The document is a catalog for NEMA Contactors and Starters, detailing separate enclosures, coil modification kits, replacement parts, and accessories. It provides specifications for various enclosure types, their applications, and how to order them. The catalog includes tables for equipment compatibility and ordering information for different classes and types of enclosures.

Uploaded by

emadali2025e
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views20 pages

9999CT9701R0817

The document is a catalog for NEMA Contactors and Starters, detailing separate enclosures, coil modification kits, replacement parts, and accessories. It provides specifications for various enclosure types, their applications, and how to order them. The catalog includes tables for equipment compatibility and ordering information for different classes and types of enclosures.

Uploaded by

emadali2025e
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

NEMA Contactors and Starters

Separate Enclosures, Coil Modification Kits,


Replacement Parts, and Accessories

Catalog
9999CT9701R08/17
2017
Class 9991, 9998, 9999

CONTENTS
Separate Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 2
Approximate Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 5
Magnet Coils and Modification Kits. . . . . . . . . . . . . . . . . . . . . . . . . . .Page 9
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 13


NEMA Contactors and Starters NEMA Type 3R, 4, 4X, and 12
Separate Enclosures Class 9991

Separate enclosures can be used with open style devices for field assembly of enclosed controls.
These enclosures, plus the open style components, are equivalent to a factory-assembled device.
Separate enclosures are to be used only with the equipment listed below:
• NEMA 4 and 12, Class 9991 Separate Enclosures for Type S devices
Standard devices come with closing plates. See the selection chart below for the specific number
of closing plates on various enclosures. For applications requiring enclosures without closing
plates, consult your local Schneider Electric representative.
• NEMA 3R Enclosures for field assembly of equipment for outdoor applications
Standard devices come with three closing plates, a reset mechanism, and a predrilled panel. For
Type SCA11 conduit connection to the top of these enclosures, select watertight hubs from Digest Section 16 in
NEMA 12 Enclosure
accordance with applicable code requirements. Square D™ brand NEMA 12 enclosures can also
be modified for outdoor use. For details, refer to the NEMA 12 enclosure modification information
on page 4.
NOTE: Not for use in high-corrosive outdoor locations or sea coast environments.
• NEMA 4X Enclosures for Type S devices, Sizes 0–2 and 30–60 A
Standard devices come without closing plates. Cover-mounted control units for NEMA 4X separate
enclosures are available as a factory modification only.
Cover-mounted control units, Class 9001 Type K or Type SK, can easily be installed into the openings
when the closing plates are removed from NEMA 4, 12, and 3R enclosure covers. Refer to Table 37 on
page 13.
Table 1: Equipment Used with Separate Enclosures
Type SCW11
NEMA 4 Enclosure Enclosure Classification
For Use With NEMA 4X NEMA 4 [1]
NEMA 12/3R NEMA 3R
NEMA Size or Glass-Polyester Stainless Steel
Types (All Pole Ampere Rating Number of Number of
Class Type Type Type [2] Type
Arrangements) Closing Plates Closing Plates
Manual Starters
2510 MBO, MCO M0, M1, M1P MW1 [3] MW11 — MA1 — —
Magnetic Contactors
SAO, SBO, SCO 00, 0, 1 SCW20 SCW11 2 SCA11 2 SCH2
SDO 2 SDW20 SDW11 2 SDA11 2 SDH1
8502 [4]
SEO 3 — SEW11 3 SEA11 3 SEH1
SFO 4 — SFW11 3 SFA11 3 SFH1
Magnetic Starters
SAO, SBO, SCO 00, 0, 1 SCW21 SCW11 2 SCA11 2 SCH2
SDO 2 SDW21 SDW11 2 SDA11 2 SDH1
8536
SEO 3 — SEW11 [5] 3 SEA11 [5] 3 SEH1
SFO 4 — SFW11 [5] 3 SFA11 3 SFH1
Lighting Contactors, Non-Combination, Electrically and Mechanically Held
Type SCH2 LO, LXO 20 A SDW20 SDW11 2 SDA11 2 SDH1
NEMA 3R Enclosure
SMO 30 A SCW20 [6] SCW11 2 SCA11 2 SCH2
8903 [4] SPO 60 A SCW20 [6] SDW11 2 SDA11 2 SDH1
SQO 100 A — SEW11 3 SEA11 3 SEH1
SVO 200 A — — — — — SFH1
Reversing and Two-Speed, Horizontally Arranged Contactors and Starters
8702 [4] SBO, SCO 0, 1 SCW12 SCA12 —
— 3 3
8736 SDO 2 SDW12 SDA12 —
8810 SBO & SCO 0, 1 — SCW13 3 SCA13 3 —
[1] The standard cabinet has a brushed finish.
[2] NEMA 12 enclosures for Type S devices can be field modified for outdoor non-corrosive and non–service entrance rated applications. See page 4 for
more information.
[3] Type MBO, Size M0 only.
[4] For contactors, replace the reset assembly with a proper closing plate: for NEMA 4, use 9001K52; for NEMA 3R and 12, use 9001K51. Class 9991
Types SCW20 and SDW20 are designed for contactors only; reset closing plates are not required.
[5] The enclosure is suitable for starters with melting alloy overload relays or solid-state overload relays only.
[6] For electrically held devices only.

Table 2: How to Order


To Order, Specify Catalog Number
Type SCW21 • Class Number Class Type
NEMA 4X Enclosure • Type Number 9991 SCA11

2
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters NEMA 1 and Flush Mounting
Separate Enclosures Class 9991

Flush-Mounting General Purpose separate enclosures include the The NEMA 1 General Purpose separate
following provisions for cover-mounted control units: enclosures listed in Table 5—when used with
open style components—are equivalent to a
• Type S Sizes 0–2, or 30–60 A: knock-outs in the cover for field
standard factory assembled control device.
assembly of one Class 9999 push button or selector switch kit and
one Class 9999 pilot light kit. See page 13.
• Type S Size 3, or 100 A: three closing plates for installation of
Class 9001 Type K oiltight control units. For enclosure dimensions,
see page 8.

Table 3: Flush Mounting Selection Table 5: NEMA 1 Selection


Flush Mounting General Purpose (Components) NEMA 1
NEMA For Use With
For Use With Class 9991
Size Flush Plates Mounting Class Type Number of Poles Type
or Pullbox
[1] Strap
Types (All Pole Ampere Standard Stainless Steel F and K All EN1
Class 2510 M-Sizes M0 and M1 All MG1
Arrangements) Rating Type Type Type Type
M-Size M1P All MG2
Manual Contactors CO All UE1
M0 MF1 (includes pullbox and plaster adjustment) 2–12,
XO
2510 MBO & MCO M1 8501 2–4 with attachments
UE7
M1P MF2 (includes mounting strap but not pullbox) 2–8 without
XDO
attachments
Magnetic Contactors
SAO, SBO, SCO 2–4 SCG7
SBO & SCO 0, 1 SCF11 SCF12 SCF2 SCF1 SDO 2–4 SDG7
8502
8502 [2] SEO 2–4 SEG7
SDO 2 SDF11 SDF12 SDF2 SDF1
SFO 2–4 SFG8
SEO 3 SEF11 (enclosure complete) SAO, SBO, SCO 2–4 SCG8
Magnetic Starters SDO 2–4 SDG8
8536 SEO 2–4 SEG8 [1]
SBO & SCO 0, 1 SCF11 SCF12 SCF2 SCF1
8536 SFO 2–4 SFG8 [1]
SDO 2 SDF11 SDF12 SDF2 SDF1 SGO 3 SGG8 [1], [2]
Lighting Contactors, Non-Combination, Electrically and Mechanically Held 8702, SAO,SBO, SCO All SCG9 [3]
8736 SDO All SDG9 [3]
LO, LXO 20 A SDF13 — SDF2 SDF1
LO, LXO All LXG1 [4]
SMO 1–4 30 A SCF11 — SCF2 SCF1 SMO All SCG7 [5]
8903 SPO All SDG7 [5]
SMO 10–13 30 A SCF13 — SCF2 SCF1
8903 [2] SQO All SFG8
SPO 1–4 60 A SDF11 — SDF2 SDF1 SVO All SFG4
SPO 10–13 60 A SDF13 — SDF2 SDF1 DP 1–2 DPG1
DPA12, 13, 22, 23,
SQO 1–13 100 A SEF11 (enclosure complete) 2–3 DPG1
32, 33, 42, 43
8910 DPA14, 24, 34, 44,
2–4 DPG2
52, 53
DPA62, 63 2–3 DPG3
DPA72, 73, 92, 93 2–3 DPG4
DPSO13, 23, 33, 43 3 DPSG1
8911
DPSO53 3 DPSG2
AO (Single Head) All UE6
9050
HO All UE6
EO51, EO61, EO71,
— SDG4
K750, K1000
EO2, EO3, EO4,
EO15, EO16, EO18,
9070
EO19, T75, T100, — LG1
T150, T200, T250,
T300, T350, T500
EO1, EO17, T50 — UE7
Type SCG8, NEMA 1 Enclosure Flush Mounting Starter Pullbox and
Mounting Strap with [1] The enclosure is suitable only for starters with melting alloy
Plaster Adjustment Feature or solid-state overload relays (SSOLRs). For SSOLR on
Sizes 3-4, the reset extender kit (9999ER4) must be used.
Table 4: How to Order [2] Series B starter enclosure.
To Order, Specify: Catalog Number [3] For horizontally arranged Class 8702 contactors, replace the
• Class Number Class Type reset assembly with a Class 9001 Type K51 closing plate.
• Type Number 9991 DPG1
[4] If cover-mounted control units are required, select an
oversize enclosure as listed in Table 9 on page 5.
[1] The standard cabinet has a brushed finish. [5] For electrically held contactors only.
[2] For contactors, replace the reset assembly with a proper closing plate. For flush mounting, use Class 9999
Type SG2—except for Class 9991 Type SDF11, which requires a Class 9001 Type K51 or K11 closing plate.
Class 9991 Type SEF11 is designed for contactors only; reset closing plates are not required.

3
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters Oversize NEMA 1, 4, and 12/3R
Separate Enclosures Class 9991

Addition of Control Circuit Transformer—Oversize NEMA 1, 4, and 12/3R Enclosures

NEMA Contactors and Starters: Class 8502 or 8536, Type S, NEMA Size 0, 1, 1P, or 2
The Class 9991 oversize enclosures listed in Table 6 accept an open-style contactor or starter, along
with a fused control-circuit transformer (Form F4T), for field assembly of enclosed controllers. Knock-
outs in the cover of the Class 9991 Type SCG1 enclosure provide for field addition of Class 9999
rectangular cover-mounted control units. All other Class 8502 and 8536 enclosures include a panel
with space and drilling for an open-style device and a fused control-circuit transformer. In addition,
each cover includes three closing plates for easy installation of Class 9001 Type K or SK control units.
Lighting Contactors: Class 8903 Type L and LX (20 A) and Type S (30 and 60 A)
Type SCW4 Oversize enclosures for open-style electrically and mechanically held lighting contactors include a
NEMA 4 Enclosure drilled panel with space for the following: an open-style contactor, a fused control-circuit transformer
(Form F4T), and an auxiliary relay for use with single-pole pilot devices (Form R6). When an auxiliary
relay is required, use a Class 8501 Type XO11 relay. Three closing plates come standard for easy
installation of Class 9001 Type K or SK control units.
NOTE: If a Form F4T control transformer (with or without cover control units) is required on a
Class 8903 Type SMO, 30 A, electrically held lighting contactor, then a Class 9991 Type SCG1,
NEMA 1 separate enclosure can also be used.

Table 6: Oversize Enclosure and Transformer Selection


Recommended Class 9070
For Use With Class 9991 Enclosure
Transformer Selection Fuse
NEMA No. NEMA 4 NEMA Extra Capacity Block
NEMA 1 [2] Standard
Class Type Size or of 12/3R [3] 100 VA 150 VA 300 VA [1]
Rating (A) Poles Type Type Type Type VA Type Type Type
Magnetic Contactors and Starters
SAO,SBO 1–3 T50 50 VA T100 [5] T150 [5] —
8502, 00, 0, & 1 SCG1 [1] SCW4 SCA4
& SCO 4–5 T100 [5] 100 VA — T150 [5] —
8536 [4]
SDO 2 2–5 SDG4 SDW4 SDA4 T100 100 VA — T150 T300
Lighting Contactors, Non-Combination Class
9999
LO, T50 50 VA — — —
20 A All Type
Type SCG1 LXO T50 50 VA T100 [5] T150 [5] — SFR4
with Starter, Transformer, 8903 1–3 SDG3 SDW3 SDA3 T100 [5] 100 VA — T150 [5] —
SMO [6] 30 A
and Fuse Block Installed 4–5
T100 100 VA — T150 T300
SPO [6] 60 A 2–5
[1] The Class 9991 Type SCG1 enclosure comes standard with a Class 9999 Type SF4 fuse block.
[2] The standard cabinet has a brushed finish. For electropolished finish, specify Form G16.
[3] NEMA 12 modified for outdoor use (see below).
[4] For contactors (Class 8502), a separate closing plate is provided with each enclosure to replace the reset mechanism—with the exception of Class 9991
Type SCG1, which requires a separate reset closing plate, Class 9999 Type SG2.
[5] For mounting an SCG1 enclosure, a Class 9991 Type S1 adapter bracket is also required.
[6] Mechanically held.

NEMA 12 Enclosures Modified for Outdoor Applications


(Do not use in salt air or corrosive environments)
Field Modifications for NEMA 3 dusttight, raintight, and sleet resistant outdoor applications include:
Watertight conduit hubs or equivalent provision for watertight connection at the conduit entrance shall
be used.
Field Modifications for NEMA 3R dusttight, rainproof, and sleet resistant outdoor applications
include:
1. Watertight conduit hubs or an equivalent provision for watertight connection at the conduit
entrance, when the conduit enters at a level higher than the lowest live part, shall be used.
2. Drain holes of 1/8 in. diameter must be added to the bottom of the enclosure.
Table 7: Control Unit Selection Table
Class 9999
Control Function
Kit Contents Class 9001 Type K oiltight/watertight control units can easily be installed in
Type Class & Type Description separate enclosures (NEMA 4, 12, and oversize Type 1) that include
1–9001 KR1B Start Operator closing plates. When installing control units, simply remove the closing
1–9001 KR1R Stop Operator
SA3
Start-Stop
1–9001 KN201 Start Legend Plate plates and install the proper Class 9001 Type K components.
Push Button
1–9001 KN202 Stop Legend Plate
2–9001 KA1 Contact Block Convenient control unit kits, complete with assembled and pre-wired
1–9001 KS43B Selector Operator Switch operators for quick installation, are available as Class 9999 field
Hand-Off-Auto
SC8 1–9001 KN260 Hand-Off-Auto Legend Plate modification kits. See Table 7 for kit contents. As an alternative, Class 9001
Selector Switch
1–9001 KA1 Contact Block
Type SK, NEMA 4X corrosion-resistant control units can be used.
SP28R Pilot Light (120 V) 1–9001 KP1R31 Red Pilot Light

4
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters NEMA 1 and Oversize—Approximate Dimensions
Separate Enclosures Class 9991

Table 8: NEMA 1 General Purpose Enclosures (Standard)


Class For Use With Dimensions, in. (mm)
Weight
9991 NEMA Size No. of Fig. Mounting (lb)
Type No. Class Type or A Rating Poles No. Screws
A B C D E F G H I J K L
7.81 12.69 6.03 1.09 10.50 1.09 1.09 5.63 5.75 1.09 5.63
LXG1 8903 LO, LXO 20 A 2–12 1 — — 8
(198) (322) (153) (28) (267) (28) (28) (143) (146) (28) (143)
DP 1–2 4.85 8.5 4.03 2.42 0.109 5.75 0.531 0.92 3.00 3.75
DPG1 8910 20–40 A 1 (4) #10 — — 2
DPA 1–3 (123) (216) (102) (62) (3) (146) (13) (23) (76) (95)
8903 SMO (E.H.) 30 A All
SAO 00 2–3 5.28
SCG7
8502 SBO 0 (134)
All
SCO 1
6.00 10.00 3.00 0.88 8.13 1.00 0.94 4.13 5.00
SAO 00 2–3 1 (3) #10 — — 4
(152 (254 (76) (22) (206) (25) (24) (105) (127)
SCG8 8536 SBO 0
All 5.56
SCO 1
(141)
DPG2 8910 DP — —
DPSG1 8911 DPS — —
8903 SPO (E.H.) 60 A 2–12 6.03
SDG7
8502 SDO 2 All (153)
7.81 12.69 1.09 10.50 1.09 1.09 5.63 5.75 1.09 5.63
SDG8 8536 SDO 2 All 1 (4) 1/4" — 8
(198 (322 6.31 (28) (267) (28) (28) (143) (146) (28) (143)
DPG3 8910 DPA — —
(160)
DPSG2 8911 DPS — —
SEG7 8502 SEO 3 All
8.00
8536 SEO 3 All
SEG8 11.44 21.81 (203) 1.53 18.75 1.53 1.53 8.38 7.75 1.53 8.38
8911 DPSG63 to 93 — All 1 (4) 3/8" — 23
(286 (554 (39) (476) (39) (39) (213) (197) (39) (213)
8.38
DPG4 8910 DPA — —
(213)
8502 SFO 4 All
8536 SFO 4 All 11.25 25.15 8.99 8.60 1.25 1.25 22.31 1.42 0.44
SFG8 2 (4) 7/16" — — — 34
SQO (286 (639 (228) (218) (32) (32) (567) (36) (11)
8903 100 A All
(E.H. & M.H.)
8702
[1] SBO, SCO 2
11.88 11.88 7.41 9.75 1.06 1.06 9.75 1.06 0.31
SCG9 All 2 (4) 5/16" — — — 16
ETBC20, (302 (302 (188) (248) (27) (27) (248) (27) (8)
8922 —
ETBC36
8702
[1] SCO 2 14.88 14.13 7.56 12.75 1.06 1.06 12.00 1.06 0.31
SDG9 All 2 (4) 5/16" — — — 24
(378 (359 (192) (324) (27) (27) (305) (27) (8)
8922 ETBC60 —
[1] Standard enclosure has space for a fused control transformer, Form F4T, on Sizes 0–2.

Table 9: NEMA 1—General Purpose Enclosures (Oversize)


For Use With Dimensions, in. (mm)
Class
NEMA Size Weight
9991 No. of Fig. Mounting (lb)
Type No. Class Type or Ampere
Poles No. Screws
A B C D E F G H I
Rating
LO, LXO 20 A
SDG3 8903 SMO (M.H.) 30 A All 7.56 15
SPO (Form F4T) 60 A (192)
8502 SDO (Form F4T) 2 All 14.88 14.13 12.75 1.06 1.06 12.00 1.06 0.31
2 (4) 5/16"
(378) (359) 7.66 (324) (27) (27) (305) (27) (8)
8536 SDO (Form F4T) 2 All
SDG4 (194) 21
EO51, EO61, EO71, 7.56
9070 — —
T750, T1000 (192)
8502 SBO, SCO (Form F4T) 0, 1 All
6.34 15.88 5.19 4.66 0.84 14.38 0.75 0.28 0.35
SCG1 8536 SBO, SCO (Form F4T) 0, 1 All 3 (4) 9/32" SCG1
(161) (403) (132) (118) (21) (365) (19) (7) (9)
8903 SMO (E.H.) (Form F4T) 30 A All

Figure 1 Figure 2 Figure 3 in.


Dimensions
A (4) I Dia. H
(mm)
D C A Mounting Holes
K L K J
H
E

Pilot
Light
G B
B B G
F
Reset

RESET

H
G
F D E C
H I E D C
H A (4) I Dia. Mtg. Holes

5
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters NEMA 1, 3R—Approximate Dimensions
Separate Enclosures Class 9991

Table 10: NEMA 1 General Purpose Enclosures—see Figure 4

Class 9991 For Use With Dimensions, in. (mm) Dia. K.O., in. Weight
Type No. Class Type No. of Poles A B C D E F G H J L (lb)
3.63 5.28 3.31 1.88 3.63 1.06 1.50 0.5 0.5
UE1 [1] 8501 CO All 0.25 in. [1] 2
(92) (134) (84) (48) (92) (27) (38) 0.75 0.75
8910 H, J, K, L & M All 0.5
4.91 5.75 5.53 3.50 4.38 1.56 2.00 0.75 0.5
UE6 AO (single head) All 0.28 in. 2
9050 (125) (146) (140) (89) (111) (40) (51) 1 0.75
HO All 1.25
2–12, 2–4 with
XO
8501 attachments
4.87 7.79 7.53 3.50 6.38 1.31 1.88 0.5 0.5
UE7 #10 4
XDO 2–8 (125) (196) (191) (89) (162) (33) (48) 0.75 0.75
9070 EO1, EO17, T25, & T50 —
EO2, EO3, EO4, EO15, EO16, 0.5 0.5
7.53 9.78 5.91 6.13 8.38 1.31 1.88
LG1 [2] 9070 EO18, EO19, K75, K100, K150, — 0.28 in. 0.75 0.75 10
(191) (248) (150) (155) (213) (33) (48)
K200, K250, K300, K350, & K500 1 [2] 1 [2]
[1] Class 9991 UE1 has only three mounting holes: two in the bottom as shown in Figure 4, and one centered at the top.
[2] Class 9999 LG1 has three knockouts, top and bottom.

Table 11: NEMA 3R—Rainproof and Sleet-Resistant Enclosures—see Figure 5

Class For Use With Dimensions, in. (mm) K.O., in.


9991 NEMA Size No. of
Type No. Class Type or A Rating Poles A B C D1 D2 E F G1 G2 H1 H2 J K L M N P X Y

8502 SBO, 0.5 0.5


0, 1 8.83 12.30 7.12 1.39 1.44 6.00 7.50 2.61 2.19 2.08 2.62 14.28 1.37 1.37 1.88 4.38 1.83
SCH2 8536 SCO All 0.75 0.75
(224) (312) (181) (35) (37) (152) (191) (66) (56) (53) (66) (363) (35) (35) (48) (111) (46)
8903 SMO 30 A 1 1

8502
SDO 2
8536
1
9.83 16.30 6.62 1.39 1.44 7.00 11.50 2.61 2.19 2.08 2.62 16.78 1.31 1.75 2.13 4.88 1.83 0.5
SDH1 LO All 1.25
8903 20 A (250) (414) (219) (35) (37) (178) (192) (66) (56) (53) (66) (426) (33) (44) (54) (124) (46) 0.75
LXO 1.5
8903 SPO 60 A
8502 1
SEO 3
8536 12.63 25.30 8.62 1.39 1.44 10.00 20.60 2.61 2.19 2.08 2.62 19.78 1.31 2.31 2.69 6.38 1.83 1.25 0.5
SEH1 All
(326) (643) (219) (35) (37) (254) (521) (66) (56) (53) (66) (502) (33) (59) (68) (162) (46) 2 0.75
8903 SQO 100 A 2.5
8502 1
SFO 4 All
8536 12.63 40.30 9.12 1.39 1.44 10.00 35.50 2.61 2.19 2.08 2.62 20.28 1.31 2.31 2.69 6.38 1.83 1.25 0.5
SFH1
(326) (1024) (232) (35) (37) (254) (902) (66) (56) (53) (66) (515) (33) (59) (68) (162) (46) 2 0.75
8903 SVO 200 A 2–3 2.5

Figure 4 Figure 5
A A
D1 E D2 C
N P

G1

B E
F B

G2

(4) H Dia. D
(4) 0.36 Dia. Mounting Holes
Mounting Holes
J Dia. K.O., Top and Bottom (3) Closing Plates
L Dia. K.O., Top and Bottom
J
M
C M
X X
F Y K L

G/2 H1
H2
G

6
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters NEMA 4, 4X—Approximate Dimensions
Separate Enclosures Class 9991

Table 12: NEMA 4X—Watertight and Corrosion Resistant Enclosures—see Figure 6


Class For Use With Dimensions, in. (mm) Hub Dia., in.
Weight
9991 NEMA Size No. of
W [1] X [2] (lb)
Type No. Class Type or A Rating Poles
A B C D E F G H I J K L
SMO
8903 30 A All
(E.H.)
SCW20
SBO, 6.50 6.44 12.13 0.75 5.00 8.25 1.69 3.34 10.06 1.31 2.13 0.31
8502 0, 1 All 0.75 1 7
SCO (165) (164) (308) (19) (127) (210) (43) (85) (256) (33) (54) (8)
SBO,
SCW21 8536 0, 1 All
SCO
LO,
8903 20 A All
LXO
SDW20 SPO 8.50 7.06 13.88 0.75 7.00 10.50 1.69 3.91 11.94 1.63 2.38 0.31
8903 60 A All 0.75 1.5 13
(E.H.) (216) (179) (352) (19) (178) (267) (43) (99) (303) (41) (60) (8)
8502 SDO 2 All
SDW21 8536 SDO 2 All

Table 13: NEMA 4—Watertight Enclosures (Standard)—see Figure 6


Class For Use With Dimensions, in. (mm) Hub Dia., in.
Weight
9991 NEMA Size No. of
W [1] X [2] (lb)
Type No. Class Type or A Rating Poles
A B C D E F G H I J K L
8903 SMO 30 A All 6.38 7.13 13.19 1.56 3.25 12.00 0.59 1.88 11.78 1.63 2.31 0.31
8502 SBO, SCO 0, 1 All (162) (181) (335) (40) (83) (305) (15) (48) (299) (41) (59) (8)
SCW11 0.75 1 12
6.38 7.81 13.19 1.56 3.25 12.00 0.59 1.88 11.78 1.63 2.31 0.31
8536 SBO, SCO 0, 1 All
(162) (198) (335) (40) (83) (305) (15) (48) (299) (41) (59) (8)
8903 LO, LXO 20 A All
8.13 7.88 16.19 1.56 5.00 15.00 1.09 1.94 14.75 2.00 2.63 0.31
8903 SPO 60 A All
(206) (200) (411) (40) (127) (381) (28) (49) (375) (51) (67) (8)
SDW11 8502 SDO 2 All 0.75 1.5 18
8.13 8.56 16.19 1.56 5.00 15.00 1.09 2.88 14.75 2.00 2.63 0.31
8536 SDO 2 All
(206) (217) (411) (40) (127) (381) (28) (73) (375) (51) (67) (8)
8903 SQO 100 A All 18.15 8.77 32.21 3.08 12.00 30.50 0.86 3.67 26.71 2.58 3.19 0.44
SEW11 8502 SEO 3 All (461) (223) (818) (78) (305) (775) (22) (93) (678) (66) (81) (11)
8536 SEO 3 All 18.15 9.58 32.21 3.08 12.00 30.50 0.86 4.48 26.71 2.58 3.19 0.44 0.75 2.5 51
8536 SFO 4 All (461) (243) (818) (78) (305) (775) (22) (114) (678) (66) (81) (11)
SFW11 18.15 8.77 32.21 3.08 12.00 30.50 0.86 3.67 26.71 2.58 3.19 0.44
8502 SFO 4 All
(461) (223) (818) (78) (305) (775) (22) (93) (678) (66) (81) (11)

Table 14: NEMA 4—Watertight Enclosures (Oversize)—see Figure 7


Class For Use With Dimensions, in. (mm) Hub Dia., in.
Weight
9991 NEMA Size No. of
W [1] X [2] (lb)
Type No. Class Type or A Rating Poles
A B C D E F G H I J K L
8702
SCW2 SCO 1 All 23
8736
SBO 0 12.63 7.81 14.69 2.56 7.50 13.50 0.59 3.88 18.41 1.66 2.31 0.31
SCW3 8810 All 0.75 1 19
SCO 1 (321) (198) (373) (65) (191) (343) (15) (98) (468) (42) (59) (8)
8502 SBO, SCO
SCW4 0, 1 All 24
8536 (Form F4T)
8702
SDW2 SDO 2 All 25
8736
LO, LXO 20 A
14.88 7.25 16.19 2.56 9.75 15.00 0.38 3.88 20.88 1.72 2.63 0.31
SDW3 8903 SMO, SPO 30 A All 0.75 1.5 29
(378) (184) (411) (65) (248) (381) (10) (98) (530) (44) (67) (8)
(Form F4T) 60 A
8502 SDO
SDW4 2 All 28
8536 (Form F4T)
[1] Bottom Only. [2] Top and Bottom.

Figure 6 A Figure 7 A
D E D G B D E D G B

F C
F C

G
G
(4) L Dia. Mounting Holes
(4) L Dia. Mounting Holes
I I
W X
J W X
in. J
H Dimensions H
K (mm) K

7
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters NEMA 1, 12/3R—Approximate Dimensions
Separate Enclosures Class 9991

Table 15: NEMA 12/3R—Dusttight and Driptight Enclosures (Standard)—See Figure 8

Class For Use With Dimensions, in. (mm)


Weight
9991 NEMA Size No. of (lb)
Type No. Class Type or A Rating Poles
A B C D E F G H I J
A
D E D G 8502 SBO, SCO 0, 1 All
6.38 8.53 12.75 1.56 3.25 12.00 0.38 3.56 12.50 0.31
SCA11 8536 SBO, SCO 0, 1 All 10
(162) (217) (324) (40) (83) (305) (10) (90) (318) (8)
8903 SMO 30 A All
F
C 8502 SDO 2 All
8536 SDO 2 All 8.13 9.28 16.00 1.56 5.00 15.00 0.50 3.56 15.38 0.31
SDA11 15
8903 LO, LXO 20 A All (206) (236) (406) (40) (127) (381) (13) (90) (391) (8)
G B
(4) J Dia. Mounting Holes 8903 SPO 60 A All

I
8903 SQO 100 A All 18.15 9.24 31.50 3.08 12.0 30.50 0.50 3.67 26.71 0.44
SEA11 8502 SEO 3 All (461) (235) (800) (78) (305) (775) (13) (93) (678) (11)

8536 SEO 3 All 18.15 9.58 31.50 3.08 12.0 30.50 0.50 4.48 26.71 0.44 51
H 8536 SFO 4 All (461) (243) (800) (78) (305) (775) (13) (114) (678) (11)

Figure 8 SFA11 18.15 9.24 31.50 3.08 12.0 30.50 0.50 3.67 26.71 0.44
8502 SFO 4 All
(461) (235) (800) (78) (305) (775) (13) (93) (678) (11)

Table 16: NEMA 12/3R—Dusttight and Driptight Enclosures (Oversize)—See Figure 9

Class For Use With Dimensions, in. (mm)


Weight
9991 NEMA Size No. of (lb)
Type No. Class Type or A Rating Poles
A B C D E F G H I J
A
D E D G 8702
SCA2 SCO 1 All 17
8736
SBO 0 11.88 7.75 13.5 2.56 6.75 12.75 0.38 3.66 18.13 0.31
SCA3 8810 All 18
F SCO 1 (302 (197 (343 (65 (171 (324 (10 (93 (460 (8)
C
8502 SBO, SCO
SCA4 0, 1 All 19
8536 (Form F4T)

G B 8702
SDA2 SDO 2 All 24
(4) J Dia. Mounting Holes 8736
LO, LXO 20 A
I 14.88 7.88 16.00 2.56 9.75 15.00 0.50 3.66 21.25 0.31
SDA3 8903 SMO, SPO 30 A All 27
(378 (200 (406 (65 (248 (381 (13 (93 (540 (8)
(Form F4T) 60 A
8502 SDO
SDA4 2 All 27
8536 (Form F4T)
H

Figure 9
Table 17: Flush Mounting General Purpose Enclosures—see Figure 10

Class For Use With Dimensions, in. (mm)


Weight
9991 NEMA Size No. of (lb)
Type No. Class Type or A Rating Poles
A B C D E F G H

SDF13
15.19 8.94 7.63 12.88 5.44 10.94 5.13 0.38
(w/SDF1 8903 LO, LXO 20 A All 17
(386) (227) (194) (327) (138) (278) (130) (10)
& SDF2)
8502 SBO, SCO 0, 1 All
SCF11
8536 SBO, SCO 0, 1 All 13.44 7.19 5.88 11.13 4.75 9.19 4.50 0.38
C H (w/SCF1 10
(341) (183) (149) (283) (121) (233) (114) (10)
H E G & SCF2) SMO
8903 30 A All
(E.H.)
8502 SDO 2 All
A D F SDF11
8536 SDO 2 All 15.19 8.94 7.63 12.88 5.44 10.94 5.13 0.38
(w/SDF1 17
(386) (227) (194) (327) (138) (278) (130) (10)
& SDF2) SPO
8903 60 A All
(E.H.)
B
8502 SEO 3 All 31.00 16.75 14.25 26.25 8.00 0.18
SEF11 — — 48
Figure 10 8903 SQO 100 A All (787) (425) (362) (667) (203) (5)

in.
Dimensions
(mm)

8
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters Magnet Coils and Modification Kits
Replacement Parts Class 9998

Table 18: Replacement AC Magnet Coils for Magnetic Contactors and Starters
(See Table 21 on page 10 for the listing of mechanically held unlatch coils)
Suffix Number (the complete coil part number consists
Equipment To Be Serviced Coil Prefix, Coil VA
of the prefix or the Class and Type, followed by the suffix)
or Class Hz
In-
Device Size Type Poles and Type 24 V 110–115 V 120 V 208 V 220 V 240 V 277 V 380 V 440 V 480 V 550 V 600 V Sealed
rush
60 23 — 44 50 — 53 55 — — 62 — 65 150 30
2–6 9998L
50 24 44 45 52 53 54 — 60 62 63 65 66 140 30
L
60 23 — 44 50 — 53 55 — — 62 — 65 180 35
8–12 9998LH
Coils 50 24 44 45 — 53 54 — 60 62 — 65 — 170 35
30 A
for 60 23 — 44 50 — 53 55 — — 62 — 65 150 —
Present 2–4 9998L
LX 50 24 44 45 52 53 54 — 60 62 63 65 66 140 —
Design
Magnetic (Latch) 60 23 — 44 50 — 53 55 — — 62 — 65 180 —
6–12 9998LH
50 24 44 45 — 53 54 — 60 62 — 65 — 170 —
Contactors
and SA 60 23 — 45 52 — 54 55 59 — 62 — 65 165 33
00 All 9998SAC
Starters (Series B) 50 — 45 — — 54 — — — 62 — 65 — — —
Classes 00
8502, 0, 1, SA (Series A) 60 20 — 42 48 — 51 52 56 58 — 61 62 245 27
8536, All 31041-400
1–P & SB, SC & SM 50 22 42 43 — 51 53 — 57 60 60 62 64 232 26
8538, 30 A
8539,
8606, 60 16 — 38 44 — 47 49 53 — 57 — 60 311 37
2–3 31063-409
8630, 2& 50 17 38 39 — 47 48 — 54 57 — 60 61 296 36
SD & SP
8640, 60 A 60 16 — 38 44 — 47 49 53 — 57 — 60 438 38
8647, 4–5 31063-400
50 17 38 39 — 47 48 — 54 57 — 60 61 429 37
8650,
8651, 60 16 — 38 44 — 47 49 53 — 57 — 60 700 46
DPA12_, 2–3 31074-400
8702, 3& 50 17 38 39 — 47 48 — 54 57 — 60 61 678 47
SE, SQ &
8736, 100 A 60 — — 38 44 — 47 49 53 — 57 — 60 1185 85
SYD138 4–5 31091-400
8738, 50 — 38 39 — 47 48 — 54 57 58 60 61 1260 89
8739,
4& SF, SV & 60 — — 38 44 — 47 49 53 — 57 — 60 1185 85
8810, All 31091-400
200 A SYD230 50 — 38 39 — 47 48 — 54 57 58 60 61 1260 89
8811,
8812, SG, SX & 60 — — 09 15 — 18 19 21 — 24 — 29 2970 212
All 31096-400
8903, 5& SYD368 Series A 50 — 09 10 — 18 — — 22 24 — 29 30 2970 250
8910 300 A SG, SX & 60 — 50 50 51 52 52 53 54 55 55 — — 1300 14
and All 31096-320
SYD368 Series B 50 — 50 50 — 52 52 — 54 55 55 — — — —
8940
(except 6&7 SH & SJ 1780 48
NP) SY, SZ, SJ 2–3 Coil Part Number 3110440050 (All System Voltages)
400, 1960 59
(Electrically Held)
600 &
800 A SY, SZ, SJ 60 — — 09 15 — 18 19 — — 24 — 29 1530 —
2–3 31104-418
(Mechanically Held) 50 — 09 — — 18 — — — 24 — 29 — 1250 —

NEMA Size 5 E-Coil Modification Kit

These kits are for use with devices of the following Classes: 8502, 8536, 8538, 8539, 8606, 8630,
8640, 8647, 8650, 8651, 8702, 8736, 8738, 8739, 8810, 8811, 8812, 8910, and 8903.
The kits include the following:
• E-coil
• Armature
• Bottom magnet
• 15 A, 600 V fuse and holder (Class 9999SFR)
• Instruction manual

Table 19: Coil Modification Kits


Description Catalog Number
120 V 9998SG120
480 V 9998SG480
277 V 9998SG277
208 V 9998SG208
240 V 9998SG240
380 V 9998SG380

Table 20: How to Order


To Order, Specify Catalog Number
Coil Prefix and Suffix 31063-409-38
Class and Type plus Suffix 9998L23

9
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters Magnet Coils
Replacement Parts Class 9998

Table 21: Replacement AC Magnet Coils for Relays, Timers, and Contactors
Equipment Coil Suffix Number (the complete coil part number consists
Coil VA
To Be Serviced Prefix, of the prefix or the Class and Type, followed by the suffix)
Hz
or Class 110– In-
Device Type Poles and Type 24 V 120 V 208 V 220 V 240 V 277 V 380 V 440 V 480 V 550 V 600 V Sealed
115 V rush
Classes 8501 and 9050
8501 60 23 — 44 51 52 53 55 — — 62 — 65 148 23
X All 9998X [1]
(Relays) 50 24 44 — 52 53 — — — 62 — 65 — 143 25
60 W25A W31B W32A W34A W34B W35A W35B — W37B W38A W38B W39A 74 17
A All 2959-S49-
9050 50 W25B W32A W32B W34B W35A W35B W36A — W38A W38B W39A W39B 68 17
(Timer) 60 33 — 54 61 61 63 65 — 70 72 73 75 165 27
B [2] All 31017-400-
50 34 — 55 — 63 64 — — 72 73 75 76 155 27
Mechanically Held Unlatch Coils—Class 8903 (for latch coils, see Table 18 on page 9)
60 23 — 44 51 — 53 55 — — 62 — 65 25 —
LX All 9998LX
50 — 44 — — 53 — — — 62 — 65 — — —
60 W23B — W30B W33A — W33B W34A — — W36B — W37B 80 —
8903 SM, SP All 2959-S13
50 W24B W30B W31B — W33B W34B — W36A W36B — W37B — — —
(Lighting
Contactors) SQ, SV, SX, 60 03 — 09 15 — 18 20 — — 24 — 28 550 —
All 31096-416
SY, SZ 50 — 09 — — 18 — — 22 24 — 28 — — —
60 03 — 09 15 — 18 20 — — 24 — 28 2100 —
SJ All 31123-403
50 — 09 — — 18 — — 22 24 — 28 — — —
[1] To order an unlatch coil, add letter L to the Type number and letter B to the suffix number. Example: For a 120 V 60 Hz unlatch coil, order Class 9998 Type XL44B.
[2] Series C (double pole) and Series E (single pole).

Table 22: Replacement DC Magnet Coils for Magnetic Relays and Timers
Suffix Number (the complete coil part number consists
Equipment To Be Serviced Coil Prefix, Coil
or Class of the prefix or the Class and Type, followed by the suffix) Burden
Class Type Poles and Type 6V 12 V 18 V 24 V 32 V 48 V 64 V 72 V 90 V 110 V 115/ 125 V 220 V 230/ 250 V (Watts)
XD All 9998 XD 19 28 34 37 40 46 49 52 55 — 58 — 67 18
8501
XDL — 9998 XDL 19 28 34B 37B 40B 46B 49B 52B 55B — 58B — 67B 50
(Relays)
XUD All 9998 XUD 19 28 — 37 — 46 — — — — 58 [1] — 67 [1] 16
9050 C — 31018-400- 22 31 — 40 — 49 — — — — 61 — 70 14
(Timers) H — 4491S1 W21 W24 — W27 — W30 — — — — W34 — W37 14
[1] Not dual voltage rated; 250 Vdc only.

Table 23: Replacement Coil for 8903 Panel Board Lighting Contactors
Class Type Replacement Solenoid Catalog Number
120 V 9998PBV02
208 V 9998PBV08
8903 PB
240/277 V 9998PBV39
480 V 9998PBV28

Table 24: How to Order


To Order, Specify Catalog Number
• Class Number Class Type
• Type Number 9998 PBV02

10
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters Contact Kits and Control Transformers
Replacement Parts Class 9998

Class 9998 replacement parts kits are available for servicing Square D NOTE: Contact springs
relays, contactors, and starters as well as pressure, vacuum, and float are built into the contact
switches. Each kit contains the necessary movable and stationary contacts, carrier, and are not
contact springs (when required), and additional hardware needed to service available for NEMA
the devices listed below. When servicing devices with more poles than the Size 3 and above.
corresponding kit contains, you may need to order an additional kit.
Table 25: Magnetic Contactor and Starter Contact Kits Table 27: Manual Starter Contact Kits
Present Designs—NEMA, Type S Contactors Equipment To Be Serviced No. of
Equipment To Be Serviced No. of Poles Class 9998 Class 9998
NEMA Poles
Class Type Parts Kit Type No.
Class Type NEMA Size in Kit Parts Kit Type No. Size in Kit
SA (Series B) 00 3 SJ1 2510 M-0 3 ML1
3 SL2 Manual M-, T- M-1 &
8502 SB 0 3 ML2
4 SL12 Starters M-1P
8536
8538 SB, SC (Power Pole Adder) 0&1 1 SL22
1 & 1P 3 SL3
8539 SC
1 4 SL13
Table 28: Replacement Control
8547
8549 3 SL4 Transformers (150 VA)
8606 SD 2
8630
4 SL14 Class 8502, 8536 Type S Size 6
SD (Power Pole Adder) 2 1 SL24
8640 Voltage
8647 2 SL6 Part Number
SE 3 60 Hz 50 Hz
8702 3 SL7
8736 2 SL8 240/480–120 220/440–110 3110451250
8738 SF 4
3 SL9 208–120 — 3110451252
8739 2 SL10 277–120 — 3110451253
8810 SG 5
3 SL11 — 380–110 3110451254
8811
8812 2 SL25 600–120 550–110 3110451251
SH 6
8940 3 SL26
120–120 110–110 3110451255
2 SL30
SJ 7 240–120 220–110 3110451256
3 SL31
Lighting Contactors
Equipment To Be Serviced No. of Poles Class 9998
Table 29: Replacement Control
Class Type Rating (A) in Kit Parts Kit Type No. Transformers (200 VA)
L (Series C) & LX (Series B) 30 A 4 RA5B Class 8502/8536 Type S, Size 7
3 SL3 Voltage
SM 30 A
4 SL13 Part Number
60 Hz 50 Hz
3 SL4
SP 60 A 240/480–120 220/440–110 3112350150
4 SL14
2 SL6 208–120 — 3112350152
SQ 100 A
3 SL7 277–120 — 3112350153
2 SL8 — 380–110 3112350154
SV 200 A
3 SL9 600–120 550–110 3112350151
2 SL10 120–120 110–110 3112350155
SX 300 A
3 SL11
240–120 220–110 3112350156
8903 2 SL25
SY 400 A
3 SL26
2 SL32 Table 30: Class 8910, 8911, and 8965
SZ 600 A
3 SL33 Replacement Contact Kits
2 SL30
SJ 800 A Device To Be Serviced Class 9998
3 SL31
PBM, PBP 30, 60 A Class Class Class
2 PB2 1-Pole 3-Pole
PBN, PBQ 75, 100 A 8910 8911 8965 Series
Type No. Type No.
PBM, PBP 30, 60 A
Type Type Type
3 PB3 SYD138 — — — — SL27
PBN, PBQ 75, 100 A
SYD230 — — — — SL28
PBR, PBV, PBW 150, 200, 225 A 2 PB14 SYD368 — — — — SL29
PBR, PBV, PBW 150, 200, 225 A 3 PB15 DPA_50A DPSO5_ DPR5_ A, B DRC5 —
Obsolete Designs DPA_60 [1] DPSO6_ DPR6_ A, B DRC6 —
DPA_75A DPSO7_ — A DRC7 —
Equipment To Be Serviced No. of Poles in Class 9998 DPA_90A DPSO9_ — A DRC9 —
Class Type NEMA Size Kit Parts Kit Type No.
8502 & 3 SL2
8536 [1]
SA (Series A) 00
4 SL12 Table 31: Class 8965
8903
LL, L (Series A, B) & LX
20 A 4 RA5
Replacement Contact Kits
(Series A) Class
Device Device Class 9998 Device
9998
Type Series Kit Type Series
Table 26: How to Order Kit Type
To Order, Specify Catalog Number DPR53 A DRC5 (single-pole kit)
— —
DPR63 A DRC6 (single-pole kit)
• Class Number Class Type
RO10 A&B RA10 C RA14
• Type Number 9998 SL6
RO11 A&B RA11 C RA15
[1] Includes reversing, two speed, and similar devices. RO12 A&B RA12 C RA16
RO13 A&B RA13 C RA17
[1] For Class 8911, 60 A starter, use the 9998DRC7 contact kit.

11
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters Universal Baseplates and Overload Relay Parts
Replacement Parts Class 9998

Table 33: Contact Units for Melting Alloy Style Overload Relays
One normally closed contact, Class 9998 Type SO1, is provided in each overload relay block on
Type S starters, Sizes 00–6. (On the Size 5, Series A, a normally closed contact was provided with
each of the three overload relay blocks). The Class 9998 Type SO1 contact unit listed below is
provided as standard in each Class 9065 Type M melting alloy overload relay. Contact modules can be
easily replaced and are identified in Table 33. Isolated overload relay alarm circuit contacts are
available as an optional feature. A pilot light or alarm bell can be wired in series with this contact to
Class 9998 Type SO1 indicate that the overload relay has tripped. For further information on isolated alarm contacts, refer to
Class 9999 Types SO4 and SO5.

Magnetic Starter
Description Parts Kit Number
NEMA Size Type Series
00–4, 6 SA–SF, SH A
Standard N.C. contact unit Class 9998 Type SO1 [1]
00–6 SA–SH B
Standard N.C. contact unit 31102–514–50
5 SG A
N.C. and N.O. alarm (three point) contact unit 31102–514–51
[1] The Type SO1 is also the replacement contact unit for Class 9065 Type M melting alloy overload relays.

Overload Contact Unit


Part No. 31102–514–50 Table 34: Class 9998 Type UB Universal Baseplate
A universal baseplate may be used to retrofit a Square D Type S NEMA starter into an application that
is currently using a competitor’s NEMA starter. The universal baseplate is a metal plate that attaches
to the panel in the location of the starter to be replaced. The Type S starter then mounts to the
baseplate. It is available for NEMA Sizes 00–4, and mounting screws are provided with each plate.
The universal baseplate adapter allows the Type S starter to replace the following competitor’s
starters.

NEMA Size
Competitor’s Starter
Type UB01 Type UB02 Type UB03 Type UB04
Allen-Bradley 509 0, 1 2 3 4
Allen-Bradley 709 1 2 3 4
Cutler Hammer Freedom Series 00, 0, 1 2 3 4
Furnas ESP100 0, 1 2 3 4
Furnas INNOVA 0, 1 2 3 4
General Electric CR306 00, 0, 1 2 3 4

L1 L2 Table 35: Melting Alloy Overload Relay Jumper Strap Kits


Disconnecting Means Provided
by User or with Controller
Jumper strap kits are for use on three-phase manual or magnetic starters with melting alloy overload
relays only, where a three-phase starter is used to control a single-phase motor. These kits include two
1 L1 L2 L3
jumper straps, a wiring diagram showing how to wire a three-phase starter to control a single-phase
motor, and single-phase (one thermal unit) selection tables.
T1 T2 T3
For Starter Class 9998
T2 Class
T1 Size Type Kit Type Number
Three-Phase Starter
Motor Wired to Control a
Single-Phase Motor
00, 0, 1, 2, 5 (Series B), and M0 & M1 SA, SB, SC, SD, SG, and M & T (Manual) SO31
All 3, 4 SE, SF SO32
Melting Alloy Overload
Relay Jumper Strap Kits 5 (Series A) SG None Available

Table 36: How to Order


To Order, Specify Catalog Number
• Class Number Class Type
• Type Number 9998 UB02

12
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters Cover-Mounted Control Units and Closing Plates
Accessories Class 9999

Cover-Mounted Control Units

With the Class 9999 cover-mounted control unit kits, you can field install push buttons, selector
switches, and pilot lights into the enclosure cover of a NEMA 1, 3R, 4, or 12 Type S contactor or
starter. Knockouts or removable closing plates are furnished with many enclosure covers for
convenient field installation of control units. Kits include leads and clearly illustrated instructions.
The Class 9999 cover-mounted control unit kits are identical to the factory-installed units.
NOTE: No field modification kits are available for the polyester enclosures.

Table 37: Cover-Mounted Control Unit Selection (6–600 V, 50–60 Hz), Class 9999
NEMA 1 Kit NEMA 1 and 12/3R Kit
NEMA 4/4X Kit
For Use With Class 8538, 8539, or 8903 Class 8538, 8539, or 8903
(Stainless) [1]
Pre-Series K Series K and Later [1]
Red or Green Push Selector Red or Green Push Selector
Red or Green Pilot Light[2] Push Button Selector Switch
Pilot Light Button Switch Pilot Light Button Switch
NEMA
Size or No. of With Control Hand- Start- Hand- Start- Hand-
Class Type Start- On- On- 120 V 120 V
Rating Poles Transformer Standard Off- Stop or Off- Stop or Off-
Stop Off Off 60 Hz 60 Hz
(A) (Form F4T) Auto On-Off Auto On-Off Auto
Type Type Type Type Type Type Type Type Type Type Type Type
SA, SB, 00, 0, 1, [3]
All SP28R SP2R
SC 1P
SD 2 All SP28R [3] SP3R SA2 SA10 SC2 SC22
8502 2–3 SP28R [3] SP4R
8536 SE 3
4–5 SP28R [3] SP5R
SF 4 All SP28R [3] SP28R [3]
SA3 SA3 SC8 —
SG–SJ 5–7 All SP28R [3] SP28R [3]
SB, SC 0, 1 All SP12R SP12R SP28R [2], [3] SP29R [2], [3]
(incandescent) (incandescent)
8538 SD 2 All SP13R SP13R
8539 SA2 SA10 SC2 SC22 SPL28R SPL29R
SE 3 All SP14R SP14R SA3 [5] SC8 SA13 SC9
8702 (LED–Red) (LED–Red)
8736 SF 4 All SP15R SP15R SPL28G SPL29G
SG–SJ 5–7 All SP28R [3] SP28R [3] SA3 SA3 SC8 — (LED–Green) (LED–Green)
L 20 A All SP28R [3] — — SA10 [4] — SC22[4]
SM 30 A All SP28R [3] SP2R
8903 SA2 [5] SA10 [5] SC2 SC22
SP 60 A All SP28R [3] SP3R
(Elec-
trically SQ 100 A All SP28R [3] SP28R [3] SA3 [5] SA3 [5] SC8 —
Held) SJ, SV,
200–800
SX, SY, All SP28R [3] SP28R [3] SA3 [5] SA3 [5] SC8 —
A
SZ
[1] User-made openings are required in order to field install these modification kits on standard Class 8502 and 8536 Type S NEMA Size 0–2, and Class 8903 Size 30–60 A,
NEMA 4 and 12 enclosures.
[2] Each pilot light kit contains one red and one green lens cap.
[3] The pilot light rating must match the coil voltage. The listed kit contains one 120 Vac, 60 Hz red pilot light control unit, 9001KP1R31. For other voltages, refer to the 9001KP pilot light selection
tables in Section 19 of the Digest.
[4] To mount a control unit in a NEMA 1 enclosure, a 9999LX bracket is also required.
[5] Also requires an N.O. auxiliary contact for the holding circuit contact when used on Class 8903 electrically held lighting contactors.

Table 38: NEMA 1 Enclosure Closing Plates


For Use With
Type S Contactor Lighting Contactor Description Type
Class Type
NEMA Size Ampere Rating

SA–SE or For Pilot Light or Reset—Slip-on Cover, NEMA 1 Enclosure SG2


8502, 8536, 8903 00–3 30–60 A
SM–SP For Push Button or Selector Switch—Slip-on Cover, NEMA 1 Enclosure SG3
For Push Button or Selector Switch—Hinged Cover, NEMA 1 Enclosure SG1
8538, 8539 pre-Series K SB–SF 0–4 —
For Pilot Light—Hinged Cover, NEMA 1 Enclosure SG2
8538, 8539 Series J and later SB–SF 0–4 — Push Button or Pilot Light, NEMA Combination Starter Class9001
8903 SM–SV — 30–400 A Combination Lighting Contactor Type K51

Table 39: How to Order

To Order, Specify Catalog Number

Class Type
• Class Number
• Type Number
9999 SP29R

9999SP2R 9999SA2 9999SC2 9999SA3

13
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters Auxiliary Contacts
Accessories Class 9999

Auxiliary Contacts for Manual and Magnetic Contactors and Starters


Internal Contacts
The Class 9999 Type SX11 internal contact kit is a replacement unit for the N.O. holding circuit contact
that comes standard on Type S Size 00–2 three-phase starters and contactors. The Class 9999
Type SX12 is a replacement unit for the N.C. electrical contact that comes standard on Type S,
Size 00–2 mechanically interlocked devices (for example, Class 8736 reversing starters). Internal
Internal Auxiliary Contact contacts are also used on Class 2510 Type M and T manual starters. The internal contacts can be used
for other applications as long as the electrical rating is not exceeded. See Table 40 for electrical ratings.
External Contacts
The Class 9999 Type SX6 external auxiliary contact comes standard as the N.O. holding circuit
contact on Type S Size 3–7 starters and contactors. Additional auxiliary contacts can be added to
Type S contactors, starters, and lighting contactors. These contacts mount on either side of the basic
contactor, and are available with convertible or non-convertible contacts. The convertible contacts can
be changed from N.O. to N.C. or vice versa in the field. The non-convertible contacts are fixed, either
External Single-Circuit N.O. or N.C.
Auxiliary Contact
To determine the number of auxiliary contacts that can be added to each Type S contactor or starter,
refer to the Class 8536 (non-reversing starter) or Class 8736 (reversing starter) section of the Digest.
See Table 40 for electrical ratings.

Table 40: Maximum Ratings for Type S Auxiliary Contacts and Timers
Contact Ratings Contact Ratings
Class 9999 Class 9999
AC Only (35% Power Factor) AC Only (35% Power Factor)
Type No. Vac Continuous Type No. Vac Continuous
Make Break Make Break
≤120 30 A 3A 3A SX6–SX10 ≤120 60 A 6A 10 A
SX11, SX12
120–600 3600 VA 360 VA 3A SX13–SX17 120–600 7200 VA 720 VA 10 A

Table 41: Type S Contactors Table 42: Class 8965 Reversing/Hoist Contactors—
and Starters Auxiliary Contacts
For Use With Device To Be Serviced Auxiliary Contact Kit
Class 9999
Kit Description Class 8965 Contact Type of Class 9999
Type NEMA Size Type No.
Type No. Arrangement Connector Type No.
External—Field Convertible 1 N.O. D10
1 N.O. Contact SX6 1 N.C. D01
1 N.C. Contact SX7 Screw/
SA–SJ 00–7 DPR 1 N.O./1 N.C. D11
1 N.O. and 1 N.C. Isolated Contacts SX8 Quick Connect
1 N.O. Overlapping Contact SX9 [1]
1 N.C. Overlapping Contact SX10 [1] 2 N.O. D20

External—Non-Convertible RO2 & RG2


1 N.O.
1 N.O. Contact SX13 RO10 Form X1 R10
each side
1 N.C. Contact SX14 RO11 Form X1
SA–SJ 00–7 Slip-on
1 N.O. and 1 N.C. Isolated Contacts SX15 RO3 & RG3
1 N.O. Overlapping Contact SX16 [1] 1 N.C.
RO10 Form X2 R11
1 N.C. Overlapping Contact SX17 [1] each side
RO11 Form X2
RO5 & RG5
1 N.O.
RO12 Form X1 R12
Internal—Non-Convertible each side
RO13 Form X1
SA–SD 00–2 1 N.O. Contact SX11 [2] Screw
1 N.C. Contact SX12 [2] RO6 & RG6
1 N.C.
RO12 Form X2 R13
each side
RO13 Form X2
[1] Types SX9 and SX10 or Types SX16 and SX17 must be used together and mounted on the same side of the contactor. They are suitable for applications where it is necessary for a normally
open contact to overlap a normally closed contact.
[2] Types SX11 and SX12 are not applicable on NEMA Size 3 or larger. Internal contacts can also be used on Class 2510 Types M and T manual starters.

Table 43: Table 44: Class 8910 and 8911 Definite Purpose Contactors and Starters—
How to Order Auxiliary Contacts
Auxiliary Contact Kit, Class 9999
To Order, Catalog Definite Purpose
Contact 20–90 A 20–40 A
Specify Number Device
Arrangement Series B, and Series C after date code 1401 Series C before date code 1401
• Class Number Class Type 1 N.O. D10 DD10
Contactor
• Type Number 9999 R11 Class 8910 Type DPA 1 N.C. D01 DD01
Starter 1 N.O./1 N.C. D11 DD11
Class 8911 Type DPS 2 N.O. D20 DD20

14
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters Motor Logic™ Accessories
Accessories Class 9999

Motor Logic™ Solid-State Overload Relay Accessories

These Class 9999 accessories are for the Class 9065 Motor Logic solid-state overload relay (SSOLR).

Table 45: Isolated Auxiliary Contacts for Motor Logic Overload Relays
Overload relay auxiliary contacts are available factory installed or in kit form for field installation on
Motor Logic overload relays. These contacts can be used for isolated alarm contact applications.

For Use With


Parts Kit Description Class 9999 Type Number
Class and Type NEMA Size [1]
8536 SA–SJ 00B through 7 N.O. or N.C. Auxiliary
AC04
9065 SS, SR, SF, ST 00B through 7 Contact (Field Convertible)

Table 46: DIN Adapter


The DIN adapter mounts the Motor Logic overload relay to a 35 mm DIN rail.

For Use With


Parts Kit Description Class 9999 Type Number
Class and Type NEMA Size [1]
9065 SS or SF 00B, 00C, 0, and 1 DIN Adapter DA01

Table 47: Lug–Lug and Lug Extender Kits


Standard overload relays, Sizes 00B, 00C, 0, and 1 (Class 9065 Type SS and SF), come without lugs.
• A Class 9999 Type LL0 lug–lug kit can be field installed on separately mounted overload relays.
• A Class 9999 Type LB0 lug extender kit is designed for retrofit starter applications. This kit allows
the lugs to be in the same location as for the Class 9065 melting alloy overload relay, eliminating
the need for additional wire length.

For Use With Class 9999


Parts Kit Description
Class and Type NEMA Size [1] Type Number
Lug–Lug Kit
LL0
for separate mounting
9065 SS or SF 00B, 00C, 0, and 1 Lug Extender Kit
for retrofitting existing LB0
Type S NEMA starters

Table 48: Remote Reset Module


The remote reset module can easily be field installed on SSOLRs. This module allows the overload
relay to be reset from a remote location.

For Use With Class 9999


Parts Kit Description
NEMA Size [1] Class and Type Type Number
8536 SA–SJ Remote Reset Module
00B through 7 RR04
9065 SS, SR, SF, ST (120 Vac power required)
8536 SE–SF Top Mounting Bracket
3 and 4 RB34
9065 SS, SR, SF, ST (to mount the remote reset module on the top of the overload relay)
[1] Sizes 00B and 00C are not actual NEMA sizes. These designations differentiate the lower FLA of these devices from the NEMA Size 00 Motor Logic
SSOLR.

Table 49: How to Order SSOLR Accessories


To Order, Specify Catalog Number
• Class Number Class Type
• Type Number 9999 AC04

15
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters Power Pole Adders and Compression Lugs
Accessories Class 9999

Table 50: Power Pole Adders


One single- or double-circuit power pole kit can be field added to a Size 0–2, basic two- or three-pole
Type S contactor or starter, or to a 30–60 A lighting contactors. See the table below for selection. The
ratings for these power pole adders correspond to the NEMA contact ratings found in Section 16 of the
Digest. A two- or three-pole contactor or starter will accept only one single- or double-circuit unit. A
power pole cannot be used on four- or five-pole devices or on mechanically interlocked devices.
Adding a power pole to a Size 2 or 60 A device requires a coil change. Select a 4–5 pole coil from the
selection tables on page 9, or specify Form Y118 as noted in the footnote below. When adding a
Size 0–2 power pole kit to a Size 3–7 or 100–800 A device, an adapter bracket (Class 9999 Type
SBT1) is required.
The Class 9999 Types SB6–SB15 power pole kits are suitable for use with copper wire only.
Types SB21–25 come with lugs suitable for copper and aluminum wire.

Power Pole Adder Kit For Use with Type S NEMA Contactors For Use with Lighting Contactor Power Pole Adder Kit
Description Type Size Type Size Class 9999 Type No.
SB, SC 0, 1 SM 30 A SB6
One N.O.
SD 2 — — SB11 [1]
power pole adder
Class 9999 Type SB6 — — SP 60 A SB21 [1]
Single Power Pole Adder
SB, SC 0, 1 SM 30 A SB7
One N.C.
SD 2 — — SB12 [1]
power pole adder
— — SP 60 A SB22 [1]
SB, SC 0, 1 SM 30 A SB8
One N.O. and one N.C.
SD 2 — — SB13 [1]
power pole adder
— — SP 60 A SB23 [1]
SB, SC 0, 1 SM 30 A SB9
Two N.O.
SD 2 — — SB14 [1]
power pole adders
— — SP 60 A SB24 [1]
SB, SC 0, 1 SM 30 SB10
Two N.C.
SD 2 — — SB15 [1]
power pole adders
Class 9999 Type SB9 — — SP 60 A SB25 [1]
Double Power Pole Adder Adapter bracket SE–SJ 3–7 SQ–SZ & SJ 100–800 A SBT1
[1] To order a Size 2 or a 60 A power pole kit complete with a new starter coil, specify Form Y118, the voltage, and the frequency (for example, Class 9999
Type SB11 Form Y118, 120 V, 60 cycles.)

Table 51: Compression Lugs


A Class 9999 Type AL hardware kit is required to install Versa-Crimp™ compression lugs on
Class 8903 Type S, 100–800 A lighting contactors. The lugs are suitable for both copper and
aluminum wire.
One VCEL lug is required for each line or load terminal. Each Class 9999 Type AL hardware kit
includes mounting hardware for 3 terminals, line or load side.
Example: To install compression lugs on a 300 A three-pole device, line and load sides, order six
VCEL–060–12H1 lugs and two Class 9999 Type AL11 hardware kits.

For Use With Versa-Crimp Hardware Kit


Wire Range
Rating Class 8903 Type Number Catalog Number Class 9999 Type Number
100 A SQ VCEL–021–14S1 8–1/0 AWG Al/Cu None Required
VCEL–022–516H1 1–2/0 AWG Al/Cu 2-Pole: AL13
200 A SV VCEL–024–516H1 2/0–4/0 AWG Al/Cu 3-Pole: AL14
4-Pole: AL15
VCEL–030–516H1 4–300 MCM Al/Cu
VCEL–050–12H1 2/0–500 MCM Al/Cu
400–600 MCM Al
VCEL–060–12H1
300 A SX 400–500 MCM Cu AL11
500–750 MCM Al
VCEL–075–12H1
500 MCM Cu
400–600 MCM Al
400 A SY VCEL–060–12H2 [1]
400–50 0MCM Cu
Class 8903 with or or AL12
Compression Lugs 600 A SZ 500–750 MCM Al
VCEL–075–12H2 [1]
500 MCM Cu
Installed
Available only as a factory modification. Order Form Y1574. Specify wire size up to 750 MCM Al or
800 A SJ
500 MCM Cu and number of terminals.
[1] One or two lugs may be mounted on each terminal.

16
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters Accessories
Accessories Class 9999

Table 58: Control Circuit Fuse Holder The control circuit fuse holder is for use on Type S contactors and
Description (fuses not included) Class 9999, Type No.
starters, Sizes 00–7, when one or two control circuit fuses ≤600 V are
Single-Fuse Unit SF3
required. The Type SF3 and SF4 fuse holders accept standard 600 V
Single-Fuse Unit for Class CC Fuse SFR3 Bussmann® Type KTK or equivalent fuses (13/32 x 1-1/2"), 6 A maximum.
Two-Fuse Unit SF4 The SFR3 and SFR4 accept Class CC 600 V Bussmann Type KTK–R or
Two-Fuse Unit for Class CC Fuses SFR4 equivalent fuses only.

Table 59: Transient Suppression Module The transient suppression module is for use where the transient voltage
(generated when opening the coil circuit) interferes with the proper
Class 9999
Description operation of nearby integrated or solid-state control circuits. The module
Type Number
For Sizes 00–2 ST1 consists of an RC circuit and is designed to suppress the coil voltage
For Sizes 3–5 ST2 transients to approximately 200% of peak coil supply voltage. The module is
wired across the coil for Type S devices, Sizes 00–5, and is designed for
coil voltages of 120 V only.

Table 61: Isolated Alarm Contacts for Isolated overload relay alarm contacts are available factory installed or in
Melting Alloy Overload Relays kit form for field installation in Type S, NEMA Size 00–6 [1] starters and
Class 9065 Types M and S melting alloy overload relays.
Magnetic
Starter Class 9999
Description Parts Kit The Type S, NEMA Size 7 device uses a solid-state overload relay, which
NEMA Type No. has isolated alarm contacts as a standard feature. The alarm contacts allow
Type
Size
the starter to be used in applications that require isolated contacts, such as
N.O. Isolated Alarm Contact Plus
Standard N.C. Overload Contact
SO4 inputs to a computer.
00–6 [1] SA–SH
N.C. Isolated Alarm Contact Plus
Standard N.C. Overload Contact
SO5 Class 9999 Types SO4 and SO5 modules are interchangeable with the
[1]
standard module (Class 9998 Type SO1) and may be installed on starters
Isolated alarm contacts cannot be added in the field to the Type SG,
Size 5, series A starter. Current transformers and a Size 1 overload already in service. The case is made of clear plastic (polycarbonate) to
block must be used. For factory installation specify Form Y342.
allow for visual inspection of contacts.

Table 62: Tie Point Terminal Block The tie point terminal block provides easy wiring of a Hand-Off-Auto
selector switch or Start-Stop push buttons with separate control. The T7
Magnetic Contactor or Starter Class 9999
Type Number
terminal block requires no panel space. It simply snaps on Type S, Size 00–
NEMA Size Type
4 contactors and starters by two tabs, and is secured to the left hand coil
00–4 SA–SF T7
terminal.

Table 63: Solid Neutral Solid neutral—The Class 9999 Type SN kit can be used on Class 8903
Type S lighting contactors and other controllers where field addition of a
Number Wire Capacity Class 9999
of Lugs Per Lug (Cu/Al) Type Number solid neutral is required. Each kit has lugs suitable for both copper and
4 14 AWG – 2/0 AWG SN1 aluminum wire. The kit mounts with two screws.
(1) 4 AWG – 600 MCM or
3 SN2
(2) 1/0 AWG – 250 MCM
3 (Dual) (2) 2 AWG – 600 MCM SN3
2 (Dual) (2) 6 AWG – 350 MCM SN4

Table 64: How to Order


To Order, Specify Catalog Number
• Class Number Class Type
• Type Number 9999 ST2

Fuse Kit Class 9999 Type ST1 Tie Point Terminal Block Isolated Alarm Contact
Class 9999 Type SF4 Transient Suppression Module Type SO4

17
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
NEMA Contactors and Starters Mechanical Interlocks and Mounting Brackets
Accessories Class 9999

Mechanical Interlock

General: Type S contactors or starters can be mechanically interlocked so that only one device is
energized at a time. The mechanical interlock is an interference (non-jamming) type, locking at the
beginning of the stroke of any starter or contactor.
Type S Sizes 00–2: The mechanical interlock is mounted on the underside of the reversing baseplate.
Two pins extend from the mechanical interlock through openings in the baseplate and engage the
contact carrier of each contactor. Two styles of mechanical interlocks are used: one version for three-
pole contactors, and another version for four- or five-pole contactors.
NOTE: When adding a power pole to the left-hand side of an existing Size 0–2 three-pole reversing
Type SM1
contactor, a new mechanical interlock must also be installed. When added to the right-hand side
only, the power pole will not be mechanically interlocked with the left-hand contactor.
Type S Sizes 3–4: The mechanical interlock is separate from the mounting pan on Sizes 3–4. Cams
on the mechanical interlocks are operated by the contact carrier of each contactor. The mechanical
interlock is attached to the underside of the two contactor baseplates on Sizes 3–4.
Table 65: Mechanical Interlock for Two Contactors
The following mechanical interlock kits can be used to interlock 2–5 pole contactors. Mechanical
interlocks for horizontal and vertical arrangement are listed in various pole arrangements.

Contactor Kit, Class 9999


Mechanical Interlock Arrangements
NEMA Size Type Number

00, 0, 1 SM1

0, 1 SM2

Type SM12
0, 1 SM3

Horizontal Horizontal Vertical 0, 1 SM4


Type SM1 for Size 00–1 Type SM2 [1] for Size 0 or 1 Type SM2 [1] for Size 0 or 1
Type SM6 for Size 2 Type SM7 for Size 2 Type SM10 for Size 2
Type SM12 for Sizes 3–4 Type SM12 for Sizes 3–4 Type SM11 for Size 3 0, 1 SM5
Type SM13 for Size 4

2 SM6

2 SM7

2 SM8

2 SM9

2 SM10

Horizontal Vertical Vertical 3 SM11


Type SM3 for Size 0 or 1 Type SM4 for Size 0 or 1 Type SM5 for Size 0 or 1
Type SM8 for Size 2 Type SM9 for Size 2 Type SM11 for Size 3 3, 4 SM12
Type SM12 for Sizes 3–4 Type SM11 for Size 3 Type SM13 for Size 4
Type SM13 for Size 4 4 SM13

[1] The Type SM2 interlock is factory assembled for horizontal mounting but can easily be converted to vertical mounting. Conversion instructions are
included.

Table 66: Overload Relay Mounting Bracket


Mechanical interlocks, Types SM1–SM10 for Sizes 00–2 devices, use overload relay mounting
brackets to support the overload relay portion of the starter.

Kit Description Class 9999 Type Number


Bracket for one overload relay used with horizontal mechanical interlocks, Types SM1–SM10 SO11
Overload Relay Bracket for two overload relays used with vertical mechanical interlocks, Types SM2, SM4, SM5, SM9, and SM10 SO12
Mounting Bracket

18
© 1997–2017 Schneider Electric ™ 08/2017
All Rights Reserved
NEMA Contactors and Starters Fuse Clip and Auxiliary Contact Kits
Accessories Class 9422, 9999

Fuse Clip Kits

Table 67: Class 9422 Replacement Fuse Clip Kits


A Class 9422 fuse clip kit can convert the following non-fusible devices to fusible: Sizes 0–2, Type S
combination starters, Class 8538 (Series D and newer) and Class 8738 (Series E and newer); and 30–
60 A lighting contactors, Class 8903 (Series C and newer). Both fusible and non-fusible combination
devices have the same size enclosure in NEMA 1, 4, and 12 construction, which permits this
Class 9422 Type TC33 conversion. The 9422 fuse clip kits contain line and load fuse clips, load base, and fuse pullers.
Fuse Block
For Use On NEMA Class H, K, J, R Fuses NEMA Class R Fuses
Disconnect
Type S NEMA Combo Starter Lighting Contactor Fuse Clip Ratings (A) Rejection Kit
Rating (A) Class and Type
Size Ampere Rating 250 V Max. 600 V Max. Catalog Number [1]
0–30 — 9422TC30 [2] RFK03
0, 1 30 A 30
31–60 0–30 9422TC33 [2] RFK06
31–60 0–30 9422TC33 RFK06
2 60 A 60
— 31–60 9422TD63 RFK06H
[1] This is the full catalog number. No Class Number is required.
[2] When using the kit with a 9422 FTCN or FTCF disconnect switch in Class 8538 or 8738 combination starters, remove and discard the metal base plate.

Table 68: Table 69: Class 9999 Replacement Fuse Clip Kits (8538 Pre-Series D, 8738 Pre-Series E)
How to Order For Use On NEMA Class H Fuses NEMA Class R Fuses NEMA Class J Fuses
Specify Catalog Number Type S Lighting Disconnect Fuse Clip
Fuse Clip Ratings (A) Fuse Clip Ratings (A)
• Class Class Type Combo Contactor Rating (A) Type Type Ratings (A) Type
• Type 9999 R6 NEMA Size Rating (A) 250 V Max. 600 V Max. 250 V Max. 600 V Max. 600 V Max.
0–30 — S1 0–30 — SR1 — —
0, 1 30 A 30 — 0–30 S2 — 0–30 SR2 0–30 SJ2
31–60 0–30 S2 31–60 0–30 SR2 0–30 SJ2
31–60 0–30 S2 31–60 0–30 SR2 0–30 SJ2
2 60 A 60
— 31–60 S3 — 31–60 SR3 31–60 SJ3
61–100 61–100 S4 [1] 61–100 61–100 SR4 [2] 61–100 SJ4
3 100 A 100 [1] [2]
101–200 — S5 101–200 — SR4 — —
4 200 A 200 101–200 101–200 S5 [1] 101–200 101–200 SR4 [2] — —
5 300 A 400 — — — 201–400 201–400 SR5 [2] — —
6 400, 600 A 600 — — — 401–600 401–600 SR5 [2] — —
[1] Cannot be used in Series B or newer 8538 devices.
[2] Fuse clips are not included in the Type SR4 and SR5 kits. On new installations, Class 9999 Type S fuse clips must also be purchased. Three non-
removable pins are included and can be installed only in the latest production devices, which have a hole in the lower fuse clips.

Table 70: Class 9999 Auxiliary Contact Kits for Disconnect Switches and Circuit Breakers
For Use On Kit, Class 9999 Type
Class Type SPDT DPDT
8538, 8738 SB, SC (Series C) R45 R46
8539, 8739 SB, SC, SD, SE, SF, SG R26 R27
8538 SBA, SCA, SBG, SCG (Series K) TC11 TC21
8738 SBA, SCA, SBG, SCG (Series K) TC10 TC20
8538 SB [1], SC [1], SD [1] (Series B) R6 R7
8538 SBAS8, SCAS8, SBGS8, SCGS8 (Series K) TC10 TC20
8538, 8738 SD (Series C) R43 R44
8538 SDA, SDA [1], SDG, SDG [1] (Series K) TC10 TC20
8738 SDA, SDG (Series K) TC10 TC20
8538, 8738 SE (Series B and C) R41 R42
8538, 8738 SE, SF (Series A) R8 R9
8538, 8738 SF (Series B and C) R39 R40
8538, 8738 SG R35 R36
Disconnect Switches
9422 BTCF, BTCN, BTDF, BTEF, BTEN TC11 TC21
9422 TCF, TCN, TDF, TDN, TEF, TEN TC10 TC11
9422 TF R8 R9
Circuit Breaker Operating Mechanisms
9421 LF, LK, LL, LM, LN, LP, LR, LT, LW R47 R48
9422 RM, RN, RP, RQ, RR, RT R26 R27
9422 CFA, CKA, CLA, CSF, CMP R26 R27
[1] Class 8538 Type numbers ending in suffix S8.

19
08/2017 ™ © 1997–2017 Schneider Electric
All Rights Reserved
Schneider Electric USA, Inc.
800 Federal Street Schneider Electric and Square D are trademarks and the property of Schneider Electric SE, its
Andover, MA 01810 USA subsidiaries, and affiliated companies. All other trademarks are the property of their respective owners.
888-778-2733 9999CT9701R08/17 Replaces 9999CT9701R10/07
www.schneider-electric.us © 1997–2017 Schneider Electric All Rights Reserved

08/2017