Cable Gland Specification (Unit1)
Owner
                                                          STAR ENERGY GEOTHERMAL
                                                            (WAYANG WINDU) LIMITED
                                                Project
                                                          WAYANG WINDU UNITS 1 AND 2
                                                             RETROFITS PROJECT
                                                Contract No.                                Origin
                                                               3200001256                    FH
                                                Contractor
                                                                           CONSORTIUM OF
                                                                       FUJI ELECTRIC CO., LTD. &
                                                                     PT. WASA MITRA ENGINEERING
                                                SEGWWL Drawing No.                        Revision
                                                WWRP1-EE-EC-8261                             0
                                                Internal drawing No.PD520931
                                                Dwg. Status
                                                            FOR CONSTRUCTION
DOCUMENT SUBMITTAL STATUS :
       ☐ FOR INFORMATION         ☐ FOR REVIEW      ☒ FOR CONSTRUCTION          ☐ AS-BUILT
  0    Issued for construction        2024/07/16           S.Tsuji     N.watanabe     J.Yamamoto
 Rev              Description           Date              Prepared     Checked         Approved
                             Specification of Cable Gland
Regarding the cable gland, materials should be selected by ambient air condition include H2S Gas.
And installation parts should be decided for each situation as follows.
1. Material of cable gland
        Kind of cable                Cable Outer Diameter                             Material
                              22mm or Less                            Polycarbonate Plastics
Power / C & I Cable
                              More than 22mm                          Aluminum
Grounding Cable               All                                     Polycarbonate Plastics
2. Location of cable gland installation
              Location                        Install           Type of cable gland          Remarks
                                                                                          For bottom cable
                                                                                        entry part of Panel /
                                                                                       Cubicle and terminal
                                                                                         Box, sealing putty
                                          Not Applicable          Not Applicable         should be applied
                                                                                           instead of cable
                                                                                                gland.
                                                                                      It is separate from the
               Air                                                                             open air.
               Conditioning Area
    Indoor
                                                                                       For cable entry part
                                                                    Armored
                                                                                      of Panel / Cubicle and
                                           Applicable               No Biting
                                                                                      Terminal Box without
                                                                     Type
                                                                                           bottom part.
               No Air
                                           Applicable                                            -
               Conditioning Area                                  Polycarbonate
                                                                        or
                                                                   Aluminum
                                                                      IP66
   Outdoor               -                 Applicable                                            -
3. Supply Cable Gland : Armored-No Bite Type
   Cable gland should isolate inside of Panel / Cubicle / Terminal-Box from outside open air included H2S Gas
   at cable entry part. [Ingress Protection : IP66]
   There are Long cable entry holes of terminal Boxes electrical equipments.Therefore, Armored No Biting type
   cable gland should be adopted. Please refer to following drawings for detail of cable gland installation.
   Cable load should be supported by conduit, cable tray and cable bracket.
   Armor (Wire / Tape )should be grounded inside of each panel, cubicle and terminal box.
                                                        [2/8]
                                             0
3-1. Typical Installation of Armored Cable
(Long Cable Entry Hole of Terminal Box)
                     [3/8]
                                             0
3-2. Typical Installation of Armored Cable
 (Thin Cable Entry Hole of Terminal Box)
                     [4/8]
                                                 0
3-3. Typical Installation of Non-Armored Cable
                       [5/8]
                                     0
4. Detail Dimension of Cable Gland
                 [6/8]
Aluminum Type
                        SAMPLE
                [7/8]
Polycarbonate Type
                             SAMPLE
                     [8/8]