Submit t al
Jo b/Pro je ct : Re pre se nt at ive :
ESP-Syst e mwize : WIZE-9BEC2B9C Cre at e d O n: 02/18/2025 Pho ne :
Lo cat io n/Tag: Email:
Engine e r: Submit t e d By: Dat e :
Co nt ract o r: Appro ve d By: Dat e :
In-Line Fire Pump Selection Criteria NFPA Limits
Pump Mo de l: 4x4x9.5F Rat e d Flo w 500 US gpm 140% He ad o f Rat e d He ad 112 psi
No m. Spe e d: 3550 rpm Rat e d He ad 80 psi 65% He ad at 150% Flo w 52 psi
Marke t : List e d Fire Pump Imp. Dia 7.295 in Flo w at 150% 750 US gpm
Appro val/List ing: FM/UL Po we r Re quire d at Dut y 31.7 hp He ad at 150% 58.1 psi
Rat e d Efficie ncy 73.5 % Po we r Re q at 150% 36.4 hp
Fluid Wat e r Efficie ncy at 150% 69.6 %
T e mpe rat ure 85 ºF Max BHP 38 hp
Sp. Gravit y 1.000 Clo se d Valve He ad 92.6 psi
140% He ad o f Rat e d He ad 112PSI
Typical Performance Curve is shown. Fire Pumps are tested to ANSI/HI 14.6 acceptance grade 1U.
Rated Duty Point is guaranteed within the following tolerances: Flow 0% to + 10%, Head 0% to + 6%.
NO OTHER POINTS ARE GUARANTEED. PLEASE CONSULT FACTORY IF NEEDED.
Pe rfo rmance Curve Dat a
Flo w (US gpm) He ad (psi) Efficie ncy (%) Po we r Re quire d (hp) NPSHr (ft )
0 92.6 0 0 12
125 90.4 38.3 20.1 12
250 88.2 53.7 23.9 12
375 85.4 67.7 27.6 12
500 80 73.5 31.7 12.2
750 58.1 69.6 36.4 19.8
1046 7.88 13.9 34.5 33.5