PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Preface
We are required under the Health and Safety at Work Act 1974, to make available to users of this equipment certain information
regarding its safe use.+
The equipment, when used in normal or prescribed applications within the parameters set for its mechanical and electrical performance,
should not cause any danger or hazard to health or safety if normal engineering practices are observed and they are used in accordance
with the instructions supplied.
If, in specific cases, circumstances exist in which a potential hazard may be brought about by careless or improper use, these will be
pointed out and the necessary precautions emphasised.
While we provide the fullest possible user information relating to the proper use of this equipment, if there is any doubt whatsoever about
any aspect, the user should contact the Product Safety Officer at Feedback Instruments Limited, Crowborough.
This equipment should not be used by inexperienced users unless they are under supervision.
We are required by European Directives to indicate on our equipment panels certain areas and warnings that require attention by the
user. These have been indicated in the specified way by yellow labels with black printing, the meaning of any labels that may be fixed to
the instrument are shown below:
PRODUCT IMPROVEMENTS
We maintain a policy of continuous product improvement by incorporating the latest developments and components into our equipment,
even up to the time of dispatch.
All major changes are incorporated into up-dated editions of our manuals and this manual was believed to be correct at the time of
printing. However, some product changes which do not affect the instructional capability of the equipment, may not be included until it is
necessary to incorporate other significant changes.
COMPONENT REPLACEMENT
Where components are of a ‘Safety Critical’ nature, i.e. all components involved with the supply or carrying of voltages at supply
potential or higher, these must be replaced with components of equal international safety approval in order to maintain full equipment
safety.
In order to maintain compliance with international directives, all replacement components should be identical to those originally supplied.
Any component may be ordered direct from Feedback or its agents by quoting the following information:
38-001-3 i
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Preface
OPERATING CONDITIONS
WARNING:
This equipment must not be used in conditions of condensing humidity.
This equipment, when operated in accordance with the supplied documentation, does not cause electromagnetic disturbance outside its
immediate electromagnetic environment.
COPYRIGHT NOTICE
© Feedback Instruments Limited
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any
means, electronic, mechanical, photocopying, recording or otherwise, without the prior permission of Feedback Instruments Limited.
ACKNOWLEDGEMENTS
Feedback Instruments Ltd acknowledge all trademarks.
MICROSOFT, WINDOWS XP, WINDOWS 2000, WINDOWS ME, WINDOWS 98, Internet Explorer are registered trademarks of
Microsoft Corporation.
ii 38-001-3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Foreword
Foreword
This manual provides in Chapters 1 and 2 details of trainer installation and relevant
setting-up procedures.
Note:
Assignments for all three trainers, 38-001, 38-002 and 38-003,
are provided in manual 38-901-M PROCON Process Control
Trainer Level, Flow & Temperature.
38-001-3 iii
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Foreword
Notes
iv 38-001-3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Contents
TABLE OF CONTENTS
3 Assignments 3-1
38-001-3 TOC-1
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Contents
38-001-3 TOC-3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Contents
Notes
TOC-4 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
1.1 Introduction
This chapter describes how to install and configure the hardware for the Level/Flow
(38-001), Temperature (38-002) or Level/Flow & Temperature (38-003) Process Control
Trainers. Instructions describing how to install the software can be found on the software
distribution CD 38-901-M. For general information on how to install the software, refer to
Feedback Manual – IMS Compatible Content, Installation and User Guide 93-IMS.
This product uses a Serial interface to allow the Computer to control and interrogate single
or multiple Process Controllers (38-300). The hardware should be connected to the
workstation computer as described below.
Use the multiway cable terminated in a 25-way ‘D’ type connector, supplied with the
accessories, to connect from the RS232 socket on the rear of the 38-300 to the PC Serial
port ‘COM1‘ or ‘COM2’. Note that a 25-way connection is required at the PC. Set the
‘connection’ switch to ‘on’ and the ‘termination’ switch to ‘on’. The serial page parameters
must be set up correctly using the manual setting method before reliable computer control
can be established.
Particular attention should be paid to the setting up of the controller identity. When a single
controller is in use the Modbus Address should be set to ‘1’. See the section on Serial
Controller Parameters at the end of this chapter for details.
Use the multiway cable terminated in a 25-way ‘D’ type connector to connect to the RS232
socket on the rear of the 38-300 to the PC Serial port ‘COM1’ or ‘COM2’. Note that a 25-
way connection is required at the PC. Set the 38-300 ‘connection’ switch to ‘on’ and the
‘termination’ switch to ‘off’.
The RS485 serial cable should then be used to connect between the RS485 connection on
the rear of the first controller to the RS485 connection on the rear of the second controller.
The ‘connection‘ switch on the second controller should be set to ‘off’ and the ‘termination’
switch should be set to ‘on’.
Figure 1-1 shows clearly the connections to be made and the required switch positions.
38-001-3 1-1
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Again, particular attention should be paid to the setting up of the controller identities. The
identity of the Process Controller 1 should be set to ‘1’. The Modbus Address of Process
Controller 2 should be set to ‘2’. Successful communications cannot take place unless
these addresses are correctly set. See the section on Serial Controller Parameters at the
end of this chapter for further details.
IMPORTANT:
Remove the fixing screws from the case of the Process Controller and lift-off
the cover. Position the controller so that the inside-rear of the case can be
clearly seen. A circuit board will be seen on the right hand-side. This board
contains a set of jumpers labelled ‘GEN’. It is these jumpers that determine
the RS232 transmission characteristics.
These jumpers are factory set across JP6 and JP7. They should be carefully
moved to connect across JP5 and JP8. The diagram below shows the
jumper settings before and after adjustment.
1-2 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
The following sections describe simple installation tests which can be applied to the
various items in the Feedback 38-001 to 003 PROCON range of equipment. Omit items
not applicable to the options you have chosen.
Unpack the relevant items and proceed with the installation tests as follows:
Close the system drain valve and fill the sump at least three-quarters full with clean
distilled water.
IMPORTANT
If possible, distilled water should always be used with the Process Rigs to avoid
build-up of algae within the system. Boiled water can be used as a satisfactory
substitute if distilled water is not available. Using normal tap water will not
damage the system, but will slightly increase the level of maintenance required.
38-001-3 1-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Make sure the power is switched off at the main supply and connect the equipment as
shown in Figure 1-3.
Set up the Float Level Sensor, from the Level Sensor Pack 38-400, as described below.
Set the manual drain valve to about half open and all other manual valves open (except
the system drain valve).
Switch on the power and then the pump. Press the ‘Auto/Manual’ switch once if the
manual control LED (M) is lit. After a few minutes the system should settle with about 50%
level in the process tank. The Process Controller lower display should show about ‘30’.
The actual value will depend very much on the exact setting of the manual drain valve.
IMPORTANT
The pump should not be run without water. The rotor bearings use water lubrication
and will be permanently damaged without it.
Observe that the float in the visual flowmeter is indicating the flow-rate. Also observe that
the digital display is indicating the output from the pulse flow transmitter, if fitted.
Introduce a step function by switching on the extra drain valve (SV2). Observe the change
in the flow-rate indicators.
Check that the other solenoid valves function correctly by moving the connection on the
side of the rig to energise them in turn. Note that the two drain solenoid valves have
different flow rates.
Close the manual bypass valve, MV2, and check that the flow can be stopped and started
using SV1.
1-4 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Figure 1-3: Basic Process Rig Test Connections
38-001-3 1-5
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Notes:
1. 38-490 Digital Display Module can be fitted in-line with any of the signal cables which
have a 7-pin DIN connection. It can, for example, be used to monitor float level, pulse
flow or valve control signals.
2. The controller remembers its previous settings at power on. Factory settings are to
operate level control with P + I terms (no derivative). After the equipment is correctly
set up, all that should be necessary is to switch the power on.
3. There are many control settings which can be altered but not all are relevant to this set
up.
For stable control only Proportional + Integral terms are required, with:
Proportional This gives a full swing in o/p from the controller for only a
band = 10% 10% change in the error.
To increase prop. gain, prop. band must be reduced.
5 The 38-421 is not used for control in this set-up, it is included only for test purposes.
6 BARGRAPH
This is a visual indication of the error. The green bar only = no error. Each red bar
represents 5% error, positive or negative.
8 The controller is switched between auto/manual modes with the front panel button,
status is shown by the M LED, on = manual. The control will not function if this is on.
1-6 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
There are two adjustments which are required, potentiometer position with reference to.
pulley and electrical span/zero adjustment. The pot/pulley position must be set first.
1 Fold the cord in half and secure the loop around the large plastic rivet see Figure
1-4. Wrap the cord twice around the pulley and check that the cord is not wound over
itself and that the pulley turns freely.
2 Attach the level sensor to the Process Tank and make the electrical connections as
shown in Figure 1-3, but temporarily connect the output signal from the Float Level
Transmitter (38-401) to the Digital Display Module (38-490) then switch the power on.
Do not run the pump so that the Process tank remains empty.
4 If the sensor is correctly set-up there will be a reading of 3.8 to 4.0 mA with the float
level with the ‘zero’ marked on the front of the tank. If adjustment is needed,
continue, if not go to 7.
38-001-3 1-7
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
5 Using a small screwdriver adjust ‘zero’ on 38-401, until the above reading is
obtained, if satisfactory then go to 7, if not continue.
6 Disconnect the potentiometer sensor input plug and set the ‘zero’ adjuster on the 38-
401 to give a reading of 4.0 mA. Re-connect the input plug then, with the float at the
minimum level, hold the pulley still with one hand and using a screwdriver, turn the
potentiometer shaft anticlockwise until the reading can be seen to progress from a
high value, down to approximately 4.0 mA. This method avoids the possibility of error
which might occur if the potentiometer wiper is set off the end of its resistive track.
Now repeat 5.
7 Raise the float up to the ‘100’ level on the tank and adjust span on 38-401 for a
reading of between 19 to 21 mA.
8 Set-up is now complete so re-connect the units as per Figure 4-6. The 38-300
displays its measured variable (large upper display) as a percentage, 0% indicates
an empty tank and 100% a full tank. The float sensor is only used in the practicals to
take readings in the region between the maximum and minimum marks. This is due
to the inaccuracies introduced by the proximity of inflow and outflow disturbances.
Note that a similar procedure could be used to calibrate different levels to 0 and 100%.
The 38-100 Basic Process Rig and 38-600 Temperature Process Rig are both equipped
with an Optical Pulse Flowmeter. The output of this device is a pulsed signal whose
‘frequency’ alters in proportion to the rate of liquid flow past its rotating impeller. The output
signal is fed into the Pulse Flow Transmitter which converts the pulses into a 4 mA to 20
mA standard control format.
A zero flow condition should produce a 4 mA output from the Pulse Flow Transmitter; a
maximum flow condition should produce a 20 mA output.
The Pulse Flow Transmitter can be calibrated by following the steps below:
1 Connect the transducer, Pulse Flow Transmitter and Digital Display Module as shown
in Figure 1-3.
2 Ensure that the pump is switched off. There should be zero flow.
3 Adjust the ‘zero’ control on the PFT until the DDM reads 4 mA. This represents zero
flow.
1-8 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
6 Adjust the ‘span’ control on the PFT until the DDM reads 20 mA. This represents
maximum flow.
The Optical Pulse Flowmeter supplied as part of the Temperature Process Rig and Basic
Process Rig may need occasional cleaning to remove scale from the internal LED detector
mechanism. If a deterioration in performance is noted, the following cleaning procedure
should be followed:
4 Using a small screwdriver gently remove the impeller from inside the case.
If poor performance is still apparent after cleaning, see the later section entitled ‘Controller
Input Filter’ for further measures.
38-001-3 1-9
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
The Temperature Rig has two isolated water circuits. The primary circuit, which is normally
used as a heat source, comprises; a heater, a circulation pump, a servo-valve for flow
control, a pulse flowmeter, a header tank and a heat exchanger. The secondary circuit
contains a heat exchanger and a cooler.
The primary circuit is self contained and has to be filled before the system is used. The
secondary circuit is normally supplied, via flexible hoses, from the Basic Control Rig which
is set up to provide a controlled flow. An alternative arrangement is to use a Temperature
Auxiliary Control Pack 38-480 to provide a controlled flow from a mains water tap.
Warning:
This Rig has many pipes and surfaces which will
reach temperatures of up to 70°C.
1-10 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Figure 1-5: Temperature Process Rig Test Connections
38-001-3 1-11
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Check that both switches on the Process Interface are UP, the pump speed setting (on the
pump body) is at (2) and the appropriate manual valves are open.
Switch on the Process Interface and Controller and fill the temperature rig as described
below.
Important:
The Pump and Heater must not be run without
water in the primary circuit.
2 Fully open the servo valve by setting the controller to manual and entering op=100.
(Refer to the notes below and the Operating Instructions for COMMANDER 350 if
you do not know how to do this).
4 Remove the header tank cover and start to fill the system with clean distilled water, if
available. The use of distilled water in the system reduces fungal build-up. Switch on
the pump to clear the initial air-locks.
Important:
The header tank should not be filled beyond the maximum level
marked. If extra water is added whilst the rig is at ambient room
temperature overflow will occur during the heating process.
NOTE If the pump appears not to work, it may be necessary to free the shaft. This is
carried out by removing the vent plug and inserting a small screwdriver (3 mm)
into the end of the shaft, pushing gently and rotating the shaft several times to
ensure it is free. This is particularly important for pumps which have not been
used for some time.
5 Continue to introduce clean water until the header tank remains at the ‘max level’
mark. Switch off the pump, wait for 1 minute, then open 'air bleed 1' to release any
trapped air.
1-12 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
6 Switch on the pump and repeat step 5 until no air escapes when 'air bleed 1' is
opened.
Once this procedure has been completed the water flow in the primary circuit should be
‘solid’ and free of air. A good indication of flow quality can be obtained from the flow
transducer. A steady reading on the DDM is usually produced by a flow free of air. If any
air remains in the system, a further procedure can be attempted.
2 Run the pump and release air from the system with ‘air bleed 1’ valve until flow
begins. This can usually be heard.
4 Open the manual valve in stages; after each stage run the pump and add extra
water as required.
5 Repeat the process until all air has been removed from the system.
Switch on the heater. Approximately 10 minutes is required for water in the primary flow
circuit to reach maximum temperature. This is limited by a thermostat to 70°C.
The primary circuit pump is capable of pressurising the system to a pressure of 11 bar,
however the maximum working pressure for the secondary flow is 5 bar. This is equivalent
to approximately 70 psi.
38-001-3 1-13
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
With this flow control loop the ‘process’ to be controlled is in fact the valve itself,
which we can explain as follows:
The transfer function relating valve position to flow is straightforward. Since the pump
provides a continuous pressure differential across the valve, flow is simply
proportional to valve position.
However when the controller output signal changes suddenly there is a delay before
the valve reaches its new position which is due both to motor inertia and the high
gear ratio used (it takes a few seconds to fully open or close the valve). So in fact it is
the valve transfer function which dominates the ‘process’.
For this installation example control parameters are chosen to give little or no
overshoot in response to sudden changes in flow demand.
The set point should always be in the range 5 - 95%. This is a note to remember for
other practicals, the control will be non-linear and may be unpredictable if the
measured variable reaches its high or low limit. Adjust the setpoint using the [up] and
[down] buttons
3 SECURITY CODE
There are security codes that restrict access to different sets of parameters. They
should not be set, unless you wish access to the controller to be restricted.
4 BARGRAPH
This is a visual indication of the error. Green bar only = no error. Each red bar
represents 5% error, positive or negative.
5 To get back to the standard display from anywhere press [alarm acknowledge]
then [parameter advance] .
6 The controller is switched between auto/manual modes with the front panel button,
status is shown by the M LED, on = manual. The control will not function if this is on.
1-14 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Check that the following parameters are set. Refer to the Operating Instructions given in
the COMMANDER 350 Process Controller manual.
Observe that the rate of flow is controlled and will change when the setpoint is adjusted.
Water for the secondary flow circuit may be obtained from the Basic Process Rig 38-100,
which should be located on the bench to the right of the Temperature Process Rig. Make
sure the Basic Rig pump is switched off and the water is all drained down into the sump.
Remove the double elbow link on the left hand side, making sure to pull it evenly and
keeping the locking rings in with your thumb and fore-finger.
Use the short lengths of plastic hose provided to connect the flow output (lower pipe) to
the heat exchanger input and the return input (upper pipe) to the cooler output. The plastic
pipes have push fit terminations which can be removed as described above. You may also
need to use the adaptors provided to adjust for pipe diameter.
When the connections are made switch on the Basic rig pump and adjust the flow to
approximately 2 litres/min.
Secure the 38-480 in the place marked on the rig. Connect the drain pipe onto the pipe
leaving the cooling radiator and the supply pipe to the input of the 38-480. Attach the
supply pipe to a mains water supply which can deliver at least 4 litres/minute. The mains
water supply should have a pressure of nominally 1.5 bar, with a maximum of 2 bar. If your
mains supply is of greater pressure, a pressure reducer must be used to bring it to the 1.5
bar nominal value. Such a reducer is available from Feedback, with details on request.
38-001-3 1-15
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Water for the secondary is obtained from this supply; ensure the servo valve is fully open
by setting the controller to manual and entering op=100, now turn on the mains water
supply and set the flow to 25% using the manual valve located on the 38-480.
Switch the Thermistor Temperature Transmitter 38-441 to sensor A. Press the 25°C
calibrate button and adjust ‘zero’ to give a ‘25’ display on the 38-490.
Press 80°C calibrate button and adjust ‘span’ to give an ‘80’ display on 38-441.
The Temperature Process Rig is normally supplied with the five temperature sensing
thermistors fitted. The thermistor units are fragile and should not be removed unless
absolutely necessary. The Thermistor Temperature Transmitter 38-441 is designed to
accept inputs from two thermistors and a switch is provided to select the required one.
Check the various components are functioning by making the following temperature
comparisons:
1 T2 should be less than T1; Heat being transferred from Primary to Secondary.
2 T3 should be less than T4; Cold water being heated in the Heat Exchanger.
3 T5 should be less than T4; Heated water being cooled before returning.
Completing these tests will check that the main components are all functioning.
Dual loop control is concerned with the final assignment and can only be carried out if a
full set of Level / Flow (38-100) and Temperature (38-600) hardware is available
(Workstation 38-003). The two rigs should be connected together as described previously.
Manually set the Basic Process Rig controller to ‘ident 1’ and the Temperature Process
Rig controller to ‘ident 2’ (see below). You will need the RS485 lead from the PROCON
accessories to physically connect the two controllers together. Connect one end of the
cable to the RS485 connection on one of the controllers and the other to the RS485
connection on the other controller. On the Basic Process Rig controller, which should have
1-16 38-001-3
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
the RS232 connection to the computer in place, set the ‘connection’ switch to ON and the’
termination’ switch to OFF. On the Temperature Process Rig controller set the ‘connection’
switch to OFF and the ‘termination’ switch to ON.
Please refer to the earlier section for more detailed information regarding connection of
two controllers.
The controller serial page must be set up as shown to allow communication with the
Discovery Software. Refer to the Operating Instructions given in the COMMANDER 350
User Guide, Page 67.
The settings should be:
Serial Config 4
Parity None
Modbus Addresses
Single 38-300 1
Second 38-300 2
The Process Controller incorporates the facility to filter the process variable input. This
function is intended for use as a ‘smoothing’ stage for stepped input signals. It may also be
more usefully used in this case to clean ‘noisy’ signals to a certain degree.
The output from the pulse flow sensor can in some cases be extremely noisy. This is not a
fault with the hardware, rather a characteristic of the flow detector type. This noise can
sometimes be amplified to an unacceptable degree if presented to the Process Controller
in a high-gain state.
The Programmable Filter can be set by accessing Level 9. The parameter FLt.1 (Input
Filter Time Constant) should be accessed and set.
The filter time represents the time a step in the input takes to change the displayed
process variable from 10 to 90% of the step. The time can be set between 0 to 60 seconds
in 1 second increments.
38-001-3 1-17
Chapter 1
PROCON REFERENCE MANUAL Installing 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
When both the hardware and the software installation has been completed, you can then
start the stand alone environment by double-clicking on the Discovery icon that the
environment installation program created on your computers desktop.
1-18 38-001-3
Chapter 2
PROCON REFERENCE MANUAL Using the 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
The software package for the ‘Level and Flow’ can be accessed by double-clicking the
‘Process Control’ top-level menu, followed by ‘PROCON Process Control Trainers’. Here,
software can be initiated for a number of assignments that contains Theory, Background
and practical information.
When a practical starts, you will be presented with the warning message. This is to remind
you that problems may arise if the Controller is turned off while your PC is preparing to
receive data.
When the practical has started, the Controller automatically configures the process rig,
allowing particular components of the rig to be studied.
If you begin a practical before the Controller has been turned on, an error message is
displayed:
If this occurs, you should exit the practical page by changing to a non-practical page (such
as background, theory or question pages). When on pages other than a practical page,
turn the Controller on and reselect the required practical. This will re-initialise the
Controller.
Note:
Always remember to wait a moment before selecting the practical after turning on
the power to the Controller. The computer needs time to initialise the Controller so
that its interface can be configured.
Do not overload the system by trying to open one practical before the last practical has
finished. Although protection has been built into the software to prevent problems arising,
the hardware may become confused, causing problems with the running of the software.
Always ensure that other applications that may be running simultaneously, such as word
processors or e-mail packages are closed. The Level and Flow software has been
designed as ‘real-time’ as possible. Other applications may interfere the with displaying of
signals from the process rig. Similarly, ensure that no other copies of the Internet Explorer
browser program are running.
When you have to change process rigs, you should exit a practical to a non-practical page,
such as the background or theory pages, then power down.
38-001-3 2-1
Chapter 2
PROCON REFERENCE MANUAL Using the 38-001 to 003
LEVEL, FLOW & TEMPERATURE Process Control Trainers
Although powering down during the operation of a practical will not usually cause
difficulties, your computer may be left waiting for data from the Controller.
Note:
Always ensure that you leave a practical page before you power down the Controller
when you change process rigs.
The software performs checks before a process rig is configured. If an incorrect process
rig is connected, an error message is displayed.
When this occurs, leave the current practical page by selecting non-practical page, power
down the Controller, select plug in the required process rig, power up the Controller and
select your required practical.
2-2 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
3 Assignments
3.1 Introduction
The Procon 38 Series Process Control Trainer is a complete package dealing with all
aspects of Process Control, and includes many industry standard features. It includes the
relevant hardware process control rigs, monitoring and interface devices, and an industry
standard controller. With a high degree of modularity, the system is very flexible and many
different methods of process control can be demonstrated.
Operating the hardware with the software package provides a series of practical
assignments which demonstrate each type of process control, and allow the student to
explore the strengths and weaknesses of a particular type. The software package also
provides theory, objectives and questions relating to each practical to increase the breadth
of the subject covered. The hardware will operate under the automatic control of the PC
running the software, with the exact nature of operation controlled by the student.
This chapter describes in section 3.1 the Procon Level/Flow and Temperature Process
Control systems which introduce all aspects of modern industrial control, and allow
different control algorithms to be constructed. Additionally, this chapter provides details of
assignment contents (section 3.2) and assignment answers (section 3.3).
• One 38-100 Basic Level/Flow Process Rig consisting of a self contained pumped
water circuit and associated solenoid, manual and servo valves.
• One 38-200 Process Interface providing all necessary power outlets for the Basic
Level/Flow Process Rig and its sensors.
• One 38-300 Industry Standard Process Controller which can provide a range of
control functions.
• One 38-400 Level Sensor Pack comprising a Float Level Transmitter 38-401, a
Float Level Sensor and a Float Switch.
• One 38-420 Flow Sensor Pack comprising a Pulse Flow Transmitter 38-421 and
Sensor.
• One 38-490 Digital Display Module displaying signal current or signal percentage.
38-001-3 3-1
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
• One 38-901-M Software Pack for Level/Flow and Temperature (includes 38-801
RS485 Serial Cable).
• One 38-600 Basic Temperature Process Rig with a self contained pumped and
electrically heated water circuit and a second cold water process circuit
• One 38-200 Process Interface providing all necessary power outlets for the Basic
Level/Flow Process Rig and its sensors
• One 38-300 Industry Standard Process Controller which can provide a range of
control functions
• One 38-490 Digital Display Module displaying signal current or signal percentage
• One 38-901-M Software Pack for Level/Flow and Temperature (includes 38-801
RS485 Serial Cable).
• One 38-100 Basic Level/Flow Process Rig consisting of a self contained pumped
water circuit and associated solenoid, manual and servo valves
• Two 38-200 Process Interfaces providing all necessary power outlets for the Basic
Level/Flow Process Rig and its sensors
• Two 38-300 Industry Standard Process Controllers which can provide a range of
control functions
3-2 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
• One 38-400 Level Sensor Pack comprising a Float Level Transmitter 38-401, a
Float Level Sensor and a Float Switch
• Two 38-420 Flow Sensor Pack comprising a Pulse Flow Transmitter 38-421 and
Sensor
• Two 38-490 Digital Display Module displaying signal current or signal percentage
• One 38-600 Basic Temperature Process Rig with a self contained pumped and
electrically heated water circuit and a second cold water process circuit
• One 38-901-M Software Pack for Level/Flow and Temperature (includes 38-801
RS485 Serial Cable).
38-001-3 3-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Introduction to Procon
Flow/Level Rig Familiarisation
Flow/Level Rig Calibration
Interface Familiarisation
Interface Calibration
Controller Familiarisation
Controller Calibration
Float Level Transmitter
Pulse Flow Transmitter
On/Off Level Control
Proportional Control: Level
Proportional Control: Flow
PI & PID: Level Control
PI & PID: Flow Control
Tuning PID Controllers
Process Controller: Advanced Features
Temperature Rig Initialisation
Temperature Rig Familiarisation
Manual Flow Control
Temperature Process Control
P, PI and PID Temperature Control
Complex Control Loops
Required hardware is the Basic Level/Flow Process Rig 38-100, the Process Interface
38-200, a Digital dc milliammeter (0 – 20 mA) and a Tape Measure
3-4 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Practicals
Required hardware is the Basic Level/Flow Process Rig 38-100, the Process Interface
38-200, the Digital Display Module 38-490 and a Tape Measure.
Practicals
Required hardware is the Basic Level/Flow Process Rig 38-100, the Process Interface
38-200, the Digital Display Module 38-490 and a dc Voltmeter (0- 2 V).
Practicals
38-001-3 3-5
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Required hardware is the Basic Level/Flow Process Rig 38-100, the Process Interface
38-200, and the Digital Display Module 38-490. This assignment contains only one
practical, but it does discuss other areas of the Process Interface that are used in later
assignments.
Practicals
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, and the Digital Display Module 38-490
Practicals
1 Serial Communication
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, and the Digital Display Module 38-490.
Practicals
1 38-300 Calibration
2 38-300 Relays
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Float Level Transmitter 38-401, the Float Level
Sensor, and the Digital Display Module 38-490.
3-6 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Practicals
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Pulse Flow Transmitter 38-421, the Pulse Flow
Sensor and the Digital Display Module 38-490.
Practicals
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Float Level Transmitter 38-401, the Float Level
Sensor, the Float Level Switch, and the Digital Display Module 38-490.
Practical
38-001-3 3-7
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Float Level Transmitter 38-401, the Float Level
Sensor, and the Digital Display Module 38-490.
Practicals
1 Simulation
4 Proportional Band
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Pulse Flow Transmitter 38-421, the Pulse Flow
Sensor and the Digital Display Module 38-490.
Practical
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Float Level Transmitter 38-401, the Float Level
Sensor, and the Digital Display Module 38-490.
Practicals
1 PI Control of Level
2 Limitations of PI Control
3-8 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Pulse Flow Transmitter 38-421, the Pulse Flow
Sensor and the Digital Display Module 38-490.
Practicals
1 PI Control of Flow
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Float Level Transmitter 38-401, the Float Level
Sensor, and the Digital Display Module 38-490.
Practicals
1 Zeigler-Nichols Tuning
2 Self-Tuning
Required hardware is the Process Controller 38-300, the Basic Level/Flow Process Rig
38-100, the Process Interface 38-200, the Float Level Transmitter 38-401, the Float Level
Sensor, and the Digital Display Module 38-490.
Practicals
2 Profile Programming
38-001-3 3-9
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Required hardware is the Process Controller 38-300, the Temperature Process Rig 38-
600, the Process Interface 38-200, the Thermistor Temperature Transmitter 38-441, and
the Digital Display Module 38-490. The Basic Level/Flow Process Rig 38-100 is optional
for the completion of the assignment.
Practicals
2 Thermistors
Required hardware is the Process Controller 38-300, the Temperature Process Rig 38-
600, the Process Interface 38-200, the Thermistor Temperature Transmitter 38-441, and
the Digital Display Module 38-490. The Basic Level/Flow Process Rig 38-100 is optional
for the completion of the assignment.
Required hardware is the Temperature Process Rig 38-600, the Process Interface 38-200,
the Thermistor Temperature Transmitter 38-441, and the Digital Display Module 38-490.
The Basic Level/Flow Process Rig 38-100 is optional for the completion of the assignment.
Practicals
1 Simulation
3-10 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Required hardware is the Process Controller 38-300, the Temperature Process Rig 38-
600, the Process Interface 38-200, the Thermistor Temperature Transmitter 38-441, and
the Digital Display Module 38-490. The Basic Level/Flow Process Rig 38-100 is optional
for the completion of the assignment..
Practicals
Required hardware is the Process Controller 38-300, the Temperature Process Rig 38-
600, the Process Interface 38-200, the Thermistor Temperature Transmitter 38-441, and
the Digital Display Module 38-490. The Basic Level/Flow Process Rig 38-100 is optional
for the completion of the assignment.
Practicals
2 PI Control of Temperature
Required hardware is two Process Controllers 38-300, the Basic Level/Flow Process Rig
38-100, the Temperature Process Rig 38-600, two Process Interfaces 38-200, the
Thermistor Temperature Transmitter 38-441, two Digital Display Modules 38-490, the Float
Level Transmitter 38-401, the Float Level Sensor and the Pulse Flow Sensor.
Practicals
38-001-3 3-11
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Note:
These are not necessarily definitive answers to the questions in
38-901-M, but are rather guide lines covering the main points that
should be included in a student’s solution.
1 What are the special features and principle of operation of the centrifugal pump?
Explain how the pump is used in this practical. What is the purpose of the overflow
pipe?
2 If initially the upper tank is empty, how long does it take from the time you switch on
the pump, until overflow occurs? What is the volume of the water at overflow? Hence,
calculate the rate of flow.
3 Why is the flow through the piping network less than the full flow capability of the
pump?
1 What is process control and how does it differ from servo control? How do you think
the Basic Process Rig fits into process control? What instruments are used in a
process control system? What are the characteristics of those instruments, that are
of interest to a control engineer?
3-12 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
2 What are the principles of operation of the manual valve and the visual flowmeter?
How would you classify these instruments from a control engineering point of view?
Manual valves cut off flow and are controlled by the user. Visual flow meter is
displacement type and gives approximate flow. Both are passive instruments, not
applicable to automatic control.
3 Visualise the process control system of Practical 2 and sketch a block diagram of it,
identifying each element. Is this control system manual or automatic? Is it an open
loop or a closed loop system?
1 What is the principle of operation and the physical structure of the servo valve? Why
is it called a servo valve? How is the servo valve controlled and what is its response?
Servo valve is a gate lowered and raised on demand. 100% open to 100% closed. It
is a servo system where output (position) follows input (current). Controlled by the 4-
20 mA current signal produced by the Process Controller and response is
approximately linear.
38-001-3 3-13
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
2 Compare the servo valve with the manual valve, listing similarities, differences,
advantages and disadvantages?
Both control flow, but servo allows automatic control. Manual is simple, but its
position is approximate. Servo position is totally variable and can be known precisely.
3 What should you not forget to do before switching off the servo valve, so that no
future practical is affected by the state of the servo valve?
1 Describe the physical structure and principle of operation of the solenoid valve. What
is the normal state of the solenoid valve?
Solenoid is on/off binary device, with electrical solenoid coil that opens when current
is passed through it. Normal state is closed.
2 Compare the solenoid valve with the servo valve, listing the advantages,
disadvantages and control applications.
Solenoid is binary, only two positions, simple, well suited to on/off control.
3 What is the significance of the valve size in process control? Having repeated
Practical 4 using SV3 in place of the SV2, what do you deduce about the size of
SV3?
Valve size controls maximum flow (and so proportion of maximum flow). SV3 is
smaller than SV2
4 The two solenoid valves SV1 and SV2 used in the practical are the same size. Why
then, when both valves are open, does the water level in the upper tank not remain
constant at an intermediate level, and adjustments to the manual valve MV1 are
necessary to keep the input and output flows equal?
3-14 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 Define the term 'calibration'. Why is calibration important? List the calibration
procedures applicable to measurement instruments. How is calibration affected?
2 What kind of human errors are important when measuring dimensions and what rules
should be followed in order to avoid them?
Random errors are removed by averaging. Systematic errors are avoided by careful
operation of measuring devices (parallax error).
3 What is the length and width of the upper right hand tank? What is the mathematical
expression relating volume and level for this part of the tank? What is the expression
for the whole tank?
length 180 mm, width 110 mm, area 19800 mm2 (19.8 cm2). Volume = area x level
(or depth) so...
Volume = 19.8 x level. Area will be larger for the whole tank.
4 Compare the two expressions. What is the significance of the level to volume
correspondence?
Volume can be calculated very quickly. Obvious how the volume will be greater in a
large tank at the same level as that in a smaller tank.
1 What are the two main types of measurement error? What are the sources of these
errors? How can these errors be reduced to a minimum?
38-001-3 3-15
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
2 How is flow measurement performed in this experiment and what factors should be
considered? Why do you have to take the average value of the flow rates
measured? (Relate this to question one). Can you now appreciate the level to
volume correspondence?
3 How is the calibration of the variable area flow meter performed? How inaccurate is
the flow meter and what is its resolution?
1 Why are measurement errors impossible to eliminate? How are signal processing
techniques used to improve the quality of the measurement signal? Give some
examples.
2 What are the differences between analogue and digital signal processing? What are
the advantages and disadvantages of Digital Signal Processing (DSP) over analogue
signal processing?
Analogue is simple and straight forward, digital is complex but is very accurate, digital
requires slightly longer processing time and will also involve analogue to digital (A/D)
conversion.
3 Plot the graph of flow rate against current. Is the graph linear or non-linear? Why
should the graph be linear?
3-16 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 What is the significance of the valve size in process control? Having repeated
Practical 4 using SV3 in place of the SV2, what do you deduce about the size of
SV3?
The size of the solenoid valve is controlling the flow through that valve. SV3 is
smaller than SV2.
2 Having calculated the size coefficients of SV2 and SV3, compare them to the
manufacturer's figures reproduced below. How do they compare?
Manufacturer’s figures for the valves: SV2 6 mm hole size and flow coefficient of 0.6
gives a size coefficient of 3.6. SV3 3 mm size hole and flow coefficient of 0.3 gives a
size coefficient of 0.9. Experimental results should compare approximately with
these.
Calibrating a solenoid valve will ensure its size coefficient is suitable for the system.
1 What is the use of the circuit breaker? How does it operate? How would you test its
operation?
2 Which parts of the PI have you dealt with in this practical and how are they used?
Power section, current source, process connections. The power section provides
power for the Process Controller, Pumps, Heater and Transmitters. The current
source can be used to directly open and close the servo valve. It produces a
4-20 mA current control signal. The process connections are used to make power,
control and signal connections for the control of the processes.
3 How and why is a current loop used in process control? What type of current source
is incorporated in the PI and what are its advantages and disadvantages over the
other type?
38-001-3 3-17
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Current loop allows long distance signalling and standard communication formats to
be used (4-20 mA). The PI contains a transmitter as a current source, which is
independent of line resistance, but requires a separate supply and has no fail safe.
4 What is the general purpose of the Digital Display Module (DDM) and how is it used
in this practical? What is the significance of the mA / % switch?
Servo valve supply socket is input and servo DIN on PI is the output.
2 What is the effect of a change in the loop current on the DDM and variable area
flowmeter?
Changing loop current is displayed on the DDM, and will change servo position,
changing flow and so changing visual flow meter.
3 What are the signals that are carried by the 7-pin DIN socket of the servo valve
process connection 5?
4 How is the state of the servo valve opening described with reference to the DDM,
and why is this way generally preferable in process control?
1 What is the use of the I-V converters, particularly in process control, and how do they
operate?
Converts current signal to a voltage across a 100 Ohm resistor. Voltage can be used
with voltage controlled devices (solenoids).
2 How is I1-V1 converter incorporated in this practical? How else can the I-V converters
be used with the rest of the equipment?
Returning current signal from plant is converted. Voltage signals allow logic control to
be implemented.
3-18 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
3 Plot a graph of the voltage across terminals G and 0V against the current in the loop,
as the current source output is varied. What is the approximate shape of the graph
plotted? What is the error involved and where does it come from?
1 What is meant by calibration? Why is calibration so important? What are the critical
issues in calibration?
2 What are the two controls associated with the current source calibration and how are
they used?
3 How would you calibrate the current source if high accuracy was required?
1 What is a comparator? What are the different types of comparator that exist?
Describe the one included in the Process Interface.
Non-linear circuit based on Op Amps which produces two discrete outputs dependent
on input level. Inverting or non-inverting, positive feedback creates a Schmitt trigger,
included in the PI.
38-001-3 3-19
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
2 What is hysteresis and how is it associated with a Schmitt trigger? What is the effect
of varying the hysteresis on the operation of the Schmitt trigger?
3 What are the benefits of taking care when choosing the threshold voltage Vt? What
can occur if Vt is chosen incorrectly?
Minimise noise at the switching levels. Too large degrades crossover point.
1 Why is it vital that this practical is completed before any others that involve the
Process Controller (38-300) and a personal computer?
2 The first two steps deal with the physical link between the 38-300 and a computer,
what does the third deal with? What would be the effect of incorrectly completing this
step?
1 When controlling the PI, of what type are the process inputs and outputs of the
Process Controller (38-300)? What input signals does the 38-300 accept?
2 What is the major restriction when using the 38-300 in terms of monitoring process
variables? What sort of control can be implemented using this controller, and so how
many variables can be controlled?
3 Considering the operations carried out before the parameters on the Control and Set
Point pages were recorded, and the information given in the background to this
practical on computer initialisation, what do you suggest is the reason for the
differences in the two sets of parameter values recorded? As well as saving time and
effort, what is another advantage of using a computer to initialise the 38-300 before
attempting a practical?
3-20 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 Hysteresis, with regard to the 38-300 alarms, is the difference between the switch-on
level and the switch-off level of the variable assigned to the alarm. Did you find your
experimental results were the same as the values set up in the controller by your
personal computer (these can be found by observing the 'SEtUP ALAr_S' page)?
When is hysteresis operational, and when using it what can be said about the
variable as it moves inside the trip level?
Hysteresis is operational when alarm is active. Shows how far inside the trip level
variable travels.
2 When transferring between modes of the 38-300, what is a 'bump' and what are the
conditions that would cause a bump? What steps should be carried out to prevent
bumps, and what facility is available on modern controllers to prevent bumps? What
is the anomalous situation that can occur if care is not taken when transferring modes
in a modern controller?
A bump is difference between set point and operating (measured) point when
changing mode. Equating these will remove bump. Automatic bumpless transfer can
produce deviation between operating point and set point.
3 Considering what you have learnt in this and previous assignments about automatic
and manual control systems, split the following into Automatic Control and Manual
Control:
38-001-3 3-21
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 What are the four steps that make up the 38-300 pre-practical set-up procedure?
(Clue: three were met in the previous assignment)
2 Why is it unnecessary to calibrate the 38-300 in the same way that the current source
on the Process Interface was calibrated? What devices would be needed to calibrate
the 38-300 to an accuracy level greater than the one it has already been calibrated
to?
1 What is a relay? What are the different types of relay available in the 38-300
controller? What type of control are they well suited to?
Relays - Voltage controlled switches, normally open / normally closed, positive action
/ negative action. Suited to On / Off control.
2 Describe the operation of the process in this practical. What types of relays were
used, how do they differ?
3 What are the trip levels and hysteresis values of the alarms that are controlling the
relays, as found experimentally by investigating the full range of output?
4 By assigning relays to alarms, what do the relays inherit, and how does it affect the
way in which they operate?
3-22 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 What is the difference between a READ command and a WRITE command as sent
by your computer to the 38-300?
2 In this practical you have met two virtual instruments that are used when controlling a
process with your computer. Briefly outline the different facilities that a computer
offers to process control; include which direction communication is passing, and
between whom.
Control bars - write to and read from the controller to the computer.
Computer initialisation - write to and read from the controller to the computer.
3 What type of controller is the 38-300, and what is the nature of the subservient
relationship between controller and computer.
4 Why are there steps in the curve being drawn by the chart recorder? What are these
steps dependent on? How could the size of the steps be reduced, how could the
curve be made smoother?
Sampling rate of the computer. Step size dependent on sampling frequency fs.
Sample quicker, or use interpolation techniques.
1 Why are the signals from the Float Level Sensor converted to the 4-20 mA format by
the Float Level Transmitter?
Signals from the sensor could be in any form, so converted to a standard form. Also
long distance communication is possible.
2 What is the Float Level Transmitter providing to the controller, and how does this
enable feedback control to be carried out?
38-001-3 3-23
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
3 Considering what you have already learnt about using instruments, and what must be
done to them before they can be relied upon in a measurement situation, why is it
possible that the Float Level Sensor and Transmitter combination is not producing a
4-20 mA signal proportional to the level of water in the tank?
1 Consider the following instruments in turn; Does each one have to be calibrated
regularly if its readings are to be relied on absolutely?
• A Current Source
• A Digital Multimeter
• A Weighing Machine
• A Geiger Counter
• A Digital Watch
• A Thermostat
the 'master' and the 'slave' controller master - computer, slave - 38-300
3-24 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
the desired level (or set point) chart recorder, control bar
both places
1 What type of signal is the Pulse Flow Sensor producing, and what is done to make
this suitable for transmission to other instruments around the process system?
Pulse flow sensor produces a pulse train, which is converted to 4-20 mA signal by the
pulse flow transmitter.
2 What is also being controlled by limiting the flow around the system?
Level.
3 Considering what you have already learnt about using instruments, and what must be
done to them before they can be relied upon in a measurement situation, why is it
possible that the Pulse Flow Sensor and Transmitter combination is not producing a
4-20 mA signal proportional to the rate of flow through the pipe network?
38-001-3 3-25
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
2 What can we now do reliably and accurately, and what does it provide for the
system? What can be constructed with either this, or the previous assignment's
instruments?
Measure flow, providing information on the state of the process. A feedback loop can
be constructed.
3 Why use different transmitters if the outputs from both the float level transmitter and
the pulse flow transmitter are 4-20 mA signals? Could you reliably use the same
transmitter for two seemingly identical pulse flow sensors without adjustment?
The inputs to the transmitters from the sensors are different. Must be calibrated, two
devices should not be considered identical.
2 What is happening to the measured value that makes proportional control unsuitable
for flow rate control without any modification or improvement?
Oscillation
3 Explain exactly what is occurring to the system, as the effect from question 2 is
exhibited. What is the 38-300 trying to do, and what happens when it applies a
control effort to the system?
Flow is fluctuating back and forth. 38-300 is trying to set flow by controlling servo
position, but control effort is too large for system and sends process in opposite
direction.
3-26 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 What is on/off control and why is it sometimes preferable to other types of control?
What are the disadvantages of on/off control?
On/Off control is two state binary control, only using extremes. Simple and cheap.
Oscillation often occurs, it will cure deviation when it occurs rather than prevent
deviation.
2 How is on/off control used in this practical to control the level of the water in the
upper tank? Which pieces of equipment are involved?
Signal from float level sensor converted to current signal from transmitter, converted
to voltage level by I-V1. Current source current converted to voltage level by I-V2.
Two voltages are inputs to Schmitt trigger, they are compared and output switches
pump on/off dependent on deviation.
3 What are the meanings of the following terms: reference value, measured value, and
deviation? What do they represent in this practical, how are they produced, and how
are they used?
4 What is the significance of manual valve MV3 connected to the upper tank, with
reference to the operation of the on/off level control and how should it be set for
correct operation?
MV3 controls rise and fall times of upper tank (outflow rate). Must be such that level
increases with pump on, decreases when pump off.
1 Why is on/off control of the pump avoided and a solenoid valve used instead?
Pump not designed to be switched repeatedly and indefinitely, but solenoid is.
2 Describe the different actions that can be produced from the comparator and Schmitt
trigger arrangement, depending where the reference voltage is connected.
38-001-3 3-27
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
3 What is being imitated when the water is swished around in the upper tank? How
does the hysteresis level affect this, how does it control disturbance rejection?
Disturbance. Hysteresis controls trip levels, and large hysteresis value has wide trip
levels so disturbance rejection.
4 Sketch a hysteresis loop for a Vt value of 1V, with output switching between 0V and
5V. What would be output of the Schmitt trigger if;
a) the reference voltage is 2.5 V connected to the inverting input of the comparator,
and the measured value is i) 1 V, ii) 4 V, and is connected to the non-inverting input
of the comparator.
What else must be known about b) ii) before an output level can be specified?
1 Why was it necessary to recalibrate the FLT before beginning this practical?
2 Describe the operation of the whole process during this practical. Split it into the
following stages:
3-28 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Filling -measured value < reference, Schmitt trigger output = 5 V, solenoid is open,
float switch output is low.
4 How does varying the current source (and so the reference voltage) affect this
process?
38-001-3 3-29
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Disturbance.
1 Which type of relay is being used on the 38-300? Why is this? What sort of control
action is being produced, inverting or non-inverting?
SV2 is controlled with normally closed, positive action relay. It needs to be closed
when deviation is negative. This is non-inverting action.
2 What does the 38-300 allow us to do, that the single PI did not?
Set up more than one trip level/action. Each tripping/ hysteresis/ control action would
require a separate PI.
3 Describe the operation of the process for each of the following stages:
• switching state
• switching state
For each stage consider alarm status, relay status, actuator logic input and measured
level with respect to desired level.
Increasing - alarm off, relay closed, logic level low, measured level < desired level.
Passing and switching - alarm off, relay closed, logic level low.
4 When using the 38-300, the trip level and hysteresis value of the alarm are available
to the user, to determine how the system will operate. What are the equivalent of
these two variables when the PI is used as the controller?
3-30 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 What benefits might the use of a mimic diagram have in an industrial environment?
Proportional band represents the change in a measured variable that will generate a
100% change in control effort. Therefore an increase in the proportional band width
will reduce the gain of the control system and reduce the observed reaction to
process variable changes.
1 As the measured variable approaches the set point on the chart recorder, its rate of
approach decreases (the curve becomes more horizontal). Why is this so?
2 What does the quiescent point correspond to in a practical process control situation?
What is the significance of this quiescent point?
3 If the control law was such that the measured value approached the set point by half
the error for every time step, should the measured value ever reach the set point?
Theoretically, they should never be equal, but the deviation will become negligible,
and the actuator has a resolution, a minimum movement.
1 Why is an error (or offset) always present when using proportional control, and how
can it be reduced? What must you be aware of when attempting to reduce offset?
38-001-3 3-31
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
2 For the four examples of process input below, decide if each is manual control,
proportional control, or neither. Compare each case to the general form of the
proportionally controlled input, met in the proportional control theory.
2.a) U = 10 manual
2.b) U = 10 + (2 x t x C) neither
2.c) U = 10 + (0.5 x C) proportional
2.d) U = t x C neither
1 What is the relationship between system gain and proportional band? Why is
proportional band given as a percentage?
2 Considering the equations given in the theory section on Proportional Band, and then
those given in the theory section on Proportional Control, explain the operation of the
system when the proportional band is varied. How are the following changing; PB, K,
U, Uc, Um, e?
3 What is the value of proportional band that caused the measured value to begin
oscillating? Was is possible to completely remove offset without triggering
oscillations?
3-32 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Flow is dynamically much quicker than level. Control effort should be reduced
accordingly to avoid overcompensation and oscillation.
2 Describe qualitatively the terms Uc, PB and K, when using proportional control. What
are the two expressions that link all three, and one other variable? What is A, the
constant of proportionality?
K - controller gain.
3 The combination of the 38-300 reading the process variable, your personal
computer reading the 38-300, and the chart recorder drawing the variables has produced a
curve made up of small steps. If the sample rate of both devices was fast enough to be
considered 'continuous', what would be the resulting shape of the smoothed curve?
Sinewave.
1 What is the value of proportional band that caused the measured value to stop
oscillating? As proportional band was decreased, did the oscillatory behaviour
increase linearly? What else occurred?
2 Recalling the value of proportional band that caused oscillation in the last practical of
Assignment 11, why are the two different? What are the corresponding system gain
values, with respect to each other?
38-001-3 3-33
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
3 When the proportional band was at a level high enough for there to be no oscillation,
there was the variable offset as met in the last assignment. How does it compare with
the offset found when controlling level?
4 Why are the two values of offset (when controlling level, and when controlling flow)
different?
1 Explain the behaviour of the parameter Proportional Band, and describe how it
affects the process characteristics? (You should have a pretty good idea about PB
from this and the two previous assignments)
2 Discuss integral action, and the differences between Proportional and Proportional +
Integral control. What part does the reset time Tr play and how does it determine the
contribution of the reset component?
Integral action is control term which is integral of error, (so area under error against
time curve) and it will be present until error is zero, removing offset. Tr controls length
of time integral is taken over so determines contribution of integral action.
3 Can you now reduce the offset produced by Proportional control to zero?
Yes
4 How readily did the system oscillate when the integral action was turned on?
1 How does Proportional Band affect the response time of the controller? (Consider
what PB is and how it influences the control effort)
3-34 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
PB influences total size of control effort whatever algorithm is being applied, since it
is a function of gain. Smaller PB, larger gain, larger control effort, faster response.
2 Recall the simple equations met in earlier theory sections, and explain how PB and Tr
can be traded off against each other to produce a desired control action?
PB will control oscillation but will introduce an offset, Tr will reduce offset, so PB can
be large to reduce any chances of oscillation and Tr can be small to reduce offset.
3 Why must the integral action be large if PB is large (explain each step linking these
two parameters)?
A large integral action is produced by a small Tr. PB large, so small control effort, so
large offset, so small Tr for large integral action to decrease offset.
1 Discuss the effect of derivative action, both theoretically and experimentally. What
will it do to a process plant and controller?
2 How do the three control effort parameters determine the response of the controller?
Are their values critical, or could a particular controller responses be provided by a
range of parameters?
3 Can you foresee any possible problems with PID control, in particular the derivative
element of the control effort, that would become apparent when controlling a
dynamically fast system? (Consider this question carefully but do not worry if you are
unable to answer it as this will be considered in the next assignment)
38-001-3 3-35
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 What is the main difference between controlling flow and controlling level, in terms of
the process variables themselves?
• 'A large PB value corresponds to a small gain value and a small control effort for
a deviation between measured value and set point'
• 'Using proportional control, an offset will always be present because control effort
is proportional to error, without this there would be no control effort'
• 'Integral or reset action will remove offset by applying a control effort until the
error is zero'
1 What is the reason for any oscillation when the measured value is increasing towards
the set point? Does this increase in severity as Td increases? (Consider rate of
change of error) Would you consider this process variable (flow) suitable for PID
control?
Error changes very fast and so control effort is very large to compensate, too large
for system and oscillation is the result. This will increase as Td increases. Flow is not
really suitable for PID control.
• 'If there is a large change in a process output for a small change in process input,
the process is considered to have a large gain'
• 'The derivative of deviation between measured value and set point is the rate of
change of that deviation'
3-36 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 Using the table of recommended settings met in the background to this practical, and
reproduced below, calculate all parameters for P, PI and PID control of your process
plant.
Continuous Cycling Zeigler-Nicholls Tuning
Control Controller
Algorithm PB Tr Td
P 2PBU - -
Tu
PI 2. 2PBU -
12
.
Tu Tu
PID 1.7PBU
2 8
1 Was the controller able to automatically tune itself to the process and put forward
values that settled down oscillation?
Should be yes.
2 Were these values similar to the values produced manually in the last two practicals?
(The parameters are not expected to be identical, but they should all be of a similar
magnitude)
38-001-3 3-37
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 Describe how the Remote Set Point facility is used by the controller, both in this
practical and generally in a real industrial situation.
Remote set point uses another measured variable to control the set point (actually
providing the set point) for a process.
2 What are you pretending to be by manually varying the current source of the PI to
change the remote set point?
1 Discuss how the different control algorithms coped with a changing set point.
This will be affected by the system and the control algorithm, but there are general
points which have already been explored: PID should control deviation, but if it is very
quick the control effort may be too great - overshoot, P control may appear slow but
there should be no overshoot, the responses should exhibit behavioural
characteristics that have been discussed previously.
2 Which control method could best follow the set point profile?
1 Discuss the differences between conventional On/Off control and Time Proportioned
Output control.
On/Off control switches the state of the control effort as deviation changes sign. Time
Proportioned Output control is essentially a pulse train, where the periods of high and
low control effort are determined by the deviation (with no deviation, T.P.O should
output a square wave).
2 What is the characteristic of On/Off control that Time Proportioned Output control
helps to avoid?
Conventional On/Off control will always force a system in one direction and then
compensate accordingly (oscillate), but T.P.O. control will hope to maintain a
system’s operating point by switching the control effort as a square wave.
3-38 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
3 Why could conventional On/Off control still be chosen for a process plant even
though Time Proportioned Output control will limit oscillation?
1 Consider the following instruments in turn; Does each one have to be calibrated
regularly if its readings are to be relied on absolutely?
Thermostat Yes
Power is dissipated in a thermistor in the form of heat. This heat raises the
temperature of the component body above that of the surrounding environment.
38-001-3 3-39
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
The conduction of heat through air is less efficient than through water. The subject is
covered at length in the theory and background to this assignment.
Problems with inefficient heat transfer, overheating and vibration would occur. Other
problems would also occur dependent on the process involved.
Advantage-It can provide the required control with the minimum initial cost and
outlay.
Disadvantage-Due to system lags the measured value can oscillate. The actuators
are driven to the two outer process limits.
2 When using on/off control with the TPR what prevents the potential temperature from
being reached instantaneously?
1 Explain with the aid of a diagram the operation of the heat exchanger.
2 Why are the signals from the thermistors converted to the 4-20mA format by the
Thermistor Temperature Transmitter?
This is an industry standard control signal format accepted and understood by most
process control equipment. It allows longer transmission lines.
3 What is the Thermistor Temperature Transmitter providing to the controller, and how
does this enable feedback control to be carried out?.
3-40 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 From the following list of systems, identify and explain the types of cooling used:
2 Define the areas of lag associated with the Temperature Process Rig.
Distance Velocity Lag - This is the time taken for the primary flow (heating fluid) to
travel from the valve (heating reservoir) to the heat exchanger.
Transfer lag between primary and secondary flows of the heat exchanger. Due to
supply capacity, time is required following a change in valve position for the
secondary flow to heat up or cool down.
This question can be answered with reference to the theory section of this
assignment.
The temperature rig is an analogue system. This means that the parameters within it
(ie, temperature and flow) are infinitely variable. This means that they can be at any
value. The hands on the face of an analogue clock can occupy any position. The
simulation allows the parameters only to move in discrete steps; the analogue
variables are being represented by discrete digital values.
38-001-3 3-41
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
The primary flow must remain in ratio with the secondary flow. However if the
secondary flow is held constant, the primary flow should remain constant, except for
the fact that the secondary flow heats up. This has the effect of reducing the heat
transfer effectively, hence as the secondary heats up, the primary flow must increase.
This is true until such a point as the secondary flow has reached the same
temperature as the system set point. At such a point the temperature of the
secondary continues to increase and the system becomes unstable.
2 Explain in detail the effect of the secondary flow temperature on the efficiency of the
heat exchanger?
See above.
2 Explain why less control effort is required once the system `settles down'?
Once the system as settled down the temperature fluctuations are very small, hence
minimal control effort is required.
3 What would be observed if the system was left running for a long period of time?
The system would become unstable, as the secondary flow temperature rose above
the system set point.
3-42 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
a) Items of Hardware
the measurement instrument thermistor
the measured variable temperature
the feedback path thermistor, TTT, DDM, PI, 38-300
the 'master' and the 'slave' controller master - computer, slave - 38-300
the actuator servo
b) On The 38-300 Display
the measured (or process) variable top display
the control effort output lower display
the desired level (or set point) lower display
c) Displayed On Screen
the measured (or process) variable chart recorder
the desired level (or set point) ....both places chart recorder, control bar
the difference (or error) chart recorder
1 What are the advantages of using mimic diagrams in an industrial plant situation?
The major advantages are more user friendly instrumentation and control, the
concentration of all instrumentation to one convenient location, global system and
error reporting, etc.
The relative merits of mimic diagrams and virtual instrumentation are discussed in the
theory associated with this assignment.
38-001-3 3-43
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 What is on/off control, and why is it sometimes preferable to other types of control?
On/Off control allows only two states for the controlling device. This can be open or
closed, on or off, depending on the device. The greatest advantage is the simplicity
of implementation this method of control allows.
2 Explain the meaning of the hysteresis value when applied to on/off control. What
effect does the level of hysteresis have on the performance of a system?
The hysteresis level defines the difference between the on/off switching levels when
the variable is moving up of down. A small hysteresis level can lead to oscillation,
while a large hysteresis level can lead to an un-responsive system.
1 Why is there always an offset present when using proportional control and how can it
be reduced ?
Offset will always be present in a proportional control application because the control
effort is a function of error, for there to be a control effort there must also be an error.
The error can be reduced by increasing the system gain (achieved by reducing the
proportional band value), producing a larger control action for the error present.
2 What are the effects of a narrow proportional band and what would result if the
proportional band was increased 50%?
Small offset due to any load changes. Offset increases dramatically such that control
would be insufficient.
λ It reduces offset.
The system generally takes longer to stabilise than with proportional control only.
For negative deviation, integral action shifts the whole proportional band above the
set point until the controlled condition reaches it. This means that the correcting
element does not start to close until it is too late to prevent overshoot.
3-44 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Control process having large distance velocity and transfer lags. Also where load
changes may be sudden and/or sustained.
It improves the response of the controller to rapidly changing loads and provides a
braking effect when the measured variable approaches the set point.
1 Explain with the aid of a diagram, a system for automatically proportioning the flow of
liquid in two separate pipelines.
The system to achieve this task is known as ratio flow control and is covered in detail
in the theory section of this assignment.
In some cases dual loop control (two controllers) has to be carried out in order to
achieve satisfactory control, which would have been unattainable with only single
loop control.
1 What is the effect of increasing and decreasing the flow set point ?
2 Name two industrial applications where flow and temperature has to be controlled ?
38-001-3 3-45
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
1 Discuss the effect of changing the level set point on the rest of the system.
If the level set point was increased, the secondary flow would have to increase to
attain the new level, which subsequently results in the primary flow increasing to
maintain the temperature set point. opposite is true if the level set point was
decreased.
The major advantages are user friendly instrumentation and control, the
concentration of all instrumentation in one location, global system and error
reporting, etc.
3-46 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
“Calculate the volume of water in the tank at overflow and hence calculate the rate of flow
through the pipes from lower to upper tank”
Volume of tank / Time to fill tank from empty to overflow = Rate of flow
They are equal; hence the level of water in the tank remains constant.
Also, the accuracy of the final volume calculation can only be as good as the accuracy of
the measurements used to perform the calculation.
38-001-3 3-47
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
The markings on the visual flow meter are in 0.2 litre/minute graduations. Readings taken
from the meter are to this accuracy at best. The problems associated with taking visual
readings in-general should also be considered.
The information contained within the Background for this practical should be consulted.
The DDM is showing the control output from the 38-300 Process Controller.
3-48 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Rapid on/off switching occurs as the level rapidly changes. As the hysteresis level is
altered so the switching alters.
The temperature indicated by the DDM should increase as the heat from the hand is
conducted through the piping to the thermistor T1.
Only a small amount of heat is being conducted away from the primary flow via conduction
into the body of the heat exchanger and into the stationary secondary flow.
The heat exchanger is now passing both the primary and secondary flows. Thus greater
heat transfer takes place.
Even without the fan, a certain degree of cooling occurs across the radiator.
38-001-3 3-49
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
The fan is now operating, and a greater heat loss is occurring across the radiator. The
radiator is functioning as it should.
“Why is there a drop in temperature across the heat exchanger when secondary flow is
zero?”
“What happens if you turn off both primary and secondary flows. Why?”
“Why is there a difference in temperature between the water flowing into the rig to that
flowing out of the rig.?
The water entering the rig has been cooled by the large volume of water contained in the
sump tank. This situation is temporary as the water in the sump tank will eventually be
heated to the same temperature as the primary flow.
This controls the temperature at T5 because the primary flow rate determines how much
heat is transferred to the secondary flow, and hence T5.
“As the secondary flow water temperature rises it becomes increasingly difficult to control
the temperature set-point. Why?”
The cooling water temperature slowly rises towards that of the water it is cooling. As this
happens the water loses its ability to cool.
3-50 38-001-3
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
The ratio between the two rates of flow is being maintained by controller 2. The changing
set-point is being re-transmitted by controller 1 to controller 2.
The temperature and flow within the primary and secondary circuits is being maintained
independently.
38-001-3 3-51
Chapter 3
PROCON REFERENCE MANUAL
LEVEL, FLOW & TEMPERATURE Assignments
Notes
3-52 38-001-3