0% found this document useful (0 votes)
52 views20 pages

MCCB

The document describes the Meta-MEC series of Adjustable Molded Case Circuit Breakers (MCCBs) designed for high performance and multi-functionality, available in 100 to 250 Ampere Frame ratings. It highlights features such as adjustable rated and instantaneous currents, increased breaking capacity, and easy installation of accessories, along with compliance to various international standards. The MCCBs come in different types and configurations, offering flexibility for various applications.

Uploaded by

santhu kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views20 pages

MCCB

The document describes the Meta-MEC series of Adjustable Molded Case Circuit Breakers (MCCBs) designed for high performance and multi-functionality, available in 100 to 250 Ampere Frame ratings. It highlights features such as adjustable rated and instantaneous currents, increased breaking capacity, and easy installation of accessories, along with compliance to various international standards. The MCCBs come in different types and configurations, offering flexibility for various applications.

Uploaded by

santhu kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

99 -12

ISO 14001, ISO 9001

Adjustable Molded Case


Circuit Breaker (GB-Type)

Adjustable Molded Case Circuit Breaker


Meta - MEC Series
I t ’ s a b o u t

M U L T I

High performance and multi-functional MCCB to


meet the customer's need

AF coverage of LG MCCB
Ampere Frame

W
NE
GB � Type

AB � Type

※ The dotted line means that we do not have MCCB with


that AF but we can cover the rated current
2
G B - T Y P E M e t a - M E C S E R I E S

F U L

Adjustable type MCCB(GB-type)


(100�250 Ampere Frame)
The NEW Meta-MEC series was developed as an adjustable type and has high
performance and multi-function under modern design concept

Remarkably increased breaking capacity meets the customer's need in the trend
of steadily increasing the capacity of a transformer

The rated current and instantaneous current are adjustable and that solves the
load control and stock management problems

Accessories are made in the customer's side concept, and new accessories such
as rear connection terminal and E-handle are available with the standard
offered accessories

3
Characteristics

1
1. Simplified external sizes
and ampere frame
●Dimension: 2 sizes (Type A, Type B)
●Ampere Frame: 2 types (100AF, 250AF)
Type
AF

GB N-type
GB H-type
GB L-type
100AF
16, 20, 25, 32, 40, 50, 63, 80, 100A
Type A
(90 × 140 × 86)
250AF
125, 160, 200, 250A

Type B
(105 × 165 × 86)

Type A
GBN 100
GBH 100

Type B
GBL 100, 100E
GBN 250
GBH 250
GBL 250, 250E

4
G B - T Y P E M e t a - M E C S E R I E S

2
2. Unified panel cutting size
●Handle cutting size (Width × Height : 37×52mm)
●Depth and the height of a terminal : D(79mm)
●Location of trip button: T1, T2
T2

Type A
D
T1

Type B
T2
D
T1

3
3. Adjust the rated current and instantaneous current
Type

Rated current ● 3 steps

Instantaneous
0.8, 0.9, 1.0×In
● Fixed type
Thermal magnetic type
100AF 250AF

● 6 steps
●6 steps
Electronic type
100AF 250AF

0.5, 0.6, 0.7, 0.8, 0.9, 1.0×In


●7 steps(Note)
● 10×In (100AF) 5, 6, 7, 8, 9, 10×In 2, 3, 4, 5, 6, 8, 10×Ir
current
min. 500A

Note) In electronic type, only the short time current is adjustable (2�10×Ir)
the instantaneous current is fixed to 11 times of the rated current

4
4. Increased breaking
capacity (kA)
●30�300% increased breaking
capacity compared with the old
series in the same AF
(Hi-MEC series)
●In the 'L type', the max.
breaking capacity is 85 (kA)
at AC 460V
85kA

65kA

50kA
42kA
35kA

18kA
14kA
10kA
Comparing the breaking capacity (Meta-MEC/Hi-MEC) (AC 460V basis)

100AF 250AF (Note)


Note) Compared with the 225AF Hi-MEC series Hi-MEC Series (AB � -a type)
Meta-MEC Series (GB � type)

5
Characteristics

5
5. Easy to install accessories
●Easy to install and replace the cassette type accessories
●Common use of the general internal accessories
(AX, AL, SHT, UVT): 100 / 250AF common use
●Adopting screw type wiring, it is easy to separate
and replace the lead wire from the MCCB

6
6. Certifications
●Standard
�IEC 60947-2
�KSC 8321
●Certifications and approvals
�CE
�KEMA type test
�ISO 9001/14001

6
G B - T Y P E M e t a - M E C S E R I E S

Type designations

GB N 20 3 E 250A X SHT 110V

MCCB Ampere Frame Operational characteristics Terminal wiring


Global breaker 10 100AF - Thermal magnetic - Standard
20 250AF E Electronic x Rear connection

Type Pole Rated current Accessories


N N-Type 2 2Pole AF Thermal magnetic Electronic AX Auxiliary s/w
H H-Type 3 3Pole 100AF 16A AL Alarm s/w
L L-Type 4 4Pole 20A SHT Shunt trip
Note) In electronic trip Note) 2pole and 25A UVT Under voltage trip
unit, only L-type 3pole are 32A Rear connection
is available same in 40A D-handle
external size
50A E-handle
63A Note) Insulation barriers are
80A standard offered without
100A 100A any symbol
250AF 125A
160A
200A Operational voltage of accessories
250A 250A Refer to Page 12,13

7
Ratings

Ampere Frame AF 100AF


Type N-type H-type L-type
Thermal magnetic GBN102 GBN103 GBN104 GBH102 GBH103 GBH104 GBL102 GBL103 GBL104
Electronic type - - - - - - - GBL103E -
Rated insulation voltage (V) Ui 690 690 690
Rated impulse voltage (kV) Uimp 6 6 6
Rated operating voltage (V) Ue AC voltage 600 600 600
DC voltage 250 250 250
Number of pole 2 3 4 2 3 4 2 3 4
Rated current (A) In Thermal magnetic 16,20,25,32,40,50,63,80,100 16,20,25,32,40,50,63,80,100 16,20,25,32,40,50,63,80,100
Electronic - - 100
Adjusted current (A) Ir Thermal magnetic (0.8, 0.9, 1.0)×In (0.8, 0.9, 1.0)×In (0.8, 0.9, 1.0)×In
Electronic - - (0.5, 0.6, 0.7, 0.8, 0.9, 1.0)×In
Rated Icu AC voltage 600V 18 25 35
breaking 500 / 550V 22 35 50
capacity (kA) 480V 30 42 65
(Sym)
440 / 460V 35 50 85
KS C 8321 380 / 415V 35 50 85
IEC 60947-2 220 / 240V 50 85 125
NEMA AB-1
DC voltage 250V 35 50 85
125V - - -
Ics ... %×Icu 75 75 75
Short time limit Im Electronic Adjustable - - (2, 3, 4, 5, 6, 8, 10)×Ir
Instantaneous It Thermal
Magnetic (Note1)
Fixed type 10×In 10×In 10×In
Electronic Fixed type - - 11×In
Endurance Mechanical 20,000 20,000 10,000
Electrical 10,000 10,000 5,000
Dimensions (mm) W×L×H (H=Panel cutting) 90×140×86(A type) 90×140×86(A type) 105×165×86(B type)
Weight (kg) 1.1 1.2 1.5 1.1 1.2 1.5 1.5 1.7 2.1
Accessories Auxiliary s/w AX � � �
Alarm s/w AL � � �
Shunt trip SHT � � �
Under voltage UVT � � �
Terminal cover � � �
Insulation barrier Standard offer Standard offer Standard offer
Rear connections � � �
Operating handle Direct mount � � �
Extensible type � � �
Certifications KEMA test (Note2) � � �
CE-mark � � �

Accessories 12�15 Page 12�15 Page 12�15 Page


Characteristics curve 16�17 Page 16�17 Page 16�17 Page
Dimensions 18�19 Page 18�19 Page 18�19 Page
Note1) In the thermal-magnetic trip type MCCB, the short time limit current (Im) is the same with Note2) The GBH103, GBL103 was approved by the KEMA
instantaneouls current (It) test according to IEC 60947-2 at 415V, 480V

8
G B - T Y P E M e t a - M E C S E R I E S

Ampere Frame AF 250AF


Type N-type H-type L-type
Thermal magnetic GBN202 GBN203 GBN204 GBH202 GBH203 GBH204 GBL202 GBL203 GBL204
Electronic type - - - - - - - GBL203E -
Rated insulation voltage (V) Ui 690 690 690
Rated impulse voltage (kV) Uimp 6 6 6
Rated operating voltage (V) Ue AC voltage 600 600 600
DC voltage 250 250 250
Number of pole 2 3 4 2 3 4 2 3 4
Rated current (A) In Thermal magnetic 125, 160, 200, 250 125, 160, 200, 250 125, 160, 200, 250
Electronic - - 250
Adjusted current (A) Ir Thermal magnetic (0.8, 0.9, 1.0)×In (0.8, 0.9, 1.0)×In (0.8, 0.9, 1.0)×In
Electronic - - (0.5, 0.6, 0.7, 0.8, 0.9, 1.0)×In
Rated Icu AC voltage 600V 18 25 35
breaking 500 / 550V 22 35 50
capacity (kA) 480V 30 42 65
(Sym)
440 / 460V 35 50 85
KS C 8321 380 / 415V 35 50 85
IEC 60947-2 220 / 240V 50 85 125
NEMA AB-1
DC voltage 250V 35 50 85
125V - - -
Ics ... %×Icu 75 75 75
Short time limit Im Electronic Adjustable - - (2, 3, 4, 5, 6, 8, 10)×Ir
Instantaneous It Thermal
Adjustable (5, 6, 7, 8, 9, 10)×In (5, 6, 7, 8, 9, 10)×In (5, 6, 7, 8, 9, 10)×In
Magnetic (Note1)
Electronic Fixed type - - 11×In
Endurance Mechanical 10,000 10,000 10,000
Electrical 5,000 5,000 5,000
Dimensions (mm) W×L×H (H=Panel cutting) 105×165×86(B type) 105×165×86(B type) 105×165×86(B type)
Weight (kg) 1.5 1.7 2.1 1.5 1.7 2.1 1.5 1.7 2.1
Accessories Auxiliary s/w AX � � �
Alarm s/w AL � � �
Shunt trip SHT � � �
Under voltage UVT � � �
Terminal cover � � �
Insulation barrier Standard offer Standard offer Standard offer
Rear connections � � �
Operating handle Direct mount � � �
Extensible type � � �
Certifications KEMA test (Note2) � � �
CE-mark � � �

Accessories 12�15 Page 12�15 Page 12�15 Page


Characteristics curve 16�17 Page 16�17 Page 16�17 Page
Dimensions 18�19 Page 18�19 Page 18�19 Page
Note1) In the thermal-magnetic trip type MCCB, the short time limit current (Im) is the same with Note2) The GBH203, GBL203 was approved by the KEMA
instantaneouls current (It) test according to IEC 60947-2 at 415V, 480V

9
Trip unit
■Two types of adjustable trip unit
TMU: Thermal magnetic trip unit
STU: Electronic trip unit

Rated current(A)

TMU16�TMU100(Fixed instantaneous )
Thermal magnetic
TMU125�TMU250(Adjustable instantaneous)

Electronic STU50 STU100 STU250

Thermal magnetic
Electronic

TMU type (Thermal magnetic trip unit)


1 Rated current regulating knob In : Rated current
Ir : Adjusted current
3steps: 0.8 / 0.9 / 1.0 x In Im : Instantaneous
current
1
2 Instantaneous current(Im=It) regulating knob
● Fixed instantaneous current type (at 100AF)
: 10 x In ( Min. 500A)
2
● Adjustable instantaneous current type (at 250AF)
: 5 / 6 / 7 / 8 / 9/ 10 x In (6 steps)

1 2

AF 100AF 250AF
Trip unit TMU16 TMU20 TMU25 TMU32 TMU40 TMU50 TMU63 TMU80 TMU100 TMU125 TMU160 TMU200 TMU250
Ranges 0.8×In 13 16 20 26 32 40 50 64 80 100 128 160 200
of the In 0.9×In 14 18 23 29 36 45 57 72 90 113 144 180 225
1.0×In 16 20 25 32 40 50 63 80 100 125 160 200 250
Ranges of the Im 500A 10×In 5, 6, 7, 8, 9, 10×In

10
G B - T Y P E M e t a - M E C S E R I E S

STU type (Electronic trip unit)


1 Rated current(In) regulating knob
6steps: 0.5 / 0.6 / 0.7 / 0.8 / 0.9 / 1.0 x In
2 Short time-limit current(Im) regulating knob
7steps: 2 / 3 / 4 / 5 / 6 / 8 / 10 x Ir
3 Pre-alarm LED (PAL)
●70�110% x Ir : LED on & off
●Over 110% : LED on
4 Frequency selection s/w
●50 or 60Hz (Default is 60Hz)
In : Rated current
Ir : Adjusted current
1 Im : Short time-limit
current
It : Instantaneous
current

1 2 2

3 4

Trip unit STU50 STU100 STU250


0.5×In 25 50 125
0.6×In 30 60 150
Ranges 0.7×In 35 70 175
of the In 0.8×In 40 80 200
0.9×In 45 90 225
1.0×In 50 100 250
Ranges of the Im 2, 3, 4, 5, 6, 8, 10×Ir
Ranges of the It 11×In

※ Default settings of the rated current and Instantaneous current are Max. value

11
Accessories

Internal accessories
Location & Max. attachable No.
Max. attachable No.
Accessories Location
Left Right Sum

Aux. s/w(AX) 2 2 4 AX AX ON AX AX

Alarm s/w(AL) 1 1 2 AL ON AL

SHT or
SHT or UVT 1 - 1 UVT ON

Aux. s/w (AX)


●Indicating MCCB is on or off
AXb1 AXa1 AXb2 AXa2 AXb3 AXa3 AXb4 AXa4
●Configurations
AX1 : 1NO+1NC AX2 : 2NO+2NC
AX3 : 3NO+3NC AX4 : 4NO+4NC
AXc1 AXc2 AXc3 AXc4

Alarm s/w (AL)


●Actuating when the MCCB is tripped
ALb1 ALa1 ALb2 ALa2

●Configurations
AL1 : 1NO+1NC
AL2 : 2NO+2NC
ALc1 ALc2

Ratings of the AX & AL


AC DC
Applied MCCB Max. switching current(A) Max. switching current(A)
Operational voltage(V) Operational voltage(V)
Resistive load Inductive load Resistive load Inductive load
GBN 100, 250 125 5 3 30 4 3
GBH 100, 250 250 3 2 125 0.4 0.4
GBL 100, 250(E) 250 0.2 0.2

12
G B - T Y P E M e t a - M E C S E R I E S

Shunt trip device (SHT)


●Trips the MCCB in remote S1
●Operational voltage
AC: 70�110% of the Vc
DC: 70�125% of the Vc
* Vc : Control voltage
S2

Under voltage trip device (UVT)


●Trips the MCCB when there is voltage drops P1
●Operational voltage
AC: 20�70% of the Vc U<
DC: 20�70% of the Vc
●Restore voltage P2
AC: 85�110% of the Vc
DC: 85�125% of the Vc

Ratings of the SHT and UVT


SHT UVT
Applied MCCB Applied voltage Applied voltage
Time Time
AC,DC voltage common use AC voltage DC voltage AC,DC voltage common use AC voltage
GBN 100, 250 12 100�125 100�110 24 380�440
GBH 100, 250 24 200�240 125 48 440�480
GBL 100, 250(E) 48 380�450 200�220 Continuous 100�110 Continuous
60 440�480 240 200�220
250 500�550 250

External accessories
Insulation barrier
●Provide insulation between circuit
breaker poles (standard)
●Common use in 100AF, 250AF
●Please install on the line and road
side of the MCCB for safety

Terminal cover
●Provide the required electrical ●Types and name of the terminal cover
clearance between circuit Applied MCCB 2pole, 3pole 4pole
breaker poles GBN 100
TB-13T TB-14T
GBH 100

GBN, H 250
TB-23T TB-24T
GBL 100, 250(E)

13
Accessories
Direct rotary handle (D-type) ●Types and names of the operational handle
●Mechanically transfer the position of Type Applied MCCB
a MCCB On↔Trip↔Off D-30S
D-30L GBN / H 100
●Directly mount on the MCCB D-30R
D-Type
D-60S
GBN / H 250
D-60L
GBL 100, 250(E)
D-60R
E-30S
E-30L GBN / H 50, 100
E-30R
Extended rotary handle (E-type) E-Type
E-60S
GBN / H 250
●Externally operate the MCCB and can E-60L
GBL 100, 250(E)
be applied to enclosures of varying depths E-60R
Note) S (For standard mounting) : When you install MCCB
●According to IP54 vertically use the 'S 'type operational handle
L (For line left mounting)
●Standard length of a shaft is 469mm : Use the 'L' type operational handle
R (For line right mounting)
: Use the 'R' type operational handle

※ Padlock the handle is available when the


MCCB is On or Off condition
※ Panel door does not open when the MCCB
is 'On' or 'Trip' condition
(When the door does not open easily use
the release screw)
Rear connection
●Replace the standard terminal with
the rear connection terminal

●External dimensions

Applied MCCB Types of rear A B C D E


connection
X-10S
GBN / H 100 63 8 16 ф14 5
X-10L
GBN / H 250 X-20S
72 12 18 ф20 6
GBL 100, 250 X-20L

●Types and configuration


Type 2Pole 3Pole 4Pole
Applied MCCB X-102 X-202 X-103 X-203 X-104 X-204
GBN 100 X-10S : 4pcs X-10S : 4pcs
X-10S : 4pcs - - -
GBH 100 X-10L : 2pcs X-10L : 4pcs
GBN, H 250 X-20S : 4pcs X-20S : 4pcs
- X-20S : 4pcs - -
GBL 100, 250(E) X-20L : 2pcs X-20L : 4pcs

14
G B - T Y P E M e t a - M E C S E R I E S

External dimensions of the operational handle


D-30S, 30L, 30R type (D-type)

Front view Side view Panel cutting size

D-60S, 60L, 60R type (D-type)

Front view Side view Panel cutting size

E-30S, 30L, 30R type (E-type)

Front view Side view Panel cutting size

E-60S, 60L, 60R type (E-type)

Front view Side view Panel cutting size

15
Characteristics curve
Thermal magnetic type
GBN 100 / GBH 100

Graphs of the temperature


compensation

GBN 250 / GBH 250 / GBL 100, 250

16
G B - T Y P E M e t a - M E C S E R I E S

Electronic trip unit


GBL 50E, 100E, 250E

Note) In: Rated current, Ir: Adjusted current, Im: Short time limit current, It: Instantaneous current

17
External dimensions
GBN 100 / GBH 100

※ Thickness below 6mm

Panel mounting size Panel cover cutting size

18
G B - T Y P E M e t a - M E C S E R I E S

GBN 250 / GBH 250 / GBL 100, 250 / GBL 50E, 100E, 250E

※ Thickness below 6mm

Panel mounting size Panel cover cutting size

19
LG constantly endeavors to improve
our products, so that information in
this catalog is subject to change
Miami Breaker, Inc.
without notice. 7060 NW 52nd Street, Miami FL 33166
Phone : (786) 336 5780 / (800) 941 1112
Fax : (786) 336 5790 / (888) 941 1112

MCCB Adj.-99.9901/Dec. 1999 Printed in Korea STAFF

You might also like