Schedule of Loads and Computations: General Notes
Schedule of Loads and Computations: General Notes
DISTRIBUTION PANELBOARD " DPA " (GROUND FLOOR) POWER PANELBOARD "PPH"
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH BRANCH BRANCH
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. CKT. VA PER CKT. BREAKER SIZE OF HOMERUN CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT ) NO. CKT. ( WIRES IN CONDUIT )
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C AF P AT AF P AT
3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE 1 LIGHTING OUTLETS 1260 230 100 2 20 1 2760 230 50 2 30
POWER COMPANY SERVICE POINT.
2 LIGHTING OUTLETS 915 20 2 2760 230 50 2 30
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
3 LIGHTING OUTLETS 1070 20 TOTAL 5520 MACB : 50AF, 2P, 250V, 50AT, 10KAIC
5.
4 CEILING FAN OUTLETS 600 20
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND TOTAL CONNECTED LOADS: 4600 VA
INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
5 CEILING FAN OUTLETS 600 20
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE 5520
I L @ 100% D.F. = (1.0) + 0.25 (12) = 27 AMPERES
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 6 CONVENIENCE OUTLETS 1440 20 230
8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE.
7 CONVENIENCE OUTLETS 1440 20
MAIN DISTRIBUTION PANELBOARD "MDP "
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE
ELECTRICAL INSTALLATION SHALL BE USED. 8 REFRIGERATOR 1500 20 BRANCH
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS
10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN 9 SPECIAL PURPOSE OUTLET 3000 30 NO. CKT. ( WIRES IN CONDUIT )
THE PLAN. AF P AT
13 SPARE 1500 20
TOTAL 53235 MACB : 225AF, 2P, 250V, 225AT, 25KAIC
300mm
ENCLOSED CIRCUIT BREAKER
1800mm
WP WP
12 CONVENIENCE OUTLETS 2160 20
M FIN. FLOOR LINE A A
ELECTRIC SERVICE METER
13 3910 40 FIN. GRADE LINE
MH
ELECTRIC SERVICE ENTRANCE 14 SPARE 1500 20 TO "MDP"- 3
15 SPARE 1500 20
GROUNDING SYSTEM 3000mm COPPERCLAD AUTOMATIC CIRCUIT BREAKER
GROUNDING ELECTRODE A 50AF, 2P, 240VOLTS, 30AT
16 SPARE 1500 20 2400mm COPPERCLAD
IN NEMA 3R ENCLOSURE
GROUNDING ELECTRODE
FACP FIRE ALARM CONTROL PANEL TOTAL 22040 MAIN ACB: 225AF, 2P, 125AT, 250V, 18KAIC ELECTRICAL RISER DIAGRAM
NOT TO SCALE
TOTAL CONNECTED LOADS: 22040 VA
(85.70 A / 130 A )