Kabllo 1915 - Nyy

The datasheet provides specifications for NYY PVC insulated power cables suitable for fixed installations, with a voltage rating of 0.6/1kV. It details the construction, temperature ranges, bending radii, and current carrying capacities for various configurations and sizes of the cables. The document also includes compliance with relevant standards and manufacturer contact information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views3 pages

Kabllo 1915 - Nyy

The datasheet provides specifications for NYY PVC insulated power cables suitable for fixed installations, with a voltage rating of 0.6/1kV. It details the construction, temperature ranges, bending radii, and current carrying capacities for various configurations and sizes of the cables. The document also includes compliance with relevant standards and manufacturer contact information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Datasheet Version 1/2009

NYY PVC Insulated Core 0,6/1kV


Single and Multicore
Application: This power cable is suitable for fixed installations, preferably in cable ducts,
indoors, outdoors, in water or underground if no mechanical damage is to be
expected.

Construction: 1 ..... solid (RE) or stranded (RM/SM) bare copper


2 ..... core insulation of polyvinylchloride (PVC)
3 ..... PVC core covering or taping
4 ..... outer sheath of polyvinylchloride (PVC), black

Information: short circuit temperature on core (max. 5 sec.)


<=300mm² --> 160°C
>300mm² --> 140°C

According to: DIN VDE 0276-603


HD 603 S1:1994 + A2:2003
DIN EN 60228 class 1 and 2 (construction)
HD 308 S2 (core identification)

Technical data:

Nominal voltage Uo/U [V] 600 / 1000 Volt


Test voltage [V]AC 4000
Temperature range in motion - 5°C till +70°C
fixed -20°C till +70°C
Bending radius single-core style x diameter 15
multi-core style x diameter 12
Flammability standard EN 60332-1-2

Number of cores and Copper Overall Weight Current Current


nominal cross figure diameter carrying carrying
section capacity capacity
appr. ground air
mm² kg/km appr. mm kg / km A A
1 x 16 RE 160 11 233 107 84
1 x 25 RM 250 12 370 138 114
1 x 35 RM 350 14 480 164 139
1 x 50 RM 500 16 640 195 169
1 x 70 RM 700 17 850 238 213
1 x 95 RM 950 19 1.120 286 264
1 x 120 RM 1.200 21 1.375 325 307
1 x 150 RM 1.500 23 1.660 365 352
1 x 185 RM 1.850 25 2.050 413 406
1 x 240 RM 2.400 28 2.634 479 483
1 x 300 RM 3.000 30 3.295 541 557
1 x 400 RM 4.000 32 4.231 614 646
1 x 500 RM 5.000 34 5.284 693 747
1 x 630 RM 6.300 42 6.850 777 858

 MEINHART KABEL ÖSTERREICH GMBH , MEINHART, MEINHART LAN and MEINHART-Logo are registered trademarks of MEINHART Kabel Österreich GmbH
Meinhart Kabel Österreich GmbH, Westbahnstraße 6, A- 4490 St. Florian, Tel. +43 (0)7224 690-0, Fax +43 (0)7224 690-610INTERNET: HTTP://WWW.MEINHART.AT,
UID-NR.: ATU63684739, FN: 299994v LANDESGERICHT STEYR
The above values correspond to the manufacturer´s specifications and are not guaranteed.. Created from Meinhart Kabel Österreich GmbH Date Oktober 2009
Datasheet Version 1/2009
Number of cores and Copper Overall Weight Current Current
nominal cross figure diameter carrying carrying
section capacity capacity
appr. ground air
mm² kg/km appr. mm kg / km A A
2 x 1,5 RE 30 11 220 27 20
2 x 2,5 RE 50 12 267 36 25
2x 4 RE 80 14 342 47 34
2x 6 RE 120 15 412 59 43
2 x 10 RE 200 16 510 79 59
2 x 16 RM 320 18 670 102 79
3 x 1,5 RE 45 13 244 27 20
3 x 2,5 RE 75 14 294 36 25
3x 4 RE 120 16 393 47 34
3x 6 RE 180 17 481 59 43
3 x 10 RE 300 18 645 79 59
3 x 16 RE 480 20 872 102 79
3 x 16 RM 480 20 872 102 79
3 x 25 RM 750 25 1.350 133 106
3 x 35 SM 1.050 25 1.460 159 129
3 x 50 SM 1.500 25 1.460 159 129
3 x 70 SM 2.100 25 1.460 159 129
3 x 95 SM 2.850 35 3.560 280 246
3 x 120 SM 3.600 38 4.310 318 285
3 x 150 SM 4.500 42 5.310 359 326
3 x 185 SM 5.550 47 6.630 406 374
3 x 240 SM 7.200 53 8.480 473 445
3 x 25/16 RM/RE 910 25 1.513 133 106
3 x 35/16 SM/RE 1.210 27 1.804 159 129
3 x 50/25 SM/RM 1.750 31 2.349 188 157
3 x 70/35 SM 2.450 35 3.117 232 199
3 x 95/50 SM 3.350 39 4.167 280 246
3 x 120/70 SM 4.300 44 5.190 318 285
3 x 150/70 SM 5.200 47 6.161 359 326
3 x 185/95 SM 6.500 53 7.673 406 374
3 x 240/120 SM 8.400 59 9.850 473 445
3 x 300/150 SM 10.500 65 11.900 535 511
4 x 1,5 RE 60 14 278 27 20
4 x 2,5 RE 100 15 340 36 25
4x 4 RE 160 17 460 47 34
4x 6 RE 240 18 570 59 43
4 x 10 RE 400 20 775 79 59
4 x 10 RM 400 20 775 79 59
4 x 16 RE 640 22 1.072 102 79
4 x 16 RM 640 22 1.072 102 79
4 x 25 RM 1.000 27 1.632 133 106
4 x 35 SM 1.400 27 1.959 159 129
4 x 50 SM 2.000 32 2.595 188 157
4 x 70 SM 2.800 36 3.488 232 199
4 x 95 SM 3.800 41 4.637 280 246
4 x 120 SM 4.800 43 5.689 318 285
4 x 150 SM 6.000 49 6.973 359 326
4 x 185 SM 7.400 54 8.663 406 374
4 x 240 SM 9.600 60 11.140 473 445
5 x 1,5 RE 75 15 317 * *
5 x 2,5 RE 125 16 391 * *
5x 4 RE 200 18 537 * *
5x 6 RE 300 19 672 * *
5 x 10 RE 500 21 921 * *
5 x 10 RM 500 21 921 * *
5 x 16 RE 800 24 1.294 * *

 MEINHART KABEL ÖSTERREICH GMBH , MEINHART, MEINHART LAN and MEINHART-Logo are registered trademarks of MEINHART Kabel Österreich GmbH
Meinhart Kabel Österreich GmbH, Westbahnstraße 6, A- 4490 St. Florian, Tel. +43 (0)7224 690-0, Fax +43 (0)7224 690-610INTERNET: HTTP://WWW.MEINHART.AT,
UID-NR.: ATU63684739, FN: 299994v LANDESGERICHT STEYR
The above values correspond to the manufacturer´s specifications and are not guaranteed.. Created from Meinhart Kabel Österreich GmbH Date Oktober 2009
Datasheet Version 1/2009
Number of cores and Copper Overall Weight Current Current
nominal cross figure diameter carrying carrying
section capacity capacity
appr. ground air
mm² kg/km appr. mm kg / km A A
5 x 16 RM 800 24 1.294 * *
5 x 25 RM 1.250 29 2.004 * *
5 x 35 RM 1.750 30 2.575 * *
5 x 50 RM 2.500 36 3.193 * *
5 x 70 RM 3.500 40 4.319 * *
5 x 95 RM 4.750 46 5.783 * *
5 x 120 RM 6.000 50 7.095 * *
5 x 150 RM 7.500 59 8.240 * *
7 x 1,5 RE 105 16 376 * *
10 x 1,5 RE 150 19 495 * *
12 x 1,5 RE 180 18 440 * *
14 x 1,5 RE 210 20 494 * *
16 x 1,5 RE 240 21 600 * *
19 x 1,5 RE 285 22 614 * *
21 x 1,5 RE 315 23 700 * *
24 x 1,5 RE 360 24 769 * *
30 x 1,5 RE 450 26 918 * *
40 x 1,5 RE 600 29 1.250 * *
7 x 2,5 RE 175 17 472 * *
10 x 2,5 RE 250 20 530 * *
12 x 2,5 RE 300 21 578 * *
14 x 2,5 RE 350 22 680 * *
16 x 2,5 RE 400 23 750 * *
19 x 2,5 RE 475 24 870 * *
21 x 2,5 RE 525 25 900 * *
24 x 2,5 RE 600 26 1.035 * *
30 x 2,5 RE 750 28 1.300 * *
40 x 2,5 RE 1.000 31 1.700 * *
7 x 4 RE 280 18 600 * *
7 x 6 RE 420 20 760 * *
7 x 10 RE 700 22 1.080 * *

* The current carrying capacity of the cables depends on the number of cores loaded (see DIN VDE 0276-627)

 MEINHART KABEL ÖSTERREICH GMBH , MEINHART, MEINHART LAN and MEINHART-Logo are registered trademarks of MEINHART Kabel Österreich GmbH
Meinhart Kabel Österreich GmbH, Westbahnstraße 6, A- 4490 St. Florian, Tel. +43 (0)7224 690-0, Fax +43 (0)7224 690-610INTERNET: HTTP://WWW.MEINHART.AT,
UID-NR.: ATU63684739, FN: 299994v LANDESGERICHT STEYR
The above values correspond to the manufacturer´s specifications and are not guaranteed.. Created from Meinhart Kabel Österreich GmbH Date Oktober 2009