0% found this document useful (0 votes)
400 views1 page

Input Module IUX 760 M-I

The document provides specifications for the IUX 760 M-I input module, a miniature interface designed for fire alarm panels with Loop AP protocol. It monitors the state of dry normally open contacts and indicates various statuses through LEDs. The module operates within a temperature range of -20 °C to +60 °C and has specific electrical and connection requirements detailed in the document.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
400 views1 page

Input Module IUX 760 M-I

The document provides specifications for the IUX 760 M-I input module, a miniature interface designed for fire alarm panels with Loop AP protocol. It monitors the state of dry normally open contacts and indicates various statuses through LEDs. The module operates within a temperature range of -20 °C to +60 °C and has specific electrical and connection requirements detailed in the document.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Product Sheet I Detection

Standard detectors
Modules, addressable, DIN rail mounting

Input module IUX 760 M-I Part no.: 908531


Miniature interface for use in devices with little space.
The mini switch monitor monitors the state of one or more
dry normally open contacts and reports the status to a fire
alarm panel. Applicable for operation in fire alarm panels
with Loop AP protocol. Optional equipped with interrupt
for rapid alarm signals like a manual call point.
The states “quiescent”, “pre-alarm”, “alarm” and “fault”
can be recognized. Addressing via DIP switches; the
address can also be modified after installation.

Technical specifications Connection / mounting


Operating voltage 17 V - 28 V DC Connection cable  2-wire
Recommended cable, standard 747180
Current consumption JY(ST)Y-2x2x0.8 mm
at 24 V DC:
0.2 mA Conductor cross-section max. 1,5 mm2 (AWG 15)
Min. (quiescent)
Max. (alarm input)
3.6 mA Electrostatic shielding  not required

Inputs 1 Contact input:


Outputs 0 Voltage at contact input  9 - 11 V DC
Alarm indication red LED Cable resistance max.  50 Ohm
End-of-line resistor EOL (R3) 20 kOhm
Bus activity indication green LED Pre-alarm resistor (R2) 10 kOhm
Short-circuit indication Alarm resistor (R1) 1 kOhm
on the loop or fault of the yellow LED
monitors input
Connection diagram
Integrated isolator yes
-20 °C to +60 °C
Operating temperature
(-4 °F to +140 °F)
Technology / protocol Loop AP / XP95
0 to 95%
Relative humidity
no condensation
Weight 30 g (0.1 lbs)
39 x 39 x 20 mm (WxHxD)
Dimensions
1.5 x 1.5 x 0.8 inch (WxHxD)
The contents of this publication are subject to modifications without notice. All rights reserved.

Approvals / marking

G 210034 2531-CPR-CSP11042
311-810_001 / AI04 / 2021-Aug-18 / en

1/1

Minimax GmbH | Industriestr. 10/12 | 23840 Bad Oldesloe | detection@minimax.de | www.minimax.com