Design calculation sheet
Project no:                 Date:      20-09-07       Sheet No.                   1 of 2      Computed by:   ASF
         Subject:                     Fire pump Head Calculation                                       Checked by:
                                                                                                      Approved by:
1- Abbreviations:
            Hs               =   Static Head (m)
            Hr               =   Residual Head (m)
             HL              =   Friction Loss Head (m)
             Q               =   Flow rate (gpm)
             C               =   Hazen-Williams C value
             d               =   Diameter of pipe (inches)
             P               =   Frictional resistance (psi /ft of pipe)
2- Parameters:
             Q1              =      1250                     gpm
             Q2              =      750                      gpm
             Q3              =      500                      gpm
             d1              =        8                      inch
             d2              =        6                      inch
             d3              =        6                      inch
             L1              =       50                       m
                             =     164.04                     ft
             L2              =       90                       m
                             =     295.28                     ft
             L3              =      100                       m
                             =     328.08                     ft
             C               =      120                                   (see NFPA13 - Table 22.4.4.7)
             P               =   4.52 * (Q)      /C
                                              1.85    1.85
                                                             *d    4.87
                                                                          (see NFPA13 - Enc# 22.4.2.1.1)
3- Static Head:
             Hs              =        0                       m
                             =      0.00                      ft
4- Residual Pressure:
             Hr              =       6.9                     bar
                             =     230.86                     ft
5- Friction Loss Head:
1- Friction Loss in Pipes:
             P1              =    0.01380                Psi/ ft
             P2              =    0.02177                Psi/ ft
             P3              =    0.01028                Psi/ ft
            HL1              =    2.26383                    Psi
            HL2              =    6.42906                    Psi
            HL3              =    3.37393                    Psi
            HLT              =      12.07                    Psi
                             =   0.8320071                   bar
=   27.84   ft
Design calculation sheet
        Project no:                           Date:     20-09-07       Sheet No.        2 of 2   Computed by:   ASF
         Subject:                              Fire pump Head Calculation                         Checked by:
                                                                                                 Approved by:
2- Friction Loss in Fittings and valves:
            HLF                     =         5.57               ft    (20% of pipes)
6- Head of fire pump:
             H                      =      Hs + Hr + HLF + HLP
                                    =        264.26               ft
                                    =         80.55               m
                                    =          7.90              bar
                                    =        114.55              Psi
                             H=                      120                Psi