Produced on 3/11/2025 with Xpress Selection V10.4.
2 - database DIL
18.7.1
Project                   Tòa nhà cao
name                      cấp
Project                   bro 1
address
                          Viet Nam
Reference                 bro 2
Client name               Mẹ Châm
Client                    111
address
Revision                  111
Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of
these data.
1. Material List
 Model Type   Model Name Qt               Description
                         y
Outdoor unit RXYQ10TAY1   1 Heat pump VRV IV STANDARD
             RXYQ8TAY1    1 Heat pump VRV IV STANDARD
Indoor unit           FXDQ40NDVE                 1 VRV D(PDVE) - Slim Ceiling Mounted Duct
                      FXDQ50NDVE                 4 VRV D(PDVE) - Slim Ceiling Mounted Duct
                      FXDQ63NDVE                 3 VRV D(PDVE) - Slim Ceiling Mounted Duct
Branch unit           BHFP22P100                 1 Outdoor unit multi connection piping kit
                      KHRP26A22T                 5 Refnet branch piping kit
                      KHRP26A33T                 1 Refnet branch piping kit
                      KHRP26A72T                 1 Refnet branch piping kit
Gas tight             BDGTA06/                   5 Daikin gas tight joint
joint                 SDGTB06
                      BDGTA09/                 17 Daikin gas tight joint
                      SDGTB09
                      BDGTA12/                   5 Daikin gas tight joint
                      SDGTB12
                      BDGTA15/                 11 Daikin gas tight joint
                      SDGTB15
                      BDGTA19/                   5 Daikin gas tight joint
                      SDGTB19
                      BDGTA22/                   3 Daikin gas tight joint
                      SDGTB22
                      KMJ31A                     2 Daikin gas tight joint
                      SDGTB1915                  1 Daikin gas tight joint
                      SDGTB2522                  1 Daikin gas tight joint
Option or             BRC1E63                    8 Wired Remote Controller (Navigation Remote
add-on                                             Controller)
Daikin gas tight joints model and quantity may change depending on the actual piping length and
the installation.
Daikin gas tight joints for field piping can only be calculated for systems where the individual pipe
lengths are input.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name      Logical name of the device
FCU       Device model name
Tmp       Indoor conditions in cooling (dry bulb
C         temp. / RH)
Rq TC     Required total cooling capacity
Max       Available total cooling capacity
TC
Rq SC     Required sensible cooling capacity
Max       Available sensible cooling capacity
SC
Tevap     Evaporating temperature of indoor unit
          coil
Tmp       Indoor temperature in heating
H
Rq HC     Required heating capacity
Max       Available heating capacity
HC
Airflo    Supplied airflow
w
Soun      Sound pressure low and high
d
PS        Power supply (voltage and phases)
MCA       Minimum Circuit Amps
WxHx      WidthxHeightxDepth
D
Wght      Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    2
2.2. Out 1 - RXYQ18TANY1
Capacity data at conditions and connection ratio (95%) as entered
 Na           FCU          Tmp C         Rq Max Rq Max Tev Tmp Rq                                     Max        Airfl
 me                                      TC TC  SC SC  ap   H  HC                                     HC         ow
                               °C        kW kW kW kW    °C  °C kW                                     kW          l/s
Ind     FXDQ63N               24.0 /      n/a       6.8     n/a       5.0 Aut        20.0      n/a        8.0      275
1       DVE                    50%                                          o
Ind     FXDQ63N               24.0 /      n/a       6.8     n/a       5.0 Aut        20.0      n/a        8.0      275
2       DVE                    50%                                          o
Ind     FXDQ50N               24.0 /      n/a       5.4     n/a       4.0 Aut        20.0      n/a        6.3      208
3       DVE                    50%                                          o
Ind     FXDQ63N               24.0 /      n/a       6.8     n/a       5.0 Aut        20.0      n/a        8.0      275
4       DVE                    50%                                          o
Ind     FXDQ50N               24.0 /      n/a       5.4     n/a       4.0 Aut        20.0      n/a        6.3      208
5       DVE                    50%                                          o
Ind     FXDQ50N               24.0 /      n/a       5.4     n/a       4.0 Aut        20.0      n/a        6.3      208
6       DVE                    50%                                          o
Ind     FXDQ40N               24.0 /      n/a       4.3     n/a       3.2 Aut        20.0      n/a        5.0      175
7       DVE                    50%                                          o
Ind     FXDQ50N               24.0 /      n/a       5.4     n/a       4.0 Aut        20.0      n/a        6.3      208
8       DVE                    50%                                          o
Required cooling capacity towards the outdoor unit: 46.4kW.
Required heating capacity towards the outdoor unit: 54.2kW.
The sum of the required indoor unit capacities is 46.4kW for cooling and 54.2kW for heating.
However, the outdoor unit selection uses reduced load values for cooling of 41.8kW (= -10%) and for
heating of 48.8kW (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or
increased wear and tear.
 Na Sou              PS       MC        WxHxD            Wg
 me nd                        A                          ht
    dBA                       A            mm            kg
Ind     29-      220V          1.1 1100×200                31
1       33       1ph               ×620
Ind     29-      220V          1.1 1100×200                31
2       33       1ph               ×620
Ind     27-      220V            1 900×200×                28
3       33       1ph               620
Ind     29-      220V          1.1 1100×200                31
4       33       1ph               ×620
Ind     27-      220V            1 900×200×                28
5       33       1ph               620
Ind     27-      220V            1 900×200×                28
6       33       1ph               620
Ind     26-      220V            1 900×200×                27
7       30       1ph               620
Ind     27-      220V            1 900×200×                28
8       33       1ph               620
Outdoor unit placed 90.0m above the indoor units.
The maximum height difference between the outdoor unit and an indoor unit placed below it (90.0m)
exceeds 50.0m. The main liquid pipe is sized up
The minimum connection ratio for this height difference is 50%.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    3
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name   Logical name of the device
Model  Device model name
Tmp C  Outdoor temperature in cooling
CC     Available cooling capacity
Rq CC  Required cooling capacity
Tmp    Outdoor conditions in heating (dry bulb temp. /
H      RH)
HC     Available heating capacity (integrated heating
       capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse    Standard factory refrigerant charge (5m actual
Refr   piping length)
       excluding extra refrigerant charge
       For calculation of extra refrigerant charge refer to
       the databook
PS     Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHx WidthxHeightxDepth
D
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    4
3.2. Outdoor Details
 Na          Model           Comb Tmp C               CC       Rq       Tmp H HC Rq
 me                                                            CC                HC
                                %          °C        kW        kW        °C   kW kW
Out RXYQ18TA                       95       32.0 43.5          41.8         15.0 / 53. 48.8
1   NY1                                                                      50%    2
 Na   Model                Pipi   Refrigerant
 me                        ng
                            m Type Bse Refr                        Ex
                                                                  Refr
                                                     kg            kg
Out RXYQ18TA               110. R410                      11.9        n/a
1   NY1                      0A
 Na   Model                  PS     MC              WxHxD            Wght
 me                                  A
                                     A                 mm               kg
Out RXYQ18TAN 400V
1   Y1        3ph
    ×                                       22 930×1657                   195
    RXYQ10TAY                                  ×765
    1
    ×                                      16. 930×1657                   185
    RXYQ8TAY1                               1 ×765
Sufficient distance should be respected between the modules according to the service & operation
space rules as mentioned in the databook.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    5
4. Piping Diagrams
Pipes marked with a short red stripe in the diagrams must be connected to the device with a
reducing joint.
4.1. Piping Out 1
                  Out 1
              RXYQ18TANY1
     RXYQ10TAY1         RXYQ8TAY1
            9.5×22.2             9.5×19.1
      BHFP22P100
      19.1×31.8        9.5×15.9  9.5×15.9   6.4×12.7
                  KHRP26A72T KHRP26A22T KHRP26A22T
                                                           Ind 6
                                                        FXDQ50NDVE
                                             6.4×12.7
                                                           Ind 7
                                                        FXDQ40NDVE
                                             6.4×12.7
                                                           Ind 8
                                                        FXDQ50NDVE
       9.5×22.2        9.5×19.1  9.5×15.9   9.5×15.9
                  KHRP26A33T KHRP26A22T KHRP26A22T
                                                           Ind 4
                                                        FXDQ63NDVE
                                             6.4×12.7
                                                           Ind 5
                                                        FXDQ50NDVE
                                             6.4×12.7
                                                           Ind 3
                                                        FXDQ50NDVE
       9.5×15.9                              9.5×15.9
                  KHRP26A22T
                                                           Ind 2
                                                        FXDQ63NDVE
                                             9.5×15.9
                                                           Ind 1
                                                        FXDQ63NDVE
Warning: The pipe diameter values are purely indicative. Depending on the required pipe
lengths, a different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    6
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.
5.1. Wiring Out 1
                                                                    P1,P2
                   Out 1                                                          BRC1E63
                                                         Ind 6
               RXYQ18TANY1
                                                      FXDQ50NDVE
                             IN F1,F2        F1,F2
               RXYQ10TAY1                            L,N 1A 1ph
       Q1,Q2                 L1,L2,L3,N                             P1,P2
                                   22A 3ph               Ind 7                    BRC1E63
                                                      FXDQ40NDVE
                RXYQ8TAY1                    F1,F2
       Q1,Q2                 L1,L2,L3,N              L,N 1A 1ph
                                 16.1A 3ph                          P1,P2
                                                         Ind 8                    BRC1E63
                                                      FXDQ50NDVE
                                             F1,F2
                                                     L,N 1A 1ph
                                                                    P1,P2
                                                         Ind 4                    BRC1E63
                                                      FXDQ63NDVE
                                             F1,F2
                                                     L,N 1.1A 1ph
                                                                    P1,P2
                                                         Ind 5                    BRC1E63
                                                      FXDQ50NDVE
                                             F1,F2
                                                     L,N 1A 1ph
                                                                    P1,P2
                                                         Ind 3                    BRC1E63
                                                      FXDQ50NDVE
                                             F1,F2
                                                     L,N 1A 1ph
                                                                    P1,P2
                                                         Ind 2                    BRC1E63
                                                      FXDQ63NDVE
                                             F1,F2
                                                     L,N 1.1A 1ph
                                                                    P1,P2
                                                         Ind 1                    BRC1E63
                                                      FXDQ63NDVE
                                             F1,F2
                                                     L,N 1.1A 1ph
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield
(but shielded cable can be used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    7
6. Device Options
6.1. Outdoor Unit Options
 Model              Description                                       Used by
BHFP22P1 Outdoor unit multi connection                            Out 1
00       piping kit                                               [RXYQ18TANY1]
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress
Selection Program.
                                                                                                                                                                    8