ground or in recess as Meter 128 19
required.
Supplying and Fixing 40mm x 5mm copper strip on
33035(iii) surface or in recess or in 50mm dia G.I. pipe as Meter 1,019 161
required.
SECTION - G : CABLING
Supply and Laying of 1.1kV grade LT XLPE insulated
armoured, aluminium conductor cable, making good
the damages, end terminations with aluminium
33036 crimping socket/ plugs, provisions of cable route
markers, testing & commissioning etc. as required as
per technical specifications:
(i) 2 Core 16 sq.mm Meter 338 25
(ii) 2 Core 25 sq.mm Meter 392 25
(iii) 2 Core 70 sq.mm Meter 669 41
(iv) 2 Core 185 sq.mm Meter 1,380 56
(v) 4 Core 16 sq.mm Meter 438 25
(vi) 4.0 Core 35 sq.mm Meter 618 25
(vii) 4.0 Core 70 sq.mm Meter 986 41
(viii) 4.0 Core 120 sq.mm Meter 1,557 56
(ix) 4.0 Core 185 sq.mm Meter 2,179 56
(x) 4.0 Core 300 sq.mm Meter 3,531 103
(xi) Single Core 400 sq.mm Meter 1,135 103
(xii) Trenching work for single cable Meter 0 236
(xiii) Trenching work for multiple cables Meter 0 425
SECTION - H : ELECTRIFICATION BY HIGH MASTS
Supply, Erection, Testing and Commissioning of hot
dipped galvanised, high mast system complete with
all accessories, foundation, carriage arrangement
suitable for LED luminaries symmetrically arranged &
33037 control gear boxes and lighting finial etc., twin dome
aviation obstruction lights, control panel, multi core
flexible copper conductor cable, connection to
earthing system and fencing panel as per
requirement:
16 Meter high mast system, suitable for 6 to 9 nos
(i) Job 3,01,819 47,588
luminaires.
12 Meter high mast system, suitable for 6 to 9 nos
(ii) Job 2,62,390 43,509
luminaires.
25 Meter high mast system suitable for 9 to 12 nos
(iii) Job 4,60,936 51,667
luminaires.
SECTION - I : LAYING OF 11 KV / 33 KV CABLES
Supply and Laying of following sizes XLPE (E)
33038 insulated, armoured, aluminium conductor HT
cable:
(i) 11 kV, 3 Core 70 sq mm Meter 959 79
(ii) 11 kV, 3 Core 185 sq mm Meter 1,702 100
(iii) 33 kV, 3 Core 300 sq mm Meter 2,376 161
(iv) 33 kV, 3 Core 400 sq mm Meter 2,986 161
(v) Trenching work for cable Meter 0 257
Supply and Erection of RFID based electronic
Cable/pipe marker of reputed make suitable to work
upto 1.5m depth, min dia of 22 CMs, having inbuilt
GPS module for storing GPS coordinates, each
marker identification with 10 digits Hexadecimal
33039 (i) Code, 134kHZ frequency with self generated power Nos 2,248 54
source having capability to receive signals and
transmit back, working life >= 40 yrs. Marker to be
similar to Smart RFID marker SM 1500 or superior
as approved by Engineer.

33039 (ii) Supply and Erection of MS cable route marker. No. 411 19
Supply of outdoor type, heat shrinkable, end
termination kit, suitable for following cable sizes
XLPE(E) insulated, armoured aluminium conductor
33040
cable and making termination, connections with
overhead conductor, testing and commissioning etc:

(i) 3 core 11kV 70 to 185sq mm. No. 13,713 2,154


(ii) 3 core 33kV 240 to 400sq mm. No. 43,010 4,253
Supply, Testing and Commissioning of RFID Marker
locator 1.5m Depth Range, capable of acquiring and
storing min 8000 RFID marker records, having built
in GPS Module for logging GPS coordinates and
audio guidance for operator to navigate to locations
33041 of RFID markers, LCD/LED Display, data port to Nos 3,35,098 3,640
allow data output to PC with marker database
software. Similar to Smart RFID marker locator
Energy/SML or superior as approved by Engineer.

Supply & Erection of pre-stressed, cement concrete


(PSCC) double pole structure 9-11m long
suitable for 330Kg working load with top section
200mm x 105mm and bottom section 410mm x
140mm complete with 4 nos. channel cross arms & 2 82,854 8,192
33042(i) No.
nos cross bracing angles, clamps, bolt, nuts,
galvanized stay set, anti climbing devices, Danger
plates on the erected pole galvanised stay rod,
casting of foundation for poles & stay etc. as
required.
Supply of Material Fabrication and Erection of 9-
11m long 'H' pole (Double pole) with M.S Beam
150mm x 150mm, 4 nos. channel cross arms &
2 nos cross bracing angles, clamps, bolts, nuts,
33042(ii) galvanized stay set, anti climbing device, Danger No. 92,839 23,210
plates on the erected pole galvanised stay rod,
casting of foundation for poles & stay and painting
etc. as per concerned SEB requirements.
Supply and Erection of 11kV Porcelain Disc insulator
complete with galvanised iron hardware etc.
33043 including terminating with 11kV / 33kV overhead No. 1,493 148
conductor and dismantling, handing over works as
required.
Supply andLlaying of HDPE pipe as per IS:4984-
1995 (PN-4/PE-80, with minimum wall thickness of
6.2 mm) of different sizes under the Railway track/
33044(a) road etc after digging of trench and back filling with
excavated earth after laying of pipe and making good
the damages as required.
(i) Outer Dia-63mm Meter 91 24
(ii) Outer Dia-110mm Meter 266 24
(iii) Outer Dia-160mm Meter 552 24
(iv) Outer Dia-200mm Meter 880 24
(v) Extra for hard soil/soft rock locations. Meter 0 12
Supply and Laying of HDPE pipe as per IS: 4984-
1995 (PN-4/PE-80, with minimum wall thickness of
33044(b) 6.2mm) of different sizes under the Railway track
with trenchless boring method and making good the
damage as required.
(i) Outer Dia-63 mm Meter 91 1,255
(ii) Outer Dia-110 mm Meter 266 1,255
(iii) Outer Dia-160mm Meter 552 1,255
(iv) Outer Dia-200mm Meter 880 1,255
(v) Extra for hard soil/soft rock/hard rock locations. Meter 0 1,255
Supply and Laying of DWC HDPE pipe (either
single piece of full round or two half round split
pieces set) as per IS 14930 Part-II or latest(ISI
33044(c) marked) along with all accessories, digging of
trench and back filling with excavated earth after
laying of pipe and making good the damages as
required:
(i) Outer Dia-63mm Meter 80 24
(ii) Outer Dia-110mm Meter 157 24
(iii) Outer Dia-160mm Meter 271 24
(iv) Outer Dia-200mm Meter 390 24
(v) Extra for hard soil/soft rock locations Meter 0 12
SECTION - J : PROVISION OF PUMPS
Supply, installation, testing and commissioning of
submersible pump set suitable to operate on 3
phase, 415V, 50Hz AC supply along with control
33045
panel etc. complete for supplying water at suitable
discharge and head as per site requirement:

(i) 7.5 HP pump set Job 97,222 9,613


(ii) 5 HP pump set Job 89,034 8,806
SECTION - K : MISC. WORK
Co-ordination/ liasoning and chasing with State Utility
Company for availing new electrical connection/
augmentation of sanctioned load at stations, level
crossings etc. including applying for load, collection
of estimates for loads, modification of power line
crossings, arranging payment from RVNL, depositing Each
33046 0 10,374
payment to State Utility Company, arranging release Location
of load & other related works, payment to be made to
SEB for new connection, load augmentation,
modification of power line crossings etc. shall be
made by RVNL.

Design and Preparation of working & completion


drawings of all HT/LT electrical installations of the
project section where work is carried out such as
platform lighting, internal electrification of staff
33047 quarters, level crossings, station building, offices, Job 0 2,13,810
power line crossings, power supply distribution
arrangements of stations/sub-stations, electrification
of sub-station buildings etc & approval from the
competent authority.
Conducting check survey of the complete project
section to compile details of all the existing LT, HT
and EHT Power line Electrical overhead and
underground power /telegraphic/other lines running
along or across the track and recording
measurements of horizontal distances of structures
from the existing & proposed tracks, vertical
clearance of conductors & guard wire from rail level,
angle of crossings w.r.t. track, height and type of
towers/poles and preparation of lists as below:
i) List of Overhead/Underground Crossings infringing
33048 Job 0 1,68,796
and requiring modification. Proposed modification
may also be indicated.
ii) List of Overhead/Underground Parallel Alignments
infringing and requiring modification.Proposed
modification may also be indicated.

SECTION - L : GLOW SIGN BOARDS


Supply, Installation, testing and Commissioning of
outdoor type, single side /Double side Glow sign
boards/Pictorial signage boards with suspension/side
mounting/wall mounting type arrangements as
33049 required. Sq. Feet 434 65
(Payment for Double sided glow sign board shall be
made @ 150% of the rate of single sided glow sign
boards)
SECTIOIN -M : BATTERY CHARGING & PRE - COOLING
ARRANGEMENT
Supply, Installation, testing and Commissioning of
Silicon rectifier battery charging set conforming to
relevant IS (latest), suitable for operation on 3 phase
33050 4 wire, 415Volts AC supply system, 125Volts to No. 1,45,368 22,832
150Volts DC output, 200Amps capacity as per Tech
Specification including earthing, etc as required.

Fabrication, Supply, Installation, Testing and


Commissioning of 110Volts battery charging point
33051 suitable for operation on 150Volts DC supply system Job 5,257 827
including erection on MS channel, foundation etc
complete.
Fabrication, Supply, Installation, Testing and
33052 Commissioning of pre-cooling point as per details Job 14,225 2,234
given in explanatory notes.
SECTION - N : DISMANTLING WORKS
Dismantling of wiring installations of buildings, sheds,
quarters, etc. complete with luminaries, fans,
distribution boards, LT Panels and associated cables
including accountal, stocking, transportation and Each
33053 handing over of released materials to Electrical Station/G 0 9,838
department as directed by the Engineer and making ate lodge
temporary arrangements if required.

Dismantling of erected pole/overhead conductor, GI


wire, cross arm brackets, insulators, stay, luminary
etc including accountal, stocking, and handing over
33054 (i) the released materials to railway's authorized official No. 0 984
as instructed by the Engineer and making temporary
arrangements if required.
Dismantling of sub-station equipments such as
transformers, DG Set, HT & LT Panels, cables etc at
site including transporting, stocking and handing over
33054 (ii) Job 0 19,674
to Electrical department as instructed by the
Engineer and making temporary arrangements if
required.
Provision of temporary lighting arrangement with
1x40 watt FL tube light/CFL/LED/Halogen /MH/flood
light fitting and pedestal/ceiling fans, desert coolers
in temporary tents, buildings, goomties, on tracks, in
yard area including wiring, cabling, earthing etc as
directed by the Engineer and as per site requirement
33055 (i) for pre/post/during non-interlocking period, including Per day 0 29,511
providing stand by D.G set of suitable capacity and
deployment of staff for operation of DG set as per
site requirement.
NOTE: Normal power supply may be used, up to sanctioned
load, if surplus available at site.
Extra for operation and maintenance of temporary
wiring installations, replacement of consumables,
33055 (ii) supply of diesel oil, lub oil etc for operation of DG set Per day 0 5,856
etc.
Supply, Installation, Testing and Commissioning of
AC unit, complete with LCD display cordless remote,
min 3 star energy rating, suitable for 1-Phase,
33056 230Volts +10% AC supply including supply &
installation of suitable rating, wall mounted, IC
controlled electronic auto voltage corrector.

(a) 2.0 Tonne window type AC No. 51,965 3,934


1.5 Tonne window type AC(minimum 5-star rating)
(b) No. 40,250 3,934
2.0 Tonne split type AC, inverter type(minimum 3-star
(c) No. 70,212 3,934
rating)
(d) 1.5 Tonne split type AC, inverter type No. 50,092 3,934
Supply & Erection of G.I Octagonal pole including
digging of pit, making foundation with cement, sand
33057 & concrete in ratio 1:2:6, muffing, accommodating G.I
pipe in foundation for cable loop-in-loop out of
suitable size as required:
i) 5 meters long. No. 12,665 3,109
ii) 7 meters long. No. 17,557 4,310
Additional cost of single arm bracket suitable for
iii) No. 528 131
street light fixture.
Additional cost of double arm bracket suitable for
iv) No. 626 155
street light fixture.
Supply, Installation, Testing & Commissioning of
cubical type mast mounted, dust & vermin proof, LT
33058 control switch board conforming to IS:8623 (latest
version), complete:
a) with TPN MCCB 32A, 35kA, fixed type
i) (Ics=100% Icu)-1 No. No. 16,016 3,931
b) copper busbars 200A ( for 5 KVA AT).
a) with TPN MCCB 63A, 35kA, fixed type
ii) (Ics=100% Icu) -1 No. No. 18,758 4,604
b) copper busbars 200A ( for 10kVA AT).
a) with TPN MCCB 150A, 35kA, fixed type
iii) (Ics=100% Icu) -1 No. No. 22,287 5,469
b) copper busbars 300A ( for 25kVA AT).
SECTION - O (Misc. Items)
Supply, Installation, Testing & Commissioning of
15W LED Solar Street light system with 6/7 m pole
33059 GI complete with all accessories as per RDSO No. 58,783 4,218
specifications RDSO/PE /SPEC /PS/0093-2008
(Rev.0) Amend-3 or latest.
Supply, Erection, Testing & Commissioning of FLAT
PLATE COLLECTOR BASED type solar water
heating system of 300 liters capacity complete with
solar collector, insulated tank, supporting stand,
33060 Job 59,762 14,941
connecting pipes, instrumentation etc including
tapping of water supply from the existing
arrangement /system as required.
Design, Supply, Erection and Commissioning of grid
connected solar power plant consisting of solar
panels, PCU mounting structures and all other
33061 associated equipments as per RDSO/PE KWp 64,236 6,557
/SPEC/PS/0092-2008 (Rev.0) with latest
amendment.
Supply & Erection of perforated cable tray size
75x75x350mm, manufactured with 2 mm thick G.I
33062 Meter 756 189
Sheet holding on G.I angle 50x50x6mm for supprot
as required.
Supply and Installation of Furniture set for substation
33063 (i) control room. Set 87,192 0

33063 (ii) Supply and installation of Ladder set. Set 1,49,198 0


Supply and Erection of all types of Galvanised Steel
Structures/Small Parts Steel etc for the exclusive
33064 work in the field of General Electrical Service. MT 1,11,032 3,731

Supply, Erection, Testing & Commissioning of 33kV,


1560MVA, 3 pole Type, VCB panel out door type,
breaking capacity 1560A with terminal connector
33065 suitable for DOG ACSR conductor, spring operated Nos 9,15,908 1,01,767
motor mechanism with all standard essential
accessories and post /support insulators as required.

Supply, Erection, Testing & Commissioning of control


& relay panel for 33kV VCB (Triple Pole) and
33/11kV, 3000kVA transformers with necessary
numerical relays and indicating devices including
33066 measurement of energy and MD. This shall include Nos 3,05,302 33,922
outdoor CT & PT with post insulators etc including
control cables as required for above functions.

Supply, Erection, Testing & Commissioning of


33kV/42kV peak non linear resistor type station class
33067 Set 61,060 6,784
Lightening arrestor with surge monitor complete with
all accessories.
Supply, Erection, Testing & Commissioning of 33kV,
400A outdoor type triple pole horizontal mounting
33068 rotating type double air break gang operated Isolator Set 35,618 3,958
with all standard accessories and post insulators as
required.
Supply, Erection, Testing & Commissioning of 33kV
Bus bar made of ACSR DOG conductor of size
33069 16/4.72+7/1.57 mm including Disc type, post type Mtr 71 9
insulators, jumper connection with suitable
connector, clamps etc as required.
Supply, Erection, Testing & Commissioning of
33kV/11KV, 3-phase, 3000kVA, ONAN outdoor type
transformer with off load tap changer(+5% to -10%
33070 Nos 61,62,249 30,005
with 2.5% step size) with bushing termination on
33kV and cable box termination on 11kV side.

Supply, Erection, Testing & Commissioning of LED


33071 signage (similar to neon sign) M/s Glowz or similar. Sqft 6,155
Supply, Erection, Testing & Commissioning of LED
33072 Sqft 1,815
edge lit signage board.
Supply and Erection of stay set with CC foundation
in ratio 1:3:6, stay rod, stay tightner, stay insulator, GI
33073 wire 7/8 SWG, thimble and other fixing accessories set 1,965
as required.
Supply, Erection and Commissioning of hydraulic
elevating platform (articulated type-02 boom) having
working height of 9.5m, outer reach of 3.7m, safe
working load of 120Kg, slewing range of 300 degree,
33074 fibreglass cage of required size to facilitate fixing of Nos 11,78,624
fittings and maintenance of electric poles suitably
mounted on TATA ACE, HT BS–IV chassis and
engine complete with all accessories.

Supply and installation of Refrigerator minimum


270Ltr capacity, double door, min 3 star rating
33075 Nos 19,443
suitable for 230V AC supply with stabilizer of suitable
rating:
33076 (i) Supply, Erection, Testing & Commissioning of
11kV/433V, 250kVA, Compact sub-station with
following configurations(HT – 2 LBS Manual
operated +1VCB Motorized); Oil immersed Set 23,86,988 2,65,221
Transformer and LT Nos. MCCB – 400 Amps in
weather proof enclosure as per IS: 1180 or latest.

33076 (ii) Supply, Erection, Testing & Commissioning of


11kV/433V, 500kVA CSS with following
configurations (HT – 1 LBS Manual operated + 1VCB
Motorized), Dry Type Cast Resin Transformer –
Set 28,98,048 3,22,005
500kVA, LT – 1 Nos. ACB – 800Amps + 125kVAr
APFC & 4 Nos. 400Amps MCCBs in weather proof
enclosure as per IS: 1180 or latest.

33076 (iii) Supply, Erection, Testing & Commissioning of


11kV/433V, 500kVA CSS with following
configurations (HT – 2 LBS Manual operated + 1VCB
Motorized), Dry Type Cast Resin Transformer –
Set 30,09,296 3,34,367
500kVA, LT – 1 Nos. ACB – 800Amps + 125kVAr
APFC & 4 Nos. 400Amps MCCBs in weather proof
enclosure as per IS: 1180 or latest.

33076 (iv) Supply, Erection, Testing & Commissioning of


11kV/433V, 500kVA CSS with following
configurations (HT – 2 LBS Manual operated +
1VCB Motorized), Transformer – Oil immersed, LT – Set 29,62,313 3,29,146
2 Nos. ACB – 800Amps + 125kVAr APFC & 3 Nos.
400Amps MCCBs in weather proof enclosure as per
IS: 1180 or latest.
33076 (v) Supply, Erection, Testing & Commissioning of
11kV/433V, 800kVA CSS with following
configurations (HT – 2 LBS Manual operated + 1VCB
Motorized), Transformer – Oil immersed, LT – 2 Nos. Set 32,94,439 3,66,049
ACB – 800Amps + 125kVAr APFC & 3 Nos.
400Amps MCCBs in weather proof enclosure as per
IS: 1180 or latest.