PART 5
FIRE AND SAFETY – MEASURES AND FEATURES
ii                                                                                                      ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART     Table of Contents
5
Fire and Safety – Measures and Features
                CONTENTS
                CHAPTER 1        Passive Fire Protection.......................................................................... 1
                                 Section 1     General .................................................................................. 2
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                                   iii
This Page Intentionally Left Blank
PART     Chapter 1: Passive Fire Protection
5
CHAPTER           1     Passive Fire Protection
                CONTENTS
                SECTION 1        General .................................................................................................... 2
                                 1     General ............................................................................................... 2
                                            1.1         Administration Review ..................................................................... 2
                                            1.3         ABS Review .................................................................................... 2
                                            1.5         Materials Containing Asbestos ........................................................ 2
                                            1.7         Alternative Design and Arrangements ............................................. 2
                                 3          Structural Fire Protection .................................................................... 2
                                 5          Protection of Accommodation Spaces, Service Spaces and
                                            Control Stations .................................................................................. 7
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                                             1
PART    Section 1: General
5
CHAPTER           1     Passive Fire Protection
SECTION 1 General
1      General (1993)
       All mobile offshore drilling units are to meet the requirements of this Chapter with regard to structural fire
       protection, protection of accommodation spaces, service spaces and control stations.
2                                       ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part            5     Fire and Safety – Measures and Features
Chapter         1     Passive Fire Protection
Section         1     General                                                                                                              5-1-1
                                                 TABLE 1
                      Fire Integrity of Bulkheads Separating Adjacent Spaces (2017)
             Spaces                        (1)      (2)      (3)     (4)       (5)       (6)        (7)         (8)       (9)      (10)    (11)
Control Stations                    (1)   A-0 (4)   A-0     A-60     A-0      A-15      A-60       A-15       A-60 (5)   A-60        *     A-0
Corridors                           (2)              C      B-0      B-0      B-0       A-60       A-0        A-0 (5)    A-0         *     B-0
                                                                    A-0 (2)
Accommodation Spaces                (3)                       C      B-0       B-0      A-60        A-0       A-0 (5)     A-0       *       C
                                                                    A-0 (2)
Stairways                           (4)                              B-0       B-0      A-60        A-0       A-0 (5)     A-0       *      B-0
                                                                    A-0 (2)   A-0 (2)                                                     A-0 (2)
Service Spaces (low risk)           (5)                                         C       A-60       A-0         A-0        A-0      *       B-0
Machinery Spaces of Category A      (6)                                                 *Note 1   A-0 (1)      A-60      A-60      *       A-0
Other Machinery Spaces              (7)                                                           A-0 (1,3)    A-0        A-0      *       A-0
Hazardous Areas                     (8)                                                                         —         A-0      —       A-0
Service Spaces (high risk)          (9)                                                                                  A-0 (3)   *       A-0
Open Decks                         (10)                                                                                            —        *
Sanitary and Similar Spaces        (11)                                                                                                     C
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                                           3
Part          5     Fire and Safety – Measures and Features
Chapter       1     Passive Fire Protection
Section       1     General                                                                                                                       5-1-1
                                                  TABLE 2
                         Fire Integrity of Decks Separating Adjacent Spaces (2012)
Spaces ↓            Space →                 (1)          (2)         (3)         (4)        (5)      (6)       (7)      (8)       (9)      (10)   (11)
Below               Above
Control Stations                      (1)   A-0          A-0        A-0         A-0         A-0    A-60       A-0      A-0 (5)    A-0       *     A-0
Corridors                             (2)   A-0           *          *          A-0          *     A-60       A-0      A-0 (5)    A-0       *      *
Accommodation Spaces                  (3)   A-60         A-0         *          A-0          *     A-60       A-0      A-0 (5)    A-0       *      *
Stairways                             (4)   A-0          A-0        A-0          *          A-0    A-60       A-0      A-0 (5)    A-0       *     A-0
Service Spaces (low risk)             (5)   A-15         A-0        A-0         A-0          *      A-60      A-0       A-0       A-0       *     A-0
Machinery Spaces of Category A        (6)   A-60        A-60        A-60        A-60        A-60   *Note 1   A-60      A-60      A-60       *     A-0
Other Machinery Spaces                (7)   A-15         A-0        A-0         A-0         A-0    A-0 (1)   *Note 1    A-0       A-0       *     A-0
                                                  (5)         (5)         (5)         (5)
Hazardous Areas                       (8) A-60          A-0         A-0         A-0         A-0    A-60       A-0        —        A-0      —      A-0
Service Spaces (high risk)            (9)   A-60         A-0        A-0         A-0         A-0    A-60       A-0       A-0      A-0 (3)    *     A-0
Open Decks                           (10)    *            *          *           *           *       *         *         —         *       —       *
Sanitary and Similar Spaces          (11)   A-0          A-0         *          A-0          *      A-0       A-0       A-0       A-0       *      *
4                                                       ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part         5   Fire and Safety – Measures and Features
Chapter      1   Passive Fire Protection
Section      1   General                                                                                              5-1-1
                  (6)      Machinery Spaces of Category A are all spaces which contain internal combustion type
                           machinery used either:
                           •    For main propulsion or
                           •    For other purposes where such machinery has in the aggregate a total power of not less
                                than 375 kW (500 hp) or which contain any oil-fired boiler or oil fuel unit; and trunks
                                to such spaces.
                  (7)      (1999) Other Machinery Spaces are those spaces, including trunks to such spaces, containing
                           propulsion machinery, boilers, oil fuel units, steam and internal combustion engines,
                           generators and major electrical machinery (SCR, MCC and switchgear); oil filling station;
                           refrigerating, ventilation and air-conditioning machinery with motors having an aggregate
                           capacity greater than 7.5 kW (10 hp); and similar spaces, but are not machinery spaces of
                           Category A.
                  (8)      Hazardous Areas are all those areas where, due to the possible presence of a flammable
                           atmosphere arising from the drilling operation, the use without proper consideration of
                           machinery or electrical equipment may lead to fire hazard or explosion. See Section 4-3-6.
                  (9)      Services Spaces (high risk) are lockers, storerooms and working spaces in which flammable
                           materials are stored, galleys, pantries containing cooking appliances, paint rooms and
                           workshops other than those forming part of the machinery space.
                  (10)     Open Decks are open deck spaces excluding hazardous spaces.
                  (11)     Sanitary and Similar Spaces are communal sanitary facilities such as showers, baths,
                           lavatories, etc., and isolated pantries containing no cooking appliances. Sanitary facilities
                           which serve a space and with access only from that space shall be considered a portion of
                           the space in which they are located.
3.11
          Continuous “B” class ceilings or linings in association with the relevant decks or bulkheads will be accepted
          as contributing to the required insulation and integrity of a division.
3.13      (2012)
          Structural fire protection details are to avoid the risk of heat transmission at intersections and terminal
          points of required thermal barriers. The insulation of a deck or bulkhead is to be carried past the penetration,
          intersection or terminal point for a distance of at least 450 mm in the case of steel and aluminum structures.
          If a space is divided with a deck or a bulkhead of “A” class standard having insulation of different values,
          the insulation with the higher value is to continue on the deck or bulkhead with the insulation of the lesser
          value for a distance of at least 450 mm.
3.15
          Windows and sidescuttles, with the exception of navigation bridge windows, are to be of the non-opening
          type. Navigation bridge windows may be of the opening type, provided the design of such windows permits
          rapid closure. Windows and sidescuttles outside of hazardous areas may be of the opening type.
3.17      (2011)
          i)    The fire resistance of doors are to be equivalent to that of the division in which they are fitted.
          ii)    (2018) External doors in superstructures and deckhouses are to be at least “A-0” class standard and
                 be self-closing, where practicable. Where external doors in bulkheads of superstructures and deckhouses
                 are required to be watertight, they need not be self-closing; however, they are to be fitted with a
                 notice on both sides of the door stating that the doors are to be kept closed unless an adjacent self-
                 closing fire rated door is provided.
          iii)   (2017) Watertight doors in a watertight division fitted below the bulkhead deck need not be tested
                 to the Fire Test Procedure Code (Resolution MSC.307(88)) requirements for the fire rating of the
                 division in which the door is fitted. The bulkhead deck is the highest deck to which watertight
                 bulkheads extend and are made effective.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                5
Part           5   Fire and Safety – Measures and Features
Chapter        1   Passive Fire Protection
Section        1   General                                                                                                5-1-1
          iv)      (2017) Watertight doors fitted in a fire rated division above the bulkhead deck are to be tested to
                   the Fire Test Procedure Code (Resolution MSC.307(88)) requirements for the fire rating of the
                   division in which the door is fitted and, if applicable, the watertight door are to meet the self-closing
                   requirements. Watertight doors are to meet the requirements of ii), when applicable.
          v)       Where a watertight door is located adjacent to a fire door, both doors are to be capable of independent
                   operation, remotely if required and from both sides of each door.
          vi)      (2012) Self-closing doors in fire rated bulkheads are not to be fitted with hold-back hooks. However,
                   hold-back arrangements incorporating remote release fittings of the fail-safe type may be utilized.
3.19      (1999)
          Arrangements are to be made to ensure that the fire resistance is not impaired when
          i)        “A” and “B” class divisions are penetrated for the passage of electrical cables, pipes, trunks, ducts, etc.
          ii)       “A” class divisions are penetrated for girders, beams or other structural members, or
          iii)      “B” class divisions are penetrated for the fitting of ventilation terminals, lighting fixtures and similar
                    devices.
3.21      (2011)
          Where pipes penetrate “A” class divisions, such penetrations are to be tested in accordance with the Fire
          Test Procedures Code. If the penetration is constructed of steel or fitted with a steel sleeve at least 3 mm
          (0.12 in.) thick and at least 900 mm (35.4 in.) long (preferably 450 mm (17.7 in.) on each side of the
          division) and provided with fire insulation having the same length and fire integrity as the division, testing
          is not required. See 5-1-1/Figure 1.
          Uninsulated metallic pipes penetrating “A” class divisions are to be of materials having a melting
          temperature which exceeds 950°C (1742°F).
                                                FIGURE 1
                               Pipes Penetrating “A” Class Divisions (2018)
          “A” Class Division (Pipe material: Steel, Copper, Al-alloy, PVC)
                               (1) “A-0” Class                          (2) “A-15”, “A-30”, “A-60” Class
                                                    steel penetration piece
                         Division                            t mm                                Division
                                    L       L                                          L      L
                                                               pipe
                                                         steel sleeve
                         Division                           t mm                                 Division
                                    L       L                                          L      L
                                                               pipe
6                                            ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5   Fire and Safety – Measures and Features
Chapter        1   Passive Fire Protection
Section        1   General                                                                                           5-1-1
3.23      (2011)
          Where pipes penetrate “B” class divisions, such penetrations are to be tested in accordance with the Fire
          Test Procedures Code. Testing is not required however if:
          i)        Pipes having diameters greater than or equal to 150 mm (5.91 in.) penetrating “B” class divisions
                    are steel or lined with steel sleeves at least 1.8 mm thick and at least 900 mm (35.4 in.) long
                    (preferably 450 mm (17.7 in.) on each side of the division). See 5-1-1/Figure 2.
          ii)       Pipes having diameters less than 150 mm (5.91 in.) are to be steel or lined with steel sleeves at
                    least 1.8 mm thick and at least 600 mm (23.6 in.) long (preferably 300 mm (11.81 in.) on each side
                    of division). See 5-1-1/Figure 2.
          iii)      Pipes other than steel or copper are connected to the ends of the sleeve defined in i) and ii) by
                    flanges or couplings; or the clearance between the sleeve and the pipe is not to exceed 2.5 mm; or
                    any clearance between pipe and sleeve is to be made tight by means of non-combustible or other
                    suitable material. Uninsulated metallic pipes (including copper) penetrating “B” class divisions
                    have a melting temperature which exceeds 850°C (1562°F).
                                                 FIGURE 2
                                Pipes Penetrating “B” Class Divisions (2018)
          “B” Class Division
                    (1) Steel Pipe, Copper (1)                                         (2) Al-alloy Pipe, PVC Pipe
Division
                                                       Steel sleeve or                  L               L
       t ≥ 1.8 mm (0.07 in.)                           penetration piece
                                                       t ≥ 1.8 mm (0.07 in.)
5.1       (2016)
          In addition to the requirements of 5-1-1/3.7, accommodation spaces, service spaces and control stations, in
          general, are not to be located adjacent to hazardous areas. However, where this is not practicable, an
          engineering evaluation is to be performed to verify that the level of fire protection and blast resistance of
          the bulkheads and decks separating these spaces from the hazardous areas are adequate for the likely
          hazard. A Risk Analysis is to be submitted for review addressing the possible fire and explosion hazardous
          and identifying the worst foreseen hazards (fire and/or explosion). Depending on the type of hazard as
          determined from the risk analysis a Fire Load Analysis and/or a Blast Analysis are to be submitted for
          review with the mitigation measures (where needed) to allow safe operations.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                               7
Part        5     Fire and Safety – Measures and Features
Chapter     1     Passive Fire Protection
Section     1     General                                                                                               5-1-1
          5.1.1
                   Where a blast analysis is needed based on the risk analysis, the analysis is to show for the worst
                   foreseen blast scenario that the space is protected.
                   i)       Plastic deformation of the spaces’ structure is acceptable.
                   ii)      Attention is to be paid to penetrations through the bulkheads such as doors and HVAC
                            openings.
                   iii)     No penetration of the blast overpressure is allowed to enter the space through the division
                            panels. Overpressures of 0.07 bar (0.07 kgf/cm2; 1 psi) are allowable through penetrations
                            of the division; the point of measurement of the overpressure is where the overpressure
                            enters the open air of the space (i.e., the vent duct grill). Unmanned service spaces can
                            have higher overpressures through penetrations if justified.
                   iv)      Windows subject to blast overpressures are to remain intact.
                   For simplified blast analysis, the overpressure values in API RP 2FB, Table C.6.4.1 may be used.
                   Justification for the level of congestion (congested/non-congested) that an area has must be
                   provided. Justification on the duration of the assumed blast impulse must be provided.
          5.1.2
                   Where a fire analysis is needed based on the risk analysis, the analysis is to show that for the worst
                   foreseen fire scenario the following internal temperature and structural criteria:
                   i)       The temperature of the protected side of the fire division (bulkhead or deck) does not
                            increase more than:
                            a)       139°C (282°F) on average above ambient temperature for the time period of the
                                     event, but need not exceed 120 minutes and
                            b)       180°C (356°F) at any point above ambient temperature for the time period of the
                                     event, but need not exceed 120 minutes
                   ii)      The structure of the division (bulkhead or deck) is to remain intact with the main structure
                            of the vessel, and is to maintain its structural integrity for two (2) hours. Structural Integrity
                            means that the structure will not fall under its own weight, nor will it crumble or break
                            upon normal contact after exposure to a fire lasting two (2) hours.
                   Buildings with bulkheads and decks that are H-120 Class fire divisions facing hazardous areas
                   would not need a fire analysis; thus, only blast loads would need to be considered. Division sides
                   not facing the fire hazard but which share a common edge with a division that faces the hazard are
                   to have a 3 meter extension of the H-120 Class fire rated division. See Chapter 2, Section 1 of the
                   ABS Rules for Building and Classing Facilities on Offshore Installations (Facilities Rules) for the
                   definition of “H-120” divisions.
          5.1.3    (2017)
                   Where it is shown that normally occupied spaces may be exposed to a radiant heat flux in excess
                   of 100 kw/m2, the bulkhead or deck should be constructed to at least an “H-60” standard.
5.3       (2012)
          All bulkheads that are to be “A” class divisions are to extend from deck to deck and to the deckhouse side
          or other boundaries.
5.5       (2012)
          All bulkheads forming “B” Class divisions are to extend from deck to deck and to the deckhouse side or
          other boundaries, unless continuous “B” Class ceilings and/or linings are fitted on both sides of the bulkhead, in
          which case the bulkhead may terminate at the continuous ceiling or lining. In corridor bulkheads, ventilation
          openings are to be provided only in and under the doors of cabins, public spaces, offices and sanitary spaces.
          The openings are to be provided only in the lower half of the door. Any such opening in or under a door is to
8                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5   Fire and Safety – Measures and Features
Chapter        1   Passive Fire Protection
Section        1   General                                                                                          5-1-1
          have a total net opening no larger than 0.05 m2 (0.54 ft2) and is to be fitted with a noncombustible grill. Such
          openings are not to be provided in a door in a division forming a stairway enclosure.
5.7       (2012)
          Stairs are to be constructed of steel or other equivalent material which would not be rendered ineffective
          by heat.
5.9       (2012)
          Stairways which penetrate only a single deck are to be protected at least at one level by “A” or “B” Class
          divisions and self-closing doors so as to limit the rapid spread of fire from one deck to another. Elevator
          trunks are to be protected by “A” Class divisions. Stairways and elevator trunks which penetrate more than
          a single deck are to be surrounded by “A” Class divisions and protected by “A” Class self-closing doors at
          all levels.
5.11      (2012)
          Air spaces enclosed behind ceilings, paneling or linings are to be divided by close fitting draft stops spaced
          not more than 14 m (46 ft) apart. In the vertical direction, such enclosed air spaces, including those behind
          linings of stairways, trunks, etc., are to be closed at each deck.
5.13      (2012)
          Except for insulation in refrigerated compartments, insulating materials, including pipe and vent duct lagging,
          ceilings, linings and bulkheads are to be of non-combustible material. Vapor barriers and adhesive used in
          conjunction with insulation, as well as insulation of pipe fittings for cold service systems need not be
          noncombustible, but they should be kept to a minimum and their exposed surfaces are to have low flame
          spread characteristics. In spaces where penetration of oil products is possible, the insulation surfaces are to
          be impervious to oil or oil vapors.
5.15
          The framing, including grounds and the joint pieces of bulkheads, linings, ceilings and draft stops are to be
          of noncombustible material.
5.17
          In accommodation and service spaces and control stations, the following surfaces are to have low flame-
          spread characteristics:
          i)        All exposed surfaces in corridors and stairway enclosures;
          ii)       Surface in concealed or inaccessible spaces;
          iii)      Exposed surfaces of ceilings.
5.19      (2012)
          Bulkheads, linings and ceilings may have combustible veneers, provided that the thickness of such veneers
          does not exceed 2.5 mm (0.10 in.) within any space other than corridors, stairway enclosures and control
          stations where the thickness is not to exceed 1.5 mm (0.06 in.). Combustible materials used on these surfaces
          are to have a calorific value not exceeding 45 MJ/m2 of the area for the thickness used.
5.21      (2012)
          Primary deck coverings, if applied, within accommodation and service spaces and control stations, are to be
          of approved materials which will not readily ignite, this being determined in accordance with the FTP Code.
5.23      (2012)
          Paints, varnishes and other finishes used on exposed interior surfaces are not to be capable of producing
          excessive quantities of smoke and toxic products, this being determined in accordance with the FTP Code.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                               9
Part           5   Fire and Safety – Measures and Features
Chapter        1   Passive Fire Protection
Section        1   General                                                                                             5-1-1
5.25
          Ventilation ducts are to be of a noncombustible material, unless they are no more than 2 m (6.6 ft) long and
          have a cross-sectional area no more than 0.02 m2 (0.22 ft2) and:
          i)        Are of a material which has a low fire risk
          ii)       Are used only at the end of the ventilation device
          iii)      Are not situated less than 600 mm (23.5 in.), measured along the duct, from its penetration of any
                    “A” or “B” class division, including continuous “B” class ceilings
5.27      (2012)
          Ventilation ducts having an internal cross-sectional area greater than 0.02 m2 (0.22 ft2) penetrating “A”
          class divisions are to be steel or lined with a steel sheet sleeve that:
          i)        Are at least 3 mm (0.118 in.) thick and at least 900 mm (35.4 in.) long (preferably 450 mm (17.7 in.) on
                    each side of the division), provided with fire insulation having the same fire integrity as the division;
                    and
          ii)       Those exceeding 0.075 m2 (0.81 ft2), except those serving hazardous areas, are to also have automatic
                    fire damper capable of being closed manually from both sides of the bulkhead or deck and with a
                    position indicator which shows whether the damper is open or closed. The fire dampers are not
                    required where ducts pass through spaces surrounded by “A” class divisions, without serving those
                    spaces, provided those ducts have the same fire integrity as the divisions which they penetrate.
          iii)      For control stations, where the duct line serves other category spaces, a fire damper is to be provided
                    regardless of size.
          iv)       (2017) Where a fire damper is located within a ventilation coaming and cannot be examined by
                    other means, an inspection port or opening at least 150 mm (6 in.) in diameter is to be provided in
                    the coaming to facilitate survey of the damper without disassembling the coaming or the ventilator.
                    The closure provided for the inspection port or opening is to maintain structural integrity of the
                    coaming and, if appropriate, the fire integrity of the coaming.
          Ventilation ducts less than or equal to 0.02 m2 (0.22 ft2) penetrating “A” class divisions are to be steel or
          lined with steel sheet sleeves that are at least 3 mm (0.12 in.) thick and at least 200 mm (7.88 in.) long
          (preferably 100 mm (3.93 in.) on each side of bulkhead or, in the case of the deck, wholly laid on the lower
          side of the deck pierced) and provided with fire insulation having the same fire integrity as the division.
          See 5-1-1/Figure 3.
10                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part            5     Fire and Safety – Measures and Features
Chapter         1     Passive Fire Protection
Section         1     General                                                                                                     5-1-1
                                                    FIGURE 3
                             Ventilation Ducts Penetrating “A” Class Divisions (2012)
                                        (1) “A-0” Class                           (2) “A-15”, “A-30”, “A-60” Class
                                                                  steel sleeve
                               Division                              t mm                                Division
                                            L        L                                      L         L
                                                                     steel duct
5.29      (2016)
          Ventilation systems include the air handling units and/or fans, associated supply, return and/or exhaust
          ducting, and miscellaneous components.
          Ventilation systems for machinery spaces of category A, galleys, and hazardous areas are to be separated
          from each other and from the ventilation systems serving other spaces, (see also 4-3-6/9.1).
          Ducts serving hazardous areas are to not pass through accommodation spaces, service spaces, or control
          spaces.
          Ducts provided for the ventilation of machinery spaces of category A and galleys are not to pass through
          accommodation spaces, control stations or service spaces unless:
          i)              Constructed of steel at least 3 mm (0.12 in.) thick for ducts 300 mm (12 in.) wide or less, and at
                          least 5 mm (0.20 in.) for ducts 760 mm (30 in.) wide and over.
                          The minimum thickness is to be interpolated for widths or diameters between 300 and 760 mm
                          (12 and 30 in.);
          ii)             Fitted with an automatic fire damper close to the boundaries penetrated;
          iii)            Insulated to “A-60” standard from the machinery space or galleys to a point at least 5 m (16.4 ft)
                          beyond each fire damper; and
          iv)             The ducts are to be suitably supported and stiffened;
          or
          v)              Constructed of steel in accordance with 5-1-1/5.29i) and 5-1-1/5.29iv) above; and
          vi)             Insulated to “A-60” standard throughout the accommodation spaces, service spaces or control stations.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                           11
Part            5   Fire and Safety – Measures and Features
Chapter         1   Passive Fire Protection
Section         1   General                                                                                         5-1-1
          5.29.1
                     The galley ventilation system may also serve other spaces associated to the galley (pantry with no
                     cooking appliances, provisions store, dry goods store, scullery room) if all the following conditions
                     are satisfied:
                     i)     The galley and the associated space have a common boundary,
                     ii)    The associated space is surrounded by A-rated divisions,
                     iii)   An automatic fire damper with manual closures from both sides and fitted with position
                            indicator is to be installed at the common boundary penetrated, regardless of the size of the
                            duct,
                     iv)    The fire damper is to be connected to the Air-conditioning and Heating Unit (AHU) control
                            panel such that upon loss of power to the AHU fan, the fire damper closes,
                     v)     Fire detection in accordance with the requirements of 5-2-5/1.1 is to be installed in the
                            associated space, such that upon detection of fire, the AHU shuts down and the fire damper
                            in the common bulkhead closes, and
                     vi)    At least one means of egress for the associated space, independent from the galley egress, is
                            to be provided.
5.31
          Ducts provided for ventilation of accommodation and service spaces or control stations are not to pass through
          machinery spaces of Category A hazardous areas or galleys. However, a relaxation from this requirement,
          except for the ducts passing through hazardous areas, will be considered, provided:
          i)         The ducts where they pass through a machinery space of category A or a galley are constructed of
                     steel in accordance with 5-1-1/5.29i) and 5-1-1/5.29iv).
          ii)        Automatic fire dampers are fitted close to the boundaries penetrated; and
          iii)       The integrity of the machinery space or galley boundaries is maintained at the penetrations;
          or
          iv)        The ducts where they pass through a machinery space of category A or a galley are constructed of
                     steel in accordance with 5-1-1/5.29i) and 5-1-1/5.29iv); and
          v)         Are insulated to “A-60” standard within the machinery space or galley.
5.33      (2018)
          Ventilation ducts having an internal cross-sectional area greater than 0.02 m2 (0.22 ft2) penetrating “B”
          class bulkheads are to be steel or lined with steel sheet sleeves at least 1.8 mm (0.07 in.) thick and at least
          900 mm (35.4 in.) long (preferably 450 mm (17.7 in.) on each side of the division). Ventilation ducts having
          an internal cross-sectional area 0.02 m2 (0.22 ft2) or less are to be steel or lined with steel sheet sleeves at
          least 1.8 mm (0.07 in.) thick and at least 200 mm (7.88 in.) long (preferably 100 mm (3.93 in.) on each side
          of division). See 5-1-1/Figure 4.
12                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5       Fire and Safety – Measures and Features
Chapter        1       Passive Fire Protection
Section        1       General                                                                                            5-1-1
                                                  FIGURE 4
                           Ventilation Ducts Penetrating “B” Class Divisions (2018)
                             (1) Steel Duct                                        (2) Non-steel (non-combustible) Duct
Division
                                                                                              L             L
       t ≥ 1.8 mm (0.07 in.)                               Steel sleeve
                                                           t ≥ 1.8 mm (0.07 in.)
5.35
          Exhaust ducts from galley ranges are to be “A” class fire division integrity or equivalent where they pass
          through accommodation spaces or spaces containing combustible materials.
5.37      (2012)
          Each galley exhaust duct is to be fitted with:
          i)            A grease trap readily removable for cleaning;
          ii)           A fire damper located in the galley end of the duct which is automatically and remotely operated
                        and, in addition a remotely operated fire damper located in the exhaust end of the duct;
          iii)          Arrangements, operable from within the galley, for shutting off the exhaust fans; and
          iv)           Fixed means for extinguishing a fire within the duct.
5.39
          All ventilation systems’ main inlets and outlets are to be capable of being closed from outside the space
          being ventilated.
5.41
          Power ventilation of accommodation spaces, service spaces, control stations, machinery spaces and hazardous
          areas are to be capable of being stopped from an easily accessible position outside the space being served
          and in the event of a fire in the space served. The means for stopping the power ventilation serving machinery
          spaces or hazardous areas are to be entirely separate from the means provided for stopping ventilation of
          other spaces.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                   13
Part           5   Fire and Safety – Measures and Features
Chapter        1   Passive Fire Protection
Section        1   General                                                                                           5-1-1
5.43
          Windows and sidescuttles in boundaries which are required to meet an “A-60” standard which face the
          drill floor area are to be:
          i)        Constructed to an “A-60” standard; or
          ii)       (1999) Protected by a water curtain system on the exposed wall. The water curtain system should
                    be designed to provide a discharge rate of 6.0 liters per minute per square meter (0.15 gpm per
                    square foot); or
          iii)      Fitted with shutters of steel or equivalent material.
5.45
          The ventilation of the accommodation spaces and control stations are to be arranged in such a way as to
          prevent the ingress of flammable, toxic or noxious gases, or smoke from surrounding areas.
5.47      (2012)
          In addition to the air balancing openings as permitted in 5-1-1/5.5, air balancing ducts (jumper ducts) may
          be fitted only when all the following conditions are complied with:
          i)        The air balancing ducts are connecting two service spaces or a service space with a machinery
                    space other than a Category A machinery space or two machinery spaces other than Category A
                    machinery spaces.
          ii)       The spaces connected are located outside the accommodation deckhouse.
          iii)      The air balance duct is 3 mm (0.12 in.) thick, 900 mm (35.4 in.) long (preferably 450 mm (17.7 in.)
                    on each side) and fitted with a fire damper close to the boundary penetrated.
          iv)       The fire damper is to be automatically operated upon detection of smoke in any of the spaces
                    connected and remotely operated from a normally manned control station where the fire-detection
                    main indicator board for the spaces concerned is located. In addition, the fire damper is to be capable
                    of being closed locally.
          Air balancing openings between hazardous areas, such as openings between mud tank room and mud
          tanks, will be specially considered.
14                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART     Chapter 2: Active Fire Protection Systems and Equipment
5
CHAPTER           2     Active Fire Protection Systems and Equipment
                CONTENTS
                SECTION 1        General .................................................................................................. 17
                                 1     Governmental Authority .................................................................... 17
                                 3     Plans and Specifications ................................................................... 17
                                            3.1         General.......................................................................................... 17
                                            3.3         Fire Control Plans .......................................................................... 17
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                                              15
                 13        Spaces Containing Equipment with Oil Filled Capacitors .................31
16                      ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART        Section 1: General
5
CHAPTER              2      Active Fire Protection Systems and Equipment
SECTION 1 General
3.1     General
        The following plans together with supporting data and particulars are to be submitted.
        •      Arrangement and details of fire main systems
        •      Foam smothering systems
        •      Other fire extinguishing arrangements.
        •      Fire control plans
        •      Fire detection systems
        •      Fixed fire extinguishing systems
        •      Fire extinguishing appliances
        •      Control station for emergency closing of openings and stopping machinery
        •      Gas detection systems
        •      Fireman’s outfits
        •      (2010) The most severe service condition for the operation of the emergency fire pump (e.g., lightest
               draft as shown in Trim and Stability Booklet, etc.)
        •      (2010) Calculations and pump data demonstrating that the emergency fire pump system can meet the
               operational requirements specified in 5-2-2/1.1 with the proposed pump location and piping arrangements
               (e.g., adequate suction lift, discharge pressure, capacity, etc.) at the most severe service condition
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                          17
Part           5   Fire and Safety – Measures and Features
Chapter        2   Active Fire Protection Systems and Equipment
Section        1   General                                                                                       5-2-1
18                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART     Section 2: Fixed Fire Fighting Systems
5
CHAPTER              2   Active Fire Protection Systems and Equipment
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                         19
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     2     Fixed Fire Fighting Systems                                                                        5-2-2
20                                         ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     2     Fixed Fire Fighting Systems                                                                        5-2-2
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                               21
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     2     Fixed Fire Fighting Systems                                                                      5-2-2
                                                  FIGURE 1
                                       International Shore Connection
                                                                Coupling permanently attached that will
                                                                  fit the vessel's hydrants and hose.
                                      14.5 mm (9/16 in.)min.
Flat Face
                                                                          64 mm
                                                                         (21/2 in.)
                                                                                               132 mm
                                                                                               (51/4 in.)
                                                                                          178 mm
                                                                                           (7 in.)
                                                    19 mm
                                                    (3/4 in.)
22                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART      Section 3: Additional Fixed Fire Fighting Systems
5
CHAPTER              2   Active Fire Protection Systems and Equipment
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                           23
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     3     Additional Fixed Fire Fighting Systems                                                            5-2-3
3 Gas Smothering
3.1       General
          3.1.1    Storage (2013)
                   Where the gas smothering medium is stored outside of the protected space, the storeroom is to be
                   situated in a safe and readily accessible position and is to be effectively ventilated by a ventilation
                   system independent of all other spaces.
                   Spaces for storage of cylinders or tanks for extinguishing gas are not to be used for other purposes.
                   These spaces are not to be located forward of the forward collision bulkhead, when fitted. Access
                   to these spaces is to be possible from the open deck. Spaces situated below the deck are to be
                   located no more than one deck below the open deck.
                   Spaces where entrance from the open deck is not provided or which are located below deck are to
                   be fitted with mechanical ventilation. The exhaust duct (suction) is to be lead to the bottom of the
                   space. Such spaces are to be ventilated with at least six air changes per hour.
          3.1.2    Design (2018)
                   Containers and associated pressure components are to be designed based upon an ambient temperature
                   of 55°C (131°F).
                   For CO2 fire extinguishing systems, the wall thickness of steel piping is to be suitable for the
                   pressure and not less than the thickness identified in 5-2-3/Table 1. Column A is for piping from
                   storage containers to distribution station, and column B is for piping from distribution station to
                   nozzles. For other fixed gas fire extinguishing systems, calculations showing compliance with
                   4-2-2/5.7 are to be submitted for approval.
                   Where the fire-extinguishing medium is used as the power source for the pre-discharge alarm, the
                   piping to the alarm is to comply with Column B of 5-2-3/Table 1.
                   The pressure rating of pipe connections such as flanges from the distribution aftermost valve to
                   discharge nozzles is to be not less than the maximum pressure developed during the discharge of
                   CO2 into protected spaces.
                   The relief valve of a CO2 fire extinguishing system is to discharge outside of the CO2 container
                   storage compartment, in a safe area. In addition, in piping sections where valve arrangements introduce
                   sections of closed piping, such sections are to be fitted with a pressure relief valve and the outlet
                   of the valve is to be led to open deck.
                   Gray cast iron piping components are not to be used for fixed gas fire extinguishing systems. All
                   discharge piping, fittings and nozzles in the protected spaces are to be constructed of materials
                   having a melting temperature which exceeds 925°C (1697°F). The piping and associated equipment
                   are to be adequately supported.
                   Threaded joints in CO2 systems are to be allowed only inside protected spaces and in CO2 cylinder
                   rooms.
24                                         ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     3     Additional Fixed Fire Fighting Systems                                                                   5-2-3
                                               TABLE 1
                               Minimum Steel Pipe Wall Thickness for CO2
                                   Medium Distribution Piping (2013)
                  Nominal      OD         A          B                       Nominal        OD          A         B
                  size, mm     mm        mm         mm                       size, in.      in.        in.       in.
                    15        21.3       2.8        2.6                         1/2        0.840     0.110      0.102
                    20        26.9       2.8        2.6                         3/4        1.050     0.110      0.102
                    25        33.7       4.0        3.2                         1          1.315     0.157      0.126
                    32        42.4       4.0        3.2                        11/4        1.660     0.157      0.126
                    40        48.3       4.0        3.2                        11/2         1.9      0.157      0.126
                    50        60.3       4.5        3.6                         2          2.375     0.177      0.142
                    65        76.1       5.0        3.6                        21/2        2.875     0.197      0.142
                    80        88.9       5.5        4.0                         3           3.5      0.220      0.157
                    90        101.6      6.3        4.0                        31/2         4.0      0.248      0.157
                    100       114.3      7.1        4.5                         4           4.5       0.28      0.177
                    125       139.7      8.0        5.0                         5          5.563     0.315      0.197
                    150       168.3      8.8        5.6                         6          6.625     0.346      0.22
             Notes:
                          1     The above minimum thicknesses are derived from those thicknesses available in ISO
                                4200 Series 1 (OD), JIS (N.P.S.), or ASTM (N.P.S.). Diameter and thickness according
                                to other recognized standards will be accepted.
                          2     For threaded pipes, where approved, the thickness is to be measured to the bottom of
                                the thread.
                          3     The internal surface of pipes outside of the engine room is to be galvanized.
                          4     For larger diameters the minimum wall thickness will be subject to special consideration
                                by ABS.
                          5     In general, the minimum thickness is the nominal wall thickness and no allowance need be
                                made for negative tolerance or reduction in thickness due to bending.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                    25
Part        5       Fire and Safety – Measures and Features
Chapter     2       Active Fire Protection Systems and Equipment
Section     3       Additional Fixed Fire Fighting Systems                                                                  5-2-3
          3.1.4      Controls
                     Except as otherwise permitted herein two independent manual control arrangements are to be
                     provided, one of them being positioned at the storage location and the other in a readily accessible
                     position outside of the protected space.
5 Foam
26                                            ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     3     Additional Fixed Fire Fighting Systems                                                            5-2-3
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                              27
Part            5   Fire and Safety – Measures and Features
Chapter         2   Active Fire Protection Systems and Equipment
Section         3   Additional Fixed Fire Fighting Systems                                                              5-2-3
                     Automatic actuation is not permitted when the protected space is normally manned or interferes
                     with the safety navigation of the vessel. If the protected space is normally unmanned and may be
                     entered occasionally for brief periods such as for repairs, maintenance or other purpose, automatic
                     actuation may be allowed in addition to manual actuation, provided that the following conditions
                     are met
                     i)       The egress from the protected space is horizontal. Exit doors from the spaces are to be
                              outward-swinging self-closing doors (i.e., opening in the direction of escape routes) which
                              can be opened from the inside, including when the doors are locked from the outside.
                     ii)      Notices that the space is protected by an automatic activation system are prominently
                              posted at the entrance to the space.
                     iii)     A switch is provided near the entrance to disable the automatic release feature of the system.
                              The switch is to have an indicator of its status such as red pilot light to indicate when the
                              switch is activated (automatic release feature disabled). A sign is to be posted near the switch
                              indicating that the automatic release feature is to be disabled when the space is occupied
                              and that the automatic actuation is to be enabled when leaving the space. The sign is to
                              also indicate that the manual release of the system remains enabled and the space is to be
                              vacated immediately when the release alarm sounds.
                     iv)      When the automatic release feature is disabled, all other controls, alarms, etc., are to remain
                              activated.
                     v)       An indicator at the control console is provided to indicate when the automatic release
                              feature has been disabled.
                     vi)      The medium release warning alarm is to operate for the length of time needed to evacuate
                              the space, but in no case less than 30 seconds for space exceeding 6000 ft3 (170 m3) and
                              20 seconds for spaces 6000 ft3 (170 m3) or less before the medium is released.
                     vii)     The automatic release of a clean agent fire extinguishing system is to be approved by the
                              vessel’s flag Administration.
          8.7.4      Nozzles
                     The nozzle type, maximum nozzle spacing, maximum height and minimum nozzle pressure are to
                     be within the limits to provide fire extinction as tested and verified in the appropriate fire test (see
                     5-2-3/8.3).
28                                           ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     3     Additional Fixed Fire Fighting Systems                                                             5-2-3
                   a)       The deckhouse top or other similar structures and bulkheads under the helideck are to
                            have no openings,
                   b)       Windows under the helideck are to be provided with steel shutters. Alternatively, windows
                            are to be certified for A-60 applications in accordance with applicable requirements of
                            IMO FTP Code, and the arrangement is to be flag Administration approved.
                   c)       After each fire on the helideck or supporting structure, the helideck is to undergo a
                            structural analysis to determine its suitability for further use.
          A firefighting system as required by 5-2-3/9.3 is to be provided and arranged so as to adequately protect
          both the helicopter deck and helicopter fuel storage areas where provided, see 4-2-6/7 for the fuel storage
          requirements.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                              29
Part           5   Fire and Safety – Measures and Features
Chapter        2   Active Fire Protection Systems and Equipment
Section        3   Additional Fixed Fire Fighting Systems                                                           5-2-3
                    DIFFS performance criteria need to consider several pop-up nozzles rendered ineffective by the
                    impact of a helicopter on the landing area. The number of pop-up nozzles rendered ineffective by
                    a crash situation will depend on the pattern (spacing) of the nozzle arrangement and the type(s) of
                    helicopters operating to the helicopter deck, but not less than 15% of the nozzles installed. The
                    remaining pop-up nozzles are to be capable of delivering finished foam to the landing area at or
                    above the minimum application rate, considering the individual supply pipes to the damaged pop-
                    up nozzles ruptured.
                    DIFFS activation is to be initiated manually. Activation controls are to be located in at least two
                    positions having immediate access to the helicopter landing area and separated as far as practicable.
                    Foam delivery at the minimum application rate is to start within 30 seconds of system activation.
                    The operation of DIFFS is not to interfere with the simultaneous operation of the fire main.
                    Where a DIFFS is used in tandem with a passive fire-retarding system demonstrated to be capable
                    of removing significant quantities of unburned fuel from the surface of the helideck in the event of
                    a fuel spill from a ruptured aircraft tank, it is permitted to select a seawater-only DIFFS to deal
                    with any residual fuel burn. A seawater-only DIFFS, when permitted by the Flag Administration,
                    is to meet the same application rate and duration as specified for a performance level B foam
                    DIFFS in paragraphs 2.10 and 2.11 of CAP 437, as stated in this paragraph and 5-2-3/9.3.4 above.
11.1      Lockers of 4 m2 (43 ft2) or More Floor Area and Lockers with Access to Accommodation
          Spaces
          Paint lockers and flammable liquid lockers of floor area 4 m2 (43 ft2) or more and also such lockers of any
          floor area with access to accommodation spaces are to be provided with one of the fixed fire-extinguishing
          systems specified below:
          i)        CO2 system, designed for 40 % of the gross volume of the space
          ii)       Dry powder system, designed for at least 0.5 kg/m3 (0.03 lb/ft3)
          iii)      Water spraying system, designed for 5 liters/m2/minute (0.12 gpm/ft2). The water spraying system
                    may be connected to the unit’s fire main system, in which case the fire pump capacity is to be
                    sufficient for simultaneous operation of the fire main system as required in 5-2-2/1.1.5 and the water
                    spray system. Precautions are to be taken to prevent the nozzles from being clogged by impurities
                    in the water or corrosion of piping, nozzles, valves and pump.
          iv)       Systems or arrangements other than those referenced above may be also considered, provided they
                    are not less effective.
11.3      Lockers of Less Than 4 m2 (43 ft2) Floor Area Having no Access to Accommodation
          Spaces
          For paint lockers and flammable liquid lockers of floor area less than 4 m2 (43 ft2) having no access to
          accommodation spaces, portable fire extinguisher(s) sized in accordance with 5-2-4/1.1 and which can be
          discharged through a port in the boundary of the lockers may be accepted. The required portable fire
          extinguishers are to be stowed adjacent to the port. Alternatively, a port or hose connection may be provided
          for this purpose to facilitate the use of water from the fire main.
30                                         ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5   Fire and Safety – Measures and Features
Chapter        2   Active Fire Protection Systems and Equipment
Section        3   Additional Fixed Fire Fighting Systems                                                   5-2-3
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                     31
PART     Section 4: Portable Fire Fighting Systems
5
CHAPTER           2      Active Fire Protection Systems and Equipment
1.3    Sand
       On self-propelled units fitted with main or auxiliary oil-fired boilers, each firing space is to be provided
       with a receptacle containing at least 0.28 m3 (10 ft3) of sand, sawdust impregnated with soda or other dry
       material suitable for extinguishing oil fires. Alternatively, an approved portable extinguisher may be substituted
       therefore.
32                                      ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5    Fire and Safety – Measures and Features
Chapter        2    Active Fire Protection Systems and Equipment
Section        4    Portable Fire Fighting Systems                                                                                  5-2-4
          The apparatus is to be suitably located in a sheltered space above main deck level on the unit.
          Intakes for air compressors are to draw from a source of clean air. The air is to be filtered after compression
          to eliminate compressor oil contamination.
          The recharging capacity is to meet the requirements of SOLAS regulation II-2/10.10.2.6.
3.7       Lifeline
          Each breathing apparatus is to have attached to its belt or harness, by means of a snap-hook, a fireproof
          lifeline of sufficient length and strength.
3.13      Helmet
          A rigid helmet is to be supplied which will provide effective protection against impact.
                                                TABLE 1
                   Classification of Portable and Semi-portable Extinguishers (2012)
          Fire extinguishers are designated by types as follows: A, for fires in combustible materials such as wood; B, for
          fires in flammable liquids and greases; C, for fires in electrical equipment.
          Fire extinguishers are designated by size where size II is the smallest and size V is the largest. Size II is a hand
          portable extinguisher, and sizes III, IV, and V are semi-portable extinguishers.
         Classification              Water, liters         Foam, liters      Carbon Dioxide,          Dry Chemical,    Wet Chemical,
      Type               Size       (U.S. gallons)        (U.S. gallons)         kg (lb)                 kg (lb)        liters (U.S.
                                                                                                                          gallons)
        A                 II            9 (2.5)              9 (2.5)                —                   5 (11) (2)        9 (2.5)
        B                 II              —                  9 (2.5)              5 (11)                  5 (11)            —
        B                III              —                  45 (12)             15.8 (35)               9.0 (20)           —
        B                IV               —                  76 (20)             22.5 (50)              22.5 (50)           —
        B                 V               —                 152 (40)            45 (100) (1)           22.5 (50) (1)        —
        C                 II              —                    —                  5 (11)                  5 (11)            —
        C                III              —                    —                 15.8 (35)               9.0 (20)           —
        C                IV               —                    —                 22.5 (50)              13.5 (30)           —
      F or K              II              —                    —                    —                       —             9 (2.5)
          Notes:
                     1          For outside use, double the quantity of agent that must be carried.
                     2          Must be specifically approved as type A, B, or C extinguisher.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                             33
Part           5   Fire and Safety – Measures and Features
Chapter        2   Active Fire Protection Systems and Equipment
Section        4   Portable Fire Fighting Systems                                                                                    5-2-4
                                         TABLE 2
           Hand Portable Fire Extinguishers and Semi-portable Fire-Extinguishing
                                      Systems (2018)
                           Space                         Classification*                     Quantity and Location
     Accommodation Spaces
     Cabins, lavatories, offices, pantries with no
                                                               —            None required.
     cooking appliances, and similar spaces.
     Public spaces                                            A-II          1 for each 250 m2 (2,691 ft2) or fraction thereof
     Stairway and elevator enclosure                           —            None required.
                                                                            Travel distance to an extinguisher not to exceed 25 m
     Corridors                                                A-II
                                                                            (82 ft) within each deck (May be located in stairways)
     Hospital                                                 A-II          1 required.
     Service Spaces
                                                                            1 for each 250 m2 (2,691 ft2) or fraction thereof
                                                              B-II          located in vicinity of exits, either inside or outside
     Galleys                                                                the spaces (see Note 2).
                                                           F-II or K-II     1 additional for galleys with deep fat fryers
     Pantries with cooking appliances and laundry                           1 for each 250 m2 (2,691 ft2) or fraction thereof
                                                           A-II or B-II
     drying rooms                                                           suitable for hazards involved.
     Paint and lamp rooms                                     B-II          1 outside each room in vicinity of exit. (See Note 2)
                                                                            1 for each 250 m2 (2,691 ft2) or fraction thereof
     Lockers and storerooms (deck area of 4 m2 or
                                                              B-II          located in vicinity of exits, either inside or outside
     more)
                                                                            the spaces. (See Note 2)
     Small lockers and storerooms (deck area less
                                                               —            None required.
     than 4 m2)
     Workshops (not part of machinery spaces,
                                                              B-II          1 outside each space in vicinity of an exit. (See Note 2)
     galley) and similar spaces
     Control Stations
                                                                            2 near the exit; 1 only if less than 50 m2 (538 ft2).
     Wheelhouse                                            A-II or C-II
                                                                            (See Note 1)
     Control rooms (other than Wheelhouse)                 A-II or C-II     1 required
     Radio room                                               C-II          1 outside the space in vicinity of exit. (See Note 2)
     Machinery Spaces
     (2018) Central control station for propulsion                          1 required; when main switchboards are arranged in
     machinery/Space containing the controls for the     A-II and/or C-II   central control station, 1 additional suitable for
     main source of electrical power                                        electrical fires
                                                                            2 required in each space, in addition to the required
     Machinery spaces of Category A                           B-II
                                                                            for the machinery contained.
                                                                            2 required in each space (1 at each entrance (see Note
     (2018) Machinery spaces of Category A which
                                                              B-II          3)) in addition to the required for the machinery
     are periodically unattended
                                                                            contained.
     Spaces containing oil-fired boilers, either main
                                                              B-V           1 required in each space.
     or auxiliary, or their fuel units
     Internal combustion engines or gas turbines                            1 for each 750 kW (1000 hp) but not less than 2 nor
                                                              B-II
     with total power output not less than 750 kW                           more than 6 in each space.
     (1000 hp).                                               B-III         1 required in each space.
     Internal combustion engines or gas turbines with                       1 outside the space containing engines or turbines in
                                                              B-II
     total power output less than 750 kW (1000 hp).                         vicinity of exit. (See Note 2)
     Electric generators, propulsion motors, thrusters
                                                              C-II          1 for each motor or generator.
     that do not have enclosed ventilating system.
     Electric generators, propulsion motors, thrusters
                                                               —            None required.
     that have enclosed ventilating systems.
34                                              ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part        5     Fire and Safety – Measures and Features
Chapter     2     Active Fire Protection Systems and Equipment
Section     4     Portable Fire Fighting Systems                                                                                   5-2-4
                                    TABLE 2 (continued)
           Hand Portable Fire Extinguishers and Semi-portable Fire-Extinguishing
                                      Systems (2018)
                          Space                          Classification*                     Quantity and Location
    Machinery Spaces (cont’d)
                                                                            2 required in the vicinity of the switchboards.
    Main switchboards                                         C-II
                                                                            (See Note 2)
                                                                            1 outside the space containing motors or generators
    Electric emergency motors or generators                   C-II
                                                                            in vicinity of exit. (See Note 2)
    Steam driven auxiliary machinery                           —            None required.
    Enclosed space with oil-fired inert gas
                                                              B-II          2 required in each space.
    generators, incinerators and waste disposal units
    Separately enclosed room with fuel oil purifiers           —            None required.
    Workshops forming part of propulsion
                                                          B-II or C-II      1 required in each space.
    machinery spaces and other machinery spaces
    Trunks to machinery spaces                                 —            None required.
    Fuel tanks                                                 —            None required.
    Miscellaneous Areas
    Open decks                                                 —            None required.
    Lifeboat embarkation and lowering stations and
                                                               —            None required.
    external escape routes
    Drill floor                                               C-II          2 required, one at each exit.
    Mud pump room                                             C-II          1 required.
                                                                            1 for each enclosed space (travel distance to an
    Mud pits and mud processing areas                         B-II          extinguisher not to exceed 10 m (33 ft) for open
                                                                            space)
    Cranes with electric motors/hydraulics                     —            None required.
                                                                            2 required, one in cab and one at exterior of engine
    Cranes with internal combustion engines                   B-II
                                                                            compartment in vicinity of exit. (See Note 2)
    Helicopter landing decks                             (See 5-2-3/9.3)
    Helicopter fueling facilities                        (See 5-2-3/9.3)
  Notes:
            1         One of which must be placed inside. If chartroom is adjacent to wheelhouse and with direct access from it, no
                      additional fire extinguisher will be required for the chartroom.
            2         Vicinity is intended to mean within 1 m (3 ft)
            3         (2018) A portable extinguisher provided for that space may be located outside near the entrance to that space. A
                      portable fire extinguisher placed outside near the entrance to that space may also be considered as satisfying the
                      provisions for the space in which it is located.
            *         See 5-2-4/Table 1.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                            35
PART    Section 5: Fire and Gas Detection
5
CHAPTER             2   Active Fire Protection Systems and Equipment
36                                     ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5   Fire and Safety – Measures and Features
Chapter        2   Active Fire Protection Systems and Equipment
Section        5   Fire and Gas Detection                                                                           5-2-5
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                              37
Part           5   Fire and Safety – Measures and Features
Chapter        2   Active Fire Protection Systems and Equipment
Section        5   Fire and Gas Detection                                                                          5-2-5
          The gas detectors are to be connected to an audible and visual alarm system with indicators on the drill
          floor and at the required emergency control stations (See 5-3-1/7). The alarm system is to clearly indicate
          the location and concentration of the gas hazard. The combustible gas detectors are to alarm at not more
          than 25% and at 60% of the lower explosive limit (LEL).
          In addition to the fixed automatic gas detection system, two portable combustible gas detectors are to be
          provided on the unit.
38                                           ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART     Chapter 3: Outfitting
5
CHAPTER           3       Outfitting
                CONTENTS
                SECTION 1            General .................................................................................................. 41
                                     1     Means of Escape .............................................................................. 41
                                     3     Means of Access and Egress ........................................................... 42
                                                3.1        General.......................................................................................... 42
                                                3.3        Means of Escape and Access for Helicopter Decks ...................... 42
                                     5          Guards and Rails .............................................................................. 43
                                                5.1        Floor Deck Areas and Openings ................................................... 43
                                                5.3        Helicopter Landing Deck ............................................................... 43
                                     7          Emergency Control Stations ............................................................. 43
                                     9          Arrangements in Machinery Space ................................................... 43
                                                9.1        Ventilating Fans and Openings ..................................................... 43
                                                9.3        Other Auxiliaries ............................................................................ 44
                                                9.5        Oil Tank Suction Pipes .................................................................. 44
                                                9.7        Oil Fuel Unit................................................................................... 44
                                                9.9        Floor Plating in Machinery Spaces of Category A ......................... 44
                                     11         Segregation of Fuel Oil Purifiers ....................................................... 44
                                     13         Rotary Table Area ............................................................................. 44
                                     15         Fire Precautions for Machinery Spaces ............................................ 45
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                                                 39
     APPENDIX 2 Fiber Reinforced Plastic (FRP) Guard Railings.................................. 49
                1      General .............................................................................................49
                3      FRP Guard Railing Material Systems ...............................................49
                5      Fire Test Requirements ....................................................................49
                                    5.1        Fire Retardance ............................................................................. 49
                                    5.3        Flame Spread ................................................................................ 49
                                    5.5        Self Extinguishing .......................................................................... 50
                          7         Application of FRP Guard Railing .....................................................50
                          9         Other Requirements..........................................................................50
40                               ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART     Section 1: General
5
CHAPTER           3      Outfitting
SECTION 1 General
1.1
        The following requirements are to apply to accommodation spaces, service spaces and control stations:
        1.1.1
                In every general area that is likely to be regularly manned or in which personnel are accommodated,
                at least two separate escape routes are to be provided, situated as far apart as practicable, to allow
                ready means of escape to the open decks and/or embarkation stations. Exceptionally, one means of
                escape may be considered, taking into account the nature and location of spaces and the number of
                persons who might normally be accommodated or employed there.
        1.1.2
                Stairways are to normally be used for means of vertical escape. However, a vertical ladder may be
                used for one of the means of escape from machinery spaces when the installation of a stairway is
                shown to be impracticable.
        1.1.3
                Every escape route should be readily accessible and unobstructed and all exit doors along the route
                are to be readily operable from both sides. Dead-end corridors exceeding 7 m (23 ft) in length are
                not permitted.
        1.1.4   (2012)
                In addition to the emergency lighting, the means of escape in accommodation areas, including
                stairways and exits, are to be marked by lighting or photoluminescent strip indicators placed not more
                than 300 mm above the deck at all points of the escape route, including angles and intersections.
                The marking is to enable personnel to identify the routes of escape and readily identify the escape
                exits. If electric illumination is used, it is to be supplied by the emergency source of power and it
                is to be so arranged that the failure of any single light or cut in a lighting strip will not result in the
                marking being ineffective. Additionally, escape route signs and fire equipment location markings
                are to be of photoluminescent material or marked by lighting. The lighting or photoluminescent
                equipment are to be evaluated, tested and applied in accordance with the International Code for
                Fire Safety Systems (Resolution MSC.98(73)) (FSS Code).
1.3     (2014)
        Two means of escape are to be provided from every machinery space of Category A by either of the following:
        1.3.1
                Two sets of steel ladders as widely separated as practicable leading to doors in the upper part of
                the space similarly separated and from which access is provided to the open deck. One of these
                ladders is to be located within a protected enclosure that satisfies 5-1-1/Tables 1 and 2, category
                (4), from the lower part of the space it serves to a safe position outside the space. Self-closing fire
                doors of the same fire integrity standards are to be fitted in the enclosure. The ladder is to be fixed
                in such a way that heat is not transferred into the enclosure through non-insulated fixing points.
                The enclosure is to have minimum internal dimensions of at least 800 mm by 800 mm, and is to be
                provided with emergency lighting.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                              41
Part            5   Fire and Safety – Measures and Features
Chapter         3   Outfitting
Section         1   General                                                                                         5-3-1
          1.3.2
                     One steel ladder leading to a door in the upper part of the space from which access is provided to
                     the open deck. Additionally, in the lower part of the space and in a position well separated from
                     the ladder referred to, a steel door capable of being operated from each side is to be provided with
                     access to a safe escape route from the lower part of the space to the open deck.
          The minimum width between stringers of the above mentioned ladders, or of any other vertical or inclined
          ladder fitted to provide means of escape within and from machinery spaces, is not be less than 600 mm.
1.5
          From machinery spaces other than those of Category A, escape routes are to be provided having regard to
          the nature and location of the space and whether persons are normally employed in that space.
1.7
          Elevators are not to be considered as forming one of the required means of escape.
1.9
          At least one escape route from the superstructure and deckhouses to the survival craft embarkation area is
          to be protected against radiation effects of a drill floor area fire as far as practicable
1.11      (2012)
          Stairways and corridors used as a means of escape are to be not less than 700 mm (27.6 in.) in clear width
          and are to have a handrail on one side. Stairways and corridors with a clear width of 1800 mm (70.9 in.)
          and over are to have handrails on both sides. Clear width is considered the distance between the handrail
          and the bulkhead on the other side or between the handrails. The angle of inclination of stairways is to be,
          in general, 45°, but not greater than 50°, and in machinery spaces and small spaces not more than 60°.
          Doorways which give access to a stairway are to be of the same size as the stairway.
1.13      (2012)
          All materials that comprise the escape routes and muster stations are to be of steel or equivalent material
          which would not be rendered ineffective by heat. Fiber Reinforced Plastic (FRP) gratings may be considered,
          provided all conditions listed in Appendix 5-3-A1 are fully met and are accepted by the Flag Administration.
3.1       General
          At least two means of escape from the unit are to be provided. They are to consist of fixed stairways or
          fixed ladders constructed of steel and extending from the unit to the surface of the water. In the case of self-
          elevating units, the means of escape will be specially considered. Sufficient personnel landings are to be
          provided on each unit to assure safe access and egress. When, due to special construction, personnel landings
          are not feasible, suitable transfer facilities to provide safe access and egress are to be installed.
42                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5     Fire and Safety – Measures and Features
Chapter        3     Outfitting
Section        1     General                                                                                               5-3-1
          iii)         The firefighting equipment, which includes the hose reel, portable fire extinguishers, fixed foam
                       system, is to provide coverage for the access/egress platforms and stairways. The capacity of the
                       fixed foam system is to be increased to include the additional areas of protection for the aluminum
                       access/egress platforms and stairways.
          iv)          Where the helideck is also used as a firefighting station, the aluminum access/egress platforms and
                       stairways are to meet the L3 fire integrity test, or equivalent as per 5-3-A1/Table 1.
          v)           Where alternative means of fire protection (such as deluge system) are provided (typically along
                       stairways or access under the helideck), and the arrangement and locations of the firefighting
                       equipment, required in 5-3-1/3.2i) above are also available at or cover the access/egress route, the
                       L3 performance test will not be necessary.
          vi)          Where the helideck is fitted with a refueling station, there is to be sufficient distance from the
                       refueling station to at least one of the stairs, such that the aluminum stairs are not impacted by the
                       fire at the refueling station.
          In case of a fire outside the helideck area, access platforms and stairways are not to be considered part of
          an escape route.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                    43
Part           5   Fire and Safety – Measures and Features
Chapter        3   Outfitting
Section        1   General                                                                                            5-3-1
44                                          ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part           5   Fire and Safety – Measures and Features
Chapter        3   Outfitting
Section        1   General                                                                                            5-3-1
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                               45
PART    Appendix 1: Fiber Reinforced Plastic (FRP) Gratings
5
CHAPTER           3      Outfitting
1 General
1.1    (2018)
       FRP gratings may be used in other machinery spaces, cargo areas, and on-deck areas. FRP gratings are not
       accepted in accommodation, service, control spaces, and areas where smoke and toxicity is a concern. The
       floor plating and gratings in Category A machinery spaces is to be made of steel. Refer to 5-3-A1/Table 1.
       FRP gratings are to meet the performance requirements of and are to be tested in accordance with ASTM
       F3059-15, Standard Specification for Fiber-Reinforced Polymer (FRP) Gratings Used in Marine Construction
       and Shipbuilding.
1.3
       Changes in either the type, amount, and/or architecture, of either the reinforcement materials, resin matrix,
       coatings, or manufacturing processes shall require separate testing in accordance with the procedures below.
       Manufacturers should provide evidence, such as enrollment in a follow-up program, that the FRP gratings
       being installed are the same as those which were tested and approved.
3.1
       All fire integrity, flame spread, smoke, and toxicity testing, where required, shall be conducted on each
       material system.
46                                       ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
Part     5        Fire and Safety – Measures and Features
Chapter 3         Outfitting
Appendix 1        Fiber Reinforced Plastic (FRP) Gratings                                                                   5-3-A1
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                                           47
Part     5         Fire and Safety – Measures and Features
Chapter 3          Outfitting
Appendix 1         Fiber Reinforced Plastic (FRP) Gratings                                                                        5-3-A1
                                               TABLE 1 (continued)
                                       Structural Fire Integrity Matrix (2018)
                 Location                                                Service                                         Fire Integrity
 Accommodation, service, and
                                         All personnel walkways, catwalks, ladders, platforms or access areas          Not permitted
 control spaces
 Lifeboat embarkation or temporary
 safe refuge stations in open deck       All personnel walkways, catwalks, ladders, platforms or access areas          L2
 areas
                                         Operational areas and access routes for deck foam firefighting systems
                                                                                                                       L2
                                         on tank vessels
                                         Walkways or areas which may be used for escape, or access for
                                         firefighting systems and AFFF hose reels, emergency operation, or
                                                                                                                       L2
                                         rescue on MODUs and production platforms including safe access to
 Open Decks or semi-enclosed areas       tanker bows
                                         Walkways or areas which may be used for escape, or access for
                                         firefighting, emergency operation or rescue other than those described        L3(5)
                                         above
                                         Personnel walkways, catwalks, ladders, platforms or access areas other
                                                                                                                       L3
                                         than those described above
Notes:
         1           (2018) Machinery spaces of category A is as defined in 4-1-1/3.3 and 5-1-1/3.9.2(6).
         2           If the machinery space does not contain any internal combustion machinery, other oil-burning, oil-heating, or
                     oil-pumping units, fuel oil filling stations, or other potential hydrocarbon fire sources, and has not more than
                     2.5 kg/m2 of combustible storage, gratings of L3 integrity may be used in lieu of L1.
         3           If these spaces are normally entered when underway, gratings of L1 integrity shall be required.
         4           If these spaces are normally entered when underway, gratings of L3 integrity shall be required.
         5           (2018) Vessels fitted with deck foam or dry powder firefighting systems require gratings of L2 integrity for the
                     firefighting system operational areas and access routes.
11.1
         The ABS Surveyor may authorize the use of FRP gratings without Main Office approval in applications
         where structural fire integrity of the FRP gratings is not a concern, provided they meet the applicable flame
         spread and smoke generation requirements set forth in 5-3-A1/5.3 and 5-3-A1/5.5. Applications where the
         use of FRP gratings have been authorized in the past, without any structural fire integrity requirements,
         include the following:
         i)          Sea chest coverings;
         ii)         Small sundeck awnings and supports;
         iii)        Lifeboat bilge flooring;
         iv)         Electrical control flooring;
         v)          Pipe guards on deck, in cargo holds, and in engine rooms;
         vi)         Removable guards over hawse holes, anchor hawse pipes, and scuppers;
         vii)        Personnel barriers, such as protection for electrical panels; and
         viii)       Ship staging and work platforms (Occupational Safety and Health Administration (OSHA)
                     requirements may also apply).
48                                              ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018
PART      Appendix 2: Fiber Reinforced Plastic (FRP) Guard Railings
5
CHAPTER           3      Outfitting
1 General
1.1
        FRP guard railings are not specifically addressed in the individual vessel regulations. However, the resins
        typically used in the manufacture of these guard railings are combustible and heat sensitive; therefore, FRP
        guard railings use must be limited based on the requirements discussed below.
1.3
        These requirements are not intended to eliminate any other design criteria or requirement pertaining to the
        material, construction, or performance of the FRP guard railings in the non-fire condition.
1.5
        FRP guard railings are to comply with:
        i)      Appendix 5-3-A2 of the MODU Rules
        ii)     Flag Administration requirements
        iii)    A published standard from an organization recognized by ABS as being acceptable
3.1
        All flame spread, smoke, and toxicity testing, where required, are to be conducted on each material system.
3.3
        Changes in either the type, amount, and/or architecture, of either the reinforcement materials, resin matrix,
        coatings, or manufacturing processes shall require separate testing in accordance with the procedures below.
        Manufacturers should provide evidence, such as enrollment in a follow-up program, that the FRP guard
        railings being installed are the same as those which were tested and approved.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018                                        49
Part     5     Fire and Safety – Measures and Features
Chapter 3      Outfitting
Appendix 2     Fiber Reinforced Plastic (FRP) Guard Railings                                                      5-3-A2
       5.3.1
                Tested to ASTM E-84 with a flame spread rating not to exceed 20; or
       5.3.2
                Tested to IMO Resolution A.653(16), Recommendation on Improved Fire Test Procedures for Surface
                Flammability of Bulkhead, Ceiling and Deck Finish Materials and meeting the criteria for bulkheads,
                linings, or ceilings.
                                                TABLE 1
                                Application of FRP Guard Railing (2016)
                     Location                                               Service
        Holds/Storages                      Personnel walkways, catwalks, ladders, platforms or access areas,
        Open Decks or semi-enclosed areas   except where used for escape, or access for firefighting, emergency
        not protected by deck foam          operation or rescue
        firefighting system
9 Other Requirements
9.1
       The FRP guard rails are to be fabricated in accordance with a recognized standard, such as ASTM E985,
       with adequate strength to withstand the anticipated loads.
9.3
       The weathering characteristics of the FRP guard rails should be in compliance with a recognized standard
       (for example ASTM D4587, ASTM D4329) for testing resistance to ultraviolet degradation for those exposed
       to weather.
50 ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2018