TS1600HAC1

The Susol Molded Case Circuit Breaker TS1600H is a 1600A, 3-pole device designed for AC networks with a rated operational voltage of 690V. It features various trip unit characteristics, including overload and short-circuit protection, and has a mechanical durability of 10,000 cycles. The product is compliant with IEC standards and suitable for isolation, with a pollution degree of 3 and an ambient temperature range of -20 to 70 °C for operation.

Uploaded by

Eredia Alfredo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views7 pages

TS1600HAC1

The Susol Molded Case Circuit Breaker TS1600H is a 1600A, 3-pole device designed for AC networks with a rated operational voltage of 690V. It features various trip unit characteristics, including overload and short-circuit protection, and has a mechanical durability of 10,000 cycles. The product is compliant with IEC standards and suitable for isolation, with a pollution degree of 3 and an ambient temperature range of -20 to 70 °C for operation.

Uploaded by

Eredia Alfredo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Product Data Sheet Characteristics

Susol Molded Case Circuit Breaker


TS1600H

General
Product code 0173008500

Product description TS1600H AC1 1600A 3P EXP

Trip Unit AC1(Ammeter, Comm., AC/DC 100V~250V, 60Hz)

[In] rated current 1600 A at 40 ℃

Poles description 3P

Protected poles
3T
description

Neutral position -

Network type AC (50/60 Hz)

Upside connection Front (screw)

Downside connection Front (screw)

Characteristics
[Ue] rated operational
690 V AC
voltage (AC 50/60 Hz)

[Ue] rated operational


-
voltage (DC)

[Uimp] rated impulse


8 kV
withstand voltage

[Ui] rated insulation 1000 V


voltage

Mechanical durability 10000 cycles

Electrical durability (AC) 1000 cycles 690 V In


Electrical durability (DC) -

Utilisation category Category B

Suitability for isolation Yes

Reference standard IEC 60947-2

75 kA at 220/240 V AC 50/60 Hz, IEC 60947-2

70 kA at 380/415 V AC 50/60 Hz, IEC 60947-2

65 kA at 440/460 V AC 50/60 Hz, IEC 60947-2

50 kA at 480/500 V AC 50/60 Hz, IEC 60947-2


[Icu] rated Ultimate short-
circuit breaking capacity
-

45 kA at 660/690 V AC 50/60 Hz, IEC 60947-2

56 kA at 220/240 V AC 50/60 Hz, IEC 60947-2

52 kA at 380/415 V AC 50/60 Hz, IEC 60947-2

48 kA at 440/460 V AC 50/60 Hz, IEC 60947-2

37 kA at 480/500 V AC 50/60 Hz, IEC 60947-2


[Ics] rated service
breaking capacity
-

33 kA at 660/690 V AC 50/60 Hz, IEC 60947-2

165 kA at 220/240 V AC 50/60 Hz, IEC 60947-2

154 kA at 380/415 V AC 50/60 Hz, IEC 60947-2

143 kA at 440/460 V AC 50/60 Hz, IEC 60947-2


[Icm] rated short-circuit
marking capacity
105 kA at 480/500 V AC 50/60 Hz, IEC 60947-2

94.5 kA at 660/690 V AC 50/60 Hz, IEC 60947-2

25 kA at AC 50/60 Hz (1s), IEC 60947-2

-
[Icw] rated short-time
withstand current
-
-

Electronic

L : for overload protection (long time)

S : for short time short-circuit protection

I : for instantaneous short-circuit protection

G : for earth fault protection


Trip unit characteristics
Ammeter

Communication

Zone selective interlocking

Control voltage & frequency : AC/DC 100V~250V, 60Hz)

Adjustable, 9 settings
[Ir] Long-time pick-up
adjustment range
0.8, 0.83, 0.85, 0.88, 0.9, 0.93, 0.95, 0.98, 1 x Iu

Adjustable, 6 settings
[Iu] Long-time pick-up
adjustment range
0.5, 0.6, 0.7, 0.8, 0.9, 1.0 x In

Adjustable, 9 settings
[tr] Long-time delay
adjustment range
0.5s, 1s, 2s, 4s, 8s, 12s, 16s, 20s at 6 x lr, tolerance ±15% or below 100ms

Adjustable, 9 settings
[Isd] Short-time pick-up
adjustment range
1.5, 2, 3, 4, 5, 6, 8, 10, off x Ir, tolerance ±10%

Adjustable, 5 settings

I²t on / off mode

0.05s at 10 x Ir (Tripping time : 20ms < t ≤ 80ms), off mode only


[tsd] Short-time delay
0.1s at 10 x Ir (Tripping time : 80ms < t ≤ 140ms)
adjustment range
0.2s at 10 x Ir (Tripping time : 160ms < t ≤ 240ms)

0.3s at 10 x Ir (Tripping time : 260ms < t ≤ 340ms)

0.4s at 10 x Ir (Tripping time : 360ms < t ≤ 440ms)

Adjustable, 9 settings
[Ii] Instantaneous pick-up
adjustment range 2, 3, 4, 6, 8, 10, 12, 15, off x In (Tripping time : 50ms ± 10ms)
Adjustable, 9 settings
[Ig] Ground-fault
protection pick-up
0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 1, off x In, tolerance: ±10% (Ig>0.4 x In) or ±20% (Ig ≤ 0.4 x
adjustment range
In)

Adjustable, 5 settings

I²t on / off mode

0.05s at 1 x Ir (Tripping time : 20ms < t ≤ 80ms), off mode only


[tg] Ground-fault
protection time delay 0.1s at 1 x Ir (Tripping time : 80ms < t ≤ 140ms)
adjustment range
0.2s at 1 x Ir (Tripping time : 160ms < t ≤ 240ms)

0.3s at 1 x Ir (Tripping time : 260ms < t ≤ 340ms)

0.4s at 1 x Ir (Tripping time : 360ms < t ≤ 440ms)

-
Earth leakage pick-up
adjustment range
-

-
Earth leakage alam time
delay adjustment range
-

-
Earth leakage trip time
delay adjustment range
-

-
[Ip] Pre-trip alarm pick-up
adjustment range
-

-
[tp] Pre-trip alarm time
delay adjustment range
-

Ir (90% ~ 105%) : Trun on


Alarm LED
Ir (105% ~) : Blink

Environment
Pollution degree 3, IEC 60664-1

Degree of protection IP30, IEC 60529

Ambient air temperature


-20…70 °C
for operation

Ambient air temperature


-40…70 °C
for storage

Mounting mode Fixed


Mounting support Backplate

CE (Europe)

-
Approvals1) (General)
CCC (China)

EAC (Russia)

Approvals (shipping) -

RINA (Italy)

1) LS ELECTRIC's standard products are designed for CE.


To check the product with regional certificates, please contact LSE sales representatives.

Dimensions
Width 210 mm

Height 327 mm
Product
Depth 152.5 mm

Weight 13 kg

Width 252 mm

Height 369 mm

Packing Depth 213 mm

Weight 13 kg

Quantity (in a box) 1 pcs.