IEEE384
IEEE384
                            Sponsor
                            Nuclear Power Engineering Committee
                            of the
                            IEEE Power Engineering Society
                            Abstract: The independence requirements of the circuits and equipment comprising or associated with
                            Class 1E systems are described. Criteria for the independence that can be achieved by physical separation
                            and electrical isolation of circuits and equipment that are redundant are set forth. The determination of what
                                                                                                                                                                          --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                            is to be considered redundant is not addressed.
                            Keywords: associated circuit, barrier, Class 1E, independence, isolation, isolation device, raceway,
                            separation
                            Use of an IEEE Standard is wholly voluntary. The existence of an IEEE Standard does not imply that there are no other
                            ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE
                            Standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change
                            brought about through developments in the state of the art and comments received from users of the standard. Every
                            IEEE Standard is subjected to review at least every Þve years for revision or reafÞrmation. When a document is more
                            than Þve years old and has not been reafÞrmed, it is reasonable to conclude that its contents, although still of some
                            value, do not wholly reßect the present state of the art. Users are cautioned to check to determine that they have the
                            latest edition of any IEEE Standard.
                            Comments for revision of IEEE Standards are welcome from any interested party, regardless of membership afÞliation
                            with IEEE. Suggestions for changes in documents should be in the form of a proposed change of text, together with
                            appropriate supporting comments.
                            Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as they relate to
                            speciÞc applications. When the need for interpretations is brought to the attention of IEEE, the Institute will initiate
                            action to prepare appropriate responses. Since IEEE Standards represent a consensus of all concerned interests, it is
                            important to ensure that any interpretation has also received the concurrence of a balance of interests. For this reason
                            IEEE and the members of its technical committees are not able to provide an instant response to interpretation requests
                            except in those cases where the matter has previously received formal consideration.
                                                                                                                                                         --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                            445 Hoes Lane
                                            P.O. Box 1331
                                            Piscataway, NJ 08855-1331
                                            USA
                                IEEE Standards documents are adopted by the Institute of Electrical and Electronics Engineers without regard to
                                whether their adoption may involve patents on articles, materials, or processes. Such adoption does not assume
                                any liability to any patent owner, nor does it assume any obligation whatever to parties adopting the standards
                                documents.
                                                                      (This foreword is not a part of IEEE Std 384-1992, IEEE Standard Criteria for Independence of Class 1E Equipment
                                                                      and Circuits.)
                                                                      This standard provides criteria and requirements for establishing and maintaining the independence of Class 1E
                                                                      equipment and circuits and auxiliary supporting features by physical separation and electrical isolation.
                                                                      This 1992 revision of IEEE Std 384-1981, IEEE Standard Criteria for Independence of Class 1E Equipment and
                                                                      Circuits, reßects the results of separation testing completed by the nuclear industry on internally generated electrical
                                                                      faults. The working group has performed the following activities:
                                                                          1)   Assessed completed industry test reports to determine their applicability in support of changes in separation
                                                                               distances and reported these results to the Nuclear Power Engineering Committee (NPEC).
                                                                          2)   Conducted a panel discussion on the test results at the 1988 Institute of Electrical and Electronics Engineers
                                                                               (IEEE) Winter Power Meeting.
                                                                          3)   Presented a technical paper on the test results at the 1989 IEEE Winter Power Meeting (IEEE Paper No. 90
                                                                               WM 254-3EC).
The working groupÕs review has resulted in changes to Section 6. of the standard as follows:
                                                                          1)   Separation distance criteria for conÞgurations identiÞed in IEEE Std 384-1981 have been reduced in some
                                                                               cases. In other cases, insufÞcient testing data were available to support reducing the distances in IEEE Std
                                                                               384-1981.
                                                                          2)   Separation distance criteria for conÞgurations not addressed in IEEE Std 384-1981 have been added to the
                                                                               standard based on test results. These conÞgurations include cable trays and conduits, cable trays and cable in
                                                                               free air, and conduits and cable in free air.
                                                                      Other sections of this standard have been reviewed, and many editorial improvements have been made. As part of this
                                                                      work, the working group assessed Nuclear Regulatory Commission (NRC) Regulatory Guide 1.75, Revision 2, which
                                                                      endorses IEEE Std 384-1974.
                                                                      A Request for Interpretation of IEEE 384-1977, Paragraph 6.1.2 (now 7.1.2), was received by the working group
                                                                      regarding the phrase Òmaximum credible voltage or current transient.Ó A deÞnition of this phrase has been added to the
                                                                      standard.
                                                                      A request for proposed revision from the DC Auxiliary Power Working Group (Nuclear Power Subcommittee of the
                                                                      Power Generation Committee) was received regarding the use of fuses as isolation devices in power circuits. The
                                                                      standard has been revised to permit the use of fuses as isolation devices in power circuits.
                                                                      Section 8 of IEEE Std 384-1981 was previously included to provide interim criteria for implementation of
                  --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                                                      independence requirements for safe shutdown systems required for exposure Þres. 10 CFR 50, Appendix R has since
                                                                      been issued to provide the requirements for safe shutdown; consequently, Section 8 has been eliminated from the
                                                                      present issue of this standard.
                                                                      The Working Group has received suggestions and recommendations regarding the application of Þber optic cabling to
                                                                      Class 1E circuits. However, to date, there have been no analyses or test programs submitted to the Working Group to
                                                                      support special criteria for separating these cables in a manner different than already provided by considering them
                                                                      equivalent to typical instrumentation cable. If sufÞcient information becomes available to justify special separation
                                                                      criteria, the Working Group will consider adding this criteria to the standard in a future revision.
                                                                      The IEEE has developed these criteria to provide guidance in the determination of the independence requirements
                                                                      related to the class 1E systems of the nuclear facility. Adherence to these criteria may not sufÞce for assuring the public
                                                                      health and safety, because it is the integrated performance of the structures, the ßuid systems, and the instrumentation
                                                                      and electric systems of the station that establish the consequences of accidents. Failure to meet these requirements may
                                                                      be an indication of system inadequacy. Each applicant has the responsibility to assure himself and others that this
                                                                      integrated performance is adequate.
                            The revision to this standard was prepared by Working Group SC 6.5 of Subcommittee 6 under the NPEC. At the time
                            this standard was approved, the members of Working Group SC 6.5 were as follows:
M. S. Zar, Chair
                            The Working Group acknowledges the contribution of T. S. Killen, former Working Group Chair, to the preparation of
                            this revision.
                            The following persons were on the balloting committee that approved this document for submission to the IEEE
                            Standards Board:
                                                                                                                                                          --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                     R. C. Carruth                        G. K. Henry                                            P. B. Stevens
                                     G. L. Doman                          J. D. Hutson                                           P. Szabados
                                     E. F. Dowling                        S. Kasturi                                             L. D. Test
                                     A. R. Ducharme                       J. T. Keiper                                           J. E. Thomas
                                     R. E. Dulski                         D. C. Lamken                                           J. T. Ullo
                                     R. Fleming                           J. D. Lamont                                           F. J. Volpe
                                     J. Forster                           A. Marion                                              M. S. Zar
When the IEEE Standards Board approved this standard on June 18, 1992, it had the following membership:
* Member Emeritus
                            iv
Copyright The Institute of Electrical and Electronics Engineers, Inc.
Provided by IHS under license with IEEE                                               Licensee=Alstom Power - Massy France/5956125004
No reproduction or networking permitted without license from IHS                      Not for Resale, 07/30/2008 00:32:14 MDT
                            Also included are the following nonvoting IEEE Standards Board liaisons:
                                                                               Paula M. Kelty
                                                                        IEEE Standards Project Editor
--`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                                                              CLAUSE                                                                                                                                                                 PAGE
                                                                              1.      Scope ...................................................................................................................................................................1
2. Purpose................................................................................................................................................................1
3. References ...........................................................................................................................................................1
4. Definitions...........................................................................................................................................................2
Annex A Relationship of Cable Testing Programs to IEEE Std 384-1992 (Informative) ............................................21
vi
1. Scope
                            This standard describes the independence requirements of the circuits and equipment comprising or associated with
                            Class 1E systems. It sets forth criteria for the independence that can be achieved by physical separation and electrical
                            isolation of circuits and equipment that are redundant, but does not address the determination of what is to be
                            considered redundant.
                                                                                                                                                                              --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                            2. Purpose
                            This standard establishes the criteria for implementation of the independence requirements of IEEE Std 603-1991
                            [12]1 and IEEE Std 308-1991 [8].
3. References
                            The following publications shall be used in conjunction with this standard. When they are superseded by an approved
                            revision, the revision shall apply:
                            [1] ANSI/ANS-58.2-1988, Design Basis for Protection of Light Water Nuclear Power Plants Against the Effects of
                            Postulated Pipe Rupture.2
[4] ANSI/NFPA 803-1988, Fire Protection for Light Water Nuclear Power Plants.
[5] ASTM E84-91a, Test Methods for Surface Burning Characteristics of Building Materials.4
                            1 The numbers in brackets correspond to the references listed in Section 3. of this standard.
                            2 ANS publications are available from the American Nuclear Society, 555 N. Kensington, La Grange Park, IL 60525.
                            3 NFPA publications are available from Publication Sales, National Fire Protection Association, 1 Batterymarch Park, P. O. Box 9101, Quincy, MA
                            02269-9101, USA.
                            4 ASTM publications are available from the Customer Service Department, American Society for Testing and Materials, 1916 Race Street,
                            Philadelphia, PA 19103, USA.
[6] ASTM E119-88, Method for Fire Tests of Building Construction and Materials.
[7] ASTM E136-92, Test for Behavior of Materials in a Vertical Tube Furnace at 750 °C.
                            [8] IEEE Std 308-1991, IEEE Standard Criteria for Class 1E Power Systems for Nuclear Power Generating Stations
                            (ANSI).
                            [9] IEEE Std 383-1974 (Reaff 1992), IEEE Standard for Type Test of Class 1E Electric Cables, Field Splices, and
                            Connections for Nuclear Power Generating Stations (ANSI).5
                            [10] IEEE Std 420-1982, IEEE Standard for the Design and QualiÞcation of Class 1E Control Boards, Panels, and
                            Racks Used in Nuclear Power Generating Stations (ANSI).
                            [11] IEEE Std 494-1974 (Reaff 1990), IEEE Standard Method for IdentiÞcation of Documents Related to Class 1E
                            Equipment and Systems for Nuclear Power Generating Stations (ANSI).
[12] IEEE Std 603-1991, IEEE Standard Criteria for Safety Systems for Nuclear Power Generating Stations.
                            [13] IEEE Std 628-1987, IEEE Standard Criteria for the Design, Installation, and QualiÞcation of Raceway Systems
                            for Class 1E Circuits for Nuclear Power Generating Stations (ANSI).
                            [14] IEEE Std 690-1984, IEEE Standard for the Design and Installation of Cable Systems for Class 1E Circuits in
                            Nuclear Power Generating Stations.
4. Definitions
                            design basis events: Postulated abnormal events used in the design to establish the acceptable performance
                            requirements of the structures, systems, and components.
                            division: The designation applied to a given system or set of components that enables the establishment and
                            maintenance of physical, electrical, and functional independence from other redundant sets of components.
                            5 IEEE publications are available from the Institute of Electrical and Electronics Engineers, Service Center, 445 Hoes Lane, P.O. Box 1331,
                            Piscataway, NJ 08855-1331.
                            6 NEMA publications are available from the National Electrical Manufacturers Association, 2101 L Street, NW, Washington, DC 20037, USA.
                            NOTE Ñ The terms division, train, channel, separation group, safety group, or load group, when used in this context, are
                                   interchangeable.
                            enclosure: An identiÞable housing, such as a cubicle, compartment, terminal box, panel, or enclosed raceway, used for
                            electrical equipment or cables.
                            ßame retardant: Capable of limiting the propagation of a Þre beyond the area of inßuence of the energy source that
                            initiated the Þre.
                            independence: The state in which there is no mechanism by which any single design basis event, such as a ßood, can
                            cause redundant equipment to be inoperable.
                            isolation device: A device in a circuit that prevents malfunctions in one section of a circuit from causing unacceptable
                            inßuences in other sections of the circuit or other circuits.
                            maximum credible voltage or current transient: That voltage or current transient that may exist in circuits, as
                            determined by test or analysis, taking into consideration the circuit location, routing, and interconnections combined
                            with failures that the circuits may credibly experience.
                            raceway: Any channel that is designed and used expressly for supporting or enclosing wires, cable, or busbars.
                            Raceways consist primarily of, but are not restricted to, cable trays and conduits.
                            redundant equipment or system: Equipment or system that duplicates the essential function of another piece of
                            equipment or system to the extent that either may perform the required function regardless of the state of operation or
                            failure of the other.
                            safety class structures: Structures designed to protect Class 1E equipment against the effects of the design basis
                            events.
                            NOTE Ñ For the purposes of this standard, separate safety class structures can be separate rooms in the same building. The rooms
                                   may share a common wall.
                            separation distance: Space that has no interposing structures, equipment, or materials that could aid in the
                            propagation of Þre or that could otherwise disable Class 1E systems or equipment.
                            Physical separation and electrical isolation shall be provided to maintain the independence of Class 1E circuits and
                            equipment so that the safety functions required during and following any design basis event can be accomplished.
                                                                                                                                                                 --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                            The physical separation of circuits and equipment shall be achieved by the use of safety class structures, separation
                            distance, or barriers or any combination thereof. Electrical isolation shall be achieved by the use of separation distance,
                            isolation devices, shielding and wiring techniques, or combinations thereof.
                            Equipment and circuits requiring independence shall be determined and delineated during the plant design and shall be
                            identiÞed on documents and drawings in a distinctive manner. (See IEEE Std 494-1974 [11] for guidance in
                            identiÞcation.)
                            The independence of Class 1E circuits and equipment shall not be compromised by the functional failure of auxiliary
                            supporting features. For example, an auxiliary supporting feature (such as Class 1E switchgear room ventilation) shall
                            be assigned to the same division as the Class 1E system it is supporting in order to prevent the loss of mechanical
                            function in one division from causing loss of electrical function in another division.
5.5.1 General
Non-Class 1E power, control, and instrumentation circuits become associated in one or more of the following ways:
                                   1)       Electrical connection to a Class 1E power supply without the use of an isolation device. (See Fig 1.)
                                   2)       Electrical connection to an associated power supply without the use of an isolation device. (See Fig 1.)
                                   3)       Proximity to Class 1E circuits and equipment without the required physical separation or barriers. (See
                                            Fig 2.)
                                   4)       Proximity to associated circuits and equipment without the required physical separation or barriers. (See
                                            Fig 2.)
                                   5)       Sharing a Class 1E or associated signal source without the use of an isolation device. (See Figs 3 and 8.)
--`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
5.5.2 Criteria
                                                                               1)   They shall be uniquely identiÞed as such or as Class 1E and shall remain with (traceable to the associated
                                                                                    Class 1E division), or be physically separated the same as, those Class 1E circuits with which they are
                                                                                    associated. They shall be subject to the requirements placed on Class 1E circuits, unless it can be
                                                                                    demonstrated by analysis or testing that the absence of such requirements cannot degrade the Class 1E
                                                                                    circuits below an acceptable level.
                                   2)       They shall be in accordance with (1) above from the Class 1E equipment to and including an isolation device.
                                            Beyond the isolation device, such a circuit is non-Class 1E provided that it does not again become associated
                                            with a Class 1E system.
                                   3)       They shall be analyzed or tested to demonstrate that Class 1E circuits are not degraded below an acceptable
                                            level.
                            NOTE Ñ Preferred power supply circuits from the transmission network and those similar power supply circuits from the unit
                                   generator that become associated circuits solely by their connection to the Class 1E distribution system input terminals
                                   are exempt from the requirements for associated circuits.
                            Associated circuits, including their isolation devices or the connected loads without the isolation devices, shall be
                            subject to the qualiÞcation requirements placed on Class 1E circuits to assure that the Class 1E circuits are not
                            degraded below an acceptable level. Associated circuits need not be qualiÞed for performance of function, since the
                            function is non-Class 1E.
                            The independence of non-Class 1E circuits from Class 1E circuits or associated circuits shall be achieved by
                            complying with the following requirements:
                                   1)       Non-Class 1E circuits shall be physically separated from Class 1E circuits and associated circuits by the
                                            minimum separation requirements speciÞed in 6.1.3, 6.1.4, 6.1.5, or 6.6, except as permitted in 5.6 (4), or the
                                            non-Class 1E circuits shall be associated circuits. (See Fig 2.)
                                   2)       Non-Class 1E circuits shall be electrically isolated from Class 1E circuits and associated circuits by the use
                                            of isolation devices, shielding, and wiring techniques or separation distance, except as permitted in 5.6 (4), or
                                            the non-Class 1E circuits shall be associated circuits. (See Fig 1.)
                                                                                                                                                                          --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                   3)       The effects of less than minimum separation or the absence of electrical isolation between the non-Class 1E
                                            circuits and the Class 1E circuits or associated circuits shall be analyzed to demonstrate that Class 1E circuits
                                            are not degraded below an acceptable level or the non-Class 1E circuits shall be associated circuits.
                                   4)       Non-Class 1E instrumentation signal and control circuits (see IEEE Std 690-1984 [14]) are not required to be
                                            physically separated or electrically isolated from associated circuits provided that (a) the non-Class 1E
                                            circuits are not routed with associated cables of a redundant division and (b) the non-Class 1E circuits are
                                            analyzed to demonstrate that Class 1E circuits are not degraded below an acceptable level. As part of the
                                            analysis, consideration shall be given to potential energy and identiÞcation of the circuits involved.
                            Class 1E circuits shall be routed or protected so that failure of the mechanical equipment of one division cannot disable
                            Class 1E circuits or equipment essential to the performance of the safety function by the systems of the redundant
                            division(s). The effects of failure or misoperation of a mechanical system on its own division shall be considered when
                            the Class 1E circuits or equipment are required to mitigate the consequences of such failure or misoperation. The
                            effects of pipe whip, jet impingement, water spray, ßooding, radiation, pressurization, elevated temperature, or
                            humidity on redundant electrical systems caused by failure, misoperation, or operation of mechanical systems shall be
                            considered. The potential hazard of missiles resulting from failure of rotating equipment or high energy systems shall
                            be considered.
                            Independence and redundance of required Class 1E systems shall be maintained during and subsequent to failure of
                            structures and equipment not qualiÞed for design basis events.
                                                                             In areas where redundant division equipment and circuits must be placed within the area of inßuence of a Þxed Þre
                                                                             protection system, the design of the equipment and circuits and the Þre protection system shall be coordinated so that
                                                                             the independence of the Class 1E system will not be compromised.
5.10 Fire
                                                                             5.10.1
                         --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                                                             An electrically generated Þre in one Class 1E division shall not cause a loss of functions in its redundant Class 1E
                                                                             division.
5.10.2
                                                                             The independence of redundant Class 1E circuits and equipment shall be such that a Þre in a Þre hazard area shall not
                                                                             prevent the capability to perform safety functions.
6.1.1 General
                                                                             The areas through which Class 1E and associated circuits cables are routed and in which equipment is located shall be
                                                                             reviewed for the existence of potential hazards such as high energy piping, missiles, combustible material, ignition
                                                                             sources, and ßooding. These areas shall be classiÞed as follows:
                                                                             Separation commensurate with the damage potential of the hazard shall be provided for early in the design through the
                                                                             use of features such as separate rooms. Opposite sides of rooms or areas may be used provided that there is an adequate
                                                                             heat removal capability.
                                                                             The minimum separation distances speciÞed in 6.1.3, 6.1.4, and 6.1.5 may be used to provide adequate physical
                                                                             separation if the following criteria are met:
                                                                                 1)   All cables involved shall meet the Þre propagation requirements of IEEE Std 383-1974 [9].
                                                                                 2)   Exposed raceways other than conduit shall be noncombustible per ASTM E136-92 [7]. Exposed conduit shall
                                                                                      meet the requirements of metallic conduit per IEEE Std 628-1987 [13].
                                                                                 3)   Raceway Þre stops through Þre barriers shall have a Þre-resistance rating commensurate with the Þre hazards
                                                                                      being protected against.
                                                                                 4)   Open trays shall be as deÞned in NEMA VE 1-1991 [15] for ladder or trough-type.
                                                                                 5)   Enclosed trays shall be solid-bottom-type as deÞned in NEMA VE 1-1991 [15] with a solid cover or open
                                                                                      trays with solid top and bottom covers.
                            These distances reßect the minimum acceptable for physical separation to maintain independence. Other
                            considerations such as maintenance, cable pulling, and termination may require greater distances.
In 6.1.3, 6.1.4, and 6.1.5, separation distances are grouped into the following three categories:
                                   1)       Open to open: Includes open tray to open tray, open tray to free-air cable, and free-air cable to free-air cable
                                            conÞgurations.
                                   2)       Enclosed to enclosed: Includes enclosed tray to enclosed tray, enclosed tray to conduit, and conduit to conduit
                                            conÞgurations.
                                   3)       Enclosed to open: Includes enclosed tray to open tray, enclosed tray to free-air cable, conduit to open tray,
                                            and conduit to free-air cable conÞgurations.
                            NOTE Ñ For the purposes of this standard, conduit encompasses the following: rigid steel, rigid aluminum, electrical metallic
                                   tubing, ßexible metal with or without coating, and intermediate metal.
If lesser separation distances are necessary they shall be established as in 6.1.1.3 to meet practical plant constraints.
                            Lesser separation distances than those speciÞed in 6.1.3, 6.1.4, and 6.1.5 can be established by analysis of the
                            proposed cable installation. For lesser separation distances than those speciÞed in 6.1.3 and 6.1.4, this analysis shall be
                            based on tests performed to determine the ßame retardant characteristics of the proposed cable installation considering
                            features such as insulation and jacket materials, raceway Þll, raceway types, and arrangements. For lesser separation
                            distances than those speciÞed in 6.1.5, the degree of hazards (such as size of the Þre or pipe break) and mitigative
                            measures (such as sprinklers) shall be considered.
6.1.2 Identification
                            Exposed Class 1E and associated circuit cable raceways shall be permanently marked in a distinct manner at intervals
                            not to exceed 15 ft (4.5 m) and at points of entry to and exit from enclosed areas. Class 1E and associated circuit cable
                            raceways shall be marked prior to the installation of their cables. Cables installed in these raceways shall be marked in
                            a manner of sufÞcient durability and at intervals of approximately 5 ft (1.5 m) to facilitate initial veriÞcation that the
                            installation is in conformance with the separation criteria. These cable markings shall be applied prior to or during
                            installation.
                            Class 1E and associated circuit cables shall be identiÞed by a permanent marker at each end in accordance with the
                            design drawings or cable schedule.
                                                                                                                                                                          --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                            The method of identiÞcation used to meet the above requirements shall readily distinguish between redundant Class
                            1E systems, between Class 1E and non-Class 1E systems, and between associated cables of different redundant Class
                            1E systems.
                            The minimum separation distances used for these areas are based on hazards being limited to failures or faults internal
                            to the electrical equipment or cables.
                            An area meeting the following requirements may be designated as a nonhazard area (previously called the cable
                            spreading room).
                                   1)       The area shall not contain high energy equipment such as switchgear, transformers, rotating equipment, or
                                            potential sources of missiles or pipe failure hazards, or Þre hazards.
                                                                           2)   Circuits in the area shall be limited to control and instrument functions and those power supply circuit cables
                                                                                and equipment serving the equipment located within the area.
                                                                           3)   Power circuit cables in this area shall be installed in enclosed raceways.
                                                                           4)   Administrative control of operations and maintenance activities shall control and limit introduction of
                                                                                potential hazards into the area.
                   --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
NOTE Ñ Refer to IEEE Std 690-1984 [14] for deÞnitions of power, control, and instrumentation cables.
                                                                           1)   The area shall be bounded by and separated from any other adjacent area by a Þre barrier having a Þre
                                                                                resistance rating commensurate with the Þre hazard that can exist. In lieu of this, a 3-hour Þre barrier shall be
                                                                                used. (See ANSI/NFPA 803-1988 [4] for Þre barrier requirements and deÞnitions.)
                                                                           2)   The area shall be bounded by and separated from any adjacent pipe hazard area or missile hazard area by a
                                                                                barrier capable of withstanding the design basis hazard at that location.
The minimum separation distances for circuits requiring separation per Section 5. are identiÞed in Table 1.
                                                                                                                                                                       --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                                                        Figure 4ÑExamples of Separation Distances
                            Where the above minimum separation distances cannot be maintained, barriers shall be provided between those
                            circuits requiring separation. Figures 5, 6, and 7 illustrate examples of acceptable arrangements of barriers in which
                            the minimum separation distance cannot be maintained.
                            The minimum separation distances used for these areas are based on hazards being limited to failures or faults internal
                            to the electrical equipment or cables. Limited hazard areas (previously called general plant areas) are those plant areas
                            from which potential hazards such as missiles, non-electrically induced Þres, and pipe failure are excluded.
                            NOTE Ñ In both a limited hazard area and a nonhazard area, the only energy available to damage electrical circuits is that energy
                                   associated with failure or faults internal to electrical equipment or cables within the area. The primary difference
                                   between a limited hazard area and a nonhazard area is that power circuits and equipment are restricted in the nonhazard
                                   areas.
                            The minimum separation distances for circuits requiring separation per Section 5. are identiÞed in Table 2. This table
                            includes three columns that provide minimum distance requirements based on the types and sizes of the cables
                            involved in each interaction.
                                   Open to open                         1 in (2.5 cm) horizontal,                         6 in (15 cm) horizontal,                        3 ft (0.9 m) horizontal,
                                   configurations                       3 in (7.5 cm) vertical                            12 in (0.3 m) vertical                          5 ft (1.5 m) vertical
                                   Enclosed to enclosed                 1 in (2.5 cm) horizontal,                         1 in (2.5 cm) horizontal,                       1 in (2.5 cm) horizontal,
                                   configurations                       1 in (2.5 cm) vertical                            1 in (2.5 cm) vertical                          1 in (2.5 cm) vertical
                                   Enclosed to open                     1 in (2.5 cm) horizontal,                         6 in (15 cm) horizontal,                        3 ft (0.9 m) horizontal,
                                   configurations                       3 in (7.5 cm) vertical*                           12 in (0.3 m) vertical                          5 ft (1.5 m) vertical
                                 *Vertical separation may be reduced to 1 in (2.5 cm) if the enclosed is below the open.
                                   The minimum separation may be reduced to 1 in (2.5 cm) horizontal and 3 in (7.5 cm) vertical if the circuits in the open configuration are
                                 limited to control and instrumentation circuits.
                            Where the minimum separation distances in Table 2 cannot be maintained, barriers shall be provided between those
                            circuits requiring separation. Figures 5, 6, and 7 illustrate examples of acceptable arrangements of barriers in which
                            the minimum separation distance cannot be maintained.
                            Independence of redundant Class 1E systems must be maintained at an acceptable level in hazard areas by cable
                            routing restrictions or by a combination of special physical separation, as required by 6.1.6, 6.1.7, and 6.1.8.
The minimum distance between non-Class 1E circuits and Class 1E or associated circuits shall be as provided in 6.1.4.
                            An area shall be designated a pipe failure hazard area if it contains piping normally operating at high or moderate
                            energies. See ANSI/ANS 58.2-1988 [1].
                            For moderate energy piping, pipewhip and jet impingement need not be considered; however, the wetting and
                            environmental effects must be considered.
                            Protection of nonhazard and limited hazard areas from pipe failure hazard areas shall be accomplished by the use of
                            barriers, restraints, separation distance, or appropriate combination thereof.
                            The routing of Class 1E or associated circuit cables or raceways in pipe failure hazard areas shall conform to the
                            following requirements, unless it can be demonstrated that pipe failure cannot prevent the Class 1E circuits and
                            equipment from performing their safety function:
                            12                                                        --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                                                                                                                                             Copyright © 1992 IEEE All Rights Reserved
                                   1)       Where the piping involved is qualiÞed for design basis events, is not assignable to a single division, and the
                                            pipe failure requires no protective action; Class 1E or associated circuit cables or raceways routed through the
                                            area shall be limited to a single division.
                                   2)       Where the pipe failure requires protective action, Class 1E or associated circuit cables or raceways shall not
                                            be routed through the area except those cables (see NOTE) that must terminate at devices or loads within the
                                            area.
                                            NOTE Ñ Special provisions (such as additional system redundancy or diversity) may be required for these cables to
                                                   meet the single failure criteria.
                                   3)       Where the piping involved is qualiÞed for design basis events, is assignable to a single division, and the pipe
                                            failure requires no protective action, Class 1E or associated circuit cables or raceways routed through the area
                                            shall be limited to the same division as the piping.
                                   4)       Where the piping involved is not qualiÞed for design basis events, Class 1E or associated circuit cables or
                                            raceways shall not be located in the area, except for those cables that must terminate at devices or loads within
                                            the area.
                                            NOTE Ñ Where Class 1E or associated circuit cables and raceways are routed in areas that have been classiÞed as
                                                   hazard areas due to nonqualiÞed piping, they must be protected from the area by the methods speciÞed in
                                                   6.1.6.2, or the piping involved must be qualiÞed for design basis events.
                            An area shall be designated a missile hazard area if it contains any missile source having sufÞcient kinetic energy
                            under design basis event conditions to damage redundant Class 1E circuits routed through the area and separated as
                            stated in 6.1.4.
                            Protection of nonhazard and limited hazard areas from missile hazard areas shall be accomplished by the use of
                            barriers, orientation, separation distance, or appropriate combination thereof.
                            The routing of Class 1E or associated circuit cables or raceways through the area shall conform to the following
                            requirements:
                                   1)       Where the missile source involved is qualiÞed for design basis events, is not assignable to a single division,
                                            and the effect of the missile does not require protective action; Class 1E or associated cables or raceways
                                            routed through the area shall be limited to a single division.
                                   2)       Where the effect of the missile source involved requires protective action, Class 1E or associated circuit
                                            cables or raceways shall not be routed through the area, except those cables (see NOTE) that must terminate
                                            at devices or loads within the area.
                                            NOTE Ñ Special provisions (such as additional redundancy or diversity) may be required for these cables to meet the
                                                   single failure criteria.
                                   3)       Where the missile source involved is qualiÞed for design basis events, is assignable to a single division, and
                                            the effect of the missile involved requires no protective action; Class 1E or associated circuit cables or
                                            raceways routed through the area shall be limited to the same division as the missile source.
                                   4)       Where the missile source involved is not qualiÞed for design basis events, Class 1E or associated circuit
                                            cables or raceways shall not be routed in the area, except for those cables that must terminate at devices
                                            within the area.
                                            NOTE Ñ Where Class 1E or associated circuit cables and raceways are routed in areas that have been classiÞed as
                                                   hazard areas due to nonqualiÞed missile sources, they must be removed from that area by the methods in
                                                   6.1.7.2 or the missile source must be qualiÞed for design basis events.
An area shall be designated a Þre hazard area if it contains any of the following potential hazards:
                                   1)       Liquids which are classiÞed as ßammable or combustible per ANSI/NFPA 321-1987 [3].
                                            Solids7 exhibiting a ßame spreading classiÞcation of 26 or higher per ASTM E84-91a [5].
                                                                                                                                                                            --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                   2)
                                   3)       Coatings exhibiting a ßame spread classiÞcation of 50 or higher per ASTM E84-91a [5].
                            An area need not be designated a Þre hazard area if administrative control provides suppression measures for
                            temporary ignition source use or the introduction of the above hazards is temporary or limited to an acceptable
                            quantity.
                            Protection of a nonhazard or limited hazard area from a Þre hazard area shall be accomplished by the use of Þre
                            barriers or separation distance, or both, as follows: SD + 17B ³50 where SD is the separation distance from hazard to
                            nonhazard and limited hazard areas in feet, and B is the Þre barrier Þre resistance rating per ASTM E119-88 [6] in
                            hours (derived from ANSI/NFPA 80A-1987 [2]).
                            Lesser separation may be utilized if a test or analysis, taking into account the potential duration and intensity of the Þre
                            source, demonstrates that the effects of lesser separation do not degrade Class 1E circuits below an acceptable level.
                            The routing of Class 1E or associated circuit cables or raceways in Þre hazard areas shall conform to the following
                            requirements:
                                   1)       Where the Þre hazard source involved is qualiÞed for design basis events, is not assignable to a single
                                            division, and the Þre requires no protective action; Class 1E or associated circuit cables or raceways routed
                                            through the area shall be limited to a single division.
                                   2)       Where the effect of the Þre hazard requires protective action, Class 1E or associated circuit cables or
                                            raceways shall not be routed through the area, except those cables that must terminate at devices or loads
                                            within the area.
                                            NOTE Ñ Special provisions (such as additional system redundancy or diversity) may be required for these cables to
                                                   meet the single failure criteria.
                                   3)       Where the Þre hazard source involved is qualiÞed for design basis events, is assignable to a single division,
                                            and protective action is not required; Class 1E or associated circuit cables or raceways routed through the area
                                            shall be limited to the same division as the Þre hazard.
                                   4)       Where the Þre hazard source involved is not qualiÞed for design basis events, Class 1E or associated circuit
                                            cables or raceways shall not be routed in the area except for those cables that must terminate at devices within
                                            the area.
                                            NOTE Ñ Where Class 1E or associated circuit cables and raceways are routed in the areas that have been classiÞed as
                                                   hazard areas due to nonnuclear safety-related Þre hazard sources, they must be protected from that area by the
                                                   methods in 6.1.8.2.
Redundant Class 1E standby generating units shall be placed in separate safety class structures.
7Excluding cables.
                            The auxiliaries and local controls for redundant standby generating units shall be located in the same safety class
                            structure as the unit they serve or be physically separated in accordance with the requirements of Section 5..
6.3 DC System
6.3.1 Batteries
                            Battery chargers for redundant Class 1E batteries shall be physically separated in accordance with the requirements of
                            Section 5.
6.4.1 Switchgear
                            Redundant Class 1E distribution switchgear groups shall be physically separated in accordance with the requirements
                            of Section 5..
                            Redundant Class 1E motor control centers shall be physically separated in accordance with the requirements of
                            Section 5.
Redundant Class 1E distribution panels shall be physically separated in accordance with the requirements of Section 5.
                            Redundant Class 1E containment electrical penetrations shall be physically separated in accordance with the
                            requirements of Section 5.. Compliance with Section 5. will generally require that redundant penetrations be widely
                            dispersed around the circumference of the containment. The minimum physical separation for redundant penetrations
                            shall meet the requirements for cables and raceways given in 6.1.4 and 6.1.5.
                            Non-Class 1E circuits routed in penetrations containing Class 1E circuits shall be treated as associated circuits in
                            accordance with the requirements of 5.5.
                            Main control switchboards shall be located in a non-hazard area within a safety class structure. Local control
                            switchboards shall be located in accordance with 6.1.
                            Separation of redundant Class 1E equipment and circuits may be achieved by locating them on separate control
                            switchboards physically separated in accordance with the requirements of 6.1. Where operational considerations
                                                                         dictate that redundant Class 1E or Class 1E and non-Class 1E equipment be located on a single control switchboard or
                                                                         cabinet, the requirements of 6.6.2, 6.6.3, 6.6.4, 6.6.5, and 6.6.6 shall apply.
                                                                         The minimum separation distance between circuits requiring separation per Section 5. that are internal to the control
                                                                         switchboards can be established by analysis of the proposed installation. This analysis shall be based on tests
                                                                         performed to determine the ßame retardant characteristics of the wiring, wiring materials, equipment, and other
                                                                         materials internal to the control switchboard. Where the control switchboard materials are ßame-retardant and analysis
                                                                         is not performed, the minimum horizontal separation distance shall be 1 in (2.5 cm) and the minimum vertical
                                                                         separation distance shall be 6 in (15 cm). The minimum vertical separation distance may be reduced to 1 in (2.5 cm)
                                                                         if the wiring is supported to ensure that under worst-case transient conditions:
                                                                              1)   Heating of non-Class 1E wires will not result in the wires sagging and touching Class 1E wires or
                                                                                   components and
                                                                              2)   Heating of Class 1E wires will not result in the wires sagging and touching Class 1E wires or components in
                                                                                   a redundant division.
                                                                         An acceptable support method includes stainless steel ties and other metallic supports spaced every 6 in (15 cm) along
                                                                         the length of the wires.
                                                                         In the event the above separation distances are not maintained, barriers shall be installed between circuits requiring
                                                                         separation.
                                                                         Class 1E wire bundles or cables internal to the control switchboards shall be identiÞed in a distinct permanent manner
                                                                         at a sufÞcient number of points to readily distinguish between redundant Class 1E wiring and between Class 1E and
                                                                         non-Class 1E wiring.
                                                                         For a control switchboard or compartment therein containing only Class 1E wiring of a single division, no distinctive
                                                                         identiÞcation is required.
                                                                         Where circuits requiring separation per Section 5. are terminated on a common device, the provisions of 6.6.2 shall be
                                                                         met.
                                                                         Non-Class 1E wiring, not separated from Class 1E or associated wiring by the minimum separation distance
                                                                         (determined in 6.6.2) or by a barrier, shall become associated circuits and shall be subject to the applicable
                                                                         requirements of 5.5.
NOTE Ñ Refer to IEEE Std 420-1982 [10] for additional criteria regarding control switchboards.
                                                                         Cables requiring separation per Section 5. entering the control switchboard enclosure shall meet the requirements of
                                                                         6.1.
                            Instruments requiring separation per Section 5. shall be located in separate cabinets or compartments of a cabinet
                            complying with the requirements of 6.6.
                            Where the instruments requiring separation are located in separate compartments of a single cabinet, attention must be
                            given to routing of external cables to the instruments to assure that cable separation is retained.
In locating Class 1E instrument cabinets, attention shall be given to the effects of all pertinent design basis events.
6.8 Sensors
                            Sensors requiring separation per Section 5. shall be independent and sufÞciently separated that capability of the
                            protection system will be maintained despite any single design basis event or result therefrom.
                            Locations of Class 1E actuated equipment, such as pump drive motors and valve operating motors, are normally
                            dictated by the location of the driven equipment. The resultant locations of this equipment must be reviewed to ensure
                            that separation of actuated equipment is acceptable.
7.1.1 General
                            Electrical isolation of power circuits shall be achieved by Class 1E isolation devices applied to interconnections of the
                            following kinds of circuits (see Fig 1):
NOTE Ñ Refer to IEEE Std 690-1984 [14] for a deÞnition of power cables.
                            A device is considered to be a power circuit isolation device if it is applied such that the maximum credible voltage or
                            current transient applied to the non-Class 1E side of the device will not degrade below an acceptable level the
                            operation of the circuit on the other side of that device.
                            A circuit breaker automatically tripped by fault current is considered an isolation device, provided the following
                            coordination criteria are met:
                                   1)       The breaker time-overcurrent trip characteristic for all circuit faults will cause the breaker to interrupt the
                                            fault current prior to initiation of a trip of any upstream breaker. Periodic testing shall demonstrate that the
                                            overall coordination scheme remains within the limits speciÞed in the design criteria. This testing may be
                                            performed as a series of overlapping tests.
                                                                              2)   The power source shall supply the necessary fault current for sufÞcient time to ensure the proper coordination
                                                                                   without loss of function of Class 1E loads.
                                                                                   NOTE Ñ For example, diesel generator excitation systems should be capable of providing the required transient current
                                                                                          during faults.
                                                                         A circuit breaker is considered an isolation device if it is automatically tripped by an accident signal generated within
                                                                         the same division as that to which the isolation device is applied provided that the time delay involved in generating the
                                                                         accident signal and tripping the breaker does not cause unacceptable degradation of the Class 1E power system.
                                                                         Devices that will limit the input current to an acceptable value under faulted conditions of the output are considered
                                                                         isolation devices. Periodic testing shall verify that the current-limiting characteristic has not been compromised or lost.
                                                                         NOTE Ñ Devices in this category may include inverters, regulating transformers, and battery chargers with current limiting
                                                                                characteristics.
7.1.2.4 Fuses
A fuse may be used as a power isolation device if the following criteria are met:
                                                                              1)   Fuses shall provide the design overcurrent protection capability for the life of the fuse.
                                                                              2)   The fuse time-overcurrent trip characteristic for all circuit faults shall cause the fuse to open prior to the
                                                                                   initiation of an opening of any upstream interrupting device.
                                                                              3)   The power source shall supply the necessary fault current to ensure the proper coordination without loss of
                                                                                   function of Class 1E loads.
7.2.1 General
                                                                         Electrical isolation methods shall be used as required in instrumentation and control circuits to maintain the
                     --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---
                                                                         independence of redundant circuits and equipment such that safety functions required during and following any design
                                                                         basis event can be accomplished. This electrical isolation of instrumentation and control circuits shall be achieved
                                                                         through the use of Class 1E isolation devices applied to interconnections of (a) Class 1E and non-Class 1E circuits, (b)
                                                                         associated circuits and non-Class 1E circuits, or (c) Class 1E logic circuits of redundant divisions as shown in Fig 8.
                                                                         Shielding and wiring techniques may also be necessary to achieve and maintain the independence of redundant circuits
                                                                         and equipment.
NOTE Ñ Refer to IEEE Std 690-1984 [14] for deÞnitions of control and instrumentation cables.
7.2.2.1 General
                            A device is considered an electrical isolation device for instrumentation and control circuits if it is applied so that (a)
                            the maximum credible voltage or current transient applied to the device's non-Class 1E side will not degrade the
                            operation of the circuit connected to the device Class 1E or associated side below an acceptable level; and (b) shorts,
                            grounds, or open circuits occurring in the non-Class 1E side will not degrade the circuit connected to the device Class
                            1E or associated side below an acceptable level.
                            The highest voltage to which the isolation device non-Class 1E side is exposed shall determine the minimum voltage
                            level that the device shall withstand across the non-Class 1E side terminals, and between the non-Class 1E side
                            terminals and ground. Transient voltages that may appear in the non-Class 1E side must also be considered.
                               The separation of the wiring at the input and output terminals of the isolation device may be less than 1 in (2.5 cm) as
                               required in 6.6.2 provided that it is not less than the distance between input and output terminals.
                               Minimum separation requirements do not apply for wiring and components within the isolation device; however,
                               separation shall be provided wherever practicable.
                               The capability of the device to perform its isolation function shall be demonstrated by qualiÞcation test. The
                               qualiÞcation shall consider the levels and duration of the fault current on the non-Class 1E side.
                               When the requirements of 7.2.2.1 are met, the following devices may be used as acceptable isolation devices for
                               instrumentation and control circuits:
                                       1)          AmpliÞers
                                       2)          Control switches
                                       3)          Current transformers
                                       4)          Fiber optic couplers
                                       5)          Photo-optical couplers
                                       6)          Relays
                                       7)          Transducers
                                       8)          Power packs
                                       9)          Circuit breakers
                               NOTE Ñ In using contact-to.contact isolation, consideration shall be given to the effect on independence that may occur from
                                      welding of contacts.
7.2.2.3 Fuses
                               When the requirements of 7.2.2.1 are met, a fuse may be used as an isolation device (except between redundant
                               divisions) if the following additional criteria are met:
                                       1)          Fuses shall provide the design overcurrent protection capability for the life of the fuse.
                                       2)          The fuse time-overcurrent trip characteristic for all circuit faults shall cause the fuse to open prior to the
                                                   initiation of an opening of any upstream interrupting device.
                                       3)          The power source shall supply the necessary fault current to ensure the proper coordination without loss of
                                                   function of Class 1E loads.
                               20
       --`,`````,`,,`,`,```,`,,,``,`,`-`-`,,`,,`,`,,`---                                                                            Copyright © 1992 IEEE All Rights Reserved
                              The separation criteria presented in this standard were developed by the IEEE Nuclear Power Engineering Committee
                              Working Group Subcommittee (SC) 6.5 through the review of test programs conducted by various public utilities.
                              These tests were conducted to address the issue of NRC Regulatory Guide 1.75 compliance during the construction of
                              commercial nuclear power generating stations. These utility sponsored test programs used actual plant construction
                              materials, simulated plant installations, and were conducted with actual plant fault current situations.
                              The typical test sequence was a four-step procedure. The Þrst step was the measurement of electrical properties on the
                              test cables to establish a baseline condition. The second step involved the heating of the cables with current until
                              nominal plant operating temperatures were achieved on the conductors of the test specimens. The third step was the
                              application of a long-term fault current to the fault cable that was intentionally placed in the worst possible physical
                              location relative to the other cables. This current was allowed to ßow until either the cable conductor fused open or
                              indications of phase-to-phase short circuits occurred. In the latter case, the fault current was increased to short-circuit
                              current level amperage, after which the fault cable open-circuited rapidly. The last step consisted of repeating the
                              electrical parameter measurements and comparing the results to the baseline values. The test data included video tapes
                              of the results, temperature data from multiple thermocouples mounted on the test setup, test currents, times of
                              application of currents, still photographs, and electrical parameter test results. All test programs were documented in
                              formal test reports which were used as the basis for licensing the affected plants.
                              Working Group SC 6.5 obtained permission from ten of the utilities to review the test data and to determine if a
                              revision to the standard was warranted. The test data were separated into the categories in Section 6. of the standard
                              and the results evaluated by the committee members. Additional test programs have been conducted beyond the ten
                              reviewed by the Working Group. Although not released to the Working Group, the members are familiar with these test
                              programs and feel that the additional data would further support the separation criteria in this standard.
                              The results of the data review effort were presented in a panel discussion at the IEEE Power Engineering Society (PES)
                              Winter Meeting in 1988, and a technical paper was written and presented at the 1989 Winter PES Meeting. This
                              technical paper (ÒCable SeparationÑWhat Do Industry Testing Programs Show?Ó IEEE Reference Number 90 WM
                              254- 3EC) was published detailing the committee's data analysis and recommended separation distances.
                              This standard does not incorporate all of the recommendations in the technical paper. SpeciÞcally, cable wrapping
                              systems and raceway crossing criteria are not used. Although test data exists on the use of cable wrapping materials to
                              lessen the recommended separation distances, no speciÞed recommendation on the use of these materials is included
                              in this standard. The reason for this omission is that the test results vary widely with the type of material and
                              application of the wrapping system to the cables. The use of cable wrapping is an acceptable method to reduce the
                              separation distances but each wrapping system should be analyzed or tested on a case-by-case basis. Working Group
                              SC 6.5 also did not incorporate the recommendations in the technical paper regarding raceway crossing conÞgurations.
                              The reason for this omission was to simplify the separation criteria. In addition, in some cases, Working Group SC 6.5
                              modiÞed the separation criteria recommendations provided in the technical paper to be consistent with other areas of
                              the standard and to add margin in areas where it was felt to be prudent.
                              Users of this standard should be aware that the testing program did not utilize medium voltage cables, and thus, the
                              separation distances for these circuits were not revised.