Donaldson
Donaldson
IMPORTANT
2
Installation, Operation and Maintenance Manual
TABLE OF CONTENTS
1. Introduction 5
2. Delivery and MOUNTING INSTRUCTIONS 7
TABLE OF FIGURES
FIGURE 1: TCB FRONT PANEL .............................................................................................................................................................6
FIGURE 2: TERMINAL VIEW OF I/O MODULE PCB ..................................................................................................................................9
FIGURE 3: WIRING DIAGRAM MODULE PCB (DETAIL) ..........................................................................................................................10
FIGURE 4: DISPLAY PCB BATTERY ....................................................................................................................................................28
4
Installation, Operation and Maintenance Manual
1. INTRODUCTION
For installation in hazardous areas, all work must be carried out with the electrical supply
isolated or only when the potentially explosive atmosphere is not present. Checks should be
made to ensure the category of equipment is suitable for the zone in which the installation is
made.
All electrical work has to be done by a qualified electrician according to the national and local
electric codes that apply. (EN60204.1, IEC 364).
All electrical power must be shut off during installation of the Control Board.
Do not apply power on any circuits before all connections have been made.
On outside installations, always isolate power before opening the controller in wet weather
conditions.
• Starting and stopping of the cleaning function at the assigned (adjustable) set points, initiating the
individual pulses in an appropriate sequence, providing the correct time interval between pulses,
energizing the solenoid valve for the proper length of time, and also providing the logic to control
the alternate cleaning modes
• Connection of up to 32 valves in parallel mode. (16 valves for the light version - based on 22w /
Valve).
• Connection of up to 96 valves in a serial linked, multi module system. (based on 22w / Valve).
• Operation of multiple fan systems (e.g. ECB units) under either standard or ‘ATEX‘ mode
cleaning.
• An LCD-display showing all settings and alarm messages
• Push buttons to start and stop the fan
• Overload protection of the fan(s).
• A visual display of the pulse cleaning
• A bar graph indicating the differential pressure over the filter elements
• Possibility to set an adjustable off-line cleaning cycle
• A visual display of the off-line cleaning cycle when set
• ‘Stop-and-go’ or ‘stop-and-end’ setting (explanation: see chapter 7.11)
• Programmable input and output functions
• Optional remote control installation
• Optional alarm installation
5
Installation, Operation and Maintenance Manual
6
Installation, Operation and Maintenance Manual
When the Control Board is received, verify that the enclosure has not been damaged during
shipment. Compare the items received against the packing list. If you find any components that
are damaged or missing, notify the delivery company and your local Nordson representative.
Unpack the Control Board enclosure. Some items may have been shipped inside the enclosure.
Remove any packing material and dispose of it properly.
The distance away from the Afterfilter is limited by the length of tubing and cable supplied with the
equipment (standard 10 m).
In order to get reliable signals to the sensors, the Control Board’s pneumatic sensor lines should not
exceed 20 m. Lengths in excess of this may weaken the signals to the point that they are not reliable.
Contact your Nordson representative for assistance if the sensor lines must be longer than 20 m.
If the area in which the controller is to be located is defined as a hazardous area check to ensure the
rating of the controller supplied is suitable for this area.
To avoid ingress of powder into the controller pressure transducer, it is recommended that an
in-line filter is fitted between the dirty side of the collector and the controller connection. For
collectors handling explosive powders this filter must be used in both the clean and dirty side
connections.
7
Installation, Operation and Maintenance Manual
3. ELECTRICAL INSTALLATION
For the connections to the control box see the wiring diagram shipped inside the enclosure.
y All electrical work must be done by a qualified electrician according to the national and
local codes that apply.
y Do not attempt to wire any electrical components while energized. Electrocution
and/or damage to the components may occur.
For controllers shipped loose connections should be made to the DIN rail terminals according to the
wiring diagrams delivered inside the TCB.
8
Installation, Operation and Maintenance Manual
+24V DC
+24V DC
+24V DC
5 6 7 8 9 10 11 19
Fuse T 2A
12 14 16 17 18
13 15
1. Pressure transducer
7. Optional isolation amplifier (6 - 9) 14. Fan alarm (28, 25)
2. Cleaning mode switch
8. Output O1 (10,11) 15. Alarm input I1 (28, 26)
3. Module number switch
9. Optional output O2 (12,13) 16. Alarm input I2 (28, 27)
4. Valve connectors (-, V1 – V16)
10. Fan starter (14 – 17) 17. ‘In use’ lamp (31, 29)
5. Input voltage 24 VAC (1,2)
11. Alarm relay (18 – 20) 18. ‘Alarm’ lamp (31, 30)
6. RS 485 bus link (3,4,5)
12. Remote ON/OFF terminals (21- 23) 19. 4 – 20 mA
13. External ON (28, 24) terminals (32 – 34)
(Terminal Numbers)
9
Installation, Operation and Maintenance Manual
3.6. Optional isolation amplifier for thermistor protection and/or bursting disc: terminals 6–9
An optional isolation amplifier for motor thermistor protection or bursting disk observer circuit can be
plugged into the I/O module PCB. The input connections will be made to terminal 6 and 7; at terminal 8
and 9 a potential free contact (NC) is available as output signal. This output signal can then be used for
example to initiate an alarm in the TCB by connecting it to terminals 26 and 28.
The terminals for the thermistor will be included as standard on the TCB board, but the Thermistor
module itself is an option.
3.7. Connections for Fan starters : terminals 14–17 (+ 12 & 13 for ECB 4 units)
The contactors for fan starting will be connected as follows:
Terminal 14 = Common = 24V AC Supply.
Terminal 15 = Main contactor for Star-Delta systems, Fan 1 contactor for DOL / multiple fan systems.
Terminal 16 = Star contactor for Star-Delta systems, Fan 2 contactor for multiple fan system
Terminal 17 = Delta contactor for Star-Delta systems, Fan 3 contactor for multiple fan system.
10
Installation, Operation and Maintenance Manual
Note all stop / start signals have equal priority and the system can be stopped and started
using the display or remote stop buttons even if terminals 24 and 28 are bridged. To restart
from terminals 24 and 28 this connection must be opened and re-closed. The fan will not start
when the main power is turned on even if 24 & 28 are bridged.
11
Installation, Operation and Maintenance Manual
Input I1 = terminals 26-28, Input I2 = terminals 27-28. Terminals bridged = no alarm / input, opening
connection = alarm / input active.
Note : The programmable outputs 1 and 2 are not available in multi fan ECB systems as the
relays are used to connect fan contactors in these configurations.
12
Installation, Operation and Maintenance Manual
All valve connections made with the I/O module PCBs must be in numerical sequence without
gaps.
I/O module PCBs have only RS485 bus and valve connection terminals.
13
Installation, Operation and Maintenance Manual
4. PRE-START-UP CHECKLIST
• Make sure all connections to both air and electrical supplies are in the correct position
(when not pre-mounted).
• Recheck all the electrical and air connections for tightness.
• Verify that all electrical systems have been properly grounded.
• Verify if the motor protection switch setting matches the motor full load current.
• Check the star/delta change over delay setting. Factory default is at 5 seconds, but it can
be adjusted in the setting mode (see chapter 7.7).
• For a multi-module system ensure all interconnecting cables are in place and mode and
address switches are set correctly.
After the electrical connections are in place ensure that the door is correctly closed and
secured. The enclosure is designed so the main switch needs to be turned off before the front
panel can be opened.
5. OPERATION
The TCB control board provides the output signals to the diaphragm valves mounted on the Afterfilter
and also controls the fan motor start-up procedure (and can controls other auxiliary equipment if fitted –
e.g. rotary valve, screw conveyor etc). The differential pressure measured gives a clear indication of the
pressure loss over the filter elements.
By default the unit will start pulsing when the threshold value of 80 daPa is exceeded. A cleaning cycle
normally pulses all valves of the unit in sequence with an interval of 10 seconds between every pulse.
As soon as the differential pressure drops below 40 daPa, the controller will stop the cleaning when a
full cycle is completed; this is called ‘Stop & End’ cleaning.
The LCD display will indicate the status of the unit during operation e.g. SYSTEM ON, CLEANING ON
etc. as well as indicating the current filter differential pressure.
When the differential pressure rises above 150 daPa, an alarm message will be displayed and the
alarm LED will illuminate.
The off-line clean function allows the cleaning cycle to continue for a number of cycles after the fan has
been switched off. This function is switched off by default but can be initiated by altering parameter
P06.
These factory default values can be altered when needed using the guidelines detailed in the following
chapters.
The TCB control board provides the output signals to the diaphragm valves mounted inside the
Afterfilter and also controls the fan motor start-up sequence. The differential pressure measured gives a
clear indication of the pressure loss over the filter elements.
For standard units handling non-explosive powders the cleaning will, by default, start pulsing when the
threshold value of 80 daPa is exceeded. A cleaning cycle normally pulses all valves of the unit in
sequence with an interval of 10 seconds between every pulse. As soon as the differential pressure
14
Installation, Operation and Maintenance Manual
drops below 40 daPa, the controller will stop the cleaning when a full cycle is completed; this is called
‘Stop & End’ cleaning.
If off-line cleaning is to be carried out this is done one module at a time, the fans of the other modules
maintaining suction in their respective unit sections to avoid powder clouds being generated outside the
unit.
The number of cleaning cycles carried out depends on the pressure drop at the time the unit is stopped,
the number of cycles set and also the pressure drop across the filters during the cleaning cycle. This
sequence is designed to optimise the cleaning effectiveness while minimising air usage and cleaning
time. During off-line cleaning the display will indicate the module being cleaned and the number of
cycles remaining.
For ECB units handling explosive powders, and hence operating in a hazardous area the cleaning
sequence is carried out only when the unit is off-line using the sequence described above. Cleaning on
line is not initiated, regardless of filter differential pressure, to avoid generating a potentially hazardous
atmosphere within the collector during periods where the working area outside the unit could potentially
generate ignition sources.
The contactor provided to activate working area lighting is de-energised during off-line cleaning periods.
The software parameters controlling these cleaning sequences are factory set to correspond to the unit
type supplied and installation conditions and cannot be changed.
The status LEDs on the front display panel of the TCB have the following meanings:
• SERVICE LED - When during normal operation the service LED lights up, the unit needs to be
checked by a Nordson representative.
• LED BAR GRAPH - The LED Bar graph will indicate the actual status of the filter
• ALARM LED - The Alarm LED will light up when one of the followings alarms occur:
- Fan overload protection tripped
- One or both additional alarm inputs at the module are “low”
- DeltaP Alarm
• FAN / PULSE LED - The Pulse LED will flash when a pulse is active. When the Fan set is
running, this LED will be on. When in the mean time the valves are pulsing, this LED will go out
briefly on every active pulse. When the fan is not running, the LED will be out and flash when a
pulse is active.
• PULSE STOP LED - The pulse stop LED will light up when cleaning is not active.
• OFF LINE CLEANING LED - The Off-line Cleaning LED will light up during off-line cleaning.
15
Installation, Operation and Maintenance Manual
Button Function
GO DOWN in the menu system
GO UP in the menu system
ENTER the menu system or execute a function.
1.1 EXIT MENU SYSTEM Press ENTER to leave the menu system
DP MIN
1.2 Show DeltaP Min value
P02 xxx daPa
DP MAX
1.3 Show DeltaP Max value
P03 xxx daPa
DP MAX ALARM
1.4 Show DeltaP Max Alarm value
P04 xxx daPa
LOW PRESS ALARM
1.5 Show the Low pressure alarm value
P05 xxx daPa
OFF LINE CLEAN C
1.6 Show number of Offline Cleaning Cycles
P06 xx CYCLES
PULSE INTERVAL 1
1.7 Show Pulse Interval
P09 xxx SEC
TEST CONTROLLER After pressing ENTER all LED’s on the control panel light up for
1.8
P48 END 10 sec.
TOTAL OPERAT H
1.9 Show total number of operating hours
M05 xxxxxx HOURS
SETTING MODE PIN
1.10 Enter PIN code to go to the Setting Mode
P00 xxxx
16
Installation, Operation and Maintenance Manual
You can now scroll through all parameters in the setting mode. To change a parameter push the
ENTER button and the value can be changed. The new value needs to be confirmed by pushing the
ENTER button again for 2 seconds otherwise the changed value will not be saved, but instead the
message “Program cancelled” will be displayed. The values can only be changed within the range
shown in the last column. The value between brackets is the factory setting. Following fields can be
displayed:
2.1 EXIT MENU SYSTEM Press ENTER to leave the menu system
DP MIN
2.2 Setting of DeltaP Min value 10 – 190 daPa (40)
P02 xxx daPa
DP MAX
2.3 Setting of DeltaP Max value 30 – 340 daPa (80)
P03 xxx daPa
DP MAX ALARM
2.4 Setting of DeltaP Max Alarm value 20 – 350 daPa (150)
P04 xxx daPa
LOW PRESS ALARM 0 – 200 daPa (0 =
2.5 Setting of Low pressure alarm value
P05 xxx daPa Alarm off)
OFF LINE CLEAN C
2.6 Setting of Offline Cleaning Cycles 0 – 15 cycles (0)
P06 xx CYCLES
ST TR SW TIME
2.7 Setting of Star/Triangle switch time 1 – 60 s (5)
P07 xxx SEC
PULSE INTERVAL 1
2.8 Setting of Pulse Interval 2 – 30 s (10)
P09 xxx SEC
CLEAN PULSE TIME
2.9 Setting of valve Pulse time 40 – 235 ms (100)
P12 xxx MS
DISPLAY LANG See chapter 7.10 for
2.10 Setting the Display Language
P15 ENGLISH different options
INPUT FUNCT I1 See chapter 7.11 for
2.11 Setting the alarm function of input I1.
P17 0 (actual Mode) different options
INPUT FUNCT I2 See chapter 7.12 for
2.12 Setting the alarm function of input I2.
P18 0 (actual Mode) different options
OUTPUT FUNCT O1 See chapter 7.13 for
2.13 Setting of function for output O1
P19 0 (actual Mode) different options
OUTPUT FUNCT O2 See chapter 7.14 for
2.14 Setting of function for output O2
P20 0 (actual Mode) different options
DP CLEAN MODE See chapter 7.15 for
2.15 Setting of the Delta P Cleaning Mode
P22_(actual Mode) different options
NUMBER VALVES
2.16 Shows the number of valves No setting possible
P26 xxx VALVES
Setting of summer and winter time or
T/D DISPLAY See chapter 7.17 for
2.17 automatic switch between summer and
P40 (Actual Mode) different options
winter
DATE
2.18 Setting of date (day / month / year)
P41 DD.MM.20YY
TIME
2.19 Setting of time
P41 hh:mm
17
Installation, Operation and Maintenance Manual
PROGRAM VERSION
2.19 Shows the version of the program No setting possible
P44 VXX.XX.XX/X
Shows the valve that is being pulsed.
ACTIVE PULSE
2.20 XX: Number of module No setting possible
P46 VALVE XX YY
YY: Number of valve
TEST CONTROLLER After pressing ENTER all LED’s on the
2.21
P48 END control panel light up for 10 sec
TOTAL OPERAT H Shows the total number of operating
2.22 No setting possible
M05 XXXXXX HOURS hours
FACTORY SETTINGS
2.23 Resetting all values to factory settings
P50
SETTING MODE PIN
2.24 Setting a new PIN code by the customer 4-digit code (9999)
P00 XXXX
DP_MIN__________
PO2_____XXX_daPa
Once the cleaning has started, if the differential pressure drops below the value DP Min for at least 10
seconds, the cleaning stops.
DP_MAX__________
PO3_____XXX_daPa
When the fan set is switched on, and the differential pressure increases to above the DP Max value for
at least 10 seconds, the cleaning sequence is started.
7.4. P04 Delta P Max Alarm
DP_MAX_ALARM____
PO4_____XXX_daPa
When the fan set is switched on, and the differential pressure rises above the DP Max Alarm value for
at least 10 seconds, the DP Max Alarm is displayed. The alarm can be switched off after pushing the
ENTER button when the differential pressure drops to a value at least 10% less than Delta P max. You
can switch off the Delta P max alarm function by setting its value to “0”.
LOW_PRESS_ALARM_
PO5_____XXX_daPa
18
Installation, Operation and Maintenance Manual
If one minute after the fan set is switched on, the differential pressure is less than the value of the Low
Pressure Alarm for at least 10 seconds, a Low Pressure alarm is displayed. This alarm can be
switched off after pushing the ENTER button when the differential pressure has risen above the Low
pressure alarm. You can switch off the Low pressure alarm function by setting its value to “0”.
OFF_LINE_CLEAN_C
PO6_____XX_CYCLES
Once the fan set is switched off, Off Line Cleaning is initiated and completes the number of cycles
selected here. You can choose anything between 0 and 15 cycles. If the setting is “0”, Off Line Cleaning
is switched off.
ST_TR_SW_TIME___
P07______XXX_SEC
After the fan set is switched on, outputs K1 (mains contactors) and K3 (star contactors) are activated.
At the end of the star/triangle switch-over time, output K3 (star contactor) is switched off, and output
K2 (triangle contactor) is activated with a delay of approximately 0,5 seconds.
PULSE_INTERVAL_1
P09______XXX_SEC
Cleaning Pulse interval is the time in seconds between cleaning pulses when cleaning is operational.
CLEAN_PULSE_TIME
P12_______XXX_MS
The pulse time for the cleaning valves is the time for which the solenoids are energised each pulse.
Factory default setting is 100 milliseconds – this is suitable for most Afterfilter types however please
refer to the specific installation and operation manual for your unit type to verify the correct pulse time
and adjust this parameter if required.
DISPLAY_LANG_____
P15_______ENGLISH
The display text can be output in eight different languages. The default language is English, but you can
also choose one of following languages: German, French, Dutch, Italian, Spanish, Danish, and
Swedish. The set language will be used in all menu’s and modes.
19
Installation, Operation and Maintenance Manual
Parameter
Display Description
value
INPUT_FUNCT_I1__
0 P17_0__NO_FUNCT
Input I1 or I2 has no function
INPUT_FUNCT_I1__ When contact opens on Input, The system will give an Alarm
1 P17_1__ALARM. message
INPUT_FUNCT_I1__ When contact opens on Input, cleaning is activated with interval
2 P17_2_EXT_CLEA_1 1. Cleaning will be activated until the contact is closed
INPUT_FUNCT_I1__ When contact opens on Input, cleaning is activated with interval
3 P17_3_EXT_CLEA_2 2. Cleaning will be activated until the contact is closed
When contact opens on Input, cleaning remains active until a full
INPUT_FUNCT_I1__
4 P17_4_STOP_CLEAN
cleaning cycle is completed. When the contact closes again the
cleaning will not start again based on this input.
When contact opens on Input, Cleaning stops immediately and
INPUT_FUNCT_I1__ the valve number of the last activated valve is stored. When the
5 P17_5_URG_CLE_ST contact closes again the cleaning will not start again based on
this input.
When contact opens on Input, Fan and Cleaning stops
INPUT_FUNCT_I1__ immediately, the valve number of the last activated valve is
6 P17_6_STOP_ALL_ stored. When the contact closes again the fan will restart again
but the cleaning will not start again based on this input.
When contact opens on Input, Fan and Cleaning stops
immediately, the valve number of the last activated valve is
INPUT_FUNCT_I1__
7 P17_7_EMERG_STOP
stored. The system will also generate an Alarm message. When
the contact closes again the fan will NOT restart again and also
the cleaning will NOT start again based on this input.
INPUT_FUNCT_I1__ When contact opens on Input I1, the Alarm messages of Output
8 P17_8_CONF_AL_O1 O1 is cleared/confirmed
INPUT_FUNCT_I1__ When contact opens on Input I2, the Alarm messages of Optional
9 P17_9_CONF_AL_O2 Output O2 is cleared/confirmed
When the cleaning stops using input signal option 4, 5, 6 or 7, it will not restart when the input
contact closes again, but only when the differential pressure measurement or a different input
signal causes a restart.
Input functions 2 – 6 and 7 & 8 are not available when the TCB is used to operate several fans
in ECB mode.
20
Installation, Operation and Maintenance Manual
7.13. P19 Function of output relay O1 (Relay contact cleaning on / terminals 10-11)
A programmable output (volt free relay) is available at terminals 10 and 11 – the contact is normally
open. This can be programmed to close under a number of different conditions as detailed in the table
below.
Parameter
Display Description
value
OUTPUT_FUNCT_O1_
0 Output O1 or O2 has no function
P19_0__NO_FUNCT
OUTPUT_FUNCT_O1_ Output relay is activated (Contacts closed) when cleaning is
1
P19_1_CLEAN_ON__ active
OUTPUT_FUNCT_O1_
2 Output relay is activated (Contacts closed) when fan is running
P19_2_FAN_ON
OUTPUT_FUNCT_O1_ Output relay is activated (Contacts closed) when fan is running or
3
P19_3_FAN_ON+__ (off line) cleaning is active
OUTPUT_FUNCT_O1_ Output relay is activated (Contacts closed) when Delta P Max
4
P19_4_DP_MAX_AL Alarm is active
OUTPUT_FUNCT_O1_ Output relay is activated (Contacts closed) when Low Pressure
5
P19_5_LOW_PRE_AL Alarm is active
OUTPUT_FUNCT_O1_ Output relay is activated (Contacts closed) when Fan Alarm is
6
P19_6_FAN_ALARM active
Alarm communication: These Alarm output relays stay active, it will only be de-activated by a
confirmation of the alarm by the ENTER button or remotely by a signal on Input I1 or I2.
These output functions are not available when the TCB is used to operate several fans in ECB
mode. (The relays are then used to power the fan contactors for fans 4 and the working area
lighting circuit).
7.14. P20 Function of Optional output relay O2 (Relay contact start extracting equipment /
terminals 12-13)
If this option is supplied a second programmable output is available at terminals 12 and 13. Details and
possible setting options are as for O1 - See chapter 7.13.
21
Installation, Operation and Maintenance Manual
When off line cleaning is activated (option 3), make sure that parameter P06 (number of off-
line cleaning cycles) is not set to zero. Otherwise the unit will never start to pulse clean the
filter elements.
Multi fan ECB units operating with Explosive powder will only clean off-line and P22
parameter has no effect. A number of offline clean cycles must be set – otherwise cleaning
will not be initiated.
NUMBER_VALVES___
P26___XXX_VALVES
Configuration of the number of valves connected to the controller. When the controller starts, all
valves are addressed and checked. If a valve has failed, it is skipped.
22
Installation, Operation and Maintenance Manual
Setting of the current time of the system: Os = summer time, Ow = winter time, and A = Automatic
setting of summer- and wintertime depending on date and time settings in the system (Parameter
P41).
The time and date setting must be re-set after the battery has been removed / changed.
This parameter field shows the version of the software. The update and/or uploading of new
software can only be done by a Nordson representative.
This parameter field shows the number of the valve that is last activated.
XX = Number of the module / YY = Number of the valve
During this test, all LED’s on the control panel will light up for 10 seconds to be able to detect
defective LED’s.
23
Installation, Operation and Maintenance Manual
With this parameter the system will reset all the parameters as described in the next table to default
factory settings.
The settings will be reset by pressing the enter button for more then 2 seconds. The system will ask
for a confirmation after which the enter button needs to be pressed again for more then 2 seconds.
Display of active operating hours (with running fan) of the control box since start-up.
24
Installation, Operation and Maintenance Manual
Alarm
Display line Alarm description
code
_FAN_ALARM______ Fan Alarm.
E01
E01_HH:MM_______ Fan overload contactor tripped.
Communication alarm
_COMM_ALARM_____
E02 A bus component connected is not responding (e.g. slave
E02__HH:MM_____
module, I/O Module )
Low Pressure Alarm
LOW_PRES_AL_daPA
E05 E05__HH:MM__XXX_ After fan start the differential pressure is below the set value
P05
DP_MAX_AL_(daPA) DP Max Alarm
E06
E06__HH:MM__XXX_ The differential pressure is above the set value P04
Data alarm
_DATA_ALARM__
E07 E07__HH:MM______ Data has been lost. All parameter values must be checked
and corrected if necessary
_ALARM_INPUT_I1_
E08 Error message / Alarm on Input I1
E08__hh:mm______
_ALARM_INPUT_I2_
E09 E09__hh:mm______ Error message / Alarm on Input I2
LOW BATTERY
E10 / SET TIME Low battery for real time clock or incorrect time setting.
E10__HH:MM______
DP SENSOR ALARM
E11 Wrong connection of Delta P when Delta P is smaller then 0
E11__HH:MM______
EMERG STOP Emergency stop of fan set and cleaning based on input
E12 E12__HH:MM______ signal option 7 (see chapter 7.11)
HIGH DP SYS.STOP After an off-line cleaning cycle of an ECB unit the pressure
E13
E13__HH:MM______ drop has remained above the set DP Max level.
When any of the above alarms are active it will be impossible to start up the fan set. Unless
the alarm triggers a shutdown, the fan set will keep running when it was already activated
before the alarm.
25
Installation, Operation and Maintenance Manual
26
Installation, Operation and Maintenance Manual
27
Installation, Operation and Maintenance Manual
9. MAINTENANCE
In general the TCB control box does not require any maintenance. There are some items however
that need to be checked on a regular basis:
• In-line Micrafilters in the air lines: when these are very dirty, there will be a pressure drop
over them, making the differential pressure measurement over the elements unreliable.
• Air lines and cable glands to and from control box should be checked for damage and/or
tightness. If these become loose, the values shown on the display may not be accurate,
and possibly powder or moisture will be able to enter the enclosure causing damages and
possible short-circuits.
• The clock on the front PCB has a CR 2032 battery. This battery will deplete over time and
needs to be changed as soon as the alarm message is displayed. In order to do this, the
cover over the front PCB needs to be removed first. Make sure to mount the battery with
the ‘+’ side facing to the right of the PCB.
• Re-set the time and date after replacing the battery.
• Forced cleaning time: initiates a forced cleaning cycle at a specified time interval.
• Fan run-on time: fan set remains activated during a certain period after system is switched
off.
• Optional input signal: possibility to initiate for example an alarm to stop cleaning cycle.
• Optional output signal: possibility to start for example a rotary airlock on off-line cleaning.
• DeltaP sensor type: possibility to measure DeltaP over filter elements by a 4-20 mA
pressure transducer.
The options mentioned above can also cause alarm messages to be displayed on the TCB.
Relieving the alarm is done in the same way by pressing the ENTER button after correcting
the input to the control board.
28
Installation, Operation and Maintenance Manual
11. SPECIFICATIONS
Differential Pressure 0-500 daPa, Display Range 0-500 daPa. Accuracy - 2,5%
Transducer
Valve outputs 24 V DC
Single I/O module system - Max. 1,9 A (2 x 22W Valve per output)
Slave I/O modules - Max. 1.0 A (1 x 22W Valve per output)
29
Installation, Operation and Maintenance Manual
30
Installation, Operation and Maintenance Manual
31
Installation, Operation and Maintenance Manual
Nordson GmbH
Heinrich Hertz Strasse 42
40699 Erkrath
Germany
32