M U L T I
AF coverage of LG MCCB
Ampere Frame
W
NE
GB � Type
AB � Type
F U L
Remarkably increased breaking capacity meets the customer's need in the trend
of steadily increasing the capacity of a transformer
The rated current and instantaneous current are adjustable and that solves the
load control and stock management problems
Accessories are made in the customer's side concept, and new accessories such
as rear connection terminal and E-handle are available with the standard
offered accessories
3
Characteristics
1
1. Simplified external sizes
and ampere frame
●Dimension: 2 sizes (Type A, Type B)
●Ampere Frame: 2 types (100AF, 250AF)
Type
AF
GB N-type
GB H-type
GB L-type
100AF
16, 20, 25, 32, 40, 50, 63, 80, 100A
Type A
(90 × 140 × 86)
250AF
125, 160, 200, 250A
Type B
(105 × 165 × 86)
Type A
GBN 100
GBH 100
Type B
GBL 100, 100E
GBN 250
GBH 250
GBL 250, 250E
4
G B - T Y P E M e t a - M E C S E R I E S
2
2. Unified panel cutting size
●Handle cutting size (Width × Height : 37×52mm)
●Depth and the height of a terminal : D(79mm)
●Location of trip button: T1, T2
T2
Type A
D
T1
Type B
T2
D
T1
3
3. Adjust the rated current and instantaneous current
Type
Instantaneous
0.8, 0.9, 1.0×In
● Fixed type
Thermal magnetic type
100AF 250AF
● 6 steps
●6 steps
Electronic type
100AF 250AF
Note) In electronic type, only the short time current is adjustable (2�10×Ir)
the instantaneous current is fixed to 11 times of the rated current
4
4. Increased breaking
capacity (kA)
●30�300% increased breaking
capacity compared with the old
series in the same AF
(Hi-MEC series)
●In the 'L type', the max.
breaking capacity is 85 (kA)
at AC 460V
85kA
65kA
50kA
42kA
35kA
18kA
14kA
10kA
Comparing the breaking capacity (Meta-MEC/Hi-MEC) (AC 460V basis)
5
Characteristics
5
5. Easy to install accessories
●Easy to install and replace the cassette type accessories
●Common use of the general internal accessories
(AX, AL, SHT, UVT): 100 / 250AF common use
●Adopting screw type wiring, it is easy to separate
and replace the lead wire from the MCCB
6
6. Certifications
●Standard
�IEC 60947-2
�KSC 8321
●Certifications and approvals
�CE
�KEMA type test
�ISO 9001/14001
6
G B - T Y P E M e t a - M E C S E R I E S
Type designations
7
Ratings
8
G B - T Y P E M e t a - M E C S E R I E S
9
Trip unit
■Two types of adjustable trip unit
TMU: Thermal magnetic trip unit
STU: Electronic trip unit
Rated current(A)
TMU16�TMU100(Fixed instantaneous )
Thermal magnetic
TMU125�TMU250(Adjustable instantaneous)
Thermal magnetic
Electronic
1 2
AF 100AF 250AF
Trip unit TMU16 TMU20 TMU25 TMU32 TMU40 TMU50 TMU63 TMU80 TMU100 TMU125 TMU160 TMU200 TMU250
Ranges 0.8×In 13 16 20 26 32 40 50 64 80 100 128 160 200
of the In 0.9×In 14 18 23 29 36 45 57 72 90 113 144 180 225
1.0×In 16 20 25 32 40 50 63 80 100 125 160 200 250
Ranges of the Im 500A 10×In 5, 6, 7, 8, 9, 10×In
10
G B - T Y P E M e t a - M E C S E R I E S
1 2 2
3 4
※ Default settings of the rated current and Instantaneous current are Max. value
11
Accessories
Internal accessories
Location & Max. attachable No.
Max. attachable No.
Accessories Location
Left Right Sum
Aux. s/w(AX) 2 2 4 AX AX ON AX AX
Alarm s/w(AL) 1 1 2 AL ON AL
SHT or
SHT or UVT 1 - 1 UVT ON
●Configurations
AL1 : 1NO+1NC
AL2 : 2NO+2NC
ALc1 ALc2
12
G B - T Y P E M e t a - M E C S E R I E S
External accessories
Insulation barrier
●Provide insulation between circuit
breaker poles (standard)
●Common use in 100AF, 250AF
●Please install on the line and road
side of the MCCB for safety
Terminal cover
●Provide the required electrical ●Types and name of the terminal cover
clearance between circuit Applied MCCB 2pole, 3pole 4pole
breaker poles GBN 100
TB-13T TB-14T
GBH 100
GBN, H 250
TB-23T TB-24T
GBL 100, 250(E)
13
Accessories
Direct rotary handle (D-type) ●Types and names of the operational handle
●Mechanically transfer the position of Type Applied MCCB
a MCCB On↔Trip↔Off D-30S
D-30L GBN / H 100
●Directly mount on the MCCB D-30R
D-Type
D-60S
GBN / H 250
D-60L
GBL 100, 250(E)
D-60R
E-30S
E-30L GBN / H 50, 100
E-30R
Extended rotary handle (E-type) E-Type
E-60S
GBN / H 250
●Externally operate the MCCB and can E-60L
GBL 100, 250(E)
be applied to enclosures of varying depths E-60R
Note) S (For standard mounting) : When you install MCCB
●According to IP54 vertically use the 'S 'type operational handle
L (For line left mounting)
●Standard length of a shaft is 469mm : Use the 'L' type operational handle
R (For line right mounting)
: Use the 'R' type operational handle
●External dimensions
14
G B - T Y P E M e t a - M E C S E R I E S
15
Characteristics curve
Thermal magnetic type
GBN 100 / GBH 100
16
G B - T Y P E M e t a - M E C S E R I E S
Note) In: Rated current, Ir: Adjusted current, Im: Short time limit current, It: Instantaneous current
17
External dimensions
GBN 100 / GBH 100
18
G B - T Y P E M e t a - M E C S E R I E S
GBN 250 / GBH 250 / GBL 100, 250 / GBL 50E, 100E, 250E
19
LG constantly endeavors to improve
our products, so that information in
this catalog is subject to change
Miami Breaker, Inc.
without notice. 7060 NW 52nd Street, Miami FL 33166
Phone : (786) 336 5780 / (800) 941 1112
Fax : (786) 336 5790 / (888) 941 1112