95-8661-7.4 (UD10) - Web
95-8661-7.4 (UD10) - Web
FlexVu® Explosion-Proof
Universal Display Unit
Model UD10
IMPORTANT
Be sure to read and understand the entire instruction
manual before installing or operating the gas detection
system. This product can be used with a variety of Det-
Tronics gas detectors to provide early warning of the
presence of a toxic or explosive gas mixture. Proper
device installation, operation, and maintenance is
required to ensure safe and effective operation. If this
equipment is used in a manner not specified in this
manual, safety protection may be impaired.
APPLICATION
The FlexVu® Model UD10 is recommended for
applications that require a gas detector with digital
readout of detected gas levels as well as analog 4-20
mA output with HART, relay contacts, and Modbus
RS485. The UD10 Universal Display Unit is designed for
use with Det‑Tronics gas detectors listed in Table 1.
The UD10 features non-intrusive calibration. A magnet Visible Outputs: Backlit LCD display
is used to perform calibration as well as to navigate the HART slave interface via HART
UD10’s internal menu. Communicator
Notes: All values are a percentage of full scale with the exception of Oxygen, which is the actual percent of Oxygen, and models OPECL and LS2000, which are the value in LFL-meters.
Low alarm must be less than or equal to the high alarm.
Changing the Measurement Range will reset all alarm and Cal Gas values to the default settings for the selected range.
Alarm relays are selectable for either normally energized or normally de-energized coils, with selectable latching or non-latching contacts. Fault relay is normally energized (with no
faults).
When the auxiliary relay is set for latching and the gas level goes above the auxiliary alarm threshold, the 4-20 mA output will latch to the highest gas level detected until it is reset.
When CGS mode is selected, the default setting for the auxiliary relay is a threshold of 90% full scale, with latching output.
*Does not support C7064C hydrogen sulfide or C7065E oxygen, but includes C7064E hydrogen sulfide,
C7067E chlorine, C7066E carbon monoxide, and C7068E sulfur dioxide.
7.4 2 95-8661
HART COMMUNICATION To actuate a magnetic switch, lightly touch the magnet to the viewing
window of the UD10 directly over the switch icon on the faceplate.
A HART interface provides device status information and field
programming capability.
CAUTION
Handle magnets with care! Personnel wearing
MAGNETIC SWITCHES pacemakers/defibrillators should not handle magnets.
Four internal magnetic switches provide a non‑intrusive user Modern magnet materials are extremely strong
interface that allows navigation through the menu and adjustment magnetically and somewhat weak mechanically. Injury
of configuration parameters in the field without the use of a HART is possible to personnel, and magnets themselves can
handheld device. See Figure 1 for switch locations. easily get damaged if allowed to snap towards each
other, or if nearby metal objects are allowed to be
attracted to the magnets.
PREVIOUS
CANCEL / ESCAPE
ENTER / SELECT
NEXT
B2426
CANCEL / ESCAPE
NEXT
7.4 3 95-8661
NOTE Access To Menus
Det-Tronics offers two magnet options for activating
To access the menus, use the magnet to activate the ENTER/
internal magnetic switches. While the two magnets can
SELECT button. This will display the Main Menu.
usually be used interchangeably, the best results will
be achieved if they are used as follows: The Magnetic
The actual menu structure varies depending upon the device that
Tool (p/n 009700-001) is the stronger magnet and is
is connected to the UD10. Menus for the various devices can be
recommended for activating the switches on the UD10
found in the corresponding appendix in this manual.
viewing window. The Calibration Magnet (p/n 102740‑002)
is recommended for applications that involve initiating
Some areas of the menu contain additional information, which is
calibration or resetting the detector by touching the side
indicated by the presence of an arrow on that particular line. By
of a metal junction box or detector housing (PIRECL,
placing the magnet to the glass over the ENTER/SELECT button,
OPECL, etc). Throughout this manual, the term “magnet”
the next screen with the additional information will be shown.
can refer to either device.
The UD10 automatically returns to the main screen after 10 minutes
GAS LEVEL INDICATION if no activity occurs.
The UD10 display will show a plus sign “+” to the right of the
indicated value (i.e., 100+%LFL, 1000+PPM), to indicate an over- Quick Access/Shortcut: Fault Menu
range. During an under-range condition, the display continues to
To access the fault menu quickly, when a fault is present, touch the
show 0%LFL or 0PPM. Actual sensor signal / gas level can be
magnet to the glass by the PREVIOUS button.
examined using display to check the device (sensor) “PROCESS
VARS” > ANALOG INPUT XX.XX mA to check an actual device
output. Refer to the appropriate appendix for the attached sensor
type.
SPECIAL STATES
Special states other than warm-up, normal operation, and fault
require user action for activation. These include calibration,
configuration, and parameter indication / verification. See Table 2.
7.4 4 95-8661
RELAYS UD10 with Model PIRECL
The display unit has 4 output relays — high alarm, low alarm, PIRECL supports two fault modes: PIR9400 and Eclipse mode.
auxiliary alarm, and fault. The relays have form C (SPDT) contacts. PIR9400 fault mode uses fault codes below 1 mA, while Eclipse
Low, auxiliary, and high alarm relay contacts are selectable for mode uses no levels below 1 mA. In the Standard (default) mode,
latching or non‑latching operation, as well as normally energized or the UD10 programs the PIRECL for Eclipse fault mode to ensure
normally de‑energized (default) coils. During normal operation, the proper HART communication in the event of a fault. In the Replicate
fault relay is energized. mode, the UD10 programs the PIRECL for PIR9400 fault mode.
IMPORTANT
MODBUS COMPATIBILITY
Direct connection of 120/240 VAC to the relay terminals
inside the UD10 enclosure is not allowed, since The UD10 supports RS485 Modbus RTU communi-cation. See
switching relay contacts can induce electrical noise Addendum number 95-8639 for details.
into the electronic circuitry, possibly resulting in a false
alarm or other system malfunction. If the application
requires that AC powered equipment be controlled by DEVICE ENCLOSURE
the transmitter, the use of externally located relays is The UD10 housing is a 5 port aluminum or stainless steel explosion‑proof
recommended. junction box with a clear viewing window.
7.4 5 95-8661
LOGGING IMPORTANT SAFETY NOTES
Events that can be logged in the UD10 include:
CAUTION
• • Calibration (Date, time, and success Y/N are logged for The wiring procedures in this manual are intended to
detectors that do not provide their own calibration logging ensure proper functioning of the device under normal
capabilities.) conditions. However, because of the many variations in
wiring codes and regulations, total compliance to these
Faults that are logged in the UD10 include: ordinances cannot be guaranteed. Be certain that all
• • Detector fault wiring complies with the NEC as well as all local codes.
If in doubt, consult the authority having jurisdiction
• • Low power
before wiring the system. Installation must be done by
• • General fault a properly trained person.
Alarms that are logged in the UD10 for gas detector inputs include:
CAUTION
• • High gas alarm This product has been tested and approved for use in
• • Low gas alarm hazardous areas. However, it must be properly installed
and used only under the conditions specified within
• • Aux alarm.
this manual and the specific approval certificates. Any
device modification, improper installation, or use in a
The UD10 has its own battery backed real time clock (RTC) and its
faulty or incomplete configuration will render warranty
own event logs. The RTC in the UD10 can be set from the UD10
and product certifications invalid.
display, Modbus or HART interfaces. The RTC in the gas detector
(any HART detector having an RTC) can be set independently using
the UD10 menu, or by using the synchronize command, which will set CAUTION
the detector RTC to the same time as the UD10 RTC. See Figure 3. The device contains no user serviceable components.
Service or repair should never be attempted by the
The UD10 can display the detector event and calibration logs (if user. Device repair should be performed only by the
available). The UD10 has its own 1,000‑entry event log available manufacturer.
under the Display Status‑>History‑>Event Log menu.
LIABILITIES
UD10 event logs can be read from the HART interface or the The manufacturer’s warranty for this product is void,
Modbus interface. and all liability for proper function of the detector is
irrevocably transferred to the owner or operator in the
Detector calibration and event logs can also be read from the event that the device is serviced or repaired by personnel
detector HART interface (where available). not employed or authorized by Detector Electronics
Corporation, or if the device is used in a manner not
conforming to its intended use.
WARNING
To avoid a potential Electrostatic Discharge (ESD),
the painted surface of the junction box should only be
cleaned with a damp cloth.
MODBUS CONTROL
SYSTEM
PLC/DCS CAUTION
GAS
DETECTOR HART UD10 Unused conduit entries must be closed with suitably
CONTROL certified blanking elements upon installation.
HART
SYSTEM
PLC/DCS
HART
Handheld AMS
HART
Handheld
7.4 6 95-8661
INSTALLATION IDENTIFICATION OF DETECTOR MOUNTING
LOCATIONS
NOTE
The gas detector housing must be electrically connected Identification of the most likely leak sources and leak accumulation
to earth ground. A dedicated earth ground terminal is areas is typically the first step in identifying the best detector
provided on the UD10. mounting locations. In addition, identification of air current/wind
patterns within the protected area is useful in predicting gas leak
NOTE dispersion behavior. This information should be used to identify
Refer to the Model UD10 Safety Manual, number 95- optimum detector installation points.
8668, for specific requirements and recommendations
applicable to the proper installation, operation, and If the vapor of interest is lighter than air, place the detector above
the potential gas leak. Place the detector close to the floor for
maintenance of SIL-Certified Model UD10 displays.
gases that are heavier than air. Note that air currents may cause a
gas that is slightly heavier than air to rise under some conditions.
The detector must always be installed per local installation codes.
Heated gases may also exhibit the same phenomenon.
Before installing the gas detector, define the following application
The most effective number and placement of detectors varies
details:
depending on the conditions on site. The individual designing the
installation must often rely on experience and common sense to
IDENTIFICATION OF VAPOR(S) TO BE DETECTED determine the detector quantity and best locations to adequately
protect the area. Note that it is typically advantageous to locate
It is necessary to identify the vapor(s) of interest at the job site. detectors where they are accessible for maintenance. Locations
The fire hazard properties of the vapor, such as vapor density, near excessive heat or vibration sources should be avoided.
flashpoint, and vapor pressure should be identified and used to
assist in selecting the optimum detector mounting location within Final suitability of possible gas detector locations should be
the area. verified by a job site survey.
For cross sensitivity information, refer to each gas detector’s The gas detector must be mounted with the sensor in the correct
corresponding instruction manual. Refer to Table 6 in the orientation as shown in Table 3.
“Specifications” section for a list of gas detectors and their
corresponding instruction manuals. If the UD10 faceplate is not correctly oriented, it can be rotated
at 90 degree increments by pulling the electronic module from
the four mounting posts that secure it to the junction box and
repositioning it as desired. Note that the module is held in place
Table 3—Device Orientation
by a compression fitting – no screws are involved.
Device Orientation
PIR9400 Horizontal
PIRDUCT Horizontal
PIRECL Horizontal
PIRECL-CO2 Horizontal
OPECL Horizontal
LS2000 Horizontal
7.4 7 95-8661
WIRING SHIELD CONNECTIONS
The UD10 provides terminals for proper grounding of wiring
POWER SUPPLY REQUIREMENTS cable shields (located on the sensor, 4-20 mA, and operating
power terminal blocks). These shield terminals are not connected
Calculate the total gas detection system power consumption rate
internally, but are connected to ground through capacitors. The
in watts from cold start-up. Select a power supply with adequate
capacitors ensure an RF ground, while preventing 50/60 Hz ground
capability for the calculated load. Ensure that the selected power
loops.
supply provides regulated and filtered 24 Vdc output power for the
entire system. If a back-up power system is required, a float‑type
Ground all shields as shown in the wiring examples throughout this
battery charging system is recommended. If an existing source of 24
manual.
Vdc power is being utilized, verify that system requirements are met.
The acceptable voltage range is 18-30 Vdc measured at the input to
IMPORTANT
the UD10.
For proper grounding, all junction boxes / metal
enclosures must be connected to earth ground.
NOTE
The power supply must meet the noise requirements
The following are required for installations requiring CE Mark
for HART systems. If noise or ripple on the main power
compliance:
source could interfere with the HART function, an isolated
power source (Figure 11) is recommended. (For detailed • • For shielded cable installed in conduit, attach the wire
information regarding power supply specifications, refer shields to the “shield” connections on the terminal blocks, or to
to the HART Communication Foundation’s document earth ground on the case.
“FSK Physical Layer Specification” HCF_SPEC-54.) • • For installations without conduit, use double shielded
cable. Terminate the outer shield to earth ground on the case.
Terminate the inner shield to the “shield” connection on the
WIRING CABLE REQUIREMENTS
terminal blocks.
Always use proper cabling type and diameter for input power as •
well as output signal wiring. 14-18 AWG, 2.5–0.75 mm2 shielded
stranded copper wire is recommended. Correct wire size depends JUMPER SETTING FOR 4-20 MA LOOP
on the device and wire length. Refer to the appropriate appendix for
In order for the 4-20 mA current loop to operate properly, +24 Vdc
additional information. The maximum cable length from power source
must be applied to terminal P1-3. This can be accomplished in one
to UD10 is 2000 feet. Maximum cable length from UD10 to sensor is
of two ways:
2000 feet.
• • For a non-isolated 4-20 mA loop, set jumper plug as
NOTE shown in Figure 4. This applies +24 Vdc to P1-3 via an internal
The use of shielded cable in conduit or shielded armored connection to terminals P2-2 and P2-5.
cable is highly recommended. In applications where • • If the 4-20 mA loop will receive power from a source other
the wiring is installed in conduit, dedicated conduit than the UD10’s main power source (isolated), set the jumper
is recommended. Avoid low frequency, high voltage, plug as shown in Figure 5 to remove the internal connection.
and non‑signaling conductors to prevent nuisance EMI
problems.
CAUTION
The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent water
ingress and/or maintain the explosion-proof rating.
7.4 8 95-8661
WIRING PROCEDURE Figure 7 shows a UD10 Wired to a PLC using 3-Wire Shielded
Cable with a 4-20 mA Non-Isolated Sourcing Output.
NOTE
The following section shows the output of the UD10
Figure 8 shows a UD10 Wired to a PLC using 4-Wire Shielded
wired to a generic 4-20 mA signal receiver in various
Cable with a 4-20 mA Non-Isolated Sourcing Output.
configurations. Since the UD10 can be used with a
variety of different detection devices, information that
Figure 9 shows a UD10 Wired to a PLC with a 4-20 mA Isolated
is specific to each detector model (wiring, calibration,
Sourcing Output.
HART menus, etc.) is covered in an appendix that is
dedicated to that device. Refer to the appropriate
appendix at the back of this manual for specific GREASE/LUBRICATION
information when wiring the detection system. For
To ease installation and future removal, ensure that all junction box
information on devices not covered in an appendix, refer
covers and sensor threads are properly lubricated. If the need arises
to the manual provided by the device’s manufacturer.
for additional lubrication, use either Lubriplate grease (see Ordering
Information for part number) or Teflon tape. Avoid the use of silicone
Figure 4 shows jumper plug P12 positioned to power the 4-20 mA
grease.
loop from the main power source (non‑isolated output).
•
Figure 5 shows jumper plug P12 positioned for powering the 4-20
mA loop from an external wire/jumper of from a separate power
source (isolated output).
J3-2
J3-3
J3-4
J3-5
J3-1
J3-2
J3-3
J3-4
J3-5
J3 J3
CALIBRATE
CALIBRATE
24 VDC –
24 VDC –
SHIELD
24 VDC +
SHIELD
24 VDC +
4-20 mA
4-20 mA
P1-3 4-20 mA + HIGH ALARM NC J4-2 P1-3 4-20 mA + HIGH ALARM NC J4-2
Relay Connector
Modbus J2-3 LOW ALARM NC J4-8 Modbus J2-3 LOW ALARM NC J4-8
Connector LOW ALARM NO J4-9 Connector LOW ALARM NO J4-9
J2-2 + FAULT COM J4-10 WHEN P12 IS IN J2-2 + FAULT COM J4-10
P9
24 VDC –
P7
SHIELD
P1-3 IS INTERNALLY P9 P7
SHIELD
24 VDC –
24 VDC –
24 VDC +
24 VDC +
24 VDC +
24 VDC +
TO POWER THE
SHIELD
SHIELD
P2-5
P2-4
P2-3
P2-2
P2-1
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2 P2
P12 P12
Figure 4—Position of Jumper P12 for Figure 5—Position of Jumper P12 for
Non-Isolated 4-20 mA Loop Output Isolated 4-20 mA Loop Output
7.4 9 95-8661
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
SHIELD
SHIELD
MODBUS J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
C2399
UD10
DISPLAY UNIT
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
24 VDC +
24 VDC +
SHIELD
J4
OHMS + Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
P12
Power Supply Connector
Figure 7—UD10 Wired to PLC using 3-Wire Shielded Cable with 4-20 mA Non-Isolated Sourcing Output
7.4 10 95-8661
UD10
DISPLAY UNIT
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
24 VDC –
24 VDC –
24 VDC +
24 VDC +
250-600 24 VDC MODBUS
SHIELD
SHIELD
J4
OHMS + Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
P12
Power Supply Connector
Figure 8—UD10 Wired to PLC using 4-Wire Shielded Cable with 4-20 mA Non-Isolated Sourcing Output
UD10
DISPLAY UNIT
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
24 VDC +
24 VDC +
SHIELD
J4
OHMS + Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
P12
IMPORTANT
Isolated operation is highly recommended to prevent noise or ripple on the main power source from interfering with the HART
function.
7.4 11 95-8661
STARTUP RTC
NOTE
After power has been applied and the warm-up period is complete, The UD10 is set at the factory for US Central Standard
select the UD10 operating mode. To do this: time.
1. Access the Main Menu by touching the magnet to the ENTER/ To display and set the Real Time Clock and Date for the UD10:
SELECT button. From there, navigate to the “Mode Select”
menu. 1. Using the magnet to activate the switches on the UD10 display,
navigate to the RTC menu.
Display Setup
Alarm Setting
Display Setup
Mode Select
Main Menu Alarm Setting
HART Option Mode Select Mode Select
Process Vars
RTC HART Device Main Menu
Display Status HART Option
RS485 PIR9400 Process Vars RTC
Device Status RTC
Input Loop Cal PIRDUCT Display Status Displayed
Display Setup RS485
Contrast Contrl C706X Device Status Seconds
Device Setup Input Loop Cal
Output Mode 505 Display Setup Minutes
Device Cal Contrast Contrl
Backlight Ctrl NTMOS Device Setup Hours
Display Test Output Mode
Heater Ctrl CGS Device Cal Day
Device Test Backlight Ctrl
Write Protect Generic Device Display Test Month
Language Heater Ctrl
OP Feedback Flt Device Test Year
Write Protect
Scrolling Display Language
OP Feedback Flt
Set Scrolling Rate
Scrolling Display
Set Scrolling Rate
2. From the “Mode Select” menu, select and enter the appropriate
operating mode based on the type of detector being used. 2. The first item on the RTC screen is “Displayed”. Y (Yes) or N
(NO) is shown to indicate whether the time and date will be
NOTE displayed on the main screen. To change the setting, use the
If using a PIR9400, note that changing the gas type ENTER/SELECT button to go to the next screen, then use
on the UD10 does not change the gas type at the the PREVIOUS or NEXT buttons to toggle between Y and N.
PIR9400. This change is made using a switch located Once the chosen input is selected, use the ENTER/SELECT
in the PIR9400. Refer to the PIR9400 instruction manual button to enter the selection. Use the CANCEL/ESCAPE
95‑8440 for details. button to exit without changing.
7.4 12 95-8661
4-20 mA LOOP CALIBRATION UD10 Input Trim
Both the input and output current loops of the UD10 are trimmed When the UD10 is used with a detector that supports HART
at the factory. They can also be trimmed in the field for maximum communication, an automated process can be used to trim the
accuracy using the following procedures. If the detector connected UD10 input. Navigate down the menu to “Input Loop Cal”.
to the UD10 is HART enabled, its 4-20 mA output signal can also
be trimmed. Display Setup
Alarm Setting
When the UD10 is used with a detector that supports HART Main Menu
Mode Select
HART Option
communication, the output of the detector should be calibrated first. Process Vars
RTC
Display Status
RS485
Device Status
Input Loop Cal
Display Setup
HART Detector Signal Calibration Device Setup
Contrast Contrl
Output Mode
Device Cal
Navigate down the menu to Device Test > D/A (Digital to Analog) Display Test
Backlight Ctrl
7.4 13 95-8661
UD10 Output Trim Self-Test
To calibrate the UD10 output loop, navigate down the menu to This test commands the UD10 to perform a fully automatic internal
Display Test > D/A Trim. test. At the completion of the test, the UD10 will indicate a pass or
fail.
Main Menu
Process Vars
Display Status Response Test
Display Test
Device Status
Display Setup
Self Test D/A Trim This test inhibits the UD10’s outputs, thereby providing a means of
Response Test
testing the system by applying gas to the detector without activating
Zero Trim
Device Setup
Loop Test Gain Trim
Device Cal
Display Test
D/A Trim any alarms or affecting the output.
Device Test
Language NOTE
If the Response Test is not terminated by the operator,
the test will automatically time out after 10 minutes and
Select Zero Trim. When this screen is entered, a warning message the UD10 will return to normal operation.
is presented. Select ENTER to continue. When the message
“Connect Reference Meter” is presented, install the current meter
on the UD10 mA output. Select ENTER to continue. When the Loop Test
message “Set Output Current to 4mA?” is presented, select ENTER This test temporarily forces the UD10’s 4-20 mA output to a specific
to begin the Zero Trim function. The UD10 will now set its 4 mA level. This is an easy way to test the output signal of the UD10 for
output value. If the measured value on the current meter is not 4.00 accuracy, to verify the capabilities of the system, and to verify the
mA, enter the measured value into the UD10 using the Previous and input signal of a receiver. To perform this test, connect a current
Next switches. The UD10 calculates and corrects for the difference meter to the output loop. Navigate to Display Test and select Loop
between the actual and entered values. When the current meter Test, then follow the prompts on the UD10 Screen.
value is at the desired 4.00 mA, select ENTER to accept the new
Zero Trim value. NOTE
If the Loop Test is not terminated by the operator, the
Select Gain Trim. Follow the same procedure for gain/span test will automatically time out after one minute and the
calibration. UD10 will return to normal operation.
7.4 14 95-8661
PASSWORD PROTECTION DISPLAY BACKLIGHT OPERATION
The UD10 allows the use of a password for restricting changes The UD10 can be programmed to turn on the backlight feature
to configuration parameters and limiting access to safety critical of the digital display when an alarm or fault occurs or a magnetic
commands. The UD10 is shipped from the factory with the password switch is activated. Navigate to the Backlight Ctrl screen.
protection (Write Protect) feature disabled.
Display Setup
The following are locked when Write Protect security is enabled: Alarm Setting
Mode Select
Main Menu
Alarm Setting screen – All options except “RST Latch Alarms” Process Vars
HART Option
RTC
Display Status
Mode Select screen – All options Device Status
RS485 Backlight Ctrl
Input Loop Cal Off
HART Option – All options Display Setup
Contrast Contrl On
Device Setup
Output Mode
RTC – All options except Displayed Y/N Device Cal
Backlight Ctrl
Automatic
Display Test
Heater Ctrl
Output Mode Device Test
Write Protect
Language
Display Test screen – All options OP Feedback Flt
Scrolling Display
Set Scrolling Rate
To enable the Write Protect feature, navigate to the Write Protect
screen.
Off = The backlight is always off.
Display Setup
Alarm Setting On = The backlight is always on.
Mode Select
Main Menu
Process Vars
HART Option
Automatic = Normal operation – Backlight is off
RTC
Display Status
Device Status
RS485
Write Protect
Alarm – Backlight flashes on and off
Display Setup
Input Loop Cal
Contrast Contrl
Change State Fault – Backlight is on steady
Device Setup Change Password
Device Cal
Output Mode
Write Protect xxx Magnetic Switch – Backlight is on steady
Backlight Ctrl
Display Test
Heater Ctrl
Device Test
Write Protect The backlight automatically turns off 10 minutes after the last
Language
OP Feedback Flt Magnetic Switch activation.
Scrolling Display
Set Scrolling Rate
If the backlight is on following a magnetic switch activation and then
an alarm condition occurs, the backlight will remain on steady and
Select “Change State” to toggle between Enabled and Disabled. not flash until the 10 minute time-out is complete. Then it will begin
flashing.
Select “Change Password” to enter a new password.
IMPORTANT
Take care not to lose the password. Future changes
cannot be made without a password.
7.4 15 95-8661
TROUBLESHOOTING Example:
If a Fault condition is indicated on the UD10 faceplate, the nature of For a Display (UD10) related fault:
the fault can be determined by using the magnetic tool to navigate Main Menu > Display Status > Fault/Status > Fault
to the appropriate Fault screen.
For a Device (Sensor) related fault:
NOTE
Main Menu > Device Status > Fault/Status > Sensor Fault
Refer to the Menu in the appropriate appendix of this
manual for the path to the proper Fault screen.
When the active fault has been identified, refer to the Troubleshooting
Tables for a description of the fault and suggested corrective action.
Shortcut: From the main display screen, touch the
magnet to the “Previous” switch to go directly to the
Fault screen. Refer to Table 4 for Display Faults and Table 5 for Device Faults.
Note: A fault condition will cause an oxygen detector to generate an alarm output as the decreasing 4-20 mA signal passes through the alarm range.
7.4 16 95-8661
Table 5—Troubleshooting Guide - Device Faults
*OPECL only.
7.4 17 95-8661
Table 5—Troubleshooting Guide - Device Faults, Continued
7.4 18 95-8661
SPECIFICATIONS RELAY CONTACTS—
Three Alarm Relays: Form C, 5 amperes at 30 Vdc.
OPERATING VOLTAGE— Selectable energized/de-energized.
24 Vdc nominal, operating range is 18 to 30 Vdc. Selectable latching or non‑latching.
Ripple cannot exceed 0.5 volt P-P. Refer to Table 1 for range and
default settings.
OPERATING POWER—
Standard model, with heater and backlight off: WARNING
No alarm: 1.5 watts @ 24 Vdc. When in non-latching mode, the control device must
Alarm: 3 watts @ 24 Vdc (20 mA current loop latch the alarm output.
output and all 3 alarm relays energized.)
Backlight on: 0.5 watt additional. One Fault Relay: Form C, 5 amperes at 30 Vdc.
Heater on: 3.5 watts additional. Normally energized for no fault
CGS model: Add 4 watts with CGS interface board and condition with power applied.
CGS sensor installed.
Maximum power in alarm, with heater and backlight on: RELAY RESPONSE TIME—
7 watts @ 30 Vdc (Standard model) ≤ 2 seconds.
11 watts @ 30 Vdc (CGS model)
WIRING TERMINALS—
NOTE 14–18 AWG, 2.5–0.75 mm2 wire can be used.
Heater turns on when the internal temperature drops
below –10°C (default operation). Heater function can be OPERATING TEMPERATURE—
disabled to save power. –55°C to +75°C
S Y S T E M O U T P U T A C C U R A C Y: U D10 W I T H
CGS—
The UD10 with CGS sensor directly attached has an overall system
accuracy of ±3% for 0-50 LFL range and ±5% for 51-100 LFL
range, including error added by UD10.
7.4 19 95-8661
6.48 4.7
(16.5) (11.9)
3.46
(8.8)
5.2
(13.2)
5.86
(14.9)
11.28
(28.7)
R0.175
A2442
7.4 20 95-8661
5.86 CERTIFICATION—
(14.9)
For complete approval details, refer to the appropriate appendix:
5.2
(13.2)
2.7
(6.9) ®
4.7
(11.9)
Appendix A – FM
3.46
(8.8)
Appendix B – CSA
Appendix C – ATEX
Appendix D – IECEx
Appendix E – INMETRO
3.77
(9.6)
1.28
(3.3)
C2281
Catalytic IR Ultrasonic
Device Toxic1 Instruction Manual
Combustible Combustible2 Acoustic
GT3000 X 95-8616
PIR9400 X 95-8440
PIRDUCT X 95-8573
PIRECL X 95-8526
PIRECL-CO2* X 95-8676
OPECL X 95-8556
CGS X 90-1041
505/CGS X 95-8472
C706X3 X 95-8396, 95-8411, 95-8414, 95-8439
NTMOS** X 95-8604
AC100/ATX10 X 95-8657
LS2000 X 95-8714
1 Hydrogen sulfide, Ammonia, Chlorine, Hydrogen, Oxygen,
Carbon Monoxide, and Sulfur Dioxide.
2 Hydrocarbons, see device manual for details.
3 C7065E Oxygen detector is not supported.
* Carbon dioxide only.
** Hydrogen sulfide only.
7.4 21 95-8661
DEVICE REPAIR AND RETURN ORDERING INFORMATION
Prior to returning devices, contact the nearest local Detector Sensor module, transmitter module and termination boxes (if used)
Electronics office so that a Return Material Authorization (RMA) must be ordered separately.
number can be assigned. A written statement describing
the malfunction must accompany the returned device or Refer to the UD10 Model Matrix for ordering details.
component to assist and expedite finding the root cause of
the failure.
ACCESSORIES
Pack the unit properly. Always use sufficient packing material.
Where applicable, use an antistatic bag as protection from Part Number Description
electrostatic discharge. The RMA number should be clearly marked 009700-001 Magnetic Tool
on the outside of the box. 103922-003 AMS Trex Device Communicator
010268-001 Gas Inspector CD
NOTE 010204-001 W6300G1003 Gas Inspector Connector
Inadequate packaging that ultimately causes damage 005003-001 Lubriplate grease, 1 oz.
to the returned device during shipment will result in a 101197-001* Stop Plug, 3/4” NPT, AL
service charge to repair the damage incurred during 101197-004* Stop Plug, 3/4” NPT, SS
shipment. 101197-005 Stop Plug, M25, AL, IP66
101197-003 Stop Plug, M25, SS, IP66
Return all equipment transportation prepaid to the factory in 102804-001 Reducer, M25 to M20, AL
Minneapolis. 102804-003 Reducer, M25 to M20, SS
7.4 22 95-8661
UD10 MODEL MATRIX
MODEL DESCRIPTION
UD10 Universal Display Unit
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
5E 5 Port, 1/2” NPT
5F 5 Port, Metric M20
5M 5 Port, Metric M25
5N 5 Port, 3/4” NPT
TYPE OUTPUTS
25 Relay, 4-20 mA, RS485, HART
28 EQP / DCU Emulator
TYPE APPROVALS*
B INMETRO (Brazil)
R Russia
S SIL
T SIL/FM/CSA/ATEX/CE/IECEx
W FM/CSA/ATEX/CE/IECEx
TYPE CLASSIFICATION (Div/Zone)
2 Ex d (Flameproof)
TYPE OPTIONAL CONDITIONING BOARD
(Blank) None
C CGS
N NTMOS**
7.4 23 95-8661
APPENDIX A
FM APPROVAL DESCRIPTION
This approval does not include or imply approval of gas detector heads or other apparatus to which the subject instrument may be connected.
In order to maintain a Factory Mutual Research approved system, the measurement input signal to which this instrument is connected must
also be approved by Factory Mutual Research.
UD10 hazardous location and performance testing was successfully completed down to –55°C. However, the FM approved rating is limited
to –50°C as there are no conduit fittings, cables, or cable glands that are presently listed for use below –50°C in the US. FM approvals policy
does not allow product temperature ratings to exceed required installation components (such as conduit seals). The user must ensure that
conduit fittings, cables, cable glands, etc., are rated for the expected minimum ambient temperature of the installation.
NOTE
Consideration must be given to overall Gas System Performance Requirements.
WARNING
When a sensor/detector is connected directly to the UD10 housing, the lower ratings
of the two devices will prevail.
7.4 F-24
A-1 95-8661
APPENDIX B
CSA 2029512.
Class I, Div. 1, Groups B, C & D (T5);
Class I, Div. 2, Groups B, C & D (T4);
Class II/III, Div. 1/2, Groups E, F & G.
(Tamb = –55°C to +75°C)
Type 4X
Conduit seal not required.
NOTE
Consideration must be given to overall Gas System Performance Requirements.
WARNING
When a sensor/detector is connected directly to the UD10 housing, the lower
ratings of the two devices will prevail.
7.4 F-25
B-1 95-8661
APPENDIX C
0539 II 2 D
FM
APPROVED
®
UL21ATEX2385X
Ex db IIC T6 Gb EN 60079-29-1
Ex tb IIIC T90°C Db EN 60079-29-1
(without integral CGS)
Ta = -55°C to +75°C
IP66
Ex db IIC T5 Gb EN 60079-29-1
Ta = -40°C to +75°C
(with integral CGS)
IP53
Compliance with:
• EN IEC 60079-0:2018
• EN 60079-1:2014
• EN 60079-31:2014
NOTE
Consideration must be given to overall Gas System Performance Requirements.
WARNING
When a sensor/detector is connected directly to the UD10 housing, the lower ratings
of the two devices will prevail.
7.4 F-26
C-1 95-8661
CATALYTIC COMBUSTIBLE GAS SENSOR (CGS)
0539 II 2 G
FM
APPROVED
®
7.4 C-2
F-27 95-8661
APPENDIX D
Compliance with:
• IEC 60079-0:2017
• IEC 60079-1:2014-06
NOTE
Consideration must be given to overall Gas System Performance Requirements.
WARNING
When a sensor/detector is connected directly to the UD10 housing, the lower ratings
of the two devices will prevail.
7.4 F-28
D-1 95-8661
CATALYTIC COMBUSTIBLE GAS SENSOR (CGS)
IECEx UL 21.0018X
Ex db IIC T3, T5 Gb
T5 = -40°C to +75°C
T3 = -55°C to +125°C
ADDITIONAL APPROVALS
INMETRO (Brazil)
UL-BR 24.0681X
Ex db IIC T5 Gb
T5 (Tamb –40°C to +75°C) With integral CGS
– OR –
Change to:
Ex db IIC T6 Gb
Ex tb IIIC T90°C Db
T6 (Tamb –55°C to +75°C) Without integral CGS
All cable entry devices shall be Brazil certified in the type of explosion protection, flameproof enclosure “d,” suitable for the conditions of use
and correctly installed, with an ingress protection rating of IP66.
A screw or cover lock is provided for a secondary means of fastening the cover.
Compliance with:
ABNT NBR IEC 60079-0:2020
ABNT NBR IEC 60079-1:2016
ABNT NBR IEC 60079-31:2014
ABNT NBR IEC 60079-29-1:2008
IEC 60079-29-4:2009 (Not listed for INMETRO)
7.4 F-D-3
E-1 95-8661
APPENDIX F
NOTE
Refer to the front of this manual for complete information regarding installation, wiring, and startup of the UD10.
WIRING
UD10
DISPLAY UNIT
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
24 VDC –
24 VDC –
24 VDC +
24 VDC +
250-600 24 VDC MODBUS
SHIELD
SHIELD
J4
OHMS + Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
P12
IMPORTANT
To ensure proper operation of the HART communication system, a power supply with low noise and ripple must be used. If
noise or ripple on the main power source could interfere with the HART function, an isolated power source is recommended.
For additional information, refer to “Power Supply Requirements” in the “Wiring” section of this manual.
MENU STRUCTURE
Refer to the following menu tree when using a HART handheld communicator, connected to the UD10’s 4-20 mA output.
MENU HELP
Status menus only allow the user to view the data.
The Setup menus allow the user to both view and edit the data.
NOTE
For complete information regarding the GT3000 Gas Detector, refer to instruction manual 95-8616.
WIRING
UD10 with GT3000
4000
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to sensor/STB termination box is 2000 feet.
BLACK
RED
UD10
DISPLAY UNIT
GREEN
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
BLACK
RED
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector GREEN
HIGH ALARM COM J4-1
D
P1-3 4-20 mA +
RE
HIGH ALARM NC J4-2
K
AC
HIGH ALARM NO J4-3
BL
P1-2 4-20 mA –
AUX ALARM COM J4-4
Relay Connector
P1-1 SHIELD
RED
AUX ALARM NC J4-5
BLACK
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
GT3000
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector GAS DETECTOR
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
NOTE
Removing the sensor module with power applied will
result in a fault condition until a new sensor module of
the same type is installed. When replacing an oxygen
sensor, this action will also result in an alarm condition
as the decreasing 4-20 mA signal passes through
the alarm range. Inhibit response devices to prevent
unwanted actuation.
LED
MAGNETIC
SWITCH 2. Activate “Execute” (Enter/Select) to start calibration.
3. The UD10 will display “Waiting for Zero” on the main display
screen, with the yellow LED on the detector housing illuminated
continuously. The device automatically performs the zero
calibration.
4. The UD10 will then display “Waiting for Gas” on the screen,
while the yellow LED on the detector is flashing.
A2443
6. The UD10 will display “Waiting for Span” on the screen, while UD10 mA Output During Calibration
the yellow LED on the detector is flashing. (UD10 with GT3000)
Replicate
7. When the UD10 displays “Remove Cal Gas” on the screen and UD10 Display Reading Standard Mode
Mode
all LEDs on the detector housing are off, remove the calibration
gas. Waiting for Zero 3.8 3.8
4. After successful calibration, the green LED on the GT3000 is on 3. The UD10 will display “Waiting for Zero” on the main display
continuously and the UD10 automatically returns to the normal screen, with the yellow LED on the detector housing illuminated
display. continuously. The device automatically performs the zero
Remove calibration gas (if used). calibration.
MENU STRUCTURE
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the PIR9400 Gas Detector, refer to instruction manual 95-8440.
WIRING
UD10 with PIR9400/PIRDUCT
4000
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to PIR9400/PIRTB termination box is 2000 feet.
PIR9400
J3-1
J3-2
J3-3
J3-4
J3-5
J3
POINTWATCH
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector YELLOW
HIGH ALARM COM J4-1
4-20 mA +
BLACK
P1-3 HIGH ALARM NC J4-2
WHITE
P1-2 4-20 mA – HIGH ALARM NO J4-3
P1-1 SHIELD
AUX ALARM NC J4-5 GREEN
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
J3-1
J3-2
J3-3
J3-4
J3-5
J3
SPARE CHASSIS
CALIBRATE
CAL
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop CAL
Connector YELLOW
HIGH ALARM COM J4-1 4 – 20 4 – 20 WHITE
4-20 mA +
P1-3 HIGH ALARM NC J4-2 RET RET BLACK
HIGH ALARM NO J4-3 RED
P1-2 4-20 mA –
+24 +24
AUX ALARM COM J4-4
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
IMPORTANT
In applications where both PointWatch and catalytic
type sensors are used, ensure that the grease used
to lubricate the PointWatch detector threads does not
come into contact with the catalytic sensors, since
poisoning of the catalytic sensors could result. It is
strongly recommended that maintenance personnel
wash their hands between handling the two types of
sensors.
To initiate calibration of the PIR9400 from the UD10 Display: Waiting for Span 3.8 3.8
Main Menu
Process Vars
Display Status 3. The UD10 will then display “Waiting for Gas” on the screen,
Device Status Device Cal Calibration
Display Setup Calibration Execute
while the LED at the PIRTB is flashing red.
Device Setup Cal Gas Conc Abort
Device Cal 4. Apply calibration gas to the PIR9400 detector.
Display Test
Language
5. The UD10 will display “Waiting for Span” on the screen, with a
red flashing LED at the PIRTB.
2. Activate “Execute” (Enter/Select) to start calibration.
6. When the UD10 displays “Remove Cal Gas” on the screen and
3. The UD10 will display “Waiting for Zero” on the main display the LED at the PIRTB turns off, remove the calibration gas.
screen.
7. After successful calibration, the UD10 automatically returns to
4. The UD10 will then display “Waiting for Gas” on the screen. the normal mode, and the LED on the PIRTB remains off.
remove the calibration gas from the PIR9400. TO ACTIVATE CALIBRATION SWITCH
2. The UD10 will display “Waiting for Zero” on the main display
screen, with a steady red LED at the PIRTB.
B2056
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the PIRECL Gas Detector, refer to instruction manual 95-8526.
WIRING
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to detector/STB termination box is 2000 feet.
24 VDC + 2 RED
CALIBRATE 3
24 VDC – 4
24 VDC + 5 1
4-20 MA + 6
4-20 MA – WHITE
7
RS-485 B 8
RS-485 A 9
UD10 DISPLAY UNIT
RELAY POWER (RED) 10
WIRING TO OPTIONAL FAULT (ORANGE) 11
RELAY BOARD Sensor Connector
NO USER CONNECTION LOW ALARM (WHITE) 12
J3-1
J3-2
J3-3
J3-4
J3-5
J3
HIGH ALARM (YELLOW) 13
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
NOTE 1 INTERNAL JUMPER REQUIRED FOR Connector
NON-ISOLATED CURRENT OUTPUT
(SINGLE POWER SUPPLY).
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
C2404
ORIENTATION
It is highly recommended that the PIRECL be installed in the
horizontal position. The detector is not position-sensitive in terms
of its ability to detect gas. However, the weather baffle assembly
provides superior performance when the PIRECL is installed with
the baffle in a horizontal position.
CORRECT INCORRECT
Main Menu 2. The UD10 will display “Waiting for Zero” on the main display
Process Vars screen, with a solid red LED on the PIRECL housing illuminated.
Display Status
Device Cal
Device Status
Calibration
Display Setup
Cal Gas Con
Execute
3. The UD10 will then display “Waiting for Gas” on the screen,
Cal Gas Type
Device Setup
Calibration Abort while the LED on the PIRECL is flashing red.
Device Cal
Date
Display Test
Device Test 4. Apply calibration gas to the PIRECL detector.
Language
5. The UD10 will display “Waiting for Span” on the screen, while a
red flashing LED on the PIRECL housing is illuminated.
2. Activate “Execute” (Enter/Select) to start calibration.
6. When the UD10 displays “Remove Cal Gas” on the screen and
3. The UD10 will display “Waiting for Zero” on the main display the LED on the PIRECL housing is off, remove the calibration
screen, with a solid red LED on the PIRECL housing illuminated. gas.
4. The UD10 will then display “Waiting for Gas” on the screen, 7. After successful calibration, the UD10 automatically returns to
while the LED on the PIRECL is flashing red. the normal mode with the green LED illuminated on the PIRECL.
6. The UD10 will display “Waiting for Span” on the screen, while a
red flashing LED on the PIRECL housing is illuminated.
7. When the UD10 displays “Remove Cal Gas” on the screen and MULTICOLOR LED
CALIBRATION MAGNET
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the OPECL Gas Detector, refer to instruction manual 95-8556.
WIRING
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to detector/STB termination box is 2000 feet.
J3-1
J3-2
J3-3
J3-4
J3-5
J3
11
NO USER CONNECTION
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
12
Connector
HIGH ALARM COM J4-1
13 P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-5
P2-4
P2-3
P2-2
P2-1
P2
NON-ISOLATED CURRENT OUTPUT
(SINGLE POWER SUPPLY).
Power Supply Connector
NOTE 2 UD10 HOUSING MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND. C2405
3. The UD10 will display “Waiting for Zero” on the main display
screen, with a solid red LED on the OPECL housing illuminated.
A2306
The Fault status will indicate Y (Yes). Click on “Fault” and the Fault
menu will identify the fault as a “Lamp Fault.”
Main Menu
PLACE CALIBRATION MAGNET Process Vars
HERE TO ACTIVATE INTERNAL
REED SWITCH Display Status Device Status
Fault/Status
Device Status General Info
Op Mode
Display Setup Fault/Status
Cal State
Device Setup Device Info
Fault Y
Device Cal Sensor Info
Status
Display Test History
Device Test
Language
A2349
MENU STRUCTURE
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the NTMOS Gas Detector, refer to instruction manual 95-8604.
WIRING
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to detector/STB termination box is 2000 feet.
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
J2
LOW ALARM COM J4-7 NTMOS
LOW ALARM NC J4-8 DETECTOR
J2-3 COM
LOW ALARM NO J4-9
J2-2 RS485 A FAULT COM J4-10
FAULT NC J4-11
J2-1 RS.485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-5
P2-4
P2-3
P2-2
P2-1
P2
NOTE 2 UD10 HOUSING MUST BE ELECTRICALLY
Power Supply Connector CONNECTED TO EARTH GROUND.
F2434
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
YELLOW
BLACK
GREY
FAULT NC J4-11
J2-1 RS.485 B
FAULT NO J4-12
NTMOS
H2S DETECTOR
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
NOTE 1 GREY AND ORANGE WIRES FOR FACTORY USE ONLY.
Power Supply Connector
NOTE 2 HOUSINGS MUST BE ELECTRICALLY CONNECTED TO
EARTH GROUND.
C2482
UD10 Wired to NTMOS Detector with STB Termination Box (Non-HART Applications Only)
J2
CAL
RTN
SHIELD
24V
4/20
ORANGE
WHITE
RED
YELLOW
GREY
BLACK
NTMOS
H2S DETECTOR
COM 2 (ORANGE)
CAL (YELLOW)
COM 1 (GRAY)
RTN (BLACK)
4/20 (WHITE)
24V (RED)
P1
NTMOS CONNECTOR BOARD
NTMOS Detector Wired Directly to UD10 via the NTMOS Connector Board
(NTMOS Connector Board is Required for HART Communication)
UD10
DISPLAY UNIT CONNECT TO UD10 MODULE’S J3 WITH
FACTORY INSTALLED CABLE
J2
CAL
RTN
SHIELD
24V
4/20
COM 2 (ORANGE)
CAL (YELLOW)
COM 1 (GRAY)
RTN (BLACK)
4/20 (WHITE)
24V (RED)
ORANGE
WHITE
RED
YELLOW
BLACK
GREY
P1
NTMOS
NTMOS CONNECTOR BOARD H2S DETECTOR
B2494
UD10 with NTMOS Connector Board Wired to NTMOS Detector with STB Termination Box
(NTMOS Connector Board is Required for HART Communication)
NOTE
When calibrating with bottled 50 ppm H2S in air, the
humidification tube MUST be used.
CALIBRATION
Calibration Notes
The NTMOS detector must be calibrated using 50 ppm H2S in air
(never use H2S in nitrogen).
WARNING
The use of any other H2S calibration mixture will produce NTMOS H2S DETECTOR
6. With 50 ppm H2S applied to the detector, the UD10 display will
continue to show “Waiting for Span” while the span calibration is
being performed.
8. When the gas level falls below the lowest alarm setpoint, the
UD10 automatically exits the Calibrate mode and returns to
normal operating mode.
MENU STRUCTURE
Main Menu
Process Vars
Display Status
Device Status Device Cal Calibration
Display Setup Calibration Execute
Device Setup Cal Gas Conc
Device Cal
Display Test UD10 mA Output During Calibration
Language
(UD10 with NTMOS)
Replicate
UD10 Display Reading Standard Mode
2. Activate “Execute” (Enter/Select) to begin the zero calibration. Mode
NOTE
For complete information regarding the C7064E H2S Gas Sensor, refer to instruction manual 95-8396.
For the C7067E Chlorine Gas Sensor, refer to instruction manual 95-8439.
WIRING
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to sensor/STB termination box is 2000 feet.
RED
GREEN
UD10 Sensor Connector
DISPLAY UNIT
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop SEE NOTE 1
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
C706X SENSOR
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-5
P2-4
P2-3
P2-2
P2-1
P2
TO THE CHASSIS GROUND LUG ON THE
INSIDE BOTTOM OF THE DISPLAY ENCLOSURE.
Power Supply Connector
NOTE 2 UD10 HOUSING MUST BE ELECTRICALLY
C2422 CONNECTED TO EARTH GROUND.
BLACK
SEE NOTE 1
RED
J3-2
J3-3
J3-4
J3-5
J3 BOX
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1 +
P1-3 4-20 mA + –
HIGH ALARM NC J4-2 G
D
HIGH ALARM NO J4-3 RE
P1-2 4-20 mA – + BLK
AUX ALARM COM J4-4 –
Relay Connector
P1-1 SHIELD G
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
C706X SENSOR
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
4. Double check that all wiring is the proper size and type and has
been installed correctly. Check operating voltage at the C706X
sensor and the UD10 Display Unit.
NOTE
Do not apply power to the system with the junction box
cover removed unless the area has been de-classified.
2. Activate “Execute” (Enter/Select) to start calibration. When connecting a HART Communicator to the UD10’s 4-20 mA
Main Menu
output, refer to the “UD10 HART Handheld” menu in Appendix F.
Process Vars
Display Status MENU HELP
Device Status
Display Setup
Device Cal Calibration Status menus only allow the user to view the data. The
Calibration
Device Setup Cal Gas Conc
Execute
Setup menus allow the user to both view and edit the
Device Cal data.
Display Test
Language
3. The UD10 will display “Waiting for Zero” on the main display
screen as it performs zero calibration.
6. The UD10 will display “Waiting for Span” on the screen while
the span calibration is being performed.
WIRING
1750
1500
AWG
Distance in ft.
1000 12
14
750 16
500
18
250
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to CGS sensor is 500 feet
(using 16 AWG, 1.5 mm2 cable minimum).
NOTE
CAUTION
When the auxiliary relay is set for latching and the gas
When used as a stand alone device, the high alarm must
level goes above the auxiliary alarm threshold, the 4-20
always be programmed for latching operation. When
mA output will latch to the highest gas level detected
used in conjunction with a Control Unit and configured
until it is reset. When CGS mode is selected, the default
for a non-latching high alarm, the control unit must
setting for the auxiliary relay is a threshold of 90% full
always latch and require a deliberate manual action to
scale, with latching output.
clear a high gas alarm.
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
J11
2
BL
CGS INTERFACE BOARD
1
W
HT
J10
RE
D
P10
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
W
HT
RE
D
1
J10
P10
BLK
WHT
RED
CGS
B2508 SENSOR
NOTE
Do not apply power to the system with the junction box UD10 mA Output During Calibration
cover removed unless the area has been de‑classified. (UD10 with CGS)
Replicate
5. Proceed with startup and calibration. UD10 Display Reading Standard Mode
Mode
To view the mV signal from the most recent calibration only, from Main Menu
the Main Menu, navigate to: Process Vars
Device Status > Device Info > Response. Display Status
Device Status Device Option
Device Setup
A typical new sensor reads between 45 and 55 mV. Display Setup
Device Setup
Device Option
Gas Name
K-Factor
Device Cal
• At 21-55 mV, “Cal OK” is recorded in the Cal Log, along with the Display Test
Span value. Language
• At 15-20 mV, “Cal OK” is recorded in the Cal Log, along with the
Span value. In addition, “Weak Sensor” is shown on the UD10
display for about 20 seconds. After 20 seconds, the “Weak The UD10 communicates the K-Factor to the CGS Interface Board
Sensor” message is no longer seen, but a “Weak Sensor” status during the calibration process, where the proper correction is made
is recorded (Device Status > Fault/Status > Status). to ensure accurate calibration.
• At 14 mV or less, “Weak Sensor” is shown on the UD10 display The actual effect of the K-Factor can be observed as the span
for about 20 seconds, then a Cal Fault is shown. The Cal Log portion of the calibration is completed. For example, suppose a
shows “Cal Fail” with a Span value of 0.00 mV. K-Factor of 0.865 has been programmed. When calibration is
performed, the UD10 will display 50% as span is accepted. It will
then apply the K-Factor, and the displayed value will change to
43.3% LFL.
MENU STRUCTURE
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the Model 505 Transmitter, refer to instruction manual 95-8472.
WIRING
UD10 with PIRECL/OPECL/Model 505
4000
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to sensor/STB termination box is 2000 feet.
Sensor Connector
UD10
DISPLAY UNIT
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2 MODEL 505 TRANSMITTER
P1-2 4-20 mA – HIGH ALARM NO J4-3
SHIELD SIG
P1-1 –
AUX ALARM NC J4-5 +
P1
AUX ALARM NO J4-6
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2 MODEL 505 TRANSMITTER
P1-2 4-20 mA – HIGH ALARM NO J4-3
Relay Connector
SHIELD SIG
P1-1 –
AUX ALARM NC J4-5 +
P1
AUX ALARM NO J4-6
24 VDC –
24 VDC –
24 VDC +
MODBUS 24 VDC +
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
UD10 Wired to Model 505 Transmitter/CGS Sensor Using Sensor Separation Termination Box
INSTALLATION ORIENTATION
Refer to the Model 505 instruction manual number 95-8472 for The Model 505/CGS must be mounted with the CGS sensor
complete information regarding proper installation of the Model 505 opening pointing down.
with combustible gas sensor.
Model 505
The Model 505/CGS must be calibrated when the system is
commissioned as well as when the CGS sensor is replaced.
Calibration is performed at the Model 505 using the following
procedure. Calibration at the UD10 is not supported.
WARNING
Before removing the junction box cover, verify that no dangerous levels of gas are present.
ZERO/SPAN switch in the ZERO 1. Adjust the ZERO potentiometer to read 0.000 Vdc on the
2
position. voltmeter. See Note 3 below.
1. Sensitivity test. The meter must read greater than 0.015 Vdc.
ZERO/SPAN switch in the ZERO See Note 4 below.
4
position. 2. Remove the calibration gas.
3. When the meter reads 0.002 Vdc or less, remove the test probes.
NOTES:
1. When the CAL/NORM switch is in the CAL position, the yellow LED turns on and the 4-20 mA output signal goes to 3.4 mA.
3. If the possibility of background gases exists, purge the sensor with clean air prior to the zero adjustment to assure accurate
calibration.
4. A typical sensitivity reading with 50% LFL gas applied to the sensor is 35 to 50 millivolts for a new sensor. Sensor replacement
is recommended when the sensitivity reading is less than 15 millivolts.
5. If a dust cover or splash shield is used, inspect it to be sure that it is not dirty or plugged. A plugged dust cover can restrict
the flow of gas to the sensing element, seriously reducing its effectiveness. For optimum performance, sensor covers/filters
should be replaced frequently to ensure that they are not degraded or plugged.
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding installation, wiring, and calibration of the sensor, refer to the instruction manual
provided by the sensor manufacturer.
OPERATION ALARMS
The UD10 can be used with generic sensors that generate a The Low, High, and Auxiliary alarm levels are independently field
calibrated linear 4-20 mA signal, with or without HART. The UD10 adjustable. Alarm levels are set and displayed with the selected
allows the operator to select the upper and lower range values and measurement units. All alarm levels must be within the LRV to
unit of measurement. The UD10 then analyzes the 4-20 mA input URV range.
signal from the sensor and displays the value with the designated
measurement unit, and also controls the alarm outputs. ALARM LATCHING
Latching or non-latching function is independently selectable for
UPPER AND LOWER RANGE VALUES each alarm. The default setting is non‑latching. Latched alarms can
The upper range value (URV) and lower range value (LRV) are be reset with a “Reset Latched Alarms” command from the menu
selected using the magnetic tool and the UD10’s menu system system or a power cycle.
(Main Menu > Device Setup). The URV corresponds to the 20
mA signal while the LRV corresponds to 4 mA. The default values SENSOR CALIBRATION
are 0 for the LRV and 100 for the URV. When the generic detector
supports HART communication, the URV and LRV come from the The UD10 does not support generic sensor calibration. Generic
attached detector. sensors must be pre-calibrated following the procedure described
in the instruction manual provided by the sensor manufacturer.
The operator can enter a low input fault threshold in the range of Refer to the following menus when using the UD10’s LCD display
0.5–4 mA (default is 3.5 mA). When the input signal is at or below and internal magnetic switches. Two different menus are provided
this point, an “Out of Range Low Fault” is annunciated. This feature to accommodate sensors with or without HART communication.
can be enabled/disabled as desired.
When connecting a HART Communicator to the UD10’s 4-20 mA
output, refer to the “UD10 HART Handheld” menu in Appendix F.
HIGH FAULT THRESHOLD
MENU HELP
The operator can enter a high input fault threshold in the range of
Status menus only allow the user to view the data. The
20–27 mA (default is 21 mA). When the input signal is at or above
Setup menus allow the user to both view and edit the
this point, an “Out of Range High Fault” is annunciated. This feature
data.
can be enabled/disabled as desired.
NOTE
For complete information regarding the FlexSonic Acoustic Detector, refer to instruction manual 95-8657.
WIRING
UD10 with FlexSonic Acoustic
4000
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to sensor is 2000 feet.
INSTALLATION NOTE
The ATX10 transmitter module is shipped with the SD
NOTE card installed in the memory module. A piece of tape has
Detector housings must be electrically connected to been installed to secure the card in place and prevent it
earth ground. A dedicated earth ground terminal is from becoming dislodged during shipping. The shipping
provided. tape should be removed prior to commissioning the
acoustic detector.
NOTE
The AC100 has an Intrinsic Safety (IS) Barrier. Proper
NEC/CEC IS grounded must be ensured.
NOTE
The detector must always be installed per local
installation codes.
NOTE
Use of a threaded adapter for connecting the AC100 to
the STB or ATX10 is prohibited.
P3
-4
P3
-3
JU
P3
M
-2
PE
P3
N
D
R
-1
TO
A
G
N
D
+
A
C
VD
24 B J3
24
A
-1
VD ORANGE
m
C J3
20
24 +
–
-2
4-
VD GRAY
C
-4
VD
P1
C J3
SH – -3
RED
24
D
IEL
-3
L
J3
P1
D
IE
-4
BLACK
SH
-2
J3
P1
-5
-1
P1
SENSOR
POWER
AND OUTPUT GREEN
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
IS GROUND
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2 UD10
HIGH ALARM NO J4-3
DISPLAY UNIT
P1-2 4-20 mA –
AUX ALARM COM J4-4
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
J2
LOW ALARM COM J4-7 AC100
COM
LOW ALARM NC J4-8 ACOUSTIC
J2-3
LOW ALARM NO J4-9 SENSOR
J2-2 RS485 A FAULT COM J4-10
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
NOTES: DEVICE HOUSINGS MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
CONNECT THE GREEN WIRE FROM THE AC100 TO THE GROUND SCREW
Power Supply Connector INSIDE THE ATX10 HOUSING.
ALARM MODE
AL ARM
BASIC
5 9 DB ALARM LEVEL
09 NOV 2 0 1 5 0 8 :5 2
A2697
AUDIBLE RANGE
4X 30 BANDS = 120 BANDS
ULTRASONIC RANGE
8X 3 BANDS = 24 BANDS
A2698
Figure 6-2—UD10 Display Uses 12 Bands to Represent the FlexSonic Acoustic Detector’s 144 Bands
MENU STRUCTURE
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the PIRDUCT Gas Detector, refer to instruction manual 95-8573.
WIRING
UD10-DCU with PIRDUCT
4000
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10-DCU is 2000 feet.
Maximum recommended cable length from UD10-DCU to PIR9400/PIRTB termination box is 2000 feet.
J3-2
J3-3
J3-4
J3-5
J3
PIRDUCT
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector YELLOW
HIGH ALARM COM J4-1
4-20 mA +
BLACK
P1-3 HIGH ALARM NC J4-2
WHITE
P1-2 4-20 mA – HIGH ALARM NO J4-3
P1-1 SHIELD
AUX ALARM NC J4-5 GREEN
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
J3-1
J3-2
J3-3
J3-4
J3-5
J3
SPARE CHASSIS
CALIBRATE
CAL
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop CAL
Connector YELLOW
HIGH ALARM COM J4-1 4 – 20 4 – 20 WHITE
4-20 mA +
P1-3 HIGH ALARM NC J4-2 RET RET BLACK
HIGH ALARM NO J4-3 RED
P1-2 4-20 mA –
+24 +24
AUX ALARM COM J4-4
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
INSTALLATION NOTES
CORRECT
Direction of Air Flow
IMPORTANT
Hydrocarbon-based grease emits hydrocarbon
vapors that will be measured by PIRDUCT, resulting
in inaccurate gas level readings. Use only low vapor
pressure Lubriplate grease or Teflon tape on the
PIRDUCT detector and associated termination box. Do
not get grease on the optics of the detector. A suitable
grease is listed in the “Ordering Information” section in
this manual.
ORIENTATION
The PIRDUCT Detector is a position sensitive instrument. It must be
installed in the proper orientation to achieve proper vapor detection.
Ensure that the installation location selected will accommodate the Direction of Air Flow
instrument in the proper mounting orientation. B2280
To initiate calibration of the PIRDUCT from the UD10 Display: Waiting for Span 3.8 3.8
Main Menu
Process Vars
Display Status 3. The UD10 will then display “Waiting for Gas” on the screen,
Device Status Device Cal Calibration
Display Setup Calibration Execute
while the LED at the PIRTB is flashing red.
Device Setup Cal Gas Conc Abort
Device Cal 4. Apply calibration gas to the detector.
Display Test
Language
5. The UD10 will display “Waiting for Span” on the screen, with a
red flashing LED at the PIRTB.
2. Activate “Execute” (Enter/Select) to start calibration.
6. When the UD10 displays “Remove Cal Gas” on the screen and
3. The UD10 will display “Waiting for Zero” on the main display the LED at the PIRTB turns off, remove the calibration gas.
screen.
7. After successful calibration, the UD10 automatically returns to
4. The UD10 will then display “Waiting for Gas” on the screen. the normal mode, and the LED on the PIRTB remains off.
remove the calibration gas from the PIRDUCT. TO ACTIVATE CALIBRATION SWITCH
2. The UD10 will display “Waiting for Zero” on the main display
screen, with a steady red LED at the PIRTB.
B2056
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the PIRECL CO2 Gas Detector, refer to instruction manual 95-8676.
WIRING
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10-DCU is 2000 feet.
Maximum recommended cable length from UD10-DCU to detector/STB termination box is 2000 feet.
24 VDC + 2 RED
CALIBRATE 3
24 VDC – 4
24 VDC + 5 1
4-20 MA + 6
4-20 MA – WHITE
7
RS-485 B 8
RS-485 A 9
UD10 DISPLAY UNIT
RELAY POWER (RED) 10
WIRING TO OPTIONAL FAULT (ORANGE) 11
RELAY BOARD Sensor Connector
NO USER CONNECTION LOW ALARM (WHITE) 12
J3-1
J3-2
J3-3
J3-4
J3-5
J3
HIGH ALARM (YELLOW) 13
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
NOTE 1 INTERNAL JUMPER REQUIRED FOR Connector
NON-ISOLATED CURRENT OUTPUT
(SINGLE POWER SUPPLY).
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
C2404
ORIENTATION
It is highly recommended that the PIRECL CO2 be installed
in the horizontal position. The detector is not position-sensitive
in terms of its ability to detect gas. However, the weather baffle
assembly provides superior performance when the PIRECL CO2 is
installed with the baffle in a horizontal position.
CORRECT INCORRECT
Main Menu 2. The UD10 will display “Waiting for Zero” on the main display
Process Vars screen, with a solid red LED on the PIRECL CO2 housing
Display Status
Device Status
Device Cal illuminated.
Cal Gas Con Calibration
Display Setup
Cal Gas Type Execute
Device Setup
Calibration Abort 3. The UD10 will then display “Waiting for Gas” on the screen,
Device Cal
Display Test
Date while the LED on the PIRECL CO2 is flashing red.
Device Test
Language 4. Apply calibration gas to the PIRECL CO2 detector.
5. The UD10 will display “Waiting for Span” on the screen, while a
2. Activate “Execute” (Enter/Select) to start calibration. red flashing LED on the PIRECL CO2 housing is illuminated.
3. The UD10 will display “Waiting for Zero” on the main display 6. When the UD10 displays “Remove Cal Gas” on the screen
screen, with a solid red LED on the PIRECL CO2 housing and the LED on the PIRECL CO2 housing is off, remove the
illuminated. calibration gas.
4. The UD10 will then display “Waiting for Gas” on the screen, 7. After successful calibration, the UD10 automatically returns to
while the LED on the PIRECL CO2 is flashing red. the normal mode with the green LED illuminated on the PIRECL
CO2.
5. Apply calibration gas to the PIRECL CO2.
6. The UD10 will display “Waiting for Span” on the screen, while a
red flashing LED on the PIRECL CO2 housing is illuminated.
7. When the UD10 displays “Remove Cal Gas” on the screen MULTICOLOR LED
and the LED on the PIRECL CO2 housing is off, remove the
calibration gas. HART COMMUNICATION PORT
(COVER INSTALLED)
CALIBRATION MAGNET
Waiting for Zero 3.8 2.2 Model PIRECL CO2 Gas Detector
MENU HELP
Status menus only allow the user to view the data. The
Setup menus allow the user to both view and edit the
data.
NOTE
For complete information regarding the LS2000 Gas Detector, refer to instruction manual 95-8714.
WIRING
UD10 with LS2000
4000
3500
3000
AWG
Distance in ft.
2000 12
14
1500 16
1000
18
500
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Power Supply Voltage
Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Maximum recommended cable length from UD10 to sensor is 2000 feet.
0V COM 1 SPARE 11
SHIELD 4 SHIELD 14
INTR B 5 INTR A 15
RS-485 B 8 RS-485 A 18
–mA 9 +mA 19
HART
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
FAULT NC J4-11
J2-1 RS485 B
FAULT NO J4-12
24 VDC –
24 VDC –
24 VDC +
24 VDC +
MODBUS
SHIELD
SHIELD
J4
Connector
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
NON-ISOLATED CURRENT OUTPUT
(SINGLE POWER SUPPLY).
Power Supply Connector
NOTE 2 UD10 HOUSING MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND. A2695
3. The UD10 will display “Waiting for Zero” on the main display
screen, with a solid red LED on the LS2000 housing illuminated.
FlexSonic ® Acoustic X3301 Multispectrum PointWatch Eclipse ® IR FlexVu ® Universal Display Eagle Quantum Premier®
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System