Product Sheet I Detection
Standard detectors
Modules, addressable, DIN rail mounting
Input module IUX 760 M-I Part no.: 908531
Miniature interface for use in devices with little space.
The mini switch monitor monitors the state of one or more
dry normally open contacts and reports the status to a fire
alarm panel. Applicable for operation in fire alarm panels
with Loop AP protocol. Optional equipped with interrupt
for rapid alarm signals like a manual call point.
The states “quiescent”, “pre-alarm”, “alarm” and “fault”
can be recognized. Addressing via DIP switches; the
address can also be modified after installation.
Technical specifications Connection / mounting
Operating voltage 17 V - 28 V DC Connection cable 2-wire
Recommended cable, standard 747180
Current consumption JY(ST)Y-2x2x0.8 mm
at 24 V DC:
0.2 mA Conductor cross-section max. 1,5 mm2 (AWG 15)
Min. (quiescent)
Max. (alarm input)
3.6 mA Electrostatic shielding not required
Inputs 1 Contact input:
Outputs 0 Voltage at contact input 9 - 11 V DC
Alarm indication red LED Cable resistance max. 50 Ohm
End-of-line resistor EOL (R3) 20 kOhm
Bus activity indication green LED Pre-alarm resistor (R2) 10 kOhm
Short-circuit indication Alarm resistor (R1) 1 kOhm
on the loop or fault of the yellow LED
monitors input
Connection diagram
Integrated isolator yes
-20 °C to +60 °C
Operating temperature
(-4 °F to +140 °F)
Technology / protocol Loop AP / XP95
0 to 95%
Relative humidity
no condensation
Weight 30 g (0.1 lbs)
39 x 39 x 20 mm (WxHxD)
Dimensions
1.5 x 1.5 x 0.8 inch (WxHxD)
The contents of this publication are subject to modifications without notice. All rights reserved.
Approvals / marking
G 210034 2531-CPR-CSP11042
311-810_001 / AI04 / 2021-Aug-18 / en
1/1
Minimax GmbH | Industriestr. 10/12 | 23840 Bad Oldesloe | detection@minimax.de | www.minimax.com