Schedule of Loads and Computations: General Notes
Schedule of Loads and Computations: General Notes
DISTRIBUTION PANELBOARD " DPA " (GROUND FLOOR) POWER PANELBOARD "PPH"
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH BRANCH BRANCH
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. CKT. VA PER CKT. BREAKER SIZE OF HOMERUN CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT ) NO. CKT. ( WIRES IN CONDUIT )
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C AF P AT AF P AT
3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE 1 LIGHTING OUTLETS 1260 230 100 2 20 1 2760 230 50 2 30
POWER COMPANY SERVICE POINT.
2 LIGHTING OUTLETS 840 20 2 2760 230 50 2 30
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
3 LIGHTING OUTLETS 1070 20 TOTAL 5520 MACB : 50AF, 2P, 250V, 50AT, 10KAIC
5.
4 CEILING FAN OUTLETS 900 20
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND TOTAL CONNECTED LOADS: 4600 VA
INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
5 CONVENIENCE OUTLETS 1440 20
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE 5520
I L @ 100% D.F. = (1.0) + 0.25 (12) = 27 AMPERES
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 6 CONVENIENCE OUTLETS 1800 20 230
8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE.
7 COMPUTER OUTLETS 1250 20
MAIN DISTRIBUTION PANELBOARD "MDP "
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE
ELECTRICAL INSTALLATION SHALL BE USED. 8 COMPUTER OUTLETS 1250 20 BRANCH
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS ( WIRES IN CONDUIT )
10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN 9 COMPUTER OUTLETS 1250 20 NO. CKT.
THE PLAN. AF P AT
300mm
3100mm (MIN.) - 5500mm (MAX.)
PB PULLBOX 2 LIGHTING OUTLETS 840 20
ELECTRIC SERVICE
3 LIGHTING OUTLETS 1030 20 METER (CTC METERING)
MAIN DISTRIBUTION PANELBOARD "MDP"- 2 2ND FLOOR
4 LIGHTING OUTLETS 1260 20 "PPH"
60Hz., AC, WATER PUMP MOTOR
DISTRIBUTION PANELBOARD M "DPA" "MDP"
5 LIGHTING OUTLETS 840 20 MANHOLE SIZE
AS REQUIRED
1800mm
M ELECTRIC SERVICE METER WP
WP
6 LIGHTING OUTLETS 1080 20
FIN. FLOOR LINE A A
ELECTRIC SERVICE ENTRANCE 7 CEILING FAN OUTLETS 600 20 FIN. GRADE LINE
MH
8 CEILING FAN OUTLETS 900 20 TO "MDP"- 3
GROUNDING SYSTEM
9 CEILING FAN OUTLETS 600 20
3000mm COPPERCLAD AUTOMATIC CIRCUIT BREAKER
FACP GROUNDING ELECTRODE A 50AF, 2P, 240VOLTS, 30AT
FIRE ALARM CONTROL PANEL 10 CEILING FAN OUTLETS 900 20 2400mm COPPERCLAD
IN NEMA 3R ENCLOSURE
GROUNDING ELECTRODE
11 CONVENIENCE OUTLETS 2160 20 ELECTRICAL RISER DIAGRAM
NOT TO SCALE
12 CONVENIENCE OUTLETS 2160 20
13 3910 40
14 SPARE 1500 20
15 SPARE 1500 20
16 SPARE 1500 20
22040
I L @ 85% D.F. = (0.85) + 0.25 (17) = 85.70 AMPERES
230
(85.70 A / 130 A )