0% found this document useful (0 votes)
100 views8 pages

Ul FM 38

The document provides detailed specifications for Clean Agent Extinguishing System Units manufactured by Tyco Safety Products, including models for FM-200 and Novec 1230 agents. It outlines the nominal charging capacities, operating temperatures, and design limitations for various units, as well as the necessary installation manuals and software for proper implementation. The document emphasizes the importance of UL certification and the conditions for reproducing its material.

Uploaded by

karimnasser0101
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views8 pages

Ul FM 38

The document provides detailed specifications for Clean Agent Extinguishing System Units manufactured by Tyco Safety Products, including models for FM-200 and Novec 1230 agents. It outlines the nominal charging capacities, operating temperatures, and design limitations for various units, as well as the necessary installation manuals and software for proper implementation. The document emphasizes the importance of UL certification and the conditions for reproducing its material.

Uploaded by

karimnasser0101
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

CLEAN AGENT EXTINGUISHING SYSTEM UNITS | UL Product iQ https://iq.ulprospector.com/en/profile?

e=226440

See General Information for Clean Agent Extinguishing System Units

TYCO SAFETY PRODUCTS EX15488


Burlingham House
Hewett Rd
Gapton Hall Industrial Estate
Great Yarmouth, NORFOLK NR31 0NN UNITED KINGDOM
(Container
Nom (Container) Indicator) Mounting Valve Type (Valve)
Size, kg Part No. Fill Range, kg Position (Size NPS) Part No.

50 MFC-P50 31.2-60.6 Vertical 40A CVL-R40

75 MFC-P70 44.1-85.6 Vertical 40A CVL-R40

100 MFC-P100 57.2-111.0 Vertical 50A CVL-R50

Size mm/NPS 180° Nozzle Part No. 360° Nozzle Part No.

15A — MFN-15-XXX

20A — MFN-15-XXX

25A — MFN-15-XXX

32A — MFN-15-XXX

40A — MFN-15-XXX

50A — MFN-15-XXX

Note: XXX = orifice code number

Component Part No.

FM-200 Needle Cylinder (manual/pneumatic actuator) MNC-06

Nitrogen Cylinder, 60 bar N68-60

Nitrogen Cylinder, 70 bar N68-70

Nitrogen Cylinder, 80 bar N68-80

1 of 3 10/30/2019, 12:10 AM
CLEAN AGENT EXTINGUISHING SYSTEM UNITS | UL Product iQ https://iq.ulprospector.com/en/profile?e=226440

Flex Hose, 20A, 600 mm length MFH-206

Flex Hose, 20A, 700 mm length MFH-207

Flex Hose, 20A, 900 mm length MFH-209

Flex Hose, 50A MFH-50

Union Elbow MUE-501

Union Elbow MUE-502

Adapter (for 40A discharge valve) MVA-40

Check Valve, 50A MCV-50

Selector Valve, 32A MSV-32

Selector Valve, 40A MSV-40

Selector Valve, 50A MSV-50

Selector Valve, 65A MSV-65

Selector Valve, 80A MSV-80

Selector Valve, 100A MSV-100

Selector Valve, 125A MSV-125

Selector Valve, 150A MSV-150

Actuation Box MAB-C1

Solenoid Cutter MSC-01

Actuation Cylinder MAC-01

Pressure Switch MPS-01

TYCO FM-200 Piston Flow System - (FM-200 PFS), Models MFC-P50, MFC-P75, MFC-P100 and MFC-P150, FM-200 (HFC-227ea) Clean
Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 50, 75, 100, and 150 kg of FM-200
(HFC-227ea) Clean Agent, respectively. The units are super-pressurized to 25 bar with operating temperatures of 32°F to 130°F (0°C to
55°C). The units are designed for total-flooding protection against Class A surface burning, Class B flammable liquid, and Class C fires
occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation
and design manual, part number MM-FM200-01T, Rev. 00, dated July 13, 2016. These installations require the use of the Listee's flow
calculation software version TYC4.00. Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (lbs) Part No.

66.6 to 133.6 MFC-P50

93.9 to 188.7 MFC-P75

125.7 to 244.3 MFC-P100

2 of 3 10/30/2019, 12:10 AM
CLEAN AGENT EXTINGUISHING SYSTEM UNITS | UL Product iQ https://iq.ulprospector.com/en/profile?e=226440

86.7 to 168.3 MFC-P150

Last Updated on 2017-02-08

The appearance of a company's name or product in this database does not in itself assure that products so identified have been
manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and
covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The
Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in
a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online
Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material
must include a copyright notice in the following format: "© 2019 UL LLC"

3 of 3 10/30/2019, 12:10 AM
CLEAN-AGENT EXTINGUISHING SYSTEM UNITS | UL Product iQ https://iq.ulprospector.com/en/profile?e=39966

See General Information for Clean-agent Extinguishing System Units

TYCO SAFETY PRODUCTS EX15488


Burlingham House
Hewett Rd
Gapton Hall Industrial Estate
Great Yarmouth, NORFOLK NR31 0NN UNITED KINGDOM
ENGINEEREED UNITS

3M™ Novec™ 1230 Fire Protection Fluid (FK-5-1-12) Clean Agent Extinguishing System Units, utilizing DOT rated cylinders, Models
303.207.010, 303.207.001, 303.207.002, 303.207.003, 303.207.004, 303.207.005, 303.207.006, 303.207.007 and 303.207.008, stored
pressure type, having nominal storage capacities of 11, 21, 42, 84, 137, 280, 388, 459 and 851 lb (5.4, 9.6, 19.2, 38.4, 62.4, 127.2, 176.4,
208 and 386 kg) of Novec™ 1230 Fluid (FK-5-1-12), respectively. 3M™ Novec™ 1230 Fire Protection Fluid (FK-5-1-12) Clean Agent
Extinguishing System Units utilizing TPED rated cylinders, Models 303.207.020, 303.207.021, 303.207.022, 303.207.023, 303.207.024 and
303.207.025, stored pressure type, having nominal storage capacities of 21, 42, 84, 137, 280, and 388 lb (9.6, 19.2, 38.4, 62.4, 127.2, and
176.4 kg) of Novec™ 1230 Fluid (FK-5-1-12), respectively. The units are pressurized to 360 psig (24.8 bar) at 70F with operating
temperatures of 0°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable
liquid and Class C fires occurring within an enclosure. A description of these extinguishing system units and the design and installation
limitations are contained in the Listee's installation manual P/N 14A-11T dated 2010-08 (Issue 3), supplemental Technical Bulletin for
Cable Pneumatic Manual (CPM) Actuator, P/N 15527 dated 2012-03-21, and Actuator Placement Indicator Switch Technical Bulletin p/n
16056A dated December 10, 2015 and Technical Bulletin 16284 for Electrical Actuator (p/n 304205030) dated 24 April 2019. These
installations require the use of the Listee's Novec 1230 Engineered System Flow Calculation Software Versions TSP 3.61b or TYCO4.00.
Copies are available from the above Listee.

Engineered FM-200® Models 303.205.026, 015, 016, 017, 030, 018, 031, 032, 019, 020, 021 and 022 Clean Agent Extinguishing System
Units utilizing DOT rated cylinders, stored pressure type, having nominal charging capacities of 4.5, 8, 16, 32, 40, 52, 67, 80, 106, 147,
180, 343 L (9, 17, 35, 70, 88, 114, 148, 176, 233, 324, 396 and 756 lbs) of FM-200® Clean Agent, respectively. Engineered FM-200®
Models 303.205.045, 046, 047, 048, 049, and 050 Clean Agent Extinguishing System Units utilizing TPED rated cylinders, stored pressure
type, having nominal charging capacities of 8, 16, 32, 52, 106, and 147 L (17, 35, 70, 114, 233, and 324 lbs) of FM-200® Clean Agent,
respectively. The units are super-pressurized to 25 bar (360 psig) with operating temperatures of 0°C to 54°C (32°F to 130°C). The units
are designed for total flooding protection against Class A surface burning, Class B flammable liquid and C fires occurring within an
enclosure. A description of these extinguishing system units and the design and installation limitations are contained in the Listee's
Engineered System Installation, Recharge and Maintenance Manual, p/n 14A-07T dated 2010-03, supplemental Technical Bulletin for
Cable Pneumatic Manual (CPM) Actuator, P/N 15527 dated 2012-03-21, Actuator Placement Indicator Switch Technical Bulletin p/n
16056A dated December 10, 2015, Electrical Actuator (p/n 304205030) Technical Bulletin no. 16284 dated 24 April 2019, and the
FM-200® Engineered System Flow Calculation Software Versions TSP 3.04b or TYCO4.00. Copies are available from the above Listee.

Engineered HFC-227ea Models 303.205.026, 015, 016, 017, 030, 018, 031, 032, 019, 020, 021 and 022 Clean Agent Extinguishing System
Units utilizing DOT rated cylinders, stored pressure type, having nominal charging capacities of 4.5, 8, 16, 32, 40, 52, 67, 80, 106, 147,
180, 343 L (9, 17, 35, 70, 88, 114, 148, 176, 233, 324, 396 and 756 lbs) of HFC-227ea Clean Agent, respectively. Engineered HFC-227ea
Models 303.205.045, 046, 047, 048, 049, and 050 Clean Agent Extinguishing System Units utilizing TPED rated cylinders, stored pressure
type, having nominal charging capacities of 8, 16, 32, 52, 106, and 147 L (17, 35, 70, 114, 233, and 324 lbs) of HFC-227ea Clean Agent,
respectively. The units are super-pressurized to 25 bar (360 psig) with operating temperatures of 0°C to 54°C (32°F to 130°C). The units
are designed for total flooding protection against Class A surface burning, Class B flammable liquid and C fires occurring within an
enclosure. A description of these extinguishing system units and the design and installation limitations are contained in the Listee's
Engineered System Installation, supplemental Technical Bulletin for Cable Pneumatic Manual (CPM) Actuator, P/N 15527 dated
2012-03-21, Recharge and Maintenance Manual, p/n 14A-18T dated 2011-02, Actuator Placement Indicator Switch Technical Bulletin
p/n 16062 dated January 4, 2016, and the HFC-227ea Engineered System Flow Calculation Software Versions TSP 3.34b or TYCO4.00.
Copies are available from the above Listee.

1 of 3 10/30/2019, 12:07 AM
CLEAN-AGENT EXTINGUISHING SYSTEM UNITS | UL Product iQ https://iq.ulprospector.com/en/profile?e=39966

Engineered HFC-227ea Models 303.205.055, 056, 057, 058, 040, 041, 042, and 059 Clean Agent Extinguishing System Units utilizing
DOT rated cylinders, stored pressure type, having nominal charging capacities of 8, 16, 32, 52, 106, 147, 180, and 343 L (17, 35, 70, 114,
233, 324, 396 and 756 lbs) of HFC-227ea Clean Agent, respectively. The units are super-pressurized to 25 bar (360 psig) with operating
temperatures of 0°C to 54°C (32°F to 130°C). The units are designed for total flooding protection against Class A surface burning, Class
B flammable liquid and C fires occurring within an enclosure. A description of these extinguishing system units and the design and
installation limitations are contained in the Listee's Engineered System Installation, supplemental Technical Bulletin for Cable
Pneumatic Manual (CPM) Actuator, P/N 15527 dated 2012-03-21, Recharge and Maintenance Manual, p/n 14A-07T/CH Issue 3 dated
2013-03, Actuator Placement Indicator Switch Technical Bulletin p/n 16056A dated December 10, 2015, and the FM-200® Engineered
System Flow Calculation Software Versions TSPC 3.34b or TYCO4.00. Copies are available from the above Listee.

Engineered Sapphire® Models 303.207.010, 303.207.001, 303.207.002, 303.207.003, 303.207.004, 303.207.005, 303.207.006,
303.207.007 and 303.207.008 Clean Agent Extinguishing System Units utilizing DOT rated cylinders, stored pressure type, having
nominal charging capacities of 11, 21, 42, 84, 137, 280, 388, 459 and 851 lb (9.6, 19.2, 38.4, 62.4, 127.2, 176.4, 208 and 386 kg) of 3MTM
NovecTM 1230 Fire Protection Fluid (FK-5-1-12) Clean Agent, respectively.

Engineered Sapphire® Models 303.207.020, 303.207.021, 303.207.022, 303.207.023, 303.207.024 and 303.207.025 Clean Agent
Extinguishing System Units utilizing TPED rated cylinders, stored pressure type, having nominal charging capacities of 21, 42, 84, 137,
280 and 388 lb (9.6, 19.2, 38.4, 62.4, 127.2, and 176.4 kg) of 3MTM NovecTM 1230 Fire Protection Fluid (FK-5-1-12) Clean Agent,
respectively.

The units are super-pressurized to 360 psig (25 bar) with operating temperatures of 32°F (0°C) to 130°F (54.4°C). The units are
designed for total flooding protection against Class A surface burning, Class B flammable liquid and C fires occurring within an
enclosure.

These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge
and Maintenance Manual, P/N 14A-11T dated 2010-08 (Issue 03), Actuator Placement Indicator Switch Technical Bulletin p/n 16056A
dated December 10, 2015, Electrical Actuator (p/n 304205030) Technical Bulletin no. 16284 dated 24 April 2019, and the Sapphire
Engineered System Flow Calculation Software Version HYG3.61 b.

Engineered FM-200® Models 303.205.026, 303.205.015, 303.205.016, 303.205.017, 303.205.030, 303.205.018, 303.205.031, 303.205.032,
303.205.019, 303.205.020, 303.205.021 and 303.205.022 Clean Agent Extinguishing System Units utilizing DOT rated cylinders, stored
pressure type, having nominal charging capacities of 4.5, 8, 16, 32, 40, 52, 67, 80, 106, 147, 180, and 343 L (9, 17, 35, 70, 88, 114, 148,
176, 233, 324, 396 and 756 lbs) of FM-200® Clean Agent, respectively.

Engineered FM-200® Models 303.205.045, 303.205.046, 303.205.047, 303.205.048, 303.205.049 and 303.205.050 Clean Agent
Extinguishing System Units utilizing TPED rated cylinders, stored pressure type, having nominal charging capacities of 8, 16, 32, 52, 106,
and 147 L (17, 35, 70, 114, 233, and 324 lbs) of FM-200® Clean Agent, respectively.

The units are super-pressurized to 25 bar (360 psig) with operating temperatures of 0°C to 54°C (32°F to 130°C). The units are designed
for total flooding protection against Class A surface burning, Class B flammable liquid and C fires occurring within an enclosure.

These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge
and Maintenance Manual, p/n 14A-07T - Issue 02 dated 2010-03, Actuator Placement Indicator Switch Technical Bulletin p/n 16056A
dated December 10, 2015, Electrical Actuator (p/n 304205030) Technical Bulletin no. 16284 dated 24 April 2019, and the FM-200®
Engineered System Flow Calculation Software Version HYG 3.04b.

TYCO FM-200 Piston Flow System - (FM-200 PFS), Models MFC-P50, MFC-P75, MFC-P100 and MFC-P150, FM-200 (HFC-227ea) Clean
Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 50, 75, 100, and 150 kg of FM-200
(HFC-227ea) Clean Agent, respectively. The units are super-pressurized to 25 bar with operating temperatures of 32°F to 130°F (0°C to
55°C). The units are designed for total-flooding protection against Class A surface burning, Class B flammable liquid, and Class C fires
occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation
and design manual, part number MM-FM200-01T, Rev. 00, dated July 13, 2016. These installations require the use of the Listee's flow
calculation software version TYC4.00. Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (lbs) Part No.

66.6 to 133.6 MFC-P50

93.9 to 188.7 MFC-P75

2 of 3 10/30/2019, 12:07 AM
CLEAN-AGENT EXTINGUISHING SYSTEM UNITS | UL Product iQ https://iq.ulprospector.com/en/profile?e=39966

125.7 to 244.3 MFC-P100

86.7 to 168.3 MFC-P150

Last Updated on 2019-05-08

The appearance of a company's name or product in this database does not in itself assure that products so identified have been
manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and
covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The
Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in
a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online
Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material
must include a copyright notice in the following format: "© 2019 UL LLC"

3 of 3 10/30/2019, 12:07 AM
Clean Agent Fire Extinguishing Systems
These systems contain electrically nonconducting, volatile, or gaseous fire extinguishing agents that don't leave a residue upon
evaporation (per NFPA 2001 paragraph 1-3.1). They are effective for total flooding protection against hazards involving liquid
flammable materials, electrical equipment, and ordinary solid combustibles in occupancy arrangements which produce only surface
burning. In general, these agents are not effective or appropriate for hazards which produce deep-seated burning or for those which
involve chemicals containing their own oxygen (such as cellulose nitrate), metal hydrides, or reactive metals (such as sodium,
magnesium or uranium).
Clean Agent systems are similar in many respects to Halon 1301 and carbon dioxide systems. Discharge of the agent by total flooding
or local application may create atmospheric hazards to personnel. Toxic thermal decomposition products can be minimized by fast fire
detection coupled with rapid agent discharge. Personnel should not remain in the area following system discharge. Table A-1-5.1.1 of
NFPA 2001 provides information on toxicological and physiological effects covered in this equipment classification. The No Observed
Adverse Effect Level (NOAEL) is the highest concentration at which no adverse physiological or toxicological effect has been
observed. The Lowest Observed Adverse Effect Level (LOAEL) is the lowest concentration at which an adverse physiological or
toxicological effect has been observed.
Systems can only be FM Approved under this classification if they use agents having a component Approval. The system Approvals
specifically reference the relevant agent Approval. Individual agent listings appear under the category Clean Extinguishing Agents.
Compatible FM Approvals controls must be used. (See AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER
FIRE PROTECTION EQUIPMENT under ELECTRICAL SIGNALING.)
Application of this equipment should be subject to the limitations specified and subject to FM Global's acceptance of plans prior to
installation. Required design concentrations vary from agent to agent and depending upon maximum design parameters, the
concentration may vary among system manufacturers. The design concentrations listed by the system manufacturers are generally
accepted in electrical/electronic hazards, i.e. computer, telecommunication areas, provided that Class A ordinary combustibles are
kept to a minimum, thereby minimizing the potential for a deep seated Class A fire.
System charging and recharging shall be done only by the manufacturer or a FM Approved representative.
The Clean Agent systems FM Approved under this classification have been addressed by NFPA 2001, Standard on Clean Agent
Extinguishing Systems, 1994 Edition and must be listed in the United States Environmental Protection Agency (EPA) Significant New
Alternatives Policy (SNAP) as an acceptable substitute to Halon 1301.
Jurisdictions outside the United States may not recognize NFPA and EPA sanction of certain clean agents. Local and national
governmental regulations should be consulted prior to agent selection.
*Alternative to Halon 1211 and Halon 1301.

Tyco Safety Products FM-200 / HFC 227ea Fire Suppression Systems

System Designation: Tyco Safety Products FM-200® / HFC 227ea Fire Suppression Systems

System Type: Engineered Systems

Agent Identification: FM-200® / HFC-227ea

Minimum and Maximum Agent


32°F to 130°F (0°C to 54°C)
Storage Temperatures:

Minimum and Maximum Nozzle 16 ft (4.9 m) Maximum Height


Heights: 1 ft (0.3 m) Minimum Height

Types of Nozzles Available: 180°, 360°

Maximum Area of Coverage for 180°: Radius 33 ft (10.05 m)


Nozzle Type: 360°: Radius 28.6 ft (8.7 m)

Minimum Design Concentrations for Class A – 7.17%


Hazard Class: Class B – 9.0%

Minimum and Maximum Discharge


6 to 10 seconds
Times:

Tyco Safety Products FM-200® / HFC 227ea Total Flood Fire Suppression Systems
Design, Installation, Operation, and Engineered Systems Design and Installation Manual, 14A-07T, Issue 02, 2013-03
Maintenance Manuals:
Flow Calculation Software Manual - Version TYCO4.00, P/N 441301, March 2014

Tyco Safety Products Flow Calculation Software TSPC 3.34b


Design Software:
Tyco Clean Agent System Flow Calculation Software v4.00

© 2007-2019 FM Approvals. All rights reserved. 1 of 2


Limitations or Exceptions to the
None.
Approval:

Tyco Fire Protection Products (TFPP)


Burlingham House, Hewett Rd, Gapton Hall Industrial Estate,
Great Yarmouth NR31 0NN, United Kingdom

Approved Filling Stations: Tyco Fire & Security UAE LLC


Al Quoz 1
PO Box 38163
Dubai
United Arab Emirates

Company Name: Tyco Fire Protection Products


Burlingham House, Hewett Rd, Gapton Hall Industrial Estate, Great Yarmouth NR31 0NN, United
Company Address:
Kingdom
Company Website: http://tyco-fire.com
New/Updated Product
No
Listing:
Listing Country: United Kingdom
Agent Type: FM-200, HFC-227
Certification Type: FM Approved

© 2007-2019 FM Approvals. All rights reserved. 2 of 2