BK52x0 and LC5200: Documentation - EN

The document provides detailed information about the BK52x0 and LC5200 Bus Couplers for DeviceNet, including product introductions, technical specifications, and installation instructions. It emphasizes the importance of following safety guidelines and using the documentation correctly for trained specialists in control and automation engineering. The document also outlines the modularity and flexibility of the Beckhoff Bus Terminal system, which supports various I/O communication types.

Uploaded by

mstvieira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views47 pages

BK52x0 and LC5200: Documentation - EN

The document provides detailed information about the BK52x0 and LC5200 Bus Couplers for DeviceNet, including product introductions, technical specifications, and installation instructions. It emphasizes the importance of following safety guidelines and using the documentation correctly for trained specialists in control and automation engineering. The document also outlines the modularity and flexibility of the Beckhoff Bus Terminal system, which supports various I/O communication types.

Uploaded by

mstvieira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 47

Documentation | EN

BK52x0 and LC5200


Bus Coupler for DeviceNet

2021-09-21 | Version: 2.0.0


Table of contents

Table of contents
1 Foreword .................................................................................................................................................... 5
1.1 Notes on the documentation.............................................................................................................. 5
1.2 Safety instructions ............................................................................................................................. 6
1.3 Documentation issue status .............................................................................................................. 7

2 Product overview....................................................................................................................................... 8
2.1 BK5200 - Introduction ........................................................................................................................ 8
2.2 BK5250 - Introduction ........................................................................................................................ 9
2.3 LC5200 - Introduction ...................................................................................................................... 10
2.4 Technical data ................................................................................................................................. 11

3 Basic Function Principles....................................................................................................................... 12


3.1 The Beckhoff Bus Terminal system ................................................................................................. 12
3.2 Principle of the Bus Terminal........................................................................................................... 14
3.3 DeviceNet ........................................................................................................................................ 15
3.3.1 DeviceNet Introduction .................................................................................................... 15
3.3.2 Data exchange................................................................................................................. 16
3.3.3 Vendor ID......................................................................................................................... 18
3.3.4 DeviceNet Group ............................................................................................................. 18

4 Mounting and wiring................................................................................................................................ 19


4.1 Instructions for ESD protection ........................................................................................................ 19
4.2 Dimensions ...................................................................................................................................... 19
4.3 Installation on mounting rails ........................................................................................................... 20
4.4 Power supply, potential groups ....................................................................................................... 22
4.5 Electrical isolation ............................................................................................................................ 24
4.6 DeviceNet connection – pin assignment ......................................................................................... 25
4.7 Bus cable lengths and pin assignment ............................................................................................ 26
4.8 ATEX - Special conditions (standard temperature range) ............................................................... 28
4.9 ATEX - Special conditions (extended temperature range) .............................................................. 29
4.10 Continuative documentation for ATEX and IECEx .......................................................................... 30

5 Parameterization and Commissioning .................................................................................................. 31


5.1 Start-up behaviour of the Bus Coupler ............................................................................................ 31
5.2 Peripheral Data in the Process Image ............................................................................................. 31
5.3 Configuration of the Bus Coupler .................................................................................................... 35
5.4 Diagnostic LEDs .............................................................................................................................. 37
5.4.1 LED displays.................................................................................................................... 38
5.4.2 LED Function Matrix ........................................................................................................ 39

6 Appendix .................................................................................................................................................. 41
6.1 Composition of a process image in the Bus Coupler....................................................................... 41
6.2 Support and Service ........................................................................................................................ 44

BK52x0 and LC5200 Version: 2.0.0 3


Table of contents

4 Version: 2.0.0 BK52x0 and LC5200


Foreword

1 Foreword

1.1 Notes on the documentation


Intended audience

This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.

The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.

Disclaimer

The documentation has been prepared with care. The products described are, however, constantly under
development.

We reserve the right to revise and change the documentation at any time and without prior announcement.

No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.

Trademarks

Beckhoff®, TwinCAT®, TwinCAT/BSD®, TC/BSD®, EtherCAT®, EtherCAT G®, EtherCAT G10®, EtherCAT P®,
Safety over EtherCAT®, TwinSAFE®, XFC®, XTS® and XPlanar® are registered trademarks of and licensed by
Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by
third parties for their own purposes could violate the rights of the owners.

Patent Pending

The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 with corresponding
applications or registrations in various other countries.

EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany.

Copyright

© Beckhoff Automation GmbH & Co. KG, Germany.


The reproduction, distribution and utilization of this document as well as the communication of its contents to
others without express authorization are prohibited.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a
patent, utility model or design.

BK52x0 and LC5200 Version: 2.0.0 5


Foreword

1.2 Safety instructions


Safety regulations

Please note the following safety instructions and explanations!


Product-specific safety instructions can be found on following pages or in the areas mounting, wiring,
commissioning etc.

Exclusion of liability

All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.

Personnel qualification

This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.

Description of instructions

In this documentation the following instructions are used.


These instructions must be read carefully and followed without fail!

DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.

WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.

CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.

NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.

Tip or pointer
This symbol indicates information that contributes to better understanding.

6 Version: 2.0.0 BK52x0 and LC5200


Foreword

1.3 Documentation issue status


Version Modifications
2.0.0 • Migration
• BK5250 added
• Technical data updated
• Ex-markings added to the technical data
• Chapter Notes on ESD protection added
• LED function matrix added
• Document structure updated
• Safety instructions adapted to IEC 82079-1
• New title page

BK52x0 and LC5200 Version: 2.0.0 7


Product overview

2 Product overview

2.1 BK5200 - Introduction

Fig. 1: BK5200 – Bus Coupler for DeviceNet

The BK5200 Bus Coupler connects the DeviceNet bus system to the modularly extendable electronic
terminal blocks. One unit consists of one Bus Coupler, any number from 1 to 64 terminals and one bus end
terminal.

The DeviceNet Bus Coupler also works without problems with other DeviceNet devices in a network on the
basis of the CAN protocol. DeviceNet is based on definitions of communications objects and services for the
exchange of data from the sensor/actuator area that have been specially agreed upon for automation
technology. The Bus Couplers support all the types of I/O communication described by DeviceNet.

Parameterization of the Bus Couplers and the Bus Terminals can be carried out via the PC using the
KS2000 configuration software. Commissioning without KS2000 is also possible. Appropriate EDS files are
available for DeviceNet configuration tools.

8 Version: 2.0.0 BK52x0 and LC5200


Product overview

2.2 BK5250 - Introduction

Fig. 2: BK5250 – Compact Bus Coupler for DeviceNet

The Compact Bus Coupler BK5250 for DeviceNet extends the Beckhoff Bus Terminal system by a cost-
optimized version in a compact housing. Up to 64 Bus Terminals are supported; with the Terminal Bus
Extension, up to 255 Bus Terminals can be connected. The DeviceNet Bus Coupler offers automatic baud
rate detection up to 500 kbaud and two address selection switches for address assignment. A 5-pin
connector for the fieldbus connection is included in the scope of supply. Optionally, the ZS1052-3000
connector with integrated terminating resistor can be connected.

BK52x0 and LC5200 Version: 2.0.0 9


Product overview

2.3 LC5200 - Introduction

Fig. 3: LC5200 - Low-cost Bus Coupler for DeviceNet

The LC5200 low-cost bus coupler is characterized by its compact design and less expensive connection
technology. It corresponds to the functions of the BK5210 DeviceNet Bus Coupler in relation to operation
with Bus Terminals and its fieldbus properties. Up to 64 digital input/output terminals can be connected. The
firmware can be updated via the configuration interface.

The LC5200 Bus Coupler is particularly suitable for use in small, low-price stations. The 24 VDC supply
voltage feeds the peripheral devices via the power contacts, as well as the Bus Coupler electronics and the
K-bus electronics. Electrical isolation from the I/O level has been dispensed with in the Bus Coupler; it can
be implemented if necessary with a power feed terminal. The LC5200 Bus Coupler can be replaced by a Bus
Coupler from the BK5210 series.

All the bit-oriented terminals can be connected to the low-cost Bus Coupler. All digital input and output
terminals are supported with the exception of KL15xx, KL25x2, KL2692 and KL27x1. All the system
terminals, with and without diagnostics, can also be connected.

10 Version: 2.0.0 BK52x0 and LC5200


Product overview

2.4 Technical data


Technical data BK5200 BK5210 BK5250 LC5200
Number of Bus Terminals 64 64 (255 with K- 64
bus extension)
Digital peripheral signals 512 inputs/outputs 256 inputs/ 1,020 inputs/ 256 inputs/
outputs outputs outputs
Analog peripheral signals 256 inputs/outputs - 256 inputs/ -
outputs
Protocols
Configuration possibility via the KS2000 configuration software or the controller (TwinCAT)
Maximum number of bytes 512 bytes of input 32 bytes of input 512 bytes of input 32 bytes of input
data, 512 bytes of data, 32 bytes of data, 512 bytes data, 32 bytes of
output data output data of output data output data
Bus connection 1 x open pluggable connector, 5-pin directly to spring-
loaded terminal
Power supply 24 VDC (-15%/+20%), via bus cable 11 … 25 V
(according to DeviceNet specification)
Input current 70 mA + (total K-bus current)/4, 500 mA max.
Input inrush current approx. 2.5 x continuous current
K-bus power supply up to 1750 mA 500 mA 1750 mA 500 mA
Power contact voltage maximum 24 VDC
Power contact current load maximum 10 A
Dielectric strength 500 V (power contact / supply voltage / Bus Coupler)
Recommended fuse ≤ 10 A
Mounting [} 20] on 35 mm support rail according to EN 60715
Weight app. 150 g approx. 130 g approx. 100 g approx. 100 g
Permissible ambient 0 °C ... +55 °C 0 °C ... +55 °C -25 °C ... +60 °C 0 °C ... +55 °C
temperature range during (ET)
operation
Permissible ambient -25 °C ... +85 °C -25 °C ... +85 °C -40 °C ... +85 °C -25 °C ... +85 °C
temperature range during
storage
Permissible relative humidity 95 %, no condensation
Vibration / shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission conforms to EN 61000-6-2 / EN 61000-6-4
Installation position variable
Protection class IP20
Approvals/markings CE, cULus, CE, cULus, GL, CE, cULus, CE, cULus,
ATEX [} 28] ATEX [} 28] ATEX [} 29] ATEX [} 28]

System data DeviceNet BK5200, BK5210, BK5250, LC5200


Number of I/O modules 64
Data transfer medium shielded, twisted copper wire with energy supply, 5-pin
Max. cable length 500 m 250 m 100 m
Data transfer rates 125 kbaud 250 kbaud 500 kbaud
Operation modes Bit-Strobe, Polling, Cyclic, Change-of-State (COS)
DeviceNet type Communications adapter

Ex marking
Standard Marking
ATEX II 3 G Ex nA IIC T4 Gc

BK52x0 and LC5200 Version: 2.0.0 11


Basic Function Principles

3 Basic Function Principles

3.1 The Beckhoff Bus Terminal system


Up to 256 Bus Terminals, with 1 to 16 I/O channels per signal form

The Bus Terminal system is the universal interface between a fieldbus system and the sensor / actuator
level. A unit consists of a Bus Coupler as the head station, and up to 64 electronic series terminals, the last
one being an end terminal. Up to 255 Bus Terminals can be connected via the K-Bus extension. For each
technical signal form, terminals are available with one, two, four or eight I/O channels, which can be mixed
as required. All the terminal types have the same mechanical construction, so that difficulties of planning and
design are minimized. The height and depth match the dimensions of compact terminal boxes.

Decentralized wiring of each I/O level

Fieldbus technology allows more compact forms of controller to be used. The I/O level does not have to be
brought to the controller. The sensors and actuators can be wired decentrally, using minimum cable lengths.
The controller can be installed at any location within the plant.

Industrial PCs as controllers

The use of an Industrial PC as the controller means that the operating and observing element can be
implemented in the controller's hardware. The controller can therefore be located at an operating panel, in a
control room, or at some similar place. The Bus Terminals form the decentralized input/output level of the
controller in the control cabinet and the subsidiary terminal boxes. The power sector of the plant is also
controlled over the bus system in addition to the sensor/actuator level. The Bus Terminal replaces the
conventional series terminal as the wiring level in the control cabinet. The control cabinet can have smaller
dimensions.

Bus Couplers for all usual bus systems

The Beckhoff Bus Terminal system unites the advantages of a bus system with the possibilities of the
compact series terminal. Bus Terminals can be driven within all the usual bus systems, thus reducing the
controller parts count. The Bus Terminals then behave like conventional connections for that bus system. All
the performance features of the particular bus system are supported.

Mounting on standardized mounting rails

The installation is standardized thanks to the simple and space-saving mounting on a standardized mounting
rail (EN 60715, 35 mm) and the direct wiring of actuators and sensors, without cross connections between
the terminals. The consistent labelling scheme also contributes.

The small physical size and the great flexibility of the Bus Terminal system allow it to be used wherever a
series terminal is also used. Every type of connection, such as analog, digital, serial or the direct connection
of sensors can be implemented.

Modularity

The modular assembly of the terminal strip with Bus Terminals of various functions limits the number of
unused channels to a maximum of one per function. The presence of two channels in one terminal is the
optimum compromise of unused channels and the cost of each channel. The possibility of electrical isolation
through potential feed terminals also helps to keep the number of unused channels low.

Display of the channel state

The integrated LEDs show the state of the channel at a location close to the sensors and actuators.

12 Version: 2.0.0 BK52x0 and LC5200


Basic Function Principles

K-Bus

The K-Bus is the data path within a terminal strip. The K-Bus is led through from the Bus Coupler through all
the terminals via six contacts on the terminals' side walls. The end terminal terminates the K-Bus. The user
does not have to learn anything about the function of the K-Bus or about the internal workings of the
terminals and the Bus Coupler. Many software tools that can be supplied make project planning,
configuration and operation easy.

Potential feed terminals for isolated groups

The operating voltage is passed on to following terminals via three power contacts. You can divide the
terminal strip into arbitrary isolated groups by means of potential feed terminals. The potential feed terminals
play no part in the control of the terminals, and can be inserted at any locations within the terminal strip.

Up to 64 Bus Terminals can be used in a terminal block, with optional K-Bus extension for up to 256 Bus
Terminals. This count does include potential feed terminals, but not the end terminal.

Bus Couplers for various fieldbus systems

Various Bus Couplers can be used to couple the electronic terminal strip quickly and easily to different
fieldbus systems. It is also possible to convert to another fieldbus system at a later time. The Bus Coupler
performs all the monitoring and control tasks that are necessary for operation of the connected Bus
Terminals. The operation and configuration of the Bus Terminals is carried out exclusively by the Bus
Coupler. Nevertheless, the parameters that have been set are stored in each Bus Terminal, and are retained
in the event of voltage drop-out. Fieldbus, K-Bus and I/O level are electrically isolated.

If the exchange of data over the fieldbus is prone to errors or fails for a period of time, register contents (such
as counter states) are retained, digital outputs are cleared, and analog outputs take a value that can be
configured for each output when commissioning. The default setting for analog outputs is 0 V or 0 mA. Digital
outputs return in the inactive state. The timeout periods for the Bus Couplers correspond to the usual
settings for the fieldbus system. When converting to a different bus system it is necessary to bear in mind the
need to change the timeout periods if the bus cycle time is longer.

The interfaces

A Bus Coupler has six different methods of connection. These interfaces are designed as plug connectors
and as spring-loaded terminals.

BK52x0 and LC5200 Version: 2.0.0 13


Basic Function Principles

3.2 Principle of the Bus Terminal

Fig. 4: Principle of the Bus Terminal

14 Version: 2.0.0 BK52x0 and LC5200


Basic Function Principles

3.3 DeviceNet

3.3.1 DeviceNet Introduction

Fig. 5: DeviceNet

DeviceNet is an open system based on CAN. CAN was developed some years ago by R. Bosch for data
transmission in motor vehicles. Millions of CAN chips are now in use. A disadvantage for application in
automation is that CAN does not contain definitions for the application layer. CAN only defines the physical
and data link layer.

DeviceNet specifies a uniform application layer and this makes it possible to use the CAN protocol for
industrial applications. ODVA (the Open DeviceNet Vendor Association) is an independent association which
supports manufacturers and users of the DeviceNet system. ODVA ensures that all devices which conform
to the specification can operate together in one system, regardless of their manufacturer.

Fig. 6: Example of DeviceNet in use

DeviceNet is a sensor/actuator bus system. It is internationally standardised (EN50325) and is based on


CAN (Controller Area Network). DeviceNet supports a number of communication types for the input and
output data:
• Polling: The master module ("scanner") sends the output data cyclically to the assigned devices and
receives the input data in an answer telegram.
• Change-of-State: Telegrams are sent as soon as their contents have changed.
• Cyclic: The modules send the data automatically after a cycle time has elapsed.
• Strobed: The scanner requests the input data using a broadcast telegram to all the devices.

The DeviceNet devices support all I/O communication types.

The DeviceNet devices are parameterized via acyclical services (explicit messaging).

The effective utilization of the bus bandwidth allows DeviceNet, particularly in Change-of-State mode, to
achieve short system reaction times in spite of the relatively low data rates. The BECKHOFF DeviceNet
devices have a powerful implementation of the protocol. Through active participation in the ODVA's technical
committees, BECKHOFF are contributing to the further development of this bus system, and has in this way
itself gathered profound DeviceNet expertise.

BK52x0 and LC5200 Version: 2.0.0 15


Basic Function Principles

Configuration

The node address is set in the range from 0 to 63 using two decimally coded rotary switches. The data
transfer rate set at the DeviceNet scanner is automatically recognized by the DeviceNet Box (auto baud
rate). "Electronic Data Sheets" (EDS files) for DeviceNet configuration tools are available for download from
the Beckhoff internet site (http://www.beckhoff.de), and on the BECKHOFF product CDs. Special I/O
parameters that are not covered by the DeviceNet standard can be set via the KS2000 software (serial
connection) or via acyclical explicit messages.

Diagnostics

The extensive diagnostic functions of the BECKHOFF DeviceNet devices allow rapid fault localisation. The
diagnostic messages are transmitted over the bus and collated by the master. The status of the network
connection, the device status, the status of the inputs and outputs and of the power supply are displayed by
LEDs.

Data transfer rates

Three data transfer rates from 125 kbaud to 500 kbaud are available for different bus lengths. The effective
utilization of the bus bandwidth allows DeviceNet to achieve short system reaction times at relatively low
data rates.

Topology

DeviceNet is based on a linear topology. The number of devices participating in each network is logically
limited by DeviceNet to 64, but physically the present generation of drivers allows up to 64 nodes in one
network segment. The maximum possible size of the network for any particular data rate is limited by the
signal propagation delay required on the bus medium. For 500 kbaud, for instance, the network may extend
100 m, whereas at 125 kbaud the network may reach up to 500 m. At low data rates the size of the network
can be increased by repeaters, which also allow the construction of tree structures.

Bus access procedures

CAN utilizes the Carrier Sense Multiple Access (CSMA) procedure, i.e. all participating devices have the
same right of access to the bus and may access it as soon as it is free (multi-master bus access). The
exchange of messages is thus not device-oriented but message-oriented. This means that every message is
unambiguously marked with a prioritized identifier. In order to avoid collisions on the bus when messages
are sent by different devices, a bit-wise bus arbitration is carried out at the start of the data transmission. The
bus arbitration assigns bus bandwidth to the messages in the sequence of their priority. At the end of the
arbitration phase only one bus device occupies the bus, collisions are avoided and the bandwidth is optimally
exploited.

Configuration and parameterization

The TwinCAT System Manager allows all the DeviceNet parameters to be set conveniently. An "eds" file
(electronic data sheet) is available on the BECKHOFF website (http://www.beckhoff.de) for the
parameterization of BECKHOFF DeviceNet devices using configuration tools from other manufacturers.

3.3.2 Data exchange

Data string from the DeviceNet master to the Bus Coupler

Data is transferred between masters and slaves in the form of objects. The Bus Coupler recognizes two
objects: an input object and an output object. You can use the configuration software to map the input/output
bytes onto specific memory areas in the controller. The Bus Coupler uses a consistent algorithm to correlate
the object data to the peripherals. Various examples of correlations between addresses and peripherals are
explained in the appendix. An object transmitted from the DeviceNet master to the Bus Coupler must first
contain all byte-oriented values, which is the data for analog output terminals. The bit-oriented data for digital
outputs may not be transmitted until all the byte-oriented values have been sent.

16 Version: 2.0.0 BK52x0 and LC5200


Basic Function Principles

Analog outputs receive 16 bits of data, i.e. two bytes, per channel. An analog output terminal with 2 channels
must therefore receive 4 bytes. A digital output terminal with 2 channels requires a total of 2 bits of data, 1 bit
for each channel.

First the data from all the analog outputs

The first 4 bytes of an object transmitted to the terminal strip are assigned to the first analog output terminal,
which is the analog output terminal closest to the Bus Coupler. Other terminals which are located between
the Bus Coupler and the first analog output terminals are disregarded. The next four bytes of the object go to
the second analog output terminal in the terminal strip. Any other terminals between the first and second
analog output terminals are disregarded.

Then the data for the digital outputs is transmitted in bytes

When the last analog output terminal in the terminal strip has received its data, the digital outputs are served.
Data is always transmitted byte-by-byte. The next byte from the data string contains the data for 8 digital
outputs. Bit 0 and bit 1 are assigned to channels 1 and 2 of the first digital output terminal after the Bus
Coupler. Other types of terminals which are located in between are ignored.

Bit 2 and bit 3 go to the 2 channels of the second digital output terminal, bit 4 and bit 5 to the third and bit 6
and bit 7 to the fourth. There may be other terminals located between these digital output terminals, and if so
they will be disregarded.

Additional bytes are read from the data string until the last digital output in the terminal strip has been dealt
with. If the total number of digital outputs is not a multiple of 8, there will be a number of bits left over in the
last data byte; these will be discarded.

Fig. 7: Data exchange

Object from the Bus Coupler to the DeviceNet master for transferring the input data

The object sent by the Bus Coupler to the DeviceNet master also contains the byte-oriented data at the
beginning, followed by the bit-oriented data. Transfers in this direction also include a status byte, which
comes right at the end of the object.

The byte-oriented data contains the values from the analog inputs and the bit-oriented data the values from
the digital inputs.

Byte-by-byte data

The first four bytes contain the data of the first analog input terminal in the terminal strip. 2 bytes form the 16-
bit value of each input. The next four bytes correspond to the next analog input terminal and so on,
analogously to the procedure described above.

Bit-by-bit data

After the byte-oriented data from all the analog inputs come the values from the digital inputs. Eight digital
inputs are transferred in each byte. As before, if the total number of digital inputs in the terminal strip is not a
multiple of 8, the last data byte will contain one or more unused bits.

BK52x0 and LC5200 Version: 2.0.0 17


Basic Function Principles

An extra status byte is transferred at the end of each string sent by the Bus Coupler to the DeviceNet
master, and this returns the status of the terminal strip. Its value corresponds to the status displayed on the I/
O LEDs on the Bus Coupler. If the terminal strip is working without error, the I/O RUN LED is lit and the
status byte contains the value 0. As soon as an error occurs, the I/O ERR LED lights up and the status byte
contains the value 1.

3.3.3 Vendor ID
The Vendor ID is # 108

3.3.4 DeviceNet Group


The BK5200, BK5210 and LC5200 Bus Couplers are exclusively Group 2 devices.

Fig. 8: Overview of the identifiers used

18 Version: 2.0.0 BK52x0 and LC5200


Mounting and wiring

4 Mounting and wiring

4.1 Instructions for ESD protection


NOTE
Destruction of the devices by electrostatic discharge possible!
The devices contain components at risk from electrostatic discharge caused by improper handling.
• Please ensure you are electrostatically discharged and avoid touching the contacts of the device directly.
• Avoid contact with highly insulating materials (synthetic fibers, plastic film etc.).
• Surroundings (working place, packaging and personnel) should by grounded probably, when handling
with the devices.
• Each assembly must be terminated at the right hand end with a KL9010 bus end terminal, to ensure the
protection class and ESD protection.

Fig. 9: Spring contacts of the Beckhoff I/O components

4.2 Dimensions
The system of the Beckhoff Bus Terminals is characterized by low physical volume and high modularity.
When planning a project it must be assumed that at least one Bus Coupler and a number of Bus Terminals
will be used. The dimensions of the Bus Couplers are independent of the fieldbus system.

BK52x0 and LC5200 Version: 2.0.0 19


Mounting and wiring

Fig. 10: Dimensions

4.3 Installation on mounting rails


WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals.

Mounting

The Bus Couplers and Bus Terminals are attached to commercially available 35 mm mounting rails (DIN rail
according to EN 60715) by applying slight pressure:

1. First attach the Fieldbus Coupler to the mounting rail.


2. The Bus Terminals are now attached on the right-hand side of the fieldbus Coupler. Join the compo-
nents with slot and key and push the terminals against the mounting rail, until the lock clicks onto the
mounting rail.
If the terminals are clipped onto the mounting rail first and then pushed together without tongue and
groove, the connection will not be operational! When correctly assembled, no significant gap should
be visible between the housings.

Fixing of mounting rails


The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At
the installation, the locking mechanism of the components must not come into conflict with the fixing
bolts of the mounting rail. To mount the mounting rails with a height of 7.5 mm under the terminals
and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).

Disassembly

Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:

20 Version: 2.0.0 BK52x0 and LC5200


Mounting and wiring

1. Carefully pull the orange-colored lug approximately 1 cm out of the terminal to be disassembled, until
it protrudes loosely. The lock with the mounting rail is now released for this terminal, and the terminal
can be pulled from the mounting rail without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved
housing surfaces and pull the terminal away from the mounting rail.

Connections within a Bus Terminal block

The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by
joining the components:
• The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus
Terminal electronics.
• The power contacts deal with the supply for the field electronics and thus represent a supply rail within
the Bus Terminal block. The power contacts are supplied via terminals on the Bus Coupler.

Power contacts
During the design of a Bus Terminal block, the pin assignment of the individual Bus Terminals must
be taken account of, since some types (e.g. analog Bus Terminals or digital 4-channel Bus Termi-
nals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx
and EL91xx, EL92xx) interrupt the power contacts and thus represent the start of a new supply rail.

PE power contact

The power contact labelled PE can be used as a protective earth. For safety reasons this contact mates first
when plugging together, and can ground short-circuit currents of up to 125 A.

NOTE
Risk of damage to the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the
mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g.
disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230 V).
For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In or-
der to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at
least 10 mm from the group of terminals.

WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!

Wiring

Up to eight connections enable the connection of solid or finely stranded cables to the Bus Terminals. The
terminals are implemented in spring force technology. Connect the cables as follows:

1. Open a spring-loaded terminal by slightly pushing with a screwdriver or a rod into the square opening
above the terminal.
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal closes automatically when the pressure is released, holding the wire safely and perma-
nently.

Shielding
Analog sensors and actuators should always be connected with shielded, pair-wise twisted cables.

BK52x0 and LC5200 Version: 2.0.0 21


Mounting and wiring

4.4 Power supply, potential groups


Power supply

The Bus Couplers require a 24 V DC supply for their operation. In the case of the BK52x0 Bus Couplers this
is connected via the upper spring-loaded terminals marked "24 V" and "0 V". This supply voltage feeds not
only the Bus Coupler electronics, but also the Bus Terminals via the K-bus. In the BK52x0 Bus Couplers the
power supply for the bus coupler electronics and that of the K-bus are electrically isolated from the field level
potentials.

Power supply for the power contacts

The bottom six connections with spring-loaded terminals can be used to feed the supply for the peripherals.
The spring-loaded terminals are joined in pairs to a power contact. The supply for the power contacts has no
connection to the power supply for the Bus Coupler (BK52x0). The design of the supply permits voltages of
up to 24 V. The assignment in pairs and the electrical connection between feed terminal contacts allows the
connection wires to be looped through to various terminal points. The current load from the power contact
must not exceed 10 A for long periods. The current carrying capacity between two spring-loaded terminals is
identical to that of the connecting wires.

Power contacts

On the right side of the Bus Coupler there are three spring contacts for the power contact connections. The
spring contacts are hidden in slots so that they cannot be accidentally touched. By attaching a Bus Terminal
the blade contacts on the left side of the Bus Terminal are connected to the spring contacts. The tongue and
groove guides on the top and bottom of the Bus Coupler and of the Bus Terminals guarantees that the power
contacts mate securely.

Fieldbus connection

The BK52x0 Bus Couplers have a recessed front surface on the left side. The DeviceNet connection plug
can be inserted here. A full description of the fieldbus interfaces is found elsewhere in this manual.

In the LC5200 Bus Coupler the bus is connected directly at the upper terminal pair.

Configuration interface

The BK52x0 Bus Couplers have an RS232 interface at the bottom of the front face, whereas on the LC5200
it is located under the cover on the side. The miniature connector can be joined to a PC with the aid of a
connecting cable and the KS2000 configuration software. The interface allows the analog channels to be
configured and also permits firmware updating.

The functionality of the configuration interface can also be reached via the fieldbus using the object attributes
for the register communication.

K-bus contacts

In order to connect the Bus Coupler and Bus Terminals the Bus Coupler has gold contacts on the right side.
When the Bus Terminals are pushed together the gold contacts automatically make the connection between
the Bus Terminals. The power supply to the K-bus electronics in the Bus Terminals and the data exchange
between the Bus Coupler and the Bus Terminals is carried out by the K-bus. A part of the data exchange
takes place via a ring structure within the K-bus. Opening the K-bus, e.g. by pulling out one of the Bus
Terminals, opens the ring. Data exchange is no longer possible. Special mechanisms nevertheless allow the
Bus Coupler to identify the location of the interruption and to report it.

Electrical isolation

The Bus Couplers operate by means of three independent potential groups. The supply voltage feeds the K-
bus electronics in the Bus Coupler and the K-bus itself in an electrically isolated manner. The supply voltage
is also used to generate the operating voltage for the fieldbus.

22 Version: 2.0.0 BK52x0 and LC5200


Mounting and wiring

Note: All the Bus Terminals are electrically isolated from the K-bus. The K-bus is thus electrically isolated
from everything else.

Fig. 11: BK5200, BK5210, BK5250 – potential groups

The LC5200 does not provide electrical isolation from the fieldbus and peripheral level. If the peripheral level
nevertheless needs to have an electrically isolated implementation, this can easily be achieved through the
use of isolating terminals (KL9xxx).

BK52x0 and LC5200 Version: 2.0.0 23


Mounting and wiring

4.5 Electrical isolation


BK5200, BK5210

The BK5200 and BK5210 Bus Couplers have electrical isolation between the DeviceNet bus cable and the
communication electronics of the Bus Coupler.

Fig. 12: Potential levels of the BK5200 and BK5210

LC5200

The LC5200 does not provide electrical isolation from the fieldbus and peripheral level. If the peripheral level
nevertheless needs to have an electrically isolated implementation, this can easily be achieved through the
use of isolating terminals (KL9xxx).

24 Version: 2.0.0 BK52x0 and LC5200


Mounting and wiring

4.6 DeviceNet connection – pin assignment


A 5-pin connector is supplied for the connection of the DeviceNet bus cable. When it is plugged into the Bus
Coupler, pin 1 is at the top. The figure shows the socket in the Bus Coupler. The power supplied by this plug
is isolated from the power supply of the terminal to the right of the Bus Coupler. Both power sources must be
connected before the system can operate.

Fig. 13: DeviceNet connection – pin assignment

Pin Signal
1 V+
2 CAN-H
3 GND
4 CAN-L
5 V-

LC5200 DeviceNet connection

In the low-cost LC5200 coupler, the CAN line is connected directly to the terminal points 1 (CAN-H, marked
with C+) and 5 (CAN-L, marked with C-). V+ is applied to the terminal points 2 or 6. V- is applied to the
terminal points 3 or 7. The shield can optionally be applied to terminal points 4 or 8, which are connected to
the DIN rail via an R-C circuit.

Fig. 14: LC5200 - Connection diagram

BK52x0 and LC5200 Version: 2.0.0 25


Mounting and wiring

4.7 Bus cable lengths and pin assignment


The maximum length of cable which can be used depends on the selected baud rate. The following lengths
should be understood as the total length of the main line plus any drop lines.

Baud rate Bus length


500 kbit/s < 100 m
250 kbit/s < 250 m
125 kbit/s < 500 m

Fig. 15: DeviceNet – Baud rate and bus length

Fig. 16: Layout of the ZB5200 CAN/DeviceNet cable

The cable consists of two shielded wire pairs. One pair carries out the transmission. The second pair
distributes the supply voltage.

26 Version: 2.0.0 BK52x0 and LC5200


Mounting and wiring

Fig. 17: Cable assignment

BK52x0 and LC5200 Version: 2.0.0 27


Mounting and wiring

4.8 ATEX - Special conditions (standard temperature


range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
standard temperature range in potentially explosive areas (directive 2014/34/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of at
least IP54 in accordance with EN 60079-15! The environmental conditions during use are thereby to be
taken into account!
• For dust (only the fieldbus components of certificate no. KEMA 10ATEX0075 X Issue 9): The equipment
shall be installed in a suitable enclosure providing a degree of protection of IP54 according to
EN 60079-31 for group IIIA or IIIB and IP6X for group IIIC, taking into account the environmental condi-
tions under which the equipment is used!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose tempera-
ture data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of 0 to 55°C for the use of Beckhoff fieldbus compo-
nents standard temperature range in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply volt-
age has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if
a non-explosive atmosphere is ensured!

Standards

The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
• EN 60079-31:2013 (only for certificate no. KEMA 10ATEX0075 X Issue 9)

Marking

The Beckhoff fieldbus components with standard temperature range certified according to the ATEX directive
for potentially explosive areas bear one of the following markings:

II 3G KEMA 10ATEX0075 X Ex nA IIC T4 Gc Ta: 0 … +55°C


II 3D KEMA 10ATEX0075 X Ex tc IIIC T135°C Dc Ta: 0 ... +55°C
(only for fieldbus components of certificate no. KEMA 10ATEX0075 X Issue 9)
or

II 3G KEMA 10ATEX0075 X Ex nA nC IIC T4 Gc Ta: 0 … +55°C


II 3D KEMA 10ATEX0075 X Ex tc IIIC T135°C Dc Ta: 0 ... +55°C
(only for fieldbus components of certificate no. KEMA 10ATEX0075 X Issue 9)

28 Version: 2.0.0 BK52x0 and LC5200


Mounting and wiring

4.9 ATEX - Special conditions (extended temperature


range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
extended temperature range (ET) in potentially explosive areas (directive 2014/34/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of at
least IP54 in accordance with EN 60079-15! The environmental conditions during use are thereby to be
taken into account!
• For dust (only the fieldbus components of certificate no. KEMA 10ATEX0075 X Issue 9): The equipment
shall be installed in a suitable enclosure providing a degree of protection of IP54 according to
EN 60079-31 for group IIIA or IIIB and IP6X for group IIIC, taking into account the environmental condi-
tions under which the equipment is used!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose tempera-
ture data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of -25 to 60°C for the use of Beckhoff fieldbus com-
ponents with extended temperature range (ET) in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply volt-
age has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if
a non-explosive atmosphere is ensured!

Standards

The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
• EN 60079-31:2013 (only for certificate no. KEMA 10ATEX0075 X Issue 9)

Marking

The Beckhoff fieldbus components with extended temperature range (ET) certified according to the ATEX
directive for potentially explosive areas bear the following marking:

II 3G KEMA 10ATEX0075 X Ex nA IIC T4 Gc Ta: -25 … +60°C


II 3D KEMA 10ATEX0075 X Ex tc IIIC T135°C Dc Ta: -25 ... +60°C
(only for fieldbus components of certificate no. KEMA 10ATEX0075 X Issue 9)
or

II 3G KEMA 10ATEX0075 X Ex nA nC IIC T4 Gc Ta: -25 … +60°C


II 3D KEMA 10ATEX0075 X Ex tc IIIC T135°C Dc Ta: -25 ... +60°C
(only for fieldbus components of certificate no. KEMA 10ATEX0075 X Issue 9)

BK52x0 and LC5200 Version: 2.0.0 29


Mounting and wiring

4.10 Continuative documentation for ATEX and IECEx


Continuative documentation about explosion protection according to ATEX and
IECEx
Pay also attention to the continuative documentation
Ex. Protection for Terminal Systems
Notes on the use of the Beckhoff terminal systems in hazardous areas according to ATEX and
IECEx
that is available for download on the Beckhoff homepage www.beckhoff.com!

30 Version: 2.0.0 BK52x0 and LC5200


Parameterization and Commissioning

5 Parameterization and Commissioning

5.1 Start-up behaviour of the Bus Coupler


Immediately after being switched on, the Bus Coupler checks, in the course of a self-test, all the functions of
its components and the communication on the K-bus/E-bus. The red I/O LED blinks while this is happening.
After completion of the self-test, the Bus Coupler starts to test the attached Bus Terminals (the "Bus
Terminal Test"), and reads in the configuration. The Bus Terminal configuration is used to generate an
internal structure list, which is not accessible from outside. In case of an error, the Bus Coupler enters the
Stop state. Once the start-up has completed without error, the Bus Coupler enters the fieldbus start state.

Fig. 18: Start-up behaviour of the Bus Coupler

The Bus Coupler can be made to enter the normal operating state by switching it on again once the fault has
been rectified.

5.2 Peripheral Data in the Process Image


After being switched on, the Bus Coupler determines the configuration of the inserted input/output terminals.
The assignment of the physical slots for the input/output channels and the addresses in the process image is
carried out automatically by the Bus Coupler.

The Bus Coupler creates an internal assignment list, in which the input/output channels have a specific
position in the process image. A distinction is made here according to inputs and outputs, and according to
bit-oriented (digital) and byte-oriented (analog or complex) signal processing.

Two groups are created, one for inputs and the other for outputs. Each group has the byte-oriented channels
in ascending sequence starting from the lowest address. The bit-oriented channels are placed after this
block.

Digital signals (bit-oriented)

The digital signals are bit-oriented. This means that one bit in the process image is assigned to each
channel. The Bus Coupler creates a memory area containing the current input bits, and ensures that the bits
in a second memory area dedicated to the output channels are written out immediately.

The details of the assignment of the input and output channels to the controller's process image is explained
fully with the aid of an example in the appendix.

Analog signals (byte-oriented)

The processing of analog signals is always byte-oriented. Analog input and output values are represented in
memory by two bytes each. The values are represented in "SIGNED INTEGER" or "two's complement". The
numerical value "0" stands for input/output value "0 V", "0 mA" or "4 mA". The maximum value of an output

BK52x0 and LC5200 Version: 2.0.0 31


Parameterization and Commissioning

or input value is represented, according to the standard settings, by "7FFF" hex. Negative input/output
values, e.g. -10 V are mapped as "1000" hex. The intermediate values are correspondingly proportional. A
range with a resolution of 15 bits is not achieved for all input and output stages. With an actual resolution of
12 bits, the last 3 bits for outputs have no effect and for inputs they are read "0". Each channel also has a
control and status byte. The control and status byte is the highest value byte. Version 2.0 of the DeviceNet
coupler does not permit the control and status byte to be read. An analog channel is represented in the
process image by 2 bytes. The following versions permit expansion of a channel's data width by means of
the KS2000 configuration software.

Special signals and interfaces

A Bus Coupler supports Bus Terminals with other interfaces such as RS232, RS485, incremental encoder
and others. These signals can be considered similarly to the analog signals named above. For some special
signals the bit width of 16 is not sufficient. The Bus Coupler can support any byte width.

Default assignment of inputs/outputs to the process image

Once it has been switched on, the Bus Coupler finds out how many Bus Terminals are inserted, and creates
an assignment list. The analog and digital channels, divided into inputs and outputs, are assembled into
separate parts of this list. The assignment starts on the left next to the Bus Coupler. The software in the Bus
Coupler collects the individual entries for each of the channels in order to create the assignment list counting
from left to right.

Four groups are distinguished in the assignment

Functional type of the channel Assignment level


1. Analog outputs assignment by bytes
2. Digital outputs assignment by bits
3. Analog inputs assignment by bytes
4. Digital inputs assignment by bits

Complex multi-byte signal Bus Terminals are represented as analog inputs or outputs.

The distribution of the process image in the Bus Coupler in overview:

Fig. 19: Output data in the Bus Coupler

32 Version: 2.0.0 BK52x0 and LC5200


Parameterization and Commissioning

Fig. 20: Input data in the Bus Coupler

Process image in the BK5200 and in the PLC (scanner)

Fig. 21: Process image in the BK5200 and in the PLC (scanner)

Data consistency

Data whose content is all correctly associated is said to be consistent.


Examples of data items that belong together are

1. the high and low byte of an analog value (word consistency)


2. the control/status byte and the associated parameter word for access to the registers.

Data consistency in the interaction of peripheral devices and their controllers is, in a basic sense, only
assured for a single byte. In other words, the bits of a byte are written or read together. Byte consistency is
sufficient for handling digital signals. Whenever values have a length of more than 8 bits, analog values for

BK52x0 and LC5200 Version: 2.0.0 33


Parameterization and Commissioning

instance, the consistency must be extended. The different bus systems guarantee consistency up to the
required length. Correct transfer of the consistent data from the bus system master to the controller is
important. The corresponding manual for the bus system will provide a detailed description of the correct
procedure, in particular the description of the master interfaces used. Those chapters of this manual that
deal with the fieldbus refer to the most widespread interfaces.

Complex signal processing

All the byte-oriented signal channels such as RS232, RS485 or incremental encoders operate to some
extent with byte lengths of more than two. Apart from the difference in length, they are always handled
similarly to the analog signals.

34 Version: 2.0.0 BK52x0 and LC5200


Parameterization and Commissioning

5.3 Configuration of the Bus Coupler


Set all the DIP switches to the desired configuration before you switch on the Bus Coupler. Switches 7 and 8
are used to set the baud rate, as shown in the following table.

Fig. 22: BK5200 - Configuration

Fig. 23: DIP switch

Setting the baud rate

Setting baud rates 1 2 3 4 5 6 7 8


125 kbaud off off
250 kbaud on off
500 kbaud off on
(Default) 125 kbaud on on

Setting the MAC ID

The MAC ID is set with DIP switches 1 to 6: Switch 1 is the lowest value bit 20 and switch 6 the highest value
bit 25. The bit is set when the switch is ON.

You can select the MAC ID from the range 0 to 63.

BK52x0 and LC5200 Version: 2.0.0 35


Parameterization and Commissioning

Switch on the Bus Coupler

When you have set all the DIP switches to the desired configuration you can switch on the Bus Coupler. Any
changes you make to the switches while the system is in operation will have no effect until the next time it is
switched on.

36 Version: 2.0.0 BK52x0 and LC5200


Parameterization and Commissioning

5.4 Diagnostic LEDs


After switching on, the Bus Coupler immediately checks the connected configuration. Error-free start-up is
indicated when the red "I/O ERR" LED goes out. If the "I/O ERR" LED blinks, an error in the area of the
terminals is indicated. The error code can be determined from the frequency and number of blinks. This
permits rapid rectification of the error.

The Bus Coupler has two groups of LEDs for the display of status. The upper group with four LEDs indicates
the status of the respective fieldbus. The significance of the "fieldbus status" LED is explained in the relevant
sections of this manual - it conforms to conventional fieldbus displays.

On the upper right side of the Bus Couplers are two more green LEDs that indicate the supply voltage. The
left LED indicates the presence of the 24 V supply for the Bus Coupler. The right LED indicates the presence
of the supply to the power contacts.

Local errors

Two LEDs – the "I/O - LEDs" – below the above-mentioned Fieldbus Status LEDs display the operating
states of the Bus Terminals and the connection to these Bus Terminals. The green LED lights up in order to
indicate fault-free operation. The red LED blinks with two different frequencies in order to indicate an error.
The error is encoded in the blink code in the following way:

Fast flashing Start of the error code


First slow sequence Error code
Second slow sequence Error code argument

Error code Error code argument Description


1 pulse 0 EEPROM checksum error
1 Inline code buffer overflow
2 Unknown data type
2 pulses 0 Programmed configuration
n (n>0) Incorrect table entry / Bus Coupler
Incorrect table comparison (terminal n)
3 pulses 0 Terminal bus command error
4 pulses 0 Terminal bus data error
n Break behind terminal n (0 coupler)
5 pulses n Terminal bus error in register communication with terminal n
6 pulses 0 Special fieldbus error
n (n>0)

The number of pulses in the first sequence indicates the error type, while the second sequence indicates the
position of the last Bus Terminal before the fault. Passive Bus Terminals, such as a power feed terminal, are
not included in the count.

In the case of some errors, rectification does not cause the Bus Coupler to leave the blink sequence. The
operating state of the Bus Coupler remains "Stop". The Bus Coupler can only be re-started either by
switching the power supply off and on again, or by a scanner reset.

Insertion and removal of Bus Terminals is only permitted when switched off. The electronics in the Bus
Terminals and in the Bus Coupler are protected to a large measure against damage, but incorrect function
and damage cannot be ruled out if they are plugged in under power.

The occurrence of a fault in the course of operation does not immediately trigger the display of error codes
by the LEDs. The Bus Coupler must be requested to diagnose the Bus Terminals. The diagnostic request is
generated at power-up or through an access by the fieldbus to the Bus Coupler. This means that if no data is
being exchanged over DeviceNet when a Bus Terminal is removed from the system, the Bus Coupler will not
necessarily report an error.

BK52x0 and LC5200 Version: 2.0.0 37


Parameterization and Commissioning

5.4.1 LED displays

Module Status MS

LED Meaning
RUN green LED blinks Configuration is incorrect
green LED is steadily lit Status is OK
OVERFL red LED blinks K-bus error
red LED is steadily lit Receive queue overflow

Network Status NS

LED Meaning
CONNECT green LED blinks Bus Coupler is ready for communication, but not yet assigned
to the master
BUS OFF green LED is steadily lit Bus Coupler is assigned to the master, data is being
exchanged
red LED blinks Timeout on I/O connection
red LED is steadily lit BUS OFF: CAN error, devices have identical node address

I/O Status

LED Meaning
I/O RUN green LED is lit The Bus Terminals are working correctly
I/O ERR red LED is lit I/O error, a Bus Terminal or an internal K-bus with a fault
I/O ERR red LED blinks The Bus Terminals are being configured

38 Version: 2.0.0 BK52x0 and LC5200


Parameterization and Commissioning

5.4.2 LED Function Matrix


LEDs Network Sta- Module Status Network Sta- Module Status Net/Mod Sta- ADR RUN
tus NS MS tus NS MS tus NMS (LED red) (LED green)
(duo LED) (duo LED) (duo LED) (duo LED) (duo LED)
Products
BK5200 X X
BK5210B1 X X
BK5210B2 X X X
BK5220 X X X
BK5250 X X X
LC5200 X
IP Compact X
Box
IP Coupler X
Box
LEDs NS MS NS MS NMS ADR RUN
green flash- Boot Up OK, IO Data length Boot Up OK, IO data length Boot Up OK, IO data length
ing Device has exe- is not OK, Device has exe- is not OK, Device has exe- is not OK,
cuted duplicate check adjusted cuted duplicate check adjusted cuted duplicate check adjusted
MAC Id Check IO Data length MAC Id Check IO data length MAC Id Check IO data length
and is online at master / and is online at master/scan- and is online at master/scan-
scanner ner ner
Device is not al- Device is not al- Device is not al-
located by a located by a located by a
master/scanner, master/scanner, master/scanner,
no data ex- no data ex- no data ex-
change with a change with a change with a
master/scanner master/scanner master/scanner
green ON No Error No Error No Error No Error No Error No Error
Device is allo- Device is allo- Device is allo-
cated by a mas- cated by a mas- cated by a mas-
ter, data ex- ter, data ex- ter, data ex-
change with change with change with
master/scanner master/scanner master/scanner
is OK is OK is OK
green OFF No baud rate, K-Bus error, BusSense error BusSense error BusSense error BusSense error
device is not check for error (all OFF, includ- (all OFF, includ- (all OFF, includ- (all OFF, includ-
able to detect at connected ing IO LEDs) ing IO LEDs) ing IO LEDs) ing IO LEDs)
DeviceNet baud terminals
rate (IO LEDs
ON)
No baud rate, No baud rate, K-Bus error
device is not device is not
able to detect able to detect
DeviceNet baud DeviceNet baud
rate (IO LEDs rate (IO LEDs
ON) ON)

BK52x0 and LC5200 Version: 2.0.0 39


Parameterization and Commissioning

LEDs Network Sta- Module Status Network Sta- Module Status Net/Mod Sta- ADR RUN
tus NS MS tus NS MS tus NMS (LED red) (LED green)
(duo LED) (duo LED) (duo LED) (duo LED) (duo LED)
Products
BK5200 X X
BK5210B1 X X
BK5210B2 X X X
BK5220 X X X
BK5250 X X X
LC5200 X
IP Compact X
Box
IP Coupler X
Box
LEDs NS MS NS MS NMS ADR RUN
red flashing Time-Out, no K-Bus error, Time-Out, no K-Bus error, Time-Out, no MAC-ID (Node
connection to check for error connection to check for error connection to Address) is set
master, check at connected master, check at connected master, check by software, dif-
cabling terminals cabling terminals cabling fers from adjust-
ments of DIP
switches
Diagnostic of Diagnostic of K-Bus error,
connected ter- connected ter- check for error
minal minal at connected
terminals
red ON Duplicate MAC Duplicate MAC CAN Rx/Tx Duplicate MAC CAN Rx/Tx
Id fault, check Id fault, check Overrun, reduce Id fault, check Overrun, reduce
for same ad- for same ad- IO cycle time for for same ad- IO cycle time for
dress in net- dress in net- device at Scan- dress in net- device at Scan-
work work ner work ner
Bus OFF, check Bus OFF, check Bus OFF, check
cabling, check cabling, check cabling, check
bus termination, bus termination, bus termination,
check bus check bus check bus
length length length
CAN Rx/Tx CAN Rx/Tx CAN Rx/Tx CAN Rx/Tx
Overrun, reduce Overrun, reduce Overrun, reduce Overrun, reduce
IO cycle time for IO cycle time for IO cycle time for IO cycle for de-
device at scan- device at scan- device at scan- vice time at
ner ner ner scanner
red OFF No baud rate, No error BusSense error BusSense error BusSense error MAC Id (Node
Device is not (all OFF, includ- (all OFF) (all OFF, includ- address) from
able to detect ing IO LEDs) ing IO LEDs) DIP switches is
DeviceNet baud valid
rate (IO LEDs
ON)
No baud rate, No baud rate,
Device is not Device is not
able to detect able to detect
DeviceNet baud DeviceNet baud
rate (IO LEDs rate (IO LEDs
ON) ON)
all OFF No baud rate, No baud rate, No baud rate, No baud rate, No baud rate, No baud rate, No baud rate,
Device is not Device is not Device is not Device is not Device is not Device is not Device is not
IO LEDs ON
able to detect able to detect able to detect able to detect able to detect able to detect able to detect
DeviceNet baud DeviceNet baud DeviceNet baud DeviceNet baud DeviceNet baud DeviceNet baud DeviceNet baud
rate (IO LEDs rate (IO LEDs rate (IO LEDs rate (IO LEDs rate (IO LEDs rate (IO LEDs rate (IO LEDs
ON) ON) ON) ON) ON) ON) ON)
all OFF BusSense error BusSense error BusSense error BusSense error BusSense error
(all OFF, includ- (all OFF, includ- (all OFF, includ- (all OFF, includ- (all OFF, includ-
IO LEDs OFF
ing IO LEDs) ing IO LEDs) ing IO LEDs) ing IO LEDs) ing IO LEDs)

40 Version: 2.0.0 BK52x0 and LC5200


Appendix

6 Appendix

6.1 Composition of a process image in the Bus Coupler


An example shows the assignment of input and output channels to the process image. The sample
construction should consist of the following bus - terminal - assemblies:

Position Functional groups on the rail


POS01 Bus Coupler
POS02 Digital inputs, 2 channels
POS03 Digital inputs, 2 channels
POS04 Digital inputs, 2 channels
POS05 Digital inputs, 2 channels
POS06 Digital inputs, 2 channels
POS07 Digital outputs, 2 channels
POS08 Digital outputs, 2 channels
POS09 Digital outputs, 2 channels
POS10 Analog inputs, 2 channels
POS11 Analog outputs, 2 channels
POS12 Analog outputs, 2 channels
POS13 Analog inputs, 2 channels
POS14 Power feed terminal
POS15 Digital inputs, 2 channels
POS16 Digital inputs, 2 channels
POS17 Digital inputs, 2 channels
POS18 Digital outputs, 2 channels
POS19 Digital outputs, 2 channels
POS20 Analog outputs, 2 channels
POS21 End terminal

By default, DeviceNet only supports signal channels that are 16 bits wide. The STATUS/CONTROL BYTE is
not available. This means, for example, that an analog input terminal with 2 channels appears in the process
image with 2 x 16 bits. The images have corresponding differences with respect to byte addresses and
assignments.

Area for byte-oriented data, analog outputs

Relative byte address Bit position Process image in the controller Position in the block
0, 1 none O0, O1 POS11
2, 3 none O2, O3 POS11
4, 5 none O4, O5 POS12
6, 7 none O6, O7 POS12
8, 9 none O8, O9 POS20
10, 11 none O10, O11 POS20

BK52x0 and LC5200 Version: 2.0.0 41


Appendix

Area for bit-oriented data, digital outputs

Relative byte address Bit position Process image in the controller Position in the block
12 0 O12 POS07
12 1 O12 POS07
12 2 O12 POS08
12 3 O12 POS08
12 4 O12 POS09
12 5 O12 POS09
12 6 O12 POS18
12 7 O12 POS18
13 0 O13 POS19
13 1 O13 POS19

Area for byte-oriented data, analog inputs

Relative byte address Bit position Process image in the controller Position in the block
0, 1 none I0, I1 POS10
2, 3 none I2, I3 POS10
4, 5 none I4, I5 POS13
6, 7 none E6, E7 POS13

Area for bit-oriented data, digital inputs

Relative byte address Bit position Process image in the controller Position in the block
4 0 E4 POS01
4 1 E4 POS1
4 2 E4 POS2
4 3 E4 POS2
4 4 E4 POS3
4 5 E4 POS3
4 6 E4 POS4
4 7 E4 POS4
5 0 E5 POS5
5 1 E5 POS5
5 2 E5 POS6
5 3 E5 POS6
5 4 E5 POS15
5 5 E5 POS15
5 6 E5 POS16
5 7 E5 POS16
6 0 I6 POS17
6 1 I6 POS17

Positions POS14 and POS21 are not relevant to data exchange. They do not appear in the list. If a byte is
not fully utilized, e.g. E8, the Bus Coupler pads the remaining bits of the byte with zeros.

42 Version: 2.0.0 BK52x0 and LC5200


Appendix

Distribution of the process image in the Bus Coupler

Fig. 24: Process image in the Bus Coupler – output data

Fig. 25: Process image in the Bus Coupler – input data

The base addresses I0 and O0 listed here are used as relative addresses or addresses in the Bus Coupler.
Depending on the higher-level DeviceNet system, the addresses can appear at a freely selectable position in
the process image of the controller by the bus master. You can use the configuration software of the master
to assign the bytes to the addresses in the process image of the controller.

BK52x0 and LC5200 Version: 2.0.0 43


Appendix

6.2 Support and Service


Beckhoff and their partners around the world offer comprehensive support and service, making available fast
and competent assistance with all questions related to Beckhoff products and system solutions.

Beckhoff's branch offices and representatives

Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!

The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages: https://www.beckhoff.com

You will also find further documentation for Beckhoff components there.

Beckhoff Support

Support offers you comprehensive technical assistance, helping you not only with the application of
individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components
Hotline: +49 5246 963 157
Fax: +49 5246 963 9157
e-mail: support@beckhoff.com

Beckhoff Service

The Beckhoff Service Center supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service
Hotline: +49 5246 963 460
Fax: +49 5246 963 479
e-mail: service@beckhoff.com

Beckhoff Headquarters

Beckhoff Automation GmbH & Co. KG

Huelshorstweg 20
33415 Verl
Germany
Phone: +49 5246 963 0
Fax: +49 5246 963 198
e-mail: info@beckhoff.com
web: https://www.beckhoff.com

44 Version: 2.0.0 BK52x0 and LC5200


List of figures

List of figures
Fig. 1 BK5200 – Bus Coupler for DeviceNet ......................................................................................... 8
Fig. 2 BK5250 – Compact Bus Coupler for DeviceNet .......................................................................... 9
Fig. 3 LC5200 - Low-cost Bus Coupler for DeviceNet ........................................................................... 10
Fig. 4 Principle of the Bus Terminal....................................................................................................... 14
Fig. 5 DeviceNet .................................................................................................................................... 15
Fig. 6 Example of DeviceNet in use....................................................................................................... 15
Fig. 7 Data exchange............................................................................................................................. 17
Fig. 8 Overview of the identifiers used................................................................................................... 18
Fig. 9 Spring contacts of the Beckhoff I/O components......................................................................... 19
Fig. 10 Dimensions .................................................................................................................................. 20
Fig. 11 BK5200, BK5210, BK5250 – potential groups............................................................................. 23
Fig. 12 Potential levels of the BK5200 and BK5210 ................................................................................ 24
Fig. 13 DeviceNet connection – pin assignment...................................................................................... 25
Fig. 14 LC5200 - Connection diagram..................................................................................................... 25
Fig. 15 DeviceNet – Baud rate and bus length ........................................................................................ 26
Fig. 16 Layout of the ZB5200 CAN/DeviceNet cable............................................................................... 26
Fig. 17 Cable assignment ........................................................................................................................ 27
Fig. 18 Start-up behaviour of the Bus Coupler ........................................................................................ 31
Fig. 19 Output data in the Bus Coupler ................................................................................................... 32
Fig. 20 Input data in the Bus Coupler ...................................................................................................... 33
Fig. 21 Process image in the BK5200 and in the PLC (scanner) ............................................................ 33
Fig. 22 BK5200 - Configuration ............................................................................................................... 35
Fig. 23 DIP switch.................................................................................................................................... 35
Fig. 24 Process image in the Bus Coupler – output data ........................................................................ 43
Fig. 25 Process image in the Bus Coupler – input data........................................................................... 43

BK52x0 and LC5200 Version: 2.0.0 45


More Information: