GENERAL BASIC MECHANICS AND MATERIALS DUCT CONSTRUCTION & INSTALLATION THESE
DESIGNS,DRAWINGS,
1. IT IS THE PURPOSE AND INTENT OF THE SPECIFICATION, NOTES, AND DRAWINGS, THAT THE CONTRACTOR SHALL FURNISH 1. ALL EQUIPMENT SHALL HAVE VIBRATION ISOLATION. NEOPRENE PADS, NEOPRENE MOUNTS OR SPRING ISOLATORS. 1. ALL METALLIC DUCTS SHALL BE CONSTRUCTED AS SPECIFIED IN THE SMACNA "HVAC DUCT CONSTRUCTION STANDARDS - AND SPECIFICATIONS
ALL LABOR AND MATERIAL NECESSARY TO PROVIDE A COMPLETE INSTALLATION OF MECHANICAL SERVICES AS METAL & ARE THE PROPERTY OF
INDICATED ON THE PLANS AND AS HEREINAFTER SPECIFIED COMPLETE IN MATERIALS AND FITTINGS AS MAY BE 2. ESCUTCHEONS: MANUFACTURED WALL, CEILING, AND FLOOR PLATES; DEEP-PATTERN TYPE TO CONCEAL PROTRUDING FLEXIBLE." DESIGNLINK
REQUIRED TO MAKE THE WORK COMPLETE FOR THE PURPOSE FITTINGS AND 2. ALL DUCTWORK TO BE SEALED IN ACCORDANCE WITH THE INTERNATIONAL ENERGY CONSERVATION CODE. ENGINEERING AND
INTENDED. SLEEVES. SHALL NOT BE COPIED
OR REPRODUCE
2. THE DRAWINGS PERTAINING TO THE INSTALLATION GENERALLY INDICATE THE LOCATION OF EQUIPMENT AND OTHER 3. DIELECTRIC FITTINGS: ASSEMBLY OR FITTING HAVING INSULATING MATERIAL ISOLATING JOINED DISSIMILAR METALS TO 3. DUCTS SHALL BE SUPPORTED BY APPROVED HANGERS AT INTERVALS NOT EXCEEDING 10 FEET. FLEXIBLE & OTHER
WITHOUT ITS PRIOR
DETAILS NECESSARY TO THE COMPLETE INSTALLATION. BIDDERS SHALL ACQUAINT THEMSELVES WITH THE WORKING PREVENT GALVANIC ACTION AND STOP FACTORY-MADE DUCTS SHALL BE SUPPORTED PER MANUFACTURER'S INSTRUCTIONS.
CORROSION. WRITTEN CONSENT.
CONDITIONS AND MATERIALS REQUIRED TO ENTIRELY COMPLETE THE WORK READY FOR
USE. 4. EQUIPMENT NAMEPLATES: METAL FACTORY-APPLIED NAMEPLATE PERMANENTLY FASTENED TO EQUIPMENT WITH 4. ACCESSIBLE VOLUME DAMPERS OR OTHER MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DATES
3. ANY CHANGES IN THE LOCATION OF THE EQUIPMENT, ETC., FROM THOSE SHOWN ON THE DRAWINGS SHALL BE MADE OPERATIONAL DATA ENGRAVED OR STAMPED, MANUFACTURER NAME, MODEL NUMBER, SERIAL NUMBER & THE SEAL OR DUCTS OR AT EACH INDIVIDUAL REGISTER, GRILLE OR
WITHOUT CHARGE IF SO DIRECTED BY THE ARCHITECT/OWNER BEFORE MARK OF THE APPROVED DIFFUSER. FIRST RELEASE: 12.19.2023
INSTALLATION. AGENCY. 5. COORDINATE ACTUAL LOCATIONS OF DIFFUSERS, REGISTERS & GRILLES WITH ARCHITECT'S REFLECTED CEILING PLAN TO REVISION DATE:
4. ALL WORK SHALL BE PERFORMED IN A WORKABLE MANNER BY A FULLY LICENSED CONTRACTOR AND IN FULL 5. PRESSURE-SENSITIVE PIPE MARKERS: MANUFACTURER'S STANDARD PREPRINTED, PERMANENT ADHESIVE, AVOID CONFLICTS WITH 12.25.2023
1:
ACCORDANCE WITH LOCAL, STATE, AND NATIONAL CODES, REQUIREMENTS AND COLOR-CODED, PRESSURE-SENSITIVE VINYL PIPE MARKERS, CONFORMING TO ASME LIGHTS.
STANDARDS. A13.1. 2: 01.03.2024
6. FLEXIBLE DUCTS & AIR CONNECTORS SHALL NOT PASS THROUGH ANY FIRE RATED ASSEMBLIES.
5. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS AND INSPECTIONS FOR ALL WORK COVERED BY 6. INSTALL COMPONENTS HAVING PRESSURE RATING EQUAL TO OR GREATER THAN SYSTEM OPERATING PRESSURE. 3:
THE CONTRACT. ALL CERTIFICATES OF INSPECTION SHALL BE DELIVERED TO THE 7. PROVIDE LONG RADIUS ELBOWS OR SQUARE ELBOW WITH TURNING VANES FOR ALL DUCTWORK UNLESS NOTED
OWNER. 4:
7. FABRICATE STRUCTURAL STEEL STANDS TO SUSPEND EQUIPMENT FROM STRUCTURE ABOVE OR SUPPORT EQUIPMENT OTHERWISE.
6. ALL CUTTING AND PATCHING WHICH MUST BE DONE, IN ORDER THAT THE MECHANICAL WORK MAY BE PROPERLY ABOVE 5:
INSTALLED, SHALL BE DONE BY APPROPRIATE TRADESMEN UNDER THIS CONTRACTORS CONTRACT. ALL DISTURBED FLOOR. 8. MAXIMUM FLEXIBLE DUCT LENGTH OF 5 FEET. SUSPEND FLEXIBLE DUCTWORK SO THERE ARE NO KINKS OR SAGS. SEAL
CONSTRUCTION, SURFACES OR FINISHES MUST BE REPLACED OR REPAIRED TO THE ARCHITECT'S OR OWNERS 8. CONSTRUCT CONCRETE EQUIPMENT BASES OF DIMENSIONS INDICATED, BUT NOT LESS THAN 4" LARGER THAN END
REVISIONS
SATISFACTION AT THIS CONTRACTOR'S EXPENSE. UNDER NO CONDITION SHALL STRUCTURAL WORK BE CUT EXCEPT ” THICK. FOLLOW SUPPORTED EQUIPMENT MANUFACTURER'S
SUPPORTED UNIT IN BOTH DIRECTIONS AND AT LEAST CONNECTIONS.
A ISSUED FOR APPROVAL
UPON APPROVAL OF THE ARCHITECT OR STRUCTURAL 4
SETTING TEMPLATES FOR ANCHOR BOLT AND TIE LOCATIONS. USE 3,000-PSI, 28-DAY COMPRESSIVE STRENGTH DUCT INSULATION
B ISSUED FOR APPROVAL
ENGINEER. CONCRETE AND
7. THIS CONTRACTOR SHALL FIELD VISIT SITE PRIOR TO BID AND VERIFY ALL EXISTING CONDITIONS AND SYSTEMS TO REINFORCEMENT. 1. ALL SUPPLY, RETURN & OUTSIDE AIR DUCTWORK INSTALLED IN UNTEMPERED SPACES SHALL BE INSULATED WITH 2" C ISSUED FOR APPROVAL
DETERMINE EXTENT OF WORK. ANY ITEMS NOT SPECIFICALLY INDICATED ON DRAWINGS OR IN SPECIFICATIONS THAT ARE HANGERS AND SUPPORTS THICK, JOHNS MANVILLE MICROLITE EQ FSK TYPE 100, MINIMUM R-6. PROVIDE A REINFORCED ALUMINUM FOIL VAPOR
IN CONFLICT WITH CONTRACT WORK SHALL BE BROUGHT TO THE ATTENTION OF ARCHITECT/ENGINEER PRIOR TO BID FOR SEAL
A DECISION. NO EXTRAS WILL BE ALLOWED FOR LACK OF KNOWLEDGE OF EXISTING 1. COMPLY WITH MSS SP-69 FOR PIPE HANGER SELECTIONS AND APPLICATIONS. JACKET.
CONDITIONS. 2. ALL TOILET EXHAUST DUCTWORK INSTALLED IN UNTEMPERED SPACES SHALL BE INSULATED WITH 1/2" THICK FIBERGLASS
8. THIS CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OTHER TRADES AND VERIFY DIMENSIONS AND LOCATIONS 2. COMPLY WITH MSS SP-69 AND MSS SP-89. INSTALL HANGERS, SUPPORTS, CLAMPS, AND ATTACHMENTS AS REQUIRED TO DUCT
WRAP.
CLIENT
FROM THE ARCHITECTURAL DRAWINGS, FIELD MEASUREMENTS AND SUPPLIER SHOP PROPERLY SUPPORT PIPING FROM BUILDING
DRAWINGS. STRUCTURE. 3. ALL INSULATION, DUCT LININGS, INSULATION COVERINGS AND ACCESSORIES INCLUDING ADHESIVES SHALL HAVE A
9. LAYOUT IS DIAGRAMMATIC AND CONTRACTOR SHALL INSTALL EQUIPMENT TO MEET THE FIELD CONDITIONS. 3. FABRICATE STRUCTURAL-STEEL STANDS TO SUSPEND EQUIPMENT FROM STRUCTURE ABOVE OR TO SUPPORT MAXIMUM FLAME SPREAD INDEX OF 25 AND A SMOKE-DEVELOPED INDEX NOT EXCEEDING
EQUIPMENT ABOVE 50.
10. THIS CONTRACTOR IS RESPONSIBLE FOR THE CONDITION AND PROTECTION FROM DAMAGE OF HIS EQUIPMENT AND FLOOR. 4. LININGS SHALL BE INTERRUPTED AT THE AREA OF OPERATION OF A FIRE DAMPER & A MINIMUM OF 6" UPSTREAM & 6"
SYSTEMS. CONTRACTOR SHALL REPLACE ANY DAMAGED EQUIPMENT AT HIS EXPENSE PRIOR TO FINAL ACCEPTANCE GENERAL PLUMBING NOTES DOWNSTREAM OF ELECTRIC RESISTANCE OR FUEL-BURNING HEATERS IN A DUCT
REGARDLESS OF WHO CAUSED THE SYSTEM.
DAMAGE. THE FOLLOWING NOTES APPLY TO ALL PLUMBING PIPING SHOWN ON PIPING DRAWINGS UNLESS NOTED OTHERWISE. 5. INSULATED EXTERIOR DUCTS SHALL BE INSULATED WITH EXTERIOR 4.4" THK JOHN MANSVILLE MICROLITE EQ FSK TYPE 75
SEAL
11. CONTRACTOR SHALL REMOVE ALL DEBRIS FROM JOB SITE AND LEAVE ALL WORK AND EQUIPMENT IN CLEAN WORKING OR LINED WITH 3" THK JOHN MANSVILLE LINOCOUSTIC RC, MINIMUM R-12, & PROTECTED WITH AN APPROVED
CONDITION. 1. THE PLUMBING CONTRACTOR SHALL ACCURATELY COORDINATE THE SIZES AND LOCATIONS OF ALL PIPING AND WEATHERPROOF
EQUIPMENT WITH THE LOCATIONS OF THE LIGHT FIXTURES, STRUCTURAL, CEILING HEIGHTS AND TYPES; AND THE WORK BARRIER.
12. THIS CONTRACTOR SHALL NOTE THAT THE ELECTRICAL DESIGN AND DRAWINGS ARE BASED ON THE EQUIPMENT OF ALL OTHER TRADES TO PREVENT PIPE INSULATION
SCHEDULED AND SHOWN ON THESE DRAWINGS. IF THE MECHANICAL CONTRACTOR SHOULD SUBMIT FOR REVIEW CONFLICTS.
EQUIPMENT REQUIRING CHANGES TO THE ELECTRICAL DESIGN FOR WHICH THE ELECTRICAL CONTRACTOR WILL 2. ALL SANITARY AND STORM LINES 3" AND LARGER PITCHED AT 1/8" PER FOOT UNLESS NOTED OTHERWISE. ALL SANITARY 1. PIPE INSULATION SHALL HAVE A MAXIMUM FLAME SPREAD INDEX OF 25 AND A SMOKE-DEVELOPED INDEX NOT EXCEEDING
REQUEST AN EXTRA, THIS EXTRA WILL BE PAID BY THE MECHANICAL AND STORM LINES 2 1/2 " AND SMALLER PITCHED AT 1/4" PER FOOT UNLESS NOTED OTHERWISE. 450. INSULATION INSTALLED WITHIN AN AIR PLENUM SHALL HAVE A MAXIMUM FLAME SPREAD INDEX OF 25 AND A
CONTRACTOR 2 SMOKE-DEVELOPED INDEX NOT EXCEEDING
13. ALL EQUIPMENT AND INSTALLATION SHALL COMPLY WITH THE CURRENT CODE REQUIREMENTS. 3. THE PLUMBING CONTRACTOR SHALL PROVIDE PROPER BACKFLOW PREVENTION PER CURRENT CODES AT CONNECTION 50.
TO ALL EQUIPMENT (ICE MAKER, SINKS, FOOD SERVICE EQUIPMENT, ETC.) AND INCLUDING ITEMS PROVIDED BY PIPE INSTALLATION & MATERIALS
14. CONTRACTOR SHALL THOROUGHLY SEAL WALL AND FLOOR PENETRATIONS WITH THE APPROPRIATE MATERIAL AND/OR OTHERS. SIGNATURE
EQUIPMENT TO MEET THE FIRE 4. ALL COLD WATER, HOT/TEMPERED WATER AND HOT/TEMPERED WATER RETURN PIPING SHALL RUN ABOVE CEILING 1. STEEL PIPING SHALL BE SCHEDULE 40 BLACK STEEL CONFORMING TO ASTM A 53.
RATING. UNLESS NOTED
15. SUBMIT SHOP DRAWINGS ON ALL EQUIPMENT AND MATERIALS. OTHERWISE. 2. INSTALL PIPING FREE OF SAGS AND BENDS.
5. ALL COLD WATER, HOT/TEMPERED WATER AND HOT/TEMPERED WATER RETURN PIPING IS TO BE INSULATED FOR METAL
16. PREPARE AND PROVIDE OWNER WITH A SCALE SET OF AS-BUILT DRAWINGS. PIPING. CPVC AND PEX PIPING ARE 3. INSTALL SLEEVES FOR PIPES PASSING THROUGH CONCRETE AND MASONRY WALLS, GYPSUM-BOARD PARTITIONS,
EXEMPTED. CONCRETE FLOOR, CONCRETE ROOF SLABS AND WHERE
17. INSTRUCT OWNER IN THE PROPER OPERATION, MAINTENANCE AND SERVICING OF ALL SYSTEMS. PROVIDE IN A BOUND 6. PROVIDE SHUT OFF VALVE AT ALL PLUMBING FIXTURES SUPPLY LINE EXCEPT FIXTURES WITH IT'S OWN STOP VALVES INDICATED.
FORM THREE (3) SETS OF OPERATIONS, MAINTENANCE AND INSTRUCTION MANUALS, INCLUDING INFORMATION ON SPARE UNLESS NOTED 4. INSTALL HANGERS, SUPPORTS, CLAMPS, AND ATTACHMENTS AS REQUIRED TO PROPERLY SUPPORT PIPING FROM
PARTS, LUBRICATION SCHEDULE, WIRING DIAGRAMS, ETC., FOR ALL FIXTURES AND OTHERWISE. BUILDING STRUCTURE. COMPLY WITH MSS SP-69 AND
EQUIPMENT. 7. PROVIDE HINGED AND LATCHING TYPE GASKETED ACCESS DOORS ADJACENT TO ALL SHUT-OFF VALVES FOR INSPECTION SP-89.
18. THE CONTRACTOR SHALL PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR ALL EQUIPMENT ON SITE FOR AND 5. INSTALL MSS TYPE 40, PROTECTIVE SHIELDS ON COLD PIPING WITH VAPOR BARRIER AND MSS TYPE 39 FOR INSULATION SITE INFORMATION
REVIEW BY INSPECTORS. ALL EQUIPMENT MUST BEAR THE LABEL OF AN APPROVED INSPECTION AGENCY. THE SERVICE. WITHOUT VAPOR
CONTRACTOR SHALL SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS TO THE LOCAL AUTHORITIES AS 8. PLUMBING CONTRACTOR TO FURNISH SLEEVES FOR INSTALLATION, FOR PIPING PASSING THRU WALLS EXTENDING FULL BARRIER. ADDRESS:
PVS CHEMICAL SOLUTIONS,
REQUIRED. HEIGHT UP TO DECK. PLUMBING CONTRACTOR TO PROVIDE FIRE STOPPING OF ALL PIPE PENETRATIONS OF FIRE RATED 6. INSTALL PIPING AT CODE REQUIRED SLOPE. INC. 12260 S
CARONDOLET AVE
19. THIS CONTRACTOR SHALL PERFORM ALL EXCAVATING AND BACK FILLING REQUIRED FOR HIS WORK. WALLS. CHICAGO, IL 60633
7. JOINTS BETWEEN DIFFERENT METALLIC PIPING MATERIALS SHALL BE MADE WITH APPROVED DIELECTRIC FITTINGS OR
20. CONTRACTOR SHALL FURNISH AND INSTALL ALL STARTERS, CONTROLS, RELAYS, DEVICES, ETC. FOR A COMPLETELY 9. PLUMBING CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL TRADES PAINTING OF ALL EXPOSED BRASS CONVERTER
OPERATIONAL PIPING/INSULATION IN PUBLIC FITTINGS.
SYSTEM. SPACES. CONDENSATE DRAIN PIPING DRAWING INFORMATION
WARRANTY/GUARANTEE 10. ALL VENT PIPING FOR GAS PIPING, SANITARY PIPING, ETC. SHALL BE EXTENDED TO OUTSIDE THE BUILDING
1. ALL CONDENSATE DRAIN AND VENT PIPING SHALL BE:
DRAWN BY : NK
1. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS OR REPAIR, WITHOUT COST TO THE OWNER, ANY SUCH DEFECTS 11. INSTALL SURESEAL OR EQUAL DEVICES IN ALL EXISTING & NEW FLOOR DRAINS & HUB DRAINS.
WITHIN ONE (1) YEAR TO DATE, AFTER FINAL ACCEPTANCE OF THE BUILDING BY THE OWNER AND ENGINEER. HE SHALL 1.1. CISPI 301 HUBLESS PVC - ASTM D 2665, FITTINGS ASTM D 2949 APRVD BY : JK
ALSO GUARANTEE THAT THE WORKMANSHIP IS OF HIGH QUALITY AND THAT ALL EQUIPMENT FURNISHED UNDER THIS 12. CLEANOUT COVERS SHOULD BE SELECTED TO BLEND WITH FLOOR TYPE. PROVIDE CARPET FLANGE OR MARKER FOR 1.2. TYPE "L" HARD DRAWN COPPER SCALE : AS NOTED
CONTRACT FULFILLS THE REQUIREMENTS OF THE CARPETED AREAS, NICKEL BRONZE NON-SKID FINISHED FLOOR TOPS FOR HARD SURFACE AREAS, TOPS WITH SHALLOW
SPECIFICATIONS. PROJECT NO: 502001
DEPRESSION FOR VINYL OR FLOOR TILE & HEAVY DUTY CAST IRON TOPS FOR UNFINISHED FLOORS IN BOILER ROOM AND 2. PIPING MINIMUM SLOPE = 1% OR 1/8" PER FOOT.
PVS CHEMICAL
2. ALL EQUIPMENT AND MATERIAL WARRANTIES ARE TO BE HONORED BY THIS CONTRACTOR. MECHANICAL SPACES. COORDINATE WITH FLOOR TYPES INDICATED ON ARCHITECTURAL FLOOR PROJECT
PLANS. 3. PIPE HANGERS FOR SUSPENDED PIPE SHALL BE ADJUSTABLE. CONTROL ROOM
13. PROVIDE EASY ACCESS TO ALL PRV.
BUILDING
4. COPPER PIPE SHALL BE PROTECTED FROM DISSIMILAR METAL HANGERS.
5. HANGERS:
5.1. SWIVEL RING HANGERS - GRINNEL FIG. 69 OR EQUAL.
ISSUED FOR APPROVAL
5.2. CLEVIS HANGERS - GRINNEL FIG 260 OR EQUAL.
5.3. PIPE ROLLS - GRINNEL FIG 181 OR EQUAL.
REFERENCE
5.4. TRAPEZE HANGERS - UNISTRUT PG OR EQUAL.
DRAWING NO:
7. ALL JOINTS AND CONNECTIONS SHALL BE GAS-TIGHT AND WATER-TIGHT AND FULLY COMPLY WITH THE PLUMBING CODE.
M0-00
DESIGN TEAM
THESE
DESIGNS,DRAWINGS,
AND SPECIFICATIONS
ARE THE PROPERTY OF
DESIGNLINK
ENGINEERING AND
SHALL NOT BE COPIED
OR REPRODUCE
AHU-01
WITHOUT ITS PRIOR
LOCATION OF AHU-01 IS INDICATIVE ,SHALL
BE AS PER STRUCTURAL DRAWINGS.
WRITTEN CONSENT.
DATES
FIRST RELEASE: 12.19.2023
REVISION DATE:
1: 12.25.2023
2: 01.03.2024
T
3:
4:
CONNECTED TO AHU-01
5:
REVISIONS
A ISSUED FOR APPROVAL
MWave Freezer
4"ø EA
CLIENT
SEAL
NORTH
ROOF TOP UNIT SCHEDULE (PACKAGED UNIT) DX COOLING WITH INDIRECT FIRED GAS HEATING
SIGNATURE
UNIT DATA
OUTSIDE AIR COMPRESSOR ELECTRIC CURRENT
DX- COOLING COIL DATA ELECTRICAL HEATER
SUPPLY FAN DATA CONDITION FINAL FILTER DATA
SITE INFORMATION
EC- DISPOSA
EXTERNAL - 6.9 9 208/1/60 MERV 13 11 BARD ADDRESS:
AHU-01 1 CONTROL ROOM EC - FAN 550 0.15 MOTOR 50 11.3 YES 1.35 1.12 77.5 65 58.2 57.1 330 R-410A 91/74 -6/-7.2 BLE 16 20 208/1/60 W18HB0Z 33.3X17.1X74. 500
WALL MOUNT FILTER DN1 5
PVS CHEMICAL SOLUTIONS,
INC. 12260 S
CARONDOLET AVE
CHICAGO, IL 60633
FAN SCHEDULE
AIR TERMINAL SCHEDULE MOTOR DATA
ACTUAL
MARK QTY. AREA/SYSTEM SERVED LOCATION EXTERNAL STATIC MAX. MANUFACTURER MODEL REMARKS DRAWING INFORMATION
MAX AIRFLOW OF
MODULE SIZE PRESSURE FAN RPM DRIVE TYPE MOTOR V/Ph/Hz STARTER
MARK TYPE AIRFLOW REMARK EACH FAN
(IN) (IN WC) (WATT)
(CFM) (CFM) DRAWN BY : NK
APRVD BY : JK
SCALE : AS NOTED
EF-01 1 TOILET EC
SG-01 SUPPLY GRILLE CEILING 80 0.4 880 EC MOTOR 21.5 120/1/60 GREENHECK SP-AP
10X22 600 MOTOR PROJECT NO: 502001
CONTROL ROOM
BUILDING
NOTES: --
RG-01 RETURN GRILLE 12X22 600 01. EQUIPMENT VENDOR AND CONTRACTOR SHALL SUPPLY AND INSTALL EQUIPMENT
IN ACCORDANCE WITH THE SCHEDULE. ISSUED FOR APPROVAL
02. EQUIPMENT SCHEDULE SHALL BE READ IN CONJUNCTION WITH DRAWINGS AND SPECIFICATIONS.
REFERENCE
03. FAN SHALL HAVE AMCA SEAL & U.L.I CERTFIED.
04. SAFETY DISCONNECT SWITCH
05. DESIGN IS BASED ON SPECIFIED MANUFACTURER.
IF CONTRACTOR SELECTS EQUIPMENT FROM ANOTHER MANUFACTURER
AND IF IT REQUIRES MODIFICATION OF STRUCTURE, ELECTRICAL,
ARCHITECTURE,PIPING, DUCTWORK, CONTROLS ETC.
THEN CONTRACTOR SHALL BE RESPONSIBLE FOR NEW DESIGN AND
MODIFICATION COST. CLIENT SHALL NOT BE RESPONSIBLE FOR
EXTRA COST ASSOCIATED WITH ANY MODIFICATION.
DRAWING NO:
06. CONTRACTOR SHALL PROVIDE NECESSARY STRUCTURAL FRAMING AROUND WALL
AND ROOF OPENINGS TO SUPPORT PENETRATIONS. M0-01
DESIGN TEAM
PLUMBING FIXTURE SCHEDULE
PLUMBING FIXTURE PIPE CONNECTION SIZE
WC 1/2" - 4" 2" FLOOR-MOUNT TWO-PIECE ELONGATED 1.6 GPF TOILET WITH TANK. REFER DRAWINGS FOR DETAILS.
THESE
LAV 1/2" 1/2" 2" 1 1/2" MAKE - AMERICAN STANDARD DESIGNS,DRAWINGS,
WATER CLOSET WC MODEL NO - CHAMPION PRO AND SPECIFICATIONS
KITCHEN SINK 1/2" 1/2" 2" 1 1/2" ELONGATED TOILET
ARE THE PROPERTY OF
FD - - 3" - IT SHALL INCLUDE ROBUST METAL TRIP LEVEL & METAL SHANK FILL VALVE DESIGNLINK
ENGINEERING AND
SHALL NOT BE COPIED
OR REPRODUCE
WITHOUT ITS PRIOR
WRITTEN CONSENT.
WATER PIPE SIZING TABLE
WALL MOUNTED RESTROOM LAV SHALL BE MADE OF VITREOUS CHINA MATERIAL, 20" IN LENGTH AND 18" IN WIDTH WITH THREE HOLES,.
CONCEALED ARM CARRIER, ASSOCIATED FITTINGS LIKE DRAIN, P TRAP, STRAINER ANGLE VALVES ETC . DATES
4"ø SAN WALL MOUNTED LAV LAV
SFU RANGE MINIMUM PIPE SIZES (INTERNAL DIA.)
VTR MAKE -AMERICAN STANDARD FIRST RELEASE: 12.19.2023
FCO MODEL NO -MODER LIFE K-77767-8
REVISION DATE:
1 1/2"ø V 0-1 3/4"
1: 12.25.2023
2"ø SAN
1-2 1" 2: 01.03.2024
FD
MWave 3:
Freezer
2-6 1 1/2" HOT AND COLD WATER FAUCET FOR LAVATORY WITH 1.0 GPM PRESSURE COMPENSATING,VANDAL-RESISTANT AERATOR. 4:
4"ø SAN RUNNING TIME WILL BE 10 SECONDANS.
HOT AND COLD WATER - 5:
3"ø SAN 7-15 1 3/4" FAUCET FOR LAV MAKE -AMERICAN STANDARD
MODEL - METERING FAUCETS CENTERSET SPOUT
REVISIONS
I.E.= -1' - 6 7/16" 16-70 2" A ISSUED FOR APPROVAL
OWNER SHALL CONNECT
TO EXISTING UTILITES. B ISSUED FOR APPROVAL
71-150 2 1/2"
C ISSUED FOR APPROVAL
151-375 3"
-
LEVEL 01 -PLUMBING SANITARY PLAN STAINLESS STEEL 35-3/4" x 18-1/2" x 10", EQUAL DOUBLE BOWL UNDERMOUNT SINK KIT. SINK MANUFACTURED FROM 18 GAUGE 304 STAINLESS STEEL
WITH A LAUSTROUS STAIN FINISH, REAR CENTER DRAIN PLACEMENT, AND SIDES AND BOTTOM PADS. SUPPLY ASSOCIATED ACCESSORIES AND
SCALE: 1/4" = 1'-0" 376-1000 4"
FAUCET, OR EQUAL, REFER TO DRAWING FOR DETAIL.
KITCHEN SINK CLIENT
NORTH MAKE - ELKAY
MODEL NO - ELUH361710DBG
3" 36 42
NOTES:--
1/2"ø DCW
1/2"ø DHWS 1 SCHEDULE COVERS MAJOR PLUMBING FIXTURES, FITTINGS AND ACCESSORIES.
EWH-01 2 CONTRACTOR SHALL SUPPLY AND INSTALL ALL FITTINGS, ACCESSORY, ETC SHOWN ON DRAWING AS PER THE SPECIFICATION..
3 CONTRACTOR SHALL SUPPLY AND INSTALL THE COMPLETE OPERATING SYSTEM
1/2"ø DCW 4 IMAGES ARE SHOWN FOR REFERENCE ONLY. PLUMBING CONTRACTOR SHALL COORDINATE WITH OTHER TRADES.
1"ø DCW
DRAWN BY : NK
NOTES: - APRVD BY : JK
LEVEL 01 -PLUMBING DOMESTIC WATER PLAN 1. PROVIDE T&P RELIEF VALVE AND CONTROL ACCESSORIES.
SCALE : AS NOTED
SCALE: 1/4" = 1'-0" PROJECT NO: 502001
2. DESIGN IS BASED ON SPECIFIED MANUFACTURER. IF CONTRACTOR SELECTS EQUIPMENT FROM ANOTHER MANUFACTURER AND IF IT REQUIRES MODIFICATION OF
STRUCTURE, ELECTRICAL, ARCHITECTURAL, PIPING, DUCT WORK, CONTROLS ETC. THEN CONTRACTOR SHALL BE PROJECT PVS CHEMICAL
NORTH
RESPONSIBLE FOR NEW DESIGN AND MODIFICATION COST. CLIENT SHALL NOT BE RESPONSIBLE FOR PAYMENT ASSOCIATED WITH ANY MODIFICATION.
CONTROL ROOM
BUILDING
REFERENCE
DRAWING NO:
P0-00