0% found this document useful (0 votes)
30 views672 pages

Micom P40 Agile

The MiCOM P40 Agile P64 Technical Manual provides comprehensive information on the transformer protection IED, including hardware and firmware specifications, safety guidelines, and detailed chapters on installation, configuration, and maintenance. It covers various protection and control functions, safety compliance, and transformer differential protection principles. The document emphasizes the user's responsibility for proper application and cybersecurity measures.

Uploaded by

bera.arup2018
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views672 pages

Micom P40 Agile

The MiCOM P40 Agile P64 Technical Manual provides comprehensive information on the transformer protection IED, including hardware and firmware specifications, safety guidelines, and detailed chapters on installation, configuration, and maintenance. It covers various protection and control functions, safety compliance, and transformer differential protection principles. The document emphasizes the user's responsibility for proper application and cybersecurity measures.

Uploaded by

bera.arup2018
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 672

MiCOM P40 Agile

5th Generation
P64
Technical Manual
Transformer Protection IED

Hardware Version: Q
Firmware Version: AB
Publication Reference: P64-TM-EN-1
Copyright statement
Copyright © 2024 GE Vernova. All rights reserved.
FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista, EnerVista Launchpad, and
EnerVista D&I Setup software, CyberSentry, HardFiber, Universal Relay, Multilin, Multilin Agile, and GE Multilin
are trademarks or registered trademarks of GE Vernova.
The contents of this manual are the property of GE Vernova. This documentation is furnished on license and
may not be reproduced in whole or in part without the permission of GE Vernova. The content of this manual is
for informational use only and is subject to change without notice.

Disclaimer
It is the responsibility of the user to verify and validate the suitability of all GE Vernova Grid Automation products.
This equipment must be used within its design limits. The proper application including the configuration and
setting of this product to suit the power system assets is the responsibility of the user, who is also required to
ensure that all local or regional safety guidelines are adhered to. Incorrect application of this product could risk
damage to property/the environment, personal injuries or fatalities and shall be the sole responsibility of the
person/entity applying and qualifying the product for use.
The content of this document has been developed to provide guidance to properly install, configure and maintain
this product for its intended applications. This guidance is not intended to cover every possible contingency that
may arise during commissioning, operation, service, or maintenance activities. Should you encounter any
circumstances not clearly addressed in this document, contact your local GE Vernova service site.
The information contained in this document is subject to change without notice.
IT IS THE SOLE RESPONSIBILITY OF THE USER TO SECURE THEIR NETWORK AND ASSOCIATED
DEVICES AGAINST CYBER SECURITY INTRUSIONS OR ATTACKS. GE VERNOVA AND ITS AFFILIATES
ARE NOT LIABLE FOR ANY DAMAGES AND/OR LOSSES ARISING FROM OR RELATED TO SUCH
SECURITY INTRUSION OR ATTACKS.
P64

4 P64-TM-EN-1
Contents

Chapter 1 Introduction 1
1.1 Chapter Overview 2
1.2 Foreword 3
1.2.1 Target Audience 3
1.2.2 Typographical Conventions 3
1.2.3 Nomenclature 4
1.2.4 Compliance 4
1.3 Product Scope 5
1.3.1 Product Versions 5
1.3.2 Ordering Options 6
1.4 Features and Functions 8
1.4.1 Protection Functions 8
1.4.2 Control Functions 8
1.4.3 Measurement Functions 9
1.4.4 Communication Functions 9
1.5 Logic Diagrams 10
1.6 Compliance 12
1.7 Functional Overview 13

Chapter 2 Safety Information 15


2.1 Chapter Overview 16
2.2 Health and Safety 17
2.3 Symbols 18
2.4 Installation, Commissioning and Servicing 19
2.4.1 Lifting Hazards 19
2.4.2 Electrical Hazards 19
2.4.3 UL/CSA/CUL Requirements 20
2.4.4 Fusing Requirements 20
2.4.5 Equipment Connections 21
2.4.6 Protection Class 1 Equipment Requirements 21
2.4.7 Pre-energisation Checklist 22
2.4.8 Peripheral Circuitry 22
2.4.9 Upgrading/Servicing 24
2.5 Decommissioning and Disposal 25
2.6 Regulatory Compliance 26
2.6.1 EMC Compliance: 2014/30/EU 26
2.6.2 LVD Compliance: 2014/35/EU 26
2.6.3 UL/CUL Compliance 26
2.6.4 UKCA Compliance 26
2.6.5 EMC Compliance: Electromagnetic Compatibility Regulations 2016 26
2.6.6 Safety Compliance: Electrical Equipment (Safety) Regulations 2016 26
2.6.7 Morocco Compliance 27
2.6.8 EMC Compliance: No. 2574-14 of Ramadan 1436 27
2.6.9 Safety Compliance: No. 2573-14 of Ramadan 1436 27

Chapter 3 Hardware Design 29


3.1 Chapter Overview 30
3.2 Hardware Architecture 31
3.3 Mechanical Implementation 32
3.3.1 Housing Variants 32
3.3.2 List of Boards 33
Contents P64

3.4 Front Panel 34


3.4.1 Front Panel Compartments 34
3.4.2 HMI Panel 34
3.4.3 Keypad 35
3.4.4 USB Port 36
3.4.5 Fixed Function LEDs 36
3.4.6 Function Keys 37
3.4.7 Programable LEDs 37
3.5 Rear Panel 38
3.5.1 Terminal Block Ingress Protection 39
3.6 Boards and Modules 40
3.6.1 PCBs 40
3.6.2 Subassemblies 40
3.6.3 Main Processor Board 41
3.6.4 Power Supply Board 42
3.6.4.1 Watchdog 44
3.6.4.2 Rear Serial Port 45
3.6.5 Input Module - 1 Transformer Board 46
3.6.5.1 Input Module Circuit Description 47
3.6.5.2 Transformer Board 48
3.6.5.3 Input Board 49
3.6.6 Standard Output Relay Board 50
3.6.7 High Break Output Relay Board 51
3.6.8 IRIG-B Board 53
3.6.9 Fibre Optic Board 54
3.6.10 Rear Communication Board 55
3.6.11 Single Ethernet Board 55
3.6.12 Redundant Ethernet Board 57
3.6.13 RTD Board 60
3.6.14 CLIO Board 62

Chapter 4 Software Design 65


4.1 Chapter Overview 66
4.2 Sofware Design Overview 67
4.3 System Level Software 68
4.3.1 Real Time Operating System 68
4.3.2 System Services Software 68
4.3.3 Self-Diagnostic Software 68
4.3.4 Startup Self-Testing 68
4.3.4.1 System Boot 68
4.3.4.2 System Level Software Initialisation 69
4.3.4.3 Platform Software Initialisation and Monitoring 69
4.3.5 Continuous Self Testing 69
4.4 Platform Software 71
4.4.1 Record Logging 71
4.4.2 Settings Database 71
4.4.3 Interfaces 71
4.5 Protection and Control Functions 72
4.5.1 Acquisition of Samples 72
4.5.2 Frequency Tracking 72
4.5.3 Direct Use of Sampled Values 72
4.5.4 System Level Software Initialisation 72
4.5.5 Fourier Signal Processing 73
4.5.6 Programmable Scheme Logic 74
4.5.7 Event Recording 74
4.5.8 Disturbance Recorder 74

ii P64-TM-EN-1
P64 Contents

4.5.9 Function Key Interface 75

Chapter 5 Configuration 77
5.1 Chapter Overview 78
5.2 Settings Application Software 79
5.3 Using the HMI Panel 80
5.3.1 Navigating the HMI Panel 81
5.3.2 Getting Started 81
5.3.3 Default Display 81
5.3.4 Default Display Navigation 82
5.3.5 Processing Alarms and Records 83
5.3.6 Single Line Diagram (SLD) Viewer 84
5.3.6.1 Circuit Breaker Control (SLD View Only) 84
5.3.6.2 Switch Control (SLD View Only) 85
5.3.7 Menu Structure 86
5.3.8 Direct Access (Menu Context Keys) 87
5.3.8.1 Control Inputs 88
5.3.9 Changing the Settings 88
5.3.10 Function Keys 89
5.3.10.1 Visualisation of Protection Operation 90

Chapter 6 Transformer Differential Protection 93


6.1 Chapter Overview 94
6.2 Transformer Differential Protection Principles 95
6.2.1 Through Fault Stability 95
6.2.2 Bias Current Compensation 95
6.2.3 Three-phase Transformer Connection Types 96
6.2.4 Phase and Amplitude Compensation 99
6.2.5 Zero Sequence Filtering 100
6.2.6 Magnetising Inrush Restraint 100
6.2.7 Overfluxing Restraint 102
6.3 Implementation 103
6.3.1 Defining the Power Transformer 103
6.3.2 Selecting the Current Inputs 103
6.3.3 Phase Correction 104
6.3.4 Ratio Correction 104
6.3.5 CT Parameter Mismatch 105
6.3.6 Setting up Zero Sequence Filtering 106
6.3.7 Tripping Characteristics 106
6.3.7.1 High-Set Function 107
6.3.7.2 Circuitry Fail Alarm 108
6.3.8 Tripping Characteristic Stability 108
6.3.8.1 Maximum Bias 108
6.3.8.2 Delayed Bias 108
6.3.8.3 Transient Bias 108
6.3.8.4 CT Saturation Technique 109
6.3.8.5 No Gap Detection Technique 109
6.3.8.6 External Fault Detection Technique 109
6.3.8.7 Phase Comparison Technique 111
6.3.8.8 Current Transformer Supervision 112
6.3.8.9 Circuitry Fail Alarm 112
6.3.9 Differential Biased Trip Logic 113
6.4 Harmonic Blocking 115
6.4.1 2nd Harmonic Blocking 115
6.4.2 2nd Harmonic Blocking Logic 116

P64-TM-EN-1 iii
Contents P64

6.4.3 2nd Harmonic Setting Guidelines 116


6.4.4 5th Harmonic Blocking Implementation 117
6.4.5 5th Harmonic Setting Guideline 117
6.4.6 Geomagnetic Disturbances 118
6.4.7 Overall Harmonic Blocking Logic 118
6.5 Application Notes 119
6.5.1 Setting Guidelines 119
6.5.2 Example 1: Two-winding Transformer - No Tap Changer 120
6.5.3 Example 2: Autotransformer with Loaded Delta Winding 123
6.5.4 Example 3: Autotransformer with Unloaded Delta Winding 127
6.5.5 Setting Guidelines for Short-Interconnected Biased Differential Protection 131
6.5.6 Setting Guidelines for Shunt Reactor Biased Differential Protection 134
6.5.7 Setting Guidelines for using Spare CT Inputs 136
6.5.8 Setting Guidelines for Reference Vector Group 137
6.5.9 Stub Bus Application 138
6.5.9.1 Stub Bus Implementation 138
6.5.9.2 Stub Bus Scheme 139
6.5.10 Transformer Differential Protection CT Requirements 139
6.5.10.1 CT Requirements - Transformer Application 139
6.5.10.2 CT Requirements - Small Busbar Application 141

Chapter 7 Transformer Condition Monitoring 143


7.1 Chapter Overview 144
7.2 Thermal Overload Protection 145
7.2.1 Thermal Overload Implementation 146
7.2.1.1 Thermal Overload Bias Current 146
7.2.2 The Thermal Model 147
7.2.2.1 Top Oil Temperature Caculations 147
7.2.2.2 Hotspot Caculations 147
7.2.2.3 Thermal State Measurement 148
7.2.3 Application Notes 148
7.2.3.1 Recommendations 148
7.2.3.2 IEEE Recommendations 149
7.2.3.3 Data Provided by Transformer Manufacturers 149
7.3 Loss of Life Statistics 152
7.3.1 Loss of Life Implementation 152
7.3.1.1 Loss of Life Calculations 152
7.3.2 Application Notes 154
7.3.2.1 LOL Setting Guidelines 154
7.3.2.2 Example 154
7.4 Through Fault Monitoring 156
7.4.1 Through Fault Monitoring Implementation 156
7.4.2 Through Fault Monitoring Logic 157
7.4.3 Application Notes 157
7.4.3.1 TFM Setting Guidelines 157
7.5 RTD Protection 160
7.5.1 RTD Protection Implementation 160
7.5.2 RTD Logic 161
7.5.3 Application Notes 161
7.5.3.1 Setting Guidelines for RTD Protection 161
7.6 CLIO Protection 162
7.6.1 Current Loop Input Implementation 162
7.6.2 Current Loop Input Logic 164
7.6.3 CLO Implementation 164
7.6.4 Application Notes 166
7.6.4.1 CLI Setting Guidelines 166

iv P64-TM-EN-1
P64 Contents

7.6.4.2 CLO Setting Guidelines 166

Chapter 8 Restricted Earth Fault Protection 169


8.1 Chapter Overview 170
8.2 REF Protection Principles 171
8.2.1 Resistance-Earthed Star Windings 172
8.2.2 Solidly-Earthed Star Windings 172
8.2.3 Through Fault Stability 173
8.2.4 Restricted Earth Fault Types 173
8.2.4.1 Low Impedance REF Principle 174
8.2.4.2 High Impedance REF Principle 175
8.3 Restricted Earth Fault Protection Implementation 177
8.3.1 Enabling REF Protection 177
8.3.2 Neutral Supervision 177
8.3.3 Selecting the Current Inputs 177
8.3.4 Low Impedance REF 179
8.3.4.1 Setting the Bias Characteristic 179
8.3.4.2 Delayed Bias 180
8.3.4.3 Transient Bias 180
8.3.4.4 Restricted Earth Fault Logic 181
8.3.5 High Impedance REF 181
8.3.5.1 High Impedance REF Calculation Principles 181
8.4 Second Harmonic Blocking 183
8.4.1 REF 2nd harmonic Blocking Logic 183
8.5 Application Notes 184
8.5.1 Star Winding Resistance Earthed 184
8.5.2 Low Impedance REF Protection Application 185
8.5.2.1 Setting Guidelines for Biased Operation 185
8.5.2.2 Low Impedance REF Scaling Factor 185
8.5.2.3 Parameter Calculations 186
8.5.2.4 Dual CB Application with Different Phase CT Ratios 187
8.5.2.5 Dual CB Application with Same Phase CT Ratios 187
8.5.2.6 CT Requirements - Low Impedance REF 188
8.5.3 High Impedance REF Protection Application 189
8.5.3.1 High Impedance REF Operating Modes 189
8.5.3.2 Setting Guidelines for High Impedance Operation 191
8.5.3.3 Use of Metrosil Non-linear Resistors 193
8.5.3.4 CT Requirements - High Impedance REF 195

Chapter 9 Current Protection Functions 199


9.1 Chapter Overview 200
9.2 Overcurrent Protection Principles 201
9.2.1 IDMT Characteristics 201
9.2.1.1 IEC 60255 IDMT Curves 202
9.2.1.2 European Standards 204
9.2.1.3 North American Standards 205
9.2.1.4 IEC and IEEE Inverse Curves 207
9.2.1.5 Differences Between the North american and European Standards 208
9.2.2 Principles of Implementation 208
9.2.2.1 Timer Hold Facility 209
9.2.3 Magnetising Inrush Restraint 210
9.3 Phase Overcurrent Protection 213
9.3.1 Phase Overcurrent Protection for Power Transformers 213
9.3.2 Phase Overcurrent Protection Implementation 213
9.3.3 Selecting the Current Inputs 214
9.3.4 Non-Directional Overcurrent Logic 215

P64-TM-EN-1 v
Contents P64

9.3.5 Directional Element 216


9.3.5.1 Implementing Directionalisation 217
9.3.5.2 Directional Overcurrent Logic 218
9.3.6 Application Notes 219
9.3.6.1 Setting Guidelines 219
9.3.6.2 Parallel Feeders 220
9.4 Voltage Dependent Overcurrent Element 221
9.4.1 Current Setting Threshold Selection 221
9.4.2 VCO Implementation 221
9.4.3 VRO Implementation 222
9.5 Negative Sequence Overcurrent Protection 224
9.5.1 NPSOC Protection Implementation 224
9.5.2 Non-Directional NPSOC Logic 225
9.5.3 Directional Element 225
9.5.3.1 Directional NPSOC Logic 226
9.5.4 Application Notes 226
9.5.4.1 Setting Guidelines (General) 226
9.5.4.2 Setting Guidelines (Current Threshold) 226
9.5.4.3 Setting Guidelines (Time Delay) 227
9.5.4.4 Setting Guidelines (Directional element) 227
9.6 Earth Fault Protection 228
9.6.1 Earth Fault Protection Elements 228
9.6.2 Non-directional Earth Fault Logic 229
9.6.3 IDG Curve 229
9.6.4 Directional Element 230
9.6.4.1 Residual Voltage Polarisation 230
9.6.4.2 Negative Sequence Polarisation 231
9.6.5 Application Notes 232
9.6.5.1 Setting Guidelines (Non-directional) 232
9.6.5.2 Setting Guidelines (Directional Element) 233
9.7 Second Harmonic Blocking 234
9.7.1 Second Harmonic Blocking Implementation 234
9.7.2 Second Harmonic Blocking Logic 235
9.7.3 EF Second Harmonic Blocking Logic 236
9.7.4 Application Notes 236
9.7.4.1 Setting Guidelines 236

Chapter 10 CB Fail Protection 237


10.1 Chapter Overview 238
10.2 Circuit Breaker Fail Protection 239
10.3 Circuit Breaker Fail Implementation 240
10.3.1 Circuit Breaker Fail Timers 240
10.3.2 Zero Crossing Detection 241
10.4 Circuit Breaker Fail Logic 242
10.5 Application Notes 244
10.5.1 Reset Mechanisms for CB Fail Timers 244
10.5.2 Setting Guidelines (CB fail Timer) 244
10.5.3 Setting Guidelines (Undercurrent) 245

Chapter 11 Voltage Protection Functions 247


11.1 Chapter Overview 248
11.2 Undervoltage Protection 249
11.2.1 Undervoltage Protection Implementation 249
11.2.2 Undervoltage Protection Logic 250
11.2.3 Application Notes 251

vi P64-TM-EN-1
P64 Contents

11.2.3.1 Undervoltage Setting Guidelines 251


11.3 Overvoltage Protection 252
11.3.1 Overvoltage Protection Implementation 252
11.3.2 Overvoltage Protection Logic 253
11.3.3 Application Notes 254
11.3.3.1 Overvoltage Setting Guidelines 254
11.4 Residual Overvoltage Protection 255
11.4.1 Residual Overvoltage Protection Implementation 255
11.4.2 Residual Overvoltage Logic 256
11.4.3 Application Notes 256
11.4.3.1 Calculation for Solidly Earthed Systems 256
11.4.3.2 Calculation for Impedance Earthed Systems 257
11.4.3.3 Setting Guidelines 258
11.5 Negative Sequence Overvoltage Protection 259
11.5.1 Negative Sequence Overvoltage Implementation 259
11.5.2 Negative Sequence Overvoltage Logic 259
11.5.3 Application Notes 259
11.5.3.1 Setting Guidelines 259

Chapter 12 Frequency Protection Functions 261


12.1 Chapter Overview 262
12.2 Overfluxing Protection 263
12.2.1 Overfluxing Protection Implementation 263
12.2.1.1 Time-delayed Overfluxing Protection 264
12.2.1.2 5th Harmonic Blocking 265
12.2.1.3 Overfluxing Protection Logic 266
12.2.2 Application Notes 266
12.2.2.1 Overfluxing Protection Setting Guidelines 266
12.3 Frequency Protection 269
12.3.1 Underfrequency Protection 269
12.3.1.1 Underfrequency Protection Implementation 269
12.3.1.2 Underfrequency Protection logic 270
12.3.1.3 Application Notes 270
12.3.2 Overfrequency Protection 270
12.3.2.1 Overfrequency Protection Implementation 270
12.3.2.2 Overfrequency Protection logic 271
12.3.2.3 Application Notes 271

Chapter 13 Monitoring and Control 273


13.1 Chapter Overview 274
13.2 Event Records 275
13.2.1 Event Types 275
13.2.1.1 Opto-input Events 276
13.2.1.2 Contact Events 276
13.2.1.3 Alarm Events 276
13.2.1.4 Fault Record Events 280
13.2.1.5 Maintenance Events 281
13.2.1.6 Protection Events 281
13.2.1.7 Security Events 281
13.2.1.8 Platform Events 281
13.3 Disturbance Recorder 283
13.4 Measurements 284
13.4.1 Measured Quantities 284
13.4.1.1 Measured and Calculated Currents 284
13.4.1.2 Measured and Calculated Voltages 284
13.4.1.3 Power and Energy Quantities 284

P64-TM-EN-1 vii
Contents P64

13.4.1.4 Demand Values 285


13.4.1.5 Other Measurements 285
13.4.2 Measurement Setup 285
13.4.3 Opto-input Time Stamping 285
13.5 Current Input Exclusion Function 286
13.5.1 Current Input Exclusion Logic 286
13.5.2 Application Notes 287
13.5.2.1 Current Input Exclusion Example 287
13.6 Circuit Breaker Control 288
13.6.1 CB Control using the IED Menu 288
13.6.2 Single Line Diagram (SLD) Viewer 288
13.6.2.1 Circuit Breaker Control (SLD View Only) 288
13.6.3 CB Control using the Opto-inputs 289
13.6.4 Remote CB Control 290
13.6.5 CB Healthy Check 290
13.6.6 CB Control Logic 291
13.7 Pole Dead Function 292
13.7.1 Pole Dead Function Implementation 292
13.7.2 Pole Dead Logic 293
13.7.3 CB Status Indication 295
13.8 Switch Status and Control 296
13.8.1 Single Line Diagram (SLD) VIewer 297
13.8.2 Switch Control (SLD View Only) 297
13.8.3 Switch Control Logic 299
13.8.4 Switch Status Logic 300
13.9 Test Mode 301
13.10 IEC 61850 Control Authority 302

Chapter 14 Supervision 307


14.1 Chapter Overview 308
14.2 Voltage Transformer Supervision 309
14.2.1 Loss of One or Two Phase Voltages 309
14.2.2 Loss of all Three Phase Voltages 309
14.2.3 Absence of all Three Phase Voltages on Line Energisation 309
14.2.4 VTS Implementation 310
14.2.5 VTS Logic 311
14.3 Current Transformer Supervision 314
14.3.1 CTS Implementation 314
14.3.2 CTS Logic 316
14.3.3 Application Notes 316
14.3.3.1 Setting Guidelines 316
14.4 Trip Circuit Supervision 318
14.4.1 Trip Circuit Supervision Scheme 1 318
14.4.1.1 Resistor Values 318
14.4.1.2 PSL for TCS Scheme 1 319
14.4.2 Trip Circuit Supervision Scheme 3 319
14.4.2.1 Resistor Values 320
14.4.2.2 PSL for TCS Scheme 3 320

Chapter 15 Digital I/O and PSL Configuration 321


15.1 Chapter Overview 322
15.2 Configuring Digital Inputs and Outputs 323
15.3 Scheme Logic 324
15.3.1 PSL Editor 325
15.3.2 PSL Schemes 325

viii P64-TM-EN-1
P64 Contents

15.3.3 PSL Scheme Version Control 325


15.4 Configuring the Opto-Inputs 326
15.5 Assigning the Output Relays 327
15.6 Fixed Function LEDs 328
15.6.1 Trip LED Logic 328
15.7 Configuring Programmable LEDs 329
15.8 Function Keys 331
15.9 Control Inputs 332
15.10 User Alarms 333

Chapter 16 Communications 335


16.1 Chapter Overview 336
16.2 Communication Interfaces 337
16.3 Serial Communication 338
16.3.1 USB Front Port 338
16.3.2 EIA(RS)485 Bus 338
16.3.2.1 EIA(RS)485 Biasing Requirements 339
16.3.3 K-Bus 339
16.4 Ethernet Board Versions 341
16.5 Board Connections 342
16.6 Ethernet Configuration 344
16.6.1 Network Configuration 344
16.6.2 PRP Configuration 344
16.6.3 HSR Configuration 345
16.6.4 RSTP Configuration 345
16.6.5 Failover Configuration 345
16.6.6 SNTP IP Address Configuration 345
16.7 Redundancy Protocols 346
16.7.1 Parallel Redundancy Protocol (PRP) 346
16.7.1.1 PRP Networks 346
16.7.1.2 Network Elements 346
16.7.2 High-Availability Seamless Redundancy (HSR) 347
16.7.2.1 HSR Multicast Topology 347
16.7.2.2 HSR Unicast Topology 348
16.7.2.3 HSR Application in the Substation 349
16.7.3 Rapid Spanning Tree Protocol (RSTP) 349
16.7.4 Failover 350
16.8 Simple Network Management Protocol (SNMP) 351
16.8.1 SNMP MIBs Compatible with the IED 352
16.8.2 New SNMP System Objects 352
16.8.2.1 New SNMP Traps 352
16.8.2.2 New SNMP Objects 352
16.8.3 SNMP Alarm Enhancement 353
16.8.3.1 SNMP Alarm Format 353
16.8.3.2 List of SNMP Alarms 353
16.9 Data Protocols 355
16.9.1 Courier 355
16.9.1.1 Physical Connection and Link Layer 355
16.9.1.2 Courier Database 356
16.9.1.3 Settings Categories 356
16.9.1.4 Setting Changes 356
16.9.1.5 Event Extraction 357
16.9.1.6 Disturbance Record Extraction 358
16.9.1.7 Programmable Scheme Logic Settings 358
16.9.1.8 Time Synchronisation 358
16.9.1.9 Courier Configuration 359

P64-TM-EN-1 ix
Contents P64

16.9.2 IEC 60870-5-103 359


16.9.2.1 Physical Connection and Link Layer 360
16.9.2.2 Initialisation 360
16.9.2.3 Time Synchronisation 360
16.9.2.4 Configurable IEC 60870-5-103 Signal List 360
16.9.2.5 Spontaneous Events 361
16.9.2.6 General Interrogation (GI) 361
16.9.2.7 Cyclic Measurements 361
16.9.2.8 Commands 362
16.9.2.9 Test Mode 362
16.9.2.10 Disturbance Records 362
16.9.2.11 Command/Monitor Blocking 362
16.9.2.12 IEC 60870-5-103 Configuration 362
16.9.3 DNP 3.0 363
16.9.3.1 Physical Connection and Link Layer 363
16.9.3.2 Object 1 Binary Inputs 363
16.9.3.3 Object 10 Binary Outputs 364
16.9.3.4 Object 20 Binary Counters 365
16.9.3.5 Object 30 Analogue Input 365
16.9.3.6 Object 40 Analogue Output 365
16.9.3.7 Object 50 Time Synchronisation 365
16.9.3.8 DNP3 Device Profile 365
16.9.4 IEC 61850 374
16.9.4.1 Benefits of IEC 61850 374
16.9.4.2 IEC 61850 Interoperability 375
16.9.4.3 The IEC 61850 Data Model 375
16.9.4.4 IEC 61850 in MiCOM IEDs 376
16.9.4.5 IEC 61850 Data Model Implementation 376
16.9.4.6 IEC 61850 Communication Services Implementation 377
16.9.4.7 IEC 61850 Peer-to-peer (GOOSE) communications 377
16.9.4.8 GOOSE Message Validation 377
16.9.4.9 Mapping GOOSE Messages to Virtual Inputs 377
16.9.4.10 IEC 61850 GOOSE Configuration 377
16.9.4.11 Ethernet Functionality 378
16.9.4.12 IEC 61850 Configuration 378
16.9.4.13 IEC 61850 Edition 2 379
16.9.5 Read Only Mode 380
16.9.5.1 IEC 60870-5-103 Protocol Blocking 381
16.9.5.2 Courier Protocol Blocking 381
16.9.5.3 IEC 61850 Protocol Blocking 382
16.9.5.4 Read-Only Settings 382
16.9.5.5 Read-Only DDB Signals 382
16.10 Time Synchronisation 383
16.10.1 IRIG-B 383
16.10.1.1 IRIG-B Implementation 384
16.10.2 SNTP 384
16.10.2.1 Loss of SNTP Server Signal Alarm 384
16.10.3 IEEE 1588 Precision time Protocol 384
16.10.3.1 Accuracy and Delay Calculation 385
16.10.3.2 PTP Domains 385
16.10.4 Time Synchronisation using the Communication Protocols 385

Chapter 17 Cyber-Security 387


17.1 Disclaimer 388
17.2 Overview 389
17.3 The Need for Cyber-Security 390
17.4 Standards 391
17.4.1 NERC Compliance 391

x P64-TM-EN-1
P64 Contents

17.4.1.1 CIP 002 392


17.4.1.2 CIP 003 392
17.4.1.3 CIP 004 392
17.4.1.4 CIP 005 392
17.4.1.5 CIP 006 393
17.4.1.6 CIP 007 393
17.4.1.7 CIP 008 393
17.4.1.8 CIP 009 393
17.4.2 IEEE 1686-2013 394
17.5 Cyber-Security Implementation 395
17.5.1 Initial Setup: Default Usernames and Default Passwords 395
17.6 Roles and Permissions 396
17.6.1 Roles 396
17.6.2 Permissions 396
17.7 User Authentication 399
17.7.1 Authentication Methods 399
17.7.2 Bypass 399
17.7.3 Login 400
17.7.3.1 Front Panel Login 400
17.7.3.2 Login Failed 401
17.7.3.3 Other Login Prompts 402
17.7.3.4 MiCOM S1 Login 402
17.7.4 User Sessions 402
17.7.5 User Locking Policy 404
17.7.6 Logout 404
17.7.6.1 Front Panel Logout 404
17.7.6.2 MiCOM S1 Logout 405
17.7.7 Password Policy 406
17.7.8 Password Expiry 406
17.7.9 Change Password 407
17.7.10 RADIUS Authentication 408
17.7.10.1 RADIUS Users 408
17.7.10.2 RADIUS Client 408
17.7.10.3 RADIUS Server Settings 409
17.7.10.4 RADIUS Accounting 410
17.7.10.5 RADIUS Client-Server Validation 410
17.7.11 Recovery 410
17.7.11.1 Restore to Local Factory Default 410
17.7.11.2 Password Reset Procedure 411
17.7.11.3 Access Level DDBs 412
17.7.12 Port Hardening: Physical Ports 412
17.7.13 Port Hardening: Logical Ports (Protocols) 413
17.7.14 Service (Protocol) Mapping: Ethernet Network Ports 1 and 2 413
17.7.15 Supervise Device Dialog Box 413
17.7.16 Secure Firmware Upgrade 414
17.8 SNMP Configuration 416
17.9 Returning The IED To Factory 417
17.10 Security Event Management 418
17.10.1 Security Events: Courier 418
17.10.2 Security Events: Syslog 422
17.10.3 Syslog Client 424
17.10.4 Syslog Functionality 424
17.10.5 Security Events: SNMP 425

Chapter 18 Installation 429


18.1 Chapter Overview 430

P64-TM-EN-1 xi
Contents P64

18.2 Handling the Goods 431


18.2.1 Receipt of the Goods 431
18.2.2 Unpacking the Goods 431
18.2.3 Storing the Goods 431
18.2.4 Dismantling the Goods 431
18.3 Mounting the Device 432
18.3.1 Flush Panel Mounting 432
18.3.2 Rack Mounting 432
18.3.3 Refurbishment Solutions 433
18.4 Cables and Connectors 435
18.4.1 Terminal Blocks 435
18.4.2 Power Supply Connections 436
18.4.3 Earth Connnection 436
18.4.4 Current Transformers 436
18.4.5 Voltage Transformer Connections 437
18.4.6 Watchdog Connections 437
18.4.7 EIA(RS)485 and K-Bus Connections 437
18.4.8 IRIG-B Connection 437
18.4.9 Opto-input Connections 437
18.4.10 Output Relay Connections 438
18.4.11 Ethernet Metallic Connections 438
18.4.12 Ethernet Fibre Connections 438
18.4.13 USB Connection 438
18.4.14 RTD Connections 438
18.4.15 CLIO Connections 439
18.5 Case Dimensions 440
18.5.1 Case Dimensions 40TE 441
18.5.2 Case Dimensions 60TE 442
18.5.3 Case Dimensions 80TE 443

Chapter 19 Commissioning Instructions 445


19.1 Chapter Overview 446
19.2 General Guidelines 447
19.3 Commissioning Test Menu 448
19.3.1 Opto I/P Status Cell (Opto-input Status) 448
19.3.2 Relay O/P Status Cell (Relay Output Status) 448
19.3.3 Test Mode Cell 448
19.3.4 Test Pattern Cell 449
19.3.5 Contact Test Cell 449
19.3.6 Test LEDs Cell 449
19.3.7 Red and Green LED Status Cells 449
19.3.8 PSL Verificiation 449
19.3.8.1 Test Port Status Cell 449
19.3.8.2 Monitor Bit 1 to 8 Cells 449
19.4 Commissioning Equipment 451
19.4.1 Recommended Commissioning Equipment 451
19.4.2 Essential Commissioning Equipment 451
19.4.3 Advisory Test Equipment 452
19.5 Product Checks 453
19.5.1 Product Checks with the IED De-energised 453
19.5.1.1 Visual Inspection 453
19.5.1.2 Current Transformer Shorting Contacts 454
19.5.1.3 Insulation 454
19.5.1.4 External Wiring 454
19.5.1.5 Watchdog Contacts 454
19.5.1.6 Power Supply 455

xii P64-TM-EN-1
P64 Contents

19.5.2 Pxxx_CI_ProductChecksEnergised 455


19.5.2.1 Watchdog Contacts 455
19.5.2.2 Test Graphical HMI 456
19.5.2.3 Date and Time 456
19.5.2.4 Test LEDs 456
19.5.2.5 Test Alarm and Out-of-Service LEDs 457
19.5.2.6 Test Trip LED 457
19.5.2.7 Test User-programmable LEDs 457
19.5.2.8 Test Opto-inputs 457
19.5.2.9 Test Output Relays 457
19.5.2.10 RTD Inputs 457
19.5.2.11 Current Loop Outputs 458
19.5.2.12 Current Loop Inputs 458
19.5.2.13 Test Serial Communication Port RP1 458
19.5.2.14 Test Serial Communication Port RP2 460
19.5.2.15 Test Ethernet Communication 461
19.5.3 Secondary Injection Tests 461
19.5.3.1 Test Current Inputs 461
19.5.3.2 Test Voltage Inputs 462
19.6 Setting Checks 463
19.6.1 Apply Application-specific Settings 463
19.6.1.1 Transferring Settings from a Settings File 463
19.6.1.2 Entering settings using the HMI 463
19.7 IEC 61850 Edition 2 Testing 465
19.7.1 Using IEC 61850 Edition 2 Test Modes 465
19.7.1.1 IED Test Mode Behaviour 465
19.7.1.2 Sampled Value Test Mode Behaviour 465
19.7.2 Simulated Input Behaviour 466
19.7.3 Testing Examples 467
19.7.3.1 Test Procedure for Real Values 467
19.7.3.2 Test Procedure for Simulated Values - No Plant 468
19.7.3.3 Test Procedure for Simulated Values - With Plant 468
19.7.3.4 Contact Test 469
19.8 Checking the Differential Element 470
19.8.1 Using the Omicron Advanced Module 470
19.9 Protection Timing Checks 474
19.9.1 Bypassing the All Pole Dead Blocking Condition 474
19.9.2 Overcurrent Check 474
19.9.3 Connecting the Test Circuit 474
19.9.4 Performing the Test 475
19.9.5 Check the Operating Time 475
19.10 Onload Checks 476
19.10.1 Confirm Current Connections 476
19.10.2 Confirm Voltage Connections 476
19.10.3 On-load Directional Test 477
19.11 Final Checks 478

Chapter 20 Maintenance and Troubleshooting 479


20.1 Chapter Overview 480
20.2 Maintenance 481
20.2.1 Maintenance Checks 481
20.2.1.1 Alarms 481
20.2.1.2 Opto-isolators 481
20.2.1.3 Output Relays 481
20.2.1.4 Measurement Accuracy 481
20.2.2 Replacing the Device 482
20.2.3 Repairing the Device 483

P64-TM-EN-1 xiii
Contents P64

20.2.4 Removing the front panel 483


20.2.5 Replacing PCBs 484
20.2.5.1 Replacing the main processor board 484
20.2.5.2 Replacement of communications boards 485
20.2.5.3 Replacement of the input module 486
20.2.5.4 Replacement of the power supply board 486
20.2.5.5 Replacement of the I/O boards 487
20.2.6 Recalibration 487
20.2.7 Supercapacitor Discharged 487
20.2.8 Cleaning 488
20.3 Troubleshooting 489
20.3.1 Self-Diagnostic Software 489
20.3.2 Power-up Errors 489
20.3.3 Error Message or Code on Power-up 489
20.3.4 Out of Service LED on at power-up 490
20.3.5 Error Code during Operation 491
20.3.6 Mal-operation during testing 491
20.3.6.1 Failure of Output Contacts 491
20.3.6.2 Failure of Opto-inputs 491
20.3.6.3 Incorrect Analogue Signals 492
20.3.7 PSL Editor Troubleshooting 492
20.3.7.1 Diagram Reconstruction 492
20.3.7.2 PSL Version Check 492
20.3.8 Repair and Modification Procedure 493

Chapter 21 Technical Specifications 495


21.1 Chapter Overview 496
21.2 Interfaces 497
21.2.1 Graphical HMI 497
21.2.2 Front USB Port 497
21.2.3 Rear Serial Port 1 497
21.2.4 Fibre Rear Serial Port 1 497
21.2.5 Rear Serial Port 2 498
21.2.6 Optional Rear Serial Port (SK5) 498
21.2.7 IRIG-B (Demodulated) 498
21.2.8 IRIG-B (Modulated) 498
21.2.9 Rear Ethernet Port Copper 499
21.2.10 Rear Ethernet Port Fibre 499
21.2.10.1 100 Base FX Receiver Characteristics 499
21.2.10.2 100 Base FX Transmitter Characteristics 500
21.3 Performance of Transformer Differential Protection and Monitoring Functions 501
21.3.1 Transformer Differential Protection 501
21.3.2 Matching Factors 501
21.3.3 Circuitry Fault Alarm 501
21.3.4 Through Fault Monitoring 502
21.3.5 Thermal Overload 502
21.3.6 Transformer and Loss of Life 502
21.3.7 Low Impedance Restricted Earth Fault 502
21.3.8 High Impedance Restricted Earth Fault 503
21.4 Performance of Current Protection Functions 504
21.4.1 Transient Overreach and Overshoot 504
21.4.2 Three-phase Overcurrent Protection 504
21.4.2.1 Three-phase Overcurrent Directional Parameters 504
21.4.3 Voltage Dependent Overcurrent Protection 504
21.4.4 Earth Fault Protection 505
21.4.4.1 Earth Fault Directional Parameters 505

xiv P64-TM-EN-1
P64 Contents

21.4.5 Negative Sequence Overcurrent Protection 505


21.4.5.1 NPSOC Directional Parameters 505
21.4.6 Circuit Breaker Fail Protection 506
21.5 Performance of Voltage Protection Functions 507
21.5.1 Undervoltage Protection (P643/5) 507
21.5.2 Overvoltage Protection 507
21.5.3 Residual Overvoltage Protection (P643/5) 507
21.5.4 Negative Sequence Voltage Protection 507
21.6 Performance of Frequency Protection Functions 509
21.6.1 Overfrequency Protection 509
21.6.2 Underfrequency Protection 509
21.6.3 Overfluxing Protection 509
21.7 Performance of Monitoring and Control Functions 510
21.7.1 Voltage Transformer Supervision 510
21.7.2 Current Transformer Supervision 510
21.7.3 Pole Dead Protection 510
21.7.4 PSL Timers 511
21.8 Measurements and Recording 512
21.8.1 General 512
21.8.2 Disturbance Records 512
21.8.3 Event, Fault and Maintenance Records 512
21.8.4 Resistive Temperature Detectors 512
21.9 Ratings 514
21.9.1 AC Measuring Inputs 514
21.9.2 Current Transformer Inputs 514
21.9.3 Voltage Transformer Inputs 514
21.9.4 Auxiliary Supply Voltage 515
21.9.5 Nominal Burden 515
21.9.6 Power Supply Interruption 515
21.9.7 Supercapacitor 516
21.10 Input/Output Connections 517
21.10.1 Isolated Digital Inputs 517
21.10.1.1 Nominal Pickup and Reset Thresholds 517
21.10.2 Standard Output Contacts 517
21.10.3 High Break Output Contacts 518
21.10.4 Watchdog Contacts 518
21.11 Mechanical Specifications 519
21.11.1 Physical Parameters 519
21.11.2 Enclosure Protection 519
21.11.3 Mechanical Robustness 519
21.11.4 Transit Packaging Performance 519
21.12 Type Tests 520
21.12.1 Insulation 520
21.12.2 Creepage Distances and Clearances 520
21.12.3 High Voltage (Dielectric) Withstand 520
21.12.4 Impulse Voltage Withstand Test 520
21.13 Environmental Conditions 521
21.13.1 Ambient Temperature Range 521
21.13.2 Temperature Endurance Test 521
21.13.3 Ambient Humidity Range 521
21.13.4 Corrosive Environments 521
21.14 Electromagnetic Compatibility 522
21.14.1 1 MHz Burst High Frequency Disturbance Test 522
21.14.2 Damped Oscillatory Test 522
21.14.3 Immunity to Electrostatic Discharge 522
21.14.4 Electrical Fast Transient or Burst Requirements 522

P64-TM-EN-1 xv
Contents P64

21.14.5 Surge Withstand Capability 522


21.14.6 Surge Immunity Test 523
21.14.7 Immunity to Radiated Electromagnetic Energy 523
21.14.8 Radiated Immunity from Digital Communications 523
21.14.9 Radiated Immunity from Digital Radio Telephones 523
21.14.10 Immunity to Conducted Disturbances Induced by Radio Frequency Fields 523
21.14.11 Magnetic Field Immunity 524
21.14.12 Conducted Emissions 524
21.14.13 Radiated Emissions 524
21.14.14 Power Frequency 524

Appendix A Ordering Options 525

Appendix B Settings and Signals 529

Appendix C Wiring Diagrams 531

Appendix D Version History 647

xvi P64-TM-EN-1
CHAPTER 1

INTRODUCTION
Chapter 1 - Introduction P64

1.1 CHAPTER OVERVIEW


This chapter provides some general information about the technical manual and an introduction to the device(s)
described in this technical manual.
This chapter contains the following sections:
Chapter Overview 2
Foreword 3
Product Scope 5
Features and Functions 8
Logic Diagrams 10
Compliance 12
Functional Overview 13

2 P64-TM-EN-1
P64 Chapter 1 - Introduction

1.2 FOREWORD
This technical manual provides a functional and technical description of GE Vernova's 5th Generation transformer
protection IED, as well as a comprehensive set of instructions for using the device. The level at which this manual is
written assumes that you are already familiar with protection engineering and have experience in this discipline. The
description of principles and theory is limited to that which is necessary to understand the product. For further
details on general protection engineering theory, we refer you to GE Vernova's publication, Protection and
Automation Application Guide, which is available online or from our Contact Centre.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible. However we
cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We would therefore be
very pleased to hear from you if you discover any errors, or have any suggestions for improvement. Our policy is to
provide the information necessary to help you safely specify, engineer, install, commission, maintain, and eventually
dispose of this product. We consider that this manual provides the necessary information, but if you consider that
more details are needed, please contact us.
All feedback should be sent to our contact centre via:
GA.support@gevernova.com

1.2.1 TARGET AUDIENCE


This manual is aimed towards all professionals charged with installing, commissioning, maintaining,
troubleshooting, or operating any of the products within the specified product range. This includes installation and
commissioning personnel as well as engineers who will be responsible for operating the product.
The level at which this manual is written assumes that installation and commissioning engineers have knowledge of
handling electronic equipment. Also, system and protection engineers have a thorough knowledge of protection
systems and associated equipment.

1.2.2 TYPOGRAPHICAL CONVENTIONS


The following typographical conventions are used throughout this manual.
● The names for special keys appear in capital letters.
For example: ENTER
● When describing software applications, menu items, buttons, labels etc as they appear on the screen are
written in bold type.
For example: Select Save from the file menu.
● Filenames and paths use the courier font
For example: Example\File.text
● Special terminology is written with leading capitals
For example: Sensitive Earth Fault
● If reference is made to the IED's internal settings and signals database, the menu group heading (column)
text is written in upper case italics
For example: The SYSTEM DATA column
● If reference is made to the IED's internal settings and signals database, the setting cells and DDB signals are
written in bold italics
For example: The Language cell in the SYSTEM DATA column
● If reference is made to the IED's internal settings and signals database, the value of a cell's content is written
in the Courier font
For example: The Language cell in the SYSTEM DATA column contains the value English

P64-TM-EN-1 3
Chapter 1 - Introduction P64

1.2.3 NOMENCLATURE
Due to the technical nature of this manual, many special terms, abbreviations and acronyms are used throughout
the manual. Some of these terms are well-known industry-specific terms while others may be special product-
specific terms used by GE Vernova. The first instance of any acronym or term used in a particular chapter is
explained. In addition, a separate glossary is available on the GE Vernova website, or from the GE Vernova contact
centre.
We would like to highlight the following changes of nomenclature however:
● The word 'relay' is no longer used to describe the device itself. Instead, the device is referred to as the 'IED'
(Intelligent Electronic Device), the 'device', or the 'product'. The word 'relay' is used purely to describe the
electromechanical components within the device, i.e. the output relays.
● British English is used throughout this manual.
● The British term 'Earth' is used in favour of the American term 'Ground'.

1.2.4 COMPLIANCE
The device has undergone a range of extensive testing and certification processes to ensure and prove
compatibility with all target markets. A detailed description of these criteria can be found in the Technical
Specifications chapter.

4 P64-TM-EN-1
P64 Chapter 1 - Introduction

1.3 PRODUCT SCOPE


The MiCOM 5th Generation range of devices preserve transformer service life by offering fast protection for
transformer faults. Hosted on an advanced IED platform, the P64 products incorporate Current Differential,
Restricted Earth Fault (REF),Thermal, and Overfluxing protection, plus backup protection for uncleared external
faults. Further, the P64 devices provide a range of transformer condition monitoring functions such as Through-fault
monitoring, loss of life statistics, RTD and CLIO protection functionality.
All devices also provide a comprehensive range of additional features to aid with power system diagnosis and fault
analysis.
The P64 can be ordered in 40/60/80TE cases with several different digital input/output options also offered.
Model variants cover two and three winding power transformers, with up to five sets of 3-phase CT inputs. Backup
overcurrent protection can be directionalised, if you select the optional 3-phase VT input.
The P64 range consists of three models; the P642, P643, and P645.
● The P642 provides 8 on-board CTs to support two-winding 3-phase power transformers and 1or 2 single-
phase voltage transformers to support directionalisation and a range of voltage-related functions.
● The P643 provides 12 on-board CTs to support three-winding 3-phase power transformers, a single-phase
voltage transformer and an optional three-phase voltage transformer to support directionalisation and a range
of voltage-related functions including undervoltage, overvoltage and residual overvoltage protection.
● The P645 provides 18 on-board CTs to support three-winding 3-phase power transformers and other
applications needing 5 sets of 3-phase current inputs, a single-phase voltage transformer and an optional
three-phase voltage transformer to support directionalisation and a range of voltage-related functions
including undervoltage, overvoltage and residual overvoltage protection.
The difference in model variants are summarised below:

Feature/Variant P642 P643 P645


Case 40/60/80TE 60/80TE 60/80TE
Number of CT inputs 8 (6 Bias, 2 EF) 12 (9 bias, 3EF) 18 (15 Bias, 3EF)
Number of VT inputs 1 or 2 1 or 4 1 or 4
Number of bias inputs (3-phase CT sets) 2 3 5
Optically coupled digital inputs 8 - 32 16 - 48 16 - 48
Standard relay output contacts 8 - 32 16 - 32 16 - 32
Function keys No 10 10
Undervoltage/Overvoltage/Residual voltage protection No Yes Yes
Underfrequency/Overfrequency protection No Yes Yes
Overfluxing protection 1-phase only 1-phase + 3-phase 1-phase + 3-phase
Programmable LEDs 23 tri-colour 23 tri-colour 23 tri-colour

1.3.1 PRODUCT VERSIONS


Since software version 2, the evolution of the P64 product family has followed two paths as shown below:

P64-TM-EN-1 5
Chapter 1 - Introduction P64

J, K
02

Hardware version K (P645SV) Hardware version J (P642), K (P643/5)


Software version 12 Software version 04
 Hot-Standby Ethernet Failover  Negative Sequence Overvoltage
 Cyber Security  Voltage Controlled Overcurrent
 IEC61850 9-2L Edition 1  Low Impedance REF for autotransformer
 High Impedance REF
 User Alarms
 CT Exclusion
Hardware version M (P645SV)
Software version 20
Hardware version P (P642), M (P643/5)
 IEC61850 9-2LE Edition 2 Software version 05
 Hot-Standby Ethernet Failover
 Cyber Security
Hardware version M (P645SV)  More Disturbance Record channels
Software version 22
 Inclusion of duplicate GOOSE Hardware version P (P642), M (P643/5)
 IRG-B local sync function, for IRIG-B type Software version 06
changes from UTC to local  Extra I/O (40 opto-inputs)
 New DDBs added to indicate blocked password  2nd harmonic blocking for E/F, REF, POC
 Setting name and DDB signal changes
 Setting range extensions
 Vector Group Reference change
Hardware version M (P645SV)
 Changes to default PSL
Software version 90
 IEC 61850 Edition 1 & 2 switching
Hardware version P (P642), M (P643/5)
 RBAC
Software version 07
 Syslog
 Multi-client RCB  Sensitive CT module
 Voltage restraining overcurrent
 Additional fault record data

Hardware version P (P642), M (P643/5)


Software version 21
 IEC 61850 Edition 2
 Fourth neutral current element, derived
 Internal/external CBF initiation
 CB Control including XCBR
 UTC/Local feature in IRIG-B

Hardware version P (P642), M (P643/5)


Software version 91
 IEC 61850 Edition 1 & 2 switching
 RBAC
 Syslog
 Multi-client RCB

Hardware version Q (P64)


Software version AB
First release of MiCOM 5th Generation transformer protection. Relay models: P642/3/5 are released based on
software 91. The main changes in this new hardware and software release are as follows:
 A 10x performance increase in processing power over the previous Generation (4th Gen)
 Colour graphical HMI available as standard, and with native USB support. It includes 6 configurable pages, for
SLD, measurements and status signals
 Any model can be ordered in the 3 case sizes: 40TE (W 203.2 mm or 8"), 60TE (W 304.8 mm or 12") or 80TE (W
406.4 mm or 16"), with a variation in the number of I/O
 PRP, HSR and RSTP supported in the same order option
 CyberSentry IEC 62351-8
 5000 Events, 100 Faults, 1050s Oscillography and 128 Digital Signals
 IEC 61850 enhancements including Ed 2.1 compliance
 New Ethernet board - 1-2 Station Bus ports + Engineering port (CORTEC Hardware Option U/V/W/Y)
V00035a

Figure 1: P64x version evolution

1.3.2 ORDERING OPTIONS


All current models and variants for this product are defined in an interactive spreadsheet called the Cortec. This is
available on the company website.

6 P64-TM-EN-1
P64 Chapter 1 - Introduction

Alternatively, you can obtain it via the Contact Centre at:


GA.support@gevernova.com
A copy of the Cortec is also supplied as a static table in the Appendices of this document. However, it should only
be used for guidance as it provides a snapshot of the interactive data taken at the time of publication.
This technical manual is applicable to the product version A<PlatformSoftwareVersion>

P64-TM-EN-1 7
Chapter 1 - Introduction P64

1.4 FEATURES AND FUNCTIONS

1.4.1 PROTECTION FUNCTIONS


The P64 range of devices provides the following protection functions:
ANSI IEC 61850 Protection Function P642 P643 P645
87T LzdPDIF Transformer biased differential protection • • •

64 RefPDIF Low Impedance and High Impedance Restricted Earth Fault protection 2 3 3

49 ThmPTTR Thermal Overload (3 stages) • • •

32 PdpPDOP/PDUP Phase Directional Power (4 stages) • • •

24 PVPH Single-phase and three-phase V/Hz Overfluxing protection (4 stages) 1 1 (2) 1 (2)

LoL Loss of Life • • •

Thru Through-fault monitoring • • •

RTD RtfPTTR RTDs x 10 PT100 temperature probes (•) (•) (•)

CLIO PTUC Current Loop transducer I/O (4 input/4 output) (•) (•) (•)

50 OcpPTOC Definite time overcurrent protection (4 stages per winding) • • •

50N EfdPTOC Neutral/Ground Definite time overcurrent protection (4 stages per winding) • • •

51 OcpPTOC IDMT overcurrent protection (2 stages per winding) • • •

51N EfdPTOC Neutral/Ground IDMT overcurrent protection (2 stages per winding) • • •

46 NgcPTOC Negative sequence overcurrent (4 stages per winding) • • •


67 OcpPTOC Directional Phase Overcurrent protection (4 stages per winding) • • •
67N EfdPTOC Directional earth fault overcurrent protection (4 stages per winding) • • •
50BF RBRF CB Failure (Breaker Fail) protection (2 stages per winding) 2 3 5
27 VtpPhsPTUV Undervoltage protection (2 stages) (•) (•)
59 VtpPhsPTOV Overvoltage protection (2 stages) (•) (•)
59N VtpResPTOV Residual Overvoltage protection (2 stages) (•) (•)
47 NgvPTOV Negative sequence overvoltage protection (1 stage) (•) (•) (•)
81U FrqPTUF Underfrequency protection (4 stages) (•) (•)
81O FrqPTOF Overfrequency protection (2 stages) (•) (•)

Note:
If item is enclosed in brackets, this indicates that the feature is an ordering option.

1.4.2 CONTROL FUNCTIONS

Feature IEC 61850 ANSI


Watchdog contacts
Read-only mode
NERC compliant cyber-security
Function keys (up to 10) FnkGGIO

8 P64-TM-EN-1
P64 Chapter 1 - Introduction

Feature IEC 61850 ANSI


Programmable LEDs (up to 23) LedGGIO
Programmable hotkeys (2)
Programmable allocation of digital inputs and outputs
Fully customizable menu texts
Circuit breaker control, status & condition monitoring XCBR 52
Trip circuit and coil supervision
Control inputs PloGGIO1
Power-up diagnostics and continuous self-monitoring
Dual rated 1A and 5A CT inputs
Alternative setting groups (4)
Graphical programmable scheme logic (PSL)

1.4.3 MEASUREMENT FUNCTIONS

Measurement Function IEC 61850 ANSI


Measurement of all instantaneous & integrated values
MET
(Exact range of measurements depend on the device model)
Disturbance recorder for waveform capture – specified in samples per cycle RDRE DFR
Fault Records
Maintenance Records
Event Records/Event logging Event records
Time Stamping of Opto-inputs Yes Yes

1.4.4 COMMUNICATION FUNCTIONS


The device offers the following communication functions:

Feature ANSI
NERC compliant cyber-security
Front USB communication port for configuration
Rear serial RS485 communication port for SCADA control--Courier/DNP 3.0/IEC 60870-5-103 protocol
16S
selectable in settings
Rear serial FO communication ports for SCADA control (optional) - Courier/DNP 3.0/IEC 60870-5-103
16S
protocol selectable in settings
Ethernet communication (optional)--IEC 61850 16E
Redundant Ethernet communication (optional)--IEC 61850 16E
Rear Ethernet engineering port for configuration 16E
SNMP 16E
IRIG-B modulated and unmodulated time synchronisation (optional) CLK
IEEE 1588 PTP

P64-TM-EN-1 9
Chapter 1 - Introduction P64

1.5 LOGIC DIAGRAMS


This technical manual contains many logic diagrams, which should help to explain the functionality of the device.
Although this manual has been designed to be as specific as possible to the chosen product, it may contain
diagrams, which have elements applicable to other products. If this is the case, a qualifying note will accompany the
relevant part.
The logic diagrams follow a convention for the elements used, using defined colours and shapes. A key to this
convention is provided below. We recommend viewing the logic diagrams in colour rather than in black and white.
The electronic version of the technical manual is in colour, but the printed version may not be. If you need coloured
diagrams, they can be provided on request by calling the contact centre and quoting the diagram number.

10 P64-TM-EN-1
P64 Chapter 1 - Introduction

Key:
Energising Quantity AND gate &

Internal Signal OR gate 1

DDB Signal XOR gate XOR

Internal function NOT gate

Setting cell Logic 0 0

Setting value Timer

Hardcoded setting
Pulse / Latch

Measurement Cell S
SR Latch Q
R
Internal Calculation
S
SR Latch Q
Derived setting Reset Dominant RD

HMI key Latched on positive edge

Connection / Node Inverted logic input


1
Switch Soft switch 2

Switch Multiplier X

Bandpass filter
Comparator for detecting
undervalues

Comparator for detecting


V00063 overvalues

Figure 2: Key to logic diagrams

P64-TM-EN-1 11
Chapter 1 - Introduction P64

1.6 COMPLIANCE
The device has undergone a range of extensive testing and certification processes to ensure and prove
compatibility with all target markets. A detailed description of these criteria can be found in the Technical
Specifications chapter.

12 P64-TM-EN-1
P64 Chapter 1 - Introduction

1.7 FUNCTIONAL OVERVIEW

2nd Remote Remote Local


Ethernet Fault records
Comm. port Comm. port Communication
Disturbance
Record
I-HV Measurements
Self monitoring

47
IN-HV

50N/51N 50N/51N
IN-LV EF-1 EF-3 51V 51V
50N/51N 50N/51N DT IDMT
EF-2 EF-4

I-LV
DIFF
Thru CTS
IN-TV

I-TV

virtual
I-TV

BINARY Always Available Transformer Differential


CLIO I/O
RTDs MEASI MEASO
Optional or Specific Protection P64

1. The three-phase VT input is optional.


2. The 27, 59, 59N and VTS functions require the three-phase VT input.
3. The frequency required by the 81 function is obtained from any analog signal but the voltage signals have priority over the current signals.

E00073a

Figure 3: Functional overview

P64-TM-EN-1 13
Chapter 1 - Introduction P64

14 P64-TM-EN-1
CHAPTER 2

SAFETY INFORMATION
Chapter 2 - Safety Information P64

2.1 CHAPTER OVERVIEW


This chapter provides information about the safe handling of the equipment. The equipment must be properly
installed and handled in order to maintain it in a safe condition and to keep personnel safe at all times. You must be
familiar with information contained in this chapter before unpacking, installing, commissioning, or servicing the
equipment.
This chapter contains the following sections:
Chapter Overview 16
Health and Safety 17
Symbols 18
Installation, Commissioning and Servicing 19
Decommissioning and Disposal 25
Regulatory Compliance 26

16 P64-TM-EN-1
P64 Chapter 2 - Safety Information

2.2 HEALTH AND SAFETY


Personnel associated with the equipment must be familiar with the contents of this Safety Information.
When electrical equipment is in operation, dangerous voltages are present in certain parts of the equipment.
Improper use of the equipment and failure to observe warning notices will endanger personnel.
Only qualified personnel may work on or operate the equipment. Qualified personnel are individuals who are:
● familiar with the installation, commissioning, and operation of the equipment and the system to which it is
being connected.
● familiar with accepted safety engineering practises and are authorised to energise and de-energise
equipment in the correct manner.
● trained in the care and use of safety apparatus in accordance with safety engineering practises
● trained in emergency procedures (first aid).

The documentation provides instructions for installing, commissioning and operating the equipment. It cannot,
however cover all conceivable circumstances. In the event of questions or problems, do not take any action without
proper authorisation. Please contact your local sales office and request the necessary information.

P64-TM-EN-1 17
Chapter 2 - Safety Information P64

2.3 SYMBOLS
Throughout this manual you will come across the following symbols. You will also see these symbols on parts of the
equipment.

Caution:
Refer to equipment documentation. Failure to do so could result in damage to the
equipment

Warning:
Risk of electric shock

Warning:
Risk of damage to eyesight

Earth terminal. Note: This symbol may also be used for a protective conductor (earth) terminal if that terminal
is part of a terminal block or sub-assembly.

Protective conductor (earth) terminal

Instructions on disposal requirements

Note:
The term 'Earth' used in this manual is the direct equivalent of the North American term 'Ground'.

18 P64-TM-EN-1
P64 Chapter 2 - Safety Information

2.4 INSTALLATION, COMMISSIONING AND SERVICING

2.4.1 LIFTING HAZARDS


Many injuries are caused by:
● Lifting heavy objects
● Lifting things incorrectly
● Pushing or pulling heavy objects
● Using the same muscles repetitively

Plan carefully, identify any possible hazards and determine how best to move the product. Look at other ways of
moving the load to avoid manual handling. Use the correct lifting techniques and Personal Protective Equipment
(PPE) to reduce the risk of injury.

2.4.2 ELECTRICAL HAZARDS

Caution:
All personnel involved in installing, commissioning, or servicing this equipment must
be familiar with the correct working procedures.

Caution:
Consult the equipment documentation before installing, commissioning, or servicing
the equipment.

Caution:
Always use the equipment as specified. Failure to do so will jeopardise the protection
provided by the equipment.

Warning:
Removal of equipment panels or covers may expose hazardous live parts. Do not
touch until the electrical power is removed. Take care when there is unlocked access
to the rear of the equipment.

Warning:
Isolate the equipment before working on the terminal strips.

Warning:
Use a suitable protective barrier for areas with restricted space, where there is a risk
of electric shock due to exposed terminals.

Caution:
Disconnect power before disassembling. Disassembly of the equipment may expose
sensitive electronic circuitry. Take suitable precautions against electrostatic voltage
discharge (ESD) to avoid damage to the equipment.

P64-TM-EN-1 19
Chapter 2 - Safety Information P64

Warning:
NEVER look into optical fibres or optical output connections. Always use optical
power meters to determine operation or signal level.

Warning:
Testing may leave capacitors charged to dangerous voltage levels. Discharge
capacitors by reducing test voltages to zero before disconnecting test leads.

Caution:
Operate the equipment within the specified electrical and environmental limits.

Caution:
Before cleaning the equipment, ensure that no connections are energised. Use a lint
free cloth dampened with clean water.

Note:
Contact fingers of test plugs are normally protected by petroleum jelly, which should not be removed.

2.4.3 UL/CSA/CUL REQUIREMENTS


The information in this section is applicable only to equipment carrying UL/CSA/CUL markings.

Caution:
Equipment intended for rack or panel mounting is for use on a flat surface of a Type 1
enclosure, as defined by Underwriters Laboratories (UL).

Caution:
To maintain compliance with UL and CSA/CUL, install the equipment using UL/CSA-
recognised parts for: cables, protective fuses, fuse holders and circuit breakers,
insulation crimp terminals, and replacement internal batteries.

2.4.4 FUSING REQUIREMENTS

Caution:
Where UL/CSA listing of the equipment is required for external fuse protection, a UL
or CSA Listed fuse must be used for the auxiliary supply. The listed protective fuse
type is: Class J time delay fuse, with a maximum current rating of 15 A and a
minimum DC rating of 250 V dc (for example type AJT15).

Caution:
Where UL/CSA listing of the equipment is not required, a high rupture capacity (HRC)
fuse type with a maximum current rating of 16 Amps and a minimum dc rating of 250
V dc may be used for the auxiliary supply (for example Red Spot type NIT or TIA).
For P50 models, use a 1A maximum T-type fuse.
For P60 models, use a 4A maximum T-type fuse.

20 P64-TM-EN-1
P64 Chapter 2 - Safety Information

Caution:
Digital input circuits should be protected by a high rupture capacity NIT or TIA fuse
with maximum rating of 16 A. for safety reasons, current transformer circuits must
never be fused. Other circuits should be appropriately fused to protect the wire used.

Caution:
CTs must NOT be fused since open circuiting them may produce lethal hazardous
voltages

2.4.5 EQUIPMENT CONNECTIONS

Warning:
Terminals exposed during installation, commissioning and maintenance may present
a hazardous voltage unless the equipment is electrically isolated.

Caution:
Tighten M4 clamping screws of heavy duty terminal block connectors to a nominal
torque of 1.3 Nm.
Tighten captive screws of terminal blocks to 0.5 Nm minimum and 0.6 Nm maximum.

Caution:
Always use insulated crimp terminations for voltage and current connections.

Caution:
Always use the correct crimp terminal and tool according to the wire size.

Caution:
Watchdog (self-monitoring) contacts are provided to indicate the health of the device
on some products. We strongly recommend that you hard wire these contacts into the
substation's automation system, for alarm purposes.

2.4.6 PROTECTION CLASS 1 EQUIPMENT REQUIREMENTS

Caution:
Earth the equipment with the supplied PCT (Protective Conductor Terminal).

Caution:
Do not remove the PCT.

Caution:
The PCT is sometimes used to terminate cable screens. Always check the PCT’s
integrity after adding or removing such earth connections.

P64-TM-EN-1 21
Chapter 2 - Safety Information P64

Caution:
Use a locknut or similar mechanism to ensure the integrity of stud-connected PCTs.

Caution:
The recommended minimum PCT wire size is 2.5 mm² for countries whose mains
supply is 230 V (e.g. Europe) and 3.3 mm² for countries whose mains supply is 110 V
(e.g. North America). This may be superseded by local or country wiring regulations.
For P60 products, the recommended minimum PCT wire size is 6 mm². See product
documentation for details.

Caution:
The PCT connection must have low-inductance and be as short as possible.

Caution:
All connections to the equipment must have a defined potential. Connections that are
pre-wired, but not used, should be earthed, or connected to a common grouped
potential.

2.4.7 PRE-ENERGISATION CHECKLIST

Caution:
Check voltage rating/polarity (rating label/equipment documentation).

Caution:
Check CT circuit rating (rating label) and integrity of connections.

Caution:
Check protective fuse or miniature circuit breaker (MCB) rating.

Caution:
Check integrity of the PCT connection.

Caution:
Check voltage and current rating of external wiring, ensuring it is appropriate for the
application.

2.4.8 PERIPHERAL CIRCUITRY

Warning:
Do not open the secondary circuit of a live CT since the high voltage produced may
be lethal to personnel and could damage insulation. Short the secondary of the line
CT before opening any connections to it.

22 P64-TM-EN-1
P64 Chapter 2 - Safety Information

Note:
For most GE Vernova equipment with ring-terminal connections, the threaded terminal block for current transformer
termination is automatically shorted if the module is removed. Therefore external shorting of the CTs may not be required.
Check the equipment documentation and wiring diagrams first to see if this applies.

Caution:
Where external components such as resistors or voltage dependent resistors (VDRs)
are used, these may present a risk of electric shock or burns if touched.

Warning:
Take extreme care when using external test blocks and test plugs such as the MMLG,
MMLB and P990, as hazardous voltages may be exposed. Ensure that CT shorting
links are in place before removing test plugs, to avoid potentially lethal voltages.

Warning:
Data communication cables with accessible screens and/or screen conductors,
(including optical fibre cables with metallic elements), may create an electric shock
hazard in a sub-station environment if both ends of the cable screen are not
connected to the same equipotential bonded earthing system.

To reduce the risk of electric shock due to transferred potential hazards:

i. The installation shall include all necessary protection measures to ensure that no
fault currents can flow in the connected cable screen conductor.

ii. The connected cable shall have its screen conductor connected to the protective
conductor terminal (PCT) of the connected equipment at both ends. This connection
may be inherent in the connectors provided on the equipment but, if there is any
doubt, this must be confirmed by a continuity test.

iii. The protective conductor terminal (PCT) of each piece of connected equipment
shall be connected directly to the same equipotential bonded earthing system.

iv. If, for any reason, both ends of the cable screen are not connected to the same
equipotential bonded earth system, precautions must be taken to ensure that such
screen connections are made safe before work is done to, or in proximity to, any such
cables.

v. No equipment shall be connected to any download or maintenance circuits or


connectors of this product except temporarily and for maintenance purposes only.

vi. Equipment temporarily connected to this product for maintenance purposes shall
be protectively earthed (if the temporary equipment is required to be protectively
earthed), directly to the same equipotential bonded earthing system as the product.

Warning:
Small Form-factor Pluggable (SFP) modules which provide copper Ethernet
connections typically do not provide any additional safety isolation. Copper Ethernet
SFP modules must only be used in connector positions intended for this type of
connection.

P64-TM-EN-1 23
Chapter 2 - Safety Information P64

2.4.9 UPGRADING/SERVICING

Warning:
Do not insert or withdraw modules, PCBs or expansion boards from the equipment
while energised, as this may result in damage to the equipment. Hazardous live
voltages would also be exposed, endangering personnel.

Caution:
Internal modules and assemblies can be heavy and may have sharp edges. Take care
when inserting or removing modules into or out of the IED.

24 P64-TM-EN-1
P64 Chapter 2 - Safety Information

2.5 DECOMMISSIONING AND DISPOSAL

Caution:
Before decommissioning, completely isolate the equipment power supplies (both
poles of any dc supply). The auxiliary supply input may have capacitors in parallel,
which may still be charged. To avoid electric shock, discharge the capacitors using
the external terminals before decommissioning.

Caution:
Avoid incineration or disposal to water courses. Dispose of the equipment in a safe,
responsible and environmentally friendly manner, and if applicable, in accordance
with country-specific regulations.

P64-TM-EN-1 25
Chapter 2 - Safety Information P64

2.6 REGULATORY COMPLIANCE


Compliance with the European Commission Directive on EMC and LVD is demonstrated using a technical file.

2.6.1 EMC COMPLIANCE: 2014/30/EU


The product specific Declaration of Conformity (DoC) lists the relevant harmonised standard(s) or conformity
assessment used to demonstrate compliance with the EMC directive.

2.6.2 LVD COMPLIANCE: 2014/35/EU


The product specific Declaration of Conformity (DoC) lists the relevant harmonized standard(s) or conformity
assessment used to demonstrate compliance with the LVD directive.
Safety related information, such as the installation I overvoltage category, pollution degree and operating
temperature ranges are specified in the Technical Data section of the relevant product documentation and/or on the
product labelling.
Unless otherwise stated in the Technical Data section of the relevant product documentation, the equipment is
intended for indoor use only. Where the equipment is required for use in an outdoor location, it must be mounted in
a specific cabinet or housing to provide the equipment with the appropriate level of protection from the expected
outdoor environment.

2.6.3 UL/CUL COMPLIANCE


If marked with this logo, the product is compliant with the requirements of the Canadian and USA Underwriters
Laboratories.
The relevant UL file number and ID is shown on the equipment.

2.6.4 UKCA COMPLIANCE


Compliance with the UK Directive on EMC and Safety is demonstrated using a technical file.

2.6.5 EMC COMPLIANCE: ELECTROMAGNETIC COMPATIBILITY


REGULATIONS 2016
The product specific Declaration of Conformity (DoC) lists the relevant harmonised standard(s) or conformity
assessment used to demonstrate compliance with the EMC directive.

2.6.6 SAFETY COMPLIANCE: ELECTRICAL EQUIPMENT (SAFETY)


REGULATIONS 2016
The product specific Declaration of Conformity (DoC) lists the relevant harmonized standard(s) or conformity
assessment used to demonstrate compliance with the Safety Regulations. Safety related information, such as the

26 P64-TM-EN-1
P64 Chapter 2 - Safety Information

installation I overvoltage category, pollution degree and operating temperature ranges are specified in the Technical
Data section of the relevant product documentation and/or on the product labelling.
Unless otherwise stated in the Technical Data section of the relevant product documentation, the equipment is
intended for indoor use only. Where the equipment is required for use in an outdoor location, it must be mounted in
a specific cabinet or housing to provide the equipment with the appropriate level of protection from the expected
outdoor environment.

2.6.7 MOROCCO COMPLIANCE


Compliance with the Morocco Directive on EMC and Safety is demonstrated using a technical file.

2.6.8 EMC COMPLIANCE: NO. 2574-14 OF RAMADAN 1436


The product specific Declaration of Conformity (DoC) lists the relevant harmonised standard(s) or conformity
assessment used to demonstrate compliance with the EMC directive.

2.6.9 SAFETY COMPLIANCE: NO. 2573-14 OF RAMADAN 1436


The product specific Declaration of Conformity (DoC) lists the relevant harmonized standard(s) or conformity
assessment used to demonstrate compliance with the Safety Directive. Safety related information, such as the
installation I overvoltage category, pollution degree and operating temperature ranges are specified in the Technical
Data section of the relevant product documentation and/or on the product labelling.
Unless otherwise stated in the Technical Data section of the relevant product documentation, the equipment is
intended for indoor use only. Where the equipment is required for use in an outdoor location, it must be mounted in
a specific cabinet or housing to provide the equipment with the appropriate level of protection from the expected
outdoor environment.

P64-TM-EN-1 27
Chapter 2 - Safety Information P64

28 P64-TM-EN-1
CHAPTER 3

HARDWARE DESIGN
Chapter 3 - Hardware Design P64

3.1 CHAPTER OVERVIEW


This chapter provides information about the product's hardware design.
This chapter contains the following sections:
Chapter Overview 30
Hardware Architecture 31
Mechanical Implementation 32
Front Panel 34
Rear Panel 38
Boards and Modules 40

30 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

3.2 HARDWARE ARCHITECTURE


The main components comprising devices based on the Px4x platform are as follows:
● The housing, consisting of a front panel and connections at the rear
● The Main processor module consisting of the main CPU (Central Processing Unit), memory and an interface
to the front panel HMI (Human Machine Interface)
● A selection of plug-in boards and modules with presentation at the rear for the power supply, communication
functions, digital I/O, analogue inputs, and time synchronisation connectivity
All boards and modules are connected by a parallel data and address bus, which allows the processor module to
send and receive information to and from the other modules as required. There is also a separate serial data bus for
conveying sampled data from the input module to the CPU. These parallel and serial databuses are shown as a
single interconnection module in the following figure, which shows typical modules and the flow of data between
them.

Keypad
Output relay boards Output relay contacts
Processor module
Front panel HMI

LCD
Opto-input boards Digital inputs
LEDs
I/O
Front port
CTs Power system currents
Memory
Interconnection

Flash memory for settings


& Records
VTs Power system voltages
Analogue Inputs

RS485 modules RS485 communication


Watchdog
contacts Watchdog module
IRIG-B module Time synchronisation
+ LED

Ethernet modules Ethernet communication


Auxiliary
PSU module
Supply Communications

Note: Not all modules are applicable to all products

V00309

Figure 4: Hardware architecture

P64-TM-EN-1 31
Chapter 3 - Hardware Design P64

3.3 MECHANICAL IMPLEMENTATION


All products based on the Px4x platform have common hardware architecture. The hardware is modular and
consists of the following main parts:
● Case and terminal blocks
● Boards and modules
● Front panel
The case comprises the housing metalwork and terminal blocks at the rear. The boards fasten into the terminal
blocks and are connected together by a ribbon cable. This ribbon cable connects to the processor in the front panel.
The following diagram shows an exploded view of a typical product. The diagram shown does not necessarily
represent exactly the product model described in this manual.

Figure 5: Exploded view of IED

3.3.1 HOUSING VARIANTS


The Px4x range of products are implemented in a range of case sizes. Case dimensions for industrial products
usually follow modular measurement units based on rack sizes. These are: U for height and TE for width, where:
● 1U = 1.75 inches = 44.45 mm
● 1TE = 0.2 inches = 5.08 mm

The products are available in panel-mount or standalone versions. All products are nominally 4U high. This equates
to 177.8 mm or 7 inches.
The cases are pre-finished steel with a conductive covering of aluminium and zinc. This provides good grounding at
all joints, providing a low resistance path to earth that is essential for performance in the presence of external noise.
The case width depends on the product type and its hardware options. There are three different case widths for the
described range of products: 40TE, 60TE and 80TE. The case dimensions and compatibility criteria are as follows:

Case width (TE) Case width (mm) Case width (inches)


40TE 203.2 8
60TE 304.8 12
80TE 406.4 16

32 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

3.3.2 LIST OF BOARDS


The product's hardware consists of several modules drawn from a standard range. The exact specification and
number of hardware modules depends on the model number and variant. Depending on the exact model, the
product in question will use a selection of the following boards.

Board Use
Main Processor board - 40TE or smaller Main Processor board - without support for function keys
Main Processor board - 60TE or larger Main Processor board - with support for function keys
Power supply board - 24/54V DC Power supply input. Accepts DC voltage between 24V and 54V
Power supply board - 48/125V DC Power supply input. Accepts DC voltage between 48V and 125V
Power supply board - 110/250V DC Power supply input. Accepts DC voltage between 110V and 125V
Transformer board Contains the voltage and current transformers
Input board Contains the A/D conversion circuitry
Input board with opto-inputs Contains the A/D conversion circuitry + 8 digital opto-inputs
IRIG-B board - modulated input Interface board for modulated IRIG-B timing signal
Fibre board + IRIG-B Interface board for fibre-based RS485 connection + modulated IRIG-B
High-break output relay board Output relay board with high breaking capacity relays
Single Ethernet, universal IRIG-B, Single LC duplex Ethernet port with universal IRIG-B and IEEE1588 and 1 RJ45
IEEE1588, Maintenance Port Maintenance/Engineering Port
Redundant Ethernet RSTP + PRP + HSR + 2 LC duplex redundant Ethernet ports running RSTP + PRP + HSR + Failover
Failover ports, serial fibre port, universal (two fibre pairs), with IEC 60870-5-103 serial fibre ST ports with on-board
IRIG-B universal IRIG-B and IEEE 1588 and 1 RJ45 Maintenance/engineering port
2 RJ45 duplex redundant Ethernet ports running RSTP + PRP + HSR + Failover
Redundant Ethernet RSTP + PRP + HSR +
(two copper pairs), with on-board universal IRIG-B and IEEE 1588 and 1 RJ45
Failover universal IRIG-B
Maintenance/engineering port
2 LC duplex redundant Ethernet ports running RSTP + PRP + HSR + Failover
Redundant Ethernet RSTP + PRP + HSR +
(two fibre pairs), with on-board universal IRIG-B and IEEE 1588 and 1 RJ45
Failover ports, universal IRIG-B
Maintenance/engineering port
Output relay output board Standard output relay board
RTD board Contains 10 Resistive Temperature Device inputs
CLIO board Contains 4 current loop inputs and 4 current loop outputs

P64-TM-EN-1 33
Chapter 3 - Hardware Design P64

3.4 FRONT PANEL


Depending on the exact model and chosen options, the product will be housed in either a 40TE, 60TE or 80TE
case. By way of example, the following diagram shows the front panel of a typical unit. The front panels of the
products based on 40TE, 60TE and 80TE cases have a lot of commonality and differ only in that the 40TE front
panel does not include 10 function keys with their associated user-programmable LEDs.

Figure 6: Front panel (80TE)

The front panel consists of:


● Top and bottom compartments with hinged cover
● LCD display
● Keypad
● USB Type B port inside the bottom compartment
● Fixed function LEDs
● Function keys and LEDs (60TE and 80TE models)
● Programmable LEDs

3.4.1 FRONT PANEL COMPARTMENTS


The top compartment contains labels for the:
● Serial number
● Current and voltage ratings.

The bottom compartment contains:


● USB type B port

3.4.2 HMI PANEL


The keypad provides full access to the device functionality using a range of menu options. The information is
displayed on the colour LCD display.

34 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

The colour LCD display is an active matrix Thin Film Transistor (TFT) Liquid Crystal Display (LCD) that uses
amorphous silicon TFT as a switching device. This module is composed of a Transmissive type TFT‐LCD Panel,
driver circuit and back‐light unit. The resolution of the 4.0” TFT‐LCD is 480x480 pixels and it can display up to
16.7M colours.

Figure 7: HMI panel

3.4.3 KEYPAD
The keypad consists of the following keys:

4 arrow keys to navigate the menus, changing values within the cell or
to select the next item on the SLD (organised around the Enter key).

An enter key for changing and executing settings. When a bottom


banner menu context key label is selected, the OK key can also be
used to navigate between pages.

A clear/reset key for clearing the current setting dialogue or to navigate


to the top menu.

A home key for navigating to the default menu view.

2 menu context keys used to navigate between pages.

P64-TM-EN-1 35
Chapter 3 - Hardware Design P64

Open/Close keys (colour coded)


Note: Colour coding is selectable via labels and configuration of PSL/
SLD.

Local/remote key to select between local or remote modes.

3.4.4 USB PORT


The USB port is situated inside the bottom compartment, and is used to communicate with a locally connected PC.
It has two main purposes:
● To transfer settings between the PC and the device.
● For downloading firmware updates and menu text editing.

The port is intended for temporary connection during testing, installation and commissioning. It is not intended to be
used for permanent SCADA communications. This port supports the Courier communication protocol only. Courier
is a proprietary communication protocol to allow communication with a range of protection equipment, and between
the device and the Windows-based support software package.
You can connect the unit to a PC with a USB cable up to 5 m in length.
The inactivity timer for the front port is set to 15 minutes. This controls how long the unit maintains its level of
password access on the front port. If no messages are received on the front port for 15 minutes, any password
access level that has been enabled is cancelled.

Note:
The front USB port does not support automatic extraction of event and disturbance records, although this data can be
accessed manually.

Caution:
When not in use, always close the cover of the USB port to prevent contamination.

3.4.5 FIXED FUNCTION LEDS


Four fixed-function LEDs on the left-hand side of the front panel indicate the following conditions.
● Trip (Red) switches ON when the IED issues a trip signal. It is reset when the associated fault record is
cleared from the front display. Also the trip LED can be configured as self-resetting.
● Alarm (Yellow) flashes when the IED registers an alarm. This may be triggered by a fault, event or
maintenance record. The LED flashes until the alarms have been accepted (read), then changes to
constantly ON. When the alarms are cleared, the LED switches OFF.
● Out of service (Yellow) is ON when the IED's functions are unavailable.
● Healthy (Green) is ON when the IED is in correct working order, and should be ON at all times. It goes OFF if
the unit’s self-tests show there is an error in the hardware or software. The state of the healthy LED is
reflected by the watchdog contacts at the back of the unit.

36 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

3.4.6 FUNCTION KEYS


The programmable function keys are available for custom use for some models.
Factory default settings associate specific functions to these keys, but by using programmable scheme logic, you
can change the default functions of these keys to fit specific needs. Adjacent to these function keys are
programmable LEDs, which are usually set to be associated with their respective function keys. The device has 10
function keys in the 60TE and 80TE case size models and no function keys in the 40TE case size model.

3.4.7 PROGRAMABLE LEDS


The device has 13 of programmable LEDs, which can be associated with PSL-generated signals. The
programmable LEDs are tri-colour and can be set to RED, YELLOW or GREEN.

P64-TM-EN-1 37
Chapter 3 - Hardware Design P64

3.5 REAR PANEL


The MiCOM Px40 series uses a modular construction. Most of the internal structure consists of boards and modules
that fit into slots. Some of the boards plug into terminal blocks, which are bolted onto the rear of the unit. However,
some boards such as the communications boards have their own connectors. The rear panel consists of these
terminal blocks plus the rears of the communications boards.
The back panel cut-outs and slot allocations vary. This depends on the product, the type of boards and the terminal
blocks needed to populate the case. The following diagram shows a typical rear view of a case populated with
various boards.

Figure 8: Rear view of populated case

Note:
This diagram is just an example and may not show the exact product described in this manual. It also does not show the full
range of available boards, just a typical arrangement.

Not all slots are the same size. The slot width depends on the type of board or terminal block. For example, HD
(heavy duty) terminal blocks, as required for the analogue inputs, require a wider slot size than MD (medium duty)
terminal blocks. The board positions are not generally interchangeable. Each slot is designed to house a particular
type of board. Again this is model-dependent.
The device may use one or more of the terminal block types shown in the following diagram. The terminal blocks
are fastened to the rear panel with screws.
● Heavy duty (HD) terminal blocks for CT and VT circuits
● Medium duty (MD) terminal blocks for the power supply, opto-inputs, relay outputs and rear communications
port
● MiDOS terminal blocks for CT and VT circuits
● RTD/CLIO terminal block for connection to analogue transducers

38 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

,
Figure 9: Terminal block types

Note:
Not all products use all types of terminal blocks. The product described in this manual may use one or more of the above
types.

3.5.1 TERMINAL BLOCK INGRESS PROTECTION


IP2x shields and side cover panels are designed to provide IP20 ingress protection for MiCOM terminal blocks. The
shields and covers may be attached during installation or retrofitted to upgrade existing installations - see figure
below. For more information, contact your local sales office or our worldwide Contact Centre.

Figure 10: Example - fitted IP2x shields (cabling omitted for clarity)

P64-TM-EN-1 39
Chapter 3 - Hardware Design P64

3.6 BOARDS AND MODULES


Each product comprises a selection of PCBs (Printed Circuit Boards) and subassemblies, depending on the chosen
configuration.

3.6.1 PCBS
A PCB typically consists of the components, a front connector for connecting into the main system parallel bus via a
ribbon cable, and an interface to the rear. This rear interface may be:
● Directly presented to the outside world (as is the case for communication boards such as Ethernet Boards)
● Presented to a connector, which in turn connects into a terminal block bolted onto the rear of the case (as is
the case for most of the other board types)

Figure 11: Rear connection to terminal block

3.6.2 SUBASSEMBLIES
A sub-assembly consists of two or more boards bolted together with spacers and connected with electrical
connectors. It may also have other special requirements such as being encased in a metal housing for shielding
against electromagnetic radiation.
Boards are designated by a part number beginning with ZN, whereas pre-assembled sub-assemblies are
designated with a part number beginning with GN. Sub-assemblies, which are put together at the production stage,
do not have a separate part number.

40 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

The products in the Px40 series typically contain two sub-assemblies:


● The power supply assembly comprising:
○ A power supply board
○ An output relay board
● The input module comprising:
○ One or more transformer boards, which contains the voltage and current transformers (partially or fully
populated)
○ One or more input boards
○ Metal protective covers for EM (electromagnetic) shielding
The input module is pre-assembled and is therefore assigned a GN number, whereas the power supply module is
assembled at production stage and does not therefore have an individual part number.

3.6.3 MAIN PROCESSOR BOARD

Figure 12: Main processor board

The main processor board performs all calculations and controls the operation of all other modules in the IED,
including the data communication and user interfaces. This is the only board that does not fit into one of the slots. It
resides in the front panel and connects to the rest of the system using an internal ribbon cable.
The LCD and LEDs are mounted on the processor board along with the front panel communication ports.
The memory on the main processor board is split into two categories: volatile and non-volatile. The volatile memory
is DRAM, used by the processor to run the software and store data during calculations. The non-volatile memory is
Flash memory and is used to store Product Firmware, text and configuration data including the present setting
values, disturbance records, events, fault and maintenance record data.
There are two board types available depending on the size of the case:
● For models in 40TE cases
● For models in 60TE cases and larger

P64-TM-EN-1 41
Chapter 3 - Hardware Design P64

3.6.4 POWER SUPPLY BOARD

Figure 13: Power supply board

The power supply board provides power to the unit. One of three different configurations of the power supply board
can be fitted to the unit. This is specified at the time of order and depends on the magnitude of the supply voltage
that will be connected to it.
There are three board types, which support the following voltage ranges:
● 24/54 V DC
● 48/125 V DC or 40-100V AC
● 110/250 V DC or 100-240V AC
The power supply board connector plugs into a medium duty terminal block. This terminal block is always
positioned on the right hand side of the unit looking from the rear.
The power supply board is usually assembled together with a relay output board to form a complete subassembly,
as shown in the following diagram.

42 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

Figure 14: Power supply assembly

The power supply outputs are used to provide isolated power supply rails to the various modules within the unit.
Three voltage levels are used by the unit’s modules:
● 5.1 V for all of the digital circuits
● +/- 16 V for the analogue electronics such as on the input board
● 22 V for driving the output relay coils.
All power supply voltages, including the 0 V earth line, are distributed around the unit by the 64-way ribbon cable.
The power supply board incorporates inrush current limiting. This limits the peak inrush current to approximately 10
A.
Power is applied to pins 1 and 2 of the terminal block, where pin 1 is negative and pin 2 is positive. The pin
numbers are clearly marked on the terminal block as shown in the following diagram.

P64-TM-EN-1 43
Chapter 3 - Hardware Design P64

Figure 15: Power supply terminals

3.6.4.1 WATCHDOG
The Watchdog contacts are also hosted on the power supply board. The Watchdog facility provides two output relay
contacts, one normally open and one normally closed. These are used to indicate the health of the device and are
driven by the main processor board, which continually monitors the hardware and software when the device is in
service.

44 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

Figure 16: Watchdog contact terminals

3.6.4.2 REAR SERIAL PORT


The rear serial port (RP1) is housed on the power supply board. This is a three-terminal EIA(RS)485 serial
communications port and is intended for use with a permanently wired connection to a remote control centre for
SCADA communication. The interface supports half-duplex communication and provides optical isolation for the
serial data being transmitted and received.
The physical connectivity is achieved using three screw terminals; two for the signal connection, and the third for
the earth shield of the cable. These are located on pins 16, 17 and 18 of the power supply terminal block, which is
on the far right looking from the rear. The interface can be selected between RS485 and K-bus. When the K-Bus
option is selected, the two signal connections are not polarity conscious.
The polarity independent K-bus can only be used for the Courier data protocol. The polarity conscious MODBUS,
IEC 60870-5-103 and DNP3.0 protocols need RS485.
The following diagram shows the rear serial port. The pin assignments are as follows:
● Pin 16: Earth shield
● Pin 17: Negative signal
● Pin 18: Positive signal

P64-TM-EN-1 45
Chapter 3 - Hardware Design P64

Figure 17: Rear serial port terminals

An additional serial port with D-type presentation is available as an optional board, if required.

3.6.5 INPUT MODULE - 1 TRANSFORMER BOARD

Figure 18: Input module - 1 transformer board

The input module consists of the main input board coupled together with an instrument transformer board. The
instrument transformer board contains the voltage and current transformers, which isolate and scale the analogue
input signals delivered by the system transformers. The input board contains the A/D conversion and digital
processing circuitry, as well as eight digital isolated inputs (opto-inputs).
The boards are connected together physically and electrically. The module is encased in a metal housing for
shielding against electromagnetic interference.

46 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

3.6.5.1 INPUT MODULE CIRCUIT DESCRIPTION

Optical 8 digital inputs Optical


Isolator Isolator

Noise Noise
filter filter

Parallel Bus

Buffer

Transformer
board

VT
or
CT

Serial Serial Link


A/D Converter
interface

VT
or
CT

V00239

Figure 19: Input module schematic

A/D Conversion
The differential analogue inputs from the CT and VT transformers are presented to the main input board as shown.
Each differential input is first converted to a single input quantity referenced to the input board’s earth potential. The
analogue inputs are sampled and converted to digital, then filtered to remove unwanted properties. The samples
are then passed through a serial interface module which outputs data on the serial sample data bus.
The calibration coefficients are stored in non-volatile memory. These are used by the processor board to correct for
any amplitude or phase errors introduced by the transformers and analogue circuitry.

Opto-isolated inputs
The other function of the input board is to read in the state of the digital inputs. As with the analogue inputs, the
digital inputs must be electrically isolated from the power system. This is achieved by means of the 8 on-board
optical isolators for connection of up to 8 digital signals. The digital signals are passed through an optional noise
filter before being buffered and presented to the unit’s processing boards in the form of a parallel data bus.
This selectable filtering allows the use of a pre-set filter of ½ cycle which renders the input immune to induced
power-system noise on the wiring. Although this method is secure it can be slow, particularly for inter-tripping. This
can be improved by switching off the ½ cycle filter, in which case one of the following methods to reduce ac noise
should be considered.
● Use double pole switching on the input
● Use screened twisted cable on the input circuit

P64-TM-EN-1 47
Chapter 3 - Hardware Design P64

The opto-isolated logic inputs can be configured for the nominal battery voltage of the circuit for which they are a
part, allowing different voltages for different circuits such as signalling and tripping.

Note:
The opto-input circuitry can be provided without the A/D circuitry as a separate board, which can provide supplementary opto-
inputs.

3.6.5.2 TRANSFORMER BOARD

Figure 20: Transformer board

The transformer board hosts the current and voltage transformers. These are used to step down the currents and
voltages originating from the power systems' current and voltage transformers to levels that can be used by the
devices' electronic circuitry. In addition to this, the on-board CT and VT transformers provide electrical isolation
between the unit and the power system.
The transformer board is connected physically and electrically to the input board to form a complete input module.
For terminal connections, please refer to the wiring diagrams.

48 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

3.6.5.3 INPUT BOARD

Figure 21: Input board

The input board is used to convert the analogue signals delivered by the current and voltage transformers into
digital quantities used by the IED. This input board also has on-board opto-input circuitry, providing eight optically-
isolated digital inputs and associated noise filtering and buffering. These opto-inputs are presented to the user by
means of an MD terminal block, which sits adjacent to the analogue inputs HD terminal block.
The input board is connected physically and electrically to the transformer board to form a complete input module.
The terminal numbers of the opto-inputs are as follows:

Terminal Number Opto-input


Terminal 1 Opto 1 -ve
Terminal 2 Opto 1 +ve
Terminal 3 Opto 2 -ve
Terminal 4 Opto 2 +ve
Terminal 5 Opto 3 -ve
Terminal 6 Opto 3 +ve
Terminal 7 Opto 4 -ve
Terminal 8 Opto 4 +ve
Terminal 9 Opto 5 -ve
Terminal 10 Opto 5 +ve
Terminal 11 Opto 6 -ve
Terminal 12 Opto 6 +ve
Terminal 13 Opto 7 –ve
Terminal 14 Opto 7 +ve

P64-TM-EN-1 49
Chapter 3 - Hardware Design P64

Terminal Number Opto-input


Terminal 15 Opto 8 –ve
Terminal 16 Opto 8 +ve
Terminal 17 Common
Terminal 18 Common

3.6.6 STANDARD OUTPUT RELAY BOARD

Figure 22: Standard relay output board - 8 contacts

This output relay board has 8 relays with 6 Normally Open contacts and 2 Changeover contacts.
The output relay board is provided together with the power supply board as a complete assembly, or independently
for the purposes of relay output expansion.
There are two cut-out locations in the board. These can be removed to allow power supply components to protrude
when coupling the output relay board to the power supply board. If the output relay board is to be used
independently, these cut-out locations remain intact.
The terminal numbers are as follows:

Terminal Number Output Relay


Terminal 1 Relay 1 NO
Terminal 2 Relay 1 NO
Terminal 3 Relay 2 NO
Terminal 4 Relay 2 NO
Terminal 5 Relay 3 NO
Terminal 6 Relay 3 NO

50 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

Terminal Number Output Relay


Terminal 7 Relay 4 NO
Terminal 8 Relay 4 NO
Terminal 9 Relay 5 NO
Terminal 10 Relay 5 NO
Terminal 11 Relay 6 NO
Terminal 12 Relay 6 NO
Terminal 13 Relay 7 changeover
Terminal 14 Relay 7 changeover
Terminal 15 Relay 7 common
Terminal 16 Relay 8 changeover
Terminal 17 Relay 8 changeover
Terminal 18 Relay 8 common

3.6.7 HIGH BREAK OUTPUT RELAY BOARD

Figure 23: High Break relay output board

A High Break output relay board is available as an option. It comprises four normally open output contacts, which
are suitable for high breaking loads.
A High Break contact consists of a high capacity relay with a MOSFET in parallel with it. The MOSFET has a
varistor placed across it to provide protection, which is required when switching off inductive loads. This is because
the stored energy in the inductor causes a high reverse voltage that could damage the MOSFET, if not protected.
When there is a control input command to operate an output contact the miniature relay is operated at the same
time as the MOSFET. The miniature relay contact closes in nominally 3.5 ms and is used to carry the continuous
load current. The MOSFET operates in less than 0.2 ms, but is switched off after 7.5 ms.

P64-TM-EN-1 51
Chapter 3 - Hardware Design P64

When the control input is reset, the MOSFET is again turned on for 7.5 mS. The miniature relay resets in nominally
3.5 ms before the MOSFET. This means the MOSFET is used to break the load. The MOSFET absorbs the energy
when breaking inductive loads and so limits the resulting voltage surge. This contact arrangement is for switching
DC circuits only.
The board number is:
● ZN0042 001

High Break Contact Operation


The following figure shows the timing diagram for High Break contact operation.

Databus on off
control input

MOSFET operate 7ms 7ms


on on

MOSFET reset

Relay contact
Closed

3.5ms + contact bounce 3.5ms

Load current

V00246

Figure 24: High Break contact operation

52 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

High Break Contact Applications


● Efficient scheme engineering
In traditional hard wired scheme designs, High Break capability could only be achieved using external
electromechanical trip relays. Instead, these internal High Break contacts can be used thus reducing space
requirements.
● Accessibility of CB auxiliary contacts
It is common practise to use circuit breaker 52a (CB Closed) auxiliary contacts to break the trip coil current on
breaker opening, thereby easing the duty on the protection contacts. In some cases (such as operation of
disconnectors, or retrofitting), it may be that 52a contacts are either unavailable or unreliable. In such cases,
High Break contacts can be used to break the trip coil current in these applications.
● Breaker fail
In the event of failure of the local circuit breaker (stuck breaker), or defective auxiliary contacts (stuck
contacts), it is incorrect to use 52a contact action. The interrupting duty at the local breaker then falls on the
relay output contacts, which may not be rated to perform this duty. High Break contacts should be used in this
case to avoid the risk of burning out relay contacts.
● Initiation of teleprotection
The High Break contacts also offer fast making, which results in faster tripping. In addition, fast keying of
teleprotection is a benefit. Fast keying bypasses the usual contact operation time, such that permissive,
blocking and intertrip commands can be routed faster.

Warning:
These relay contacts are POLARITY SENSITIVE. External wiring must comply with the polarity
requirements described in the external connection diagram to ensure correct operation.

3.6.8 IRIG-B BOARD

Figure 25: IRIG-B board

P64-TM-EN-1 53
Chapter 3 - Hardware Design P64

The IRIG-B board can be fitted to provide an accurate timing reference for the device. The IRIG-B signal is
connected to the board via an BNC connector. The timing information is used to synchronise the IED's internal real-
time clock to an accuracy of 1 ms. The internal clock is then used for time tagging events, fault, maintenance and
disturbance records.
IRIG-B interface is available in modulated or demodulated formats.
The IRIG-B facility is provided in combination with other functionality on a number of additional boards, such as:
● Fibre board with IRIG-B
● Second rear communications board with IRIG-B
● Ethernet board with IRIG-B
● Redundant Ethernet board with IRIG-B

There are three types of each of these boards; one type which accepts a modulated IRIG-B input, one type which
accepts a demodulated IRIG-B input and one type which accepts a universal IRIG-B input. The order code will
indicate which variant it supports.

3.6.9 FIBRE OPTIC BOARD

Figure 26: Fibre optic board

This board provides an interface for communicating with a master station. This communication link can use all
compatible protocols (Courier, IEC 60870-5-103, MODBUS and DNP 3.0). It is a fibre-optic alternative to the
metallic RS485 port presented on the power supply terminal block. The metallic and fibre optic ports are mutually
exclusive.
The fibre optic port uses BFOC 2.5 ST connectors.
The board comes in two varieties; one with an IRIG-B input and one without:

54 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

3.6.10 REAR COMMUNICATION BOARD

Figure 27: Rear communication board

The optional communications board containing the secondary communication ports provide two serial interfaces
presented on 9 pin D-type connectors. These interfaces are known as SK4 and SK5. Both connectors are female
connectors, but are configured as DTE ports. This means pin 2 is used to transmit information and pin 3 to receive.
SK4 can be used with RS232, RS485 and K-bus. SK5 can only be used with RS232 and is used for electrical
teleprotection. The optional rear communications board and IRIG-B board are mutually exclusive since they use the
same hardware slot. However, the board comes in two varieties; one with an IRIG-B input and one without.

3.6.11 SINGLE ETHERNET BOARD

P64-TM-EN-1 55
Chapter 3 - Hardware Design P64

ZN0098001

V80016

Figure 28: Ethernet board

This board provides one optical 100Mbps LC duplex Ethernet port (NP2A) for station bus communications, with a
universal IRIG-B interface for time synchronisation, and a separate 10/100Mbps RJ45 Ethernet maintenance/
engineering interface (NP1) for monitoring and configuration purposes.
The Ethernet and other connection details are described below:

RJ45 Connector (NP1 only)


Pin Signal Name Signal Definition
1 TXP Transmit (positive)
2 TXN Transmit (negative)
3 RXP Receive (positive)
4 - Not used
5 - Not used
6 RXN Receive (negative)
7 - Not used
8 - Not used

UNIVERSAL IRIG-B Connector


● Centre connection: Signal
● Outer connection: Earth

56 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

LC Optical Fibre Connector (NP2A only)


Connector SFP
A TX
B RX

3.6.12 REDUNDANT ETHERNET BOARD

P64-TM-EN-1 57
Chapter 3 - Hardware Design P64

ZN0098002 ZN0098003 ZN0098005

V80017

Figure 29: Redundant Ethernet board

This board provides dual redundant Ethernet (NP2A and NP2B) for station bus communications. A universal IRIG-B
interface for time synchronisation and a separate Ethernet interface (NP1) for monitoring two variants. A new
variant also provides serial protocol support on fiber optics (RP1).
The available redundancy protocols are:
● RSTP (Rapid Spanning Tree Protocol)
● PRP (Parallel Redundancy Protocol)
● HSR (High-availability Seamless Redundancy)
● Failover

There are several variants for this board as follows:


Two LC duplex redundant 100Mbps Ethernet ports running RSTP + PRP + HSR + Failover, with a serial protocol
communications ST fibre port with on-board universal IRIG-B and one 10/100Mbps RJ45 maintenance/engineering
port.
Two RJ45 duplex redundant 10/100Mbps Ethernet ports running RSTP + PRP + HSR + Failover, with on-board
universal IRIG-B and one 10/100Mbps RJ45 maintenance/engineering port.
Two LC duplex redundant 100Mbps Ethernet ports running RSTP + PRP + HSR + Failover, with on-board universal
IRIG-B and one 10/100Mbps RJ45 maintenance/engineering port.
The Ethernet and other connection details are described below:

UNIVERSAL IRIG-B Connector


● Centre connection: Signal
● Outer connection: Earth

58 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

LC Optical Fibre Connector (only for NP2A or NP2B when ordering fibre ports on station bus ports)
Connector SFP
A TX
B RX

ST Optical Fibre Connector (only for RP1 serial communications)


Connector Communications
RP1 TX
RP2 RX

RJ45 Connector (NP1 or NP2A/NP2B when ordering two copper ports on station bus ports only)
Pin Signal Name Signal Definition
1 TXP Transmit (positive)
2 TXN Transmit (negative)
3 RXP Receive (positive)
4 - Not used
5 - Not used
6 RXN Receive (negative)
7 - Not used
8 - Not used

P64-TM-EN-1 59
Chapter 3 - Hardware Design P64

3.6.13 RTD BOARD

Figure 30: RTD board

The RTD board provides two banks of 15 terminals to support ten RTD inputs, of the type PT100, Ni100, or Ni120,
depending on the product. There are three terminals for each RTD, therefore 30 terminals altogether. The RTD
board fits into slot B or slot C, depending on the model variant.
The terminal numbers of the RTDs are as follows:

Terminal Number RTD Connection


Terminal 1 RTD1 wire 1
Terminal 2 RTD1 wire 2

Terminal 3 RTD1 wire 3

Terminal 4 RTD2 wire 1

Terminal 5 RTD2 wire 2

Terminal 6 RTD2 wire 3

Terminal 7 RTD3 wire 1

Terminal 8 RTD3 wire 2

Terminal 9 RTD3 wire 3

Terminal 10 RTD4 wire 1

Terminal 11 RTD4 wire 2

Terminal 12 RTD4 wire 3

60 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

Terminal Number RTD Connection

Terminal 13 RTD5 wire 1

Terminal 14 RTD5 wire 2

Terminal 15 RTD5 wire 3

Terminal 16 RTD6 wire 1

Terminal 17 RTD6 wire 2

Terminal 18 RTD6 wire 3

Terminal 19 RTD7 wire 1

Terminal 20 RTD7 wire 2

Terminal 21 RTD7 wire 3

Terminal 22 RTD8 wire 1

Terminal 23 RTD8 wire 2

Terminal 24 RTD8 wire 3

Terminal 25 RTD9 wire 1

Terminal 26 RTD9 wire 2

Terminal 27 RTD9 wire 3

Terminal 28 RTD10 wire 1

Terminal 29 RTD10 wire 2

Terminal 30 RTD10 wire 3

P64-TM-EN-1 61
Chapter 3 - Hardware Design P64

3.6.14 CLIO BOARD

Figure 31: CLIO board

The CLIO board provides two banks of 15 terminals to support four current loop inputs and four current loop
outputs. There are three terminals for each input and three for each output, therefore 24 of the terminals are used
altogether. The CLIO board fits into slot B or slot C, depending on the model variant.
The terminal numbers of the current loop inputs and outputs are as follows:

Terminal Number Current Loop Connection


Terminal 1 CLO1 - 20 mA input
Terminal 2 CLO1 - 1 mA input
Terminal 3 CLO1 - common input
Terminal 4 Not used
Terminal 5 CLO2 - 20 mA input
Terminal 6 CLO2 - 1 mA input
Terminal 7 CLO2 - common input
Terminal 8 Not used
Terminal 9 CLO3 - 20 mA input
Terminal 10 CLO3 - 1 mA input
Terminal 11 CLO3 - common input
Terminal 12 Not used
Terminal 13 CLO4 - 20 mA input

62 P64-TM-EN-1
P64 Chapter 3 - Hardware Design

Terminal Number Current Loop Connection


Terminal 14 CLO4 - 1 mA input
Terminal 15 CLO4 - common input
Terminal 16 CLI1 - 20 mA input
Terminal 17 CLI1 - 1 mA input
Terminal 18 CLI1 - common input
Terminal 19 Not used
Terminal 20 CLI2 - 20 mA input
Terminal 21 CLI2 - 1 mA input
Terminal 22 CLI2 - common input
Terminal 23 Not used
Terminal 24 CLI3 - 20 mA input
Terminal 25 CLI3 - 1 mA input
Terminal 26 CLI3 - common input
Terminal 27 Not used
Terminal 28 CLI4 - 20 mA input
Terminal 29 CLI4 - 1 mA input
Terminal 30 CLI4 - common input

P64-TM-EN-1 63
Chapter 3 - Hardware Design P64

64 P64-TM-EN-1
CHAPTER 4

SOFTWARE DESIGN
Chapter 4 - Software Design P64

4.1 CHAPTER OVERVIEW


This chapter describes the software design of the IED.
This chapter contains the following sections:
Chapter Overview 66
Sofware Design Overview 67
System Level Software 68
Platform Software 71
Protection and Control Functions 72

66 P64-TM-EN-1
P64 Chapter 4 - Software Design

4.2 SOFWARE DESIGN OVERVIEW


The device software can be conceptually categorized into several elements as follows:
● The system level software
● The platform software
● The protection and control software

These elements are not distinguishable to the user, and the distinction is made purely for the purposes of
explanation. The following figure shows the software architecture.

Protection and Control Software Layer


Protection Task
Programmable & fixed Coprocessor protection
scheme logic algorithms
Fault locator Disturbance
Signal processing Protection algorithms task recorder task

Supervisor task

Records

and control
Protection

settings
Platform Software Layer

Event, fault,
Remote
disturbance,
Settings database communications
maintenance record
Sampling function interfaces
logging

Front panel Local


interface communications
(LCD + Keypad) interfaces

Sample data + digital Control of interfaces to keypad , LCD, LEDs,


logic inputs front & rear ports.
Control of output contacts
and programmable LEDs Self-checking maintenance records

System Level Software Layer


System services (e.g. device drivers) / Real time operating system / Self-diagnostic software

Hardware Device Layer


LEDs / LCD / Keypad / Memory / FPGA

V00307

Figure 32: Software Architecture

The software, which executes on the main processor, can be divided into a number of functions as illustrated above.
Each function is further broken down into a number of separate tasks. These tasks are then run according to a
scheduler. They are run at either a fixed rate or they are event driven. The tasks communicate with each other as
and when required.

P64-TM-EN-1 67
Chapter 4 - Software Design P64

4.3 SYSTEM LEVEL SOFTWARE

4.3.1 REAL TIME OPERATING SYSTEM


The real-time operating system is used to schedule the processing of the various tasks. This ensures that they are
processed in the time available and in the desired order of priority. The operating system also plays a part in
controlling the communication between the software tasks, through the use of operating system messages.

4.3.2 SYSTEM SERVICES SOFTWARE


The system services software provides the layer between the hardware and the higher-level functionality of the
platform software and the protection and control software. For example, the system services software provides
drivers for items such as the LCD display, the keypad and the remote communication ports. It also controls things
like the booting of the processor and the downloading of the processor code into DRAM at startup.

4.3.3 SELF-DIAGNOSTIC SOFTWARE


The device includes several self-monitoring functions to check the operation of its hardware and software while in
service. If there is a problem with the hardware or software, it should be able to detect and report the problem, and
attempt to resolve the problem by performing a reboot. In this case, the device would be out of service for a short
time, during which the ‘Healthy’ LED on the front of the device is switched OFF and the watchdog contact at the
rear is ON. If the restart fails to resolve the problem, the unit takes itself permanently out of service; the ‘Healthy’
LED stays OFF and watchdog contact stays ON.
If a problem is detected by the self-monitoring functions, the device attempts to store a maintenance record to allow
the nature of the problem to be communicated to the user.
The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is performed on boot-
up, and secondly a continuous self-checking operation, which checks the operation of the critical functions whilst it
is in service.

4.3.4 STARTUP SELF-TESTING


The self-testing takes a few seconds to complete, during which time the IEDs measurement, recording, control, and
protection functions are unavailable. On a successful start-up and self-test, the ‘Healthy' state LED on the front of
the device is switched on. If a problem is detected during the start-up testing, the device remains out of service until
it is manually restored to working order.
The operations that are performed at start-up are:
1. System boot
2. System software initialisation
3. Platform software initialisation and monitoring

4.3.4.1 SYSTEM BOOT


The integrity of the Flash memory is verified using a checksum before the program code and stored data is loaded
into DRAM for execution by the processor. When the loading has been completed, the data held in DRAM is
compared to that held in the Flash memory to ensure that no errors have occurred in the data transfer and that the
two are the same. The entry point of the software code in DRAM is then called. This is the IED's initialisation code.

68 P64-TM-EN-1
P64 Chapter 4 - Software Design

4.3.4.2 SYSTEM LEVEL SOFTWARE INITIALISATION


The initialization process initializes the processor registers and interrupts, starts the watchdog timers (used by the
hardware to determine whether the software is still running), starts the real-time operating system and creates and
starts the supervisor task. In the initialization process the device checks the following:
● The status of the supercapacitor to maintain the real time clock
● The operation of the LCD controller
● The watchdog operation

At the conclusion of the initialization software the supervisor task begins the process of starting the platform
software. Coprocessor board checks are also made as follows:
● A check is made for the presence of the coprocessor board

● The DRAM on the coprocessor board is checked

If any of these checks produces an error, the coprocessor board is left out of service. The other protection functions
provided by the main processor board are left in service.

4.3.4.3 PLATFORM SOFTWARE INITIALISATION AND MONITORING


When starting the platform software, the IED checks the following:
● The integrity of the data held in non-volatile memory (using a checksum)
● The operation of the real-time clock
● The optional IRIG-B function (if applicable)
● The presence and condition of the input board
● The analog data acquisition system (it does this by sampling the reference voltage)

At the successful conclusion of all of these tests the unit is entered into service and the application software is
started up.

4.3.5 CONTINUOUS SELF TESTING


When the IED is in service, it continually checks the operation of the critical parts of its hardware and software. The
checking is carried out by the system services software and the results are reported to the platform software. The
functions that are checked are as follows:
● The Flash memory containing all program code and language text is verified by a checksum.
● The code and constant data held in system memory is checked against the corresponding data in Flash
memory to check for data corruption.
● The system memory containing all data other than the code and constant data is verified with a checksum.
● The integrity of the digital signal I/O data from the opto-inputs and the output relay coils is checked by the
data acquisition function every time it is executed.
● The operation of the analog data acquisition system is continuously checked by the acquisition function every
time it is executed. This is done by sampling the reference voltages.
● The operation of the optional Ethernet board is checked by the software on the main processor board. If the
Ethernet board fails to respond an alarm is raised and the board is reset in an attempt to resolve the problem.
● The operation of the optional IRIG-B function is checked by the software that reads the time and date from
the board.
● Where fitted, the operation of the RTD board is checked by reading the temperature indicated by the
reference resistors on the two spare RTD channels.
● Where fitted, the operation of the CLIO board is checked.

P64-TM-EN-1 69
Chapter 4 - Software Design P64

In the event that one of the checks detects an error in any of the subsystems, the platform software is notified and it
attempts to log a maintenance record.
If the problem is with the IRIG-B board, the device continues in operation. For problems detected in any other area,
the device initiates a shutdown and re-boot, resulting in a period of up to 10 seconds when the functionality is
unavailable.
A restart should clear most problems that may occur. If, however, the diagnostic self-check detects the same
problem that caused the IED to restart, it is clear that the restart has not cleared the problem, and the device takes
itself permanently out of service. This is indicated by the ‘’health-state’ LED on the front of the device, which
switches OFF, and the watchdog contact which switches ON.

70 P64-TM-EN-1
P64 Chapter 4 - Software Design

4.4 PLATFORM SOFTWARE


The platform software has three main functions:
● To control the logging of records generated by the protection software, including alarms, events, faults, and
maintenance records
● To store and maintain a database of all of the settings in non-volatile memory
● To provide the internal interface between the settings database and the user interfaces, using the front panel
interface and the front and rear communication ports

4.4.1 RECORD LOGGING


The logging function is used to store all alarms, events, faults and maintenance records. The records are stored in
non-volatile memory to provide a log of what has happened. The IED maintains four types of log on a first in first out
basis (FIFO). These are:
● Alarms
● Event records
● Fault records
● Maintenance records

The logs are maintained such that the oldest record is overwritten with the newest record. The logging function can
be initiated from the protection software. The platform software is responsible for logging a maintenance record in
the event of an IED failure. This includes errors that have been detected by the platform software itself or errors that
are detected by either the system services or the protection software function. See the Monitoring and Control
chapter for further details on record logging.

4.4.2 SETTINGS DATABASE


The settings database contains all the settings and data, which are stored in non-volatile memory. The platform
software manages the settings database and ensures that only one user interface can modify the settings at any
one time. This is a necessary restriction to avoid conflict between different parts of the software during a setting
change. Changes to protection settings and disturbance recorder settings, are first written to a temporary location
DRAM memory. This is sometimes called 'Scratchpad' memory. These settings are not written into non-volatile
memory immediately. This is because a batch of such changes should not be activated one by one, but as part of a
complete scheme. Once the complete scheme has been stored in DRAM, the batch of settings can be committed to
the non-volatile memory where they will become active.

4.4.3 INTERFACES
The settings and measurements database must be accessible from all of the interfaces to allow read and modify
operations. The platform software presents the data in the appropriate format for each of the interfaces (LCD
display, keypad and all the communications interfaces).

P64-TM-EN-1 71
Chapter 4 - Software Design P64

4.5 PROTECTION AND CONTROL FUNCTIONS


The protection and control software processes all of the protection elements and measurement functions. To
achieve this it has to communicate with the system services software, the platform software as well as organise its
own operations.
The protection task software has the highest priority of any of the software tasks in the main processor board. This
ensures the fastest possible protection response.
The protection and control software provides a supervisory task, which controls the start-up of the task and deals
with the exchange of messages between the task and the platform software.

4.5.1 ACQUISITION OF SAMPLES


After initialization, the protection and control task waits until there are enough samples to process. The acquisition
of samples on the main processor board is controlled by a ‘sampling function’ which is called by the system services
software.
This sampling function takes samples from the input module and stores them in a two-cycle FIFO buffer. The
sample rate is 24 samples per cycle. This results in a nominal sample rate of 1,200 samples per second for a 50 hz
system and 1,440 samples per second for a 60 Hz system. However the sample rate is not fixed. It tracks the power
system frequency as described in the next section.

4.5.2 FREQUENCY TRACKING


The device provides a frequency tracking algorithm so that there are always 24 samples per cycle irrespective of
frequency drift. The frequency range in which 48 samples per second are provided is between 45 Hz and 66 Hz. If
the frequency falls outside this range, the sample rate reverts to its default rate of 1,200 Hz for 50 Hz or 1,440 Hz
for 60 Hz.
The frequency tracking of the analog input signals is achieved by a recursive Fourier algorithm which is applied to
one of the input signals. It works by detecting a change in the signal’s measured phase angle. The calculated value
of the frequency is used to modify the sample rate being used by the input module, in order to achieve a constant
sample rate per cycle of the power waveform. The value of the tracked frequency is also stored for use by the
protection and control task.
The frequency tracks off any voltage or current in the order VA, VB, VC, IA, IB, IC, down to 10%Vn for voltage and
5%In for current.

4.5.3 DIRECT USE OF SAMPLED VALUES


Most of the IED’s protection functionality uses the Fourier components calculated by the device’s signal processing
software. However RMS measurements and some special protection algorithms available in some products use the
sampled values directly.
The disturbance recorder also uses the samples from the input module, in an unprocessed form. This is for
waveform recording and the calculation of true RMS values of current, voltage and power for metering purposes.
In the case of special protection algorithms, using the sampled values directly provides exceptionally fast response
because you do not have to wait for the signal processing task to calculate the fundamental. You can act on the
sampled values immediately.

4.5.4 SYSTEM LEVEL SOFTWARE INITIALISATION


The differential protection requires that the devices at the line ends exchange data messages four times per cycle.
To achieve this the coprocessor retrieves the frequency-tracked samples at 48 samples per cycle from the input
board and converts these to 8 samples per cycle based on the nominal frequency. The coprocessor calculates the
Fourier transform of the fixed rate samples after every sample, using a one-cycle window. This generates current

72 P64-TM-EN-1
P64 Chapter 4 - Software Design

measurements eight times per cycle which are used for the differential protection algorithm. These are transmitted
to the remote device(s) using the HDLC (high-level data link control) communication protocol.
The coprocessor is also responsible for managing intertripping commands via the communication link, as well as re-
configuration instigated from the remote device(s).
Data exchange between the coprocessor board and the main processor board is achieved through the use of
shared memory on the coprocessor board. When the main processor accesses this memory, the coprocessor is
temporarily halted. After the coprocessor code has been copied onto the board at initialization, the main traffic
between the two boards consists of setting change information, commands from the main processor, differential
protection measurements and output data.

4.5.5 FOURIER SIGNAL PROCESSING


When the protection and control task is re-started by the sampling function, it calculates the Fourier components for
the analog signals. Although some protection algorithms use some Fourier-derived harmonics (e.g. second
harmonic for magnetizing inrush), most protection functions are based on the Fourier-derived fundamental
components of the measured analog signals. The Fourier components of the input current and voltage signals are
stored in memory so that they can be accessed by all of the protection elements’ algorithms.
The Fourier components are calculated using single-cycle Fourier algorithm. This Fourier algorithm always uses the
most recent 24 samples from the 2-cycle buffer.
Most protection algorithms use the fundamental component. In this case, the Fourier algorithm extracts the power
frequency fundamental component from the signal to produce its magnitude and phase angle. This can be
represented in either polar format or rectangular format, depending on the functions and algorithms using it.
The Fourier function acts as a filter, with zero gain at DC and unity gain at the fundamental, but with good harmonic
rejection for all harmonic frequencies up to the nyquist frequency. Frequencies beyond this nyquist frequency are
known as alias frequencies, which are introduced when the sampling frequency becomes less than twice the
frequency component being sampled. However, the Alias frequencies are significantly attenuated by an anti-aliasing
filter (low pass filter), which acts on the analog signals before they are sampled. The ideal cut-off point of an anti-
aliasing low pass filter would be set at:
(samples per cycle) ´ (fundamental frequency)/2
At 24 samples per cycle, this would be nominally 600 Hz for a 50 Hz system, or 720 Hz for a 60 Hz system.
The following figure shows the nominal frequency response of the anti-alias filter and the Fourier filter for a 24-
sample single cycle fourier algorithm acting on the fundamental component:

1
Ideal anti-alias filter response
0.8

Real anti-alias filter Fourier response without


0.6 anti-alias filter
response

0.4
Fourier response with
anti-alias filter
0.2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Alias frequency
50 Hz 600 Hz 1200 Hz
V00301

Figure 33: Frequency Response (indicative only)

P64-TM-EN-1 73
Chapter 4 - Software Design P64

4.5.6 PROGRAMMABLE SCHEME LOGIC


The purpose of the programmable scheme logic (PSL) is to allow you to configure your own protection schemes to
suit your particular application. This is done with programmable logic gates and delay timers. To allow greater
flexibility, different PSL is allowed for each of the four setting groups.
The input to the PSL is any combination of the status of the digital input signals from the opto-isolators on the input
board, the outputs of the protection elements such as protection starts and trips, and the outputs of the fixed
protection scheme logic (FSL). The fixed scheme logic provides the standard protection schemes. The PSL consists
of software logic gates and timers. The logic gates can be programmed to perform a range of different logic
functions and can accept any number of inputs. The timers are used either to create a programmable delay, and/or
to condition the logic outputs, such as to create a pulse of fixed duration on the output regardless of the length of
the pulse on the input. The outputs of the PSL are the LEDs on the front panel of the relay and the output contacts
at the rear.
The execution of the PSL logic is event driven. The logic is processed whenever any of its inputs change, for
example as a result of a change in one of the digital input signals or a trip output from a protection element. Also,
only the part of the PSL logic that is affected by the particular input change that has occurred is processed. This
reduces the amount of processing time that is used by the PSL. The protection & control software updates the logic
delay timers and checks for a change in the PSL input signals every time it runs.
The PSL can be configured to create very complex schemes. Because of this PSL design is achieved by means of
a PC support package called the PSL Editor. This is available as part of the settings application software MiCOM S1
Agile.

4.5.7 EVENT RECORDING


A change in any digital input signal or protection element output signal is used to indicate that an event has taken
place. When this happens, the protection and control task sends a message to the supervisor task to indicate that
an event is available to be processed and writes the event data to a fast buffer controlled by the supervisor task. Up
to 5000 time-tagged event records can be stored.
When the supervisor task receives an event record, it instructs the platform software to create the appropriate log in
non-volatile memory (DRAM). The operation of the record logging to Flash is slower than the supervisor buffer. This
means that the protection software is not delayed waiting for the records to be logged by the platform software.
However, in the rare case when a large number of records to be logged are created in a short period of time, it is
possible that some will be lost, if the supervisor buffer is full before the platform software is able to create a new log
in Flash memory. If this occurs then an event is logged to indicate this loss of information.
Maintenance records are created in a similar manner, with the supervisor task instructing the platform software to
log a record when it receives a maintenance record message. However, it is possible that a maintenance record
may be triggered by a fatal error in the relay in which case it may not be possible to successfully store a
maintenance record, depending on the nature of the problem.
For more information, see the Monitoring and Control chapter.

4.5.8 DISTURBANCE RECORDER


The disturbance recorder operates as a separate task from the protection and control task. It can record the
waveforms for up to 30 calibrated analogue channels and values of up to 32 digital signals all at a high resolution of
24 samples/cycle. The recording time is user selectable. Typically, 100 waveforms of 10.5 seconds duration can be
stored. The disturbance recorder is supplied with data by the protection and control task once per cycle. The
disturbance recorder collates the data that it receives into the required length disturbance record. The disturbance
records can be extracted by settings application software such as S1 Agile, which can also store the data in
COMTRADE format, therefore allowing the use of other packages to view the recorded data.
For more information, see the Monitoring and Control chapter.

74 P64-TM-EN-1
P64 Chapter 4 - Software Design

4.5.9 FUNCTION KEY INTERFACE


The function keys interface directly into the PSL as digital input signals. A change of state is only recognized when
a key press is executed on average for longer than 200 ms. The time to register a change of state depends on
whether the function key press is executed at the start or the end of a protection task cycle, with the additional
hardware and software scan time included. A function key press can provide a latched (toggled mode) or output on
key press only (normal mode) depending on how it is programmed. It can be configured to individual protection
scheme requirements. The latched state signal for each function key is written to non-volatile memory and read
from non-volatile memory during relay power up thus allowing the function key state to be reinstated after power-up,
should power be inadvertently lost.

P64-TM-EN-1 75
Chapter 4 - Software Design P64

76 P64-TM-EN-1
CHAPTER 5

CONFIGURATION
Chapter 5 - Configuration P64

5.1 CHAPTER OVERVIEW


Each product has different configuration parameters according to the functions it has been designed to perform.
There is, however, a common methodology used across the entire product series to set these parameters.
Some of the communications setup cannot be carried out using the settings applications software, it can only be
carried out using the HMI. This chapter includes concise instructions on how to configure the device, as well as a
description of the common methodology used to configure the device in general.
This chapter contains the following sections:
Chapter Overview 78
Settings Application Software 79
Using the HMI Panel 80

78 P64-TM-EN-1
P64 Chapter 5 - Configuration

5.2 SETTINGS APPLICATION SOFTWARE


To configure this device, you will need to use the Settings Application Software. The settings application software
used in this range of IEDs is called MiCOM S1 Agile. It is a collection of software tools, which is used for setting up
and managing the IEDs.
Although you can change many settings using the front panel HMI, some of the features cannot be configured
without the Settings Application Software. For example, the programmable scheme logic, or the IEC 61850
communications or the SLD.
If you do not already have a copy of the Settings Application Software, you can obtain it from GE Vernova contact
centre.
To configure your product, you will need a data model that matches your product. When you launch the Settings
Application Software, you will be presented with a panel that allows you to invoke the “Data Model Manager”. This
will close the other aspects of the software to allow an efficient import of the chosen data model. If you don’t have,
or can’t find, the data model relating to your product, please call the GE Vernova contact centre.
When you have loaded all the data models you need, you should restart the Settings Application Software and start
to create a model of your system using the “System Explorer” panel.
The software is designed to be intuitive, but help is available in an online help system and in the Settings
Application Software user guide P40-M&CR-SAS-UG-EN-n, where 'Language' is a 2-letter code designating the
language version of the user guide and 'n' is the latest version of the settings application software.

P64-TM-EN-1 79
Chapter 5 - Configuration P64

5.3 USING THE HMI PANEL


Using the Graphical HMI, you can:
● Display and modify settings
● Display measurements
● Display fault records
● Display the Single Line Diagram (SLD)
● View the digital I/O signal status
● Reset fault and alarm indications

The keypad provides full access to the device functionality using a range of menu options. The information is
displayed on the screen.

Keys Description Function

To change between settings in a particular column, changing


Up and down cursor keys
values within a cell or to select the next item on the SLD

To change between settings in a particular column, change values


Left and right cursor keys
within a cell or to select the next item on the SLD

For changing and executing settings. When a bottom banner


ENTER/OK key Menu context key label is selected, the OK key can also be used
to navigate between pages.

Menu context keys situated directly below the graphical HMI are
Menu context keys
used to navigate between pages.

To return to the menu header from any menu cell, or to cancel a


Cancel/Reset key
setting input.

Read/Home key To navigate to the default Home page from anywhere in the menu.

Function keys (not all models) For executing user programmable functions

80 P64-TM-EN-1
P64 Chapter 5 - Configuration

Keys Description Function

Control key OPEN used to open the CB/Switch.


Control key OPEN Note: Colour coding is selectable via labels and configuration of
PSL/SLD.

Control key CLOSE used to close the CB/Switch.


Control key CLOSE Note: Colour coding is selectable via labels and configuration of
PSL/SLD.

Local/Remote key To select between local and remote operating modes.

5.3.1 NAVIGATING THE HMI PANEL


The cursor keys are used to navigate the menu. To navigate between different menus, use the Menu context keys,
which are located below the graphical display.
The cursor keys have an auto-repeat function if held down continuously. This can be used to speed up both setting
value changes and menu navigation. The longer the key is held down, the faster the rate of change or movement.

5.3.2 GETTING STARTED


When you first start the IED, it will go through its power up procedure. After a few seconds it will settle down into the
default display. If there are alarms present, the yellow Alarms LED will be flashing and the alarm counter on the top
banner will show the number of alarms that are active.
The device should be in full working order when you first start it, but an alarm could still be present. For example, if
there is no network connection for a device fitted with a network board. If this is the case, you can read the alarm by
selecting the Alarm counter on the top banner of the display.
If the device is fitted with an Ethernet board, you will need to connect the device to an active Ethernet network to
clear the alarm.

5.3.3 DEFAULT DISPLAY


The graphical HMI default display contains shortcuts to various sections of the menu, as well as a snapshot of the
current device status.

P64-TM-EN-1 81
Chapter 5 - Configuration P64

Figure 34: HMI default display

The graphical display screen consists of three main areas, which can be selected using the navigation keypad.
1. The top banner displays information left to right and includes the menu label for the current display, the user
access level, the number of active alarms and the time.
2. The content area displays information related to the chosen area of navigation. For example, settings,
measurements or SLD.
3. The bottom banner displays labels for the two Menu context keys, which are used for navigating between the
menus.

Note:
After a period defined by the “LCD screen saver” , setting the HMI will enter rest mode. This allows the HMI to reduce power
consumption and will dim the LCD backlight. The HMI may be woken from rest mode by pressing any front panel key. This
mode has no effect on IED functional performance.

5.3.4 DEFAULT DISPLAY NAVIGATION


The default display provides quick and simple navigation of the complete menu database. Use the navigation
keypad to change the highlighted cell. The highlighted entry can be selected using the Enter/OK Key. When the
bottom of the screen is reached, the selected area moves to the Bottom Banner. From here the OK key can also be
used to navigate between the pages.
The Menu view can be directly navigated to by long pressing the "Read/Home" key.

Previous level in the navigation hierarchy may be reached by pressing the "Cancel/Reset" key.

From the HMI Default Display, you can navigate to the required view or open up a Submenu using hierarchical
navigation. For example, by selecting Controls & Monitor, a Submenu is opened.

82 P64-TM-EN-1
P64 Chapter 5 - Configuration

As an alternative to hierarchical navigation, the views may be navigated to in sequence by using the hot keys as
“Next” and “Previous” buttons, and is referred as horizontal navigation.
For example, you can move to either SYSTEM DATA or MEASUREMENTS 2 Views using the horizontal
navigation, menu contexts hot keys situated directly under the screen.

5.3.5 PROCESSING ALARMS AND RECORDS


When there are no alarms, the Alarm Icon on the top banner is shown as:

While there are any standing alarms, the standing alarm count will be highlighted in red in the top HMI banner and
the yellow alarm LED will flash.

P64-TM-EN-1 83
Chapter 5 - Configuration P64

To launch the alarm list view, select the alarm counter in the HMI top banner and press the OK key. The alarm view
list may be scrolled to view all alarms.
New standing and fleeting alarms may be accepted by selecting the alarm and pressing the Ack/Clear menu
context key. Rescinded alarms may also be cleared by selecting the alarm and pressing the Ack/Clear menu
context key.
All visible alarms may be selected by pressing the Select All menu context key.
The "reset indication" command may be issued to reset latched alarms and accept the flashing led
notification. A "reset indication" may be issued from the "View Records" HMI settings view or by pressing
Ack/Clear alarm context key.
"Ack/Clear" and "reset indication" commands are available to users with ENGINEER or OPERATOR or
INSTALLER roles.
To return to the launch view from the alarm view press the Cancel key.

Figure 35: HMI Alarms Display

5.3.6 SINGLE LINE DIAGRAM (SLD) VIEWER


The SLD menu displays the saved SLD on the graphical HMI screen. You can navigate to the SLD menu using the
bottom Menu context keys or by using the quick launch menu on the Home page. The SLD is configured and
uploaded into the IED using the S1 Agile configuration tool. Items of plant can be selected on the SLD screen using
the navigation keypad.

5.3.6.1 CIRCUIT BREAKER CONTROL (SLD VIEW ONLY)


You can OPEN and CLOSE the circuit breaker selected on the SLD using the dedicated OPEN, CLOSE and L/R
buttons on the front HMI Panel.
When the CB Control by setting is selected, to option 1 Local, option 3 Local+Remote, option 5 Opto+local,
option 7 Opto+Rem+local or option 8 L/R Key in the CB CONTROL column users are allowed to use the Trip
and Close Key on the front panel to operate the CB.
To control an item of plant using the Open and Close and L/R buttons:
● Set CB control by setting to L/R Key
● Select the Local operating mode by pressing the L/R button
When the L/R button on the front panel is pressed, it will toggle the status of DDB L/R Key Status. When the DDB
status is TRUE, the L/R Key LED is red and the Local mode is selected. When the DDB status is FALSE, the L/R

84 P64-TM-EN-1
P64 Chapter 5 - Configuration

Key LED is green and the REMOTE mode is selected. The L/R Key Status DDB status is stored in non-volatile
memory, so that it’s status is recovered after an IED power cycle.
● In the SLD menu, navigate to the item of plant which you require to control using the navigation keypad
● The selected plant is highlighted with an orange border
● Use the Enter key to select the item
● Press the Open or Close key to operate

Figure 36: HMI SLD Display

For the Circuit Breaker Commands from HMI, additional checks are done:
If the CB is in indeterminant state, the switchgear command will not be available and HMI will raise a warning
dialogue with the message - "Commands blocked - Intermediate State".
If the associated "Control by" setting is set to "disabled" the switchgear command will not be available and HMI will
raise a warning dialogue with the message - "Commands blocked due to Settings".
If the associated "Control by" setting is set to "remote" the switchgear command will not be available and HMI will
raise a warning dialogue with the message "Commands blocked due to Settings".
If the associated "Control by" setting is set to "L/R key" and soft key status is set to remote, the switchgear
command will not be available, and HMI will pop-up the message - "Commands blocked - In Remote Control".
If the associated local DDB is set to local, the switchgear command will not be available, and HMI will pop-up the
message - "Commands blocked - Switchgear in Local".

5.3.6.2 SWITCH CONTROL (SLD VIEW ONLY)


You can OPEN and CLOSE the switches selected on the SLD using the dedicated OPEN, CLOSE and L/R buttons
on the front HMI Panel.
When the Switch Control by setting is selected to option 1 LOCAL, option 3 Local+Remote or option 4 L/R Key
in the SWITCH CONTROL column, users are allowed to use the Open and Close Key on the front panel to operate
the SWITCH.
To control an item of plant using the Open and Close and L/R buttons:
● Set Switch Control by setting to L/R Key
● Select the Local operating mode by pressing the L/R button

When the L/R button on the front panel is pressed, it will toggle the status of DDB L/R Key Status. When the DDB
status is TRUE, the L/R Key LED is red and the Local mode is selected. When the DDB status is FALSE, the L/R

P64-TM-EN-1 85
Chapter 5 - Configuration P64

Key LED is green and the REMOTE mode is selected. The L/R Key Status DDB status is stored in non-volatile
memory, so that its status is recovered after an IED power cycle.
● In the SLD menu, navigate to the item of plant you want to control using the navigation keypad
● The selected plant is highlighted with an orange border
● Use the Enter key to select the item
● Press the OPEN or CLOSE key to operate

Figure 37: HMI SLD display

Figure 38: For the Switch Commands from HMI, these additional checks are done:

If the Switch is in indeterminant state, the switchgear command will not be available and HMI will raise a warning
dialogue with the message - "Commands blocked - Intermediate State".
If the associated "Control by" setting is set to "disabled" the switchgear command will not be available and HMI will
raise a warning dialogue with the message - "Commands blocked due to Settings".
If the associated "Control by" setting is set to "remote" the switchgear command will not be available and HMI will
raise a warning dialogue with the message "Commands blocked due to Settings".
If the associated "Control by" setting is set to "L/R key" and soft key status is set to remote, the switchgear
command will not be available and HMI will pop-up the message - "Commands blocked - In Remote Control."
If the associated local DDB is set to local, the switchgear command will not be available and HMI will pop-up the
message - "Commands blocked - Switchgear in Local".

5.3.7 MENU STRUCTURE


Settings, commands, records and measurements are stored in a local database inside the IED. When using the
Human Machine Interface (HMI) it is convenient to visualise the menu navigation system as a table. Each item in
the menu is known as a cell, which is accessed by reference to a column and row address. Each column and row is
assigned 2-digit hexadecimal numbers, resulting in a unique 4-digit cell address for every cell in the database. The
main menu groups are allocated columns and the items within the groups are allocated rows, meaning a particular
item within a particular group is a cell.
You do not need to scroll through each of the columns horizontally to access a specific setting view. The ‘Home
Page’ can be used to quickly access the required column/setting view. Each column contains all related items, for
example all of the disturbance recorder settings and records are in the same column.

86 P64-TM-EN-1
P64 Chapter 5 - Configuration

There are three types of cell:


● Settings: this is for parameters that can be set to different values
● Commands: this is for commands to be executed
● Data: this is for measurements and records to be viewed, which are not settable

Note:
Sometimes the term "Setting" is used generically to describe all of the three types.

The table below, provides an example of the menu structure:

SYSTEM DATA (Col 00) VIEW RECORDS (Col 01) MEASUREMENTS 1 (Col 02) …
Language (Row 01) "Select Event [0...n]" (Row 01) IA Magnitude (Row 01) …
Password (Row 02) Menu Cell Ref (Row 02) IA Phase Angle (Row 02) …
Sys Fn Links (Row 03) Time & Date (Row 03) IB Magnitude (Row 03) …
… … … …

It is convenient to specify all the settings in a single column, detailing the complete Courier address for each setting.
The above table may therefore be represented as follows:

Setting Column Row Description


SYSTEM DATA 00 00 First Column definition
Language (Row 01) 00 01 First setting within first column
Password (Row 02) 00 02 Second setting within first column
Sys Fn Links (Row 03) 00 03 Third setting within first column
… … …
VIEW RECORDS 01 00 Second Column definition
Select Event [0...n] 01 01 First setting within second column
Menu Cell Ref 01 02 Second setting within second column
Time & Date 01 03 Third setting within second column
… … …
MEASUREMENTS 1 02 00 Third Column definition
IA Magnitude 02 01 First setting within third column
IA Phase Angle 02 02 Second setting within third column
IB Magnitude 02 03 Third setting within third column
… … …

The first three column headers are common throughout much of the product ranges. However, the rows within each
of these column headers may differ according to the product type. Many of the column headers are the same for all
products within the series. However, there is no guarantee that the addresses will be the same for a particular
column header. Therefore, you should always refer to the product settings documentation and not make any
assumptions.

5.3.8 DIRECT ACCESS (MENU CONTEXT KEYS)


The IED provides a pair of menu context keys directly below the LCD display, which allows scrolling between
column headings (navigation between menu screens). These keys can be pressed at any time during menu
navigation to quickly access the menu label displayed in the bottom banner of the graphical HMI.

P64-TM-EN-1 87
Chapter 5 - Configuration P64

5.3.8.1 CONTROL INPUTS


Control inputs cannot be operated through the Menu context keys. To operate control inputs, navigate to the Control
Inputs settings view on the front graphical HMI screen, select the relevant control input and Set/Reset as required.
RBAC is now applied to access control inputs for operation.

5.3.9 CHANGING THE SETTINGS


Appropriate user authority or bypass access is required to change the Settings. Please refer to the Cyber Security
chapter for user authority details.
● Starting at the default display, highlight the required settings column/menu
● Use the OK key to enter the highlighted settings menu.
● To change the value of a setting, highlight the relevant cell in the menu, then press the Enter key to change
the cell value. A settings screen will appear next to the cell. If the currently logged in user does not have the
level of access required for changing the setting, a pop-up dialog box will inform the user and prevent the
settings from being changed. Acknowledge the pop-up message, then navigate to the ‘user accounts’ section
to the top of the screen (top banner) to enter the password for the required access level to change settings.
● To change the value on the settings screen, use the cursor keys to change the desired settings. When more
settings are available than can fit on the screen, a scroll bar on the right-hand side appears. In some cases, a
virtual keyboard is provided to enter complex characters. The IED maintains dependencies between various
settings, and only the applicable settings are displayed for changing.

For Analog Value update, the new analogue value may be entered by selecting the +ve and -ve step buttons or
free-form numerals entered by virtual keyboard.

If the setting cell has the facility of drop down, the required setting can be selected from the drop down list.

Some of the settings are in the form of Binary Data Bits update. By selecting each of the Bit position the data can be
toggled.

Note:
Binary Data Bits can also be used to verify the present data of each bits for monitoring purpose.

88 P64-TM-EN-1
P64 Chapter 5 - Configuration

● Press the Enter key to confirm the new setting value or the Clear key or the on-screen ‘x’ to discard it.
● To confirm the new settings, press the Enter key. Navigate away from the currently active group settings or
press the Home key. A Settings update confirmation dialogue box will appear that requires choosing of one of
the following options:
● Save - accept all settings including the recently changed settings
● Abort - discard recent changes and keep existing settings
● Stay on page - return to the active settings page without saving recent changes

● To return to the top of the menu, hold down the Up cursor key for a second or so, or press the Clear key
once. It is possible to move across columns from anywhere in the menu by using the Menu context keys at
the bottom of the display.
● To return to the default display, press the Home key at any time.
● Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
● The Date and time can be adjusted by navigating to the top banner and selecting the displayed time. Press
the Enter key to adjust the date and time using the calendar/clock widget that pops up.

Note:
For the protection group and disturbance recorder settings, the changes are not saved unless confirmed using the Settings
update confirmation prompt.

Note:
All other Control and support settings (such as Communications and Control inputs), however, are updated immediately after
they are entered on the front HMI without the need to confirm using the Settings update confirmation prompt.

5.3.10 FUNCTION KEYS


Most products have a number of function keys for programming control functionality using the programmable
scheme logic (PSL).
Each function key has an associated programmable tri-colour LED that can be programmed to give the desired
indication on function key activation.
These function keys can be used to trigger any function that they are connected to as part of the PSL. The function
key commands are in the FUNCTION KEYS column.

P64-TM-EN-1 89
Chapter 5 - Configuration P64

Figure 39: HMI Function Keys Display

The first cell down in the FUNCTION KEYS column is the Fn Key Status cell. This contains a binary string, which
represents the function key commands. Their status can be read from the binary string.
The next cell down (Fn Key 1) allows you to activate or disable the first function key (1). The Lock setting allows a
function key to be locked. This allows function keys that are set to Toggled mode and their DDB signal active
‘high’, to be locked in their active state, preventing any further key presses from deactivating the associated
function. Locking a function key that is set to the Normal mode causes the associated DDB signals to be
permanently off. This safety feature prevents any inadvertent function key presses from activating or deactivating
critical functions.
The next cell down (Fn Key 1 Mode) allows you to set the function key to Normal or Toggled. In the Toggle mode
the function key DDB signal output stays in the set state until a reset command is given, by activating the function
key on the next key press. In the Normal mode, the function key DDB signal stays energised for as long as the
function key is pressed then resets automatically. If required, a minimum pulse width can be programmed by adding
a minimum pulse timer to the function key DDB output signal.
The next cell down (Fn Key 1 Label) allows you to change the label assigned to the function. The default label is
Function key 1 in this case. To change the label you need to press the enter key and then change the text on
the bottom line, character by character. This text is displayed when a function key is accessed in the function key
menu, or it can be displayed in the PSL.
Subsequent cells allow you to carry out the same procedure as above for the other function keys.
The status of the function keys is stored in non-volatile memory. If the auxiliary supply is interrupted, the status of all
the function keys is restored. The IED only recognises a single function key press at a time and a minimum key
press duration of approximately 200 ms is required before the key press is recognised. This feature avoids
accidental double presses.
The function keys needs operator permissions to operate. If operator permissions are not held by the present user
an information dialogue is raised to inform the operation has failed.

5.3.10.1 VISUALISATION OF PROTECTION OPERATION


Where there is a protection operation/trip, in addition to the front panel LED indications, the standing trip is indicated
on the LCD screen by a red trim around the top banner. Additionally, the LCD backlight becomes lit and a dialogue
is presented with three options:

90 P64-TM-EN-1
P64 Chapter 5 - Configuration

● “OK” - close the dialogue


● “View” - Navigate to the “record” data view and open the latest fault record
● “Reset Ind” - Attempt to reset the trip indication

P64-TM-EN-1 91
Chapter 5 - Configuration P64

92 P64-TM-EN-1
CHAPTER 6

TRANSFORMER DIFFERENTIAL
PROTECTION
Chapter 6 - Transformer Differential Protection P64

6.1 CHAPTER OVERVIEW

This chapter contains the following sections:


Chapter Overview 94
Transformer Differential Protection Principles 95
Implementation 103
Harmonic Blocking 115
Application Notes 119

94 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

6.2 TRANSFORMER DIFFERENTIAL PROTECTION PRINCIPLES


Transformer Differential Protection (87T) uses the well-known current differential principle where current entering
the protected equipment is compared with the current leaving the protected equipment. If there is no fault, the
current entering the transformer will be equal to the current leaving the transformer multiplied by the inverse of the
turns ratio. If there is a fault in the transformer zone, the currents will not be equal, which results in a differential
current. This differential current is proportional to the fault current for internal faults, but approaches zero for any
other operating conditions. The IED trips the circuit breakers protecting the transformer when it detects a minimum
level of differential current.
The differential scheme creates a well-defined protection zone between the CT sets protecting the transformer. Any
fault within the differential protection zone is called an internal fault, while any fault outside the differential protection
zone is called an external fault. The protection should operate only for internal faults and be sensitive to low fault
currents. It should also restrain on the highest prospective external faults, providing the CTS accurately reproduce
the primary currents. This is difficult to achieve in practice because the CTs never have identical saturation
characteristics. This will result in a differential current, which could cause undesirable operation.
An external fault, which causes a high current to flow through the transformer, is called a through fault. The through-
fault current will usually be high enough to saturate the CTs. The differences in the saturation characteristics of the
CTs will cause a differential current, which could cause the device to trip unless it is restrained. The term used to
specify the IED's ability to cope with these imperfections is called Through Fault Stability.
CT saturation is not the only cause of undesirable differential current. Other aspects which need to be considered
by the transformer differential element to avoid maloperation are:
● Phase shift between the transformer primary and secondary currents depending on the vector group
● Transformation ratio
● The zero-sequence current, which flows in the grounded star transformer winding or the grounding
transformer within the differential protection zone
● Tap changer operation to adjust the voltage
● Magnetising inrush current that flows immediately after the transformer energisation or during a voltage
recovery after the clearance of an external fault or when a second transformer is paralleled with the already
energised transformer
● Over excitation of the transformer

6.2.1 THROUGH FAULT STABILITY


In an ideal world, the CTs either side of a differentially protected system would be identical with identical
characteristics to avoid creating a differential current. However, in reality CTs can never be identical, therefore a
certain amount of differential current is inevitable. As the through-fault current in the primary increases, the
discrepancies introduced by imperfectly matched CTs is magnified, causing the differential current to build up.
Eventually, the value of the differential current reaches the pickup current threshold, causing the protection element
to trip. In such cases, the differential scheme is said to have lost stability. To specify a differential scheme’s ability to
restrain from tripping on external faults, we define a parameter called ‘through-fault stability limit’, which is the
maximum through-fault current a system can handle without losing stability.

6.2.2 BIAS CURRENT COMPENSATION


To prevent maloperation, compensation is needed for the protection to remain sensitive to internal faults but to
ignore through faults. This is achieved by applying a proportion of the scalar sum of all the currents entering and
exiting the zone. This scalar sum is called bias current.
The bias characteristic changes the operating point of the IED depending on the fault current. At low through-fault
currents, the CT performance is more reliable so a low bias current is needed. Less differential current is then
needed to trip the circuit breakers, allowing greater sensitivity to internal faults. At high through-fault currents, the

P64-TM-EN-1 95
Chapter 6 - Transformer Differential Protection P64

CTs may be close to saturation so a high bias current is needed. More differential current is then needed to trip the
circuit breakers, allowing greater security from external faults and less risk of maloperation.
This is achieved by defining an operating current characteristic. Often a triple slope characteristic is used as shown
below.

High Set Threshold

Operate region
Idiff
K2

Restraint region

K1
Is1

Is2 Ibias
V00664

Figure 40: Compensation using biased differential characteristic

Idiff is the differential current, which is the vector sum of all the current inputs. Ibias is a current which is proportional
to the scalar sum of all currents entering and leaving the zone. The bias current is used to calculate an operating
current. If the differential current calculated by the IED is above the operation current, then the device will trip
(providing no blocking signals are asserted).
The characteristic can be defined by setting certain parameters such as the minimum operating current Is1 (Iset 1),
Is2 (Iset 2), K1 and K2. Is1 sets the minimum operating current. Is2 sets the level of bias current at which the
steeper slope sets in. Constants K1 and K2 define the slopes. A High Set Threshold is usually defined, which
ensures the device will operate for very high currents, even if blocking signals are present.
The slope parts of the characteristic curve provide stability for external faults that cause CT saturation. The high
bias current region of the characteristic curve has a steeper slope than the low bias current region in order to
improve the stability even further for high-current external faults. The first slope, K1, compensates for CT errors and
tap changer errors. The second slope, K2, compensates for CT saturation. Is1 should be set above transient
overfluxing and Is2 should be considered as the transformer full load current. The CTs are sized according to the
transformer full load current.

6.2.3 THREE-PHASE TRANSFORMER CONNECTION TYPES


There are two ways of connecting a three-phase transformer winding:
● Star-connected (sometimes known as Y, or Wye)
● Delta-connected (sometimes known as D or D)

In some transformers, the windings are split at the centre point and terminals are brought out so that they can also
be interconnected. These windings can be zig-zag connected (Z-connected).
The more common connection types are:
● Y-y
● Y-d
● Y-z
● D-d
● D-y
● D-z

To differentiate between the low and high voltage sides of the transformer, a standard convention has been adopted
whereby lower case is used for the low voltage side and upper case is used for the high voltage side.

96 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Not only can the primary and secondary be connected as a star or a delta, each phase can also be reversed
resulting in a large choice of possible connections. In reality, however, only a few of these are used, because we
generally require that the phase shifts between the primary windings and their secondary counterparts be
consistent. This reduces the common connection types to those shown in the table below.
You will notice that the naming convention specifying the connection type in the first column also has a number
appended to it. This number, called the clock face vector, or vector group number represents the phase shift
between the current in a low voltage winding with respect to its counterpart on the high voltage winding. This
corresponds to the position of the number of a standard clock face. The table and diagram below shows examples
of connections with the clock vectors Midnight, 1 o’ clock, 6 o’ clock and 11 o’clock, which is equivalent to a phase
shift of 0°, -30°, -180° and +30° respectively.

Vector Group Phase Shift


Yy0 0°
Dd0 0°
Dz0 0°
Yd1 -30°
Dy1 -30°
Dz1 -30°
Yd5 -150°
Dy5 -150°
Dz5 -150°
Yy6 180°
Dd6 180°
Dz6 180°
Yd11 +30°
Dy11 +30°
Dz11 +30°

P64-TM-EN-1 97
Chapter 6 - Transformer Differential Protection P64

Type HV winding LV winding Winding Connection Phase Shift


YN yn
A2 a2
A1 A2 a2 a1

Yy0 B1 b1 0°
B2 b2
C2 B2 c2 b2 C1 c1
C2 c2

A2 a2 A1 A2 a2 a1

Dd0 C A c a B1 B2 b2 b1 0°

C2 B2 C1 C2 c2 c1
B c2 b b2

n
A2 a4
A1 A2 a4
a3 a2 a1
C A
Dz0 B1 B2 b4 0°
b3 b2 b1
C2 B2 c4 b4 C1 C2 c4
B c3 c2 c1

a2 YN

A2 c A1 A2 a2 a1
a
Yd1 c2 -30°
B1 B2 b2 b1
b
C1 C2 c2 c1
C2 B2 b2

yn
a2
A2
A1 A2 a2 a1

Dy1 A B c2 B2 b2 b1 -30°
B1

C2 B2 C1 C2 c2 c1
C b2

YN n
A2
a4 A1 A2 a4
a3 a2 a1
Yz1 B1 B2 b4 -30°
c4 b3 b2 b1
C2 B2 C1 C2 c4
b4 c3 c2 c1

YN
A2 c2
A1 A2 a1
b a2
Yd5 c -150°
b2 B1 B2 b1
b2
C2 B2 a C1 C2 c1
a2 c2

yn
A2 c2
A1 A2 a2 a1

Dy5 A B B1 B2 b2 b1 -150°
b2

C2 B2 C1 C2 c2 c1
C
a2
YN n
A2 c4 a3 a2
A1 A2 a4 a1
b4
Yz5 B1 B2 b4 b3 b2 b1 -150°

C2 B2 C1 C2 c4 c3 c2 c1
a4

V03125

Figure 41: Transformer winding connections - part 1

98 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Type HV Winding LV Winding Winding Connection Phase Shift


YN yn
A2 b1 c1
A1 A2 a2 a1
Yy6 180°
B1 B2 b2 b1
C2 B2
a1 C1 C2 c2 c1

A2 b1 b c1 A1 A2 a2 a1

Dd6 C A B1 B2 b2 b1 180°
a c

C2 B2 C1 C2 c2 c1
B a1

n
A2
c3 A2 a3 a4 a2 a1
b3
C A
Dz6 B2 b3 b4 b2 b1 180°

C2 B2 c C2 c3 c4 c2 c1
B
a3

YN
a2 A1 A2 a2
A2 b a1
Yd11 a b2 B1 B2 b2 30°
b1
c C1 C2 c2
C2 B2 c2 c1

a2 yn
A2
A1 A2 a2 a1
Dy11 A B b2 30°
B1 B2 b2 b1

C2 B2
C C1 C2 c2 c1
c2
YN n
A2 a4
A1 A2 a4 a3 a2

a1
Yz11 B1 B2 b4 b3 b2 30°
b4
b1
C2 B2 C1 C2 c4 c3 c2
c4 c1

V03126

Figure 42: Transformer winding connections - part 2

6.2.4 PHASE AND AMPLITUDE COMPENSATION


A power transformer is designed to convert voltages. This means the line currents either side of the transformer are
different in magnitude. If identical CTs were used on both sides of the transformer, the differential protection circuit
would be unbalanced, causing a differential current. Obviously, this has to be compensated for. Amplitude
compensation is theoretically arranged by having a suitable turns ratio on the secondary CT. Ideally, selecting CT
ratios that exactly match the inverse of the transformer turns ratio would compensate for the difference in the
transformer current magnitudes. However, the CT ratios associated with available CTs typically do not provide exact
ratio matching. Also for Y-delta or delta-Y connected transformers, the voltage and current magnitudes used are
changed by a factor of Ö3. Further, a phase shift is introduced, meaning the secondary side is out of phase with the
primary side. So further amplitude compensation, as well as phase compensation is required.
Before the advent of numerical IEDs, this compensation was achieved by choosing CTs with appropriate turns ratios
and connection types, and introducing interposing CTs with appropriate connection types. Of course, having CTs
with different turns ratios and connection types on each side of the protected zone exacerbates the CT errors,
therefore increasing the need for good through-fault compensation.
With modern IEDs, it is possible to do a great deal of the compensation in software, so simple Y-connected CTs can
be used on both sides of the transformer irrespective of the connection types. The CTs are chosen such that their
respective turns ratios provide a nominal current usable by the IED (1A or 5A). This in itself provides a certain
amount of amplitude compensation, but there will invariably be a CT ratio mismatch. This mismatch is compensated

P64-TM-EN-1 99
Chapter 6 - Transformer Differential Protection P64

for by software in the IED. The device calculates suitable values based on the reference power rating, transformer
voltage ratings, CT ratios and connection type (star or delta) to scale the secondary currents to a common base.

6.2.5 ZERO SEQUENCE FILTERING


An earth fault in a three-phase system will always produce a zero sequence current component. With earthed Y-
connected windings, this zero sequence current flows through the neutral conductor to earth. With delta-connected
windings, this zero sequence current component just circulates around the delta connected windings (unless an
earthing transformer is used). So in the case of a Y-delta transformer, an external fault will cause zero sequence
current to be measured by the Y-side CTs. However, because this zero sequence current is trapped on the delta
side, it is not measured by the delta-side CTs. This could cause maloperation if not compensated for. Before the
advent of numerical IEDs, this was handled by a configuration involving interposing CTs. Numerical IEDs, however,
can do this by filtering out the zero sequence component in software.

6.2.6 MAGNETISING INRUSH RESTRAINT


Whenever there is an abrupt change of magnetising voltage (e.g. when a transformer is initially connected to a
source of AC voltage), there may be a substantial surge of current through the primary winding called inrush
current.
In an ideal transformer, the magnetizing current would rise to approximately twice its normal peak value as well,
generating the necessary MMF to create this higher-than-normal flux. However, most transformers are not designed
with enough of a margin between normal flux peaks and the saturation limits to avoid saturating in a condition like
this, and so the core will almost certainly saturate during this first half-cycle of voltage. During saturation,
disproportionate amounts of MMF are needed to generate magnetic flux. This means that winding current, which
creates the MMF to cause flux in the core, could rise to a value way in excess of its steady state peak value.
Furthermore, if the transformer happens to have some residual magnetism in its core at the moment of connection
to the source, the problem could be further exacerbated.
The following figure shows the magnetizing inrush phenomenon:

100 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

+Fm

Steady state

–Fm

2Fm
Switch on at voltage
Zero – No residual flux

V = Voltage, F = Flux, Im = magnetising current, Fm = maximum flux

E03123
Figure 43: Magnetising inrush phenomenon

The main characteristics of magnetising inrush currents are:


● Higher magnitude than the transformer rated current magnitude
● Containing harmonics and DC offset
● Much longer time constant than that of the DC offset component of fault current

We can see that inrush current is a regularly occurring phenomenon and should not be considered a fault, as we do
not wish the protection device to issue a trip command whenever a transformer is switched on at an inconvenient
point during the input voltage cycle. This presents a problem to the protection device, because it should always trip

P64-TM-EN-1 101
Chapter 6 - Transformer Differential Protection P64

on an internal fault. The problem is that typical internal transformer faults may produce overcurrents which are not
necessarily greater than the inrush current. Furthermore, faults tend to manifest themselves on switch on, due to
the high inrush currents. For this reason, we need to find a mechanism that can distinguish between fault current
and inrush current. Fortunately, this is possible due to the different natures of the respective currents. An inrush
current waveform is rich in harmonics, especially 2nd harmonics, whereas an internal fault current consists only of
the fundamental. We can therefore develop a restraining method based on the 2nd harmonic content of the inrush
current. The mechanism by which this is achieved, is called second harmonic blocking.

6.2.7 OVERFLUXING RESTRAINT


Sometimes the protected transformer is subject to overfluxing due to temporary overloading with a voltage in
excess of the nominal voltage, or a reduced voltage frequency. For example, when a load is suddenly disconnected
from a power transformer, the voltage at the input terminals of the transformer may rise by 10-20% of the rated
value. Since the voltage increases, the flux also increases. As a result, the transformer steady state excitation
current becomes higher. The resulting excitation current flows in one winding only and therefore appears as
differential current which may rise to a value high enough to operate the differential protection. A typical differential
current waveform during such a condition is as follows.

E03107

Figure 44: Typical overflux current waveform

Such waveforms have a significant 5th harmonic content. We can therefore develop a restraining method based on
the 5th harmonic content of the inrush current. The mechanism by which this is achieved, is called fifth harmonic
blocking.

102 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

6.3 IMPLEMENTATION
To enable or disable Differential Protection, set Diff Protection in the CONFIGURATION column and Trans Diff in
the DIFF PROTECTION column of the of the relevant settings group.

6.3.1 DEFINING THE POWER TRANSFORMER


To set up the transformer differential protection you need to define what type of transformer is being protected. You
do this with settings in the SYSTEM CONFIG column.
The P642 only supports two-winding transformers. For the P643 and P645, the Winding Config setting determines
whether the power transformer being protected is a two-winding (HV+LV), or a three-winding (HV+LV+TV)
transformer.
The Winding Type setting determines whether the protected transformer is a conventional transformer or an
autotransformer.
The Ref Power S setting sets the reference power of the protected transformer. This is used as a reference by the
differential function to calculate the ratio correction factors (which incidentally are displayed in the Match Factor CT
cells. The reference power is the maximum MVA rating specified in the transformer nameplate.
You can define each winding as Y (or Star, or Wye), D (delta), or Z (zigzag) in the settings HV connection, LV
Connection and TV connection.
You also need to set the nominal voltage of each winding. You do this with the settings HV Nominal, LV Nominal
and TV Nominal.
To ensure the device can perform vector group correction, you need to enter the vector groups for the LV and TV
windings. You do this by entering the relevant vector group reference (available on the nameplate) using the
settings LV Vector Group and TV Vector Group.
In addition to the LV Vector Group and TV Vector Group settings, there is a setting called Ref Vector Group. This
setting allows you to apply a phase shift to the HV current inputs. In the majority of cases, this would be set to 0, but
there are some specialist applications where you may wish to set the reference vector group to something other
than 0. An application note at the end of this chapter explains why you would want do to this.
Finally, you need to set the phase sequence with the Phase Sequence setting. This will be either standard ABC
or Reverse ACB.
If the phase rotation is changed from ABC to ACB, then the vector group settings need to reflect this change
accordingly. This can be achieved by setting them to be equal to 12 minus the original value. For example a Yd11
transformer has a vector group setting of 11 when the phase sequence is ABC. However if the phase sequence
changes to ACB, then the vector group setting should be set to 1.

Note:
To minimise imbalances due to tap changer operation, current inputs to the differential element should be set according to the
mid-tap position and not the nominal voltage. The Ref Vector Group setting provides a reference vector group to which all
other vector groups are referenced. Typically, this is set to 0°.

6.3.2 SELECTING THE CURRENT INPUTS


The P642 has two current terminal inputs (T1 and T2), the P643 has up to three terminal current inputs (T1 to T3),
and the P645 has up to five current terminal inputs (T1 to T5).
For the P642, you associate one terminal current input with the HV (High Voltage) winding and the other with the LV
(Low Voltage) winding.
For the P643 and P645 you can choose to associate more than one terminal current input with particular windings.
In cases where more than one terminal CT is associated with a winding, the input to the differential protection

P64-TM-EN-1 103
Chapter 6 - Transformer Differential Protection P64

function uses the vector sum of the current terminal inputs (on a phase by phase basis) as the input to the
calculation for that winding.
You associate these current inputs with the system transformer windings with the settings HV CT Terminals, LV CT
Terminals and TV CT Terminals in the SYSTEM CONFIG column as follows:

Setting P642 P643 P645


00001
00011
001
HV CT Terminals 01 00111
011
01011
01111
10000
11000
100
LV CT Terminals 10 11100
110
11010
11110
00100
01100
TV CT Terminals 010
00110
01110

Where the terminals T1 to T5 correspond to the bits in the binary string as follows (1 = in use, 0 = not in use). The
bit order starts with T1 on the right-hand side. For example:

If a CT is assigned to more than one winding, then an alarm is issued (CT Selection Alm). When this DDB signal is
asserted, the protection is also blocked.

6.3.3 PHASE CORRECTION


The device automatically carries out phase correction based on the settings made in the SYSTEM CONFIG column.
For a reverse phase rotation (ACB), the device will automatically form a complementary value for the vector group
ID. You can achieve reverse phase rotation by setting the Phase Sequence setting in the SYSTEM CONFIG
column. The device will then automatically form the complementary value of the set vector group ID by subtracting it
from the number 12 (vector group ID = 12 - set ID).

6.3.4 RATIO CORRECTION


For transformer differential protection, ratio correction is required. The device automatically calculates the ratio
correction factor for each of the current inputs and displays the calculated matching factors in the SYSTEM
CONFIG column.
As well as the parameters of the power transformer itself, which are defined in the SYSTEM CONFIG column, you
need to set up the CT ratios and polarities. You do this in the CT AND VT RATIOS column with the Polarity,
Primary and Secondary settings for all CTs used.
The device then calculates the ratio correction factors as follows:

104 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

S ref I nom ,n
I ref ,n = K amp ,n =
3Vnom , n S ref
3Vnom, n

where:
● Sref = common reference power for all ends
● Iref,n = reference current for the respective CT input
● Kamp,n = amplitude-matching factor for the respective CT input
● Inom,n = primary nominal currents for the respective CT input
● Vnom,n = primary nominal voltage for the respective CT input
The device also checks that the matching factors are within their permissible ranges. The matching factors must
satisfy the condition:
0.05 <= Kamp <= 15 for standard CTs
0.05 <= Kamp <= 20 for sensitive CTs

6.3.5 CT PARAMETER MISMATCH


The CT parameter (CT Para) mismatch logic implemented in firmware is as follows:

One CT is configured to more than one


winding simultaneously
1 Set CT para mismatch alarm

Winding configuration = HV/LV


&
Reset CT para mismatch alarm
The ratio correction factor (amplitude
matching factor) of any CT is out of range

Winding configuration = HV/LV/TV


&

The ratio correction factor (amplitude


matching factor) of the CTs associated with
the HV winding is out of range 1

The ratio correction factor (amplitude


matching factor) of the CTs associated with
the LV winding is out of range

The ratio correction factor (amplitude


matching factor) of the CTs associated with
the TV winding is out of range &

The ratio correction factor (amplitude


matching factor) of the CTs associated with
the TV winding is greater than allowed

The ratio correction factor (amplitude


matching factor) of the CTs associated with
the TV winding is out of range Remove the current inputs from
&
the differential calculation
The ratio correction factor (amplitude
matching factor) of the CTs associated with
the TV winding is less than 0.001
V03108a

Figure 45: CT parameter mismatch logic diagram

If any of the ratio correction factors in two-winding applications are out of range, the CT para mismatch alarm is
asserted. In multi-winding applications, the alarm is asserted if the ratio correction factor of the CTs associated with

P64-TM-EN-1 105
Chapter 6 - Transformer Differential Protection P64

HV or LV windings are out of range or the ratio correction factor of the CTs associated to TV winding is greater than
15 for standard CTs and 20 for sensitive CTs.
If the ratio correction factor of the CT associated to TV winding is lower than 0.001, this current is removed from the
differential calculation, as shown in the logic diagram.
If the CT para mismatch alarm is asserted the protection is also blocked.
The phase current measured values of the windings of the protected object are always scaled by the relevant
matching factors. These are then available for further processing. Consequently, all threshold values and measured
values refer back to the relevant reference currents rather than to the transformer nominal currents or the nominal
currents of the device.

6.3.6 SETTING UP ZERO SEQUENCE FILTERING


There are two modes of operation for zero sequence filtering; simple and advanced. You set the operation mode
with the Set Mode setting in the DIFFPROTECTION column.
In simple mode, you cannot disable zero sequence filtering. It is automatically implemented for all earthed windings.
You can define whether a winding is earthed or not with the settings HV Grounding, LV Grounding and TV
Grounding in the SYSTEM CONFIG column. If a setting is set to grounded, zero sequence filtering will always be
implemented for that winding. If set to Ungrounded, it will not be implemented.
In advanced mode, you can enable or disable zero sequence filtering manually using the settings Zero seq filt HV,
Zero seq filt LV and Zero seq filt TV in the DIFF PROTECTION column.

6.3.7 TRIPPING CHARACTERISTICS


The differential and bias currents for each phase are calculated from the current variables after amplitude and
vector group matching.
The differential current is the vector sum of the CT current inputs as follows:

P642 : I diff , y = I s , y ,CT 1 + I s , y ,CT 2

P643 : I diff , y = I s , y ,CT 1 + I s , y ,CT 2 + I s , y ,CT 3

P645 : I diff , y = I s , y ,CT 1 + I s , y ,CT 2 + I s , y ,CT 3 + I s , y ,CT 4 + I s , y ,CT 5

The bias current is defined as half of the scalar sum of the CT current inputs:

P 642 : I bias , y = 0.5 ⋅  I s , y ,CT 1 + I s , y ,CT 2 


 
P 643 : I bias , y = 0.5 ⋅  I s , y ,CT 1 + I s , y ,CT 2 + I s , y ,CT 3 
 
P 645 : I bias , y = 0.5 ⋅  I s , y ,CT 1 + I s , y ,CT 2 + I s , y ,CT 3 + I s , y ,CT 4 + I s , y ,CT 5 
 
where:
● y is the measured phase (A, B or C)
● Is is the current after the amplitude and vector group are matched.

106 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

The tripping characteristic has two knees. The first knee is dependent on the settings of Is1 and K1. The second
knee is defined by the setting Is2. The lower slope provides stability for low external faults. The higher slope
provides stability for high through fault conditions, since transient differential currents may be present due to current
transformer saturation.

Idiff/Inom

Is-HS2

Is-HS1 Restraint region

K2

Operate region

K1

Is1
TC and CT errors

Is2 Ibias /Inom


V03110

Figure 46: Transformer biased tripping characteristic

Once the differential and bias currents are calculated, the following comparisons are made and an operate/restrain
signal is obtained:
For the flat slope range: 0 ≤ Ibias max ≤ Is1/K1

Idiff ≥ Is1 + transient bias


For the K1 slope range: Is1/K1 ≤ Ibias max ≤ Is2

Idiff ≥ K1.Ibias max + transient bias


For the K2 slope range: Is2 ≤ Ibias max ≤ Is-HS2/K2

Idiff ≥ K1.Is2 + K2(Ibias max - Is2 ) + transient bias

6.3.7.1 HIGH-SET FUNCTION


The High Set 1 algorithm uses a peak detection method to achieve fast operating times. The peak value is the
largest absolute value of differential current in the latest cycle. Since the High Set 1 algorithm uses a peak detection
method, Is-HS1 is set above the expected highest magnetizing inrush peak to maintain immunity to magnetizing
inrush conditions. For a High Set 1 trip, two conditions must be fulfilled:
● The peak value of the differential current is greater than Is-HS1 setting.
● The bias characteristic is in the operate region.

If the differential current is above the adjustable Is-HS1 threshold, the device will trip if in the Operate region, but
not in the restrain region. However, second harmonic blocking and overfluxing blocking are NOT taken into account.
The High Set 1 resets when the differential and bias currents are in the restraint area.
If the differential current is above the adjustable Is-HS2 threshold, bias current is not taken into account and the
device will trip regardless. As with High Set 1, second harmonic blocking and overfluxing blocking are NOT taken
into account. The High Set 2 element resets when the differential current drops below 0.95*Is-HS2.

P64-TM-EN-1 107
Chapter 6 - Transformer Differential Protection P64

6.3.7.2 CIRCUITRY FAIL ALARM


The circuitry fail alarm logic requires the following settings:
Circuitry Fail: to enable or disable the function
Is-cctfail: to define the minimum differential threshold
K-cctfail: to define the slope gradient
CctFail Delay: to set a time delay
If the differential current is larger than the Is-cctfail setting and no trip is issued after the time delay has elapsed, an
alarm is issued indicating a CT problem.

6.3.8 TRIPPING CHARACTERISTIC STABILITY


Conditions such as CT saturation and transient switching operations can cause incorrect operation of differential
elements. To avoid this a number of techniques are employed in this device. These include :
● Maximum and Residual Bias
● Transient Bias
● CT saturation detection (to discriminate between internal and external faults)
● No Gap Detection
● External Fault Detection
● Current Transformer Supervision
● Circuitry Fail Alarm
● Second Harmonic Blocking
● Fifth Harmonic Blocking

6.3.8.1 MAXIMUM BIAS


The differential and bias currents are calculated on a per phase basis eight times per cycle. A comparison between
differential and bias current is used to determine whether to trip or not. The comparison is made on a per phase
basis using the differential current measured on that phase. However a common bias current is used for all three
phases.. To assure stability, the largest bias current calculated on any phase is used to restrain all phases. This is
referred to as the Maximum Bias.

6.3.8.2 DELAYED BIAS


To provide further stability when external faults are being cleared, the protection checks for the highest value of bias
current calculated during the previous cycle. If that value is higher than the present value, it is used to restrain the
tripping decision. This is referred to as the Residual Bias. The Residual Bias technique maintains through fault
stability for clearance of external faults.

6.3.8.3 TRANSIENT BIAS


If there is a sudden increase in the mean-bias measurement, an additional bias quantity (called Transient Bias) can
be introduced into the bias calculation, on a per-phase basis. Transient Bias is only active for external faults. It can
be enabled or disabled with the Transient Bias setting in the DIFF PROTECTION column.
Transient bias, decays exponentially. The transient bias quantity is added to the operating current calculated at the
maximum bias. Therefore, the following differential current thresholds are available:
Differential threshold phase A = Iop at max bias + transient bias_phase A
Differential threshold phase B = Iop at max bias + transient bias_phase B
Differential threshold phase C = Iop at max bias + transient bias_phase C

108 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

The transient bias technique uses a time decay constant, stability coefficients, and some differential function
settings to provide a dynamic bias characteristic. The following diagram shows the behaviour during an external
fault. For the device to trip, the fundamental of the differential current should be above the operating current at max
bias + transient bias.

1.6

transient bias - phaseA

1.4 Iadiff fundamental

Iop at max bias + transient bias - phaseA


1.2

1
I (pu)

0.8

0.6

0.4

0.2

0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
t(s)
V03109

Figure 47: Transient bias characteristic

The transient bias function enhances the stability of the differential element during external faults and allows for the
time delay in CT saturation caused by small external fault currents and high X/R ratios.
No transient bias is produced under load switching conditions, or when the CT comes out of saturation.

6.3.8.4 CT SATURATION TECHNIQUE


During CT saturation the second harmonic content may be high enough to block the low set differential element.
This would result, in the operation of the low set differential element being delayed for some internal faults. The
device includes a CT Saturation Detection technique, which unblocks the low set differential element during internal
faults with heavy CT saturation. This CT saturation detection technique is capable of distinguishing between
magnetising inrush and CT saturation. Therefore the 2nd harmonic blocking will work properly for magnetising
inrush, but will not be asserted for internal faults where CT saturation is an issue. This function is enabled or
disabled with the CT Saturation setting in the DIFF PROTECTION column.

6.3.8.5 NO GAP DETECTION TECHNIQUE


The No Gap Detection technique detects light CT saturation on a per phase basis. The No Gap Detection technique
unblocks the low set differential element during light CT saturation, allowing the low set differential element to trip
faster. Stability during inrush conditions is maintained, as this technique distinguishes between an inrush and a
saturated waveform. This function is enabled or disabled with the No Gap setting in the DIFF PROTECTION
column.

6.3.8.6 EXTERNAL FAULT DETECTION TECHNIQUE


An External Fault Detection technique has been implemented so that the CT saturation and No gap detection
techniques do not affect the second harmonic blocking during an external fault.

P64-TM-EN-1 109
Chapter 6 - Transformer Differential Protection P64

This technique considers the time to saturation, a delta bias start signal, a delta differential start signal and the ratio
of delta differential to delta bias at the time of start. As soon as an external fault occurs, the bias current changes,
but the differential current only increases after the time to saturation. The external fault detection DDBs are asserted
if the following conditions are fulfilled:
The delta bias start signal is asserted first. The delta bias start signal and the delta differential start signal are
asserted if the delta bias and delta differential currents are greater than 0.65 Is1 respectively.
The time difference between the assertion of the delta bias start signal and the assertion of the delta differential
signal is greater than the time to saturation. The minimum time to saturation is 2.5 ms for a 50 Hz system and 2.08
ms for a 60 Hz system.
The ratio of delta differential to delta bias is smaller than a fixed threshold when the delta bias start signal is
asserted.
The External Fault Detection algorithm is on a per phase basis. If an external fault is detected on phase A, B or C,
signals External fault A, External fault B or External fault C are asserted. The external fault detector resets after
6 seconds from the start or after 25 cycles from the start if the current is less than 0.9Is1.
The following figure shows the time to saturation for an external fault.

110 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

I/KA

-1

IA-1 IB-1 IC-1

I/KA

2.5

0.0

-2.5

-5.0

IA-5 IB-5 IC-5


Time to saturation = 31.5ms
PU

1.0

0.5

0.0

IA-DIFF IB-DIFF IC-DIFF

PU

1.5

1.0

0.5

IA-BIAS IB-BIAS IC-BIAS

V03124

Figure 48: Time to saturation - external AN fault

6.3.8.7 PHASE COMPARISON TECHNIQUE


During some of the evolving fault conditions from an external to an internal fault, the P64 uses a phase comparison
technique for faster fault clearance.
The phase comparison technique is activated once an external fault is detected and the bias current is greater than
Is2 × Phase Comp Ratio threshold, as shown in the figure below:

P64-TM-EN-1 111
Chapter 6 - Transformer Differential Protection P64

High Set Threshold

Operate region
Idiff
K2

Restraint region

K1
Is1

is2* Is2 Ibias


V03130 Phase Comp

Figure 49: Is2 x phase comparison

When the phase comparison is activated, it compares the relative angle of each winding current after applying
phase and amplitude compensation. If the measured relative angle is less than 90 degrees, this indicates the fault is
internal and the external fault detector is reset.
When the external fault detector resets it removes the transient bias. CT saturation and NO GAP technique are
activated, making the clearance of internal faults faster.

6.3.8.8 CURRENT TRANSFORMER SUPERVISION


If the CTS Status setting in the SUPERVISION Column is set to restrain, then upon detection of a CTS condition,
and following the CTS Time Delay, the minimum operating current is raised to the Is-CTS value.
This has the effect of lifting the minimum operate current threshold on the bias characteristic as follows:

Idiff/Inom

Is-HS2

Is-HS1 Restraint region

K2

Operate region

Is-CTS
K1

Is1
TC and CT errors

Is2 Ibias /Inom


V03127

Figure 50: Effect of CTS restrain

6.3.8.9 CIRCUITRY FAIL ALARM


Under normal operating conditions there should be no differential current (although there might be a small amount
due to CT mismatch). Under conditions such as current transformer (CT) failure or a failure of the CT circuitry, a
small differential current may be seen. This product can monitor the scheme for such conditions with a dual slope
differential characteristic, by enabling the Circuitry Fail setting in the DIFF PROTECTION column. The
characteristic is then defined by the settings Is-cctfail and k-cctfail. By default it is a time-delayed element to
prevent conflict with the tripping characteristic in the event of a genuine transformer fault. But if the ratio of

112 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

differential to bias current exceeds the Is-cctfail and k-cctfail settings, but does not exceed the Is1 and k1 settings,
for the duration of the Is-cctfail setting, a circuitry fail alarm is raised. The Is-cctfail delay is set to 5 seconds by
default.
The level at which the circuitry fail alarm would operate under these circumstances is shown by the red line as
follows:

Idiff/Inom

Is-HS2

Is-HS1 Restraint region

K2

Operate region

K-cctfail
Is-CTS
K1

Is1
TC and CT errors
Is-cctfail

Is2 Ibias /Inom


V03128

Figure 51: Bias characteristic with circuitry fail alarm

6.3.9 DIFFERENTIAL BIASED TRIP LOGIC


The differential biased trip is affected by both the CT Saturation technique and by the No Gap detection technique.
If the second harmonic blocking is asserted and either the CT Saturation Detection or No Gap detection technique
is asserted, then the biased differential trip is unblocked.
CT Saturation Detection and No Gap detection act independently from 5th harmonic blocking, however. A biased
differential trip will occur only if the fifth harmonic blocking is not asserted and the bias differential start signal is
asserted. The differential biased trip logic is described below.

P64-TM-EN-1 113
Chapter 6 - Transformer Differential Protection P64

Cross blocking IA5H Diff Start


Enabled
& Id Bias Start A & Id Bias Trip A
1

1
IA2H Diff Start &
&
CT Saturation A IB5H Diff Start
1
No Gap A & Id Bias Start B & Id Bias Trip B
1

External Fault A
1
IB2H Diff Start &
&
CT Saturation B IC5H Diff Start
1
No Gap B & Id Bias Start C & Id Bias Trip C

External Fault B
1
IC2H Diff Start &
&
CT Saturation C
1
No Gap C &

External Fault C

V03113

Figure 52: Differential biased trip logic

114 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

6.4 HARMONIC BLOCKING

6.4.1 2ND HARMONIC BLOCKING


The IED filters the differential current to determine the fundamental (Idiff(fn)) and second harmonic (Idiff(2fn) current
components. The device uses these quantities to produce a blocking signal, which will block the protection in the
event that the second harmonic component exceeds a certain level.
Second harmonic blocking is phase segregated. If the ratio of the second harmonic component to fundamental
component exceeds an adjustable threshold (set by IH2 Diff Set) in two consecutive calculations, a second
harmonic blocking signal is issued for the relevant phase. These are:
IA2H Diff Start (blocking signal for phase A)
IB2H Diff Start (blocking signal for phase B)
IC2H Diff Start (blocking signal for phase C)
If the Cross Blocking setting in the DIFF PROTECTION column is enabled, any one of the phase blocking signals
will block all three phases.
No blocking signal is asserted if the differential current exceeds the set thresholds Is-HS1 or Is-HS2.
The following flow diagram summarises the 2nd harmonic blocking procedure:

Any phase N
Idiff(2 fn)/Idiff(fn) > Setting Counter = 0

Counter + = 1

N
Counter >= 2

Block 1-phase
Drop-off
Low-set diff

Y Block 3-phase
Cross Block enabled
Low-set diff

Return

V03111

Figure 53: 2nd harmonic blocking process

P64-TM-EN-1 115
Chapter 6 - Transformer Differential Protection P64

6.4.2 2ND HARMONIC BLOCKING LOGIC

Idiffa
Idiffafundamental
fundamental

Low current (hard-coded)


& IA2H Diff Start

IB2H Diff Start


Idiffa 2nd harm / I diffa
Idiffa 2nd fund
harmonic IC2H Diff Start

IH2 Diff Set

Idiffb
Idiffbfundamental
fundamental

Low current (hard-coded)


&

Idiffb 2nd harm / I diffb


Idiffb 2nd fund
harmonic

IH2 Diff Set

Idiffc
Idiffcfundamental
fundamental

Low current (hard-coded)


&

Idiffc 2nd harm / Idiffc


Idiffb 2nd fund
harmonic

IH2 Diff Set

V00706

Figure 54: 2nd harmonic blocking logic

6.4.3 2ND HARMONIC SETTING GUIDELINES


During the energization period, the second harmonic component of the inrush current may be as high as 70%,
depending on the power rating. The second harmonic level may be different for each phase, which is why phase
segregated blocking is available.
If the setting is too low, the 2nd harmonic blocking may prevent tripping during some internal transformer faults. If
the setting is too high, the blocking may not operate for low levels of inrush current which could result in undesired
tripping of the differential element during the energization period. In general, a setting of 15% to 20% is suitable.
When testing the 2nd Harmonic blocking feature using an Omicron harmonic restraint module, it is recommended
that the CT Saturation and No Gap settings are Disabled while keeping Transient Bias either Enabled or
Disabled. However, when the relay is in service it is recommended that the CT Saturation and No Gap settings
are both Enabled. This is to make sure that if an internal fault develops during energisation of the transformer, the
2nd Harmonic blocking feature does not delay tripping of the differential protection element.

116 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

6.4.4 5TH HARMONIC BLOCKING IMPLEMENTATION


The IED filters the differential current to determine the fundamental Idiff(fn) and the fifth harmonic component
Idiff(5fn). The device uses these quantities to produce a blocking signal, which will block the protection in the event
that the fifth harmonic component exceeds a certain level.
5th Harmonic blocking can be used to prevent unwanted operation of the low set differential element under transient
overfluxing conditions.
The 5th harmonic blocking threshold is adjustable between 0 - 100% differential current. The threshold should be
adjusted so that blocking will be effective when the magnetizing current rises above the chosen threshold setting of
the low-set differential protection.
Fifth harmonic blocking is phase segregated. If the ratio Idiff(5-fn)/Idiff(fn) exceeds an adjustable threshold (set by
IH5 Diff Set in two consecutive calculations, and if the differential current is larger than 0.1 pu (the minimum setting
of Is1), then the fifth harmonic blocking signal is issued for the relevant phase. The DDB signals are:
IA5H Diff Start (blocking signal for phase A)
IB5H Diff Start (blocking signal for phase B)
IC5H Diff Start (blocking signal for phase C)
No cross blocking is available for 5th harmonic blocking.
No blocking signal is asserted if the differential current exceeds the set thresholds Is-HS1 or Is-HS2.
The following flow diagram summarises the 5th harmonic blocking procedure:

Any phase N
Idiff(5 fn)/Idiff(fn) > Setting Counter = 0

Counter + = 1

N
Counter >= 2

Block 1-phase
Drop-off
Low-set diff

Return

V03112

Figure 55: 5th harmonic blocking process

6.4.5 5TH HARMONIC SETTING GUIDELINE


In most applications, the default settings will ensure stability of the differential element. If more difficult situations
exist, the 5th harmonic differential current blocking facility may be of use.
A typical setting for Ih(5)%> is 35%.

P64-TM-EN-1 117
Chapter 6 - Transformer Differential Protection P64

6.4.6 GEOMAGNETIC DISTURBANCES


To offer protection against damage due to persistent overfluxing caused by a geomagnetic disturbance, the 5th
harmonic blocking element can be mapped to an output contact using an associated timer. Operation of this
element could be used to give an alarm to the network control centre. If such alarms are received from a number of
transformers, they could serve as a warning of geomagnetic disturbance so that operators could take some action
to safeguard the power system.
Alternatively this element can be used to initiate tripping in the event of prolonged pick up of a 5th harmonic
measuring element. It is not expected that this type of overfluxing condition would be detected by the AC overfluxing
protection. This form of time delayed tripping should only be applied in regions where geomagnetic disturbances are
a known problem and only after proper evaluation through simulation testing.

6.4.7 OVERALL HARMONIC BLOCKING LOGIC


The following logic diagram shows how the differential protection blocking mechanism works under conditions of
overfluxing and magnetisation inrush.

Id biased
delay
5th harmonic
Overfluxing detection
& Idiff Trip
Id biased
Trip

2nd harmonic
Inrush detection
& Idiff HS1 Trip
1 Idiff Trip
Idiff HS2 Trip
No Gap detection

1
&
CT Saturation

External Fault

Change Is1 to
Is-CTS in
restraint mode K2
CT Supervision K1
Is1 &
Is2
Idiff > Is-HS1

Idiff > Is-HS2

V03114

Figure 56: Differential protection blocking mechanisms

118 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

6.5 APPLICATION NOTES

6.5.1 SETTING GUIDELINES


The differential setting, Configuration/Diff Protection, should be set to Enable.
The basic pick up level of the low set differential element, Is1, is variable between 0.1 pu and 2.5 pu in 0.01 pu
steps. The setting will be dependant on the item of plant being protected and by the amount of differential current
that might be seen during normal operating conditions. When the device is used to protect a transformer, we
recommend a setting of 0.2 pu.
When protecting generators and other items of plant, where shunt magnetizing current is not present, a lower
differential setting would be more typical. We recommend 0.1 pu.
The P64 percentage bias calculation is performed 8 times per cycle. A triple slope percentage bias characteristic is
implemented. Both the flat and the lower slope provide sensitivity for internal faults. Under normal operation steady
state magnetizing current and the use of tap changers result in unbalanced conditions and hence differential
current. To accommodate these conditions the initial slope, K1, may be set to 30%. This ensures sensitivity to faults
while allowing for mismatch when the power transformer is at the limit of its tap range and CT ratio errors. At
currents above rated, extra errors may be gradually introduced as a result of CT saturation, Hence, the higher slope
may be set to 80% to provide stability under through fault conditions, during which there may be transient
differential currents due to saturation effect of the CTs. The through fault current, in all but ring bus or mesh fed
transformers, is given by the inverse of the per unit reactance of the transformer. For most transformers, the
reactance varies between 0.05 to 0.2 pu, therefore typical through fault current is given by 5 to 20 In.
The wide matching factor range is provided to allow the designer to trade off between the CT selection and the
scheme sensitivity. This is useful for applications such as busbar protection where a wide range of CT ratios may be
encountered. You should also note that the matching factor check should be carried out for all ends. One end alone
is not sufficient. The maximum sensitivity achieved in this product depends on the type of analog input and is given
in the CT requirements.

Note:
Differential protection alone may not achieve the full sensitivity required, and other protection functions such as REF may
have to be incorporated in conjunction with the differential protection.

The number of biased differential inputs required for an application depends on the transformer and its primary
connections. We recommend, where possible, that a set of biased CT inputs is used for each set of current
transformers. According to IEEE C37.110-2007, separate current inputs should be used for each power source to
the transformer. If the secondary windings of the current transformers from two or more supply breakers are
connected in parallel, under heavy through fault conditions, differential current resulting from the different
magnetizing characteristics of the current transformers flows in the IED. This current only flows through one current
input in the device and can cause maloperation. If each CT is connected to a separate current input, the total fault
current in each breaker provides restraint. You should only connect CT secondary windings in parallel when both
circuits are outgoing loads. In this condition, the maximum through fault level is restricted solely by the power
transformer impedance.
The P64 IED achieves stability for through faults in two ways, both of which are essential for correct relay operation.
The first consideration is the correct sizing of the current transformers. The second is by providing a bias
characteristic as shown below:

P64-TM-EN-1 119
Chapter 6 - Transformer Differential Protection P64

Idiff/Inom

Is-HS2

Is-HS1 Restraint region

K2

Operate region

K1

Is1
TC and CT errors

Is2 Ibias /Inom


V03110

Figure 57: Triple slope characteristic

6.5.2 EXAMPLE 1: TWO-WINDING TRANSFORMER - NO TAP CHANGER


Consider a two-winding power transformer with the following specifications:
● Power rating: 90 MVA Transformer
● Connection type: YNd9
● Voltage specification 132:33 kV.
● HV CT ratio: 400:1
● LV CT ratio: 2000:1
● Percentage reactance: 10%

120 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

90 MVA
132 kV/33 kV
YNd9
400:1 2000:1
A a

B b

C c

Protected zone
Earthing
transformer

B B

Phase & amplitude Phase & amplitude


Correction B B
Correction
+ +
Zero sequence filtering Zero sequence filtering
B B

D D D

P642
V03115

Figure 58: P642 used to protect a two winding transformer

Set the following parameters in the SYSTEM CONFIG column:

Setting in GROUP 1 SYSTEM CONFIG Value


Winding Config HV+LV
Winding Type Conventional
HV CT Terminals 01
LV CT Terminals 10
Ref Power S 90.00 MVA
Ref Vector Group 0
HV Connection Y-Wye
HV Grounding Grounded
HV Nominal 132.0 kV
HV Rating 90.00 MVA
% Reactance 10.00%
LV Vector Group 9
LV Connection D-Delta
LV Grounding Grounded

P64-TM-EN-1 121
Chapter 6 - Transformer Differential Protection P64

Setting in GROUP 1 SYSTEM CONFIG Value


LV Nominal 33.00 kV
LV rating 90.00 MVA
Phase Sequence Standard ABC
VT Reversal No Swap
CT1 Reversal No Swap
CT2 Reversal No Swap

Vector correction and zero sequence filtering are automatically performed by virtue of the LV Vector Group setting
and the HV Grounding and LV Grounding settings.
The ratio correction factors are calculated as follows:

I nom ,T 1CT 400


K amp ,T 1CT = = = 1.016
S ref 90 ×106
3Vnom, HV 3 ×132 ×103

I nom ,T 2CT 2000


K amp ,T 2CT = = = 1.270
S ref 90 ×106
3Vnom , LV 3 × 33 × 103

where:
● Sref = common reference power for all ends
● Kamp, T1CT, T2CT = ratio correction factor of T1 CT or T2 CT windings
● Inom, T1CT, T2CT = primary nominal currents of the main current transformers
● Vnom, HV,LV = primary nominal voltage of HV or LV windings

These matching factors are also displayed in the SYSTEM CONFIG column (Match Factor CT1 and Match Factor
CT2)
Now set the current differential parameters as follows:

Setting in GROUP 1 DIFF PROTECTION Value


Trans Diff Enabled
Set Mode Advance
Is1 200.0e-3 PU
K1 30.00%
Is2 1.000 PU
K2 80.00%
tdiff 0s
Is-CTS 1.500 PU
Is-HS1 10.00 PU
HS2 Status Disabled
Zero seq filt HV Enabled

122 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Setting in GROUP 1 DIFF PROTECTION Value


Zero seq filt LV Enabled
IH2 Diff Block Enabled
IH2 Diff Set 20%
Cross Blocking Enabled
CT Saturation Enabled
No Gap Enabled
IH5 Diff Block Enabled
IH5 Diff Set 35%
Circuitry Fail Disabled

6.5.3 EXAMPLE 2: AUTOTRANSFORMER WITH LOADED DELTA WINDING


Consider an autotransformer with the following specifications:
● Power rating: 175/175/30 MVA
● Connection type: YNyn0d1
● Voltage specification: 230/115/13.8 kV.
● HV CT ratio: 800:5
● LV CT ratio: 1200:5
● TV CT ratio: 2000:5
● HV tap range: +5% / -15% and 19 taps

P64-TM-EN-1 123
Chapter 6 - Transformer Differential Protection P64

175/175/30 MVA
230/115/13.8 kV
YNynd1
+5% / -15% TV
800:5 19 taps 2000:5
HV
a
A
b
B
c
C

Earthing
Protected zone transformer

c
LV
1200:5

B B

Phase & amplitude Phase & amplitude


Correction Correction
B B
+ +
Zero sequence filtering Zero sequence filtering
B B

Phase & amplitude


Correction
B
+
Zero sequence filtering
B

D D D

P645

V03116

Figure 59: P645 used to protect an autotransformer with loaded delta winding

Since the transformer has an on load tap changer on the HV side, the nominal voltage of the HV winding must be
set to the mid tap voltage level. According to the nameplate data, the mid tap voltage is 218.5 kV. The mid tap
voltage can also be calculated as follows:

(5 − 15)
100 +
Mid tap voltage = 2 × 230 = 218.5kV
100

Set the following parameters in the SYSTEM CONFIG column:

124 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Setting in GROUP 1 SYSTEM CONFIG Value


Winding Config HV+LV+TV
Winding Type Auto
HV CT Terminals 00001
LV CT Terminals 10000
TV CT Terminals 00100
Ref Power S 175.00 MVA
Ref Vector Group 0
HV Connection Y-Wye
HV Grounding Grounded
HV Nominal 218.50 kV
HV Rating 175.00 MVA
% Reactance 10.00%
LV Vector Group 0
LV Connection Y-Wye
LV Grounding Grounded
LV Nominal 115.00 kV
LV rating 145.00 MVA
TV Vector Group 1
TV Connection D-Delta
TV Grounding Grounded
TV Nominal 13.800 kV
TV rating 30.00 MVA
Phase Sequence Standard ABC
VT Reversal No Swap
CT1 Reversal No Swap
CT2 Reversal No Swap

Vector correction and zero sequence filtering are automatically performed by virtue of the LV Vector Group setting
and the HV Grounding and LV Grounding settings.
The device calculates the ratio correction factors as follows:

P64-TM-EN-1 125
Chapter 6 - Transformer Differential Protection P64

I nom ,T 1CT 800


K amp ,T 1CT = = = 1.730
S ref 175 ×106
3Vnom, HV 3 × 218.5 ×103

I nom ,T 5CT 1200


K amp ,T 5CT = = = 1.366
S ref 175 × 106
3Vnom , LV 3 ×115 ×103

I nom ,T 3CT 2000


K amp ,T 3CT = = = 0.273
S ref 175 ×106
3Vnom ,TV 3 × 13.8 ×103

where:
● Sref = common reference power for all ends
● Kamp, T1CT, T2CT, T3CT = ratio correction factor of T1 CT, T2 CT, or T3 windings
Inom, T1CT, T2CT, T3CT = primary nominal currents of the main current transformers
● Vnom, HV, LV, TV = primary nominal voltage of HV, LV, or TV windings

These matching factors are also displayed in the SYSTEM CONFIG column (Match Factor CT1 and Match Factor
CT2)
Now set the current differential parameters as follows:

Setting in GROUP 1 DIFF PROTECTION Value


Trans Diff Enabled
Set Mode Advance
Is1 200.0e-3 PU
K1 30.00%
Is2 1.000 PU
K2 80.00%
tdiff 0s
Is-CTS 1.500 PU
Is-HS1 10.00 PU
HS2 Status Disabled
Zero seq filt HV Enabled
Zero seq filt LV Enabled
Zero seq filt TV Enabled
IH2 Diff Block Enabled
IH2 Diff Set 20%
Cross Blocking Enabled
CT Saturation Enabled

126 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Setting in GROUP 1 DIFF PROTECTION Value


No Gap Enabled
IH5 Diff Block Enabled
IH5 Diff Set 35%
Circuitry Fail Disabled

6.5.4 EXAMPLE 3: AUTOTRANSFORMER WITH UNLOADED DELTA WINDING


Consider an autotransformer with the following specifications:
● Power rating: 175/175/30 MVA
● Connection type: YNyn0d1
● Voltage specification: 230/115/13.8 kV.
● HV CT ratio: 1200:5
● LV CT ratio: 1200:5
● Neutral CT ratio: 1200:5
● HV taps at +5% and -15%

The winding configuration is set to HV + LV + TV. The CT on the HV line side is connected to T1 CT, the CT on the
HV neutral side is connected to T2 CT, and the CT on the LV side is connected to T3 CT.

P64-TM-EN-1 127
Chapter 6 - Transformer Differential Protection P64

175 /175 /30 MVA


230 /115 /13.8 kV
YNynd1
+5% / -15%
19 taps 1200 :5
LV
1200 :5 a
HV
A b

B c

1200 :5

Protected
zone

B B

Phase & amplitude Phase & amplitude


Correction B B
Correction
+ +
Zero sequence filtering Zero sequence filtering
B B

Phase & amplitude


Correction B
+
Zero sequence filtering
B

D D D

P643

V03117

Figure 60: P643 used to protect an autotransformer with unloaded delta winding

Set the following parameters in the SYSTEM CONFIG column:

Setting in GROUP 1 SYSTEM CONFIG Value


Winding Config HV+LV+TV
Winding Type Auto
HV CT Terminals 001
LV CT Terminals 100
TV CT Terminals 010
Ref Power S 175.00 MVA
Ref Vector Group 0
HV Connection Y-Wye
HV Grounding Ungrounded

128 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Setting in GROUP 1 SYSTEM CONFIG Value


HV Nominal 230.0 kV
HV Rating 175.00 MVA
% Reactance 10.00%
LV Vector Group 0
LV Connection Y-Wye
LV Grounding Ungrounded
LV Nominal 230.00 kV
LV rating 175.00 MVA
TV Vector Group 0
TV Connection Y-Wye
TV Grounding Ungrounded
TV Nominal 230.0 kV
TV rating 175.0 MVA
Phase Sequence Standard ABC
VT Reversal No Swap
CT1 Reversal No Swap
CT2 Reversal No Swap
CT3 Reversal No Swap

Vector correction and zero sequence filtering are automatically performed by virtue of the LV Vector Group setting
and the HV Grounding and LV Grounding settings.
It is preferable to have the ratio correction factors equal to or close to 1.
Applying Kirchoff's law, assume that the full load current is flowing, that an equivalent source is connected to the HV
winding and that an equivalent load is connected to the LV winding. The current distribution is as follows:

S 175 ×106
I FLC − HV = = = 439 A
3Vnom , HV 3 × 230 ×103

S 175 ×106
I FLC − LV = = = 878 A
3Vnom, LV 3 × 115 ×103

P64-TM-EN-1 129
Chapter 6 - Transformer Differential Protection P64

175/175/30 MVA
230 /115 /13.8 kV
YNynd1
230 kV - +5%/-15% - 19 taps

a 878 Ð0°
439 Ð0° 439 Ð0° A
Equivalent b 878 Ð-120°
load
439 Ð-120° 439 Ð-120° B
c 878 Ð-240°
439 Ð-120° 439 Ð120° C
1200:5
1200:5 1200:5

V03118

Figure 61: Unloaded delta – current distribution

The reference power is set to 175 MVA and the nominal voltage in HV, LV and TV windings is set to 230 kV. In this
application, you do not need to consider the mid tap voltage, even though, there is an on load tap changer on the
HV side.
The device calculates the ratio correction factors as follows:

I nom,T 1CT 1200


K amp ,T 1CT = K amp ,T 2CT = K amp ,T 3CT = = = 2.73
S ref 175 × 106
3Vnom 3 × 230 × 103
Now set the current differential parameters as follows:

Setting in GROUP 1 DIFF PROTECTION Value


Trans Diff Enabled
Set Mode Advance
Is1 200.0e-3 PU
K1 20.00%
Is2 1.000 PU
K2 80.00%
tdiff 0s
Is-CTS 1.500 PU
Is-HS1 10.00 PU
HS2 Status Disabled
Is-HS2 32.00 PU
Zero seq filt HV Disabled
Zero seq filt LV Disabled
Zero seq filt TV Disabled
IH2 Diff Block Enabled
IH2 Diff Set 20%

130 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Setting in GROUP 1 DIFF PROTECTION Value


Cross Blocking Enabled
CT Saturation Enabled
No Gap Enabled
IH5 Diff Block Enabled
IH5 Diff Set 35%
Circuitry Fail Disabled

The differential element does not protect the tertiary winding. Unloaded delta-connected tertiary windings are often
not protected. If protection is required, the delta winding can be earthed at one point through a current transformer
used to provide instantaneous overcurrent protection for the tertiary winding.

6.5.5 SETTING GUIDELINES FOR SHORT-INTERCONNECTED BIASED


DIFFERENTIAL PROTECTION
The P645 can be used to protect busbars. Consider the five feeders - single bus scheme and its differential
protection zone shown below:

B
Phase & amplitude Circuit Breaker 1
Correction
B
+
Zero sequence filtering
B

B
Phase & amplitude Circuit Breaker 2
B
Correction
+
Zero sequence filtering
B

B
Phase & amplitude Circuit Breaker 3
Correction
B
+
Zero sequence filtering
B

B
Phase & amplitude Circuit Breaker 4
Correction
B
+
Zero sequence filtering
B

B
Phase & amplitude Circuit Breaker 5
B
Correction
+
Zero sequence filtering
B
115kV
D D D

P645

V03119

Figure 62: Single bus differential protection zone

Assume that feeder CTs 1 to 5 are connected to inputs T1 to T5 respectively.


Set the following parameters in the SYSTEM CONFIG column:

P64-TM-EN-1 131
Chapter 6 - Transformer Differential Protection P64

Setting in GROUP 1 SYSTEM CONFIG Value


Winding Config HV+LV+TV
Winding Type Conventional
HV CT Terminals 01111
LV CT Terminals 10000
Ref Power S 145.0 MVA*
Ref Vector Group 0
HV Connection Y-Wye
HV Grounding Ungrounded**
HV Nominal 115.0 kV***
HV Rating 145.0 MVA****
% Reactance 10.00%
LV Vector Group 0
LV Connection Y-Wye
LV Grounding Ungrounded**
LV Nominal 115.0 kV***
LV rating 145.00 MVA****
TV Vector Group 0
TV Connection Y-Wye
TV Grounding Ungrounded**
TV Nominal 115.0 kV***
TV rating 145.0 MVA****

Note:
* This is the maximum load (including overloads) that would be handled by the busbar.

Note:
** This disables the zero sequence filters.

Note:
*** This is the system voltage.

Note:
**** This setting has no impact on the differential protection. It is used by other functions such as the thermal and through-fault
monitoring elements which are not required for busbar protection.

Now set the current differential parameters as follows:

Setting in GROUP 1 DIFF PROTECTION Value


Trans Diff Enabled
Set Mode Advance

132 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Setting in GROUP 1 DIFF PROTECTION Value


Is1 1.200 PU
K1 20.00%
Is2 400.0e-3 PU
K2 80.00%
tdiff 0s
Is-CTS 1.500 PU
Is-HS1 10.00 PU
HS2 Status Disabled
Zero seq filt HV Disabled
Zero seq filt LV Disabled
IH2 Diff Block Disabled
IH5 Diff Block Disabled
Circuitry Fail Enabled
Is-cctfail 100.0e-3 PU
K-cctfail 10.00%
Cctfail Delay 5.000 s

Note:
Set the Circuitry Fail alarm to Enabled and set K-cctfail to 15% to allow the maximum composite error of 10% that may be
introduced by class 10P current transformers. Is-cctfail is typically set between 5 to 20% to prevent CT noise and differential
current caused by load imbalance. This element is typically delayed by 5 s.

Note:
CT supervision should be used to prevent maloperation if there is an open circuited CT secondary. The CTS feature can be
used to desensitize the biased differential protection. To do this, raise the differential current pickup setting Is1 to the value of
Is-CTS.

P64-TM-EN-1 133
Chapter 6 - Transformer Differential Protection P64

Idiff/Inom
4
3.8
3.6
3.4 K2 = 80%
3.2
3
2.8
2.6 Is-CTS
2.4
2.2
2
1.8
1.6
1.4 Is1
1.2
1
0.8
0.6
0.4
0.2 Is-cctfail> 10%
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Ibias/Inom

P64 cctfail CT error Is-CTS

V03120a

Figure 63: Busbar biased differential protection

6.5.6 SETTING GUIDELINES FOR SHUNT REACTOR BIASED DIFFERENTIAL


PROTECTION
Shunt reactors are commonly used in the power system to compensate for the capacitive reactance of long
transmission lines. Shunt reactors are inductive loads that are used to absorb reactive power to reduce the over
voltages generated by line capacitance.
One of the main difficulties with shunt reactor protection is that the protection IED may maloperate during iron-core
reactor energization and de-energization. A shunt reactor is typically switched in and out regularly depending on the
power system load. The iron-core shunt reactor energization current contains a DC offset with a long time constant
(up to 1 second) and low frequency components. These current waveforms cause a certain level of flux in the CT
magnetic core. During normal reactor operation the current is generally the nominal current, which is not high
enough to reduce the flux level in the CT. In the next switch in operation, the flux may either increase or decrease
depending on the point o on the wave when energization occurs. The regular switching in and out of the reactor
causes CT saturation; therefore, we recommend that the current transformers on both sides of the reactor have
similar excitation characteristics to reduce the risk of maloperations. A high impedance differential scheme is
generally better than a low impedance differential scheme, because it is not affected by CT saturation.
As per IEEE C37.109-2006 the properties of shunt reactors can be summarized as follows:
● Dry air-air core type reactors: no magnetizing inrush during energization as there is no iron core. The peak
current during energization might be as high as 2 Ö2Inominal due to transient offset. Air core type reactors are
normally used up to 34.5 kV and often installed on the transformer tertiary winding.
● Oil-immersed type reactors: the gapped iron-core type might experience severe energizing inrush. The
coreless type experiences less severe magnetizing inrush.
Consider the following shunt reactor:

134 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Busbar A Busbar B

T1 CT T2 CT
400 :5 400:5

Bk 1 Bk 2 Bk 3

500 kV
163 .3 MVA

T3 CT
1000 :1

V03121

Figure 64: Shunt Reactor single line diagram

The bias differential element in the P643 would be used to protect the reactor. In a reactor application the low set
differential element Is1, should be set between 10%-15%. Inrush current in a shunt reactor does not appear as a
differential current like that which appears in a transformer, unless the CT saturates after some time due to long DC
time constant. Though the level of second harmonic in many cases can be relatively high, there are many cases
with no or very low content of harmonics in the differential current. Since the level of 2nd harmonic is small in shunt
reactors compared with transformers, the high set 1 differential element, Is-HS1, can be set to 250% of the reactor
current at rated voltage.
Set the following parameters in the SYSTEM CONFIG column:

Setting in GROUP 1 SYSTEM CONFIG Value


Winding Config HV+LV
Winding Type Conventional
HV CT Terminals 011
LV CT Terminals 100
Ref Power S 163.3 MVA
Ref Vector Group 0
HV Connection Y-Wye
HV Grounding Ungrounded
HV Nominal 500.0 kV
HV Rating 163.3 MVA
% Reactance 40.00%
LV Vector Group 0
LV Connection Y-Wye
LV Grounding Ungrounded
LV Nominal 115.0 kV
LV rating 163.3 MVA

P64-TM-EN-1 135
Chapter 6 - Transformer Differential Protection P64

Setting in GROUP 1 SYSTEM CONFIG Value


Phase Sequence Standard ABC
VT Reversal No Swap
CT1 Reversal No Swap
CT2 Reversal No Swap
CT3 Reversal No Swap

Now set the current differential parameters as follows:

Setting in GROUP 1 DIFF PROTECTION Value


Trans Diff Enabled
Set Mode Simple
Is1 100.0e-3 PU
K1 30.00%
Is2 1.000 PU
K2 80.00%
tdiff 0s
Is-CTS 1.500 PU
Is-HS1 2.500 PU
HS2 Status Disabled
Zero seq filt HV Disabled
Zero seq filt LV Disabled
IH2 Diff Block Disabled
Cross blocking Enabled
CT Saturation Disabled
No Gap Disabled
IH5 Diff Block Disabled
Circuitry Fail Disabled

6.5.7 SETTING GUIDELINES FOR USING SPARE CT INPUTS


The P643 and P645 can be configured to protect transformers for differential protection and the unused CT inputs
can be used to protect other circuits. For example the P643 can use 2 of the 3 phase CT inputs to provide
differential protection of a 2 winding transformer by setting Winding Config to HV+LV and the unused 3rd 3 phase
current input can be used to provide overcurrent protection on another circuit such as an auxiliary transformer, as
shown below:

136 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

V03122

Figure 65: P643 Using spare CT input for overcurrent protection

6.5.8 SETTING GUIDELINES FOR REFERENCE VECTOR GROUP


The following table shows how to set the zero sequence filter for the different Ref Vector Group options.

Ref Vector Group Zero Seq Filt HV Setting Zero Seq Filt LV Setting Zero Seq Filt TV Setting
0 Enabled Disabled Disabled
1 Disabled Disabled Enabled
2 Enabled Enabled Disabled
3 Disabled Disabled Enabled
4 Enabled Disabled Disabled
5 Disabled Disabled Enabled
6 Enabled Disabled Disabled
7 Disabled Disabled Enabled
8 Enabled Disabled Disabled
9 Disabled Disabled Enabled
10 Enabled Disabled Disabled
11 Disabled Disabled Enabled

In the majority of applications, the reference vector group setting Ref Vector Group is set to 0. However there are
occasional applications where it may be desirable to set it to a value other than 0.

P64-TM-EN-1 137
Chapter 6 - Transformer Differential Protection P64

One example is to increase the sensitivity for phase-to-phase faults where it is used to protect a YNyn0 transformer.
In this scenario, the P64 would normally apply a -30° phase shift to both HV and LV windings due to the way it
works. However, by setting the reference vector group to 1, the device knows it does not have to apply a -30° shift
in its calculations, thus increasing its sensitivity to phase-to-phase faults.

6.5.9 STUB BUS APPLICATION


When a winding isolator is open (e.g. for maintenance purposes), a section of energized line, called the stub, could
be left unprotected. In the diagram below, we see that the HV winding disconnector is open and there is a fault in
the stub zone, which needs to be protected against.

HV TV

LV
Isolator
open signal

P645

V00696

Figure 66: Stub Bus arrangement

We do not want the standard differential protection or low impedance REF protection to operate, as this may have
repercussions on the rest of the system. In this case, Stub Bus protection should be used, when available. Stub Bus
protection is achieved by using the isolator status , applying this to an opto-input and combining it with a phase
overcurrent element (linked to the relevant winding) to provide a trip signal for the relevant circuit breakers.

6.5.9.1 STUB BUS IMPLEMENTATION


When the protection is used in one and half breaker busbar topology and the disconnector of any of the three
windings of the transformer is open, the differential and low impedance REF elements related to this winding are
affected.
The differential and low impedance REF protection elements should not trip for a stub bus fault and should be
blocked on a per winding basis.

6.5.9.1.1 STUB BUS ACTIVATION


The Stub Bus active signals HV StubBus Act, LV StubBus Act and TV StubBus Act are asserted when the
appropriate conditions are met to activate Stub Bus for the relevant winding. A fast under current DDB signal,
available on a per winding basis along with the isolator status, should be used to assert the respective Stub Bus
active signal. The fast under current DDB will become asserted if the current measured falls below the I< Current
Set of the relevant CBF element. For the fast undercurrent DDBs, I< Current Set represents a percentage of the
CT secondary nominal current (In). CBF does not need to be activated for the fast under current DDB to assert.

6.5.9.1.2 STUB BUS DIFFERENTIAL BLOCKING


When a Stub Bus active signal is asserted for a winding, the current of the respective winding is not considered in
the calculation of the differential and bias currents. The differential trip is not blocked however, and should be
blocked on the winding with Stub Bus active only (it should remain unblocked on the other windings). For example,
if a fault occurs within the differential zone and the HV Stub Bus is active, the differential element should only trip
the breakers connected to the LV and TV sides of the transformer. In this case, blocking of the HV winding
differential trip in can be achieved via the PSL logic.

138 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

Low impedance REF protection is blocked internally on a per winding basis by the fixed scheme logic. For example,
if HV StubBus Act is activated, then HV low impedance REF is blocked.
In applications where the protection is per differential scheme, the Stub Bus protection cannot be used since the
differential protection trip will be blocked each time any Stub Bus is activated.

6.5.9.1.3 STUB BUS TRIPPING


You can protect the Stub Bus zone by a non-directional DT phase overcurrent element with a delay time set to zero
second. To issue a Stub Bus trip, the overcurrent element and the relevant Stub Bus active DDB signals must both
be high. You can configure the Stub Bus tripping scheme in PSL.

6.5.9.2 STUB BUS SCHEME

Idiff Trip
Blocking 100
Idiff Trip
& Dwell Output R4
0

HV UndCurrent Activation
& S
89 a Q HV StubBus Act
Input L1 R

89 b
&
Input L2

HV StubBus Trip
100
Tripping & Output R1
Dwell
POC 1 I>3 Trip
0

This example applies to the HV element only . The LV and TV elements follow the same principles .
In this example , the following applies :

 The differential trip output is connected to output relay 4


 The HV Stub bus trip output is connected to output relay 1
 The HV stage 3 phase overcurrent element is used
 The 89 a contact is connected to opto -input 1
 The 89 b contact is connected to opto -input 2
V03129

Figure 67: Stub Bus Scheme Logic

6.5.10 TRANSFORMER DIFFERENTIAL PROTECTION CT REQUIREMENTS


The CT requirements detailed below are applicable to both standard CTs and sensitive CTs.

6.5.10.1 CT REQUIREMENTS - TRANSFORMER APPLICATION


We strongly recommend Class X or Class 5P current transformers for transformer differential protection
applications.
The current transformer knee-point voltage requirements are based on the following settings:

Parameter Description Value


Is1 This sets the minimum differential current threshold required for the transformer differential 0.2 pu
protection to trip.
Is2 This defines the bias current threshold at which the second slope of the bias current 1 pu
characteristic becomes active.
K1 This setting defines the gradient of the first slope in the bias current characteristic. 30%

P64-TM-EN-1 139
Chapter 6 - Transformer Differential Protection P64

Parameter Description Value


K2 This setting defines the gradient of the second slope in the bias current characteristic. 80%
Is-HS1 This setting defines the first High set threshold on the bias current characteristic. This 10 pu
setting is only used in advanced mode.
Is-HS2 This setting defines the second High set threshold on the bias current characteristic. This 32 pu
setting is only used in advanced mode.
Transient Bias This setting enables or disables the transient bias factor Enabled
Zero seq filt HV This setting enables or disables zero sequence filtering on the HV winding Enabled
Zero seq filt LV This setting enables or disables zero sequence filtering on the LV winding Enabled
Zero seq filt TV This setting enables or disables zero sequence filtering on the TV winding Enabled
IH2 Diff Set This setting defines the second harmonic blocking threshold. 20%
Cross blocking This setting enables or disables cross blocking (cross blocking is where a 2nd harmonic Enabled
blocking signal from any one phase, blocks all three phases).
CT Saturation This setting enables or disables CT saturation detection. Enabled
No Gap This setting enables or disables CT Gap detection. Enabled
IH5 Diff Set This setting defines the fifth harmonic blocking threshold. 35%

The following table provides the maximum sensitivity and its corresponding matching factor for different CT types:
Matching Factor for Typical Setting
CT Type Max. Sensitivity Permitted Matching Factor Range
Is1 = 0.2 pu
Standard 43 mA 0.05 - 15 4.65
Sensitive 13 mA 0.05 - 20 15.38

A series of external faults were simulated to determine the CT requirements for the differential function, by using a
state of the art Real Time Digital Simulation system (RTDS). We performed these tests with different X/R ratios, CT
burdens, fault currents, fault types and points on the current waveform.
To achieve through-fault stability, the K dimensioning factor must comply with the following expressions:

System Conditions K Kneepoint Voltage (VK)

In < IF <= 40In VK => 16In(RCT + 2RL + Rr) (earth fault)


16
5 <= X/R <= 20 VK => 16In(RCT + RL + Rr) (phase fault)

40In < IF <= 64In VK => 30In(RCT + 2RL + Rr) (earth fault)
30
5 <= X/R <= 20 VK => 30In(RCT + RL + Rr) (phase fault)
In < IF <= 40In VK => 17In(RCT + 2RL + Rr) (earth fault)
17
20 <= X/R <= 120 VK => 17In(RCT + RL + Rr) (phase fault)
40In < IF <= 64In VK => 34In(RCT + 2RL + Rr) (earth fault)
34
20 <= X/R <= 120 VK => 34In(RCT + RL + Rr) (phase fault)

where:
● VK = kneepoint voltage
● K = CT dimensioning factor

140 P64-TM-EN-1
P64 Chapter 6 - Transformer Differential Protection

● In = rated current
● RCT = resistance of CT secondary winding
● RL = resistance of a single lead from device to current transformer
● Rr = resistance of any other protection devices sharing the current transformer

● IF = maximum external fault level

6.5.10.2 CT REQUIREMENTS - SMALL BUSBAR APPLICATION


We strongly recommend Class X or Class 5P current transformers for this application.
The current transformer knee-point voltage requirements are based on the following settings:

Parameter Description Value


This sets the minimum differential current threshold required for the transformer differential
Is1 1.2 pu
protection to trip.
This defines the bias current threshold at which the second slope of the bias current
Is2 0.4 pu
characteristic becomes active.
K1 This setting defines the gradient of the first slope in the bias current characteristic. 20%
K2 This setting defines the gradient of the second slope in the bias current characteristic. 80%
This setting defines the first High set threshold on the bias current characteristic. This
Is-HS1 10 pu
setting is only used in advanced mode.
This setting defines the second High set threshold on the bias current characteristic. This
Is-HS2 Disabled
setting is only used in advanced mode.
Transient Bias This setting enables or disables the transient bias factor Enabled
Zero seq filt HV This setting enables or disables zero sequence filtering on the HV winding Disabled
Zero seq filt LV This setting enables or disables zero sequence filtering on the LV winding Disabled
Zero seq filt TV This setting enables or disables zero sequence filtering on the TV winding Disabled
IH2 Diff Set This setting defines the second harmonic blocking threshold. Disabled
CT Saturation This setting enables or disables CT saturation detection. Disabled
No Gap This setting enables or disables CT Gap detection. Disabled
IH5 Diff Set This setting defines the fifth harmonic blocking threshold. Disabled

A series of internal and external faults were simulated to determine the CT requirements for the differential function.
We performed these tests with different X/R ratios, CT burdens, fault currents, fault types and points on the current
waveform.
The system conditions, CT dimensioning factor and CT kneepoint voltage are as follows:

System Conditions K Kneepoint Voltage (VK)


In < IF <= 40In VK => 16In(RCT + 2RL + Rr) (earth fault)
16
5 <= X/R <= 20 VK => 16In(RCT + RL + Rr) (phase fault)
40In < IF <= 64In VK => 30In(RCT + 2RL + Rr) (earth fault)
30
5 <= X/R <= 20 VK => 30In(RCT + RL + Rr) (phase fault)
In < IF <= 40In VK => 21In(RCT + 2RL + Rr) (earth fault)
21
20 <= X/R <= 120 VK => 21In(RCT + RL + Rr) (phase fault)
40In < IF <= 64In VK => 30In(RCT + 2RL + Rr) (earth fault)
30
20 <= X/R <= 120 VK => 30In(RCT + RL + Rr) (phase fault)

P64-TM-EN-1 141
Chapter 6 - Transformer Differential Protection P64

where:
● VK = kneepoint voltage
● K = CT dimensioning factor
● In = rated current
● RCT = resistance of CT secondary winding
● RL = Resistance of a single lead from device to current transformer
● Rr = resistance of any other protection devices sharing the current transformer

● IF = maximum external fault level

142 P64-TM-EN-1
CHAPTER 7

TRANSFORMER CONDITION
MONITORING
Chapter 7 - Transformer Condition Monitoring P64

7.1 CHAPTER OVERVIEW

This chapter contains the following sections:


Chapter Overview 144
Thermal Overload Protection 145
Loss of Life Statistics 152
Through Fault Monitoring 156
RTD Protection 160
CLIO Protection 162

144 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

7.2 THERMAL OVERLOAD PROTECTION


Transformer overheating can be caused due to failures of the cooling system, external faults that are not cleared
promptly, or overload and abnormal system conditions. These abnormal conditions include low frequency, high
voltage, non-sinusoidal load current, or phase-voltage imbalance.
Overheating shortens the life of the transformer insulation in proportion to the duration and magnitude of the high
temperature. If excessive, this may even result in an immediate insulation failure. Overheating can also generate
gases that could result in electrical failure, or cause the transformer coolant to be heated above its flashpoint
temperature, introducing the risk of fire.
Studies suggest that the life of insulation is approximately halved for each 10°C rise in temperature above the rated
value. However, the life of insulation is not wholly dependent on the rise in temperature but on the time the
insulation is subjected to this elevated temperature. Due to the relatively large heat storage capacity of a
transformer, infrequent overloads of short duration may not damage it. However, sustained overloads of a few
percent may result in premature aging and consequent insulation failure.
Transformer thermal overload protection is designed to protect equipment from sustained overload. Thermal
overload protection allows modest but transient overload conditions to occur, while tripping for sustained overloads,
which would not be detected by standard overcurrent protection.

Transformer Losses
The losses in a transformer are shown in the following diagram:

Transformer Losses

Load Losses No Load Losses

Core Losses
Copper Losses Stray Losses Apparent Losses
(Iron Losses)

Eddy-current Losses Hysteresis Losses


V03200

Figure 68: Transformer losses

The flow of the magnetising current through the resistance of the winding creates a real but generally relatively
small I2R loss and voltage drop. The loss that is due to this magnetizing current in the primary winding is called the
apparent loss.
Time-varying fluxes in iron-based materials, cause losses called core losses, or iron losses. These iron losses are
divided into two categories; hysteresis losses and eddy-current losses.
The sum of copper losses and the stray losses is called the load loss. Copper losses are due to the flow of load
currents through the primary and secondary windings. They are equal to I2R, and they heat up the wires and cause
voltage drops. Stray losses are due to the stray capacitance and leakage inductance. Stray capacitance exists
between turns, between one winding and another, and between windings and the core.

P64-TM-EN-1 145
Chapter 7 - Transformer Condition Monitoring P64

7.2.1 THERMAL OVERLOAD IMPLEMENTATION


The thermal overload protection in this device is based on the IEEE Standard C57.91-1995. It provides thermal
overload protection for either an individual winding or the transformer as a whole. The thermal overload protection
settings are in the THERMAL OVERLOAD column.
For individual windings, you set the MonitoredWinding setting to HV, LV, TV accordingly. If you wish to protect
the transformer as a whole set the MonitoredWinding setting to Biased Current, which provides an overall
loading picture of the transformer.
The device provides two 3-stage Definite Time delayed trip elements; one element for Hotspot temperature and one
for Top Oil temperature. Top Oil temperature can be calculated, or measured directly using CLIO or RTD methods,
but Hotspot temperature is always calculated.
A pre-trip alarm can be configured in the tPre-trip Set setting. This alarm indicates that thermal overload will trip
after the set time if the load level remains unchanged.
Four cooling modes are available. You can set the oil exponent constant and winding exponent constant
independently for each mode. You can set the cooling mode automatically in the PSL or manually in the setting file.
For the latter, you will need to configure two opto-inputs as CM Select 1X and CM Select X1, and you must wire the
contacts to energise or de-energise these inputs. The selected cooling mode would then be as follows:

CM Select 1X CM Select X1 Selected Cooling Mode


0 0 1
0 1 2
1 0 3
1 1 4

To calculate the Top Oil and hotspot winding temperature, the device takes into consideration the ratio of the actual
load to the rated load. If the monitored winding is set to HV, LV, or TV, the rated load is determined by the HV
rating, LV rating, or TV rating settings respectively and the Irated setting. If the monitored winding is set as the the
biased current, the rated load is calculated using the Sref power rating setting in the SYSTEM CONFIG column and
the Irated setting in the THERMAL PROTECTION column.
The thermal overload model is executed once every power cycle. The thermal overload trip can be based on either
hot spot temperature or top oil temperature, or both.
The device has up to three hot spot stages and up to three top oil stages. The tripping signal, Top Oil T>x Trip, is
asserted when the top oil (measured or calculated) temperature is above the setting, Top Oil>x Set, and the time
delay, tTop Oil>x Set has elapsed. Also, the tripping signal, Hotspot>x Trip, is asserted when the hottest-spot
(calculated only) temperature is above the setting, Hotspot>x Set, and the time delay, tHotspot>x Set has
elapsed.

7.2.1.1 THERMAL OVERLOAD BIAS CURRENT


The biased current used by the thermal protection is not the same as the biased current used by the differential
protection. No vector correction or zero sequence filtering is performed. To calculate the bias current, the thermal
element considers the maximum RMS current on a per winding basis. Note that the bias current calculation
performed by the thermal element is not on a per-phase basis. The thermal bias current calculation is as follows:

Max [ I HVArms , I HVBrms , I HVCrms ] Max [ I LVArms , I LVBrms , I LVCrms ] Max [ ITVArms , ITVBrms , ITVCrms ]
+ +
HV _ FLCSref LV _ FLCSref TV _ FLCSref
I bias =
2

146 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

where:
● HV_FLCSref = HV full load current at the reference power
● LV_FLCSref = LV full load current at the reference power
● TV_FLCSref = TV full load current at the reference power

7.2.2 THE THERMAL MODEL


The simplest implementation of overload protection employs an I2t characteristic. You set time constants such as
the winding time constant at Hotspot location and top oil rise time constant, so that the thermal model can follow the
correct exponential heating and cooling profile. Transformer loads are becoming increasingly non-linear; therefore
the device uses true RMS current values to replicate the winding Hotspot temperature.

Note:
"True RMS" refers to the RMS value of a non-sinusoidal waveform including the fundamental and all other components.

7.2.2.1 TOP OIL TEMPERATURE CACULATIONS


If the Top Oil temperature is not available as a measured input quantity, it is calculated every cycle by the following
equation:
QTO = QA + DQTO
where:
● QTO = Top Oil temperature
● QA = Ambient temperature
● DQTO = Top Oil rise over ambient temperature due to a step load change

You can either measure the ambient temperature directly, or set it in the Ambient T setting. The ultimate top oil rise
is given by the following equation:
n
 K 2 R + 1
∆ΘTO ,U = ∆ΘTO , R ⋅  u 
 R +1 
where:
Ku = the ratio of actual load to rated load
R = the ratio of the load loss at rated load to no load loss (Rated NoLoadLoss setting)
n = Oil exponent (Oil exp n setting)
QTO,R = Top Oil rise over ambient temperature at rated load (Top Oil Overamb setting)
The load current used in the calculations is the RMS value.

7.2.2.2 HOTSPOT CACULATIONS


The Hotspot temperature can only be obtained by calculation. The following equation is used to calculate the hot
spot temperature every cycle:
QH = QTO + DQH

P64-TM-EN-1 147
Chapter 7 - Transformer Condition Monitoring P64

where:
● QH = Hotspot (winding) temperature
● QTO = Top Oil temperature
● DQH = Hotspot rise above top oil temperature

The ultimate Hotspot rise over top oil is given by:

DQH,U = DQH,R . KU2m


where:
● DQH,R = winding hottest spot rise over top oil temperature at rated load. This parameter is set by the user
● KU = the ratio of actual load to rated load
● m = winding exponent (Winding exp m setting)

7.2.2.3 THERMAL STATE MEASUREMENT


DHot spot temperature, Top oil temperature and ambient temperature are stored in non-volatile memory. These
measurements are updated every power cycle. The thermal state can be reset to zero by any of the following:
● The Reset Thermal cell under the MEASUREMENTS 3 column on the front panel
● A remote communications interface command
● A status input state change.

The top oil temperature, hot spot temperature, ambient temperature and pre-trip time left are available as a
measured value in the MEASUREMENT 3 column.
If you need a more accurate representation of the transformer thermal state, you can use temperature monitoring
devices (RTDs or CLIO), which target specific areas. For short period overloads, RTD, CLIO and overcurrent
protection techniques provide better protection.
The PSL provides a signal indicating that the transformer is de-energised (TFR De-energised). This signal is
asserted when all the circuit breakers are open. In this case, the transformer no-load losses are not considered. As
a result, the top oil and hottest spot temperatures are equal to the ambient temperature when the monitored current
is zero. If this signal is removed, the top oil and hottest spot temperatures are not equal to the ambient temperature
even when the monitored current is zero. In this case the top oil and hottest spot temperatures will increase
according to the described equations.

7.2.3 APPLICATION NOTES

7.2.3.1 RECOMMENDATIONS

Monitored Winding
You can set the monitored winding to HV, LV, TV or Biased Current. We recommend setting it to Biased
Current to provide an overall thermal condition for the transformer.

Ambient Temperature
Ambient temperature is an important factor when determining the load capability of a transformer, because you add
it to the temperature rise due to loading to determine the operating temperature. IEEE C57.91-1995 states that
transformer ratings are based on an average ambient temperature of 30°C.
The Ambient T Source setting defines whether the ambient temperature should be set to an average level or
measured directly using a CLI or RTD input. When measuring the ambient temperature, it should be averaged over
a 24-hour period.

148 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

Top Oil Temperature


The Top Oil T source setting defines whether the Top Oil temperature is calculated or measured.
We recommend setting the rated load (Rated Current) to 1.0 pu.

7.2.3.2 IEEE RECOMMENDATIONS

Winding Exponent
IEEE C57.91-1995 suggests the following winding and oil exponents.

Type of Cooling m (Winding Exponent) n (Oil Exponent)


OA 0.8 0.8
FA 0.8 0.9
Non-directed FOA or FOW 0.8 0.9
Directed FOA or FOW 1.0 1.0

The cooling mechanisms are:


●OA (Oil/Air): The cooling system transfers heat using oil or air without using pumps or fans.
●FA (Forced Air): The cooling is aided by fans, without any pumps to circulate the oil.
●FOA (Forced Oil and Air): The cooling system uses both pumps and fans to cool the winding.
●FOW (Forced Oil and Water): The heat exchanger is water-cooled and does not have the typical radiator
configuration. The cooler is normally a chamber with many tubes inside where the oil and water exchange
heat energy. In non-directed flow transformers, the pumped oil flows freely through the tank. In directed flow
transformers, the pumped oil is forced to flow through the windings.
The exponents are empirically derived and are required to calculate the variation of DQH and DQTO with load
changes. The value of m has been selected for each mode of cooling to approximately account for effects of
changes in resistance and viscosity with changes in load. The value of n has been selected for each mode of
cooling to approximately account for effects of change in resistance with change in load.

Oil Time Constant


When setting the Hotspot and Top Oil stages take into consideration the suggested temperature limits (IEEE Std.
C57.91-1995):

Suggested Limits of Temperature for Loading Above Nameplate Distribution Transformers with 65°C Rise
Top Oil temperature 120°C
Hotspot conductor temperature 200°C

Suggested Limits of Temperature for Loading Above Nameplate Power Transformers with 65°C Rise
Top Oil temperature 110°C
Hotspot conductor temperature 180°C

7.2.3.3 DATA PROVIDED BY TRANSFORMER MANUFACTURERS


The transformer manufacturer should provide information pertaining to the following parameters:
Rated NoLoadLoss: The ratio of load loss at rated load to no load loss.
Hot Spot Overtop: Winding hottest-spot rise over Top Oil at rated load
Top Oil overamb: Top Oil rise over ambient temperature at rated load

P64-TM-EN-1 149
Chapter 7 - Transformer Condition Monitoring P64

Winding exp m: Winding exponent


Oil exp n: Oil exponent
HotSpotRiseConst: Winding time constant at Hotspot location (this may also be estimated from the resistance
cooling curve during thermal tests)
TopOilRiseConst (Oil time constant)
The following tables are examples of the thermal data provided by the transformer manufacturer:

Thermal Characteristics for a 735 MVA 300 kV +7% to -18% / 23 kV ODWF Cooled Generator Transformer
Specification Value
No load losses (core losses) 340 kW
Load losses at nominal tap 1580 kW
Load losses at maximum current tap 1963 kW
Oil time constant 2.15 hr
Oil exponent 1.0
Top Oil rise over ambient temperature at rated load 33.4 K
Winding time constant at Hotspot location 14 mins
Winding hottest spot rise over Top Oil temperature at rated load 30.2 K
Winding exponent 2.0

Note:
OD (oil directed) indicates that oil from heat exchangers (radiators) is forced through the windings. WF (Water Forced) states
that the oil is externally cooled by pumped water.

Thermal Characteristics for a 600 MVA 432/23.5 kV ODWF Cooled Generator Transformer
Specification Value
No load losses (core losses) 237 kW
Load losses at nominal tap 1423 kW
Load losses at maximum current tap 1676 kW
Oil time constant 2.2 hr
Oil exponent 1.0
Top Oil rise over ambient temperature at rated load 46.6 K
Winding time constant at Hotspot location 9 mins
Winding hottest spot rise over Top Oil temperature at rated load 33.1K
Winding exponent 2.0

Thermal Characteristics for IEC 60354 Figures Based on Medium-Large Power Transformers OD Cooled
Specification Value
Oil time constant 1.5 hr
Oil exponent 1.0
Top Oil rise over ambient temperature at rated load 49 K

150 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

Thermal Characteristics for IEC 60354 Figures Based on Medium-Large Power Transformers OD Cooled
Specification Value
Winding time constant at Hotspot location 5-10 mins
Winding hottest spot rise over Top Oil temperature at rated load 29 K
Winding exponent 2.0

P64-TM-EN-1 151
Chapter 7 - Transformer Condition Monitoring P64

7.3 LOSS OF LIFE STATISTICS


Deterioration of transformer insulation is a time dependent function of temperature, moisture and oxygen content.
The effects of moisture and oxygen can be minimized through designing in preservation systems for most modern
transformers, therefore it is temperature that is the main reason for transformer aging. Frequent overloading will
shorten the life expectancy of a transformer due to the elevated winding temperatures.
Insulation deterioration is not uniform and will be more pronounced at Hotspots within the transformer tank.
Therefore any asset management system intending to model the rate of deterioration is based on simulated real-
time Hotspot temperature algorithms. These models may take ambient temperature, Top Oil temperature, load
current, oil pump status (pumping or not), and radiator fan status (blowing or not).
Alstom transformer protection devices provide such a loss of life monitoring facility in accordance with the thermal
model defined in IEEE C57.91. The protection algorithm determines the current rate of life-loss, and uses that
information to indicate the likely remaining service time. The asset owner can be alerted in advance, so that he can
plan an outage in which to carry out the required maintenance such as reconditioning or rewinding.

7.3.1 LOSS OF LIFE IMPLEMENTATION


Loss of life settings are found in the THERMAL OVERLOAD column of the required setting group.
The device provides two single-stage definite time delay alarms based on aging acceleration factor (FAA) or loss of
life (LOL).
A reset command is provided to allow you to reset the calculated parameters displayed in the MEASUREMENTS 3
column: Loss of Life status (LOL status), Loss of Life aging factor (LOL Aging Factor), mean aging factor
(FAA,m), rate of loss of life (Rate of LOL), residual life at mean aging factor (Lres at FAA,m), and residual life at
designed (Lres at designed).
The loss of life model is executed once every power cycle.

7.3.1.1 LOSS OF LIFE CALCULATIONS


IEEE C57.91-1995 defines the aging acceleration factor as the rate at which transformer insulation aging for a given
maximum Hotspot temperature is accelerated compared with the aging rate at a reference maximum Hotspot
temperature. For transformers with average winding temperature rise of 65°C, the reference maximum Hotspot
temperature is 110°C. For transformers with average winding temperature rise of 55°C, the reference maximum
Hotspot temperature is 95°C. For maximum Hotspot temperatures in excess of the reference maximum Hotspot
temperature, the aging acceleration factor is greater than 1. For maximum Hotspot temperatures lower than the
reference maximum Hotspot temperature, the aging acceleration factor is less than 1.
The model used for loss of life statistics is given by the equations for LOL and FAA. LOL is calculated every hour
according to the following formula:
LOL = L(QH,r) - Lres(QH,r)
where:
● L(QH,r) = life hours at reference winding hottest-spot temperature (Life Hours at HS setting)
● Lres(QH,r) = residual life hours at reference winding hottest-spot temperature
The aging acceleration factor FAA is calculated once every cycle as follows:
 B 
 A+   B B 
Θ + 273
L ( Θ H ,r ) e  H ,r  
Θ
 H ,r + 273

Θ H + 273


FAA = = B
=e
L ( ΘH ) 
 A+


 Θ H + 273 
e
If a 65°C average winding rise transformer is considered, the equation for FAA is as follows:

152 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

 B B 
 − 
 383 Θ H + 273 
FAA = e

If a 55°C average winding rise transformer is considered, the equation for FAA is as follows:
 B B 
 − 
 368 Θ H + 273 
FAA = e

where:
● L(QH) = life hours at winding hottest-spot temperature
● QH,r = hottest-spot temperature at rated load
● B = constant B from life expectancy curve. This parameter is set by the user. IEEE Std. C57.91-1995
recommends a B value of 15000.

The residual life hours at reference hottest-spot temperature is updated every hour as follows:
3600

∑F i =1
AA,i (Θ H )
Lres (Θ H , r ) = Lres , p (Θ H , r ) −
3600
where:
● Lres,p(QH,r) = residual life hours at reference temperature one hour ago
● FAA,i(QH) = mean aging acceleration factor, as calculated above (calculated every second)

The accumulated loss of life is updated in non-volatile memory once per hour. It is possible to reset this to a new
value if required; for example if the device is applied in a new location with a pre-aged resident transformer.
The rate of loss of life (ROLOL) in percentage per day is as follows. It is updated every day:

24
ROLOL = ⋅ FAA, m (Θ H ) ⋅100%
L (Θ H , r )

The mean aging acceleration factor, FAA,m, is as follows. It is updated every day:
N N
∑ FAAn ⋅ ∆tn ∑ FAAn
n =1 n =1
FAA, m = N
=
∑ ∆tn N
n =1

where:
● FAA,n is calculated every power cycle
● Dtn = 1 cycle
● FAA,m states the latest one-day statistics of FAA. When the device is energized for the first time, FAA,m default
value is 1.

The residual life in hours at FAA,m is as follows. It is updated every day:

Lres (Θ H , r )
Lres ( FAA,m ) =
FAA, m

P64-TM-EN-1 153
Chapter 7 - Transformer Condition Monitoring P64

7.3.2 APPLICATION NOTES

7.3.2.1 LOL SETTING GUIDELINES


Set the life hours at the reference maximum Hotspot temperature. According to IEEE Std. C57.91-1995, the normal
insulation life at the reference temperature in hours or years must be user-defined. The following table extracted
from IEEE Std. C57.91-1995 gives values of normal insulation life for a well-dried, oxygen-free 65°C average
winding temperature rise insulation system at the reference temperature of 110°C.
Normal Insulation life Normal Insulation Life
Basis
Hours Years
50% retained tensile strength of insulation (former IEEE Std C57.92-1981
65000 7.42
criterion)
25% retained tensile strength of insulation 135000 15.41
200 retained degree of polymerization in insulation 150000 17.12
Interpretation of distribution transformer functional life test data (former
180000 20.55
IEEE Std. C57.91-1981)

Note:
Tensile strength or degree of polymerization (D.P.) retention values were determined by sealed tube aging on well-dried
insulation samples in oxygen-free oil.
Refer to I.2 in annex I of the IEEE Std. C57.91-1995 for discussion of the effect of higher values of water and oxygen and also
for the discussion on the basis given above.

You should set the designed Hotspot temperature setting (Designed HS temp) to 110°C if the transformer is rated
65°C average winding rise. If the transformer is rated 55°C average winding rise, set it to 95°C.
As recommended by IEEE C57.91-1995, set the Constant B Set setting to 5000.
If the calculated aging acceleration factor is greater than the setting FAA> Set and the time delay tFAA> Set has
elapsed, the FAA alarm DDB signal is activated.
If the calculated loss of life is greater than the setting LOL>1 Set and the time delay tLOL> Set has elapsed, the
LOL alarm DDB signal is activated.

7.3.2.2 EXAMPLE
Consider a new 65°C average winding rise rated transformer whose life hours figure at designed maximum Hotspot
temperature is 180,000 hrs. As a result, you set the Life Hours at HS setting to 180,000, and the Designed HS
temp setting to 110.0°C. Set Constant B Set to 15,000 as recommended by IEEE. The aging acceleration factor
takes into consideration the constant B and the hottest spot temperature calculated by the thermal function. For a
distribution transformer, IEEE suggests 200°C as the limit for the maximum hot spot temperature. The aging
acceleration factor alarm will be asserted when 70% of the 200°C has been reached. The aging acceleration factor
is calculated as follows:
 B B   B B 
 −   −
 383 hottest − spot −tempt + 273  0.7×200 + 273 
FAA = e = e  383 = 17.2
Therefore:
FAA>set should be set to 17.2. tFAA> Set may be set to 10.00 min. LOL>1 Set may be set to 115,000 hrs, if
it is considered that the transformer has 65,000 hrs left (Life Hours at HS – hours left = 180,000 – 65,000 = 115,000
hrs). tLOL> Set may be set to 10.00 min. Finally, the Reset Life Hours setting determines the value of the LOL
measurement once the Reset LOL command is executed. The default value is zero because considering a new
transformer, after testing the thermal function the LOL measurement should be reset to zero.

154 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

You should perform certain tests to determine the age of an old transformer. Please obtain advice from the
transformer manufacturer.

P64-TM-EN-1 155
Chapter 7 - Transformer Condition Monitoring P64

7.4 THROUGH FAULT MONITORING


Through faults are a major cause of transformer damage and failure, as they can stress the insulation and
mechanical integrity of the transformer. Through-fault monitoring is usually used to tackle this problem. This
mechanism monitors fault currents passing through the transformer, which may significantly exceed its rated
current. The through-fault monitoring mechanism is based on an I2t calculation.
According to IEEE C57.109-1993(R2008), mechanical effects are more significant than thermal effects for fault-
current magnitudes near the design capability of the transformer. However, at fault-current magnitudes close to the
overload range, mechanical effects are less important unless the frequency of fault occurrence is high. Note that
mechanical effects are more important in large kVA transformers. The standard states that the maximum duration
limit for the worst case of mechanical duty is 2 s.
The standard defines the following transformer categories:

Category Single Phase (kVA) Three-Phase (kVA)


I 5 to 500 15 to 500
II 501 to 1667 501 to 5000
III 1668 to 10000 5001 to 30000
IV Above 10000 Above 30000

Categories I and II consider only the transformer short-circuit impedance, whereas categories III and IV consider the
system short-circuit impedance at the transformer location as well as transformer short-circuit impedance. The
short-circuit impedance is expressed as a percentage of the transformer rated voltage and the rated power of the
transformer.

7.4.1 THROUGH FAULT MONITORING IMPLEMENTATION


Through-fault monitoring can be enabled with the Through Fault setting in the TF MONITORING column.
The through-fault current monitoring function monitors the fault current level, the duration of the faulty condition and
the date and time for each through-fault. An I2t calculation based on the recorded time duration and maximum
current is performed for each phase.
This calculation is only performed when the current exceeds the TF I> Trigger setting and if the DDB signal Any
Diff Start is NOT asserted. Cumulative stored calculations for each phase are monitored so you can schedule the
transformer maintenance based on this data.

A single-stage alarm is available for through-fault monitoring. The alarm is issued if the maximum cumulative I2t in
the three phases exceeds the TF I2t> Alarm setting. A through fault event is recorded if any of the phase currents
is larger than the TF I> Trigger setting. You should always set TF I> Trigger greater than the overload capability of
the transformer.

156 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

7.4.2 THROUGH FAULT MONITORING LOGIC


IA magn itude

TF I > Trigger
&
IA2t 1
& Throu fa ult Alm
TF I 2t> Alarm

TF Recorder trig
IB magn itude

TF I > Trigger
&
IB2t

TF I 2t> Alarm

IC magnitude

TF I > Trigger
&
IC2t

TF I 2t> Alarm

Any Diff Start

V03201

Figure 69: Through-fault alarm logic

7.4.3 APPLICATION NOTES

7.4.3.1 TFM SETTING GUIDELINES


According to IEEE Std. C57.109-1993, values of 3.5 x normal base current may result from overloads rather than
faults. According to IEEE C57.91-1995, the suggested load limits depend on the type of transformer and are as
follows:
● For distribution transformers: Loads above the nameplate specification with 65°C rise is 300% of rated load
during short-time loading (0.5 hours or less).
For power transformers: Loads above the nameplate specification with 55°C rise is 200% of rated load.
To set TF I2t> Alarm you should consider the recommendations given in IEEE Std. C57.109-1993 for transformers
built from the early 1970s onwards. For transformers built before this time, always consult the transformer
manufacturer concerning the short circuit withstand capabilities.

Example
The through fault monitoring element can monitor either the HV, the LV or the TV winding. In three winding
applications, you should monitor the winding through which the highest current would flow during an external fault.
Fault studies are required to determine the maximum through fault current and which winding carries the most
current. For example, consider the following autotransformer:

P64-TM-EN-1 157
Chapter 7 - Transformer Condition Monitoring P64

175/175/30 MVA
230/115/13.8 kV
YNynd1
+5% / -15% TV
800:5 19 taps 2000:5
HV
a
A
b
B
c
C

Earthing
Protected zone transformer

c
LV
1200:5

B B

Phase & amplitude Phase & amplitude


Correction Correction
B B
+ +
Zero sequence filtering Zero sequence filtering
B B

Phase & amplitude


Correction
B
+
Zero sequence filtering
B

D D D

P645

V03116

Figure 70: P645 used to protect an autotransformer with loaded delta winding

Consider the case where an equivalent source and load are connected to the 230 kV terminal and an equivalent
source and load are connected to the 115 kV terminal, but only the load is connected to the 13.8 kV terminal. An
external fault on the 230 kV side would be fed by the source on the 115 kV side. Therefore, the current would
mainly flow from the 115 kV side to the 230 kV side. If the external fault occurs on the 115 kV side, the through-fault
current would flow from the 230 kV side to the 115 kV side. If an external fault occurs on the 13.8 kV side, the
through fault current would flow from the 230 kV and 115 kV sides to the 13.8 kV side. The source and transformer
impedances determine the fault current level.
Set the TF I> Trigger setting above the maximum overload. According to IEEE Std. C57.109-1993, values of 3.5 or
less times normal base current may result from overloads instead of faults. TF I> Trigger may be set to 3.85 pu. If
the monitored current is above this level and no differential element has started, then the I2t is calculated.
To set the TF I2t> Alarm consider the maximum through fault current and the maximum time duration. The
maximum through-fault current may be determined as 1/X, where X is the transformer impedance. This

158 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

approximation is valid when the source is strong, so that its impedance is small compared with the transformer
impedance. If the transformer has an impedance of 10%, the maximum through fault current is calculated as:
1/X = 1/0.1 = 10 pu

P64-TM-EN-1 159
Chapter 7 - Transformer Condition Monitoring P64

7.5 RTD PROTECTION


Prolonged overloading of transformers may cause their windings to overheat, resulting in premature aging of the
insulation, or in extreme cases, insulation failure. To protect against this, resistive temperature sensing devices
(RTDs) can be used to measure temperatures at various locations within a transformer. RTDs work by using the
resistance versus temperature characteristic of metals. When metal heats up, its resistance changes. This can be
used to feed back temperature information, which can be used by protection devices for temperature monitoring,
alarming, or making protection decisions.
Probes are usually placed in areas of the equipment that are susceptible to overheating or heat damage. This could
protect against winding Hotspot overheating or overtemperature in the insulating oil.
Direct temperature measurement can provide more reliable thermal protection than thermal model calculations.

Note:
Do Not select RTD options if RTD board is not fitted.

7.5.1 RTD PROTECTION IMPLEMENTATION


The P64 uses PT100 RTD probes to protect against any general or localized overheating. These can measure
temperatures between –40° and +300°C. At 0°C they have a resistance of 100 Ohms.
The device accepts inputs from up to ten 2-wire or 3-wire PT100 resistive temperature sensing devices (RTD).
These are connected as shown:

RTD 1 RTD 1

3-wire PT100 RTDs 2-wire PT100 RTDs

RTD 10 RTD 10
IED IED
V03202

Figure 71: Connection for RTD thermal probes

You can enable or disable each RTD using the Select RTD setting in the RTD PROTECTION column of the
relevant settings group. The setting contains a binary string of ten digits to represent the 10 RTDs in sequence from
right to left. For example if you set Select RTD to 0000000111, RTD1, RTD2 and RTD3 would be enabled and the
associated settings would be visible in the menu.
You set the temperature setting for the alarm stage for each RTD in the RTD Alarm Set cells and the alarm stage
time delay in the RTD Alarm Dly cells.
Likewise, you set the trip stage for each RTD in the RTD Trip Set cells and the trip stage time delay in the RTD Trip
Dly cells.
Should the measured resistance of an RTD be outside of the permitted range, an RTD failure alarm is raised,
indicating an open or short circuit RTD input. These conditions are signalled by the DDB signals RTD Open Cct,
RTD Short Cct and RTD Data Error. These DDB statuses are also shown in the MEASUREMENTS 3 column.
DDB signals are also available to indicate the alarm and trip of the each and any RTD. You can set the monitor bit
cells in the COMMISSION TESTS column to view the statuses of these signals.

160 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

7.5.2 RTD LOGIC


RTD Value

RTD Alarm Set & RTD 1 Alarm

RTD 1 Alarm
RTD Open Cct

RTD Short Cct


& Any RTD Alarm
RTD Data Error

RTD Board Fail RTD 10 A larm

RTD Value

RTD Trip Set & RTD 1 Trip

RTD 1 Trip
RTD Open Cct

RTD Short Cct


& Any RTD Trip
RTD Data Error

RTD Board Fail RTD 10 Trip

Note: This diagram does not show all stages. Other stages follow similar principles.

V03203

Figure 72: RTD logic

7.5.3 APPLICATION NOTES

7.5.3.1 SETTING GUIDELINES FOR RTD PROTECTION


The following table shows typical operating temperatures for protected plant. These are for guidance only. You must
obtain the actual figures from the equipment manufacturers:

Parameter Typical Service Temperature Short Term Overloading at Full Load


60° - 80°C, depending on the type of
Bearing temperature generators 60 - 80°C+
bearing.
A temperature gradient from winding
temperature is usually assumed, so that
Top oil temperature of transformers 80°C (50 - 60°C above ambient).
top oil RTDs can provide winding
protection
Winding hot spot temperature 98°C for normal aging of insulation. 140°C+ during emergencies

P64-TM-EN-1 161
Chapter 7 - Transformer Condition Monitoring P64

7.6 CLIO PROTECTION


To help with monitoring the condition of a power systems, various transducers such as vibration monitors,
tachometers, voltage, current and pressure transducers can be used to extract useful metrics from the system.
Such transducers work by converting the measured data into currents, which can then be fed into instrumentation
device such as meters or IEDs. This mechanism is called CLIO protection. CLIO stands for Current Loop Input
Output.
Transducers have current ranges associated with the full scale of what they are measuring. Typically these ranges
are 0-1 mA, 0-10 mA, 0-20 mA, or 4-20 mA.

Note:
Do Not select CLIO options if CLIO board is not fitted.

7.6.1 CURRENT LOOP INPUT IMPLEMENTATION


Four analog current loop inputs are provided for transducers with ranges of 0 – 1 mA, 0 – 10 mA, 0 – 20 mA, or 4 –
20 mA. Each input can be configured to accept any one of these ranges. Associated with each input are two
protection stages; one for alarming and the other for tripping. Each stage can be individually enabled or disabled
and each stage has a definite time delay setting.
Each current loop input may beset to alarm for an 'over' condition or an 'under' condition. You do this with the setting
CLI Alarm Fn and selecting under or over as appropriate. Likewise, each CL input may be also set to trip for an
'over' condition or an 'under' condition. You do this with the setting CLI Trip Fn and selecting under or over as
appropriate. The sample interval is nominally 50 ms per input.
The relationship between the transducer measuring range and the current input range is linear. The maximum and
minimum settings correspond to the limits of the current input range. This relationship is shown below. The diagram
also shows the relationship between the measured current and the analog to digital conversion (ADC) count. The
hardware design allows for over-ranging, with the maximum ADC count corresponding to 1.0836 mA for the 0 -
1 mA range, and 22.7556 mA for the 0 - 10 mA, 0 - 20 mA and 4 - 20 mA ranges. The device will therefore continue
to measure and display values beyond the Maximum setting, within its numbering capability.

162 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

Transducer Value Transducer Value


Maximum

Maximum

ADC ADC
Minimum Count Minimum Count
4095 4095
0 0
0 mA 1 mA Current I/P 0 mA 10 mA Current I/P
0 - 1 mA 0 - 10 mA
1.0836 mA 22.7556 mA

Transducer Value Transducer Value


Maximum Maximum

Minimum
ADC ADC
Minimum Count Count
4095 4095
0 0
0 mA 20 mA Current I/P 0 mA 4 mA 20 mA Current I/P
0 - 20 mA 4 - 20 mA 22.7556 mA
22.7556 mA

E03204

Figure 73: Current loop input ranges

Note:
If the Maximum is set less than the Minimum, the slopes of the graphs will be negative.

Power-on diagnostics and continuous self-checking of the current loop inputs are integrated into the hardware.
When a failure is detected, the protection associated with all the current loop inputs is disabled and a single alarm
DDB signal (CL Card I/P Fail) is set and an alarm is raised. A maintenance record with an error code is also
recorded with additional details about the type of failure.
For the 4 – 20 mA input range, a current level below 4 mA indicates that there is a fault with the transducer or the
wiring. An instantaneous undercurrent alarm element is available, with a setting range from 0 to 4 mA. This element
controls a DDB output signal for each CL input (CL(n)I< Fail Alm), where (n) is the number of the CL input. You can
then map this to a user defined alarm if required.
Hysteresis is implemented for each protection element. For ‘Over’ protection, the drop-off/pick-up ratio is 95%, for
‘Under’ protection, the ratio is 105%.
A timer block input is available for each current loop input stage. This will reset the CL input timers of the relevant
stage if energized. If a current loop input is blocked, the protection and alarm timer stages and the 4 – 20 mA
undercurrent alarm associated with that input are blocked. The blocking signals may be useful for blocking the
current loop inputs when the CB is open for example.
DDB signals are available for each current loop input to indicate the start of alarm and trip stages. These are CLI(n)
Alarm Start, and CLI(n) Trip Start, CLI(n) Alarm and CLI(n) Trip, where (n) is the number of the current loop
input. The Monitor Bit cells of the COMMISSIONTESTS column can be configured to show the state of the DDB
signals.

P64-TM-EN-1 163
Chapter 7 - Transformer Condition Monitoring P64

The current loop input starts are mapped internally to the Any Start DDB signal.

7.6.2 CURRENT LOOP INPUT LOGIC


RTD Value
CLI1 Alarm S tart

RTD Alarm Set & CLI1 Alarm

CLI1 I< Fail A lm


4-20 mA input only
CLI Alarm Delay
CL Card I/P Fail

RTD Value
CLI1 Trip Start

RTD Trip Set & CLI1 Trip

CLI1 I< Fail A lm


4-20 mA input only
CLI Alarm Delay
CL Card I/P Fail

V3205 Note: This diagram does not show all stages. Other stages follow similar principles.

Figure 74: Current Loop Input logic

7.6.3 CLO IMPLEMENTATION


Four analog current outputs are provided with ranges of 0 - 1 mA, 0 - 10 mA, 0 - 20 mA or 4 - 20 mA, which can
alleviate the need for separate transducers. These may be used to feed moving coil ammeters for measuring
analog quantities, or to feed into a SCADA using an existing analog remote terminal unit (RTU).
The current loop output conversion task runs every 50 ms and the refresh interval for the output measurements is
nominally 50 ms.
You can set the measuring range for each analog output. The range limits are defined by the CLO Minimum and
CLO Maximum settings in the CLIO PROTECTION column for each CL output. This allows you to zoom in and
monitor a restricted range of the measurements with the desired resolution. You can set the voltage and current
quantities to either primary or secondary quantities with the CLO Set Values setting.
The output current of each analog output is linearly scaled to its range limits by the Maximum and Minimum
settings, as shown below:

164 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

Current Output Current Output

1 mA 10 mA

Relay Relay
Measurement Measurement
0 mA 0 mA
Minimum Maximum Minimum Maximum
0 - 1 mA 0 - 10 mA

Minimum

Current Output Current Output

20 mA 20 mA

4 mA
Relay Relay
Measurement 0 mA Measurement
0 mA
Minimum Maximum Minimum Maximum
0 - 20 mA 4 - 20 mA

E03206

Figure 75: Current Loop Output ranges

Note:
If the Maximum is set less than the Minimum, the slopes of the graphs will be negative.

The transducers inside the device are of the current output type. This means that the correct value of output is
always maintained over the load range specified. The range of load resistance varies a great deal, depending on
the design and the value of output current. Transducers with a full-scale output of 10 mA will normally feed any load
up to a value of 1000 ohms (compliance voltage 10V). This equates to an approximate cable length of 15 km. We
recommend using a screened cable, earthed at one end. This helps reduce interference on the output current
signal. The table below shows typical cable impedances per kilometer for common cables. The compliance voltage
dictates the maximum load that a transducer output can feed. Therefore, the 20 mA output will be restricted to a
maximum load of 500 ohms.

Cable 1/0.6 mm 1/0.85 mm 1/1.38 mm


CSA (mm2) 0.28 0.57 1.50
R (ohms/km) 65.52 32.65 12.38

You can connect the receiving equipment at any point in the output loop and install additional equipment later. You
do not need to adjust the transducer output, providing the compliance voltage is not exceeded.
Where you use the output current range for control purposes, you may wish to fit appropriately rated diodes, or
Zener diodes, across the terminals of each of the units in the series loop. This will guard against the possibility of
their internal circuitry becoming open circuit. In this way, a faulty unit in the loop does not cause all the indications to

P64-TM-EN-1 165
Chapter 7 - Transformer Condition Monitoring P64

disappear, because the constant current nature of the transducer output simply raises the voltage and continues to
force the correct output signal around the loop.
The device provides power-on diagnostics and continuous self-checking of the current loop hardware. If a failure is
detected, all the current loop output functions are disabled and an alarm signal (CL Card O/P Fail) is raised. A
maintenance record (with an error code) is also produced, which provides additional details about the type of failure.

7.6.4 APPLICATION NOTES

7.6.4.1 CLI SETTING GUIDELINES


For each analog input, you can define the following:
● The current input range: 0 – 1 mA, 0 – 10 mA, 0 – 20 mA, 4 – 20 mA
● The analog input function (in the form of a 16-character input label)
● Analog input minimum value
● Analog input maximum value
● Alarm threshold, range within the maximum and minimum set values
● Alarm function (under or over)
● Alarm delay
● Trip threshold, range within maximum and minimum set values
● Trip function (under or over)
● Trip delay

The Maximum and Minimum settings allow you to enter the range of physical or electrical quantities measured by
the transducer. These are without units, however, you can enter the transducer function and the unit of the
measurement using the 16-character user-defined CL Input Label. For example, if using an input to monitor a power
measuring transducer, the text could be “Active Power (MW)”.
You need to set the alarm and trip thresholds within the range of physical or electrical quantities. The device will
convert the current input value into its corresponding transducer measuring value for the protection calculation.
For example if the CL input minimum is -1000 and the CL input maximum is 1000 for a 0 to 10 mA input, an input
current of 10 mA is equivalent to a measurement value of 1000, 5 mA is 0, and 0 mA is -1000.
These values are available for display in the CLIO Input (n) cells in the MEASUREMENTS 3 menu. The top line
shows the CL Input Label and the bottom line shows the measurement value.

7.6.4.2 CLO SETTING GUIDELINES


The outputs can be assigned to any of the following relay measurements:
● Magnitudes of IA, IB, IC of every CT input
● Magnitudes of IA, IB, IC at HV, LV and TV sides of the transformer
● Magnitudes of IN Measured and IN Derived of every winding
● Magnitudes of I1, I2, I0 at HV, LV and TV sides of the transformer
● Magnitudes of VAB, VBC, VCA, VAN, VBN, VCN, VN Measured, VN Derived
● Magnitude of Vx
● VAN RMS, VBN RMS, VCN RMS
● Frequency
● CL Inputs 1-4
● RTD 1-10

166 P64-TM-EN-1
P64 Chapter 7 - Transformer Condition Monitoring

The relationship of the output current to the value of the measured values is of vital importance and needs careful
consideration. Any receiving equipment must be used within its rating but, if possible, you should apply some kind
of standard.
One of the objectives is to monitor the voltage over a range of values, so you need an upper limit, for example
120%. However, this may lead to difficulties when it comes to scaling an instrument.
The same considerations apply to current transducer outputs and with added complexity to power transducers
outputs, where both the voltage and current transformer ratios must be taken into account.
Some of these difficulties do not need to be considered if the transducer is only feeding, for example, a SCADA
outstation. Any equipment, which can be programmed to apply a scaling factor to individual inputs can
accommodate most signals. The main consideration is to ensure that the transducer is capable of providing a signal
right up to the full-scale value of the input.

P64-TM-EN-1 167
Chapter 7 - Transformer Condition Monitoring P64

168 P64-TM-EN-1
CHAPTER 8

RESTRICTED EARTH FAULT


PROTECTION
Chapter 8 - Restricted Earth Fault Protection P64

8.1 CHAPTER OVERVIEW


The device provides extensive Restricted Earth Fault functionality. This chapter describes the operation of this
function including the principles of operation, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 170
REF Protection Principles 171
Restricted Earth Fault Protection Implementation 177
Second Harmonic Blocking 183
Application Notes 184

170 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

8.2 REF PROTECTION PRINCIPLES


Winding-to-core faults in a transformer can be caused by insulation breakdown. Such faults can have very low fault
currents, but they still need to be picked up. If such faults are not identified, this could result in extreme damage to
very expensive equipment.
Often the associated fault currents are lower than the nominal load current. Neither overcurrent nor percentage
differential protection is sufficiently sensitive in this case. We therefore require a different type of protection
arrangement. Not only should the protection arrangement be sensitive, but it must create a protection zone, which is
limited to each transformer winding. Restricted Earth Fault protection (REF) is the protection mechanism used to
protect individual transformer winding sets.
The following figure shows a REF protection arrangement for protecting the delta side of a delta-star transformer.

Load

REF
IED protection zone

V00620

Figure 76: REF protection for delta side

The current transformers measuring the currents in each phase are connected in parallel. The currents from all
three phases are summed to form a differential current, sometimes known as a spill current. Under normal
operating conditions the currents of the three phases add up to zero resulting in zero spill current. A fault on the star
side will also not result in a spill current, as the fault current would simply circulate in the delta windings. However, if
any of the three delta windings were to develop a fault, the impedance of the faulty winding would change and that
would result in a mismatch between the phase currents, resulting in a spill current. If the spill current is large
enough, it will trigger a trip command.
The following figure shows a REF protection arrangement for the star side of a delta-star transformer.

REF
protection zone

Load

IED

V00621

Figure 77: REF protection for star side

Here we have a similar arrangement of current transformers connected in parallel. The difference is that we need to
measure the zero sequence current in the neutral line as well. An external unbalanced fault causes zero sequence
current to flow through the neutral line, resulting in uneven currents in the phases, which could cause the protection
to maloperate. By measuring this zero sequence current and placing it in parallel with the other three, the currents

P64-TM-EN-1 171
Chapter 8 - Restricted Earth Fault Protection P64

are balanced, resulting in stable operation. Now only a fault inside the star winding can create an imbalance
sufficient to cause a trip.

8.2.1 RESISTANCE-EARTHED STAR WINDINGS


Most distribution systems use resistance-earthed systems to limit the fault current. Consider the diagram below,
which depicts an earth fault on the star winding of a resistance-earthed Dyn transformer (Dyn = Delta-Star with star-
point neutral connection).

87
1.0

Source IF IF
IS Current p.u.
(x full load)
Pickup
IS
0.2
IF
64
20% 100%
Winding not protected

Fault position from neutral


(Impedance earthing)
V00669

Figure 78: REF protection for resistance-earthed systems

The value of fault current (IF) depends on two factors:


● The value of earthing resistance (which makes the fault path impedance negligible)
● The fault point voltage (which is governed by the fault location)

Because the fault current (IF) is governed by the resistance, its value is directly proportional to the location of the
fault.
A restricted earth fault element is connected to measure IF directly. This provides very sensitive earth fault
protection. The overall differential protection is less sensitive, since it only measures the HV current IS. The value of
IS is limited by the number of faulty secondary turns in relation to the HV turns.

8.2.2 SOLIDLY-EARTHED STAR WINDINGS


Most transmission systems use solidly-earthed systems. Consider the diagram below, which depicts an earth fault
on the star winding of a solidly-earthed Dyn transformer.

87
10

IF 8 IF
Source Current p.u.
IS (x full load) 6

2 IS
IF
64 20% 40% 60% 80% 100%

Fault position from neutral


(Solid earthing)
V00670

Figure 79: REF protection for solidly earthed system

172 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

In this case, the fault current IF is dependant on:


● The leakage reactance of the winding
● The impedance in the fault path
● The fault point voltage (which is governed by the fault location)

In this case, the value of fault current (IF) varies with the fault location in a complex manner.
A restricted earth fault element is connected to measure IF directly. This provides very sensitive earth fault
protection.
For solidly earthed systems, the operating current for the transformer differential protection is still significant for
faults over most of the winding. For this reason, independent REF protection may not have been previously
considered, especially where an additional device would have been needed. But with this product, it can be applied
without extra cost.

8.2.3 THROUGH FAULT STABILITY


In an ideal world, the CTs either side of a differentially protected system would be identical with identical
characteristics to avoid creating a differential current. However, in reality CTs can never be identical, therefore a
certain amount of differential current is inevitable. As the through-fault current in the primary increases, the
discrepancies introduced by imperfectly matched CTs is magnified, causing the differential current to build up.
Eventually, the value of the differential current reaches the pickup current threshold, causing the protection element
to trip. In such cases, the differential scheme is said to have lost stability. To specify a differential scheme’s ability to
restrain from tripping on external faults, we define a parameter called ‘through-fault stability limit’, which is the
maximum through-fault current a system can handle without losing stability.

8.2.4 RESTRICTED EARTH FAULT TYPES


There are two different types of Restricted Earth Fault; Low Impedance REF (also known as Biased REF) and High
Impedance REF. Each method compensates for the effect of through-fault errors in a different manner.
With Low Impedance REF, the through-fault current is measured and this is used to alter the sensitivity of the REF
element accordingly by applying a bias characteristic. So the higher the through fault current, the higher the
differential current must be for the device to issue a trip signal, Often a transient bias component is added to
improve stability during external faults.
Low impedance protection used to be considered less secure than high impedance protection. This is no longer true
as numerical IEDs apply sophisticated algorithms to match the performance of high-impedance schemes. Some
advantages of using Low Impedance REF are listed below:
● There is no need for dedicated CTs. As a result CT cost is substantially reduced
● The wiring is simpler as it does not require an external resistor or Metrosil
● Common phase current inputs can be used
● It provides internal CT ratio mismatch compensation. It can match CT ratios up to 1:40 resulting flexibility in
substation design and reduced cost
● Advanced algorithms make the protection secure

With High Impedance REF, there is no bias characteristic, and the trip threshold is set to a constant level. However,
the High Impedance differential technique ensures that the impedance of the circuit is sufficiently high such that the
differential voltage under external fault conditions is lower than the voltage needed to drive differential current
through the device. This ensures stability against external fault conditions so the device will operate only for faults
occurring inside the protected zone.
High Impedance REF protection responds to a voltage across the differential junction points. During external faults,
even with severe saturation of some of the CTs, the voltage does not rise above certain level, because the other

P64-TM-EN-1 173
Chapter 8 - Restricted Earth Fault Protection P64

CTs will provide a lower-impedance path compared with the device input impedance. The principle has been used
for more than half a century. Some advantages of using High Impedance REF are listed below:
● It provides a simple proven algorithm, which is fast, robust and secure
● It is less sensitive to CT saturation

8.2.4.1 LOW IMPEDANCE REF PRINCIPLE


Low Impedance REF can be used for either delta windings or star windings in both solidly grounded and resistance
grounded systems. The connection to a modern IED is as follows:

Phase A
Phase A
Phase B
Phase B
Phase C
Phase C

I Phase A
I Phase A

I Phase B
I Phase B

I Phase C
I Phase C

I Neutral

IED IED

Connecting IED to star winding for Low Connecting IED to delta winding for Low
Impedance REF Impedance REF
V00679

Figure 80: Low impedance REF connection

8.2.4.1.1 LOW IMPEDANCE BIAS CHARACTERISTIC


Usually, a triple slope biased characteristic is used as follows:

Differential current

Higher
slope

Operate region

Lower slope

Restraint region
Minimum operating current

Bias current
First knee point Second knee point
V00677

Figure 81: Three-slope REF bias characteristic

174 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

The flat area of the characteristic is the minimum differential current required to cause a trip (operate current) at low
bias currents. From the first kneepoint onwards, the operate current increases linearly with bias current, as shown
by the lower slope on the characteristic. This lower slope provides sensitivity for internal faults. From the second
knee point onwards, the operate current further increases linearly with bias current, but at a higher rate. The second
slope provides stability under through fault conditions.

Note:
In Restricted Earth Fault applications, Bias Current Compensation is also known as Low Impedance REF.

8.2.4.2 HIGH IMPEDANCE REF PRINCIPLE


This scheme is very sensitive and can protect against low levels of fault current, typical of winding faults.
High Impedance REF protection is based on the differential principle. It works on the circulating current principle as
shown in the following diagram.

Healthy CT Saturated CT
Protected
circuit

Ph-G
Zm1 Zm2
I = Is + I F
RCT1 RCT2

I IF

RL1 IS RL3

Vs RST

RL2 R
RL4

V00671

Figure 82: High impedance REF principle

When subjected to heavy through faults the line current transformer may enter saturation unevenly, resulting in
imbalance. To ensure stability under these conditions a series connected external resistor is required, so that most
of the unbalanced current will flow through the saturated CT. As a result, the current flowing through the device will
be less than the setting, therefore maintaining stability during external faults.
Voltage across REF element Vs = IF (RCT2 + RL3 + RL4)
Stabilising resistor RST = Vs/Is –RR
where:
● IF = maximum secondary through fault current
● RR = device burden
● RCT = CT secondary winding resistance
● RL2 and RL3 = Resistances of leads from the device to the current transformer
● RST = Stabilising resistor

High Impedance REF can be used for either delta windings or star windings in both solidly grounded and resistance
grounded systems. The connection to a modern IED are as follows:

P64-TM-EN-1 175
Chapter 8 - Restricted Earth Fault Protection P64

Phase A
Phase A
Phase B
Phase B
Phase C
Phase C

I Phase A

I Phase B

I Phase C
RSTAB I Neutral

I Neutral RSTAB
IED IED

Connecting IED to star winding for High Connecting IED to delta winding for High
Impedance REF Impedance REF

V00680

Figure 83: High impedance REF connection

176 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

8.3 RESTRICTED EARTH FAULT PROTECTION IMPLEMENTATION

8.3.1 ENABLING REF PROTECTION


A REF element is available for each of the windings (HV, LV, and if applicable, TV) as well as one for
Autotransformers. For each of these windings you can disable REF protection or set it to Low Impedance or High
Impedance using the settings REF HV Status, REF LV Status, REF TV Status and REF Auto Status in the REF
PROTECTION column.
Low impedance REF is blocked if:
● Current Transformer Supervision operates
● Stub Bus protection is activated (on a per-winding basis)
● Neutral supervision element is not activated (on a per-winding basis) if Enabled

High impedance REF is not blocked by Current Transformer Supervision or Stub Bus Protection.

8.3.2 NEUTRAL SUPERVISION


A low impedance REF element is available for each of the windings (HV, LV, and if applicable, TV) as well as one
for Autotransformers. For each of these windings there is a neutral current supervision element available IN Superv
HV/LV/TV/AT you can enable or disable. If the neutral current is less than the IN Set HV/LV/TV/AT setting this will
block the low impedance REF element. The neutral current supervision element can be used to supervise the REF
element to provide additional stability for through faults causing the phase CTs to saturate which can create
differential current to the REF element.

REF HV Sta rt
Idi ff

Is1 DT
Ibia s HV Is2 Ibi as & REF Trip HV

Blk REF HV
CTS HV 1
HV-LZRE F sf OOR

REF I H2 S tart HV
IH2 REF B lo ck HV &
Ena bled

IN < I N SET HV
IN Supe r HV & Note: S ame principle ap plies for LV and TV windings
Ena bled

V00708a

Figure 84: Low impedance restricted Earth Fault logic

8.3.3 SELECTING THE CURRENT INPUTS


The P642 has two current terminal inputs (T1 and T2), the P643 has up to three terminal current inputs (T1 to T3),
and the P645 has up to five current terminal inputs (T1 to T5).
For the P642, you associate one terminal current input with the HV (High Voltage) winding and the other with the LV
(Low Voltage) winding.

P64-TM-EN-1 177
Chapter 8 - Restricted Earth Fault Protection P64

For the P643 and P645 you can choose to associate more than one terminal current input with particular windings.
In cases where more than one terminal CT is associated with a winding, the input to the differential protection
function uses the vector sum of the current terminal inputs (on a phase by phase basis) as the input to the
calculation for that winding.
You associate these current inputs with the system transformer windings with the settings HV CT Terminals, LV CT
Terminals and TV CT Terminals in the SYSTEM CONFIG column as follows:

Setting P642 P643 P645


00001
00011
001
HV CT Terminals 01 00111
011
01011
01111
10000
11000
100
LV CT Terminals 10 11100
110
11010
11110
00100
01100
TV CT Terminals 010
00110
01110

Where the terminals T1 to T5 correspond to the bits in the binary string as follows (1 = in use, 0 = not in use). The
bit order starts with T1 on the right-hand side. For example:

If a CT is assigned to more than one winding, then an alarm is issued (CT Selection Alm). When this DDB signal is
asserted, the protection is also blocked.

Winding associations for the P643


You can select the REF element Phase side CT Input for each of the elements:
● For HV CT terminals, select from either HV Winding (Vector sum of multiple CT Input selected in system
config HV CT terminals) or T2 input
● For LV CT Terminals, select from either LV Winding (Vector sum of multiple CT Input selected in system
config LV CT terminals) or T2 input

Winding associations for the P645


You can select the REF element Phase side CT Input for each of the elements:
● For HV CT terminals, select from either HV Winding (Vector sum of multiple CT Input selected in system
config HV CT terminals) or T2, T3 and T4 inputs
● For LV CT Terminals, select from either LV Winding (Vector sum of multiple CT Input selected in system
config LV CT terminals) or T2, T3 and T4 inputs
● For TV CT Terminals, select from either TV Winding (Vector sum of multiple CT Input selected in system
config TV CT terminals) or T2 and T4 Inputs

178 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

8.3.4 LOW IMPEDANCE REF

8.3.4.1 SETTING THE BIAS CHARACTERISTIC


Low impedance REF uses a bias characteristic for increasing sensitivity and stabilising for through faults. The
current required to trip the differential IED is called the Operate current. This Operate current is a function of the
differential current and the bias current according to the bias characteristic.
The differential current is defined as follows:

I diff = I A + I B + I C + K I N
( )
The bias current is as follows:

1
I bias =
2
{
max  I A , I B , I C  + K I N }
where:
● K = Neutral CT ratio / Line CT ratio
● KA = Neutral CT Primary value / Line CT Primary value
● IN = current measured by the neutral CT

The allowable range for K is:


0.05 < K < 15 for standard CTs
0.05 < K < 20 for sensitive CTs

Note:
The alarm is raised and the REF element is blocked for KA when less than 0.05 or greater than 20.

The operate current is calculated according to the following characteristic:

P64-TM-EN-1 179
Chapter 8 - Restricted Earth Fault Protection P64

I DIFF

Operate K2

Restrain

I S1 K1

I S2 I BIAS

E04021

Figure 85: REF bias characteristic

The following settings are provided to define this bias characteristic:


● IREF> Is1: sets the minimum trip threshold
● IREF> Is2: sets the bias current kneepoint whereby the required trip current starts increasing
● IREF> k1: defines the first slope (often set to 0%)
● IREF> k2: defines the second slope

Note:
Is1 and Is2 are relative to the line CT, which is always the reference CT.

8.3.4.2 DELAYED BIAS


To provide further stability when external faults are being cleared, the protection checks for the highest value of bias
current calculated during the previous cycle. If that value is higher than the present value, it is used to restrain the
tripping decision. This is referred to as the Residual Bias. The Residual Bias technique maintains through fault
stability for clearance of external faults.

8.3.4.3 TRANSIENT BIAS


If there is a sudden increase in the mean-bias measurement, an additional bias quantity is introduced in the bias
calculation. Transient Bias provides stability for external faults where CT saturation might occur.
The transient bias function enhances the stability of the differential element during external faults and allows for the
time delay in CT saturation caused by small external fault currents and high X/R ratios.

180 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

No transient bias is produced under load switching conditions, or when the CT comes out of saturation.

8.3.4.4 RESTRICTED EARTH FAULT LOGIC

REF HV Start
Id iff HV I diff

DT
Is1
& REF Trip HV
Ibias HV Is2 I bias

Blk REF HV
CTS HV 1
HV-LZREF sf OOR

REF IH2 Start HV


IH2 REF Block HV & Note: Same principle applies for LV and TV windings

Enabled
V00708

Figure 86: Low impedance restricted Earth Fault logic

8.3.5 HIGH IMPEDANCE REF


A high impedance restricted earth fault protection function is available for up to three windings. An external resistor
is required to provide stability in the presence of saturated line current transformers.
TN1 CT is associated with the HV winding high impedance REF, or with the autotransformer high impedance REF.
TN2 CT is associated with the LV winding high impedance REF and TN3 CT is associated with the TV winding high
impedance REF.
Current transformer supervision, HV StubBus Act, LV StubBus Act or TV StubBus Act signals do not block the high
impedance REF protection. You must configure logic in the PSL to block the high impedance REF when any of the
above signals are asserted.

8.3.5.1 HIGH IMPEDANCE REF CALCULATION PRINCIPLES


The primary operating current (Iop) is a function of the current transformer ratio, the device operate current
(IREF>Is), the number of current transformers in parallel with a REF element (n) and the magnetizing current of
each current transformer (Ie) at the stability voltage (Vs). This relationship can be expressed in three ways:
1. The maximum current transformer magnetizing current to achieve a specific primary operating current with a
particular operating current:

1  I op 
Ie <  − [ IREF > Is ] 
n  CT ratio 
2. The maximum current setting to achieve a specific primary operating current with a given current transformer
magnetizing current:

 I op 
[ IREF > Is ] <  − nI e 
 CT ratio 
3. The protection primary operating current for a particular operating current with a particular level of
magnetizing current:

I op = ( CT ratio ) ([ IREF > Is ] + nI e )

P64-TM-EN-1 181
Chapter 8 - Restricted Earth Fault Protection P64

To achieve the required primary operating current with the current transformers that are used, you must select a
current setting for the high impedance element, as shown in item 2 above. You can calculate the value of the
stabilising resistor (RST) in the following manner.

Vs I ( R + 2 RL )
Rst = = F CT
[ IREF > Is ] [ IREF > Is ]
where:
● RCT = the resistance of the CT winding
● RL = the resistance of the lead from the CT to the IED.

Note:
The above formula assumes negligible relay burden.

We recommend a stabilizing resistor, which is continuously adjustable up to its maximum declared resistance.

182 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

8.4 SECOND HARMONIC BLOCKING

8.4.1 REF 2ND HARMONIC BLOCKING LOGIC

Idiff f undamental HV

Is-HS1 &
& REF I H2 S tart HV

Low current (hard-coded)

Idiff 2nd harm / Idiff


fund
Idiff 2nd harmonic HV

IH2 REF S et HV Note: S ame principle applies for LV and TV windings


V00705

Figure 87: REF 2nd harmonic blocking logic

P64-TM-EN-1 183
Chapter 8 - Restricted Earth Fault Protection P64

8.5 APPLICATION NOTES

8.5.1 STAR WINDING RESISTANCE EARTHED


Consider the following resistance earthed star winding below.

Primary Secondary

A a

V2 V1
B b

c
C

V00681

Figure 88: Star winding, resistance earthed

An earth fault on such a winding causes a current which is dependant on the value of earthing impedance. This
earth fault current is proportional to the distance of the fault from the neutral point since the fault voltage is directly
proportional to this distance.
The ratio of transformation between the primary winding and the short circuited turns also varies with the position of
the fault. Therefore the current that flows through the transformer terminals is proportional to the square of the
fraction of the winding which is short circuited.
The earthing resistor is rated to pass the full load current IFLC = V1/Ö3R
Assuming that V1 = V2 then T2 = Ö3T1
For a fault at x PU distance from the neutral, the fault current If = xV1/Ö3R

Therefore the secondary fault current referred to the primary is Iprimary = x2.IFLC/Ö3
If the fault is a single end fed fault, the primary current should be greater than 0.2 pu (Is1 default setting) for the
differential protection to operate. Therefore x2/Ö3 > 20%
The following diagram shows that 41% of the winding is protected by the differential element.

184 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

X in % Idiff in %
10 0.58
20 2.31
30 5.20
59% of unprotected winding
40 9.24
50 14.43
60 20.00
70 28.29
80 36.95 41% of protected winding
90 46.77
100 57.74

V00682

Figure 89: Percentage of winding protected

8.5.2 LOW IMPEDANCE REF PROTECTION APPLICATION

8.5.2.1 SETTING GUIDELINES FOR BIASED OPERATION


Two bias settings are provided in the REF characteristic. The K1 level of bias is applied up to through currents of
Is2, which is normally set to the rated current of the transformer. K1 is normally be set to 0% to give optimum
sensitivity for internal faults. However, if any CT mismatch is present under normal conditions, then K1 may be
increased accordingly, to compensate. We recommend a setting of 20% in this case.
K2 bias is applied for through currents above Is2 and would typically be set to 150%.
According to ESI 48-3 1977, typical settings for the Is1 thresholds are 10-60% of the winding rated current when
solidly earthed and 10-25% of the minimum earth fault current for a fault at the transformer terminals when
resistance earthed.

8.5.2.2 LOW IMPEDANCE REF SCALING FACTOR


The three line CTs are connected to the three-phase CTs, and the neutral CT is connected to the neutral CT input.
These currents are then used internally to derive both a bias and a differential current quantity for use by the low
impedance REF protection. The advantage of this mode of connection is that the line and neutral CTs are not
differentially connected, so the neutral CT can also be used to provide the measurement for the Standby Earth Fault
Protection. Also, no external components such as stabilizing resistors or Metrosils are required.

P64-TM-EN-1 185
Chapter 8 - Restricted Earth Fault Protection P64

Line CTs 1000:1

Phase A

Phase B

Phase C

I Phase A

I Phase B

I Phase C
Neutral CT 200:1
I Neutral

IN IED

V00683

Figure 90: Low impedance REF scaling factor

Another advantage of Low Impedance REF protection is that you can use a neutral CT with a lower ratio than the
line CTs in order to provide better earth fault sensitivity. In the bias calculation, the device applies a scaling factor to
the neutral current. This scaling factor is as follows:
Scaling factor = K = Neutral CT ratio / Line CT ratio
This results in the following differential and bias current equations:

I diff = I A + I B + I C + K I N
( )
1
I bias =
2
{
max  I A , I B , I C  + K I N }
8.5.2.3 PARAMETER CALCULATIONS
Consider a solidly earthed 90 MVA 132 kV transformer with a REF-protected star winding. Assume line CTS with a
ratio of 400:1.
Is1 is set to 10% of the winding nominal current:

= (0.1 x 90 x 106) / (Ö3 x 132 x 103)


= 39 Amps primary
= 39/400 = 0.0975 Amps secondary (approx 0.1 A)
Is2 is set to the rated current of the transformer:

= 90 x 106 / (Ö3 x 132 x 103)


= 390 Amps primary
= 390/400 = 0.975 Amps secondary (approx 1 A)
Set K1 to 0% and K2 to 150%

186 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

8.5.2.4 DUAL CB APPLICATION WITH DIFFERENT PHASE CT RATIOS


The following diagram shows the situation where low impedance REF is being used in a dual breaker (breaker-and-
a-half) application where the phase CT ratios (CTx and CTy) are different. In this example, one phase of a
conventional transformer is shown, but the explanation is also applicable to autotransformers.

CTy

CTx

Neutral CT N

V00754

Figure 91: Low-Z REF for dual CB application with different phase CT ratios

The low impedance REF function can be used in dual breaker (breaker-and-a-half) applications. The line CT ratios
can be different. In this case the low impedance REF differential and bias current formulae are calculated as
follows:

( )
I diff ( REF ) =  IACTx + IB CTx + IC CTx + K1 IACTy + K1 IB CTy + K1 IC CTy + K 2 IN 
 

1
I bias ( REF ) =
2 { ( )( )( )
max  IACTx + K1 IACTy , IB CTx + K1 IB CTy , IC CTx + K1 IC CTy  + K 2 IN
  }
where:
● CTx and CTy (T1, T2, T3, T4 or T5) are the current inputs associated with a particular winding (given in the
settings HV CT Terminals, LV CT Terminals and TV CT Terminals respectively)
● K1 = CTy Ratio/CTx Ratio (Scaling Factor K1)
● K2 = Neutral CT Ratio/CTx Ratio (Scaling Factor K2)
● Reference: CTx, which is the same as T1-CT

Note:
The above formulae are valid for autotransformers and conventional transformers when the Phase CT Ratios are different
(CTx ≠ CTy) and the reference is CTx

8.5.2.5 DUAL CB APPLICATION WITH SAME PHASE CT RATIOS


The following diagram shows the situation where low impedance REF is being used in a dual breaker (breaker-and-
a-half) application where the phase CT ratios are identical. In this example, one phase of an autotransformer is
shown, but the explanation is also applicable to conventional transformers.

P64-TM-EN-1 187
Chapter 8 - Restricted Earth Fault Protection P64

T1 CT T2 CT

Low
Impedance
REF
TN1 CT

T3 CT T4 CT T5 CT

V00707

Figure 92: Low-Z REF for dual CB application with same phase CT ratios

The low impedance REF function can be used in dual breaker (breaker-and-a-half) applications. The line CT ratios
may be identical. In this case the Restricted Earth Fault (REF) Low Impedance (Z) Differential and Bias current
formulae are calculated as follows:
n
I diff ( REF ) = ∑ ( IA
n =1
TxCT
 )
+ IBTxCT + IC TxCT  + K n I TN1 CT

  n  
  ∑ IATxCT  
  n =1  
1  n  
I bias ( REF ) = max  ∑ IB TxCT  + K n I TN1 CT 
2  n =1  
  n  
  ∑ IC TxCT  
  n =1  
where:
● Tx CT = T1, T2, T3, T4 or T5.
● Kn = TN1 CT Ratio/ Tx CT Ratio
● TN1 CT Ratio = Neutral CT Ratio.
● Reference: Tx CT.

8.5.2.6 CT REQUIREMENTS - LOW IMPEDANCE REF


We strongly recommend Class X or Class 5P current transformers for this application.

188 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

The CT requirements for low impedance REF protection are generally lower than those for differential protection. As
the line CTs for low impedance REF protection are the same as those used for differential protection the differential
CT requirements cover both differential and low impedance REF applications.
The current transformer knee-point voltage requirements are based on the following default settings for transformer
REF protection; IS1 = 27 A (primary value at 300/1 CT Ratio), IS2 = 270 A (primary value at 300/1 CT ratio), K1 =
0%, K2 = 150%.
The K dimensioning factor for the REF function is smaller than that for the transformer differential protection. Since
the highest K factor must be considered, the CT requirements for transformer differential must be considered.

8.5.2.6.1 CT REQUIREMENTS - ONE BREAKER APPLICATION


To achieve through-fault stability, the K dimensioning factor must comply with the following:

System Conditions K Kneepoint Voltage (VK)


2In < IF £ 64In
12 VK ³ 12In(RCT + 2RL + Rr)
5 £ X/R £ 120

where:
● VK = kneepoint voltage
● K = CT dimensioning factor
● In = rated current
● RCT = resistance of CT secondary winding
● RL = Resistance of a single lead from device to current transformer
● Rr = resistance of any other protection devices sharing the current transformer

8.5.2.6.2 CT REQUIREMENTS - ONE-AND-A-HALF BREAKER APPLICATION


According to the test results, to achieve through-fault stability, the K dimensioning factor must comply with the
following:

System Conditions K Kneepoint Voltage (VK)


2In < IF £ 64In
27 VK ³ 27In(RCT + 2RL + Rr)
5 £ X/R £ 20

where:
● VK = kneepoint voltage
● K = CT dimensioning factor
● In = rated current
● RCT = resistance of CT secondary winding
● RL = Resistance of a single lead from device to current transformer
● Rr = resistance of any other protection devices sharing the current transformer

8.5.3 HIGH IMPEDANCE REF PROTECTION APPLICATION

8.5.3.1 HIGH IMPEDANCE REF OPERATING MODES


In the examples below, the respective Line CTS and measurement CTs must have the same CT ratios and similar
magnetising characteristics.

P64-TM-EN-1 189
Chapter 8 - Restricted Earth Fault Protection P64

CT1
A a

B b

c
C

TN1 CT
TN2 CT
TN3 CT

CTN Rst
Varistor

V00684

Figure 93: Hi-Z REF protection for a grounded star winding

CT1
A
a

B
b

C c

TN 1 CT
TN 2 CT
Varistor TN 3 CT
Rst

V00685

Figure 94: Hi-Z REF protection for a delta winding

190 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

CT2
a

CT1
A
b
CTN
B
c

TN1 CT
Varistor
Rst

V00686

Figure 95: Hi-Z REF protection for autotransformer configuration

8.5.3.2 SETTING GUIDELINES FOR HIGH IMPEDANCE OPERATION


This scheme is very sensitive and can protect against low levels of fault current in resistance grounded systems. In
this application, the IREF>Is settings should be chosen to provide a primary operating current less than 10-25% of
the minimum earth fault level.
This scheme can also be used in a solidly grounded system. In this application, the IREF>Is settings should be
chosen to provide a primary operating current between 10% and 60 % of the winding rated current.
The following diagram shows the application of a high impedance REF element to protect the LV winding of a power
transformer.

P64-TM-EN-1 191
Chapter 8 - Restricted Earth Fault Protection P64

A 400:1
a
RCT

B b

RL
c
C

RL

RL

Transformer: High Z
RCT
90 MVA REF
33/132 kV
Dyn11, X = 5% RL
Burdens:
RCT = 0.5 W
RL = 0.98 W

V00687

Figure 96: High impedance REF for the LV winding

8.5.3.2.1 STABILITY VOLTAGE CALCULATION


The transformer full load current, IFLC, is:

IFLC = (90 x 106)/32 x 103 x Ö3) = 394 A


To calculate the stability voltage the maximum through fault level should be considered. The maximum through fault
level, ignoring the source impedance, IF, is:

IF = IFLC/TX = 394/.05 = 7873 A


The required stability voltage, VS, and assuming one CT saturated is:
Vs = KIF(RCT + 2RL)
The following figure can be used to determine the K factor and the operating time. The K factor is valid when:
● 5 ≤ X/R ≤ 120

and
● 0.5In ≤ I f ≤ 40In

We recommend a value of VK/VS = 4.


With the transformer at full load current and percentage impedance voltage of 394A and 5% respectively, the
prospective fault current is 7873 A and the required stability voltage Vs (assuming that one CT is saturated) is:
Vs = 0.9 x 7873 x (0.5 + 2 x 0.98)/400 = 45.5 V
The CTs knee point voltage should be at least 4 times Vs so that an average operating time of 40 ms is achieved.

8.5.3.2.2 PRIMARY CURRENT CALCULATION


The primary operating current should be between 10 and 60 % of the winding rated current. Assuming that the relay
effective setting or primary operating current is approximately 30% of the full load current, the calculation below
shows that a setting of less than 0.3 A is required.

192 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

Effective setting = 0.3IFLC / CT Ratio = 0.3 x 394 / 400 = approximately 0.3 A

8.5.3.2.3 STABILISING RESISTOR CALCULATION


Assuming that a setting of 0.1A is selected the value of the stabilizing resistor, RST, required is

RST = Vs/(IREF> Is1 (HV)) = 45.5/0.1 = 455 ohms


To achieve an average operating time of 40 ms, Vk/Vs should be 3.5.
The Kneepoint voltage is:
VK = 4Vs = 4 x 45.5 = 182 V.
If the actual VK is greater than 4 times Vs, then the K factor increases. In this case, Vs should be recalculated.

Note:
K can reach a maximum value of approximately 1.

8.5.3.2.4 CURRENT TRANSFORMER CALCULATION


The effective primary operating current setting is:
IP = N(Is + nIe)
By re-arranging this equation, you can calculate the excitation current for each of the current transformers at the
stability voltage. This turns out to be:
Ie = (0.3 - 0.1) / 4 = 0.05 A
In summary, the current transformers used for this application must have a kneepoint voltage of 182 V or higher
(note that maximum Vk/Vs that may be considered is 16 and the maximum K factor is 1), with a secondary winding
resistance of 0.5 ohms or lower and a magnetizing current at 45.5 V of less than 0.05 A.
Assuming a CT kneepoint voltage of 200 V, the peak voltage can be estimated as:
VP = 2Ö2VK(VF-VK) = 2Ö2(200)(9004-200) = 3753 V
This value is above the peak voltage of 3000 V and therefore a non-linear resistor is required.

Note:
The kneepoint voltage value used in the above formula should be the actual voltage obtained from the CT magnetizing
characteristic and not a calculated value.

Note:
One stabilizing resistor, part No. ZB9016 756, and one varistor, part No. 600A/S1/S256 might be used.

8.5.3.3 USE OF METROSIL NON-LINEAR RESISTORS


Current transformers can develop high peak voltages under internal fault conditions. Metrosils are used to limit
these peak voltages to a value below the maximum withstand voltage (usually 3 kV).
You can use the following formulae to estimate the peak transient voltage that could be produced for an internal
fault. The peak voltage produced during an internal fault is a function of the current transformer kneepoint voltage
and the prospective voltage that would be produced for an internal fault if current transformer saturation did not
occur.
Vp = 2Ö(2VK(VF-VK))

P64-TM-EN-1 193
Chapter 8 - Restricted Earth Fault Protection P64

Vf = I'f(RCT+2RL+RST)
where:
● Vp = Peak voltage developed by the CT under internal fault conditions
● Vk = Current transformer kneepoint voltage
● Vf = Maximum voltage that would be produced if CT saturation did not occur
● I'f = Maximum internal secondary fault current
● RCT = Current transformer secondary winding resistance
● RL = Maximum lead burden from current transformer to relay
● RST = Relay stabilising resistor

You should always use Metrosils when the calculated values are greater than 3000 V. Metrosils are connected
across the circuit to shunt the secondary current output of the current transformer from the device to prevent very
high secondary voltages.
Metrosils are externally mounted and take the form of annular discs. Their operating characteristics follow the
expression:

V = CI0.25
where:
● V = Instantaneous voltage applied to the Metrosil
● C = Constant of the Metrosil
● I = Instantaneous current through the Metrosil

With a sinusoidal voltage applied across the Metrosil, the RMS current would be approximately 0.52 x the peak
current. This current value can be calculated as follows:
4
 2VS ( RMS ) 
I RMS = 0.52  
 C 
 
where:
● VS(RMS) = RMS value of the sinusoidal voltage applied across the metrosil.

This is due to the fact that the current waveform through the Metrosil is not sinusoidal but appreciably distorted.
The Metrosil characteristic should be such that it complies with the following requirements:
● The Metrosil current should be as low as possible, and no greater than 30 mA RMS for 1 A current
transformers or 100 mA RMS for 5 A current transformers.
● At the maximum secondary current, the Metrosil should limit the voltage to 1500 V RMS or 2120 V peak for
0.25 second. At higher device voltages it is not always possible to limit the fault voltage to 1500 V rms, so
higher fault voltages may have to be tolerated.
The following tables show the typical Metrosil types that will be required, depending on relay current rating, REF
voltage setting etc.

Metrosils for devices with a 1 Amp CT


The Metrosil units with 1 Amp CTs have been designed to comply with the following restrictions:
● The Metrosil current should be less than 30 mA rms.
● At the maximum secondary internal fault current the Metrosil should limit the voltage to 1500 V rms if
possible.

194 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

The Metrosil units normally recommended for use with 1Amp CTs are as shown in the following table:

Nominal Characteristic Recommended Metrosil Type


Device Voltage Setting C b Single Pole Relay Triple Pole Relay
Up to 125 V RMS 450 0.25 600A/S1/S256 600A/S3/1/S802
125 to 300 V RMS 900 0.25 600A/S1/S1088 600A/S3/1/S1195

Note:
Single pole Metrosil units are normally supplied without mounting brackets unless otherwise specified by the customer.

Metrosils for devices with a 5 Amp CT


These Metrosil units have been designed to comply with the following requirements:
● The Metrosil current should be less than 100 mA rms (the actual maximum currents passed by the devices
shown below their type description.
● At the maximum secondary internal fault current the Metrosil should limit the voltage to 1500 V rms for
0.25secs. At the higher relay settings, it is not possible to limit the fault voltage to 1500 V rms so higher fault
voltages have to be tolerated.
The Metrosil units normally recommended for use with 5 Amp CTs and single pole relays are as shown in the
following table:

Secondary Internal Fault Current Recommended Metrosil Types for Various Voltage Settings
Amps RMS Up to 200 V RMS 250 V RMS 275 V RMS 300 V RMS
600A/S1/S1213 600A/S1/S1214 600A/S1/S1214 600A/S1/S1223
50A C = 540/640 C = 670/800 C =670/800 C = 740/870
35 mA RMS 40 mA RMS 50 mA RMS 50 mA RMS
600A/S2/P/S1217 600A/S2/P/S1215 600A/S2/P/S1215 600A/S2/P/S1196
100A C = 470/540 C = 570/670 C =570/670 C =620/740
70 mA RMS 75 mA RMS 100 mA RMS 100 mA RMS
600A/S3/P/S1219 600A/S3/P/S1220 600A/S3/P/S1221 600A/S3/P/S1222
150A C = 430/500 C = 520/620 C = 570/670 C =620/740
100 mA RMS 100 mA RMS 100 mA RMS 100 mA RMS

In some situations single disc assemblies may be acceptable, contact GE Vernova for detailed applications.

Note:
The Metrosils recommended for use with 5 Amp CTs can also be used with triple pole devices and consist of three single pole
units mounted on the same central stud but electrically insulated from each other. To order these units please specify "Triple
pole Metrosil type", followed by the single pole type reference. Metrosil for higher voltage settings and fault currents are
available if required.

8.5.3.4 CT REQUIREMENTS - HIGH IMPEDANCE REF


In a high impedance REF scheme, the required stability voltage requirement is described in terms of an external
fault (IF), burden (2RL + RCT) and a stability factor (K), as follows:

Vs => KIF(2RL + RCT)

P64-TM-EN-1 195
Chapter 8 - Restricted Earth Fault Protection P64

where:
● IF = maximum external fault level
● RCT = resistance of CT secondary winding
● RL = resistance of a single lead from device to current transformer
The assumption that one CT is completely saturated for an external fault does not describe what actually happens
when asymmetric CT saturation occurs. The CT that saturates will only saturate during parts of each current
waveform cycle. This means that the spill current waveform seen by the differential element will be highly non-
sinusoidal. The sensitivity to non-sinusoidal spill waveforms for through-faults will be a function of the REF
frequency response, the REF operating time, the REF current setting and the wave shapes.
The frequency response and the operating speed are factors that are inherent to the design. Spill current wave
shapes will be related to the ratio of the CT kneepoint voltage (VK) to the circuit impedance. The stability voltage is
determined by the current setting and the stabilising resistor. The stability of the High Impedance REF function
during through faults is determined by the ratio VK/VS. Where VK is the CT knee point voltage and VS is the stability
voltage.
The relationship between the VK/VS ratio and the required stability factor K has been found to be of a general form
for various designs that have undergone conjunctive testing. It is the absolute values of VK/VS and K that vary in the
relationship for different device designs.
Once stability has been considered, the next performance factor to take into account is the operating time for
internal faults. The CT kneepoint voltage as a multiple of the protection stability voltage setting (VK/VS) will govern
the operating time of a differential relay element for heavy internal faults with transiently offset fault current
waveforms. With the aid of the operating time curves derived for the device, it is possible to identify the ratio VK/VS
that is required to achieve a desired average operating speed for internal faults.
The approach with older electromechanical high impedance relays was to use an universally safe K factor of 1.0,
but the older relays operated quickly with a lower VK/Vs ratio. With more modern IEDs, it is desirable to identify the
optimum K factor for stability, so that the required VK/Vs ratio for stability and operating speed will not make CT
kneepoint voltage requirements worse than traditional requirements.
The high impedance REF CT requirements are shown in the following figure. They are valid for:
5 £ X/R £ 120 and 0.5In £ 40In

0.4 0.06
0.5
0.05
Average operating time
0.6
0.7 0.04
0.8 Average operating time (red curve) 0.03
K

Unstable
0.9 0.02
K (blue curve)
1.0
Stable 0.01
1.1
1.2 0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
VK /VS
V00752

Figure 97: High Impedance REF CT requirement

Using the above graphical tool:


1. Locate the required average operation time on the right-hand side of the vertical axis.
2. Draw a horizontal line across until it intersects the red curve
3. Draw a vertical line from the above intersection point
4. Read off the the Vk/Vs value from the horizontal axis
5. Where this vertical line intersects the blue curve, read off the K value on the left hand side of the vertical axis

196 P64-TM-EN-1
P64 Chapter 8 - Restricted Earth Fault Protection

If we take the example where the average operating time is 38 ms, the above graphical operations reveal that Vk/Vs
= 4 and K = 0.95.
For best accuracy we recommend class X or class 5P current transformers (CTs). The CT requirements for high
impedance REF protection are generally lower than those for differential protection. If the line CTs for high
impedance REF protection are the same as those used for differential protection, the differential CT requirements
cover both differential and high impedance REF applications. However if the line CTs for high impedance REF are
not the same as those used for differential protection, the high impedance REF CT requirements can be obtained
by using the graph shown above.

P64-TM-EN-1 197
Chapter 8 - Restricted Earth Fault Protection P64

198 P64-TM-EN-1
CHAPTER 9

CURRENT PROTECTION FUNCTIONS


Chapter 9 - Current Protection Functions P64

9.1 CHAPTER OVERVIEW


The 5th Generation provides a wide range of current protection functions. This chapter describes the operation of
these functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 200
Overcurrent Protection Principles 201
Phase Overcurrent Protection 213
Voltage Dependent Overcurrent Element 221
Negative Sequence Overcurrent Protection 224
Earth Fault Protection 228
Second Harmonic Blocking 234

200 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.2 OVERCURRENT PROTECTION PRINCIPLES


Most electrical power system faults result in an overcurrent of one kind or another. It is the job of protection devices,
formerly known as 'relays' but now known as Intelligent Electronic Devices (IEDs) to protect the power system from
faults. The general principle is to isolate the faults as quickly as possible to limit the danger and prevent fault
currents flowing through systems, which can cause severe damage to equipment and systems. At the same time,
we wish to switch off only the parts of the power grid that are absolutely necessary, to prevent unnecessary
blackouts. The protection devices that control the tripping of the power grid's circuit breakers are highly
sophisticated electronic units, providing an array of functionality to cover the different fault scenarios for a multitude
of applications.
The described products offer a range of overcurrent protection functions including:
● Phase Overcurrent protection
● Earth Fault Overcurrent protection
● Negative Sequence Overcurrent protection
● Sensitive Earth Fault protection

To ensure that only the necessary circuit breakers are tripped and that these are tripped with the smallest possible
delay, the IEDs in the protection scheme need to co-ordinate with each other. Various methods are available to
achieve correct co-ordination between IEDs in a system. These are:
● By means of time alone
● By means of current alone
● By means of a combination of both time and current.

Grading by means of current alone is only possible where there is an appreciable difference in fault level between
the two locations where the devices are situated. Grading by time is used by some utilities but can often lead to
excessive fault clearance times at or near source substations where the fault level is highest.
For these reasons the most commonly applied characteristic in co-ordinating overcurrent devices is the IDMT
(Inverse Definite Minimum Time) type.

9.2.1 IDMT CHARACTERISTICS


There are two basic requirements to consider when designing protection schemes:
● All faults should be cleared as quickly as possible to minimise damage to equipment
● Fault clearance should result in minimum disruption to the electrical power grid.

The second requirement means that the protection scheme should be designed such that only the circuit breaker(s)
in the protection zone where the fault occurs, should trip.
These two criteria are actually in conflict with one another, because to satisfy (1), we increase the risk of shutting off
healthy parts of the grid, and to satisfy (2) we purposely introduce time delays, which increase the amount of time a
fault current will flow. With IDMT protection applied to radial feeders, this problem is exacerbated by the nature of
faults in that the protection devices nearest the source, where the fault currents are largest, actually need the
longest time delay.
IDMT characteristics are described by operating curves. Traditionally, these were defined by the performance of
electromechanical relays. In numerical protection, equations are used to replicate these characteristics so that they
can be used to grade with older equipment.
The old electromechanical relays countered this problem somewhat due to their natural operate time v. fault current
characteristic, whereby the higher the fault current, the quicker the operate time. The characteristic typical of these
electromechanical relays is called Inverse Definite Minimum Time or IDMT for short.

P64-TM-EN-1 201
Chapter 9 - Current Protection Functions P64

9.2.1.1 IEC 60255 IDMT CURVES


There are four well-known variants of this characteristic:
● Standard Inverse
● Very inverse
● Extremely inverse
● UK Long Time inverse

These equations and corresponding curves governing these characteristics are very well known in the power
industry.

Standard Inverse
This characteristic is commonly known as the 3/10 characteristic, i.e. at ten times setting current and TMS of 1 the
relay will operate in 3 seconds.
The characteristic curve can be defined by the mathematical expression:

0.14
top = T 0.02
 I 
  −1
 Is 
The standard inverse time characteristic is widely applied at all system voltages – as back up protection on EHV
systems and as the main protection on HV and MV distribution systems.
In general, the standard inverse characteristics are used when:
● There are no co-ordination requirements with other types of protective equipment further out on the system,
e.g. Fuses, thermal characteristics of transformers, motors etc.
● The fault levels at the near and far ends of the system do not vary significantly.
● There is minimal inrush on cold load pick up. Cold load inrush is that current which occurs when a feeder is
energised after a prolonged outage. In general the relay cannot be set above this value but the current should
decrease below the relay setting before the relay operates.

Very Inverse
This type of characteristic is normally used to obtain greater time selectivity when the limiting overall time factor is
very low, and the fault current at any point does not vary too widely with system conditions. It is particularly suitable,
if there is a substantial reduction of fault current as the distance from the power source increases. The steeper
inverse curve gives longer time grading intervals. Its operating time is approximately doubled for a reduction in
setting from 7 to 4 times the relay current setting. This permits the same time multiplier setting for several relays in
series.
The characteristic curve can be defined by the mathematical expression:

13.5
top = T
I 
  −1
 Is 

Extremely Inverse
With this characteristic the operating time is approximately inversely proportional to the square of the current. The
long operating time of the relay at peak values of load current make the relay particularly suitable for grading with
fuses and also for protection of feeders which are subject to peak currents on switching in, such as feeders
supplying refrigerators, pumps, water heaters etc., which remain connected even after a prolonged interruption of
supply.

202 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

For cases where the generation is practically constant and discrimination with low tripping times is difficult to obtain,
because of the low impedance per line section, an extremely inverse relay can be very useful since only a small
difference of current is necessary to obtain an adequate time difference.
Another application for this relay is with auto reclosers in low voltage distribution circuits. As the majority of faults
are of a transient nature, the relay is set to operate before the normal operating time of the fuse, thus preventing
perhaps unnecessary blowing of the fuse.
Upon reclosure, if the fault persists, the recloser locks itself in the closed position and allows the fuse to blow to
clear the fault.
This characteristic is also widely used for protecting plant against overheating since overheating is usually an I2t
function.
This characteristic curve can be defined by the mathematical expression:

80
top = T 2
I 
  −1
 Is 

UK Long Time Inverse


This type of characteristic has a long time characteristic and may be used for protection of neutral earthing resistors
(which normally have a 30 second rating). The relay operating time at 5 times current setting is 30 seconds at a
TMS of 1.
This can be defined by:

120
top = T
 I 
  −1
 Is 
In the above equations:
● top is the operating time
● T is the time multiplier setting
● I is the measured current
● Is is the current threshold setting.

The ratio I/Is is sometimes defined as ‘M’ or ‘PSM’ (Plug Setting Multiplier).
These curves are plotted as follows:

P64-TM-EN-1 203
Chapter 9 - Current Protection Functions P64

1000.00

100.00

Operating time (seconds)


Long Time Inverse (LTI)

10.00

Standard Inverse (SI)

1.00
Very Inverse (VI)

Extremely Inverse (EI)

0.10
1 10 100

E00600 Current (multiples of IS)

Figure 98: IEC 60255 IDMT curves

9.2.1.2 EUROPEAN STANDARDS


The IEC 60255 IDMT Operate equation is:

 β 
top = T  α + L+C
 M −1 
and the IEC 60255 IDMT Reset equation is:

 β 
tr = T  α 
 1− M 
where:
● top is the operating time
● tr is the reset time
● T is the Time Multiplier setting
● M is the ratio of the measured current divided by the threshold current (I/Is)
● β is a constant, which can be chosen to satisfy the required curve characteristic
● α is a constant, which can be chosen to satisfy the required curve characteristic
● C is a constant for adding Definite Time (Definite Time adder)
● L is a constant (usually only used for ANSI/IEEE curves)

The constant values for the IEC IDMT curves are as follows:

Curve Description b constant a constant L constant


IEC Standard Inverse Operate 0.14 0.02 0
IEC Standard Inverse Reset 8.2 6.45 0

204 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

Curve Description b constant a constant L constant


IEC Very Inverse Operate 13.5 1 0
IEC Very Inverse Reset 50.92 2.4 0
IEC Extremely Inverse Operate 80 2 0
IEC Extremely Inverse Reset 44.1 3.03 0
UK Long Time Inverse Operate* 120 1 0
UK Rectifier Operate* 45900 5.6 0

Rapid Inverse (RI) characteristic


The RI operate curve is represented by the following equation:

 
 1 
top = K 
0.236 
 0.339 − 
 M 
where:
● top is the operating time
● K is the Time Multiplier setting
● M is the ratio of the measured current divided by the threshold current (I/Is)

Note:
* When using UK Long Time Inverse, UK Rectifier or RI for the Operate characteristic, DT (Definite Time) is always used for
the Reset characteristic.

9.2.1.3 NORTH AMERICAN STANDARDS


The IEEE IDMT Operate equation is:

 β 
top = TD  α + L+C
 M −1 
and the IEEE IDMT Reset equation is:

 β 
tr = TD  α 
 1− M 
where:
● top is the operating time
● tr is the reset time
● TD is the Time Dial setting
● M is the ratio of the measured current divided by the threshold current (I/Is)
● b is a constant, which can be chosen to satisfy the required curve characteristic
● a is a constant, which can be chosen to satisfy the required curve characteristic
● C is a constant for adding Definite Time (Definite Time adder)
● L is a constant (usually only used for ANSI/IEEE curves)

P64-TM-EN-1 205
Chapter 9 - Current Protection Functions P64

The constant values for the IEEE curves are as follows:

Curve Description b constant a constant L constant


IEEE Moderately Inverse Operate 0.0515 0.02 0.114
IEEE Moderately Inverse Reset 4.85 2 0
IEEE Very Inverse Operate 19.61 2 0.491
IEEE Very Inverse Reset 21.6 2 0
IEEE Extremely Inverse Operate 28.2 2 0.1217
IEEE Extremely Inverse Reset 29.1 2 0
CO8 US Inverse Operate 5.95 2 0.18
CO8 US Inverse Reset 5.95 2 0
CO2 US Short Time Inverse Operate 0.16758 0.02 0.11858
CO2 US Short Time Inverse Reset 2.261 2 0

The constant values for the ANSI curves are as follows:

Curve Description b constant a constant L constant


ANSI Normally Inverse Operate 8.9341 2.0938 0.17966
ANSI Normally Inverse Reset 9 2 0
ANSI Short Time Inverse Operate 0.03393 1.2969 0.2663
ANSI Short Time Inverse Reset 0.5 2 0
ANSI Long Time Inverse Operate 2.18592 1 5.6143
ANSI Long Time Inverse Reset 15.75 2 0

Note:
* When using UK Long Time Inverse or UK Rectifier for the Operate characteristic, DT is always used for the Reset
characteristic.

206 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.2.1.4 IEC AND IEEE INVERSE CURVES

IEC Standard Inverse Curve IEC Very Inverse Curve

1000

1000

100 0.0250
TMS
100
0.0500
0.0250
0.075
0.0500
0.1
10
Time in seconds

Time in seconds
10 0.0750
0.2
0.1000
0.3
0.2000
1 0.4
0.3000
1 0.5
0.4000
0.6
0.1
0.5000
0.8
0.6000 1
0.1
0.8000 0.01 1.2

1.0000

1.2000
0.01 0.001
1 10 100 1 10 100

Current in Multiples of Setting Current in Multiples of Setting

E00757
Figure 99: IEC standard and very inverse curves

IEC Extremely Inverse Curve IEEE Moderate Inverse Curve

1000 10000

1000 0.01

0.02
100
0.025
0.05
0.05 100
0.07
0.075
Time in seconds

0.1
Time in seconds

10 0.1 10 0.5

0.2 1

0.3 1 5

1 0.4 10

0.5 20
0.1
30
0.6
40
0.1 0.8
0.01
60
1
80
1.2
0.001 100

0.01 1 10 100
1 10 100 Current in Multiples of Setting
Current in Multiples of Setting

E00758
Figure 100: IEC Extremely inverse and IEEE moderate inverse curves

P64-TM-EN-1 207
Chapter 9 - Current Protection Functions P64

IEEE Very Inverse Curve IEEE Extremely Inverse Curve

TD
100000 TD 100000

0.01
0.01
10000
10000 0.02
0.02
0.05
0.05 1000
0.05
0.07
1000
0.07
0.1 100
0.1
0.5
0.5

Time in seconds
Time in seconds

100
1 10
1
5
5
10 10 1
10
20
20
30 0.1
1 30
40
40
60 0.01
60
0.1 80
80
100
0.001
100

0.01 0.0001
1 10 100 1 10 100

Current in Multiples of Setting Current in Multiples of Setting

E00759
Figure 101: IEEE very and extremely inverse curves

9.2.1.5 DIFFERENCES BETWEEN THE NORTH AMERICAN AND EUROPEAN


STANDARDS
The IEEE and US curves are set differently to the IEC/UK curves, with regard to the time setting. A time multiplier
setting (TMS) is used to adjust the operating time of the IEC curves, whereas a time dial setting is used for the
IEEE/US curves. The menu is arranged such that if an IEC/UK curve is selected, the I> Time Dial cell is not visible
and vice versa for the TMS setting. For both IEC and IEEE/US type curves, a definite time adder setting is
available, which will increase the operating time of the curves by the set value.

9.2.2 PRINCIPLES OF IMPLEMENTATION


The range of protection products provides a very wide range of protection functionality. Despite the diverse range of
functionality provided, there is some commonality between the way many of the protection functions are
implemented. It is important to describe some of these basic principles before going deeper into the individual
protection functions.
A simple representation of protection functionality is shown in the following diagram:

208 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

Energising quantity Start signal

IDMT/DT
Threshold
& & & Trip Sign al

Function inhibit

Stage Blocking signals


1 Timer Settings
Stage Blocking sett ings

Voltage
Directional Check
Current

Timer Blocking signals


1
Timer Blocking settings
V00654

Figure 102: Principle of protection function implementation

An energising quantity is either a voltage input from a system voltage transformer, a current input from a system
current transformer or another quantity derived from one or both of these. The energising quantities are extracted
from the power system. The signals are converted to digital quantities where they can be processed by the IEDs
internal processor.
In general, an energising quantity, be it a current, voltage, power, frequency, or phase quantity, is compared with a
threshold value, which may be settable, or hard-coded depending on the function. If the quantity exceeds (for
overvalues) or falls short of (for undervalues) the threshold, a signal is produced, which when gated with the various
inhibit and blocking functions becomes the Start signal for that protection function. This Start signal is generally
made available to Fixed Scheme Logic (FSL) and Programmable Scheme Logic (PSL) for further processing. It is
also passed through a timer function to produce the Trip signal. The timer function may be an IDMT curve, or a
Definite Time delay, depending on the function. This timer may also be blocked with timer blocking signals and
settings. The timer can be configured by a range of settings to define such parameters as the type of curve, The
Time Multiplier Setting, the IDMT constants, the Definite Time delay etc.
In GE Vernova products, there are usually several independent stages for each of the functions, and for three-
phase functions, there are usually independent stages for each of the three phases.
Typically some stages use an Inverse Definite Minimum time (IDMT) timer function, and others use a Definite Time
timer (DT) function. If the DT time delay is set to '0', then the function is known to be "instantaneous". In many
instances, the term 'instantaneous protection" is used loosely to describe Definite Time protection stages, even
when the stage may not theoretically be instantaneous.
Many protection functions require a direction-dependent decision. Such functions can only be implemented where
both current and voltage inputs are available. For such functions, a directional check is required, whose output can
block the Start signal should the direction of the fault be wrong.

Note:
In the logic diagrams and descriptive text, it is usually sufficient to show only the first stage, as the design principles for
subsequent stages are usually the same (or at least very similar). Where there are differences between the functionality of
different stages, this is clearly indicated.

9.2.2.1 TIMER HOLD FACILITY


The Timer Hold facility is available for stages with IDMT functionality , and is controlled by the timer reset settings
for the relevant stages (e.g. I>1 tReset, I>2 tReset ). These cells are not visible for the IEEE/US curves if an

P64-TM-EN-1 209
Chapter 9 - Current Protection Functions P64

inverse time reset characteristic has been selected, because in this case the reset time is determined by the time
dial setting (TDS).
This feature may be useful in certain applications, such as when grading with upstream electromechanical
overcurrent relays, which have inherent reset time delays. If you set the hold timer to a value other than zero, the
resetting of the protection element timers will be delayed for this period. This allows the element to behave in a
similar way to an electromechanical relay. If you set the hold timer to zero, the overcurrent timer for that stage will
reset instantaneously as soon as the current falls below a specified percentage of the current setting (typically
95%).
Another situation where the timer hold facility may be used to reduce fault clearance times is for intermittent faults.
An example of this may occur in a plastic insulated cable. In this application it is possible that the fault energy melts
and reseals the cable insulation, thereby extinguishing the fault. This process repeats to give a succession of fault
current pulses, each of increasing duration with reducing intervals between the pulses, until the fault becomes
permanent.
When the reset time is instantaneous, the device will repeatedly reset and not be able to trip until the fault becomes
permanent. By using the Timer Hold facility the device will integrate the fault current pulses, thereby reducing fault
clearance time.

9.2.3 MAGNETISING INRUSH RESTRAINT


Whenever there is an abrupt change of magnetising voltage (e.g. when a transformer is initially connected to a
source of AC voltage), there may be a substantial surge of current through the primary winding called inrush
current.
In an ideal transformer, the magnetizing current would rise to approximately twice its normal peak value as well,
generating the necessary MMF to create this higher-than-normal flux. However, most transformers are not designed
with enough of a margin between normal flux peaks and the saturation limits to avoid saturating in a condition like
this, and so the core will almost certainly saturate during this first half-cycle of voltage. During saturation,
disproportionate amounts of MMF are needed to generate magnetic flux. This means that winding current, which
creates the MMF to cause flux in the core, could rise to a value way in excess of its steady state peak value.
Furthermore, if the transformer happens to have some residual magnetism in its core at the moment of connection
to the source, the problem could be further exacerbated.
The following figure shows the magnetizing inrush phenomenon:

210 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

+Fm

Steady state

–Fm

2Fm
Switch on at voltage
Zero – No residual flux

V = Voltage, F = Flux, Im = magnetising current, Fm = maximum flux

E03123
Figure 103: Magnetising inrush phenomenon

The main characteristics of magnetising inrush currents are:


● Higher magnitude than the transformer rated current magnitude
● Containing harmonics and DC offset
● Much longer time constant than that of the DC offset component of fault current

We can see that inrush current is a regularly occurring phenomenon and should not be considered a fault, as we do
not wish the protection device to issue a trip command whenever a transformer is switched on at an inconvenient
point during the input voltage cycle. This presents a problem to the protection device, because it should always trip

P64-TM-EN-1 211
Chapter 9 - Current Protection Functions P64

on an internal fault. The problem is that typical internal transformer faults may produce overcurrents which are not
necessarily greater than the inrush current. Furthermore, faults tend to manifest themselves on switch on, due to
the high inrush currents. For this reason, we need to find a mechanism that can distinguish between fault current
and inrush current. Fortunately, this is possible due to the different natures of the respective currents. An inrush
current waveform is rich in harmonics, especially 2nd harmonics, whereas an internal fault current consists only of
the fundamental. We can therefore develop a restraining method based on the 2nd harmonic content of the inrush
current. The mechanism by which this is achieved, is called second harmonic blocking.

212 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.3 PHASE OVERCURRENT PROTECTION


Phase current faults are faults where fault current flows between two or more phases of a power system. The fault
current may be between the phase conductors only or, between two or more phase conductors and earth.
Although not as common as earth faults (single phase to earth), phase faults are typically more severe.

9.3.1 PHASE OVERCURRENT PROTECTION FOR POWER TRANSFORMERS


A fault external to a power transformer can result in damage to the transformer. If the fault is not cleared promptly,
the resulting overload on the transformer can cause severe overheating and failure. Overcurrent elements may be
used to clear the transformer from a faulted bus or line before the transformer is damaged.
For faults internal to the transformer, the overcurrent protection is less effective because sensitive settings and fast
operation times are usually not possible.
Sensitive settings are not possible because the pickup should allow overloading of the transformer when required.
Fast operating times are not possible because of the grading required with respect to downstream overcurrent
relays.

9.3.2 PHASE OVERCURRENT PROTECTION IMPLEMENTATION


The product provides three overcurrent elements for backup phase overcurrent protection. Each element provides
four-stages of non-directional or directional three-phase overcurrent protection with independent time delay
characteristics. You can select the overcurrent element operating quantity for each of the elements with the setting
cells Overcurrent 1, Overcurrent 2 and Overcurrent 3 in the OVERCURRENT column of the relevant settings
group. You can set each element as T1, T2, T3, T4, T5, HV winding, LV winding or TV winding. The HV, LV
and TV windings comprise the vector sums of the CT inputs assigned to that particular winding.
All overcurrent and directional settings apply to all three phases but are independent for each of the four stages.
You may set the overcurrent element as directional only if the three phase VT input is available in the P643/5 and if
the two single phase VT inputs are available in the P642. You may assign the VT to either of the HV, LV or TV
windings. Therefore, overcurrent directional elements are available for the current inputs associated with the
winding that has the VT input assigned.
The first two stages of overcurrent protection have time-delayed characteristics which you can set as IDMT or DT.
The third and fourth stages have definite time characteristics only.
Stages 1, 2 provide a choice of operate and reset characteristics, where you can select between:
● A range of standard IDMT (Inverse Definite Minimum Time) curves
● DT (Definite Time)
This is achieved using the cells
● I>(n) Function for the overcurrent operate characteristic
● I>(n) Reset Char for the overcurrent reset characteristic (IEEE curves only)
where (n) is the number of the stage.
The IDMT-capable stages (1 and 2) also provide a Timer Hold facility. This is configured using the cells I>(n)
tReset, where (n) is the number of the stage. This is not applicable for curves based on the IEEE standard.

Note:
Stages 3 and 4 can have definite time characteristics only.

P64-TM-EN-1 213
Chapter 9 - Current Protection Functions P64

9.3.3 SELECTING THE CURRENT INPUTS


The P642 has two current terminal inputs (T1 and T2), the P643 has up to three terminal current inputs (T1 to T3),
and the P645 has up to five current terminal inputs (T1 to T5).
For the P642, you associate one terminal current input with the HV (High Voltage) winding and the other with the LV
(Low Voltage) winding.
For the P643 and P645 you can choose to associate more than one terminal current input with particular windings.
In cases where more than one terminal CT is associated with a winding, the input to the differential protection
function uses the vector sum of the current terminal inputs (on a phase by phase basis) as the input to the
calculation for that winding.
You associate these current inputs with the system transformer windings with the settings HV CT Terminals, LV CT
Terminals and TV CT Terminals in the SYSTEM CONFIG column as follows:

Setting P642 P643 P645


00001
00011
001
HV CT Terminals 01 00111
011
01011
01111
10000
11000
100
LV CT Terminals 10 11100
110
11010
11110
00100
01100
TV CT Terminals 010
00110
01110

Where the terminals T1 to T5 correspond to the bits in the binary string as follows (1 = in use, 0 = not in use). The
bit order starts with T1 on the right-hand side. For example:

If a CT is assigned to more than one winding, then an alarm is issued (CT Selection Alm). When this DDB signal is
asserted, the protection is also blocked.

Winding associations for the P643


If an overcurrent element is assigned to the HV winding then the associated setting I>(n) Current Set is relative to
the T1 CT. Therefore if if the T1 CT setting is changed, then I>(n) Current Set will be affected accordingly.
The same is true for the LV winding and its associated T3 CT as well as for the TV winding and its associated T2
CT.

Winding associations for the P645


If an overcurrent element is assigned to the HV winding then the associated setting I>(n) Current Set is relative to
the T1 CT. Therefore if the T1 CT setting is changed, then I>(n) Current Set will be affected accordingly.
The same is true for the LV winding and its associated T5 CT as well as for the TV winding and its associated T3
CT.

214 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.3.4 NON-DIRECTIONAL OVERCURRENT LOGIC

IA POC1 I>1 Start A

IDMT/DT
I> Threshold*1
& & POC 1 I>1 Trip A
POC1 IA2H Start
I> Blocking
&
2H Blocks I>1

Timer Setting s

POC1 I>1 Start B


IB

IDMT/DT
I> Threshold*1
& & POC 1 I>1 Trip B
POC1 IB2H Sta rt
I> Blocking
&
2H Blocks I>1

Timer Setting s

POC1 I>1 Start C


IC

IDMT/DT
I> Threshold*1
& & POC 1 I>1 Trip C
POC1 IC2H Start
I> Blocking
&
2H Blocks I>1 1 POC1 I>1 Start

Timer Setting s

POC1 IH2 Any St 1 POC1 I>1 Trip


IH2 Cross Block
&
Ena bled

POC 1 I>1 TBlk

*1 The threshold set tings are influen ced by Voltage Control Overcurrent functiona lity

POC 1 I> TBlk: Blocking signal requires minimum time de lay of 50 ms for Timer settings o f DT/IDMT V00672a

Figure 104: Non-directional overcurrent logic diagram

Phase Overcurrent Modules are level detectors that detect when the current magnitude exceeds a set threshold.
When this happens, the Phase Overcurrent Module in question issues a signal, which is gated with some blocking
signals to produce the Start signal. This Start signal is gated with other blocking signals and applied to the
IDMT/DT timer module. It is also made available directly to the user for use in the PSL. For each stage, there are
three Phase Overcurrent Modules, one for each phase. The three Start signals from each of these phases are OR'd
together to create a 3-phase Start signal.
The outputs of the IDMT/DT timer modules are the trip signals which are used to drive the tripping output relay.
These tripping signals are also OR'd together to create a 3-phase Trip signal.
The IDMT/DT timer modules can be blocked by:
● A Phase Overcurrent Timer Block (I>(n) Timer Block)
If any one of the above signals is high, or goes high before the timer has counted out, the IDMT/DT timer module is
inhibited (effectively reset) until the blocking signal goes low again. There are separate phase overcurrent timer
block signals, which are independent for each overcurrent stage.

P64-TM-EN-1 215
Chapter 9 - Current Protection Functions P64

The start signal can be blocked by:


● The Second Harmonic blocking function on a per phase basis or for all three phases. The relevant bits are
set in the I> Blocking cell and this is combined with the relevant second harmonic blocking DDBs.
The G14 Data type is used for the I>Blocking setting:

Bit number I> Blocking function


Bit 0 VTS Blocks I>1
Bit 1 VTS Blocks I>2
Bit 2 VTS Blocks I>3
Bit 3 VTS Blocks I>4
Bit 4 2H Blocks I>1
Bit 5 2H Blocks I>2
Bit 9 2H Blocks I>3
Bit 10 2H Blocks I>4

These can be set via the Front panel HMI or with the settings application software.
The Phase Overcurrent threshold setting can be influenced by the Voltage Controlled Overcurrent functions, if this
functionality is available and used.

9.3.5 DIRECTIONAL ELEMENT


If fault current can flow in both directions through a protected location, you will need to use a directional overcurrent
element to determine the direction of the fault. Once the direction has been determined the device can decide
whether to allow tripping or to block tripping. To determine the direction of a phase overcurrent fault, the device
must compare the phase angle of the fault current with that of a known reference quantity. The phase angle of this
known reference quantity must be independent of the faulted phase. Typically this will be the line voltage between
the other two phases.
The phase fault elements of the IEDs are internally polarized by the quadrature phase-phase voltages, as shown in
the table below:

Phase of Protection Operate Current Polarising Voltage


A Phase IA VBC
B Phase IB VCA
C Phase IC VAB

Under system fault conditions, the fault current vector lags its nominal phase voltage by an angle depending on the
system X/R ratio. The IED must therefore operate with maximum sensitivity for currents lying in this region. This is
achieved by using the IED characteristic angle (RCA). This is the is the angle by which the current applied to the
IED must be displaced from the voltage applied to the IED to obtain maximum sensitivity.
The device provides a setting I> Char Angle, which is set globally for all overcurrent stages. It is possible to set
characteristic angles anywhere in the range –95° to +95°.
A directional check is performed based on the following criteria:

Directional forward
-90° < (angle(I) - angle(V) - RCA) < 90°

216 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

Directional reverse
-90° > (angle(I) - angle(V) - RCA) > 90°

9.3.5.1 IMPLEMENTING DIRECTIONALISATION


A directional element is available for all of the phase overcurrent stages in this device. These are found in the
direction setting cells for the relevant stage (e.g. I>1 Direction, I>2 Direction). They can be set to non-directional,
directional forward, or directional reverse.
Under system fault conditions, the fault current vector will lag its nominal phase voltage by an angle dependent
upon the system X/R ratio. Therefore the device must operate with maximum sensitivity for currents lying in this
region. This is achieved by means of the characteristic angle (RCA) setting, which defines the angle by which the
applied current must be displaced from the applied voltage in order to obtain maximum sensitivity. This is set in cell
I>Char Angle. You can set characteristic angles anywhere in the range from –95° to +95°.
In the P642, the standard single-phase VT input cam be complemented by an optional single-phase VT that can be
used to directionalise some of the overcurrent protection elements. This connection is shown on the wiring
diagrams and labelled as 'Vbc OPTIONAL'. The settings for the optional VT input that can be used to directionalise
overcurrent elements are the same as those for the overfluxing input and are described by the Aux’ VT Location,
Aux' VT Primary and Aux' VT Sec'y settings in the CT AND VT RATIOS column.
In the P643 and P645, the standard single-phase VT input can be complemented by an optional three-phase VT
input that can be used to directionalise some of the overcurrent protection elements. This connection is shown on
the wiring diagrams and labelled as ‘OPTIONAL”. The settings for the optional VT input that can be used to
directionalise overcurrent elements are those described by the ’Main VT Location, Main VT Primary and Main VT
Sec'y settings settings in the CT AND VT RATIOS column.
The overcurrent elements that can be directionalised are those associated with the windings to which the optional
VTs are assigned. You can only directionalise overcurrent elements associated with the winding to which the
optional input is assigned.
So, to provide directional overcurrent you need:
● To have the appropriate VT option
● Connect the VT input to the winding that you want directional protection for AND assign the optional VT input
to that winding in the CT AND VT RATIOS column
● Set the overcurrent to directional (either forward or reverse).

As well as directionalising a particular winding current, for models with more than two winding inputs, you can
directionalise individual inputs if they are associated with that winding.
For close up three-phase faults, all three voltages will collapse to zero and no healthy phase voltages will be
present. For this reason, the device includes a synchronous polarisation feature that stores the pre-fault voltage
information and continues to apply this to the directional overcurrent elements for a time period of 3.2 seconds. This
ensures that either instantaneous or time-delayed directional overcurrent elements will be allowed to operate, even
with a three-phase voltage collapse.

P64-TM-EN-1 217
Chapter 9 - Current Protection Functions P64

9.3.5.2 DIRECTIONAL OVERCURRENT LOGIC

IA POC1 I>1 Start A

IDMT/DT
I> Threshold
& & POC1 I>1 Trip

POC1 IA2H Start


I> Blocking
&
2H Blocks I>1
Timer Settings

POC1 IH2 Any St


I> Blocking
&
2H Blocks I>1
2H 1PH Block

IA
VAB
I>1 Direction
Non-Directional
Directional FWD Directional
Directional REV check

VTS Slow Block


I> Blocking &
VTS Blocks I>1

POC1 I>1 TBlk

Notes: Shown for phase A only. Same principle applies f or phases B and C.
This diagram does not show all st ages. Ot her stages f ollow similar principles.

V00689

Figure 105: Directional overcurrent logic diagram

The directional overcurrent logic works the same way as non-directional logic except that there is a Directional
Check function, based on the following criteria:
● Directional forward: -90° < (angle(I) - angle(V) - RCA) < 90°
● Directional reverse: -90° > (angle(I) - angle(V) - RCA) > 90°

The polarising voltages for each phase are as follows:

Phase of Protection Operate Current Polarising Voltage


A Phase IA VBC
B Phase IB VCA
C Phase IC VAB

When the element is selected as directional, blocking of the Voltage Transformer Supervision (VTS Block) is
available (I>Blocking cell). When the relevant bit is set to 1, operation of the VTS will block the stage if
directionalised. When set to 0, the stage will revert to non-directional on operation of the VTS.

218 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.3.6 APPLICATION NOTES

9.3.6.1 SETTING GUIDELINES


The overcurrent inverse time characteristic on the HV side of the transformer must grade with the overcurrent
inverse time characteristic on the LV side which in turn must grade with the LV outgoing circuits. The overcurrent
function provides limited protection for internal transformer faults because sensitive settings and fast operation
times are usually not possible. Sensitive settings are not possible because the pickup should allow overloading of
the transformer when required. Fast operating times are not possible because of the grading required with respect
to downstream overcurrent relays. To allow fast operating times, phase instantaneous overcurrent functions with low
transient overreach are required.
The pickup of the time delayed overcurrent element can be set to 125-150% of the maximum MVA rating to allow
overloading of the transformer according to IEEE Std. C37.91-2000.
As recommended by IEEE Std. C37.91-2000, you should set the instantaneous overcurrent element to pick up at a
value higher than the maximum asymmetrical through fault current. This is usually the fault current through the
transformer for a low-side three-phase fault. For instantaneous elements, variations in settings of 125–200% are
common. For elements subject to transient overreach, a pickup of 175% of the calculated maximum low-side three-
phase symmetrical fault current generally provides sufficient margin to avoid false tripping for a low-side bus fault,
while still providing protection for severe internal faults. Due to low transient overreach of the third and fourth
overcurrent stages, you may set the instantaneous overcurrent element to 120-130% of the through-fault level, thus
ensuring stability for through faults. The instantaneous pickup setting should also consider the effects of transformer
magnetising inrush current.
In summary, there are a few application considerations to make when applying overcurrent devices to protect a
transformer:
● When applying overcurrent protection to the HV side of a power transformer it is usual to apply a high set
instantaneous overcurrent element in addition to the time delayed low-set, to reduce fault clearance times for
HV fault conditions. Typically, this will be set to approximately 1.3 times the LV fault level, so that it will only
operate for HV faults. A 30% safety margin is sufficient due to the low transient overreach of the third and
fourth overcurrent stages. Transient overreach defines the response of a relay to DC components of fault
current and is quoted as a percentage. A device with a low transient overreach will be largely insensitive to a
DC offset and may therefore be set more closely to the steady state AC waveform.
● The second requirement for this element is that it should remain inoperative during transformer energisation,
when a large primary current flows for a transient period. In most applications, the requirement to set the
device above the LV fault level will automatically result in settings that will be above the level of magnetising
inrush current.
With the third and fourth overcurrent stages, it is possible to apply settings corresponding to 40% of the peak inrush
current while maintaining stability for the condition.
Where an instantaneous element is required to accompany the time delayed protection, as described above, you
should use the third or fourth overcurrent stages as these have wider setting ranges.

P64-TM-EN-1 219
Chapter 9 - Current Protection Functions P64

9.3.6.2 PARALLEL FEEDERS

33 kV

R1 R2
OC/EF OC/EF

SBEF
R3 R4
DOC/DEF DOC/DEF
OC/EF OC/EF

11 kV

R5
OC/EF

Loads

E00603

Figure 106: Typical distribution system using parallel transformers

In the application shown in the diagram, a fault at ‘F’ could result in the operation of both R3 and R4 resulting in the
loss of supply to the 11 kV busbar. Hence, with this system configuration, it is necessary to apply directional
protection devices at these locations set to 'look into' their respective transformers. These devices should co-
ordinate with the non-directional devices, R1 and R2, to ensure discriminative operation during such fault
conditions.
In such an application, R3 and R4 may commonly require non-directional overcurrent protection elements to provide
protection to the 11 kV busbar, in addition to providing a back-up function to the overcurrent devices on the outgoing
feeders (R5).
For this application, stage 1 of the R3 and R4 overcurrent protection would be set to non-directional and time
graded with R5, using an appropriate time delay characteristic. Stage 2 could then be set to directional (looking
back into the transformer) and also have a characteristic which provides correct co-ordination with R1 and R2.
Directionality for each of the applicable overcurrent stages can be set in the directionality cells (I>1 Direction).

Note:
The principles outlined for the parallel transformer application are equally applicable for plain feeders that are operating in
parallel.

220 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.4 VOLTAGE DEPENDENT OVERCURRENT ELEMENT


Where long feeders are protected by overcurrent devices, the detection of remote phase-to-phase faults may prove
difficult due to the fact that the current pick-up of phase overcurrent elements must be set above the maximum load
current, thereby limiting the element's minimum sensitivity.
If the current seen by a local device for a remote fault condition is below its overcurrent setting, a voltage dependent
element may be used to increase the sensitivity to such faults. As a reduction in system voltage will occur during
overcurrent conditions, this may be used to enhance the sensitivity of the overcurrent protection by reducing the
pick up level.
The voltage dependant overcurrent element (either voltage controlled or voltage restrained) remains blocked unless
the associated breaker is closed. However, even when this element is blocked due to the breaker being opened, the
undervoltage element settings, V<1 Poledead Inh or V<2 Poledead Inh, can be used to block the undervoltage
element.
The voltage dependant overcurrent element is also provided with a timer hold setting, which, if set to a value other
than zero, delays the resetting of the protection element timers for this period.

9.4.1 CURRENT SETTING THRESHOLD SELECTION


The threshold setting used in the level detector depends on whether there is a Voltage Dependent condition. The
Overcurrent function selects the threshold setting according to the following diagram:

Start

Yes Use the threshold setting


Does a Voltage Dependent
calculated by the Voltage
condition exist?
Dependent function

No

Use the current threshold setting


defined in the OVERCURRENT
column

End

V00673

Figure 107: Selecting the current threshold setting

9.4.2 VCO IMPLEMENTATION


Voltage Controlled Overcurrent Protection is implemented in the OVERCURRENT column of the relevant settings
group, under the sub-heading VCONTROLED O/C.
The function is available for in two stages, 1 and 2. When VCO is enabled, the under voltage detector is used to
produce a step change in the current setting, when the voltage falls below the voltage setting VCO>1 V<Setting for
stage 1 and VCO>2 V<Setting for stage 2. To achieve this, the current setting is multiplied by a constant, which is
less than 1, set by VCO>1 k Setting for stage 1 and VCO>2 k Setting for stage 2.

P64-TM-EN-1 221
Chapter 9 - Current Protection Functions P64

Each of the stages can be set to HV Winding, LV Winding, TV Winding, T1, T2, T3, T4, or T5. If the current signal
chosen for a VCO stage does not belong to the winding where the VT is located, then the VCO element is blocked
and a configuration error alarm is asserted.
The operating characteristic of the current setting when voltage controlled mode is selected is as follows:

Current
setting

Current pickup setting

K x Current pickup setting

Measured voltage
E00642 Voltage threshold setting

Figure 108: Modification of current pickup level for voltage controlled overcurrent protection

In the P643 and P645, VCO requires an optional three-phase VT to be fitted, and in the P642 it requires that two
single-phase VTs are fitted. In P643/5, the phase-to-phase voltages are derived from the measured phase-to-
neutral voltages. In the P642, two phase-to-phase voltages are measured and the third one is calculated. In the
P642 Vab and Vbc are measured, then Vca is calculated.

9.4.3 VRO IMPLEMENTATION


Voltage Restrained Overcurrent protection is implemented in the OVERCURRENT column of the relevant settings
group, under the sub-heading V DEPENDANT O/C. The function is available in two stages 1 and 2. In voltage
restrained mode the effective operating current of the protection element is continuously variable as the applied
voltage varies between two voltage thresholds, VRO>1 V1<Setting and VRO>1 V2<Setting, as shown in the figure
below.
Each of the stages can be set to HV Winding, LV Winding, TV Winding, T1, T2, T3, T4, or T5. If the current signal
chosen for a VRO stage does not belong to the winding where the VT is located, then the VRO element is blocked
and a configuration error alarm is asserted. The operating characteristic of the current setting when voltage
restrained mode is selected is as follows:
For V > Vs1: Current setting (IS) = I>
For Vs2< V < Vs1: Current setting (IS) = K I> + (I> - K I>) {(V- Vs2) / (Vs1- Vs2)}
For V < Vs2: Current setting (IS) = K I>
Where:
I> = VRO> Curr’ Set
IS = Current setting at voltage V
V = Voltage applied to relay element
Vs1 = V<1 Set
Vs2 = V<2 Set

222 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

I> Set

KI> Set

V<2 Set V<1 Set Measured voltage

E00760

Figure 109: Modification of current pickup level for voltage restrained overcurrent protection

In P643 and P645 models, VRO requires an optional three-phase VT to be fitted, whereas, the P642 model requires
that two single-phase VTs are fitted. Also, in P643 and P645 models, the phase-to-phase voltages are derived from
the measured phase-to-neutral voltages. In the P642, two phase-to-phase voltages are measured and the third one
is calculated. In the P642 Vab and Vbc are measured, then Vca is calculated.
This protection mode is considered to be better suited to Generator-Transformer applications.

P64-TM-EN-1 223
Chapter 9 - Current Protection Functions P64

9.5 NEGATIVE SEQUENCE OVERCURRENT PROTECTION


When applying standard phase overcurrent protection, the overcurrent elements must be set significantly higher
than the maximum load current. This limits the element’s sensitivity. Most protection schemes also use an earth
fault element operating from residual current, which improves sensitivity for earth faults. However, certain faults may
arise which can remain undetected by such schemes. Negative Phase Sequence Overcurrent elements can help in
such cases.
Any unbalanced fault condition will produce a negative sequence current component. Therefore, a negative phase
sequence overcurrent element can be used for both phase-to-phase and phase-to-earth faults. Negative Phase
Sequence Overcurrent protection offers the following advantages:
● Negative phase sequence overcurrent elements are more sensitive to resistive phase-to-phase faults, where
phase overcurrent elements may not operate.
● In certain applications, residual current may not be detected by an earth fault element due to the system
configuration. For example, an earth fault element applied on the delta side of a delta-star transformer is
unable to detect earth faults on the star side. However, negative sequence current will be present on both
sides of the transformer for any fault condition, irrespective of the transformer configuration. Therefore, a
negative phase sequence overcurrent element may be used to provide time-delayed back-up protection for
any uncleared asymmetrical faults downstream.

9.5.1 NPSOC PROTECTION IMPLEMENTATION


The product provides three overcurrent elements for backup negative phase sequence overcurrent protection. Each
element provides four-stages of negative sequence overcurrent protection with independent time delay
characteristics. You can select the overcurrent element operating quantity for each of the elements with the setting
cells NPS O/C 1, NPS O/C 2 and NPS O/C 3 in the NEG SEQ O/C column of the relevant settings group. You can
set each element as T1, T2, T3, T4, T5, HV winding, LV winding or TV winding. The HV, LV and TV windings
comprise the vector sums of the CT inputs associated with a particular winding.
Stages 1, 2 provide a choice of operate and reset characteristics, where you can select between:
● A range of standard IDMT (Inverse Definite Minimum Time) curves
● DT (Definite Time)

This is achieved using the cells


● I2>(n) Function for the overcurrent operate characteristic
● I2>(n) Reset Char for the overcurrent reset characteristic (IEEE only)
where (n) is the number of the stage.
The IDMT-capable stages, (1 and 2) also provide a Timer Hold facility. This is configured using the cells
I2>(n) tReset, where (n) is the number of the stage. This is not applicable for curves based on the IEEE standard.
Stages 3 and 4 can have definite time characteristics only.

224 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.5.2 NON-DIRECTIONAL NPSOC LOGIC

NPOC1 I 2>1 Start


I2

IDMT/DT
I2>1 Current Set
& & NPOC1 I 2>1 Trip

CTS B lock

NPOC1 I nhibit

NPOC1 I 2>1 TB lk

V00674

Figure 110: Negative Sequence Overcurrent logic - non-directional operation

For Negative Phase Sequence Overcurrent Protection, the energising quanitity I2> is compared with the threshold
voltage I2>1 Current Set. If the value exceeds this setting a start signal is generated, provided there are no blocks.
5% hysteresis is built into the comparator such that the drop-off value is 0.95 x of the current set threshold.
The function can be blocked by an Inhibit signal or by a CTS blocking signal.
The start signal is fed into a timer to produce the trip signal. The timer can be blocked by the timer block signal
This diagram and description applies to each stage of each element, where x is the number of the element and n is
the number of the stage.

9.5.3 DIRECTIONAL ELEMENT


Where negative phase sequence current may flow in either direction through an IED location, such as parallel lines
or ring main systems, directional control should be used.
Directionality is achieved by comparing the angle between the negative phase sequence voltage and the negative
phase sequence current. A directional element is available for all of the negative sequence overcurrent stages. This
is found in the I2>(n) Direction cell for the relevant stage for the relevant element. It can be set to non-directional,
directional forward, or directional reverse.
A suitable characteristic angle setting (I2> Char Angle) is chosen to provide optimum performance. This setting
should be set equal to the phase angle of the negative sequence current with respect to the inverted negative
sequence voltage (–V2), in order to be at the centre of the directional characteristic.

P64-TM-EN-1 225
Chapter 9 - Current Protection Functions P64

9.5.3.1 DIRECTIONAL NPSOC LOGIC

NPOC1 I2>1 Start


I2

IDMT/DT
I2>1 Current Set
& & & NPOC1 I2>1 Trip
CTS Block

NPOC1 Inhibit

I2>1 Direction

V2

Directional
I2> V2pol Set
check

VTS Slow Block


&
I2> VTS Blocking

NPOC1 I2>1 TBlk

Note: This diagram does not show all stages. Other stages follow similar principles.

V00675

Figure 111: Negative Phase Sequence Overcurrent logic - directional operation

Directionality is achieved by comparing the angle between the negative phase sequence voltage and the negative
phase sequence current. The element may be selected to operate in either the forward or reverse direction. A
suitable characteristic angle setting (I2>Char Angle) is chosen to provide optimum performance. This setting
should be set equal to the phase angle of the negative sequence current with respect to the inverted negative
sequence voltage (–V2), in order to be at the centre of the directional characteristic.
For the negative phase sequence directional elements to operate, the device must detect a polarising voltage above
a minimum threshold, I2>V2pol Set. This must be set in excess of any steady state negative phase sequence
voltage. This may be determined during the commissioning stage by viewing the negative phase sequence
measurements in the device.
When the element is selected as directional (directional devices only), a VTS blocking option is available. When the
relevant bit is set to 1, operation of the Voltage Transformer Supervision (VTS) will block the stage. When set to 0,
the stage will revert to non-directional.

9.5.4 APPLICATION NOTES

9.5.4.1 SETTING GUIDELINES (GENERAL)


Since the negative phase sequence overcurrent protection does not respond to balanced-load or three-phase faults,
negative sequence overcurrent elements may provide the desired overcurrent protection. This is particularly
applicable to Δ−Y grounded transformers where only 58% of the secondary per unit phase-to-ground fault current
appears in any one primary phase conductor. Backup protection can be particularly difficult when the Y is
impedance-grounded.

9.5.4.2 SETTING GUIDELINES (CURRENT THRESHOLD)


A negative phase sequence element can be connected in the primary supply to the transformer and set as
sensitively as required to protect for secondary phase-to-earth or phase-to-phase faults. This function will also
provide better protection than the phase overcurrent function for internal transformer faults. The NPS overcurrent
protection should be set to coordinate with the low-side phase and earth elements for phase-to-earth and phase-to-
phase faults.

226 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

The current pick-up threshold must be set higher than the negative phase sequence current due to the maximum
normal load imbalance. This can be set practically at the commissioning stage, making use of the measurement
function to display the standing negative phase sequence current. The setting should be at least 20% above this
figure.
Where the negative phase sequence element needs to operate for specific uncleared asymmetric faults, a precise
threshold setting would have to be based on an individual fault analysis for that particular system due to the
complexities involved. However, to ensure operation of the protection, the current pick-up setting must be set
approximately 20% below the lowest calculated negative phase sequence fault current contribution to a specific
remote fault condition.

9.5.4.3 SETTING GUIDELINES (TIME DELAY)


Correct setting of the time delay for this function is vital. You should also be very aware that this element is applied
primarily to provide back-up protection to other protection devices or to provide an alarm. It would therefore
normally have a long time delay.
The time delay set must be greater than the operating time of any other protection device (at minimum fault level)
that may respond to unbalanced faults such as phase overcurrent elements and earth fault elements.

9.5.4.4 SETTING GUIDELINES (DIRECTIONAL ELEMENT)


Where negative phase sequence current may flow in either direction through an IED location, such as parallel lines
or ring main systems, directional control of the element should be employed (VT models only).
Directionality is achieved by comparing the angle between the negative phase sequence voltage and the negative
phase sequence current and the element may be selected to operate in either the forward or reverse direction. A
suitable relay characteristic angle setting (I2> Char Angle) is chosen to provide optimum performance. This setting
should be set equal to the phase angle of the negative sequence current with respect to the inverted negative
sequence voltage (–V2), in order to be at the centre of the directional characteristic.
The angle that occurs between V2 and I2 under fault conditions is directly dependent on the negative sequence
source impedance of the system. However, typical settings for the element are as follows:
● For a transmission system the relay characteristic angle (RCA) should be set equal to –60°
● For a distribution system the relay characteristic angle (RCA) should be set equal to –45°

For the negative phase sequence directional elements to operate, the device must detect a polarising voltage above
a minimum threshold, I2> V2pol Set. This must be set in excess of any steady state negative phase sequence
voltage. This may be determined during the commissioning stage by viewing the negative phase sequence
measurements in the device.

P64-TM-EN-1 227
Chapter 9 - Current Protection Functions P64

9.6 EARTH FAULT PROTECTION


Earth faults are overcurrent faults where the fault current flows to earth. Earth faults are the most common type of
fault.
Earth faults can be measured directly from the system by means of:
● A separate current Transformer (CT) located in a power system earth connection
● A residual connection of the three line CTs, where the Earth faults can be derived mathematically by
summing the three measured phase currents.

Depending on the device model, it will provide one or more of the above means for Earth fault protection.

9.6.1 EARTH FAULT PROTECTION ELEMENTS


The product provides two (P642) or four (P643/P645) earth fault elements for earth fault protection backup. Each
element provides four-stages of non-directional or directional three-phase overcurrent protection with independent
time delay characteristics. You can select the overcurrent element operating quantity for each of the elements with
the setting cells Earth Fault 1, Earth Fault 2 , Earth Fault 3 and Earth Fault 4 in the EARTH FAULT column of the
relevant settings group. You can set each element as T1, T2, T3, T4, T5, HV winding, LV winding or TV
winding.
Earth Fault 1, Earth Fault 2 and Earth Fault 3 can either measure the earth fault directly or derive it by summing
the phase currents, Earth Fault 4 (P643/P645 only) may only derive the earth fault. This depends on the settings:
EF 1 Input, EF 2 Input, EF 3 Input, which you can set to Measured or Derived and, EF 4 Input (P643/P645
only), which may only be Derived. For the derived element, the HV, LV and TV windings comprise the vector sums
of the CT inputs associated with a particular winding. For the measured elements TN1, TN2 and TN3 are used.
Each earth fault element provides four stages of Earth Fault protection with independent time delay characteristics.
Stages 1 and 2 provide a choice of operate and reset characteristics, where you can select between:
● A range of standard IDMT (Inverse Definite Minimum Time) curves
● DT (Definite Time)

This is achieved using the cells:


● IN>(n) Function for the overcurrent operate characteristics
● IN>(n) Reset Char for the overcurrent reset characteristic (IEEE only)

where (n) is the number of the stage.


Stages 1 and 2 provide a Timer Hold facility. This is configured using the cells IN>(n) tReset.
Stages 3 and 4 can have definite time characteristics only.

228 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.6.2 NON-DIRECTIONAL EARTH FAULT LOGIC

EF1 IN>1 Start


IN
IDMT/ DT
IN>1 Current
& & EF1 IN>1 Trip

CTS Block

EF1 IH2 Start


IN> Blocking &
2 H Blocks IN>1

EF 1 IN>1 TBlk

V00690

Figure 112: Non-directional EF logic (single stage)

The Earth Fault current is compared with a set threshold for each stage of each element. If it exceeds this
threshold, a Start signal is triggered, providing it is not blocked. This can be blocked by the second harmonic
blocking function, or an Inhibit Earth Fault DDB signal.
The timer can be blocked by the relevant timer block signal.
Earth Fault protection can follow the same IDMT characteristics as described in the Overcurrent Protection
Principles section. Please refer to this section for details of IDMT characteristics.
The diagram and description applies to all stages of all earth fault elements.

9.6.3 IDG CURVE


The IDG curve is commonly used for time delayed earth fault protection in the Swedish market. This curve is
available in stage 1 of the Earth Fault protection.
The IDG curve is represented by the following equation:

 I 
top = 5.8 − 1.35 log e  
 IN > Setting 
where:
top is the operating time
I is the measured current
IN> Setting is an adjustable setting, which defines the start point of the characteristic

Note:
Although the start point of the characteristic is defined by the "ΙN>" setting, the actual current threshold is a different setting
called "IDG Ιs". The "IDG Ιs" setting is set as a multiple of "ΙN>".

Note:
When using an IDG Operate characteristic, DT is always used with a value of zero for the Rest characteristic.

An additional setting "IDG Time" is also used to set the minimum operating time at high levels of fault current.

P64-TM-EN-1 229
Chapter 9 - Current Protection Functions P64

10

8 IDGIsIsSetting
IDG SettingRange
Range

time (seconds)
(seconds)
7

Operating time 5

4
Operating

3
IDG Time
IDG Time Setting
Setting Range
Range
2

0
1 10 100
I/IN>

V00611

Figure 113: IDG Characteristic

9.6.4 DIRECTIONAL ELEMENT


If Earth fault current can flow in both directions through a protected location, you will need to use a directional
overcurrent element to determine the direction of the fault. Typical systems that require such protection are parallel
feeders (both plain and transformer) and ring main systems, each of which are relatively common in distribution
networks.
A directional element is available for all of the Earth Fault stages for both Earth fault columns. These are found in
the direction setting cells for the relevant stage. They can be set to non-directional, directional forward, or directional
reverse.
The P642 has two neutral current inputs (TN1 and TN2). The P643 and P645 have three terminal current inputs
(TN1, TN2 and TN3). The earth fault overcurrent elements can be directionalised if the TN input is associated with
the winding to which the optional VT input has been connected and assigned.
For standard earth fault protection, two options are available for polarisation; Residual Voltage or Negative
Sequence.

9.6.4.1 RESIDUAL VOLTAGE POLARISATION


With earth fault protection, the polarising signal needs to be representative of the earth fault condition. As residual
voltage is generated during earth fault conditions, this quantity is commonly used to polarise directional earth fault
elements. This is known as Zero Sequence Voltage polarisation, Residual Voltage polarisation or Neutral
Displacement Voltage (NVD) polarisation.
Small levels of residual voltage could be present under normal system conditions due to system imbalances, VT
inaccuracies, device tolerances etc. For this reason, the device includes a user settable threshold (IN> VNPol set),
which must be exceeded in order for the DEF function to become operational. The residual voltage measurement
provided in the MEASUREMENTS 1 column of the menu may assist in determining the required threshold setting
during the commissioning stage, as this will indicate the level of standing residual voltage present.

Note:
Residual voltage is nominally 180° out of phase with residual current. Consequently, the DEF elements are polarised from the
"-Vres" quantity. This 180° phase shift is automatically introduced within the device.

230 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

The directional criteria with residual voltage polarisation is given below:


● Directional forward: -90° < (angle(IN) - angle(VN + 180°) - RCA) < 90°
● Directional reverse : -90° > (angle(IN) - angle(VN + 180°) - RCA) > 90°

The device derives this voltage internally from the 3-phase voltage input tha must be supplied from either a 5-limb
VT or three single-phase VTs. A three-limb VT has no path for residual flux and is therefore unsuitable to supply the
device.

9.6.4.1.1 DIRECTIONAL EARTH FAULT LOGIC WITH RESIDUAL VOLTAGE POLARISATION

EF1 IN>1 Start


IN

IDMT/DT
IN>1 Current
& & & EF1 IN>1 Trip
CTS Block

EF1 IH2 Start


IN> Blocking &
IN>1 2H Block

IN> Direction

VN

IN> VNpol Set

IN Directional
check

Low Current

VTS Slow Block


IN> Blocking &
IN>1 VTS Block

EF 1 IN>1 TBlk

This diagram does not show all stages. Other stages follow similar principles.

V00691

Figure 114: Directional EF logic with neutral voltage polarization (single stage)

Voltage Transformer Supervision (VTS) selectively blocks the directional protection or causes it to revert to non-
directional operation. When selected to block the directional protection, VTS blocking is applied to the directional
checking which effectively blocks the Start outputs as well.

9.6.4.2 NEGATIVE SEQUENCE POLARISATION


In some applications, the use of residual voltage polarisation may not be possible to achieve or it can be
problematic. For example, a suitable type of VT may be unavailable, or an HV/EHV parallel line application may
present problems with zero sequence mutual coupling.
In such situations, the problem may be solved by using Negative Phase Sequence (NPS) quantities for polarisation.
This method determines the fault direction by comparing the NPS voltage with the NPS current. The operating
quantity, however, is still residual current.
This can be used for both the derived and measured standard earth fault elements. It requires a suitable voltage
and current threshold to be set in cells IN> V2pol set and IN> I2pol set respectively.
Negative phase sequence polarising is not recommended for impedance earthed systems regardless of the type of
VT feeding the relay. This is due to the reduced earth fault current limiting the voltage drop across the negative
sequence source impedance to negligible levels. If this voltage is less than 0.5 volts the device will stop providing
directionalisation.

P64-TM-EN-1 231
Chapter 9 - Current Protection Functions P64

The directional criteria with negative sequence polarisation is given below:


● Directional forward: -90° < (angle(I2) - angle(V2 + 180°) - RCA) < 90°
● Directional reverse : -90° > (angle(I2) - angle(V2 + 180°) - RCA) > 90°

9.6.4.2.1 DIRECTIONAL EARTH FAULT LOGIC WITH NPS POLARISATION

EF1 IN>1 Start


IN
IN

IDMT/DT
IN>1 Current
& & & EF1 IN>1 Trip
CTS Block

EF1 IH2 Start


IN> Blocking &
IN>1 2H Block

IN> Direction

V2

IN> V2pol Set

I2
Directional
check
IN> I2pol Set

VTS Slow Block


IN> Blocking &
IN>1 2H Block

EF 1 IN>1 TBlk

This diagram does not show all stages. Other stages follow similar principles.
V00692

Figure 115: Directional Earth Fault logic with negative phase sequence polarisation (single stage)

Voltage Transformer Supervision (VTS) selectively blocks the directional protection or causes it to revert to non-
directional operation. When selected to block the directional protection, VTS blocking is applied to the directional
checking which effectively blocks the Start outputs as well.
The directional criteria with negative sequence polarisation is given below:
● Directional forward: -90° < (angle(I2) - angle(V2 + 180°) - RCA) < 90°
● Directional reverse : -90° > (angle(I2) - angle(V2 + 180°) - RCA) > 90°

9.6.5 APPLICATION NOTES

9.6.5.1 SETTING GUIDELINES (NON-DIRECTIONAL)


To provide backup protection for downstream equipment such as the power transformer and busbar, Standby Earth
Fault (SBEF) protection is commonly applied. This function is fulfilled by a separate earth fault current input, fed
from a single CT in the transformer earth connection. The earth fault elements may be used to provide the SBEF
function.
A Neutral Earthing Resistor (NER) is used to limit the earth fault level to a particular value. It is possible that under
an earth fault condition a flashover of the NER could occur, which could lead to a dramatic increase in the earth
fault current. For this reason, it may be appropriate to apply two-stage SBEF protection. The first stage should have
suitable current and time characteristics which coordinate with downstream earth fault protection. The second stage

232 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

may then be set with a higher current setting but with zero time delay, providing fast clearance of an earth fault
which gives rise to an NER flashover.
The remaining two stages are available for customer-specific applications.

9.6.5.2 SETTING GUIDELINES (DIRECTIONAL ELEMENT)


With directional earth faults, the residual current under fault conditions lies at an angle lagging the polarising
voltage. Hence, negative RCA settings are required for DEF applications. This is set in the cell I> Char Angle in the
relevant earth fault menu.
We recommend the following RCA settings:
● Resistance earthed systems: 0°
● Distribution systems (solidly earthed): -45°
● Transmission systems (solidly earthed): -60°

P64-TM-EN-1 233
Chapter 9 - Current Protection Functions P64

9.7 SECOND HARMONIC BLOCKING

9.7.1 SECOND HARMONIC BLOCKING IMPLEMENTATION


A separate second harmonic blocking function is applied to the following overcurrent protection types:
● Phase Overcurrent protection (Overcurrent 1, Overcurrent 2 and Overcurrent 3)
● Earth Fault protection elements (Earth Fault 1, Earth Fault 2 and Earth Fault 3)
● There is no second harmonic blocking for Negative Phase Sequence Overcurrent protection

Second harmonic blocking is applicable to all stages of each of the elements. For POC, 2nd harmonic blocking can
be applied to each phase individually (phase segregated), or to all three phases at once (cross-block).
The function works by identifying and measuring the inrush currents present at switch on. It does this by comparing
the value of the second harmonic current components to the value of the fundamental component. If this ratio
exceeds the set thresholds, then the blocking signal is generated. The threshold is defined by the settings IH2 I>
Set and IH2 IN> Set for Phase Overcurrent protection and Earth Fault protection respectively.
We only want the function to block the protection if the fundamental current component is within the normal range. If
this exceeds the normal range, then this is indicative of a fault, which must be protected. For this reason there is
another settable trigger IH2 IN> Unblock for Phase Overcurrent protection and IH2 I> Unblock for Earth fault
protection, which when exceeded, stops the 2nd harmonic blocking function.
Each overcurrent protection element has an I>Blocking setting with which the stages to be blocked can be
selected.

234 P64-TM-EN-1
P64 Chapter 9 - Current Protection Functions

9.7.2 SECOND HARMONIC BLOCKING LOGIC

&
IA fundament al
& POC1 IH2 Any St
IH2 I> Unblock
1
&

& POC1 IA2H Start

Low current (hard-coded)


POC1 IB2H Start

IA 2nd harm / IA f und


IA 2nd harmonic
POC1 IC2H Start

IH2 I> Set

IA fundament al

IH2 I> Unblock


&

&
Low current (hard-coded)

IB 2nd harm / IB f und


IB 2nd harmonic

IH2 I> Set

IC 2nd harmonic

IH2 I> Unblock


&

&
Low current (hard-coded)

IC 2nd harm / I C fund


IC 2nd harmonic
Note: This diagram does not show all stages. Other stages follow similar principles.
IH2 I> Set

V00703

Figure 116: Phase overcurrent 2nd harmonic blocking Logic

P64-TM-EN-1 235
Chapter 9 - Current Protection Functions P64

9.7.3 EF SECOND HARMONIC BLOCKING LOGIC

IN fundamental

IH2 IN> Unblock &


& EF1 IH2 Start

Low current (hard-coded)

IA 2nd harm / IA f und


IN 2nd harmonic

IH2 IN> set

Note: This diagram does not show all stages. Other stages follow similar principles.
V00704

Figure 117: Earth fault 2nd harmonic blocking Logic

9.7.4 APPLICATION NOTES

9.7.4.1 SETTING GUIDELINES


During the energization period, the second harmonic component of the inrush current may be as high as 70%. The
second harmonic level may be different for each phase, which is why phase segregated blocking is available.
If the setting is too low, the 2nd harmonic blocking may prevent tripping during some internal transformer faults. If
the setting is too high, the blocking may not operate for low levels of inrush current which could result in undesired
tripping of the overcurrent element during the energization period. In general, a setting of 15% to 20% is suitable.

236 P64-TM-EN-1
CHAPTER 10

CB FAIL PROTECTION
Chapter 10 - CB Fail Protection P64

10.1 CHAPTER OVERVIEW


The device provides a Circuit Breaker Fail Protection function. This chapter describes the operation of this function
including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 238
Circuit Breaker Fail Protection 239
Circuit Breaker Fail Implementation 240
Circuit Breaker Fail Logic 242
Application Notes 244

238 P64-TM-EN-1
P64 Chapter 10 - CB Fail Protection

10.2 CIRCUIT BREAKER FAIL PROTECTION


When a fault occurs, one or more protection devices will operate and issue a trip command to the relevant circuit
breakers. Operation of the circuit breaker is essential to isolate the fault and prevent, or at least limit, damage to the
power system. For transmission and sub-transmission systems, slow fault clearance can also threaten system
stability.
For these reasons, it is common practice to install Circuit Breaker Failure protection (CBF). CBF protection monitors
the circuit breaker and establishes whether it has opened within a reasonable time. If the fault current has not been
interrupted following a set time delay from circuit breaker trip initiation, the CBF protection will operate, whereby the
upstream circuit breakers are back-tripped to ensure that the fault is isolated.
CBF operation can also reset all start output contacts, ensuring that any blocks asserted on upstream protection are
removed.

P64-TM-EN-1 239
Chapter 10 - CB Fail Protection P64

10.3 CIRCUIT BREAKER FAIL IMPLEMENTATION


Depending on the P64 model (P642, P643, P645), up to five independent sets of circuit breaker failure settings are
available, supporting one phase current and one earth undercurrent function for each set. Each CB Failure set can
be enabled or disabled by the settings T1 CBF Status, T2 CBF Status, T3 CBF Status, T4 CBF Status and T5
CBF Status respectively.
You can enable or disable each Earth undercurrent element with the IN< Status setting. If enabled, you can set
each earth undercurrent element as measured or derived using the IN< Input setting. When enabled, it can be set
as measured or derived. Depending on the model, you can use single phase CTs connected to the three neutral CT
connections TN1, TN2 and TN3 for CB failure function (see wiring diagram). You define this with the IN< Terminal
setting.

10.3.1 CIRCUIT BREAKER FAIL TIMERS


The circuit breaker failure protection incorporates two timers, CB Fail 1 Timer and CB Fail 2 Timer, allowing
configuration for the following scenarios:
● Simple CBF, where only CB Fail 1 Timer is enabled. For any protection trip, the CB Fail 1 Timer is started,
and normally reset when the circuit breaker opens to isolate the fault. If breaker opening is not detected, the
CB Fail 1 Timer times out and closes an output contact assigned to breaker fail (using the programmable
scheme logic). This contact is used to back-trip upstream switchgear, generally tripping all infeeds connected
to the same busbar section.
● A retripping scheme, plus delayed back-tripping. Here, CB Fail 1 Timer is used to issue a trip command to a
second trip circuit of the same circuit breaker. This requires the circuit breaker to have duplicate circuit
breaker trip coils. This mechanism is known as retripping. If retripping fails to open the circuit breaker, a back-
trip may be issued following an additional time delay. The back-trip uses CB Fail 2 Timer, which was also
started at the instant of the initial protection element trip.

You can configure the CBF elements CB Fail 1 Timer and CBF Fail 2 Timer to operate for trips triggered by
protection elements within the device. Alternatively you can use an external protection trip by allocating one of the
opto-inputs to the External Trip DDB signal in the PSL.
You can reset the CBF from a breaker open indication (from the pole dead logic) or from a protection reset. In these
cases resetting is only allowed if the undercurrent elements have also been reset. The resetting mechanism is
determined by the settings NonIProt Rst and Ext Prot Rst.
The resetting options are summarised in the following table:
Initiation (Menu Selectable) CB Fail Timer Reset Mechanism
IA< operates AND IB< operates AND IC< operates AND IN< operates
Current based protection (e.g.50/51/46/21/87)
or through Ext Rst DDB in PSL
Sensitive Earth Fault element ISEF< Operates or Ext Rst SEF DDB
Three options are available:
All I< and IN< elements operate or Ext Rst CBF DDB
Non-current based protection (e.g. 27/59/81/32L) Protection element reset AND (all I< and IN< elements operate or Ext
Rst DDB
CB open (all 3 poles) AND all I< and IN< elements operate
Three options are available.
All I< and IN< elements operate
External protection
External trip reset AND all I< and IN< elements operate
CB open (all 3 poles) AND all I< and IN< elements operate

240 P64-TM-EN-1
P64 Chapter 10 - CB Fail Protection

10.3.2 ZERO CROSSING DETECTION


When there is a fault and the circuit breaker interrupts the CT primary current, the flux in the CT core decays to a
residual level. This decaying flux introduces a decaying DC current in the CT secondary circuit known as
subsidence current. The closer the CT is to its saturation point, the higher the subsidence current.
The time constant of this subsidence current depends on the CT secondary circuit time constant and it is generally
long. If the protection clears the fault, the CB Fail function should reset fast to avoid maloperation due to the
subsidence current. To compensate for this the device includes a zero-crossing detection algorithm, which ensures
that the CB Fail re-trip and back-trip signals are not asserted while subsidence current is flowing. If all the samples
within half a cycle are greater than or smaller than 0 A (10 mS for a 50 Hz system), then zero crossing detection is
asserted, thereby blocking the operation of the CB Fail function. The zero-crossing detection algorithm is used after
the circuit breaker in the primary system has opened ensuring that the only current flowing in the AC secondary
circuit is the subsidence current.
This zero-crossing detection algorithm considers the current inputs T1, T2, T3, T4 and T5 on a per phase basis. If
IN< Input is set as measured, the zero crossing detection algorithm considers the current inputs TN1, TN2 and
TN3. If IN< Input is set as derived, the zero crossing detection algorithm considers the current inputs T1, T2, T3,
T4 and T5. If more than 12 consecutive samples are greater than 0A or more than 12 consecutive samples are
smaller than 0A, then a zero crossing detection condition is asserted, which blocks the operation of the circuit
breaker failure function. The zero crossing detection is asserted after the breaker in the primary system has opened
to ensure that the current flowing in the AC secondary circuit is just the subsidence current.

P64-TM-EN-1 241
Chapter 10 - CB Fail Protection P64

10.4 CIRCUIT BREAKER FAIL LOGIC

Any Trip
1 S
Extern CB1 Trip Q
R 1 Trip St ate
T1 IA< Start

T1 IB< Start
&
T1 IC< St art

T1 IN< St art

V<1 Trip & S


Q
V>1 Trip R

VN>1 Trip

F>1 Trip

F<1 Trip 1 1 Reset State

CLI1 Trip

RTD 1 Trip &

Top Oil >1 Trip 1

Hot Spot >1 Trip &


Volt Prot Reset
Prot Reset & I<
I< Only &
CB Open & I<

CB1 Closed
1
&

Note on SR Latches
S All latches are reset dominant and are triggered on the
positive edge. If the edge occurs while the reset is active,
Q
the detect ion of t he edge is delayed until the reset
Ext Prot Reset & R becomes non-active.
Prot Reset & I<
I< Only 1
CB Open & I<
&
Extern CB1 Trip

&

1
&

V00694

Figure 118: Circuit Breaker Fail Logic - part 1

242 P64-TM-EN-1
P64 Chapter 10 - CB Fail Protection

CT Select ion Alm


1
CT1 Excluded &
& CB1 ReTrip 3ph

CB Fail 1 Status
Enabled
Disabled 1

Trip St ate

CB Fail 2 Status
Enabled &
& CB1 BkTrip 3ph
Disabled

Reset State
1

T1 IA< Start
1
CT1A ZCD

T1 IB< Start
1
CT1B ZCD
&
T1 IC< St art
1
CT1C ZCD
Note: This diagram does not show all stages. Other stages follow similar principles.

T1 IN< St art
1
CT1 In ZCD

V00695

Figure 119: Circuit Breaker Fail Logic - part 2

P64-TM-EN-1 243
Chapter 10 - CB Fail Protection P64

10.5 APPLICATION NOTES

10.5.1 RESET MECHANISMS FOR CB FAIL TIMERS


It is common practise to use low set undercurrent elements to indicate that circuit breaker poles have interrupted
the fault or load current. This covers the following situations:
● Where circuit breaker auxiliary contacts are defective, or cannot be relied on to definitely indicate that the
breaker has tripped.
● Where a circuit breaker has started to open but has become jammed. This may result in continued arcing at
the primary contacts, with an additional arcing resistance in the fault current path. Should this resistance
severely limit fault current, the initiating protection element may reset. Therefore, reset of the element may
not give a reliable indication that the circuit breaker has opened fully.

For any protection function requiring current to operate, the device uses operation of undercurrent elements to
detect that the necessary circuit breaker poles have tripped and reset the CB fail timers. However, the undercurrent
elements may not be reliable methods of resetting CBF in all applications. For example:
● Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a line connected voltage transformer. Here, I< only gives a reliable reset method if the
protected circuit would always have load current flowing. In this case, detecting drop-off of the initiating
protection element might be a more reliable method.
● Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a busbar connected voltage transformer. Again using I< would rely on the feeder
normally being loaded. Also, tripping the circuit breaker may not remove the initiating condition from the
busbar, and so drop-off of the protection element may not occur. In such cases, the position of the circuit
breaker auxiliary contacts may give the best reset method.

10.5.2 SETTING GUIDELINES (CB FAIL TIMER)


The following timing chart shows the CB Fail timing during normal and CB Fail operation. The maximum clearing
time should be less than the critical clearing time which is determined by a stability study. The CB Fail back-up trip
time delay considers the maximum CB clearing time, the CB Fail reset time plus a safety margin. Typical CB
clearing times are 1.5 or 3 cycles. The CB Fail reset time should be short enough to avoid CB Fail back-trip during
normal operation. Phase and ground undercurrent elements must be asserted for the CB Fail to reset. The
assertion of the undercurrent elements might be delayed due to the subsidence current that might be flowing
through the secondary AC circuit.

244 P64-TM-EN-1
P64 Chapter 10 - CB Fail Protection

CBF resets:
1. Undercurrent element asserts
2. Undercurrent element asserts and the
breaker status indicates an open position
3. Protection resets and the undercurrent
Fault occurs element asserts

CBF Safety
Protection Maximum breaker reset margin
Normal operating time clearing time time time
operation
t

Protection Local Bks clearing


Breaker failure operating time CBF back-up trip time delay time
operation

Local 86 Remote CB
operating clearing time
time

Maximum fault clearing time

V00693 Fault occurs

Figure 120: CB Fail timing

The following examples consider direct tripping of a 2-cycle circuit breaker. Typical timer settings to use are as
follows:
CB Fail Reset Typical Delay For 2 Cycle Circuit
tBF Time Delay
Mechanism Breaker
Initiating element reset CB interrupting time + element reset time (max.) + error in 50 + 50 + 10 + 50 = 160 ms
tBF timer + safety margin
CB open CB auxiliary contacts opening/ closing time (max.) + error in 50 + 10 + 50 = 110 ms
tBF timer + safety margin
Undercurrent elements CB interrupting time + undercurrent element (max.) + safety 50 + 25 + 50 = 125 ms
margin operating time

Note:
All CB Fail resetting involves the operation of the undercurrent elements. Where element resetting or CB open resetting is
used, the undercurrent time setting should still be used if this proves to be the worst case.
Where auxiliary tripping relays are used, an additional 10-15 ms must be added to allow for trip relay operation.

10.5.3 SETTING GUIDELINES (UNDERCURRENT)


The phase undercurrent settings (I<) must be set less than load current to ensure that I< operation correctly
indicates that the circuit breaker pole is open. A typical setting for overhead line or cable circuits is 20%In. Settings
of 5% of In are common for generator CB Fail.
The earth fault undercurrent elements must be set less than the respective trip. For example:
IN< = (IN> trip)/2

P64-TM-EN-1 245
Chapter 10 - CB Fail Protection P64

246 P64-TM-EN-1
CHAPTER 11

VOLTAGE PROTECTION FUNCTIONS


Chapter 11 - Voltage Protection Functions P64

11.1 CHAPTER OVERVIEW


The device provides a wide range of voltage protection functions. This chapter describes the operation of these
functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 248
Undervoltage Protection 249
Overvoltage Protection 252
Residual Overvoltage Protection 255
Negative Sequence Overvoltage Protection 259

248 P64-TM-EN-1
P64 Chapter 11 - Voltage Protection Functions

11.2 UNDERVOLTAGE PROTECTION


Undervoltage conditions may occur on a power system for a variety of reasons, some of which are outlined below:
● Undervoltage conditions can be related to increased loads, whereby the supply voltage will decrease in
magnitude. This situation would normally be rectified by voltage regulating equipment such as AVRs (Auto
Voltage Regulators) or On Load Tap Changers. However, failure of this equipment to bring the system voltage
back within permitted limits leaves the system with an undervoltage condition, which must be cleared.
● If the regulating equipment is unsuccessful in restoring healthy system voltage, then tripping by means of an
undervoltage element is required.
● Faults occurring on the power system result in a reduction in voltage of the faulty phases. The proportion by
which the voltage decreases is dependant on the type of fault, method of system earthing and its location.
Consequently, co-ordination with other voltage and current-based protection devices is essential in order to
achieve correct discrimination.
● Complete loss of busbar voltage. This may occur due to fault conditions present on the incomer or busbar
itself, resulting in total isolation of the incoming power supply. For this condition, it may be necessary to
isolate each of the outgoing circuits, such that when supply voltage is restored, the load is not connected.
Therefore, the automatic tripping of a feeder on detection of complete loss of voltage may be required. This
can be achieved by a three-phase undervoltage element.
● Where outgoing feeders from a busbar are supplying induction motor loads, excessive dips in the supply may
cause the connected motors to stall, and should be tripped for voltage reductions that last longer than a pre-
determined time.

11.2.1 UNDERVOLTAGE PROTECTION IMPLEMENTATION


Undervoltage Protection is implemented in the VOLT PROTECTION column of the relevant settings group. The
Undervoltage parameters are contained within the sub-heading UNDERVOLTAGE.
The product provides two stages of Undervoltage protection with independent time delay characteristics.
Stage 1 provides a choice of operate characteristics, where you can select between:
● An IDMT characteristic
● DT (Definite Time)

You set this using the V<1 Function setting.


The IDMT characteristic is defined by the following formula:
t = K/( M-1)
where:
● K = Time multiplier setting
● t = Operating time in seconds
● M = Measured voltage / IED setting voltage (V<(n) Voltage Set)

The undervoltage stages can be configured either as phase-to-neutral or phase-to-phase voltages in the V<
Measur't Mode cell.
There is no Timer Hold facility for Undervoltage.
Stage 2 can have definite time characteristics only. This is set in the V<2 Status cell.
Outputs are available for single or three-phase conditions via the V< Operate Mode cell for each stage.

P64-TM-EN-1 249
Chapter 11 - Voltage Protection Functions P64

11.2.2 UNDERVOLTAGE PROTECTION LOGIC


V< Mea su r't Mo de

V<1 Start A/A B

V<1 Voltag e Set & t


& V<1 Trip A/ AB
0
V<1 Time Delay

V< Mea su r't Mo de

V<1 Start B/B C

V<1 Voltag e Set & t


& V<1 Trip B/ BC
0
V<1 Time Delay

V< Mea su r't Mo de

V<1 Start C/CA

V<1 Voltag e Set & t


& V<1 Trip C/CA
0
V<1 Time Delay
1
&
All Poles De ad
1 V<1 Start
V<1 Poled ead I nh &
& &
Ena bled

VTS Fast Block 1


&
V<1 Timer Blo ck 1 V<1 Trip
&
V< Operate Mode &
Any Ph ase
Thre e Pha se

Note: This diagram doe s not show a ll stag es. Other stag es follow similar prin ciples.
VTS Fast Block only ap plies f or d irectiona l mode ls.
V00803

Figure 121: Undervoltage - single and three phase tripping mode (single stage)

The Undervoltage protection function detects when the voltage magnitude for a certain stage falls short of a set
threshold. If this happens a Start signal, signifying the "Start of protection", is produced. This Start signal can be
blocked by the VTS Fast Block signal and an All Poles Dead signal. This Start signal is applied to the timer
module to produce the Trip signal, which can be blocked by the undervoltage timer block signal (V<(n) Timer
Block). For each stage, there are three Phase undervoltage detection modules, one for each phase. The three
Start signals from each of these phases are OR'd together to create a 3-phase Start signal (V<(n) Start), which can
be be activated when any of the three phases start (Any Phase), or when all three phases start (Three Phase),
depending on the chosen V< Operate Mode setting.
The outputs of the timer modules are the trip signals which are used to drive the tripping output relay. These tripping
signals are also OR'd together to create a 3-phase Trip signal, which are also controlled by the V< Operate Mode
setting.
If any one of the above signals is low, or goes low before the timer has counted out, the timer module is inhibited
(effectively reset) until the blocking signal goes high.
In some cases, we do not want the undervoltage element to trip; for example, when the protected feeder is de-
energised, or the circuit breaker is opened, an undervoltage condition would obviously be detected, but we would
not want to start protection. To cater for this, an All Poles Dead signal blocks the Start signal for each phase. This
is controlled by the V<Poledead Inh cell, which is included for each of the stages. If the cell is enabled, the relevant
stage will be blocked by the integrated pole dead logic. This logic produces an output when it detects either an open

250 P64-TM-EN-1
P64 Chapter 11 - Voltage Protection Functions

circuit breaker via auxiliary contacts feeding the opto-inputs or it detects a combination of both undercurrent and
undervoltage on any one phase.

11.2.3 APPLICATION NOTES

11.2.3.1 UNDERVOLTAGE SETTING GUIDELINES


In most applications, undervoltage protection is not required to operate during system earth fault conditions. If this is
the case you should select phase-to-phase voltage measurement, as this quantity is less affected by single-phase
voltage dips due to earth faults.
The voltage threshold setting for the undervoltage protection should be set at some value below the voltage
excursions that may be expected under normal system operating conditions. This threshold is dependant on the
system in question but typical healthy system voltage excursions may be in the order of 10% of nominal value.
The same applies to the time setting. The required time delay is dependant on the time for which the system is able
to withstand a reduced voltage.
If motor loads are connected, then a typical time setting may be in the order of 0.5 seconds.
Stage 1 is used for tripping and can be disabled, or selected as IDMT or DT. You can set stage 2 as an alarm stage
to warn the user of unusual voltage conditions.
If only a single-phase VT signal is available and you require an undervoltage alarm, you must set the VTS status
signal in the SUPERVISION column to Indication or disabled.

P64-TM-EN-1 251
Chapter 11 - Voltage Protection Functions P64

11.3 OVERVOLTAGE PROTECTION


Overvoltage conditions are generally related to loss of load conditions, whereby the supply voltage increases in
magnitude. This situation would normally be rectified by voltage regulating equipment such as AVRs (Auto Voltage
Regulators) or On Load Tap Changers. However, failure of this equipment to bring the system voltage back within
permitted limits leaves the system with an overvoltage condition which must be cleared.

Note:
During earth fault conditions on a power system there may be an increase in the healthy phase voltages. Ideally, the system
should be designed to withstand such overvoltages for a defined period of time.

11.3.1 OVERVOLTAGE PROTECTION IMPLEMENTATION


Overvoltage Protection is implemented in the VOLT PROTECTION column of the relevant settings group. The
Overvoltage parameters are contained within the sub-heading OVERVOLTAGE.
The product provides two stages of overvoltage protection with independent time delay characteristics.
Stage 1 provides a choice of operate characteristics, where you can select between:
● An IDMT characteristic
● DT (Definite Time)

You set this using the V>1 Function setting.


The IDMT characteristic is defined by the following formula:
t = K/( M - 1)
where:
● K = Time multiplier setting
● t = Operating time in seconds
● M = Measured voltage setting voltage (V>(n) Voltage Set)

The overvoltage stages can be configured either as phase-to-neutral or phase-to-phase voltages in the V>
Measur't Mode cell.
There is no Timer Hold facility for Overvoltage.
Stage 2 can have definite time characteristics only. This is set in the V>2 Status cell.
Outputs are available for single or three-phase conditions via the V> Operate Mode cell for each stage.

252 P64-TM-EN-1
P64 Chapter 11 - Voltage Protection Functions

11.3.2 OVERVOLTAGE PROTECTION LOGIC


V> Mea su r't Mo de
V>1 Start A/A B

t
V>1 Voltag e Set & V>1 Trip A/ AB
0

V>1 Time Delay

V> Mea su r't Mo de


V>1 Start B/B C

t
V>1 Voltag e Set & V>1 Trip B/ BC
0

V>1 Time Delay

V> Mea su r't Mo de


V>1 Start C/CA

t
V>1 Voltag e Set & V>1 Trip C/CA
0

V>1 Time Delay 1


&
1 V>1 Start
&
&

1
&
V>1 Timer Blo ck 1 V>1 Trip
&
V> Operate mode &
Any Ph ase
Thre e Pha se
Notes: This diagram does n ot show all stage s. Other stage s follo w similar principles.
VTS Fast Block only ap plies f or d irectiona l mode ls.
V00 804

Figure 122: Overvoltage - single and three phase tripping mode (single stage)

The Overvoltage protection function detects when the voltage magnitude for a certain stage exceeds a set
threshold. If this happens a Start signal, signifying the "Start of protection", is produced. This Start signal can be
blocked by the VTS Fast Block signal. This start signal is applied to the timer module to produce the Trip signal,
which can be blocked by the overvoltage timer block signal (V>(n) Timer Block). For each stage, there are three
Phase overvoltage detection modules, one for each phase. The three Start signals from each of these phases are
OR'd together to create a 3-phase Start signal (V>(n) Start), which can then be activated when any of the three
phases start (Any Phase), or when all three phases start (Three Phase), depending on the chosen V> Operate
Mode setting.
The outputs of the timer modules are the trip signals which are used to drive the tripping output relay. These tripping
signals are also OR'd together to create a 3-phase Trip signal, which are also controlled by the V> Operate Mode
setting.
If any one of the above signals is low, or goes low before the timer has counted out, the timer module is inhibited
(effectively reset) until the blocking signal goes high.

P64-TM-EN-1 253
Chapter 11 - Voltage Protection Functions P64

11.3.3 APPLICATION NOTES

11.3.3.1 OVERVOLTAGE SETTING GUIDELINES


The provision of multiple stages and their respective operating characteristics allows for a number of possible
applications:
● Definite Time can be used for both stages to provide the required alarm and trip stages.
● Use of the IDMT characteristic allows grading of the time delay according to the severity of the overvoltage.
As the voltage settings for both of the stages are independent, the second stage could then be set lower than
the first to provide a time-delayed alarm stage.
● If only one stage of overvoltage protection is required, or if the element is required to provide an alarm only,
the remaining stage may be disabled.

This type of protection must be co-ordinated with any other overvoltage devices at other locations on the system.
Transformers can typically withstand a 110% overvoltage condition continuously. The withstand times for higher
overvoltages should be declared by the transformer manufacturer.
To prevent operation during earth faults, the element should operate from the phase-phase voltages. To achieve
this, you set V>1 Measur’t Mode to Phase-Phase and V>1 Operating Mode set to Three-phase. You should
typically set the overvoltage threshold V>1 Voltage Set to 100% - 120% of the nominal phase‑phase voltage. You
should also set the time delay to prevent unwanted tripping of the delayed overvoltage protection function due to
transient over voltages, which do not pose a risk to the transformer. A typical delay setting would be 1 s - 3 s, with a
longer delay being applied for lower voltage threshold settings.
The second stage can be used to provide instantaneous high-set over voltage protection. The typical threshold
setting to be applied, V>2 Voltage Set, would typically be 130 - 150% of the nominal phase‑phase voltage. For
instantaneous operation, you should set the time delay to 0 s.
If you select phase-to-neutral operation, take care to ensure that the element will grade with other protections during
earth faults, where the phase-neutral voltage can rise significantly.
This type of protection must be coordinated with any other overvoltage devices at other locations on the system.

254 P64-TM-EN-1
P64 Chapter 11 - Voltage Protection Functions

11.4 RESIDUAL OVERVOLTAGE PROTECTION


On a healthy three-phase power system, the sum of the three-phase to earth voltages is nominally zero, as it is the
vector sum of three balanced vectors displaced from each other by 120°. However, when an earth fault occurs on
the primary system, this balance is upset and a residual voltage is produced. This condition causes a rise in the
neutral voltage with respect to earth. Consequently this type of protection is also commonly referred to as 'Neutral
Voltage Displacement' or NVD for short.
This residual voltage is derived (from the phase voltages). Derived values are used where the model does not
support measured functionality.
This offers an alternative means of earth fault detection, which does not require any measurement of current. This
may be particularly advantageous in high impedance earthed or insulated systems, where the provision of core
balanced current transformers on each feeder may be either impractical, or uneconomic, or for providing earth fault
protection for devices with no current transformers.

11.4.1 RESIDUAL OVERVOLTAGE PROTECTION IMPLEMENTATION


Residual Overvoltage Protection is implemented in the RESIDUAL O/V NVD column of the relevant settings group.
Some applications require more than one stage. For example an insulated system may require an alarm stage and
a trip stage. It is common in such a case for the system to be designed to withstand the associated healthy phase
overvoltages for a number of hours following an earth fault. In such applications, an alarm is generated soon after
the condition is detected, which serves to indicate the presence of an earth fault on the system. This gives time for
system operators to locate and isolate the fault. The second stage of the protection can issue a trip signal if the fault
condition persists.
The product provides two stages of Derived Residual Overvoltage protection with independent time delay
characteristics.
Stage 1 provides a choice of operate characteristics, where you can select between:
● An IDMT characteristic
● DT (Definite Time)

The IDMT characteristic is defined by the following formula:


t = K/( M - 1)
where:
● K= Time multiplier setting
● t = Operating time in seconds
● M = Derived residual voltage setting voltage (VN> Voltage Set)

You set this using the VN>1 Function setting.


Stage 1 also provides a Timer Hold facility.
Stage 2 can have definite time characteristics only. This is set in the VN>2 status cell
The device derives the residual voltage internally from the three-phase voltage inputs supplied from either a 5-limb
VT or three single-phase VTs. These types of VT design provide a path for the residual flux and consequently
permit the device to derive the required residual voltage. In addition, the primary star point of the VT must be
earthed. Three-limb VTs have no path for residual flux and are therefore unsuitable for this type of protection.

P64-TM-EN-1 255
Chapter 11 - Voltage Protection Functions P64

11.4.2 RESIDUAL OVERVOLTAGE LOGIC

804
VN>1 Start

VN

VN>1 Voltage Set & 700


& IDMT/DT VN>1 Trip
832
VTS Fast Block
475
Inhibit VN>1
418
VN>1 Timer Blk
Note: This diagram does not show all stages. Other stages follow similar principles.
VTS Fast Block only applies for directional models. V00802

Figure 123: Residual Overvoltage logic

The Residual Overvoltage module (VN>) is a level detector that detects when the voltage magnitude exceeds a set
threshold, for each stage. When this happens, the comparator output produces a Start signal (VN>(n) Start), which
signifies the "Start of protection". This can be blocked by a VTS Fast block signal. This Start signal is applied to
the timer module. The output of the timer module is the VN> (n) Trip signal which is used to drive the tripping output
relay.

11.4.3 APPLICATION NOTES

11.4.3.1 CALCULATION FOR SOLIDLY EARTHED SYSTEMS


Consider a Phase-A to Earth fault on a simple radial system.

256 P64-TM-EN-1
P64 Chapter 11 - Voltage Protection Functions

E S IED F
ZS ZL

VA
VA

VC VB VC VB VC VB

VA VRES
VRES
VA
VB VB VB

VC VC VC

VRES = ZS0
X3E
2ZS1 + ZS0 + 2ZL1 + ZL0

E00800

Figure 124: Residual voltage for a solidly earthed system

As can be seen from the above diagram, the residual voltage measured on a solidly earthed system is solely
dependant on the ratio of source impedance behind the protection to the line impedance in front of the protection,
up to the point of fault. For a remote fault far away, the ZS/ZL: ratio will be small, resulting in a correspondingly small
residual voltage. Therefore, the protection only operates for faults up to a certain distance along the system. The
maximum distance depends on the device setting.

11.4.3.2 CALCULATION FOR IMPEDANCE EARTHED SYSTEMS


Consider a Phase-A to Earth fault on a simple radial system.

P64-TM-EN-1 257
Chapter 11 - Voltage Protection Functions P64

E S IED F
ZS ZL
N

ZE

VA - G
S R VA - G
G,F G,F
G,F

VC - G VC - G VC - G
VB - G VB - G VB - G

VRES VRES VRES

VB - G VB - G VB - G
VA - G VA - G
VC - G VC - G VC - G

ZS0 + 3ZE
VRES = X3E
2ZS1 + ZS0 + 2ZL1 + ZL0 + 3Z
E

E00801

Figure 125: Residual voltage for an impedance earthed system

An impedance earthed system will always generate a relatively large degree of residual voltage, as the zero
sequence source impedance now includes the earthing impedance. It follows then that the residual voltage
generated by an earth fault on an insulated system will be the highest possible value (3 x phase-neutral voltage), as
the zero sequence source impedance is infinite.

11.4.3.3 SETTING GUIDELINES


The voltage setting applied to the elements is dependant on the magnitude of residual voltage that is expected to
occur during the earth fault condition. This in turn is dependant on the method of system earthing employed.
Also, you must ensure that the protection setting is set above any standing level of residual voltage that is present
on the system.

258 P64-TM-EN-1
P64 Chapter 11 - Voltage Protection Functions

11.5 NEGATIVE SEQUENCE OVERVOLTAGE PROTECTION


Where an incoming feeder is supplying rotating plant equipment such as an induction motor, correct phasing and
balance of the supply is essential. Incorrect phase rotation will result in connected motors rotating in the wrong
direction. For directionally sensitive applications, such as elevators and conveyor belts, it is unacceptable to allow
this to happen.
Imbalances on the incoming supply cause negative phase sequence voltage components. In the event of incorrect
phase rotation, the supply voltage would effectively consist of 100% negative phase sequence voltage only.

11.5.1 NEGATIVE SEQUENCE OVERVOLTAGE IMPLEMENTATION


Negative Sequence Overvoltage Protection is implemented in the NEG SEQUENCE O/V column of the relevant
settings group.
The device includes one Negative Phase Sequence Overvoltage element with a single stage. Only Definite time is
possible.
This element monitors the input voltage rotation and magnitude (normally from a bus connected voltage
transformer) and may be interlocked with the motor contactor or circuit breaker to prevent the motor from being
energised whilst incorrect phase rotation exists.
The element is enabled using the V2> status cell.

11.5.2 NEGATIVE SEQUENCE OVERVOLTAGE LOGIC

V2> Start

V2
Start
V2> Voltage Set & & DT V2> Trip
Counter

VTS Fast Block

V2> Accelerate
V00805

Figure 126: Negative Sequence Overvoltage logic

The Negative Voltage Sequence Overvoltage module (V2>) is a level detector that detects when the voltage
magnitude exceeds a set threshold. When this happens, the comparator output Overvoltage Module produces a
Start signal (V2> Start), which signifies the "Start of protection". This can be blocked by a VTS Fast block signal.
This Start signal is applied to the DT timer module. The output of the DT timer module is the V2> Trip signal which
is used to drive the tripping output relay.
The V2> Accelerate signal accelerates the operating time of the function, by reducing the number of confirmation
cycles needed to start the function. At 50 Hz, this means the protection Start is reduced by 20 ms.

11.5.3 APPLICATION NOTES

11.5.3.1 SETTING GUIDELINES


The primary concern is usually the detection of incorrect phase rotation (rather than small imbalances), therefore a
sensitive setting is not required. The setting must be higher than any standing NPS voltage, which may be present
due to imbalances in the measuring VT, device tolerances etc.
A setting of approximately 15% of rated voltage may be typical.

P64-TM-EN-1 259
Chapter 11 - Voltage Protection Functions P64

Note:
Standing levels of NPS voltage (V2) are displayed in the V2 Magnitude cell of the MEASUREMENTS 1 column.

The operation time of the element depends on the application, but a typical setting would be in the region of 5
seconds.

260 P64-TM-EN-1
CHAPTER 12

FREQUENCY PROTECTION FUNCTIONS


Chapter 12 - Frequency Protection Functions P64

12.1 CHAPTER OVERVIEW


The device provides a range of frequency protection functions. This chapter describes the operation of these
functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 262
Overfluxing Protection 263
Frequency Protection 269

262 P64-TM-EN-1
P64 Chapter 12 - Frequency Protection Functions

12.2 OVERFLUXING PROTECTION


If a power transformer is connected to an active load such as a generator, it is possible that the ratio of voltage to
frequency exceeds certain limits. This will result in Overfluxing, sometimes known as overexcitation. An excessively
high voltage or excessively low frequency causes the V/f ratio to rise, producing high flux densities in the magnetic
core of the transformer. Overfluxing causes the transformer core to saturate resulting in stray flux in non-laminated
components not designed to carry flux. This in turn causes eddy currents in solid components (e.g. core bolts and
clamps) and end-of-core laminations causing rapid overheating and damage. Transformer manufacturers provide
information about the V/f capability as a function of time. The limit is either in the form of a curve or a set-point with
a time delay.
Transformer overfluxing might arise for the following reasons:
● High system voltage
● Generator full load rejection
● Increased voltage due to light loading of transmission lines (Ferranti effect)
● Low system frequency
● Generator excitation at low speed with Automatic Voltage Regulator (AVR) in service
● Geomagnetic disturbance (effects of solar radiation)
● Low frequency earth current circulation through a transmission system

The initial effect of overfluxing is to increase the magnetising current for a transformer. This current will be seen as a
differential current, which could cause the device to maloperate, therefore some sort of restraint is needed. The fifth
harmonic component of the current is used to block the differential element during mild or short term overfluxing
conditions.
Persistent overfluxing however, may result in thermal damage or degradation of a transformer as a result of
overheating.
The following protection strategy is therefore advisable to address potential overfluxing conditions:
● Maintain protection stability during transient overfluxing by blocking the differential protection
● Ensure tripping for persistent overfluxing by applying the overfluxing protection. It is common practice to use
the overfluxing element to protect the transformer during system disturbance, especially on large network
transformers.

12.2.1 OVERFLUXING PROTECTION IMPLEMENTATION


The Overfluxing settings are in the OVERFLUXING column of the relevant settings group. Depending on your
device model, it provides one or two overfluxing elements with four stages of overfluxing protection plus an
additional alarm stage). The P642 has a single-phase VT only, therefore only one overfluxing element is provided.
The P643 and P645 can have a single-phase VT and a 3-phase VT, and therefore provides a single-phase
overfluxing element and a three-phase overfluxing element. Both elements are similar in functionality and follow the
same logical principles.
You enable or disable each stage of the overfluxing protection for each element by the relevant Status cells V/
Hz>(n) Status and V/HZ Alm Status.
The first stage can be set to operate with a definite time or inverse time delay (IDMT). This stage can be used to
provide the protection trip output. The other three stages are all definite time stages. These can be combined with
the first stage inverse time characteristic to create a combined multi-stage overfluxing trip operating characteristic
using PSL.
An inhibit signal is provided for the first stage 1 only. This allows a definite time stage to override a section of the
inverse time characteristic if required. The inhibit signal has the effect of resetting the timer, the start signal and the
trip signal.

P64-TM-EN-1 263
Chapter 12 - Frequency Protection Functions P64

In addition to tripping stages 1 to 4, an Alarm stage is also provided (V/Hz> Alm) for each of the elements. This can
be used to indicate an unhealthy condition.

12.2.1.1 TIME-DELAYED OVERFLUXING PROTECTION


Protection against damage due to prolonged overfluxing is achieved by using the first overfluxing protection stage
with the IDMT characteristic. The setting flexibility of this element, by adjustment of the time delay at various V/Hz
values, makes it suitable for various country-specific requirements. The manufacturer of the transformer should be
able to supply information about the short-time over-excitation capabilities, which you can use to determine
appropriate settings for the V/Hz tripping element. This variable time overfluxing protection should be used to trip
the transformer directly.

The IDMT characteristic is T = TMS/(M – 1)2


where:
M = (V/f p.u.) / (V/f trip setting)
V and F are measured entities

10000

t=TMS/(M-1) 2

1000
operating time (s)

100

TMS = 12
TMS = 8

10 TMS= 4

TMS = 2
TMS = 1

1
1.05 1.15 1.25 1.35 1.45 1.55
V00864 M = (V/f)/Setting

Figure 127: Variable time overfluxing protection characteristic

The IDMT characteristic is implemented as a thermal function. The internal IDMT timer is treated as a thermal
replica with a cooling characteristic. After a V/Hz excursion, the timer should reset according to the reset cooling
characteristic. Otherwise, if the unit is subjected to another V/Hz excursion before it has cooled to normal condition,
damage could occur before the V/Hz trip point is reached.
A linear reset curve with a Reset Time (V/Hz>x tReset) setting is used for this purpose. The actual reset time left is:
Reset time = tReset * IDMTtimer/tTarget

Where tTarget = TMS/(M-1)2.


The actual trip time delay is:
Trip delay = tTarget * (1-RESETtimer/tReset)

264 P64-TM-EN-1
P64 Chapter 12 - Frequency Protection Functions

To make use of the time delayed overfluxing protection, the device must be supplied with a voltage signal which is
representative of the primary system voltage on the source side of the transformer. This is defined by the Ref
Voltage setting in the OVERFLUXING column.
The following diagram explains the reset characteristic. It will take tReset time for the thermal replica to reset
completely to zero after it has reached 100% of V/f>1 trip at stage 1. If the thermal replica has not reached 100% of
V/f>1 Trip, the reset time will be reduced proportionally. For example, if the reset time is set to 100 seconds, and the
thermal replica has only reached 50% of V/f> Trip when V/Hz resets, the reset time will be 50 seconds as shown in
stage 2. If another V/Hz excursion appears before the first reset reaches V/f Reset, the V/Hz time delay takes the
reset time left into consideration, as shown in stage 3.

Stage1 Stage2 Stage3


V/f>1 Trip

V/f>1 Reset

tReset
V/f in p.u.

V00868

Figure 128: Overfluxing reset characteristic

12.2.1.2 5TH HARMONIC BLOCKING


A differential current 5th harmonic blocking feature can be used to prevent possible maloperation under transient
overfluxing conditions. The 5th harmonic signal is derived from the differential current waveform on each phase.
Blocking is on a per phase basis.
To ensure tripping for persistent overfluxing, caused by high system voltage or low system frequency, the device
provides time delayed overfluxing protection. Where there is any risk of persistent geomagnetic overfluxing, with
normal system voltage and frequency, the 5th harmonic differential current facility can be used to initiate tripping
after a long time delay. This time delay would need to be programmed in the PSL as shown:

Other trip signals


1 Any Trip
IA5H Diff Start
1000 Fault REC TRIG
IB5H Diff Start 1 Pick-up
0
IC5H Diff Start
100
Trip Initial Dwell Relay 3 Output
0

V00863

Figure 129: 5th harmonic blocking time delay in PSL

P64-TM-EN-1 265
Chapter 12 - Frequency Protection Functions P64

12.2.1.3 OVERFLUXING PROTECTION LOGIC


The overfluxing protection logic is shown below. This diagram shows the case where the first stage timer is set to
IDMT. You can select a DT timer for the first stage if required with the setting V/Hz>1 Trip Func. The diagram
shown is for the 3-phase VT element. The single-phase element follows the same principles.

3ph V/Hz>1 Start


V/f
IDMT
V/Hz>1 Trip Set & 3ph V/Hz>1 Trip

Freq Not found

Blk 3ph V/Hz>1 V/Hz>1 Trip V/Hz>1


TMS Delay

3ph V/Hz>1 Start


V/f
DT
V/Hz>1 Trip Set & 3ph V/Hz>1 Trip

Freq Not found


V/Hz>1 Delay

V/f
DT
V/Hz Alarm Set & 3Ph V/Hz> Alarm

Freq Not found


V/Hz Alarm
Delay

Note: The diagram is for a 3 -phase VT. The logic for a 1 -phase VT is the same.
This diagram does not show all stages. Other stages follow similar principles.

V00867

Figure 130: Overfluxing protection logic

12.2.2 APPLICATION NOTES

12.2.2.1 OVERFLUXING PROTECTION SETTING GUIDELINES


The pick up value for the overfluxing elements depends on the nominal core flux density levels. Unit transformers
generally run at higher flux densities than transmission and distribution transformers, so they require a higher pick
up setting and shorter tripping times which reflect this. Transmission transformers can also be at risk from
overfluxing conditions, and you should take withstand levels into consideration when deciding on the required
settings.
The IEEE C37.91-2000 standard states that overexcitation of a transformer can occur whenever the ratio of the per
unit voltage to per unit frequency (V/Hz) at the secondary terminals of a transformer exceeds its rating of 1.05 per
unit (PU) on transformer base at full load, 0.8 power factor, or 1.1 PU at no load.
Please refer to clause 4.1.6 in IEEE C57.12.00-2006 for further clarification on the capability of a transformer to
operate above rated voltage and below rated frequency.
The element is set in terms of the actual ratio of voltage to frequency. You can therefore calculate the overfluxing
threshold setting V/Hz>(n) Trip Set, as follows:
A setting of 1.05 p.u. would equate to 110/50 x 1.05 = 2.31

266 P64-TM-EN-1
P64 Chapter 12 - Frequency Protection Functions

where:
● The VT secondary voltage at rated primary volts is 110 V
● The rated frequency is 50 Hz

You should set the overfluxing alarm stage threshold V/Hz Alarm Set, lower than the trip stage setting, to provide
an indication that abnormal conditions are present and to alert an operator to adjust system parameters accordingly.
You should choose the time delay settings to match the withstand characteristics of the protected transformer. For
an inverse time characteristic, set the time multiplier setting, V/Hz>1 Trip TMS such that the operating characteristic
closely matches the withstand characteristic of transformer. For definite time trip stages, set the time delay V/Hz>(n)
Trip Delay cells. The alarm stage time delay is set in the V/Hz Alarm Delay cell.
You can use PSL to combine the stages to create a multi-stage V/Hz trip operating characteristic, as shown below:

Note:
Consult the manufacturers’ withstand characteristics before formulating these settings.

V/Hz>1

V/Hz>4
V/Hz (%)

V/Hz>3

V/Hz>2
Multi-
Characteristic

V00865a Operating Time(s)

Figure 131: Multi-stage overfluxing characteristic

P64-TM-EN-1 267
Chapter 12 - Frequency Protection Functions P64

V/Hz>2 = 1.4 p.u.


t=1s

V/Hz>2 Trip

V/Hz>3 Trip
1 R14 V/Hz Trip

V/Hz>3 = 1.2 p.u. V/Hz>3 Start


t=4s
V/Hz>1 = 1.06
V/Hz>1 Inhibit TMS = 0.08 V/Hz>1 Trip

V/Hz>4 = 1.1 p.u.


t=0s V/Hz>4 Start

E00866

Figure 132: Scheme logic for multi-stage overfluxing characteristic

268 P64-TM-EN-1
P64 Chapter 12 - Frequency Protection Functions

12.3 FREQUENCY PROTECTION


Power generation and utilisation needs to be well balanced in any industrial, distribution or transmission network.
These electrical networks are dynamic entities, with continually varying loads and supplies, which are continually
affecting the system frequency. Increased loading reduces the system frequency and generation needs to be
increased to maintain the frequency of the supply. Conversely decreased loading increases the system frequency
and generation needs to be reduced. Sudden fluctuations in load can cause rapid changes in frequency, which
need to be dealt with quickly.
Unless corrective measures are taken at the appropriate time, frequency decay can go beyond the point of no
return and cause widespread network collapse, which has dire consequences.
Normally, generators are rated for a particular band of frequency. Operation outside this band can cause
mechanical damage to the turbine blades. Protection against such contingencies is required when frequency does
not improve even after load shedding steps have been taken. This type of protection can be used for operator
alarms or turbine trips in case of severe frequency decay.
Clearly a range of methods is required to ensure system frequency stability. The frequency protection in this device
provides both underfrequency and overfrequency protection.
Frequency Protection is implemented in the FREQ PROTECTION column of the relevant settings group.

12.3.1 UNDERFREQUENCY PROTECTION


A reduced system frequency implies that the net load is in excess of the available generation. Such a condition can
arise, when an interconnected system splits, and the load left connected to one of the subsystems is in excess of
the capacity of the generators in that particular subsystem. Industrial plants that are dependant on utilities to supply
part of their loads will experience underfrequency conditions when the incoming lines are lost.
Many types of industrial loads have limited tolerances on the operating frequency and running speeds (e.g.
synchronous motors). Sustained underfrequency has implications on the stability of the system, whereby any
subsequent disturbance may damage equipment and even lead to blackouts. It is therefore essential to provide
protection for underfrequency conditions.

12.3.1.1 UNDERFREQUENCY PROTECTION IMPLEMENTATION


Simple underfrequency Protection is configured in the FREQ PROTECTION column of the relevant settings group.
The device provides 4 stages of underfrequency protection. The function uses the following settings (shown for
stage 1 only - other stages follow the same principles).
● F<1 Status: enables or disables underfrequency protection for the relevant stage
● F<1 Setting: defines the frequency pickup setting
● F<1 Time Delay: sets the time delay

P64-TM-EN-1 269
Chapter 12 - Frequency Protection Functions P64

12.3.1.2 UNDERFREQUENCY PROTECTION LOGIC

1155
Averaging F<1 Start
DT
1161
F<1 Setting & F<1 Trip

F<1 Status
Enabled
1167
Inhibit F<1

890
All Poles Dead
1
1370
Freq Not Found

F<1 Timer Block 1149


V00861

Figure 133: Underfrequency logic (single stage)

If the frequency is below the setting and not blocked the DT timer is started. If the frequency cannot be determined,
the function is blocked.

12.3.1.3 APPLICATION NOTES

12.3.1.3.1 SETTING GUIDELINES


In order to minimise the effects of underfrequency, a multi-stage load shedding scheme may be used with the plant
loads prioritised and grouped. During an underfrequency condition, the load groups are disconnected sequentially,
with the highest priority group being the last one to be disconnected.
The effectiveness of each load shedding stage depends on the proportion of power deficiency it represents. If the
load shedding stage is too small compared with the prevailing generation deficiency, then there may be no
improvement in the frequency. This should be taken into account when forming the load groups.
Time delays should be sufficient to override any transient dips in frequency, as well as to provide time for the
frequency controls in the system to respond. These should not be excessive as this could jeopardize system
stability. Time delay settings of 5 - 20 s are typical.
The protection function should be set so that declared frequency-time limits for the generating set are not infringed.
Typically, a 10% underfrequency condition should be continuously sustainable.

12.3.2 OVERFREQUENCY PROTECTION


An increased system frequency arises when the mechanical power input to a generator exceeds the electrical
power output. This could happen, for instance, when there is a sudden loss of load due to tripping of an outgoing
feeder from the plant to a load centre. Under such conditions, the governor would normally respond quickly to
obtain a balance between the mechanical input and electrical output, thereby restoring normal frequency.
Overfrequency protection is required as a backup to cater for cases where the reaction of the control equipment is
too slow.

12.3.2.1 OVERFREQUENCY PROTECTION IMPLEMENTATION


Simple overfrequency Protection is configured in the FREQ PROTECTION column of the relevant settings group.

270 P64-TM-EN-1
P64 Chapter 12 - Frequency Protection Functions

The device provides 2 stages of overfrequency protection. The function uses the following settings (shown for stage
1 only - other stages follow the same principles).
● F>1 Status: enables or disables underfrequency protection for the relevant stage
● F>1 Setting: defines the frequency pickup setting
● F>1 Time Delay: sets the time delay

12.3.2.2 OVERFREQUENCY PROTECTION LOGIC

Freq 1159
Averaging F>1 Start
DT
1165
F>1 Setting & F>1 Trip

F>1 Status
Enabled
1171
Inhibit F>1

890
All Poles Dead
1
1370
Freq Not Found

1153
F>1 Timer Block V00862

Figure 134: Overfrequency logic (single stage)

If the frequency is above the setting and not blocked, the DT timer is started and after this has timed out, the trip is
produced. If the frequency cannot be determined, the function is blocked.

12.3.2.3 APPLICATION NOTES

12.3.2.3.1 SETTING GUIDELINES


Following changes on the network caused by faults or other operational requirements, it is possible that various
subsystems will be formed within the power network. It is likely that these subsystems will suffer from a generation/
load imbalance. The "islands" where generation exceeds the existing load will be subject to overfrequency
conditions. Severe over frequency conditions may be unacceptable to many industrial loads, since running speeds
of motors will be affected. The overfrequency element can be suitably set to sense this contingency.

P64-TM-EN-1 271
Chapter 12 - Frequency Protection Functions P64

272 P64-TM-EN-1
CHAPTER 13

MONITORING AND CONTROL


Chapter 13 - Monitoring and Control P64

13.1 CHAPTER OVERVIEW


As well as providing a range of protection functions, the product includes comprehensive monitoring and control
functionality.
This chapter contains the following sections:
Chapter Overview 274
Event Records 275
Disturbance Recorder 283
Measurements 284
Current Input Exclusion Function 286
Circuit Breaker Control 288
Pole Dead Function 292
Switch Status and Control 296
Test Mode 301
IEC 61850 Control Authority 302

274 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

13.2 EVENT RECORDS


GE Vernova devices record events in an event log. This allows you to establish the sequence of events that led up
to a particular situation. For example, a change in a digital input signal or protection element output signal would
cause an event record to be created and stored in the event log. This could be used to analyse how a particular
power system condition was caused. These events are stored in the IED's non-volatile memory. Each event is time
tagged.
The event records can be displayed on an IED's front panel but it is easier to view them through the settings
application software. This can extract the events log from the device and store it as a single .evt file for analysis on
a PC.
The event records are detailed in the VIEW RECORDS column. The first event (0) is always the latest event. After
selecting the required event, you can scroll through the menus to obtain further details.
If viewing the event with the settings application software, simply open the extracted event file. All the events are
displayed chronologically. Each event is summarised with a time stamp obtained from the Time & Date cell) and a
short description relating to the event obtained from the Event Text cell). You can expand the details of the event by
clicking on the + icon to the left of the time stamp.
The following table shows the correlation between the fields in the setting application software's event viewer and
the cells in the menu database.

Field in Event Viewer Equivalent cell in menu DB Cell reference User settable?
Left hand column header VIEW RECORDS ® Time & Date 01 03 No
Right hand column header VIEW RECORDS ® Event Text 01 04 No
Description SYSTEM DATA ® Description 00 04 Yes
Plant reference SYSTEM DATA ® Plant Reference 00 05 Yes
Model number SYSTEM DATA ® Model Number 00 06 No
Address Displays the Courier address relating to the event N/A No
Event type VIEW RECORDS ® Menu Cell Ref 01 02 No
Event Value VIEW RECORDS ® Event Value 01 05 No
Evt Unique Id VIEW RECORDS ® Evt Unique ID 01 FE No

The Select Event setting allows access to individual event records, with the latest event stored at position 0. This
setting also defines the maximum number of records available.
In addition to the event log, there are two logs which contain duplicates of the last 5 maintenance records and the
last 5 fault records. The purpose of this is to provide convenient access to the most recent fault and maintenance
events.

13.2.1 EVENT TYPES


There are several different types of event:
● Opto-input events (Change of state of opto-input)
● Contact events (Change of state of output relay contact)
● Alarm events
● Fault record events
● Standard events
● Security events

P64-TM-EN-1 275
Chapter 13 - Monitoring and Control P64

Standard events are further sub-categorised internally to include different pieces of information. These are:
● Protection events (starts and trips)
● Maintenance record events
● Platform events

Note:
The first event in the list (event 0) is the most recent event to have occurred.

13.2.1.1 OPTO-INPUT EVENTS


If one or more of the opto-inputs has changed state since the last time the protection algorithm ran (which runs at
several times per cycle), a new event is created, which logs the logic states of all opto-inputs. You can tell which
opto-input has changed state by comparing the new event with the previous one.
The description of this event type, as shown in the Event Text cell is always Logic Inputs # where # is the
batch number of the opto-inputs. This is '1', for the first batch of opto-inputs and '2' for the second batch of opto-
inputs (if applicable).
The event value shown in the Event Value cell for this type of event is a binary string. This shows the logical states
of the opto-inputs, where the Least Significant Bit (LSB), on the right corresponds to the first opto-input Input L1.
The same information is also shown in the Opto I/P Status cell in the SYSTEM DATA column. This information is
updated continuously, whereas the information in the event log is a snapshot at the time when the event was
created.

13.2.1.2 CONTACT EVENTS


If one or more of the output relays (also known as output contacts) has changed state since the last time the
protection algorithm ran (which runs at several times per cycle), a new event is created, which logs the logic states
of all output relays. You can tell which output relay has changed state by comparing the new event with the previous
one.
The description of this event type, as shown in the Event Text cell is always Output Contacts # where # is the
batch number of the output relay contacts. This is '1', for the first batch of output contacts and '2' for the second
batch of output contacts (if applicable).
The event value shown in the Event Value cell for this type of event is a binary string. This shows the logical states
of the output relays, where the LSB (on the right) corresponds to the first output contact Output R1.
The same information is also shown in the Relay O/P Status cell in the SYSTEM DATA column. This information is
updated continuously, whereas the information in the event log is a snapshot at the time when the event was
created.

13.2.1.3 ALARM EVENTS


The IED monitors itself on power up and continually thereafter. If it notices any problems, it will register an alarm
event.
The description of this event type, as shown in the Event Text cell is cell dependent on the type of alarm and will be
one of those shown in the following tables, followed by OFF or ON.
The event value shown in the Event Value cell for this type of event is a 32 bit binary string. There are one or more
banks 32 bit registers, depending on the device model. These contain all the alarm types and their logic states (ON
or OFF).
The same information is also shown in the Alarm Status (n) cells in the SYSTEM DATA column. This information is
updated continuously, whereas the information in the event log is a snapshot at the time when the event was
created.

276 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

Alarm Status 1

Bit no. Bit Mask (hex) Alarm Description


0 0x00000001 Not Used
1 0x00000002 Not Used
2 0x00000004 Setting Group selection by DDB inputs invalid
3 0x00000008 CB Status Alarm
4 0x00000010 RTD Thermal Alarm
5 0x00000020 RTD Open Circuit Failure
6 0x00000040 RTD Short Circuit Failure
7 0x00000080 RTD Data Inconsistency Error
8 0x00000100 RTD Board Failure
9 0x00000200 Current Loop Input 1 Alarm
10 0x00000400 Current Loop Input 2 Alarm
11 0x00000800 Current Loop Input 3 Alarm
12 0x00001000 Current Loop Input 4 Alarm
13 0x00002000 Current Loop Input 1 Undercurrent Fail Alarm
14 0x00004000 Current Loop Input 2 Undercurrent Fail Alarm
15 0x00008000 Current Loop Input 3 Undercurrent Fail Alarm
16 0x00010000 Current Loop Input 4 Undercurrent Fail Alarm
17 0x00020000 Out of Service Alarm
18 0x00040000 Frequency Out of Range Alarm
19 0x00080000 UNUSED
20 0x00100000 UNUSED
21 0x00200000 UNUSED
22 0x00400000 Current Loop Input Failure
23 0x00800000 Current Loop Input Output Failure
24 0x01000000 VCO1 Configuration Alarm
25 0x02000000 VCO2 Configuration Alarm
26 0x04000000 UNUSED
27 0x08000000 CTS Fail Alarm
28 0x10000000 Circuitry FLT Alm
29 0x20000000 VTS VT Fail Alarm
30 0x40000000 Thermal Pre-trip Alarm
31 0x80000000 Aging Acceleration Factor (FAA) alarm

Alarm Status 2

Bit no. Bit Mask (hex) Alarm Description


0 0x00000001 LOL alarm

P64-TM-EN-1 277
Chapter 13 - Monitoring and Control P64

Bit no. Bit Mask (hex) Alarm Description


1 0x00000002 Breaker Fail Any Trip
2 0x00000004 CB Fail Alarm T1
3 0x00000008 CB Fail Alarm T2
4 0x00000010 CB Fail Alarm T3
5 0x00000020 CB Fail Alarm T4
6 0x00000040 CB Fail Alarm T5
7 0x00000080 CB Fail Alarm T6
8 0x00000100 CB Fail Alarm T7
9 0x00000200 CB Fail Alarm T8
10 0x00000400 CB Fail Alarm T9
11 0x00000800 CB Fail Alarm T10
12 0x00001000 CB Fail Alarm T11
13 0x00002000 CB Fail Alarm T12
14 0x00004000 CB Fail Alarm T13
15 0x00008000 CB Fail Alarm T14
16 0x00010000 CB Fail Alarm T15
17 0x00020000 CB Fail Alarm T16
18 0x00040000 CB Fail Alarm T17
19 0x00080000 CB Fail Alarm T18
20 0x00100000 UNUSED
21 0x00200000 HV V/Hz>1 Alarm
22 0x00400000 HV V/Hz>2 PrTrp
23 0x00800000 LV V/Hz>1 Alarm
24 0x01000000 LV V/Hz>2 PrTrp
25 0x02000000 UNUSED
26 0x04000000 UNUSED
27 0x08000000 Frequency Protection Alarm
28 0x10000000 Through fault Alarm
29 0x20000000 Z1 Test Mode
30 0x40000000 Z2 Test Mode
31 0x80000000 UNUSED

Alarm Status 3

Bit no. Bit Mask (hex) Alarm Description


0 0x00000001 Battery Fail alarm indication
1 0x00000002 Failure
2 0x00000004 unused

278 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

Bit no. Bit Mask (hex) Alarm Description


3 0x00000008 Enrolled GOOSE IED absent alarm indication
4 0x00000010 Network Interface Card not fitted/failed alarm
5 0x00000020 Network Interface Card not responding alarm
6 0x00000040 Network Interface Card fatal error alarm indication
7 0x00000080 Network Interface Card software reload alarm
8 0x00000100 Bad TCP/IP Configuration Alarm
9 0x00000200 Bad OSI Configuration Alarm
10 0x00000400 Network Interface Card link fail alarm indication
11 0x00000800 Main card/NIC software mismatch alarm indication
12 0x00001000 IP address conflict alarm indication
13 0x00002000 unused
14 0x00004000 unused
15 0x00008000 unused
16 0x00010000 unused
17 0x00020000 unused
18 0x00040000 unused
19 0x00080000 unused
20 0x00100000 SNTP Failure Alarm
21 0x00200000 MMS libraries memory allocation fails.
22 0x00400000 unused
23 0x00800000 unused
24 0x01000000 unused
25 0x02000000 unused
26 0x04000000 unused
27 0x08000000 unused
28 0x10000000 unused
29 0x20000000 unused
30 0x40000000 unused
31 0x80000000 unused

Alarm Status 4

Bit no. Bit Mask (hex) Alarm Description


0 0x00000001 User Alarm 1 (0=Self-reset, 1=Manual reset)
1 0x00000002 User Alarm 2 (0=Self-reset, 1=Manual reset)
2 0x00000004 User Alarm 3 (0=Self-reset, 1=Manual reset)
3 0x00000008 User Alarm 4 (0=Self-reset, 1=Manual reset)
4 0x00000010 User Alarm 5 (0=Self-reset, 1=Manual reset)

P64-TM-EN-1 279
Chapter 13 - Monitoring and Control P64

Bit no. Bit Mask (hex) Alarm Description


5 0x00000020 User Alarm 6 (0=Self-reset, 1=Manual reset)
6 0x00000040 User Alarm 7 (0=Self-reset, 1=Manual reset)
7 0x00000080 User Alarm 8 (0=Self-reset, 1=Manual reset)
8 0x00000100 User Alarm 9 (0=Self-reset, 1=Manual reset)
9 0x00000200 User Alarm 10 (0=Self-reset, 1=Manual reset)
10 0x00000400 User Alarm 11 (0=Self-reset, 1=Manual reset)
11 0x00000800 User Alarm 12 (0=Self-reset, 1=Manual reset)
12 0x00001000 User Alarm 13 (0=Self-reset, 1=Manual reset)
13 0x00002000 User Alarm 14 (0=Self-reset, 1=Manual reset)
14 0x00004000 User Alarm 15 (0=Self-reset, 1=Manual reset)
15 0x00008000 User Alarm 16 (0=Self-reset, 1=Manual reset)
16 0x00010000 User Alarm 17 (0=Self-reset, 1=Manual reset)
17 0x00020000 User Alarm 18 (0=Self-reset, 1=Manual reset)
18 0x00040000 User Alarm 19 (0=Self-reset, 1=Manual reset)
19 0x00080000 User Alarm 20 (0=Self-reset, 1=Manual reset)
20 0x00100000 User Alarm 21 (0=Self-reset, 1=Manual reset)
21 0x00200000 User Alarm 22 (0=Self-reset, 1=Manual reset)
22 0x00400000 User Alarm 23 (0=Self-reset, 1=Manual reset)
23 0x00800000 User Alarm 24 (0=Self-reset, 1=Manual reset)
24 0x01000000 User Alarm 25 (0=Self-reset, 1=Manual reset)
25 0x02000000 User Alarm 26 (0=Self-reset, 1=Manual reset)
26 0x04000000 User Alarm 27 (0=Self-reset, 1=Manual reset)
27 0x08000000 User Alarm 28 (0=Self-reset, 1=Manual reset)
28 0x10000000 User Alarm 29 (0=Self-reset, 1=Manual reset)
29 0x20000000 User Alarm 30 (0=Self-reset, 1=Manual reset)
30 0x40000000 User Alarm 31 (0=Self-reset, 1=Manual reset)
31 0x80000000 User Alarm 32 (0=Self-reset, 1=Manual reset)

13.2.1.4 FAULT RECORD EVENTS


An event record is created for every fault the IED detects. This is also known as a fault record.
The event type description shown in the Event Text cell for this type of event is always Fault Recorded.
The IED contains a separate register containing the latest fault records. This provides a convenient way of viewing
the latest fault records and saves searching through the event log. You access these fault records using the Select
Fault setting, where fault number 0 is the latest fault.
A fault record is triggered by the Fault REC TRIG signal DDB, which is assigned in the PSL. The fault recorder
records the values of all parameters associated with the fault for the duration of the fault. These parameters are
stored in separate Courier cells, which become visible depending on the type of fault.
The fault recorder stops recording only when:
The Start signal is reset AND the undercurrent is ON OR the Trip signal is reset, as shown below:

280 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

Start signal resets


& Fault recorder stops recording
Undercurrent is ON
1
Trip signal resets

Fault recorder trigger

V01234

Figure 135: Fault recorder stop conditions

The event is logged as soon as the fault recorder stops. The time stamp assigned to the fault corresponds to the
start of the fault. The timestamp assigned to the fault record event corresponds to the time when the fault recorder
stops.

Note:
We recommend that you do not set the triggering contact to latching. This is because if you use a latching contact, the fault
record would not be generated until the contact has been fully reset.

13.2.1.5 MAINTENANCE EVENTS


Internal failures detected by the self-test procedures are logged as maintenance records. Maintenance records are
special types of standard events.
The event type description shown in the Event Text cell for this type of event is always Maint Recorded.
The Event Value cell also provides a unique binary code.
The IED contains a separate register containing the latest maintenance records. This provides a convenient way of
viewing the latest maintenance records and saves searching through the event log. You access these fault records
using the Select Maint setting.
The maintenance record has a number of extra menu cells relating to the maintenance event. These parameters
are Maint Text, Maint Type and Maint Data. They contain details about the maintenance event selected with the
Select Maint cell.

13.2.1.6 PROTECTION EVENTS


The IED logs protection starts and trips as individual events. Protection events are special types of standard events.
The event type description shown in the Event Text cell for this type of event is dependent on the protection event
that occurred. Each time a protection event occurs, a DDB signal changes state. It is the name of this DDB signal
followed by 'ON' or 'OFF' that appears in the Event Text cell.
The Event Value cell for this type of event is a 32 bit binary string representing the state of the relevant DDB
signals. These binary strings can also be viewed in the COMMISSION TESTS column in the relevant DDB batch
cells.
Not all DDB signals can generate an event. Those that can are listed in the RECORD CONTROL column. In this
column, you can set which DDBs generate events.

13.2.1.7 SECURITY EVENTS


An event record is generated each time a setting that requires an access level is executed.
The event type description shown in the Event Text cell displays the type of change.

13.2.1.8 PLATFORM EVENTS


Platform events are special types of standard events.

P64-TM-EN-1 281
Chapter 13 - Monitoring and Control P64

The event type description shown in the Event Text cell displays the type of change.

282 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

13.3 DISTURBANCE RECORDER


The disturbance recorder feature allows you to record selected current and voltage inputs to the protection
elements, together with selected digital signals. The digital signals may be inputs, outputs, or internal DDB signals.
The disturbance records can be extracted using the disturbance record viewer in the settings application software.
The disturbance record file can also be stored in the COMTRADE format. This allows the use of other packages to
view the recorded data.
The integral disturbance recorder has an area of memory specifically set aside for storing disturbance records. The
number of records that can be stored is dependent on the recording duration. The minimum duration is 0.1 s and
the maximum duration is 10.5 s.
When the available memory is exhausted, the oldest records are overwritten by the newest ones.
Each disturbance record consists of a number of analogue data channels and digital data channels. The relevant
CT and VT ratios for the analogue channels are also extracted to enable scaling to primary quantities.
The fault recording times are set by a combination of the Duration and Trigger Position cells. The Duration cell
sets the overall recording time and the Trigger Position cell sets the trigger point as a percentage of the duration.
For example, the default settings show that the overall recording time is set to 1.5 s with the trigger point being at
33.3% of this, giving 0.5 s pre-fault and 1 s post fault recording times.
With the Trigger Mode set to Single, if further triggers occurs whilst a recording is taking place, the recorder will
ignore the trigger. However, with the Trigger Mode set to Extended, the post trigger timer will be reset to zero,
extending the recording time.
You can select any of the IED's analogue inputs as analogue channels to be recorded. You can also map any of the
opto-inputs output contacts to the digital channels. In addition, you may also map a number of DDB signals such as
Starts and LEDs to digital channels.
You may choose any of the digital channels to trigger the disturbance recorder on either a low to high or a high to
low transition, via the Input Trigger cell. The default settings are such that any dedicated trip output contacts will
trigger the recorder.
It is not possible to view the disturbance records locally via the front panel LCD. You must extract these using
suitable setting application software such as MiCOM S1 Agile.

P64-TM-EN-1 283
Chapter 13 - Monitoring and Control P64

13.4 MEASUREMENTS

13.4.1 MEASURED QUANTITIES


The device measures directly and calculates a number of system quantities, which are updated every second. You
can view these values in the relevant MEASUREMENT columns or with the Measurement Viewer in the settings
application software. Depending on the model, the device may measure and display some or more of the following
quantities:
● Measured and calculated analogue current and voltage values
● Power and energy quantities
● Peak, fixed and rolling demand values
● Frequency measurements
● Thermal measurements

13.4.1.1 MEASURED AND CALCULATED CURRENTS


The device measures phase-to-phase and phase-to-neutral current values. The values are produced by sampling
the analogue input quantities, converting them to digital quantities to present the magnitude and phase values.
Sequence quantities are produced by processing the measured values. These are also displayed as magnitude and
phase angle values.
These measurements are contained in the MEASUREMENTS 1 column.

13.4.1.2 MEASURED AND CALCULATED VOLTAGES


The device measures phase-to-phase and phase-to-neutral voltage values. The values are produced by sampling
the analogue input quantities, converting them to digital quantities to present the magnitude and phase values.
Sequence quantities are produced by processing the measured values. These are also displayed as magnitude and
phase angle values.
These measurements are contained in the MEASUREMENTS 1 column.

13.4.1.3 POWER AND ENERGY QUANTITIES


Using the measured voltages and currents the device calculates the apparent, real and reactive power quantities.
These are produced on a phase by phase basis together with three-phase values based on the sum of the three
individual phase values. The signing of the real and reactive power measurements can be controlled using the
measurement mode setting. The four options are defined in the following table:

Measurement Mode Parameter Signing


0 Export Power +
(Default) Import Power –
Lagging Vars +
Leading VArs –
1 Export Power –
Import Power +
Lagging Vars +
Leading VArs –
2 Export Power +
Import Power –
Lagging Vars –
Leading VArs +

284 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

Measurement Mode Parameter Signing


3 Export Power –
Import Power +
Lagging Vars –
Leading VArs +

The device also calculates the per-phase and three-phase power factors.
These power values increment the total real and total reactive energy measurements. Separate energy
measurements are maintained for the total exported and imported energy. The energy measurements are
incremented up to maximum values of 1000 GWhr or 1000 GVARhr at which point they reset to zero. It is possible
to reset these values using the menu or remote interfaces using the Reset demand cell.
These measurements are contained in the MEASUREMENTS 2 column.

13.4.1.4 DEMAND VALUES


The device produces fixed, rolling, and peak demand values. You reset these quantities using the Reset demand
cell.
The fixed demand value is the average value of a quantity over the specified interval. Values are produced for three
phase real and reactive power. The fixed demand values displayed are those for the previous interval. The values
are updated at the end of the fixed demand period according to the Fix Dem Period setting in the MEASURE'T
SETUP column.
The rolling demand values are similar to the fixed demand values, but a sliding window is used. The rolling demand
window consists of a number of smaller sub-periods. The resolution of the sliding window is the sub-period length,
with the displayed values being updated at the end of each of the sub-periods according to the Roll Sub Period
setting in the MEASURE'T SETUP column.
Peak demand values are produced for each phase current and the real and reactive power quantities. These
display the maximum value of the measured quantity since the last reset of the demand values.
These measurements are contained in the MEASUREMENTS 2 column.

13.4.1.5 OTHER MEASUREMENTS


Depending on the model, the device produces a range of other measurements such as thermal measurements.
These measurements are contained in the MEASUREMENTS 3 column.

13.4.2 MEASUREMENT SETUP


You can define the way measurements are set up and displayed using the MEASURE'T SETUP column and the
measurements are shown in the relevant MEASUREMENTS tables.

13.4.3 OPTO-INPUT TIME STAMPING


Each opto-input sample is time stamped within a tolerance of +/- 1 ms with respect to the Real Time Clock. These
time stamps are used for the opto event logs and for the disturbance recording. The device needs to be
synchronised accurately to an external clock source such as an IRIG-B signal or a master clock signal provided in
the relevant data protocol.
For both the filtered and unfiltered opto-inputs, the time stamp of an opto-input change event is the sampling time at
which the change of state occurred. If multiple opto-inputs change state at the same sampling interval, these state
changes are reported as a single event.

P64-TM-EN-1 285
Chapter 13 - Monitoring and Control P64

13.5 CURRENT INPUT EXCLUSION FUNCTION


In the P643 and P645, it is possible to exclude current inputs from the protection functions. This may be useful for
example in a phase shifting transformer, or during the commissioning or maintenance process.
When a current input is excluded, the device sets the current from that input to zero for calculation purposes, even if
the current measured is not zero. The device compares the actual current flowing with the under current element
threshold to ensure that the CT input is excluded if the current is below the undercurrent threshold when the master
CT exclusion DDB signal is not asserted. The under current threshold is fixed to 0.05 In.

13.5.1 CURRENT INPUT EXCLUSION LOGIC


CT Exclu Ena
&
CT1 Exclu Ena 1 S 600 ms
Q CT1 Excluded
R 30 ms
CT1 PhA UnderCur
&
CT1 PhB UnderCur &

CT1 PhC UnderCur


&
1
V01231a Note: This diagram does not show all stages. Other stages follow similar principles.

P643

CT1 Excluded

CT2 Excluded insuff No. of CT

CT3 Excluded

P645

CT1 Excluded

CT2 Excluded

CT3 Excluded insuff No. of CT

CT4 Excluded

CT5 Excluded

V01232

Figure 136: CT Exclusion logic

Only one current input can be excluded from the P643 and a maximum of three current inputs can be excluded from
the P645. An alarm DDB (Insuff No. of CT) is issued when more than the maximum number of current inputs are
excluded. The status of the exclusion DDB signals (CTx Excluded) is stored in the device's internal non-volatile
memory. An alarm (Disc CT Invalid) is raised if the stored statuses do not match the statuses after the power
supply is re-established. When the Disc CT Invalid DDB signal is asserted, all protection functions using the
relevant CT inputs are blocked.

Note:
For the differential element to operate correctly, the number of CTs used cannot be less than 2. Also CTs should be excluded
one at a time.

286 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

13.5.2 APPLICATION NOTES

13.5.2.1 CURRENT INPUT EXCLUSION EXAMPLE


In the following figure, the adjacent isolators to CB1 are open and locked because of maintenance work on CB1.

1 CB1 2 CB2

Autotransformer
230/115/13.8 kV
Auxiliary
services

CB4 CB5

V01236

Figure 137: CT input exclusion - 1.5 CB application

The current transformer associated with CB1 is connected to the T1 CT input. Auxiliary contacts from CB1 isolators
1 and 2 must be connected to an opto-input as follows.

+V DC

98b - 1
Opto input 14 1 CT1 Exclu E na
98b - 2

Opto input 14

-V DC

V01233

Figure 138: CT input exclusion - auxiliary contact connection

When isolators 1 and 2 are open, the opto-input L14 is energized and CT1 Exclu Ena is asserted. To set CT1
Excluded, T1 CT Phase A, B and C undercurrent elements must also be asserted.

P64-TM-EN-1 287
Chapter 13 - Monitoring and Control P64

13.6 CIRCUIT BREAKER CONTROL


Although some circuit breakers do not provide auxiliary contacts, most provide auxiliary contacts to reflect the state
of the circuit breaker. For P64 IEDs the status information needs to be wired in the PSL using the DDBs CBx
Closed, where x is the number of CB.
If no CB auxiliary contacts are available then no CB control will be possible.
For controls, the CB control by cell should be set accordingly.
The output contact can be set to operate following a time delay defined by the setting Man Close Delay. One
reason for this delay is to give personnel time to safely move away from the circuit breaker following a CB close
command.
The length of the trip and close control pulses can be set via the Trip Pulse Time and Close Pulse Time settings
respectively. These should be set long enough to ensure the breaker has completed its open or close cycle before
the pulse has elapsed.
If an attempt to close the breaker is being made, and a protection trip signal is generated, the protection trip
command overrides the close command.
If the CB fails to respond to the control command (indicated by no change in the state of CB Status inputs) an alarm
is generated after the relevant trip or close pulses have expired. This alarm can be viewed on the LCD display,
remotely, or can be assigned to an output contact using the programmable scheme logic (PSL).

Note:
The CB Healthy Time set under this menu section is applicable to manual circuit breaker operations only.

The device includes the following options for control of a single circuit breaker:
● The IED menu (local control)
● The CB Open/Close keys and the SLD on the graphical HMI
● The opto-inputs (local control)
● SCADA communication (remote control)

13.6.1 CB CONTROL USING THE IED MENU


You can control manual trips and closes with the CB Trip/Close command in the SYSTEM DATA column. This can
be set to No Operation, Trip, or Close accordingly.
For this to work you have to set the CB control by cell to option 1 Local, option 3 Local + Remote, option 5
Opto+Local, option 7 Opto+Local+Remote or option 8 L/R Key in the CB CONTROL column.

13.6.2 SINGLE LINE DIAGRAM (SLD) VIEWER


The SLD menu displays the saved SLD on the graphical HMI screen. You can navigate to the SLD menu using the
bottom Menu context keys or by using the quick launch menu on the Home page. The SLD is configured and
uploaded into the IED using the S1 Agile configuration tool. Items of plant can be selected on the SLD screen using
the navigation keypad.

13.6.2.1 CIRCUIT BREAKER CONTROL (SLD VIEW ONLY)


You can OPEN and CLOSE the circuit breaker selected on the SLD using the dedicated OPEN, CLOSE and L/R
buttons on the front HMI Panel.
When the CB Control by setting is selected, to option 1 Local, option 3 Local+Remote, option 5 Opto+local,
option 7 Opto+Rem+local or option 8 L/R Key in the CB CONTROL column users are allowed to use the Trip
and Close Key on the front panel to operate the CB.

288 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

To control an item of plant using the Open and Close and L/R buttons:
● Set CB control by setting to L/R Key
● Select the Local operating mode by pressing the L/R button
When the L/R button on the front panel is pressed, it will toggle the status of DDB L/R Key Status. When the DDB
status is TRUE, the L/R Key LED is red and the Local mode is selected. When the DDB status is FALSE, the L/R
Key LED is green and the REMOTE mode is selected. The L/R Key Status DDB status is stored in non-volatile
memory, so that it’s status is recovered after an IED power cycle.
● In the SLD menu, navigate to the item of plant which you require to control using the navigation keypad
● The selected plant is highlighted with an orange border
● Use the Enter key to select the item
● Press the Open or Close key to operate

Figure 139: HMI SLD Display

For the Circuit Breaker Commands from HMI, additional checks are done:
If the CB is in indeterminant state, the switchgear command will not be available and HMI will raise a warning
dialogue with the message - "Commands blocked - Intermediate State".
If the associated "Control by" setting is set to "disabled" the switchgear command will not be available and HMI will
raise a warning dialogue with the message - "Commands blocked due to Settings".
If the associated "Control by" setting is set to "remote" the switchgear command will not be available and HMI will
raise a warning dialogue with the message "Commands blocked due to Settings".
If the associated "Control by" setting is set to "L/R key" and soft key status is set to remote, the switchgear
command will not be available, and HMI will pop-up the message - "Commands blocked - In Remote Control".
If the associated local DDB is set to local, the switchgear command will not be available, and HMI will pop-up the
message - "Commands blocked - Switchgear in Local".

13.6.3 CB CONTROL USING THE OPTO-INPUTS


Certain applications may require the use of push buttons or other external signals to control the various CB control
operations. It is possible to connect such push buttons and signals to opto-inputs and map these to the relevant
DDB signals.
For this to work, you have to set the CB control by cell to option 4 opto, option 5 Opto+Local, option 6 Opto
+Remote, or option 7 Opto+Local+Remote in the CB CONTROL column.

P64-TM-EN-1 289
Chapter 13 - Monitoring and Control P64

13.6.4 REMOTE CB CONTROL


Remote CB control can be achieved by setting the CB Trip/Close cell in the SYSTEM DATA column to trip or close
by using a command over a communication link.
For this to work, you have to set the CB control by cell to option 2 Remote, option 3 Local+Remote, option 6
Opto+remote, option 7 Opto+Local+Remote or option 8 L/R Key in the CB CONTROL column.

Protection Trip

Trip
Remote
Control
Trip Close
Remote
Control
Close

Local

Remote

Trip Close

E01207

Figure 140: Remote Control of Circuit Breaker

DNP 3.0 protocol: The switch positions can be controlled from Binary Outputs/Control Relay Output Blocks.
IEC 61850 protocol: The CB and switch positions can be controlled in the ‘CSWI’ Logical Node that is linked to the
‘XCBR’ Circuit Breaker Logical Node and 'XSWI' switch Logical Nodes. For Control Authority as per IEC 61850, it is
necessary to select CB Control by cell as option 8 L/R Key.

13.6.5 CB HEALTHY CHECK


A CB Healthy check is available if required. This facility accepts an input to one of the opto-inputs to indicate that
the breaker is capable of closing (e.g. that it is fully charged). A time delay can be set with the setting CB Healthy
Time. If the CB does not indicate a healthy condition within the time period following a Close command, the device
will lockout and alarm.

290 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

13.6.6 CB CONTROL LOGIC


CB Control
Disabled Opto
Local Opto+Local
1 Enable opto-initiated CB trip and close
Remote Opto+Remote
Local+Remote Opto+Rem+Local
L/R Key L/R Key

HMI Trip Control Trip


1
& & S
Init Trip CB Q
R & Man CB Trip Fail

&
Init close CB 1 Close in Prog

HMI Close Delayed control close time


& S
Control Close
Q
Close pulse
R &
S
Q
Pulsed output latched in HMI
R
& CB Cls Fail

Reset Close Dly 1

Trip Command In 1
1
Ext. Trip 3ph

Control Trip

CB Open 3 ph
CB healthy window
CB Closed 3 ph
& Man CB Unhealthy
CB Healthy

V01290a

Figure 141: CB control logic

P64-TM-EN-1 291
Chapter 13 - Monitoring and Control P64

13.7 POLE DEAD FUNCTION


The Pole Dead Logic is used to determine and indicate that one or more phases of the line are not energised. A
Pole Dead condition is determined either by measuring:
● the line currents and/or voltages, or
● by monitoring the status of the circuit breaker auxiliary contacts, as shown by dedicated DDB signals.

It can also be used to block operation of underfrequency and undervoltage elements where applicable.

13.7.1 POLE DEAD FUNCTION IMPLEMENTATION


Pole Dead logic can be implemented in all of the P64 models. If implemented in the P642, it requires a model with
two single phase VT inputs. If implemented in the P643 or P645, it requires a three phase VT input.
In the P642, the phase -to-phase voltages VAB and VBC are considered, whilst in the P643 and P645, the phase -
to-neutral votlages VAN, VBN and VCN are considered.
The pole dead function is used to determine when the circuit breaker poles are open. This indication may be forced,
using status indication from CB auxiliary contacts (52a or 52b) mapped to opto-inputs, or internally determined by
the device. If internally determined, the 52b contacts are used and inverted in the PSL because only the CBx
closed DDB signal is available for each breaker. The device will also initiate a pole dead condition for the following
conditions:
● VTS Slow Block DDB signal is low,
● The line current and voltage fall below a preset threshold.

This is necessary so that a pole dead indication is still given even when an upstream breaker is opened. The
undervoltage and undercurrent thresholds have the following, fixed, pick-up and drop-off levels:
● VA<, VB<, VC<, these level detectors operate on phase voltages and have a fixed setting, Pick-up level = 10
V (Vn = 100/120 V), 40 V (Vn = 380/480 V), Drop Off level = 30 V (Vn = 100/120 V), 120V (Vn = 380/480 V).
● VAB<, VBC<, these level detectors operate on phase-phase voltages and have a fixed setting, Pick-up level
= 70 V (Vn = 100/120 V), Drop Off level = 95 V (Vn = 100/120 V).
● IA<, IB<, IC<, these level operate on phase currents and have a fixed setting, Pick-up level = 0.05 In, Drop
Off level = 0.055 In.

Note:
If the VT is connected at the busbar side, auxiliary contacts (52a or 52b) must be connected to the device for a correct pole
dead indication.

292 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

13.7.2 POLE DEAD LOGIC


IA

Hardcoded threshold & 1 Pole Dead A

VAB

Hardcoded threshold &

VCA

Hardcoded threshold

IB

Hardcoded threshold & 1 Pole Dead B

VAB

Hardcoded threshold &

VCA

Hardcoded threshold

IC

Hardcoded threshold & 1 Pole Dead C

VBC

1 Any Pole Dead


Hardcoded threshold &

VCA
& All Poles Dead
Hardcoded threshold

VTS Slow Block

CB1 Closed

3Ph CB Open

Terminal HV
Selection

P642: 01 CB1 Closed & 3Ph CB Open

Terminal LV
Selection

P642: 10 CB2 Closed & 3Ph CB Open

V01228

Figure 142: Pole Dead logic - P642

P64-TM-EN-1 293
Chapter 13 - Monitoring and Control P64

IA

Hardcoded threshold & 1 Pole Dead A

VA

Hardcoded threshold

IB

Hardcoded threshold & 1 Pole Dead B

VB

Hardcoded threshold

IC

Hardcoded threshold & 1 Pole Dead C

VC

1 Any Pole Dead


Hardcoded threshold

VTS Slow Block


& All Poles Dead
3Ph_CB _Open

Terminal HV Terminal TV
Selection Selection
P643: 001 CB1 Closed & 3Ph CB_Open P643: 010 CB2 Closed & 3Ph CB Open
P645: 00001

CB1 Closed CB3 Closed


P643: 011 & 3Ph CB Open P645: 00110 & 3Ph CB Open
P645: 00011 CB2 Closed CB2 Closed

LV P645: 00100 CB3 Closed & 3Ph CB Open


Terminal
Selection

CB3 Closed & 3Ph CB Open CB4 Closed


P643: 100 P645: 01100 & 3Ph CB Open
CB3 Closed
CB3 Closed
& 3Ph CB Open
P643: 110 CB2 Closed

CB5 Closed & 3Ph CB Open


P645: 10000

CB5 Closed
& 3Ph CB Open
P645: 11000 CB4 Closed

V01229

Figure 143: Pole Dead logic - P643 and P645

If both the line current and voltage fall below a certain threshold the device will initiate a Pole Dead condition. The
undervoltage (V<) and undercurrent (I<) thresholds are hardcoded internally.
If one or more poles are dead, the device will indicate which phase is dead and will also assert the Any Pole Dead
DDB signal. If all phases are dead the Any Pole Dead signal would be accompanied by the All Poles Dead signal.
If the VT fails, a VTS Slow Block signal is taken from the VTS logic to block the Pole Dead indications that would
be generated by the undervoltage and undercurrent thresholds. However, the VTS logic will not block the Pole Dead

294 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

indications if they are initiated by a CBx Closed signal. A CBx closed signal is inverted and automatically initiates
a Pole Dead condition regardless of the current and voltage measurement.

13.7.3 CB STATUS INDICATION


The Pole Dead logic needs a way of initiating the Pole Dead indications for a 3-phase CB Open condition, which
bypasses the VTS blocking. This is normally achieved with a CB State Monitoring function. However, the P64 does
not contain a dedicated CB state monitoring function, so it needs a mechanism by which to achieve this. To do this,
we produce an internal DDB signal (3 ph CB Open), by looking at the status of the CB auxiliary contacts of the
windings to which the voltage transformers are connected. Each terminal (T1 to T5) has an external CBx Closed
DDB signal associated with it, which are connected to the CB auxiliary contacts if available. The internal 3ph CB
Open indication is produced by ANDing together the statuses of the relevant CBs. This is dependent on the model
and the terminal status configuration, and is shown in the logic diagram.
For cases where there are no auxiliary contacts available, the CB Open 3 ph signal must be forced low to avoid a
false Pole Dead indication. You can do this by forcing all five CBx Closed DDB signals high using opto-inputs as
shown below.

High
Opto Input 7 1 CB1 Closed

Opto Input 8 1 CB2 Closed

Opto Input 9 1 CB3 Closed

Opto Input 10 1 CB4 Closed

Opto Input 11 1 CB5 Closed

V01230

Figure 144: Forcing CB Closed signals

P64-TM-EN-1 295
Chapter 13 - Monitoring and Control P64

13.8 SWITCH STATUS AND CONTROL


All P64 products support Switch Status and Control for up to 8 switchgear elements. This is available for
IEC60870-5-103 and IEC61850 protocols. The device is able to monitor the status of and control up to eight
switches. The types of switch that can be controlled are:
● Load Break switch
● Disconnector
● Earthing SwitchP64
● High Speed Earthing Switch

Consider the following feeder bay:

XSWI1 XSWI2

XCBR

XSWI3 Legend:
XSWI4 XSWI1 = Dis connector 1
XSWI2 = Dis connector 2
XSWI3 = Dis connector 3
XSWI4 = Earthing Switch
XCBR = Circuit Breaker
V01241

Figure 145: Representation of typical feeder bay

This bay shows four switches of the type LN XSWI and one circuit breaker of type LN XCBR. In this example, the
switches XSWI1 – XSWI3 are disconnectors and XCSWI4 is an earthing switch.
For the device to be able to control the switches, the switches must provide auxiliary contacts to indicate the switch
status. For convenience, the device settings refer to the auxiliary contacts as 52A and 52B, even though they are
not circuit breakers.
There are eight sets of settings in the SWITCH CONTROL column, which allow you to set up the Switch control,
one set for each switch. These settings are as follows:
SWITCH1 Type
This setting defines the type of switch. It can be a load breaking switch, a disconnector, an earthing switch or a high
speed earthing switch.
SWI1 Status Inpt
This setting defines the type of auxiliary contacts that will be used for the control logic. For convenience, the device
settings refer to the auxiliary contacts as 52A and 52B, even though they are not circuit breakers. "A" contacts
match the status of the primary contacts, whilst "B" contacts are of the opposite polarity.
SWI1 Control by
This setting determines how the switch is to be controlled. This can be Local (using the device directly) remote
(using a communications link), or both.
SWI1Trip/Close
This is a command t o directly trip or close the switch.

296 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

SWI1 Trp Puls T and SWI1 Cls Puls T


These settings allow you to control the width of the open and close pulses.
SWI1 Sta Alrm T
This setting allows you to define the duration of wait timer before the relay raises a status alarm.
SWI1 Trp Fail T and SWI1 Cls Fail T
These settings allow you to control the delay of the open and close alarms when the final switch status is not in line
with expected status.
SWI1 Operations
This is a data cell, which displays the number of switch operations that have taken place. It is an accumulator, which
you can reset using the Reset SWI1 Data setting
Reset SWI1 Data
This setting resets the switch monitoring data.

Note:
Settings for switch 1 are shown, but settings for all other switch elements are the same.

IEC 61850 protocol: The Switch position can be controlled in the ‘CSWI’ Logical Node that is linked to the ‘XSWI’
Switch Logical Node. For Control Authority as per IEC 61850, it is necessary to select SWx Control by cell as
option 4 L/R Key.

13.8.1 SINGLE LINE DIAGRAM (SLD) VIEWER


The SLD menu displays the saved SLD on the graphical HMI screen. You can navigate to the SLD menu using the
bottom Menu context keys or by using the quick launch menu on the Home page. The SLD is configured and
uploaded into the IED using the S1 Agile configuration tool. Items of plant can be selected on the SLD screen using
the navigation keypad.

13.8.2 SWITCH CONTROL (SLD VIEW ONLY)


You can OPEN and CLOSE the switches selected on the SLD using the dedicated OPEN, CLOSE and L/R buttons
on the front HMI Panel.
When the Switch Control by setting is selected to option 1 LOCAL, option 3 Local+Remote or option 4 L/R Key
in the SWITCH CONTROL column, users are allowed to use the Open and Close Key on the front panel to operate
the SWITCH.
To control an item of plant using the Open and Close and L/R buttons:
● Set Switch Control by setting to L/R Key
● Select the Local operating mode by pressing the L/R button

When the L/R button on the front panel is pressed, it will toggle the status of DDB L/R Key Status. When the DDB
status is TRUE, the L/R Key LED is red and the Local mode is selected. When the DDB status is FALSE, the L/R
Key LED is green and the REMOTE mode is selected. The L/R Key Status DDB status is stored in non-volatile
memory, so that its status is recovered after an IED power cycle.
● In the SLD menu, navigate to the item of plant you want to control using the navigation keypad
● The selected plant is highlighted with an orange border
● Use the Enter key to select the item
● Press the OPEN or CLOSE key to operate

P64-TM-EN-1 297
Chapter 13 - Monitoring and Control P64

Figure 146: HMI SLD display

Figure 147: For the Switch Commands from HMI, these additional checks are done:

If the Switch is in indeterminant state, the switchgear command will not be available and HMI will raise a warning
dialogue with the message - "Commands blocked - Intermediate State".
If the associated "Control by" setting is set to "disabled" the switchgear command will not be available and HMI will
raise a warning dialogue with the message - "Commands blocked due to Settings".
If the associated "Control by" setting is set to "remote" the switchgear command will not be available and HMI will
raise a warning dialogue with the message "Commands blocked due to Settings".
If the associated "Control by" setting is set to "L/R key" and soft key status is set to remote, the switchgear
command will not be available and HMI will pop-up the message - "Commands blocked - In Remote Control."
If the associated local DDB is set to local, the switchgear command will not be available and HMI will pop-up the
message - "Commands blocked - Switchgear in Local".

298 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

13.8.3 SWITCH CONTROL LOGIC

SWI1 Control by 1
&
Local 1
Local+Remote
Remote 1 &
L/R Key

Local

Remote

Blk Rmt SWI1 Ops

&
SWI1 Pulse Timer Ctrl
Enabled
SWI1 Cls Puls T

1 & SWI1 Control Cls


&
SWI1 Status Opn

SWI1 Status Cls


1
SWI1 Status Inpt
None &
& SWI1 Control Trp

SWI1 Trip/Close
Close SWI1 Trp Puls T
Trip
&

&
1 SWI1 Control Alm

&
SWI1 Cls Fail T

S t
Q
R 0

& SWI1 Cls Fail


SWI1 Status Cls

SWI1 Status Opn & SWI1 Trip Fail


SWI1 Trp Fail T

S t
Q
R 0
V01242a

Figure 148: Switch control logic

P64-TM-EN-1 299
Chapter 13 - Monitoring and Control P64

13.8.4 SWITCH STATUS LOGIC


SWI1 Status Opn
&
1
SWI1 Status Cls & SWI1 Status Opn

SWI1 Status Inpt &


52A
52B
& SWI1 Sta A larm T
52A + 52B
None

t
& SWI1 Input Alm
0

& & SWI1 Status Cls


1

&

&
V01243

Figure 149: Switch status logic

300 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

13.9 TEST MODE


The behaviour of the IED is dependant on if it is in normal operation or in one of the Test Modes. This is reflected in
some of the data that can be monitored and affects the allowed control operations, particularly using the IEC 61850
protocol.
The mode of operation is set using the IED Test Mode cell under the COMMISSION TESTS column. See the
Commissioning Instructions chapter for more information.
When the IED is in either Test or Contacts Blocked mode, IEC 61850 status and measurement data will be
transmitted with its quality parameter set to test, so that the receiver understands that they have been issued by a
device under test and can respond accordingly.
When the IED is in either Test or Contacts Blocked’ mode, the IED only responds to IEC 61850 MMS controls
from the client with the 'test' flag set (with the exception of controls on System/LLN0.Mod).
You can select the mode of operation of the P40 IED by:
● Using the front panel HMI, with the setting IED Test Mode under the COMMISSION TESTS column
● Using an IEC 61850 MMS control service to System/LLN0.Mod
● Using an opto-input via PSL with the signal Block Contacts

The following table summarises the P40 IED behaviour under the different modes:

IED Test Mode Setting IEC 61850 Mod Result


Disabled on ● Normal IED behaviour
● IED only responds to incoming GOOSE and SV
messages with quality q.test = false
Test test ● Protection remains enabled
● IED responds to incoming GOOSE and SV messages
with both quality q.test = true and q.test = false
● Relay output contacts are still active
● IEC 61850 message outputs have 'quality' q.test = true
● IED responds to incoming IEC 61850 MMS messages
with only quality q.test = true
Contacts Blocked test/blocked ● Protection remains enabled
● IED responds to incoming GOOSE and SV messages
with both quality q.test = true and q.test = false
● Relay output contacts are disabled
● IEC 61850 message outputs have quality q.test = true
● IED responds to incoming IEC 61850 MMS messages
with only quality q.test = true

Setting the Test or Contacts Blocked mode puts the whole IED into test mode. The IEC 61850 data object Beh in all
Logical Nodes (except LPHD and any protection Logical Nodes that have Beh = 5 (off) due to the function being
disabled) will be set to 3 (test) or 4 (test/blocked) as applicable.

P64-TM-EN-1 301
Chapter 13 - Monitoring and Control P64

13.10 IEC 61850 CONTROL AUTHORITY


Within the substation, control commands to the primary equipment, such as the breaker or disconnect/earth
switches can be originated from one of four levels: Device, Bay, Station or Remote.
Device: Controls are issued manually at the device in the yard/GIS. Any commands from remote locations are not
accepted. For this to happen the XCBR/XSWI.Loc object should be True. For P40 devices, the XCBR/XSWI.Loc is
mapped to these DDBs:
DDB No. DDB Name Description
2186 LocKey Local This DDB signal indicates that the IED is in local status
2187 SW1 Local This DDB signal indicates that the switch 1 is in local status
2188 SW2 Local This DDB signal indicates that the switch 2 is in local status
2189 SW3 Local This DDB signal indicates that the switch 3 is in local status
2190 SW4 Local This DDB signal indicates that the switch 4 is in local status
2191 SW5 Local This DDB signal indicates that the switch 5 is in local status
2192 SW6 Local This DDB signal indicates that the switch 6 is in local status
2193 SW7 Local This DDB signal indicates that the switch 7 is in local status
2194 SW8 Local This DDB signal indicates that the switch 8 is in local status
2195 CB1 Local This DDB signal indicates that the CB1 is in local status

2196 CB2 Local This DDB signal indicates that the CB2 is in local status

2197 CB3 Local This DDB signal indicates that the CB3 is in local status

2198 CB4 Local This DDB signal indicates that the CB4 is in local status

2199 CB5 Local This DDB signal indicates that the CB4 is in local status

If the DDBs associated are not connected, the default is False which facilitates remote operations.
Bay: The commands are issued from the HMI of the P40. The P40 has a dedicated L/R Button for selection in the
front face.

Key Description Function

Local/Remote key To select between local and remote operating modes.

When the L/R button on the front panel is pressed, it will toggle the status of DDB L/R Key Status. When the DDB
status is TRUE, the L/R Key LED is Red and the Local mode is selected. When the DDB status is FALSE, the L/R
Key LED is Green and the REMOTE mode is selected. The L/R Key Status DDB status is stored in non-volatile
memory, so that its status is recovered after an IED power cycle.
Bay Level controls are possible from the HMI if the L/R Key Status is in Local. When L/R Key is in Local the IEC
61850 Signal, System\LLN0.Loc is set as True. When L/R Key is in Remote, and a control action is attempted, the
User will be advised with a pop-up message of "Command Unavailable - in remote".
To facilitate integration of the IED into a wired Local/Remote control switch in a panel, an additional DDB L/R Key
has been provided.
This is modelled into IEC 61850 System\LLN0.LocKey. The data object LocKey represents the status of a physical
key switch and allows taking over the control authority, if the DDB is wired. If the DDB is used, and is set to 1, the
IED Local/Remote (System\LLN0.Loc) automatically changes to Local. At this stage, it is not possible to change the

302 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

IED L/R Key to remote. If the DDB is set to 0, the IED L/R does not automatically change to Remote. If necessary, a
user action is required to change the control authority to Remote.
Station/Remote: Station level commands are those originating from either the substation gateway or from the
station HMI. Remote commands are from the remote Network Control Center (NCC).
The data object LocSta modelled in System\LLN0 shows the control authority at station level. If LocSta=True,
control authority is at station level and control from remote is disabled. If LocSta=False, control commands are
allowed from remote, e.g. network control center (NCC).
P40 devices also support the concept of Multiple Level Control authority. This is done via a dedicated datapoint in
System\LLN0 known as MltLev. If true, authority control from multiple levels is allowed, otherwise no other control
level is allowed.
Under certain operational conditions, such as during maintenance, it is necessary to block commands from one or
more of these levels. The local/remote control feature (described in IEC 61850 7-4: Annex B) allows users to enable
or disable control authority from one or more of the three levels, as illustrated in the tables below:
IEC 61850 commands originating from the various levels are differentiated using the Origin.OrCat attribute value in
the IEC 61850 command.
If the control command is rejected by the P40 IED due to control authority check, the AddCause - Blocked-by-
switching-hierarchy will be shown in the IEC 61850 Client.

Control Authority for Other Controllable Objects


Device Switch Bay Control Command From
Mode of Switching Local Control
Manual
Authority for Local Control Authority at OrCat
Control at
Control Behaviour Station Level
Front Panel
XCBR.Loc
LLN0.Loc Key LLN0.Mlt Lev CSWI.Loc CSWI.Loc Sta Bay Station Remote
XWI.Loc
T n.a. F n.a. n.a. AA NA NA NA
F T F T n.a. AA NA NA NA
F T F F n.a. NA NA NA NA
F F F T n.a. AA NA NA NA
F F F F T NA NA AA NA
F F F F F NA NA NA AA

T n.a. T n.a. n.a. AA NA NA NA


F T T T n.a. AA NA NA NA
F T T F n.a. NA NA NA NA
F F T T n.a. AA NA NA NA
F F T F T NA AA AA NA
F F T F F NA AA AA AA
n.a. - Not Applicable
AA - Always Allowed
NA - Not Allowed

P64-TM-EN-1 303
Chapter 13 - Monitoring and Control P64

In addition to the CB/Switches, P40 devices follow the concept of Control Authority for other commands executed
via IEC 61850. These include:
● Control Inputs
● Reset of Trip LED
● Enable/Disable of Protection, Check Sync and Auto Recloser
● Reset of demands and thermal measurements

Control Authority for Other Controllable Objects


Device Bay Control Command From
Mode of Switching Local Control
Manual Control at
Authority for Local Control Authority at OrCat
Front Panel
Control Behaviour Station Level
LLN0.Loc Key LLN0.Mlt Lev LLN0.Loc LLN0.Loc Sta Bay Station Remote
T F n.a. n.a. AA NA NA NA
F F T n.a. AA NA NA NA
F F F T AA NA AA NA
F F F F AA NA NA AA

T T n.a. n.a. AA NA NA NA
F T T n.a. AA NA NA NA
F T F T AA AA AA NA
F T F F AA AA AA AA
n.a. - Not Applicable
AA - Always Allowed
NA - Not Allowed

IEC 61850 based control authority can be visualized from the P40 HMI.
This is under the COMMISSION TESTS Menu, under IEC 61850 Control Sub Menu:

Menu Text Description Min Max Default Controllable


Multiple Level Used to enable/disable the 'multi level control Disabled Enabled Disabled Yes
authority' feature for breaker/switch and other
controls
Station Level Used to get control command of station authority Disabled Enabled Disabled No
from IEC 61850 Client
Device Level Used to show the IED local/remote status Local Remote Local No

Multiple Level Control Authority can be selected either via an IEC 61850 MMS Command or via selection from the
menu item shown above.

Note:
The Control Authority only works if the Protocol is IEC 61850. For Legacy Protocols, the existing control mechanism remains.

304 P64-TM-EN-1
P64 Chapter 13 - Monitoring and Control

Note:
For Control Authority for CB/Switches, it is mandatory to select the option of L/R for CB/Switches if IEC 61850 is used.

P64-TM-EN-1 305
Chapter 13 - Monitoring and Control P64

306 P64-TM-EN-1
CHAPTER 14

SUPERVISION
Chapter 14 - Supervision P64

14.1 CHAPTER OVERVIEW


This chapter describes the supervison functions.
This chapter contains the following sections:
Chapter Overview 308
Voltage Transformer Supervision 309
Current Transformer Supervision 314
Trip Circuit Supervision 318

308 P64-TM-EN-1
P64 Chapter 14 - Supervision

14.2 VOLTAGE TRANSFORMER SUPERVISION


The Voltage Transformer Supervision (VTS) function is used to detect failure of the AC voltage inputs to the
protection. This may be caused by voltage transformer faults, overloading, or faults on the wiring, which usually
results in one or more of the voltage transformer fuses blowing.
If there is a failure of the AC voltage input, the IED could misinterpret this as a failure of the actual phase voltages
on the power system, which could result in unnecessary tripping of a circuit breaker.
The VTS logic is designed to prevent such a situation by detecting voltage input failures, which are NOT caused by
power system phase voltage failure, and automatically blocking associated voltage dependent protection elements.
A time-delayed alarm output is available to warn of a VTS condition.
The following scenarios are possible with respect to the failure of the VT inputs.
● Loss of one or two-phase voltages
● Loss of all three-phase voltages under load conditions
● Absence of three-phase voltages upon line energisation

14.2.1 LOSS OF ONE OR TWO PHASE VOLTAGES


If the power system voltages are healthy, no Negative Phase Sequence (NPS) current will be present. If however,
one or two of the AC voltage inputs are missing, there will be Negative Phase Sequence voltage present, even if the
actual power system phase voltages are healthy. VTS works by detecting Negative Phase Sequence (NPS) voltage
without the presence of Negative Phase Sequence current. So if there is NPS voltage present, but no NPS current,
it is certain that there is a problem with the voltage transformers and a VTS block should be applied to voltage
dependent protection functions to prevent maloperation. The use of negative sequence quantities ensures correct
operation even where three-limb or V-connected VTs are used.

14.2.2 LOSS OF ALL THREE PHASE VOLTAGES


If all three voltage inputs are lost, there will be no Negative Phase Sequence quantities present, but the device will
see that there is no voltage input. If this is caused by a power system failure, there will be a step change in the
phase currents. However, if this is not caused by a power system failure, there will be no change in any of the
phase currents. So if there is no measured voltage on any of the three phases and there is no change in any of the
phase currents, this indicates that there is a problem with the voltage transformers and a VTS block should be
applied to voltage dependent protection functions to prevent maloperation.

14.2.3 ABSENCE OF ALL THREE PHASE VOLTAGES ON LINE ENERGISATION


On line energization there should be a change in the phase currents as a result of loading or line charging current.
Under this condition we need an alternative method of detecting three-phase VT failure.
If there is no measured voltage on all three phases during line energization, two conditions might apply:
● A three-phase VT failure
● A close-up three-phase fault.

The first condition would require VTS to block the voltage-dependent functions.
In the second condition, voltage dependent functions should not be blocked, as tripping is required.
To differentiate between these two conditions overcurrent level detectors are used (VTS I> Inhibit and VTS I2>
Inhibit). These prevent a VTS block from being issued in case of a genuine fault. These elements should be set in
excess of any non-fault based currents on line energisation (load, line charging current, transformer inrush current if
applicable), but below the level of current produced by a close-up three-phase fault.

P64-TM-EN-1 309
Chapter 14 - Supervision P64

If the line is closed where a three-phase VT failure is present, the overcurrent detector will not operate and a VTS
block will be applied. Closing onto a three-phase fault will result in operation of the overcurrent detector and prevent
a VTS block being applied.

14.2.4 VTS IMPLEMENTATION


Voltage Transformer Supervision is usually used with devices with a 3-phase voltage input, such as the P643 and
P645 with the optional 3phase VT input. it can however be implemented in a P642, but only if you have ordered a
model with 2-VT inputs, and if the VTs are configured as shown in the wiring diagrams.
VTS is implemented in the SUPERVISION column of the relevant settings group, under the sub-heading VT
SUPERVISION.
The following settings are relevant for VT Supervision:
● VTS Status: determines whether the VTS Operate output will be a blocking output or an alarm indication only
● VTS Reset Mode: determines whether the Reset is to be manual or automatic
● VTS Time delay: determines the operating time delay
● VTS I> Inhibit: inhibits VTS operation in the case of a phase overcurrent fault
● VTS I2> Inhibit: inhibits VTS operation in the case of a negative sequence overcurrent fault
VTS is only enabled during a live line condition (as indicated by the pole dead logic) to prevent operation under
dead system conditions.

310 P64-TM-EN-1
P64 Chapter 14 - Supervision

14.2.5 VTS LOGIC


All Poles Dead

IA

VTS I> Inhibit


IB
1
VTS I> Inhibit
IC

VTS I> Inhibit


VA

Hardcoded threshold
VB
&
1 & S
Hardcoded threshold
Q
VC R 1
& VTS Slow Block

Hardcoded threshold
Delta IA

1 & VTS Fast Block


Hardcoded threshold
Delta IB
1 & S
Q
Hardcoded threshold
R
Delta IC

Hardcoded threshold
V2

Hardcoded threshold &

I2

I2>1 Current Set &

VTS Reset Mode


Manual &
1
Auto

MCB/VTS

VTS Status
Indication
Blocking
1 S 1 VT Fail Alarm
Any Pole Dead & Q
R
&
VTS Acc Ind

V01224 Note: This diagram does not show all stages. Other stages follow similar principles.

Figure 150: VTS logic (P642 with 2 single-phase VTs)

P64-TM-EN-1 311
Chapter 14 - Supervision P64

All Poles Dead

IA

VTS I> Inhibit

IB
1
VTS I> Inhibit

IC

VTS I> Inhibit

VAB

Hardcoded threshold
&
VBC 1 & S
Q
R 1
Hardcoded threshold & VTS Slow Block

Delt a IA

1 & VTS Fast Block


Hardcoded threshold
Delt a IB
1 & S
Q
Hardcoded threshold
R
Delt a IC

Hardcoded threshold
V2

Hardcoded threshold &

I2

I2>1 Current Set &

VTS Reset Mode


Manual &
1
Auto

MCB/VTS

VTS Status
Indicat ion
Blocking
1 S 1 VT Fail Alarm
Any Pole Dead & Q
R
&
VTS Acc Ind

V01225 Note: This diagram does not show all stages. Other stages follow similar principles.

Figure 151: VTS logic (P643 and P645 with 3-phase VTs)

For the P643 and P645, a 3-phase VT is used and each of the input voltages VA, VB and VC are with respect to
earth. For the P642, two single-phase VTs are used and the two input voltages VA and VB are phase-to-phase
voltages

312 P64-TM-EN-1
P64 Chapter 14 - Supervision

As can be seen from the diagram, the VTS function is inhibited if:
● An All Poles Dead DDB signal is present
● A phase overcurrent condition exists
● A Negative Phase Sequence current exists
● If the phase current changes over the period of 1 cycle

The VTS will operate if:


● All three of the input voltages are lower than the VTS Pickup threshold AND the function is not inhibited by
any of the above criteria
● Negative Sequence Voltage is present AND the function is not inhibited by any of the above criteria

The NPS voltage and current detection criteria (used for the case when one or two voltage inputs are lost) is
inhibited if an Any Pole Dead signal is present.

P64-TM-EN-1 313
Chapter 14 - Supervision P64

14.3 CURRENT TRANSFORMER SUPERVISION


The Current Transformer Supervision function (CTS) is used to detect failure of the AC current inputs to the
protection. This may be caused by internal current transformer faults, overloading, or faults on the wiring. If there is
a failure of the AC current input, the protection could misinterpret this as a failure of the actual phase currents on
the power system, which could result in maloperation. Also, an open circuit in the AC current circuits can cause
dangerous CT secondary voltages to be generated.

14.3.1 CTS IMPLEMENTATION


Differential current transformer supervision is based on the measurement of the ratio of negative sequence current
to positive sequence current (I2/I1) for each CT. When this ratio is not zero, one of the following two conditions may
be present:
● There is an unbalanced fault
● There is a 1 or 2 phase CT problem

If the I2/I1 ratio is greater than the high set value, CTS I2/I1>2 at all ends, it is almost certainly a genuine fault
condition, thus the CTS will not operate. If this ratio is detected at one end only, one of the following conditions may
be present:
● A CT problem
● A single end fed fault condition

The positive sequence current I1 is used to confirm whether it is a CT problem or not. If I1 is greater than the setting
CTS I1 at all terminals, it must be a CT problem and CTS is allowed to operate. If this condition is detected at only
one end, the device assumes it is caused by either an inrush condition or a single-end fed internal fault. In this case,
CTS operation is blocked.
The CTS status setting under the CT SUPERVISION sub-heading can be set to either indication or
restraint. In indication mode, the CTS alarm time delay is automatically set to zero. If a CT failure is present, an
alarm would be issued without delay, but the differential protection would remain unrestricted. In restraint mode, the
differential protection is blocked for 20 ms after CT failure has been detected, after which the restraint region of the
bias characteristic increases according to the setting Is-CTS , which has been defined in the DIFF PROTECTION
column.

Idiff/In

Operating region K2

Is-CTS

K1
Is1
Restraint region

Is1/K1 Is2 Ibias/In


V01226

Figure 152: CTS restraint region increase

The low impedance REF, earth fault and NPS overcurrent protection functions are internally blocked by CTS when a
CT failure is detected in the relevant CT. However, earth fault protection is immune to CTS blocking if IN> input is
set to measured.

314 P64-TM-EN-1
P64 Chapter 14 - Supervision

The CTS monitors the positive and negative sequence currents of all CTs (2 to 5, depending on the model). A faulty
CT is determined if the following conditions are present at the same time:
● The positive sequence current in at least two current inputs exceeds the set release threshold I1 (CTS I1
setting under the SUPERVISON column). This also means that CTS can only operate if minimum load
current of the protected object is present.
● A high set ratio of negative to positive sequence current, CTS I2/I1>2, is exceeded at one end.
● At all other ends the ratio of negative to positive sequence current is less than a low set value, CTS I2/I1> 1,
or no significant current is present (positive sequence current is below the release threshold I1).

Only a single or double phase CT failure can be detected by this logic. The probability of symmetrical three-phase
CT failures is very low, therefore in practice this is not a significant problem.

P64-TM-EN-1 315
Chapter 14 - Supervision P64

14.3.2 CTS LOGIC


CT1 I1 > CTS I1
CT2 I1 > CTS I1
CT3 I1 > CTS I1 ≥2 1 CT Fail alarm
CT4 I1 > CTS I1
CT5 I1 > CTS I1

Inhibit CTS 1
1
Inrush detector & CTS Blk

CT Exclusion Alarm

CT1 I2/I1 > CTS I2/I1>2


CT2 I2/I1 > CTS I2/I1>1 & CT1 Fail
&
CT3 I2/I1 > CTS I2/I1>1 &
CT4 I2/I1 > CTS I2/I1>1
& CTS CT1
CT5 I2/I1 > CTS I2/I1>1

CT1 I2/I1 > CTS I2/I1>1


CT2 I2/I1 > CTS I2/I1>2 & CT2 Fail
&
CT3 I2/I1 > CTS I2/I1>1 &
CT4 I2/I1 > CTS I2/I1>1
& CTS CT2
CT5 I2/I1 > CTS I2/I1>1

CT1 I2/I1 > CTS I2/I1>1


CT2 I2/I1 > CTS I2/I1>1 & CT3 Fail
&
CT3 I2/I1 > CTS I2/I1>2 &
CT4 I2/I1 > CTS I2/I1>1
& CTS CT3
CT5 I2/I1 > CTS I2/I1>1

CT1 I2/I1 > CTS I2/I1>1


CT2 I2/I1 > CTS I2/I1>1 & CT4 Fail
&
CT3 I2/I1 > CTS I2/I1>1 &
CT4 I2/I1 > CTS I2/I1>2
& CTS CT4
CT5 I2/I1 > CTS I2/I1>1

CT1 I2/I1 > CTS I2/I1>1


CT2 I2/I1 > CTS I2/I1>1 & CT5 Fail
&
CT3 I2/I1 > CTS I2/I1>1 &
CT4 I2/I1 > CTS I2/I1>1
& CTS CT5
CT5 I2/I1 > CTS I2/I1>2

1
CTS Status
Indication
Restrain

V01227

Figure 153: CTS logic diagram

14.3.3 APPLICATION NOTES

14.3.3.1 SETTING GUIDELINES


The positive sequence current in at least two current inputs exceeds the CTS I1 setting. The CTS I1 setting should
be below the minimum load current of the protected object. Therefore, 10% of the rated current might be used.

316 P64-TM-EN-1
P64 Chapter 14 - Supervision

The high set ratio of negative to positive sequence current, CTS I2/I1>2, should be set below the ratio of negative
sequence to positive sequence current for the minimum unbalanced fault current. When the balanced full load
current is flowing and the secondary of Phase A CT1 is disconnected, the currents measured by the device are:
IA = 0
IB = 1 Ð -120°
IC = 1 Ð -240°
The positive and negative sequence currents are calculated as:

1 2
I1 = ( I A + aI B + a 2 I C ) =
3 3

1 1
I1 = ( I A + a 2 I B + aI C ) =
3 3
The ratio of negative to positive sequence current is 50%, therefore a typical setting of 40% might be used.
The low set ratio of negative to positive sequence current, CTS I2/I1>1, should be set above the maximum load
unbalance. In practise, the levels of standing negative phase sequence current present on the system govern this
minimum setting. This can be determined from a system study, or by making use of the device's measurement
facilities at the commissioning stage. If the latter method is adopted, it is important to take the measurements during
maximum system load conditions, to ensure that all single-phase loads are accounted for. A 20% setting might be
used.
If the following information is recorded by the relay during commissioning:
I full load = 500 A
I2 = 50 A
Therefore I2/I1 ratio is given by I2/I1 = 50/500 = 0.1
To allow for tolerances and load variations a setting of 20% of this value may be typical. Therefore set CTS I2/I1>1
= 20%.
Due to the sensitive settings suggested above, a long time delay is necessary to ensure a true CT failure. We
recommend using the default setting for this time time delay. After the CTS Time Delay expires (CTS Time Delay),
the CTS Fail Alarm is asserted.

P64-TM-EN-1 317
Chapter 14 - Supervision P64

14.4 TRIP CIRCUIT SUPERVISION


In most protection schemes, the trip circuit extends beyond the IED enclosure and passes through components
such as links, relay contacts, auxiliary switches and other terminal boards. Such complex arrangements may
require dedicated schemes for their supervision.
There are two distinctly separate parts to the trip circuit; the trip path, and the trip coil. The trip path is the path
between the IED enclosure and the CB cubicle. This path contains ancillary components such as cables, fuses and
connectors. A break in this path is possible, so it is desirable to supervise this trip path and to raise an alarm if a
break should appear in this path.
The trip coil itself is also part of the overall trip circuit, and it is also possible for the trip coil to develop an open-
circuit fault.
This product supports a number of trip circuit supervision (TCS) schemes.

14.4.1 TRIP CIRCUIT SUPERVISION SCHEME 1


This scheme provides supervision of the trip coil with the CB open or closed, however, it does not provide
supervision of the trip path whilst the breaker is open. The CB status can be monitored when a self-reset trip
contact is used. However, this scheme is incompatible with latched trip contacts, as a latched contact will short out
the opto-input for a time exceeding the recommended Delayed Drop-off (DDO) timer setting of 400 ms, and
therefore does not support CB status monitoring. If you require CB status monitoring, further opto-inputs must be
used.

Note:
A 52a CB auxiliary contact follows the CB position. A 52b auxiliary contact is the opposite.

+ve

Trip Output Relay 52A Trip coil


Trip path

Blocking diode

52B

R1 Opto-input Circuit Breaker


V01214 -ve

Figure 154: TCS Scheme 1

When the CB is closed, supervision current passes through the opto-input, blocking diode and trip coil. When the
CB is open, supervision current flows through the opto-input and into the trip coil via the 52b auxiliary contact. This
means that Trip Coil supervision is provided when the CB is either closed or open, however Trip Path supervision is
only provided when the CB is closed. No supervision of the trip path is provided whilst the CB is open (pre-closing
supervision). Any fault in the trip path will only be detected on CB closing, after a 400 ms delay.

14.4.1.1 RESISTOR VALUES


The supervision current is a lot less than the current required by the trip coil to trip a CB. The opto-input limits this
supervision current to less than 10 mA. If the opto-input were to be short-circuited however, it could be possible for
the supervision current to reach a level that could trip the CB. For this reason, a resistor R1 is often used to limit the
current in the event of a short-circuited opto-input. This limits the current to less than 60mA. The table below shows
the appropriate resistor value and voltage setting for this scheme.

318 P64-TM-EN-1
P64 Chapter 14 - Supervision

Trip Circuit Voltage Opto Voltage Setting with R1 Fitted Resistor R1 (ohms)
48/54 24/27 1.2k
110/125 48/54 2.7k
220/250 110/125 5.2k

Warning:
This Scheme is not compatible with Trip Circuit voltages of less than 48 V.

14.4.1.2 PSL FOR TCS SCHEME 1

0 0
Opto Input dropoff Straight *Output Relay
400 0

50
& pickup Latching LED
0

User Alarm

*NC stands for Normally Closed. V01217

Figure 155: PSL for TCS Scheme 1

The opto-input can be used to drive a Normally Closed Output Relay, which in turn can be used to drive alarm
equipment. The signal can also be inverted to drive a latching programmable LED and a user alarm DDB signal.
The DDO timer operates as soon as the opto-input is energised, but will take 400 ms to drop off/reset in the event of
a trip circuit failure. The 400 ms delay prevents a false alarm due to voltage dips caused by faults in other circuits or
during normal tripping operation when the opto-input is shorted by a self-reset trip contact. When the timer is
operated the NC (normally closed) output relay opens and the LED and user alarms are reset.
The 50 ms delay on pick-up timer prevents false LED and user alarm indications during the power up time, following
a voltage supply interruption.

14.4.2 TRIP CIRCUIT SUPERVISION SCHEME 3


TCS Scheme 3 is designed to provide supervision of the trip coil with the breaker open or closed. It provides pre-
closing supervision of the trip path. Since only one opto-input is used, this scheme is not compatible with latched
trip contacts. If you require CB status monitoring, further opto-inputs must be used.

+ve
R3
Output Relay Trip coil
Trip path 52A

R2
52B

Opto-input R1 Circuit Breaker


-ve
V01216

Figure 156: TCS Scheme 3

When the CB is closed, supervision current passes through the opto-input, resistor R2 and the trip coil. When the
CB is open, current flows through the opto-input, resistors R1 and R2 (in parallel), resistor R3 and the trip coil. The

P64-TM-EN-1 319
Chapter 14 - Supervision P64

supervision current is maintained through the trip path with the breaker in either state, therefore providing pre-
closing supervision.

14.4.2.1 RESISTOR VALUES


Resistors R1 and R2 are used to prevent false tripping, if the opto-input is accidentally shorted. However, unlike the
other two schemes. This scheme is dependent upon the position and value of these resistors. Removing them
would result in incomplete trip circuit monitoring. The table below shows the resistor values and voltage settings
required for satisfactory operation.
Opto Voltage Setting with R1
Trip Circuit Voltage Resistor R1 & R2 (ohms) Resistor R3 (ohms)
Fitted
48/54 24/27 1.2k 600
110/250 48/54 2.7k 1.2k
220/250 110/125 5.0k 2.5k

Warning:
This Scheme is not compatible with Trip Circuit voltages of less than 48 V.

14.4.2.2 PSL FOR TCS SCHEME 3

0 0
Opto Input dropoff Straight *Output Relay
400 0

50
& pickup Latching LED
0

User Alarm

*NC stands for Normally Closed. V01217

Figure 157: PSL for TCS Scheme 3

320 P64-TM-EN-1
CHAPTER 15

DIGITAL I/O AND PSL CONFIGURATION


Chapter 15 - Digital I/O and PSL Configuration P64

15.1 CHAPTER OVERVIEW


This chapter introduces the PSL (Programmable Scheme Logic) Editor, and describes the configuration of the
digital inputs and outputs. It provides an outline of scheme logic concepts and the PSL Editor. This is followed by
details about allocation of the digital inputs and outputs, which require the use of the PSL Editor. A separate
"Settings Application Software" document is available that gives a comprehensive description of the PSL, but
enough information is provided in this chapter to allow you to allocate the principal digital inputs and outputs.
This chapter contains the following sections:
Chapter Overview 322
Configuring Digital Inputs and Outputs 323
Scheme Logic 324
Configuring the Opto-Inputs 326
Assigning the Output Relays 327
Fixed Function LEDs 328
Configuring Programmable LEDs 329
Function Keys 331
Control Inputs 332
User Alarms 333

322 P64-TM-EN-1
P64 Chapter 15 - Digital I/O and PSL Configuration

15.2 CONFIGURING DIGITAL INPUTS AND OUTPUTS


Configuration of the digital inputs and outputs in this product is very flexible. You can use a combination of settings
and programmable logic to customise them to your application. You can access some of the settings using the
keypad on the front panel, but you will need a computer running the settings application software to fully interrogate
and configure the properties of the digital inputs and outputs.
The settings application software includes an application called the PSL Editor (Programmable Scheme Logic
Editor). The PSL Editor lets you allocate inputs and outputs according to your specific application. It also allows you
to apply attributes to some of the signals such as a drop-off delay for an output contact.
In this product, digital inputs and outputs that are configurable are:
● Optically isolated digital inputs (opto-inputs). These can be used to monitor the status of associated plant.
● Output relays. These can be used for purposes such as initiating the tripping of circuit breakers, providing
alarm signals, etc..
● Programmable LEDs. The number and colour of the programmable LEDs varies according to the particular
product being applied.
● Function keys and associated LED indications. These are not provided on all products, but where they are,
each function key has an associated tri-colour LED.
● IEC 61850 GOOSE inputs and outputs. These are only provided on products that have been specified for
connection to an IEC61850 system, and the details of the GOOSE are presented in the documentation on
IEC61850.

P64-TM-EN-1 323
Chapter 15 - Digital I/O and PSL Configuration P64

15.3 SCHEME LOGIC


The product is supplied with pre-loaded Fixed Scheme Logic (FSL) and Programmable Scheme Logic (PSL).
The Scheme Logic is a functional module within the IED, through which all mapping of inputs to outputs is handled.
The scheme logic can be split into two parts; the Fixed Scheme Logic (FSL) and the Programmable Scheme Logic
(PSL). It is built around a concept called the digital data bus (DDB). The DDB encompasses all of the digital signals
(DDBs) which are used in the FSL and PSL. The DDBs included digital inputs, outputs, and internal signals.
The FSL is logic that has been hard-coded in the product. It is fundamental to correct interaction between various
protection and/or control elements. It is fixed and cannot be changed.
The PSL gives you a facility to develop custom schemes to suit your application if the factory-programmed default
PSL schemes do not meet your needs. Default PSL schemes are programmed before the product leaves the
factory. These default PSL schemes have been designed to suit typical applications and if these schemes suit your
requirements, you do not need to take any action. However, if you want to change the input-output mappings, or to
implement custom scheme logic, you can change these, or create new PSL schemes using the PSL editor.
The PSL consists of components such as logic gates and timers, which combine and condition DDB signals.
The logic gates can be programmed to perform a range of different logic functions. The number of inputs to a logic
gate are not limited. The timers can be used either to create a programmable delay or to condition the logic outputs.
Output contacts and programmable LEDs have dedicated conditioners.
The PSL logic is event driven. Only the part of the PSL logic that is affected by the particular input change that has
occurred is processed. This minimises the amount of processing time used by the PSL ensuring industry leading
performance.
The following diagram shows how the scheme logic interacts with the rest of the IED.

Energising quantities Protection functions Fixed LEDs


SL outputs
SL inputs

Opto-inputs Programmable LEDs


PSL and FSL

Function keys Output relays


Goose outputs
Control inputs

Goose inputs

Control input Ethernet


module processing module

V02011

Figure 158: Scheme Logic Interfaces

324 P64-TM-EN-1
P64 Chapter 15 - Digital I/O and PSL Configuration

15.3.1 PSL EDITOR


The Programmable Scheme Logic (PSL) is a module of programmable logic gates and timers in the IED, which can
be used to create customised logic to qualify how the product manages its response to system conditions. The
IED's digital inputs are combined with internally generated digital signals using logic gates, timers, and conditioners.
The resultant signals are then mapped to digital outputs signals including output relays and LEDs.
The PSL Editor is a tool in the settings application software that allows you to create and edit scheme logic
diagrams. You can use the default scheme logic which has been designed to suit most applications, but if it does
not suit your application you can change it. If you create a different scheme logic with the software, you need to
upload it to the device to apply it.

15.3.2 PSL SCHEMES


Your product is shipped with default scheme files. These can be used without modification for most applications, or
you can choose to use them as a starting point to design your own scheme. You can also create a new scheme
from scratch. To create a new scheme, or to modify an existing scheme, you will need to launch the settings
application software. You then need to open an existing PSL file, or create a new one, for the particular product that
you are using, and then open a PSL file. If you want to create a new PSL file, you should select File then New then
Blank scheme... This action opens a default file appropriate for the device in question, but deletes the diagram
components from the default file to leave an empty diagram with configuration information loaded. To open an
existing file, or a default file, simply double-click on it.

15.3.3 PSL SCHEME VERSION CONTROL


To help you keep track of the PSL loaded into products, a version control feature is included. The user interface
contains a PSL DATA column, which can be used to track PSL modifications. A total of 12 cells are contained in the
PSL DATA column; 3 for each setting group.
Grp(n) PSL Ref: When downloading a PSL scheme to an IED, you will be prompted to enter the relevant group
number and a reference identifier. The first 32 characters of the reference identifier are displayed in this cell. The
horizontal cursor keys can scroll through the 32 characters as the LCD display only displays 16 characters.

Example:

Grp(n) PSL Ref

Date/time: This cell displays the date and time when the PSL scheme was downloaded to the IED.

Example:

18 Nov 2002
08:59:32.047

Grp(n) PSL ID: This cell displays a unique ID number for the downloaded PSL scheme.

Example:

Grp(n) PSL ID
ID - 2062813232

P64-TM-EN-1 325
Chapter 15 - Digital I/O and PSL Configuration P64

15.4 CONFIGURING THE OPTO-INPUTS


The number of optically isolated status inputs (opto-inputs) depends on the specific model supplied. The use of the
inputs will depend on the application, and their allocation is defined in the programmable scheme logic (PSL). In
addition to the PSL assignment, you also need to specify the expected input voltage. Generally, all opto-inputs will
share the same input voltage range, but if different voltage ranges are being used, this device can accommodate
them.
In the OPTO CONFIG column there is a global nominal voltage setting. If all opto-inputs are going to be energised
from the same voltage range, you select the appropriate value in the setting. If you select Custom in the setting,
then the cells Opto Input 1, Opto Input 2, etc. become visible. You use these cells to set the voltage ranges for
each individual opto-input.
Within the OPTO CONFIG column there are also settings to control the filtering applied to the inputs, as well as the
pick-up/drop-off characteristic.
The filter control setting provides a bit string with a bit associated with all opto-inputs. Setting the bit to ‘1’ means
that a half-cycle filter is applied to the inputs. This helps to prevent incorrect operation in the event of power system
frequency interference on the wiring. Setting the field to ‘0’ removes the filter and provides for faster operation.
The Characteristic setting is a single setting that applies to all the opto-inputs. It is used to set the pick-up/drop-off
ratios of the input signals. As standard it is set to 80% pick-up and 60% drop-off, but you can change it to other
available thresholds if that suits your operational requirements.

326 P64-TM-EN-1
P64 Chapter 15 - Digital I/O and PSL Configuration

15.5 ASSIGNING THE OUTPUT RELAYS


Relay contact action is controlled using the PSL. DDB signals are mapped in the PSL and drive the output relays.
The driving of an output relay is controlled by means of a relay output conditioner. Several choices are available for
how output relay contacts are conditioned. For example, you can choose whether operation of an output relay
contact is latched, has delay on pick-up, or has a delay on drop-off. You make this choice in the Contact
Properties window associated with the output relay conditioner.
To map an output relay in the PSL you should use the Contact Conditioner button in the toolbar to import it. You
then condition it according to your needs. The output of the conditioner respects the attributes you have assigned.
The toolbar button for a Contact Conditioner looks like this:

The PSL contribution that it delivers looks like this:

Note:
Contact Conditioners are only available if they have not all been used. In some default PSL schemes, all Contact Conditioners
might have been used. If that is the case, and you want to use them for something else, you will need to re-assign them.

On the toolbar there is another button associated with the relay outputs. The button looks like this:

This is the "Contact Signal" button. It allows you to put replica instances of a conditioned output relay into the PSL,
preventing you having to make cross-page connections which might detract from the clarity of the scheme.

P64-TM-EN-1 327
Chapter 15 - Digital I/O and PSL Configuration P64

15.6 FIXED FUNCTION LEDS


Four fixed-function LEDs on the left-hand side of the front panel indicate the following conditions.
● Trip (Red) switches ON when the IED issues a trip signal. It is reset when the associated fault record is
cleared from the front display. Also the trip LED can be configured as self-resetting.
● Alarm (Yellow) flashes when the IED registers an alarm. This may be triggered by a fault, event or
maintenance record. The LED flashes until the alarms have been accepted (read), then changes to
constantly ON. When the alarms are cleared, the LED switches OFF.
● Out of service (Yellow) is ON when the IED's functions are unavailable.
● Healthy (Green) is ON when the IED is in correct working order, and should be ON at all times. It goes OFF if
the unit’s self-tests show there is an error in the hardware or software. The state of the healthy LED is
reflected by the watchdog contacts at the back of the unit.

15.6.1 TRIP LED LOGIC


When a trip occurs, the trip LED is illuminated. It is possible to reset this with a number of ways:
● Directly with a reset command (by pressing the Clear Key)
● With a reset logic input
● With self-resetting logic

You enable the automatic self-resetting with the Sys Fn Links cell in the SYSTEM DATA column. A '0' disables self
resetting and a '1' enables self resetting.
The reset occurs when the circuit is reclosed and the Any Pole Dead signal has been reset for three seconds
providing the Any Start signal is inactive. The reset is prevented if the Any Start signal is active after the breaker
closes.
The Trip LED logic is as follows:

Any Trip S
Q Trip LED Trigger
Reset R
1
Reset Relays/LED

Sys Fn Links
Trip LED S/Reset
3s
&

Any Pole Dead

Any Start

V01211

Figure 159: Trip LED logic

328 P64-TM-EN-1
P64 Chapter 15 - Digital I/O and PSL Configuration

15.7 CONFIGURING PROGRAMMABLE LEDS


There are three types of programmable LED signals which vary according to the model being used. These are:
● Single-colour programmable LED. These are red when illuminated.
● Tri-colour programmable LED. These can be illuminated red, green, or amber.
● Tri-colour programmable LED associated with a Function Key. These can be illuminated red, green, or amber.

DDB signals are mapped in the PSL and used to illuminate the LEDs. For single-coloured programmable LEDs
there is one DDB signal per LED. For tri-coloured LEDs there are two DDB signals associated with the LED.
Asserting LED # Grn will illuminate the LED green. Asserting LED # Red will illuminate the LED red. Asserting both
DDB signals will illuminate the LED amber.
The illumination of an LED is controlled by means of a conditioner. Using the conditioner, you can decide whether
the LEDs reflect the real-time state of the DDB signals, or whether illumination is latched pending user intervention.
To map an LED in the PSL you should use the LED Conditioner button in the toolbar to import it. You then condition
it according to your needs. The output(s) of the conditioner respect the attribute you have assigned.
The toolbar button for a tri-colour LED looks like this:

The PSL contribution that it delivers looks like this:

The toolbar button for a single-colour LED looks like this:

The PSL contribution that it delivers looks like this.

Note:
LED Conditioners are only available if they have not all been used up, and in some default PSL schemes they might be. If that
is the case and you want to use them for something else, you will need to re-assign them.

On the toolbar there is another button associated with the LEDs. For a tri-coloured LED the button looks like this:

For a single-colour LED it looks like this:

It is the "LED Signal" button. It allows you to put replica instances of a conditioned LED into the PSL, preventing you
having to make cross-page connections which might detract from the clarity of the scheme.

P64-TM-EN-1 329
Chapter 15 - Digital I/O and PSL Configuration P64

Note:
All LED DDB signals are always shown in the PSL Editor. However, the actual number of LEDs depends on the device
hardware. For example, if a small 20TE device has only 4 programmable LEDs, LEDs 5-8 will not take effect even if they are
mapped in the PSL.

330 P64-TM-EN-1
P64 Chapter 15 - Digital I/O and PSL Configuration

15.8 FUNCTION KEYS


For most models, a number of programmable function keys are available. This allows you to assign function keys to
control functionality via the programmable scheme logic (PSL). Each function key is associated with a
programmable tri-colour LED, which you can program to give the desired indication on activation of the function key.
These function keys can be used to trigger any function that they are connected to as part of the PSL. The function
key commands are found in the FUNCTION KEYS column.
Each function key is associated with a DDB signal as shown in the DDB table. You can map these DDB signals to
any function available in the PSL.
The Fn Key Status cell displays the status (energised or de-energised) of the function keys by means of a binary
string, where each bit represents a function key starting with bit 0 for function key 1.
Each function key has three settings associated with it, as shown:
● Fn Key (n), which enables or disables the function key
● Fn Key (n) Mode, which allows you to configure the key as toggled or normal
● Fn Key (n) label, which allows you to define the function key text that is displayed

The Fn Key (n) cell is used to enable (unlock) or disable (unlock) the function key signals in PSL. The Lock setting
has been provided to prevent further activation on subsequent key presses. This allows function keys that are set to
Toggled mode and their DDB signal active ‘high’, to be locked in their active state therefore preventing any further
key presses from deactivating the associated function. Locking a function key that is set to the “Normal” mode
causes the associated DDB signals to be permanently off. This safety feature prevents any inadvertent function key
presses from activating or deactivating critical functions.
When the Fn Key (n) Mode cell is set to Toggle, the function key DDB signal output will remain in the set state
until a reset command is given. In the Normal mode, the function key DDB signal will remain energised for as long
as the function key is pressed and will then reset automatically. In this mode, a minimum pulse duration can be
programmed by adding a minimum pulse timer to the function key DDB output signal.
The Fn Key Label cell makes it possible to change the text associated with each individual function key. This text
will be displayed when a function key is accessed in the function key menu, or it can be displayed in the PSL.
The status of all function keys are recorded in non-volatile memory. In case of auxiliary supply interruption their
status will be maintained.

Note:
All function key DDB signals are always shown in the PSL Editor. However, the actual number of function keys depends on
the device hardware. For example, if a small 20TE device has no function keys, the function key DDBs mapped in the PSL
will not take effect.

P64-TM-EN-1 331
Chapter 15 - Digital I/O and PSL Configuration P64

15.9 CONTROL INPUTS


The control inputs are software switches, which can be set or reset locally or remotely. These inputs can be used to
trigger any PSL function to which they are connected. There are three setting columns associated with the control
inputs: CONTROL INPUTS, CTRL I/P CONFIG and CTRL I/P LABELS. These are listed in the Settings and
Records appendix at the end of this manual.

332 P64-TM-EN-1
P64 Chapter 15 - Digital I/O and PSL Configuration

15.10 USER ALARMS


User Alarms can be operated from an opto input or a control input using the PSL. They are useful for giving an
alarm led and message on the LCD display, and an alarm indication via the communications of an external
condition - for example: trip circuit supervision alarm, and temperature alarm etc. In the USER ALARMS menu, the
Manual Reset 32 bit binary string (0 self-reset, 1 manual reset) can be used to set the operating mode of the user
alarms to self or manual reset. The User Alarm 1-32 labels in the USER ALARMS menu column are used to
individually label each user alarm. The text is restricted to 16 characters.

P64-TM-EN-1 333
Chapter 15 - Digital I/O and PSL Configuration P64

334 P64-TM-EN-1
CHAPTER 16

COMMUNICATIONS
Chapter 16 - Communications P64

16.1 CHAPTER OVERVIEW


This product supports Substation Automation System (SAS), and Supervisory Control and Data Acquisition
(SCADA) communication through multiple interfaces and a choice of data protocols.
All products support rugged serial communications for SCADA and SAS applications. Optionally, any product can
support Ethernet communications for IEC 61850, cyber security and remote access, either through a single port or
industry-standard redundant ports.
This chapter contains the following sections:
Chapter Overview 336
Communication Interfaces 337
Serial Communication 338
Ethernet Board Versions 341
Board Connections 342
Ethernet Configuration 344
Redundancy Protocols 346
Simple Network Management Protocol (SNMP) 351
Data Protocols 355
Time Synchronisation 383

336 P64-TM-EN-1
P64 Chapter 16 - Communications

16.2 COMMUNICATION INTERFACES


The products have a number of standard and optional communication interfaces. The standard and optional
hardware and protocols are summarised below:

Port Availability Physical lnterface Use Data Protocols


Front Standard USB Type B Local settings Courier
Rear Port 1 SCADA
Standard RS232/RS485/K-Bus Courier, IEC 60870-5-103, DNP3.0
(RP1 copper) Remote settings
Rear Port 1 SCADA
Optional Fibre Courier, IEC 60870-5-103, DNP3.0
(RP1 fibre) Remote settings
Rear Port 2 SCADA SK4: Courier only
Optional RS232/RS485/K-Bus
(RP2) Remote settings SK5: InterMiCOM only
IEC 61850
Ethernet Optional Ethernet IEC 61850, Courier Tunnel
Remote settings

Note:
Optional communications boards are always fitted into slot A. It is only possible to fit one optional communications board,
therefore RP2 and Ethernet communications are mutually exclusive, except for ZN0098005, where both Ethernet and serial
protocols are supported.
On RP1, any one of the data protocols can be selected at one time, from the COMMUNICATIONS Menu (it is no longer
necessary to select one as a product order option).

P64-TM-EN-1 337
Chapter 16 - Communications P64

16.3 SERIAL COMMUNICATION


The physical layer standards that are used for serial communications for SCADA purposes are:
● EIA(RS)485 (often abbreviated to RS485)
● K-Bus (a proprietary customization of RS485)

USB is used for local communication with the IED (for transferring settings and downloading firmware updates).
RS485 is similar to RS232 but for longer distances and it allows daisy-chaining and multi-dropping of IEDs.
K-Bus is a proprietary protocol quite similar to RS485, but it cannot be mixed on the same link as RS485. Unlike
RS485, K-Bus signals applied across two terminals are not polarised.
It is important to note that these are not data protocols. They only describe the physical characteristics required for
two devices to communicate with each other.
For a description of the K-Bus standard see K-Bus and GE Vernova's K-Bus interface guide reference R6509.
A full description of the RS485 is available in the published standard.

16.3.1 USB FRONT PORT


The USB interface uses the proprietary Courier protocol for local communication with the MiCOM S1 Agile settings
application software.
This is intended for temporary local connection and is not suitable for permanent connection. This interface uses a
fixed baud rate of 19200 bps, 11-bit frame (8 data bits, 1 start bit, 1 stop bit, even parity bit), and a fixed device
address of '1'.
The USB interface is a Type B connector. Normally a Type A to Type B USB cable will be required to communicate
between MiCOM S1 Agile and the IED.

16.3.2 EIA(RS)485 BUS


The RS485 two-wire connection provides a half-duplex, fully isolated serial connection to the IED. The connection is
polarized but there is no agreed definition of which terminal is which. If the master is unable to communicate with
the product, and the communication parameters match, then it is possible that the two-wire connection is reversed.
The RS485 bus must be terminated at each end with 120 Ω 0.5 W terminating resistors between the signal wires.
The RS485 standard requires that each device be directly connected to the actual bus. Stubs and tees are
forbidden. Loop bus and Star topologies are not part of the RS485 standard and are also forbidden.
Two-core screened twisted pair cable should be used. The final cable specification is dependent on the application,
although a multi-strand 0.5 mm2 per core is normally adequate. The total cable length must not exceed 1000 m. It is
important to avoid circulating currents, which can cause noise and interference, especially when the cable runs
between buildings. For this reason, the screen should be continuous and connected to ground at one end only,
normally at the master connection point.
The RS485 signal is a differential signal and there is no signal ground connection. If a signal ground connection is
present in the bus cable then it must be ignored. At no stage should this be connected to the cable's screen or to
the product’s chassis. This is for both safety and noise reasons.
It may be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal level has an
indeterminate state because the bus is not being actively driven. This can occur when all the slaves are in receive
mode and the master is slow to turn from receive mode to transmit mode. This may be because the master is
waiting in receive mode, in a high impedance state, until it has something to transmit. Jabber causes the receiving
device(s) to miss the first bits of the first character in the packet, which results in the slave rejecting the message
and consequently not responding. Symptoms of this are; poor response times (due to retries), increasing message
error counts, erratic communications, and in the worst case, complete failure to communicate.

338 P64-TM-EN-1
P64 Chapter 16 - Communications

16.3.2.1 EIA(RS)485 BIASING REQUIREMENTS


Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1 V. There should only be
one bias point on the bus, which is best situated at the master connection point. The DC source used for the bias
must be clean to prevent noise being injected.

Note:
Some devices may be able to provide the bus bias, in which case external components would not be required.

6 – 9 V DC

180 Ω bias

Master 120 Ω

180 Ω bias

0V 120 Ω

Slave Slave Slave

V01000

Figure 160: RS485 biasing circuit

Warning:
It is extremely important that the 120 Ω termination resistors are fitted. Otherwise the
bias voltage may be excessive and may damage the devices connected to the bus.

16.3.3 K-BUS
K-Bus is a robust signalling method based on RS485 voltage levels. K-Bus incorporates message framing, based
on a 64 kbps synchronous HDLC protocol with FM0 modulation to increase speed and security.
The rear interface is used to provide a permanent connection for K-Bus, which allows multi-drop connection.
A K-Bus spur consists of up to 32 IEDs connected together in a multi-drop arrangement using twisted pair wiring.
The K-Bus twisted pair connection is non-polarised.
It is not possible to use a standard EIA(RS)232 to EIA(RS)485 converter to convert IEC 60870-5 FT1.2 frames to K-
Bus. A protocol converter, namely the KITZ101 or KITZ102, must be used for this purpose. Please consult GE
Vernova for information regarding the specification and supply of KITZ devices. The following figure demonstrates a
typical K-Bus connection.

P64-TM-EN-1 339
Chapter 16 - Communications P64

C C C

IED IED IED

RS232 K-Bus

Computer RS232-USB converter KITZ protocol converter


V01001
Figure 161: Remote communication using K-Bus

Note:
An RS232-USB converter is only needed if the local computer does not provide an RS232 port.

Further information about K-Bus is available in the publication R6509: K-Bus Interface Guide, which is available on
request.

340 P64-TM-EN-1
P64 Chapter 16 - Communications

16.4 ETHERNET BOARD VERSIONS


Each board combines Ethernet communications, with universal IRIG-B timing functionality. There is a choice of
embedded protocols for the Ethernet communications, and one option that also includes support for serial protocols.

Board variants

Board Part No. Compatible With


One LC duplex Ethernet port with universal IRIG-B and IEEE1588 and Ethernet network, no native
ZN0098 001
one RJ45 Maintenance/Engineering Port redundancy.
Two RJ45 duplex redundant Ethernet ports running RSTP + PRP + HSR
Any PRP, HSR, RSTP or
+ Failover (two copper pairs), with on-board universal IRIG-B and IEEE ZN0098 002
standard Ethernet network
1588 and one RJ45 Maintenance/engineering port
Two LC duplex redundant Ethernet ports running RSTP + PRP + HSR +
Any PRP, HSR, RSTP or
Failover (two fibre pairs), with on-board universal IRIG-B and IEEE 1588 ZN0098 003
standard Ethernet network
and one RJ45 Maintenance/engineering port
Two LC duplex redundant Ethernet ports running RSTP + PRP + HSR + Any PRP, HSR, RSTP or
Failover (two fibre pairs), with serial fibre ST ports with on-board standard Ethernet network. On
ZN0098 005
universal IRIG-B and IEEE 1588 and one RJ45 Maintenance/ the serial interface Courier, IEC
engineering port 60870-5-103, DNP3

When using any of the redundant Ethernet boards on an IED, the final product will have two MAC addresses and
will require two IP addresses, one for the maintenance port (NP1) for management purposes, and one for the IED
station bus communications (NP2). Both of these are set using the IED Configurator tool of MiCOM S1 Agile
release 3.1 or later.
All Ethernet connections are made with 1300 nm multi mode 100BaseFx fiber optic Ethernet ports (LC connector).
The boards support IEC 61850 over Ethernet.

P64-TM-EN-1 341
Chapter 16 - Communications P64

16.5 BOARD CONNECTIONS

ZN0098001 ZN0098002 ZN0098003 ZN0098005

V80015

Figure 162: Board connectors

IRIG-B Connector
● Centre connection: Signal
● Outer connection: Earth

RJ45 Connector (NP1, NP2A and NP2B optional)

Pin Signal Name Signal Definition


1 TXP Transmit (positive)
2 TXN Transmit (negative)
3 RXP Receive (positive)
4 - Not used
5 - Not used
6 RXN Receive (negative)
7 - Not used
8 - Not used

LC Optical Fibre Connectors (NP2A and NP2B optional)

Connector SFP
A TX
B RX

342 P64-TM-EN-1
P64 Chapter 16 - Communications

Optical Fibre Connectors (ST only on part ZN0098005)

Connector Serial Courier, IEC 60870-5-103, DNP3


RP1 TX
RP1 RX

P64-TM-EN-1 343
Chapter 16 - Communications P64

16.6 ETHERNET CONFIGURATION


All configuration for both the monitoring/engineering port and the station bus port is done in IED Configurator.
The monitoring/engineering port is named "Network Port 1" and the redundant IEC 61850 station bus port is named
"Network Port 2".
Network Port 1 (NP1) and Network Port 2 (NP2) have independent IP address and subnet configuration
parameters, as detailed in the sub-section below. These parameters can be configured in IED Configurator, or
optionally from the Front Panel UI.
The IP addresses can be in the range 0.0.0.0 to 223.255.255.255. This means it can be configured as either a
Class A, B or C address.

Class Address Range


A 0.0.0.0 to 127.255.255.255
B 128.0.0.0 to 191.255.255.255
C 192.0.0.0 to 223.255.255.255

The NP1 and NP2 IP addresses must not be configured in the same subnet.
The primary and secondary server IP addresses for RADIUS, syslog and SNMP must also be in these ranges.

16.6.1 NETWORK CONFIGURATION


To set the IP address of the monitoring/engineering port:
1. From the main window click the Communications section.
2. Navigate to the Network Port 1.
3. Enter the required IP address, network mask and gateway.
4. The media is not configurable for the engineering port, as they are always RJ45 copper ports.
To set the IP address of the station bus port:
1. From the main window click the Communications section.
2. Navigate to the Network Port 2.
3. Enter the required IP address, network mask and gateway.
4. In the Network Port 2 General configuration section, the redundancy options become available.
5. If the board supports redundancy, choose the redundant protocol desired (Failover, RSTP, PRP and HSR).
6. Each protocol has its own protocol specific settings, covered in each protocol’s section.
7. The media is not configurable for the station bus port, as they are always enabled according to the ordering
code. The media section is available for legacy boards only.

16.6.2 PRP CONFIGURATION


To view or configure the PRP Parameters:
1. Set the redundancy mode to PRP.
● Multicast Address: Use this field to configure the multicast destination address. All DANPs in the network
must be configured to operate with the same multicast address for the purpose of network supervision.
● Life Check Interval: This defines how often a node sends a PRP_Supervision frame. All DANPs shall be
configured with the same Life Check Interval.

344 P64-TM-EN-1
P64 Chapter 16 - Communications

16.6.3 HSR CONFIGURATION


To view or configure the HSR Parameters:
Set the redundancy mode to HSR.
● Multicast Address: Use this field to configure the multicast destination address. All DANPs in the network
must be configured to operate with the same multicast address for the purpose of network supervision.
● Life Check Interval: This defines how often a node sends an HSR Supervision frame. All DANPs shall be
configured with the same Life Check Interval.

16.6.4 RSTP CONFIGURATION


To view or configure the RSTP Parameters:
Set the redundancy mode to RSTP.
Parameter Default value (second) Minimum value (second) Maximum value (second)
Bridge Max Age 20 6 40
Bridge Hello Time 2 1 10
Bridge Forward Delay 15 4 30
Bridge Priority 32768 0 61440

16.6.5 FAILOVER CONFIGURATION


To view or configure the Failover Parameters:
1. Set the redundancy mode to Failover.
● Port A and Port B radio button allows to select your main port for the Failover. The name of the port in the
board is also shown.
● The Failover time defines how long it takes for the redundancy switch over to trigger. The minimum value is
2s.

16.6.6 SNTP IP ADDRESS CONFIGURATION


To configure the SNTP server IP address:
1. From the main window click the SNTP button.
2. The General configuration allows to set the frequency of the polling of the SNTP server. It also has a check-
box IED is a clock source to configure the IED to be a SNTP server itself, to retransmit its date and time.
3. Under External Server 1 and 2, set the IP address of the SNTP server.

P64-TM-EN-1 345
Chapter 16 - Communications P64

16.7 REDUNDANCY PROTOCOLS


REB variants for each of the following protocols are available:
● PRP (Parallel Redundancy Protocol)
● HSR (High-availability Seamless Redundancy)
● RSTP (Rapid Spanning Tree Protocol)
● Failover

PRP and HSR are open standard, so their implementation is compatible with any standard PRP or HSR device
respectively. PRP and HSR provides "bumpless" redundancy. RSTP is also an open standard, so its implementation
is compatible with any standard RSTP devices. RSTP provides redundancy, however, it is not "bumpless", the
standard instead utilises a loop free topology that is recalculated when a device fails, and does not forward
messages during recalculation.

16.7.1 PARALLEL REDUNDANCY PROTOCOL (PRP)


Power system companies have traditionally used proprietary protocols for redundant communications. This is
because standardized protocols could not meet the requirements for real-time systems. Even a short loss of
connectivity may result in loss of functionality.
However, Parallel Redundancy Protocol (PRP) uses the IEC 62439 standard in Dual Star Topology networks,
designed for IEDs from different manufacturers to operate with each other in a substation redundant-Ethernet
network. PRP provides bumpless redundancy for real-time systems and is the standard for double Star-topology
networks in substations.

16.7.1.1 PRP NETWORKS


Redundant networks usually rely on the network’s ability to reconfigure if there is a failure. However, PRP uses two
independent networks in parallel.
PRP implements the redundancy functions in the end nodes rather than in network elements. This is one major
difference to RSTP. An end node is attached to two similar LANs of any topology which operate in parallel.
The sending node replicates each frame and transmits them over both networks. The receiving node processes the
frame that arrives first and discards the duplicate. Therefore there is no distinction between the working and backup
path. The receiving node checks that all frames arrive in sequence and that frames are correctly received on both
ports.
The PRP layer manages this replicate and discard function, and hides the two networks from the upper layers. This
scheme works without reconfiguration and switchover, so it stays available ensuring no data loss.
There should be no common point of failure between the two LANs. Therefore they are not powered by the same
source and cannot be connected directly together. They are identical in protocol at the MAC level but may differ in
performance and topology. Both LANs must be on the same subnet so all IP addresses must be unique.

16.7.1.2 NETWORK ELEMENTS


A PRP compatible device has two ports that operate in parallel. Each port is connected to a separate LAN. In the
IEC 62439 standard, these devices are called DANP (Doubly Attached Node running PRP). A DAN has two ports,
one MAC address and one IP address.
A Single Attached Node (SAN) is a non-critical node attached to only one LAN. SANs that need to communicate
with each other must be on the same LAN.
The following diagram shows an example of a PRP network. The Doubly Attached Nodes DANP 1 and DANP 2
have full node redundancy. The Singly Attached Nodes SAN 1 and SAN 4 do not have any redundancy. Singly
attached nodes can be connected to both LANs using a Redundancy Box (RedBox). The RedBox converts a singly
attached node into a doubly attached node. Devices such as PCs with one network board, printers, and IEDs with

346 P64-TM-EN-1
P64 Chapter 16 - Communications

one network board are singly attached nodes. A SAN behind a RedBox appears like a DAN so is called a Virtual
DAN (VDAN).

DAN DAN

SAN DAN

LAN B

LAN A

REDUNDANCY
BOX

VDAN

VDAN SAN SAN

VDAN

E01028

Figure 163: Example PRP redundant network

In a DAN, both ports share the same MAC address so it does not affect the way devices talk to each other in an
Ethernet network (Address Resolution Protocol at layer 2). Every data frame is seen by both ports.
When a DAN sends a frame of data, the frame is duplicated on both ports and therefore on both LAN segments.
This provides a redundant path for the data frame if one of the segments fails. Under normal conditions, both LAN
segments are working and each port receives identical frames. There are two ways of handling this: Duplicate
Accept and Duplicate Discard.
The GE Vernova RedBox is the H49 switch. This is compatible with any other vendor's PRP device.

16.7.2 HIGH-AVAILABILITY SEAMLESS REDUNDANCY (HSR)


HSR is standardized in IEC 62439-3 (clause 5) for use in ring topology networks. Similar to PRP, HSR provides
bumpless redundancy and meets the most demanding needs of substation automation. HSR has become the
reference standard for ring-topology networks in the substation environment. The HSR implementation of the
redundancy Ethernet board (REB) is compatible with any standard HSR device.
HSR works on the premise that each device connected in the ring is a doubly attached node running HSR (referred
to as DANH). Similar to PRP, singly attached nodes such as printers are connected via Ethernet Redundancy
Boxes (RedBox).

16.7.2.1 HSR MULTICAST TOPOLOGY


When a DANH is sending a multicast frame, the frame (C frame) is duplicated (A frame and B frame), and each
duplicate frame A/B is tagged with the destination MAC address and the sequence number. The frames A and B
differ only in their sequence number, which is used to identify one frame from the other. Each frame is sent to the
network via a separate port. The destination DANH receives two identical frames, removes the HSR tag of the first
frame received and passes this (frame D) on for processing. The other duplicate frame is discarded. The nodes
forward frames from one port to the other unless it was the node that injected it into the ring.

P64-TM-EN-1 347
Chapter 16 - Communications P64

Source

DANH DANH Redbox Switch

D frame C frame D frame


A frame B frame

Singly Attached
Nodes

D frame D frame D frame

DANH DANH DANH


V01030

Figure 164: HSR multicast topology

Only about half of the network bandwidth is available in HSR for multicast or broadcast frames because both
duplicate frames A & B circulate the full ring.

16.7.2.2 HSR UNICAST TOPOLOGY


With unicast frames, there is just one destination and the frames are sent to that destination alone. All non-recipient
devices simply pass the frames on. They do not process them in any way. In other words, D frames are produced
only for the receiving DANH. This is illustrated below.

Source

DANH DANH Redbox Switch

C frame
A frame B frame

Singly Attached
Nodes

D frame

DANH DANH DANH

Destination V01031

Figure 165: HSR unicast topology

For unicast frames, the whole bandwidth is available as both frames A & B stop at the destination node.

348 P64-TM-EN-1
P64 Chapter 16 - Communications

16.7.2.3 HSR APPLICATION IN THE SUBSTATION

S20 Switch
LINK
RX
PC SCADA
TX

reset LINK
RX
TX

DS Agile gateways

H49 H49 H49

Bay 1 Bay 2 Bay 3


E01066b

Figure 166: HSR application in the substation

16.7.3 RAPID SPANNING TREE PROTOCOL (RSTP)


RSTP is a standard used to quickly reconnect a network fault by finding an alternative path, allowing loop-free
network topology. Although RSTP can recover network faults quickly, the fault recovery time depends on the
number of devices and the topology. The recovery time also depends on the time taken by the devices to determine
the root bridge and compute the port roles (discarding, learning, forwarding). The devices do this by exchanging
Bridge Protocol Data Units (BPDUs) containing information about bridge IDs and root path costs. See the
IEEE 802.1D 2004 standard for further information.

P64-TM-EN-1 349
Chapter 16 - Communications P64

Switch 1 Switch 2 Switch 1 Switch 2

IED 1 IED 2 IED 1 IED 2

Star connection with redundant ports Ring connection managed by RSTP


managed by RSTP blocking function. blocking function on upper switches and
IEDs interconnected directly.
V01010

Figure 167: IED attached to redundant Ethernet star or ring circuit

The RSTP solution is based on open standards. It is therefore compatible with other Manufacturers’ IEDs that use
the RSTP protocol. The RSTP recovery time is typically 300 ms but it increases with network size, therefore cannot
achieve the desired bumpless redundancy.
To ensure optimal performance of the protocol, make sure that one of the Ethernet switches is always the root of the
RSTP topology.

16.7.4 FAILOVER
Failover is a simple redundancy mechanism that is not tied to any protocol. It works by selecting a main port and a
switching time that can be as low as 2 seconds. When the main port link fails, the redundant port becomes
physically active. At no point are both ports physically active, which means it can be used on any redundant or non-
redundant network.

350 P64-TM-EN-1
P64 Chapter 16 - Communications

16.8 SIMPLE NETWORK MANAGEMENT PROTOCOL (SNMP)


Simple Network Management Protocol (SNMP) is a network protocol designed to manage devices in an IP network.
SNMP uses a Management Information Base (MIB) that contains information about parameters to supervise. The
MIB format is a tree structure, with each node in the tree identified by a numerical Object Identifier (OID). Each OID
identifies a variable that can be read or set using SNMP with the appropriate software. The information in the MIB is
standardised.
Each system in a network (workstation, server, router, bridge, etc.) maintains a MIB that reflects the status of the
managed resources on that system, such as the version of the software running on the device, the IP address
assigned to a port or interface, the amount of free hard drive space, or the number of open files. The MIB does not
contain static data, but is instead an object-oriented, dynamic database that provides a logical collection of
managed object definitions. The MIB defines the data type of each managed object and describes the object.
The SNMP-related branches of the MIB tree are located in the internet branch, which contains two main types of
branches:
● Public branches (mgmt=2), which are defined by the Internet Engineering Task Force (IETF).
● Private branches (private=4), which are assigned by the Internet Assigned Numbers Authority (IANA). These
are defined by the companies and organizations to which these branches are assigned.

The following figure shows the structure of the SNMP MIB tree. There are no limits on the width and depth of the
MIB tree.

iso = 1

org = 3

dod = 6

internet = 1

mgmt = 2 private = 4

mib-2 = 1 enterprises = 1

system = 1 printers = 43 microsoft = 311

sysDescr = 1

E01033

Figure 168: SNMP MIB tree

P64-TM-EN-1 351
Chapter 16 - Communications P64

The top four levels of the hierarchy are fixed. These are:
● International Standards Organization (iso)
● Organization (org)
● Department of Defence (dod)
● Internet

Management (mgmt) is the main public branch. It defines network management parameters common to devices
from all vendors. Underneath the Management branch is MIB-II (mib-2), and beneath this are branches for common
management functions such as system management, printers, host resources, and interfaces.
The private branch of the MIB tree contains branches for large organizations, organized under the enterprises
branch. This is not applicable to GE Vernova.

16.8.1 SNMP MIBS COMPATIBLE WITH THE IED


Our IED supports four different MIBs, all available for download on the GE website:
● IEC-62439-3-MIB: Standard PRP/HSR MIB.
● RMON-MIB: Standard Remote Monitoring MIB.
● GE-PX4X-MIB.mib: Private MIB that contains all the information specific to the relay. For example, model and
serial number.
● GE-GRID-MIB.mib: Private MIB that only contains manufacturer information.

The information within the MIBs can be read using a simple text app like Notepad, or the MIB can be explored using
an MIB Browser.
The private branch of the MIB tree contains branches for large organizations, organized under the enterprises
branch. This is not applicable to GE Vernova.

16.8.2 NEW SNMP SYSTEM OBJECTS


The following elements have been added to the SNMP structure to more accurately describe the new functionalities
added in the Ethernet boards:

16.8.2.1 NEW SNMP TRAPS


Changes in the Physical link statuses (Up or Down status) of NP1, NP2A, NP2B ethernet ports will be reported as
SNMP traps.
The objects for these link statuses are added in MIB (GE-PX4X-MIB.mib). Below are the IDs for Network Port link
objects:
● np1Link: 1.3.6.1.4.1.55461.1.6.1
● np2ALink: 1.3.6.1.4.1.55461.1.6.2
● np2Blink: 1.3.6.1.4.1.55461.1.6.3

16.8.2.2 NEW SNMP OBJECTS


The following objects have been added to MIB (GE-PX4X-MIB.mib) to add more visibility to the behaviour of the
Ethernet board.
● np2Redundancy: .1.3.6.1.4.1.55461.1.6.4, represents active redundancy protocol set in the device.
● rstpRootIdentifier: .1.3.6.1.4.1.55461.1.6.5, represents RSTP Rot Bridge Identifier. It is a combination of
Root bridge's priority and its MAC address.
● rstpTimeSinceTopoChange: .1.3.6.1.4.1.55461.1.6.6, represents the time elapsed since last RSTP topology
change.
● rstpTopoChangeCount: .1.3.6.1.4.1.55461.1.6.7, represents RSTP topology change count.

352 P64-TM-EN-1
P64 Chapter 16 - Communications

16.8.3 SNMP ALARM ENHANCEMENT


An SNMP alarm is triggered by the relay when a security event occurs, if SNMP trap destination IP is configured in
the settings.

16.8.3.1 SNMP ALARM FORMAT


The format of the SNMP trap/alarm for security events consists of three parts as described below.
"Event Description, Username, Interface".
Event Description: Short description of the alarm, same as the description present in Security event.
Username: User associated with the event, provided only when Username is available for the Security event.
Interface: Interface on which Security event has occurred, same as the interface information present in Security
event.

16.8.3.2 LIST OF SNMP ALARMS


No. Security Events SNMP Trap Text
1 SECUR_EVT_PW_SET_NON_COMPLIANT User Password change failed - policy check failed
2 SECUR_EVT_PW_MODIFIED User password changed successfully
3 SECUR_EVT_PW_ENTRY_NOW_BLOCKED User locked - wrong credentials
4 SECUR_EVT_PW_ENTRY_UNBLOCKED User unlocked
5 SECUR_EVT_PW_ENTERED_WHILE_BLOCKED Log-in attempt when user is locked
6 SECUR_EVT_INVALID_PW_ENTERED Log-in failed - wrong credentials
7 SECUR_EVT_PW_TIMED_OUT Log-in failed - credentials expired
8 SECUR_EVT_RECOVERY_PW_ENTERED Recovery password entered
9 SECUR_EVT_IED_SEC_CODE_READ Security Code read
10 SECUR_EVT_IED_SEC_CODE_TMR_EXPIRED Security Code Timer expired
11 SECUR_EVT_PORT_DISABLED Port Disabled
12 SECUR_EVT_PORT_ENABLED Port Enabled
13 SECUR_EVT_PSL_SETTINGS_DOWNLOADED PSL Settings downloaded to device
14 SECUR_EVT_DNP_SETTINGS_DOWNLOADED DNP Settings downloaded to device
15 SECUR_EVT_61850_CONFIG_DOWNLOADED IEC61850 Config downloaded to device
16 SECUR_EVT_USER_CURVES_DOWNLOADED User Curves downloaded to device
17 SECUR_EVT_SETTING_GRP_DOWNLOADED Setting Group downloaded to device
18 SECUR_EVT_DR_SETTINGS_DOWNLOADED DR Settings downloaded to device
19 SECUR_EVT_PSL_SETTINGS_UPLOADED PSL Settings uploaded from device
20 SECUR_EVT_DNP_SETTINGS_UPLOADED DNP Settings uploaded from device
21 SECUR_EVT_61850_CONFIG_UPLOADED IEC61850 Config uploaded from device
22 SECUR_EVT_USER_CURVES_UPLOADED User Curves uploaded from device
23 SECUR_EVT_PSL_CONFIG_UPLOADED PSL Config uploaded from device
24 SECUR_EVT_SETTINGS_UPLOADED Settings uploaded from device
25 SECUR_EVT_CS_SETTINGS_CHANGED Control & Support settings changed

P64-TM-EN-1 353
Chapter 16 - Communications P64

No. Security Events SNMP Trap Text


26 SECUR_EVT_DR_SETTINGS_CHANGED Disturbance Record Settings changed
27 SECUR_EVT_SETTING_GROUP_CHANGED Setting Group changed
28 SECUR_EVT_DEFAULT_SETTINGS_RESTORED Default Settings restored
29 SECUR_EVT_DEFAULT_USRCURVE_RESTORED Default User Curve restored
30 SECUR_EVT_POWER_ON Device Powered On
31 SECUR_EVT_RADIUS_UNAVAIL RADIUS server not available
32 SECUR_EVT_SESSION_LIMIT Active user sessions limit reached
33 SECUR_EVT_SLD_FILE_DOWNLOADED SLD File downloaded to device
34 SECUR_EVT_SLD_FILE_UPLOADED SLD File uploaded from device
35 SECUR_EVT_RBAC_LOGIN Log-in successful
36 SECUR_EVT_RBAC_LOGOUT Log-out (user logged out)
37 Bypass mode Activated Bypass Mode Activated
38 Bypass mode Deactivated Bypass Mode Deactivated
39 RADIUS Secret Key changed RADIUS Secret Key changed
40 SECUR_EVT_SEC_SETTINGS_RESTORED Security settings restored
41 Switch to Golden Image Device switching to Firmware update mode
42 Fallback to Device Authentication Fallback to Device Authentication
43 User logged out due to inactivity timeout. Log-out by user inactivity (timeout)
44 Security events upload Security Events uploaded from device
45 SSH Passcode change SSH pass code change
46 SSH Client Authentication Fail Failed client authentication
47 SSH Client Authentication Success Successful client authentication
48 New User added User account created successfully
49 User deleted User account deleted successfully
50 User role change Permission changed successfully
51 User name change User renamed successfully

354 P64-TM-EN-1
P64 Chapter 16 - Communications

16.9 DATA PROTOCOLS


The products support a wide range of protocols to make them applicable to many industries and applications. The
exact data protocols supported by a particular product depend on its chosen application, but the following table
gives a list of the data protocols that are typically available.

DATA PROTOCOLS

Data Protocol Layer 1 Interface Description


Standard for SCADA communications developed by GE
Courier USB, K-Bus, RS232, RS485, Ethernet
Vernova.

IEC 60870-5-103 RS485 IEC standard for SCADA communications

DNP 3.0 RS485 Standard for SCADA communications

IEC standard for substation automation. Facilitates


IEC 61850 Ethernet
interoperability.

The relationship of these protocols to the lower-level physical layer protocols are as follows:

IEC 60870-5-103
Data Protocols DNP3.0 IEC 61850
Courier Courier Courier Courier Courier
Data Link Layer EIA(RS)485 Ethernet EIA(RS)232 K-Bus USB
Physical Layer Copper or Optical Fibre USB Type B

The product supports switchable serial communication data protocol on the Rear Port 1 (RP1) interface (it is no
longer necessary to select the protocol as a product order option). This setting cell is RP1 Protocol in the
COMMUNICATIONS column. For example, the product can now be configured to provide IEC 61850 on the
Ethernet interface and DNP3.0 on the serial port concurrently.

16.9.1 COURIER
This section should provide sufficient detail to enable understanding of the Courier protocol at a level required by
most users. For situations where the level of information contained in this manual is insufficient, further publications
(R6511 and R6512) containing in-depth details about the protocol and its use, are available on request.
Courier is a GE Vernova proprietary communication protocol. Courier uses a standard set of commands to access a
database of settings and data in the IED. This allows a master to communicate with a number of slave devices. The
application-specific elements are contained in the database rather than in the commands used to interrogate it,
meaning that the master station does not need to be preconfigured. Courier also provides a sequence of event
(SOE) and disturbance record extraction mechanism.

16.9.1.1 PHYSICAL CONNECTION AND LINK LAYER


Courier can be used with four physical layer protocols: USB, K-Bus, EIA(RS)232 or EIA(RS)485.
Several connection options are available for Courier
● The front USB port (for connection to Settings application software on, for example, a laptop)
● Rear Port 1 (RP1) - for permanent SCADA connection via serial RS485 or K-Bus
● Optional fibre port (RP1 in slot A) - for permanent SCADA connection via serial optical fibre
● Optional Rear Port 2 (RP2) - for permanent SCADA connection via serial RS485, K-Bus, or RS232

P64-TM-EN-1 355
Chapter 16 - Communications P64

Optional Ethernet board (NIC) - for remote communication with the S1 Agile settings application software across an
Ethernet network.
For either of the serial rear ports, both the IED address and baud rate can be selected using the front panel menu or
by the settings application software.

Note:
Changing the RP2 Port Config setting (K-Bus, EIA(RS)232) requires the IED to be rebooted, for the change to become
effective.

16.9.1.2 COURIER DATABASE


The Courier database is two-dimensional and resembles a table. Each cell in the database is referenced by a row
and column address. Both the column and the row can take a range from 0 to 255 (0000 to FFFF Hexadecimal.
Addresses in the database are specified as hexadecimal values, for example, 0A02 is column 0A row 02.
Associated settings or data are part of the same column. Row zero of the column has a text string to identify the
contents of the column and to act as a column heading.
The product-specific menu databases contain the complete database definition.

16.9.1.3 SETTINGS CATEGORIES


There are two main categories of settings in protection IEDs:
● Control and support settings
● Protection settings

With the exception of the Disturbance Recorder settings, changes made to the control and support settings are
implemented immediately and stored in non-volatile memory. Changes made to the Protection settings and the
Disturbance Recorder settings are stored in ‘scratchpad’ memory and are not immediately implemented. These
need to be committed by writing to the Save Changes cell in the CONFIGURATION column.

16.9.1.4 SETTING CHANGES


Courier provides two mechanisms for making setting changes. Either method can be used for editing any of the
settings in the database.

Method 1
This uses a combination of three commands to perform a settings change:
First, enter Setting mode: This checks that the cell is settable and returns the limits.
1. Preload Setting: This places a new value into the cell. This value is echoed to ensure that setting corruption
has not taken place. The validity of the setting is not checked by this action.
2. Execute Setting: This confirms the setting change. If the change is valid, a positive response is returned. If
the setting change fails, an error response is returned.
3. Abort Setting: This command can be used to abandon the setting change.
This is the most secure method. It is ideally suited to on-line editors because the setting limits are extracted before
the setting change is made. However, this method can be slow if many settings are being changed because three
commands are required for each change.

Method 2
The Set Value command can be used to change a setting directly. The response to this command is either a
positive confirm or an error code to indicate the nature of a failure. This command can be used to implement a
setting more rapidly than the previous method; however the limits are not extracted. This method is therefore most
suitable for off-line setting editors such as MiCOM S1 Agile, or for issuing preconfigured control commands.

356 P64-TM-EN-1
P64 Chapter 16 - Communications

16.9.1.5 EVENT EXTRACTION


You can extract events either automatically (rear serial port only) or manually (either serial port). For automatic
extraction, all events are extracted in sequential order using the Courier event mechanism. This includes fault and
maintenance data if appropriate. The manual approach allows you to select events, faults, or maintenance data as
desired.

16.9.1.5.1 AUTOMATIC EVENT RECORD EXTRACTION


This method is intended for continuous extraction of event and fault information as it is produced. It is only
supported through the rear Courier port.
When new event information is created, the Event bit is set in the Status byte. This indicates to the Master device
that event information is available. The oldest, non-extracted event can be extracted from the IED using the Send
Event command. The IED responds with the event data.
Once an event has been extracted, the Accept Event command can be used to confirm that the event has been
successfully extracted. When all events have been extracted, the Event bit is reset. If there are more events still to
be extracted, the next event can be accessed using the Send Event command as before.

16.9.1.5.2 MANUAL EVENT RECORD EXTRACTION


The VIEW RECORDS column (location 01) is used for manual viewing of event, fault, and maintenance records.
The contents of this column depend on the nature of the record selected. You can select events by event number
and directly select a fault or maintenance record by number.

Event Record Selection ('Select Event' cell: 0101)


This cell can be set the number of stored events. For simple event records (Type 0), cells 0102 to 0105 contain the
event details. A single cell is used to represent each of the event fields. If the event selected is a fault or
maintenance record (Type 3), the remainder of the column contains the additional information.

Fault Record Selection ('Select Fault' cell: 0106)


This cell can be used to select a fault record directly, using a value between 0 and 99 to select one of up to a
hundred stored fault records. (0 is the most recent fault and 99 is the oldest). The column then contains the details
of the fault record selected.

Maintenance Record Selection ('Select Maint' cell: 01F0)


This cell can be used to select a maintenance record using a value between 0 and 9. This cell operates in a similar
way to the fault record selection.
If this column is used to extract event information, the number associated with a particular record changes when a
new event or fault occurs.

Event Types
The IED generates events under certain circumstances such as:
● Change of state of output contact
● Change of state of opto-input
● Protection element operation
● Alarm condition
● Setting change
● Password entered/timed-out

P64-TM-EN-1 357
Chapter 16 - Communications P64

Event Record Format


The IED returns the following fields when the Send Event command is invoked:
● Cell reference
● Time stamp
● Cell text
● Cell value

The Menu Database contains tables of possible events, and shows how the contents of the above fields are
interpreted. Fault and Maintenance records return a Courier Type 3 event, which contains the above fields plus two
additional fields:
● Event extraction column
● Event number

These events contain additional information, which is extracted from the IED using column B4. Row 01 contains a
Select Record setting that allows the fault or maintenance record to be selected. This setting should be set to the
event number value returned in the record. The extended data can be extracted from the IED by uploading the text
and data from the column.

16.9.1.6 DISTURBANCE RECORD EXTRACTION


The stored disturbance records are accessible through the Courier interface. The records are extracted using
column (B4).
The Select Record cell can be used to select the record to be extracted. Record 0 is the oldest non-extracted
record. Older records which have already been extracted are assigned positive values, while younger records are
assigned negative values. To help automatic extraction through the rear port, the IED sets the Disturbance bit of
the Status byte, whenever there are non-extracted disturbance records.
Once a record has been selected, using the above cell, the time and date of the record can be read from the
Trigger Time cell (B402). The disturbance record can be extracted using the block transfer mechanism from cell
B40B and saved in the COMTRADE format. The settings application software software automatically does this.

16.9.1.7 PROGRAMMABLE SCHEME LOGIC SETTINGS


The programmable scheme logic (PSL) settings can be uploaded from and downloaded to the IED using the block
transfer mechanism.
The following cells are used to perform the extraction:
● Domain cell (B204): Used to select either PSL settings (upload or download) or PSL configuration data
(upload only)
● Sub-Domain cell (B208): Used to select the Protection Setting Group to be uploaded or downloaded.
● Version cell (B20C): Used on a download to check the compatibility of the file to be downloaded.
● Transfer Mode cell (B21C): Used to set up the transfer process.
● Data Transfer cell (B120): Used to perform upload or download.

The PSL settings can be uploaded and downloaded to and from the IED using this mechanism. The settings
application software must be used to edit the settings. It also performs checks on the validity of the settings before
they are transferred to the IED.

16.9.1.8 TIME SYNCHRONISATION


The time and date can be set using the time synchronization feature of the Courier protocol. The device will correct
for the transmission delay. The time synchronization message may be sent as either a global command or to any
individual IED address. If the time synchronization message is sent to an individual address, then the device will
respond with a confirm message. If sent as a global command, the (same) command must be sent twice. A time

358 P64-TM-EN-1
P64 Chapter 16 - Communications

synchronization Courier event will be generated/produced whether the time-synchronization message is sent as a
global command or to any individual IED address.
If the clock is being synchronized using the IRIG-B input then it will not be possible to set the device time using the
Courier interface. An attempt to set the time using the interface will cause the device to create an event with the
current date and time taken from the IRIG-B synchronized internal clock.

16.9.1.9 COURIER CONFIGURATION


To configure the device:
1. Select the CONFIGURATION column and check that the Comms settings cell is set to Visible.
2. Select the COMMUNICATIONS column.
3. Move to the first cell down (RP1 Protocol). Set this to the chosen communication protocol – in this case
Courier.
4. Move down to the next cell (RP1 Address). This cell controls the address of the RP1 port on the device. Up
to 32 IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique address so
that messages from the master control station are accepted by one IED only. Courier uses an integer number
between 1 and 254 for the Relay Address. It is set to 255 by default, which has to be changed. It is important
that no two IEDs share the same address.
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The inactivity timer
controls how long the IED waits without receiving any messages on the rear port before revoking any
password access that was enabled and discarding any changes. For the rear port this can be set between 1
and 30 minutes.
6. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
7. Move down to the next cell (RP1 Card Status). This cell is not settable. It displays the status of the chosen
physical layer protocol for RP1.
8. Move down to the next cell (RP1 Port Config). This cell controls the type of serial connection. Select
between K-Bus or RS485.
9. If using EIA(RS)485, the next cell (RP1 Comms Mode) selects the communication mode. The choice is
either IEC 60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no parity. If using K-Bus this cell
will not appear.
10. If using EIA(RS)485, the next cell down controls the baud rate. Three baud rates are supported; 9600, 19200
and 38400. If using K-Bus this cell will not appear as the baud rate is fixed at 64 kbps.

16.9.2 IEC 60870-5-103


The specification IEC 60870-5-103 (Telecontrol Equipment and Systems Part 5 Section 103: Transmission
Protocols), defines the use of standards IEC 60870-5-1 to IEC 60870-5-5, which were designed for communication
with protection equipment.
This section describes how the IEC 60870-5-103 standard is applied to the Px40 platform. It is not a description of
the standard itself. The level at which this section is written assumes that the reader is already familiar with the
IEC 60870-5-103 standard.
This section should provide sufficient detail to enable understanding of the standard at a level required by most
users.
The IEC 60870-5-103 interface is a master/slave interface with the device as the slave device. The device conforms
to compatibility level 2, as defined in the IEC 60870-5-103.standard.
The following IEC 60870-5-103 facilities are supported by this interface:
● Initialization (reset)
● Time synchronization
● Event record extraction

P64-TM-EN-1 359
Chapter 16 - Communications P64

● General interrogation
● Cyclic measurements
● General commands
● Disturbance record extraction
● Private codes

16.9.2.1 PHYSICAL CONNECTION AND LINK LAYER


Two connection options are available for IEC 60870-5-103:
● Rear Port 1 (RP1) - for permanent SCADA connection via RS485
● Optional fibre port (RP1 in slot A) - for permanent SCADA connection via optical fibre

If the optional fibre optic port is fitted, a menu item appears in which the active port can be selected. However, the
selection is only effective following the next power up.
The IED address and baud rate can be selected using the front panel menu or by the settings application software.

16.9.2.2 INITIALISATION
Whenever the device has been powered up, or if the communication parameters have been changed a reset
command is required to initialize the communications. The device will respond to either of the two reset commands;
Reset CU or Reset FCB (Communication Unit or Frame Count Bit). The difference between the two commands is
that the Reset CU command will clear any unsent messages in the transmit buffer, whereas the Reset FCB
command does not delete any messages.
The device will respond to the reset command with an identification message ASDU 5. The Cause of Transmission
(COT) of this response will be either Reset CU or Reset FCB depending on the nature of the reset command. The
content of ASDU 5 is described in the IEC 60870-5-103 section of the Menu Database, available from GE Vernova
separately if required.
In addition to the above identification message, it will also produce a power up event.

16.9.2.3 TIME SYNCHRONISATION


The time and date can be set using the time synchronization feature of the IEC 60870-5-103 protocol. The device
will correct for the transmission delay as specified in IEC 60870-5-103. If the time synchronization message is sent
as a send/confirm message then the device will respond with a confirm message. A time synchronization Class 1
event will be generated/produced whether the time-synchronization message is sent as a send confirm or a
broadcast (send/no reply) message.
If the clock is being synchronized using the IRIG-B input then it will not be possible to set the device time using the
IEC 60870-5-103 interface. An attempt to set the time via the interface will cause the device to create an event with
the current date and time taken from the IRIG-B synchronized internal clock.

16.9.2.4 CONFIGURABLE IEC 60870-5-103 SIGNAL LIST


From Software Version 91 onwards, there is a setting cell which allows the IEC 60870-5-103 private range signals
to be selected and de-selected from IEC 60870-5-103 communication.
The IEC 60870-5-103 standard (compatible range) signals, that are provided according to the relay type and
implementation, are always enabled. These signals cannot be disabled.
This setting cell is Config Mode in the PROTOCOL CFG column.
There are two settings associated with this cell. These are:

360 P64-TM-EN-1
P64 Chapter 16 - Communications

Setting Description
In this mode, the IED behaviour for IEC 60870-5-103 protocol is identical to pre-Software Version 91
IEDs.
All the implemented signals (IEC 60870-5-103 compatible range and private range signals) are enabled
Fixed
for IEC 60870-5-103 communication. The COT behaviour will be according to the device IEC
60870-5-103 profile.
This mode is provided for backward compatibility. This is the default setting.
In this mode, the user can select which IEC 60870-5-103 private range signals are enabled for IEC
60870-5-103 communication.
The selection is done using DDB mask setting cells in the PROTOCOL CFG column. The DDB mask
Std+UserConfig value controls only the signal selection (enabled or disabled) for IEC 60870-5-103 communication. It does
not modify the COT behaviour of the signals. The COT behaviour of the private range signals will be
according to the device IEC 60870-5-103 profile.
By default, only IEC 60870-5-103 standard signals are enabled. All private range signals are disabled.

When the Config Mode cell is set to Std+UserConfig, the DDB masks become visible in the PROTOCOL CFG
column. These masks function in a similar way to the DDB masks in the RECORD CONTROL column. Editing
these masks controls the DDB signals that are enabled for communication of the equivalent IEC 60870-5-103
private range signal, as listed in the IEC 60870-5-103 profile in the Menu Database.
Within these masks, only individual DDBs that are equivalent to IEC 60870-5-103 private range signals are editable.
By default, all of the individual DDBs that are equivalent to IEC 60870-5-103 private range signals are set to 0
(zero), that is disabled for communication. Setting any individual DDB to 1 (one), enables the equivalent IEC
60870-5-103 private range signal for communication.
Within these masks, individual DDBs that are either equivalent to IEC 60870-5-103 standard range signals, or do
not have any equivalent IEC 60870-5-103 private range signal, are not editable.

16.9.2.5 SPONTANEOUS EVENTS


Events are categorized using the following information:
● Function type
● Information Number

The IEC 60870-5-103 profile in the Menu Database contains a complete listing of all events produced by the device.
From Software Version 91 onwards, the IEC 60870-5-103 private range signals can be individually selected for
spontaneous communication, by settting the Config Mode cell to Std+UserConfig, and configuring the DDB
masks as required.

16.9.2.6 GENERAL INTERROGATION (GI)


The GI request can be used to read the status of the device, the function numbers, and information numbers that
will be returned during the GI cycle. These are shown in the IEC 60870-5-103 profile in the Menu Database.
From Software Version 91 onwards, the IEC 60870-5-103 private range signals can be individually selected for GI
reporting, by setting the Config Mode cell to Std+UserConfig, and configuring the DDB masks as required.

16.9.2.7 CYCLIC MEASUREMENTS


The device will produce measured values using ASDU 9 on a cyclical basis, this can be read from the device using
a Class 2 poll (note ADSU 3 is not used). The rate at which the device produces new measured values can be
controlled using the measurement period setting. This setting can be edited from the front panel menu or using
MiCOM S1 Agile. It is active immediately following a change.
The device transmits its measurands with maximum value of 2.4 times the rated value of the measurement.

P64-TM-EN-1 361
Chapter 16 - Communications P64

16.9.2.8 COMMANDS
A list of the supported commands is contained in the Menu Database. The device will respond to other commands
with an ASDU 1, with a cause of transmission (COT) indicating ‘negative acknowledgement’.

16.9.2.9 TEST MODE


It is possible to disable the device output contacts to allow secondary injection testing to be performed using either
the front panel menu or the front serial port. The IEC 60870-5-103 standard interprets this as ‘test mode’. An event
will be produced to indicate both entry to and exit from test mode. Spontaneous events and cyclic measured data
transmitted whilst the device is in test mode will have a COT of ‘test mode’.

16.9.2.10 DISTURBANCE RECORDS


The disturbance records are stored in uncompressed format and can be extracted using the standard mechanisms
described in IEC 60870-5-103.

Note:
IEC 60870-5-103 only supports up to 8 records.

16.9.2.11 COMMAND/MONITOR BLOCKING


The device supports a facility to block messages in the monitor direction (data from the device) and also in the
command direction (data to the device). Messages can be blocked in the monitor and command directions using
one of the two following methods
● The menu command RP1 CS103Blcking in the COMMUNICATIONS column
● The DDB signals Monitor Blocked and Command Blocked

16.9.2.12 IEC 60870-5-103 CONFIGURATION


To configure the device:
1. Select the CONFIGURATION column and check that the Comms settings cell is set to Visible.
2. Select the COMMUNICATIONS column.
3. Move to the first cell down (RP1 Protocol). Set this to the chosen communication protocol – in this case
IEC 60870-5-103.
4. Move down to the next cell (RP1 Address). This cell controls the IEC 60870-5-103 address of the IED. Up to
32 IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique address so
that messages from the master control station are accepted by one IED only. IEC 60870-5-103 uses an
integer number between 0 and 254 for the address. It is important that no two IEDs have the same
IEC 60870 5 103 address. The IEC 60870-5-103 address is then used by the master station to communicate
with the IED.
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Two baud rates are
supported by the IED, 9600 bits/s and 19200 bits/s. Make sure that the baud rate selected on the IED
is the same as that set on the master station.
6. Move down to the next cell (RP1 Meas Period). The next cell down controls the period between
IEC 60870-5-103 measurements. The IEC 60870-5-103 protocol allows the IED to supply measurements at
regular intervals. The interval between measurements is controlled by this cell, and can be set between 1 and
60 seconds.
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
8. The next cell down (RP1 CS103Blcking) can be used for monitor or command blocking.
9. There are three settings associated with this cell; these are:

362 P64-TM-EN-1
P64 Chapter 16 - Communications

Setting Description
Disabled No blocking selected.
When the monitor blocking DDB Signal is active high, either by energising an opto input or control
Monitor Blocking input, reading of the status information and disturbance records is not permitted. When in this mode
the device returns a "Termination of general interrogation" message to the master station.
When the command blocking DDB signal is active high, either by energising an opto input or control
input, all remote commands will be ignored (i.e. CB Trip/Close, change setting group etc.). When in
Command Blocking
this mode the device returns a "negative acknowledgement of command" message to the master
station.

16.9.3 DNP 3.0


This section describes how the DNP 3.0 standard is applied in the product. It is not a description of the standard
itself. The level at which this section is written assumes that the reader is already familiar with the DNP 3.0
standard.
The descriptions given here are intended to accompany the device profile document that is included in the Menu
Database document. The DNP 3.0 protocol is not described here, please refer to the documentation available from
the user group. The device profile document specifies the full details of the DNP 3.0 implementation. This is the
standard format DNP 3.0 document that specifies which objects; variations and qualifiers are supported. The device
profile document also specifies what data is available from the device using DNP 3.0. The IED operates as a
DNP 3.0 slave and supports subset level 2, as described in the DNP 3.0 standard, plus some of the features from
level 3.
The DNP 3.0 protocol is defined and administered by the DNP Users Group. For further information on DNP 3.0
and the protocol specifications, please see the DNP website (www.dnp.org).

16.9.3.1 PHYSICAL CONNECTION AND LINK LAYER


DNP 3.0 can be used with EIA(RS)485.
Several connection options are available for DNP 3.0
● Rear Port 1 (RP1) - for permanent SCADA connection via RS485
● Optional fibre port (RP1 in slot A) - for permanent SCADA connection via optical fibre

The baud rate can be selected using the front panel menu or by the settings application software.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 stop bit and optional configurable parity
bit.

16.9.3.2 OBJECT 1 BINARY INPUTS


Object 1, binary inputs, contains information describing the state of signals in the IED, which mostly form part of the
digital data bus (DDB). In general these include the state of the output contacts and opto-inputs, alarm signals, and
protection start and trip signals. The ‘DDB number’ column in the device profile document provides the DDB
numbers for the DNP 3.0 point data. These can be used to cross-reference to the DDB definition list. See the
relevant Menu Database document. The binary input points can also be read as change events using Object 2 and
Object 60 for class 1-3 event data.

Note:
For the DNP Events to be transmitted it is mandatory to have the corresponding DDBs of the Configured Point Index to be
included in the Courier Event Record. The RECORD CONTROL Menu lists all the DDBs, and the mask settings control their
inclusion/exclusion as a Courier Event.

P64-TM-EN-1 363
Chapter 16 - Communications P64

16.9.3.3 OBJECT 10 BINARY OUTPUTS


Object 10, binary outputs, contains commands that can be operated using DNP 3.0. Therefore the points accept
commands of type pulse on (null, trip, close) and latch on/off as detailed in the device profile in the relevant Menu
Database document, and execute the command once for either command. The other fields are ignored (queue,
clear, trip/close, in time and off time).
There is an additional image of the Control Inputs. Described as Alias Control Inputs, they reflect the state of the
Control Input, but with a dynamic nature.
● If the Control Input DDB signal is already SET and a new DNP SET command is sent to the Control Input, the
Control Input DDB signal goes momentarily to RESET and then back to SET.
● If the Control Input DDB signal is already RESET and a new DNP RESET command is sent to the Control
Input, the Control Input DDB signal goes momentarily to SET and then back to RESET.

DNP Latch DNP Latch DNP Latch DNP Latch


ON ON OFF OFF

Control Input
(Latched)

Aliased Control
Input
(Latched)

Control Input
(Pulsed)

Aliased Control
Input
(Pulsed)
The pulse width is equal to the duration of one protection iteration
V01002a

Figure 169: Control input behaviour

Many of the IED’s functions are configurable so some of the Object 10 commands described in the following
sections may not be available. A read from Object 10 reports the point as off-line and an operate command to
Object 12 generates an error response.
Examples of Object 10 points that maybe reported as off-line are:
● Activate setting groups: Ensure setting groups are enabled
● CB trip/close: Ensure remote CB control is enabled
● Reset NPS thermal: Ensure NPS thermal protection is enabled
● Reset thermal O/L: Ensure thermal overload protection is enabled
● Reset RTD flags: Ensure RTD Inputs is enabled
● Control inputs: Ensure control inputs are enabled

364 P64-TM-EN-1
P64 Chapter 16 - Communications

16.9.3.4 OBJECT 20 BINARY COUNTERS


Object 20, binary counters, contains cumulative counters and measurements. The binary counters can be read as
their present ‘running’ value from Object 20, or as a ‘frozen’ value from Object 21. The running counters of object 20
accept the read, freeze and clear functions. The freeze function takes the current value of the object 20 running
counter and stores it in the corresponding Object 21 frozen counter. The freeze and clear function resets the Object
20 running counter to zero after freezing its value.
Binary counter and frozen counter change event values are available for reporting from Object 22 and Object 23
respectively. Counter change events (Object 22) only report the most recent change, so the maximum number of
events supported is the same as the total number of counters. Frozen counter change events (Object 23) are
generated whenever a freeze operation is performed and a change has occurred since the previous freeze
command. The frozen counter event queues store the points for up to two freeze operations.

16.9.3.5 OBJECT 30 ANALOGUE INPUT


Object 30, analogue inputs, contains information from the IED’s measurements columns in the menu. All object 30
points can be reported as 16 or 32-bit integer values with flag, 16 or 32-bit integer values without flag, as well as
short floating point values.
Analogue values can be reported to the master station as primary, secondary or normalized values (which takes
into account the IED’s CT and VT ratios), and this is settable in the COMMUNICATIONS column in the IED.
Corresponding deadband settings can be displayed in terms of a primary, secondary or normalized value.
Deadband point values can be reported and written using Object 34 variations.
The deadband is the setting used to determine whether a change event should be generated for each point. The
change events can be read using Object 32 or Object 60. These events are generated for any point which has a
value changed by more than the deadband setting since the last time the data value was reported.
Any analogue measurement that is unavailable when it is read is reported as offline. For example, the frequency
would be offline if the current and voltage frequency is outside the tracking range of the IED. All Object 30 points
are reported as secondary values in DNP 3.0 (with respect to CT and VT ratios).

16.9.3.6 OBJECT 40 ANALOGUE OUTPUT


The conversion to fixed-point format requires the use of a scaling factor, which is configurable for the various types
of data within the IED such as current, voltage, and phase angle. All Object 40 points report the integer scaling
values and Object 41 is available to configure integer scaling quantities.

16.9.3.7 OBJECT 50 TIME SYNCHRONISATION


Function codes 1 (read) and 2 (write) are supported for Object 50 (time and date) variation 1. The DNP Need Time
function (the duration of time waited before requesting another time sync from the master) is supported, and is
configurable in the range 1 - 30 minutes.
If the clock is being synchronized using the IRIG-B input then it will not be possible to set the device time using the
Courier interface. An attempt to set the time using the interface will cause the device to create an event with the
current date and time taken from the IRIG-B synchronized internal clock.

16.9.3.8 DNP3 DEVICE PROFILE


This section describes the specific implementation of DNP version 3.0 within GE Vernova MiCOM P40 Agile IEDs
for both compact and modular ranges.
The devices use the DNP 3.0 Slave Source Code Library version 3 from Triangle MicroWorks Inc.
This document, in conjunction with the DNP 3.0 Basic 4 Document Set, and the DNP Subset Definitions Document,
provides complete information on how to communicate with the devices using the DNP 3.0 protocol.
This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 2. It also contains many
Subset Level 3 and above features.

P64-TM-EN-1 365
Chapter 16 - Communications P64

16.9.3.8.1 DNP3 DEVICE PROFILE TABLE


The following table provides the device profile in a similar format to that defined in the DNP 3.0 Subset Definitions
Document. While it is referred to in the DNP 3.0 Subset Definitions as a “Document”, it is just one component of a
total interoperability guide. This table, in combination with the subsequent Implementation and Points List tables
should provide a complete interoperability/configuration guide for the device.
The following table provides the device profile in a similar format to that defined in the DNP 3.0 Subset Definitions
Document. While it is referred to in the DNP 3.0 Subset Definitions as a "Document", it is just one component of a
total interoperability guide. This table, in combination with the subsequent Implementation and Points List tables
should provide a complete interoperability/configuration guide for the device.
DNP 3.0
Device Profile Document
Vendor Name: GE Vernova
Device Name: MiCOM P40Agile Protection Relays - compact and
modular range
Models Covered: All models
Highest DNP Level Supported*: For Requests: Level 2
* This is the highest DNP level FULLY supported. Parts of level 3 are For Responses: Level 2
also supported
Device Function: Slave
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels supported (the complete list is
described in the DNP 3.0 Implementation Table):
For static (non-change event) object requests, request qualifier codes 00 and 01 (start-stop), 07 and 08 (limited quantity), and
17 and 28 (index) are supported in addition to the request qualifier code 06 (no range (all points))
Static object requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded with qualifiers 00 or 01
Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28
For change-event object requests, qualifiers 17 or 28 are always responded
16-bit and 32-bit analogue change events with time may be requested
The read function code for Object 50 (time and date) variation 1 is supported
Analogue Input Deadbands, Object 34, variations 1 through 3, are supported
Floating Point Analogue Output Status and Output Block Objects 40 and 41 are supported
Sequential file transfer, Object 70, variations 2 through 7, are supported
Device Attribute Object 0 is supported
Maximum Data Link Frame Size (octets): Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets) Transmitted: Configurable (100 to 2048). Default 2048
Received: 249
Maximum Data Link Retries: Fixed at 2
Maximum Application Layer Retries: None
Requires Data Link Layer Confirmation: Configurable to Never or Always
Requires Application Layer Confirmation: When reporting event data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Timeouts while waiting for:
Data Link Confirm: Configurable
Complete Application Fragment: None
Application Confirm: Configurable
Complete Application Response: None
Others:
Data Link Confirm Timeout: Configurable from 0 (Disabled) to 120s, default 10s.
Application Confirm Timeout: Configurable from 1 to 120s, default 2s.

366 P64-TM-EN-1
P64 Chapter 16 - Communications

DNP 3.0
Device Profile Document
Select/Operate Arm Timeout: Configurable from 1 to 10s, default 10s.
Need Time Interval (Set IIN1-4): Configurable from 1 to 30, default 10min.
Application File Timeout 60 s
Analog Change Event Scan Period: Fixed at 0.5s
Counter Change Event Scan Period Fixed at 0.5s
Frozen Counter Change Event Scan Period Fixed at 1s
Maximum Delay Measurement Error: 2.5 ms
Time Base Drift Over a 10-minute Interval: 7 ms
Sends/Executes Control Operations:
Write Binary Outputs: Never
Select/Operate: Always
Direct Operate: Always
Direct Operate - No Ack: Always
Count > 1 Never
Pulse On Always
Pulse Off Sometimes
Latch On Always
Latch Off Always
Queue Never
Clear Queue Never
Note: Paired Control points will accept Pulse On/Trip and Pulse On/Close, but only single point will accept the Pulse Off control
command.
Reports Binary Input Change Events when no Configurable to send one or the other
specific variation requested:
Reports time-tagged Binary Input Change Events Binary input change with time
when no specific variation requested:
Sends Unsolicited Responses: Never
Sends Static Data in Unsolicited Responses: Never
No other options are permitted
Default Counter Object/Variation: Configurable, Point-by-point list attached
Default object: 20
Default variation: 1
Counters Roll Over at: 32 bits
Sends multi-fragment responses: Yes
Sequential File Transfer Support:
Append File Mode No
Custom Status Code Strings No
Permissions Field Yes
File Events Assigned to Class No
File Events Send Immediately Yes
Multiple Blocks in a Fragment No
Max Number of Files Open 1

P64-TM-EN-1 367
Chapter 16 - Communications P64

16.9.3.8.2 DNP3 IMPLEMENTATION TABLE


The implementation table provides a list of objects, variations and control codes supported by the device:
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Qualifier Codes Function Codes
Description Function Codes (dec) (dec) Qualifier Codes (hex)
Number Number (hex)
1 0 Binary Input (Variation 0 is used to 1 (read) 00, 01 (start-stop)
request default variation) 22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
1 1 Binary Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see note 06 (no range, or all) 17, 28 (index - see note 2)
1) 07, 08 (limited qty)
17, 27, 28 (index)
1 2 Binary Input with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 28 (index)
2 0 Binary Input Change - Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
2 1 Binary Input Change without Time 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
07, 08 (limited qty)
2 2 Binary Input Change with Time 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
07, 08 (limited qty)
10 0 Binary Output Status - Any Variation 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
10 2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see note 06 (no range, or all) 17, 28 (index - see note 2)
1) 07, 08 (limited qty)
17, 28 (index)
12 1 Control Relay Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
20 0 Binary Counter - Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
7 (freeze) 00, 01 (start-stop)
8 (freeze noack) 06 (no range, or all)
9 (freeze clear) 07, 08 (limited qty)
10 (frz. cl. Noack)
20 1 32-Bit Binary Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
20 2 16-Bit Binary Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
20 5 32-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see note 06 (no range, or all) 17, 28 (index - see note 2)
1) 07, 08 (limited qty)
17, 27, 28 (index)
20 6 16-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 0 Frozen Counter - Any Variation 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
21 1 32-Bit Frozen Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)

368 P64-TM-EN-1
P64 Chapter 16 - Communications

Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Qualifier Codes Function Codes
Description Function Codes (dec) (dec) Qualifier Codes (hex)
Number Number (hex)
21 2 16-Bit Frozen Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 5 32-Bit Frozen Counter with Time of 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Freeze 06 (no range, or all) 17, 28 (index - see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
21 6 16-Bit Frozen Counter with Time of 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Freeze 06 (no range, or all) 17, 28 17, 28 (index - see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
21 9 32-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see note 06 (no range, or all) 17, 28 (index - see note 2)
1) 07, 08 (limited qty)
17, 27, 28 (index)
21 10 16-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
`22 0 Counter Change Event - Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
22 1 32-Bit Counter Change Event without 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see note Time 07, 08 (limited qty)
1)
22 2 16-Bit Counter Change Event without 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
22 5 32-Bit Counter Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
22 6 16-Bit Counter Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
23 0 Frozen Counter Event (Variation 0 is 1 (read) 06 (no range, or all)
used to request default variation) 07, 08 (limited qty)
23 1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see note 07, 08 (limited qty)
1)
23 2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
07, 08 (limited qty)
23 5 32-Bit Frozen Counter Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
23 6 16-Bit Frozen Counter Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
30 0 Analog Input - Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see note 06 (no range, or all) 17, 28 (index - see note 2)
1) 07, 08 (limited qty)
17, 27, 28 (index)
30 4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 5 Short floating point 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)

P64-TM-EN-1 369
Chapter 16 - Communications P64

Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Qualifier Codes Function Codes
Description Function Codes (dec) (dec) Qualifier Codes (hex)
Number Number (hex)
32 0 Analog Change Event - Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
32 1 32-Bit Analog Change Event without 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see note Time 07, 08 (limited qty)
1)
32 2 16-Bit Analog Change Event without 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
32 3 32-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
32 4 16-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
32 5 Short floating point Analog Change 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Event without Time 07, 08 (limited qty)
32 7 Short floating point Analog Change 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Event with Time 07, 08 (limited qty)
34 0 Analog Input Deadband (Variation 0 is 1 (read) 00, 01 (start-stop)
used to request default variation) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
34 1 16 Bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34 2 32 Bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see note 06 (no range, or all) 17, 28 (index - see note 2)
1) 07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34 3 Short Floating Point Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Deadband 06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
40 0 Analog Output Status (Variation 0 is 1 (read) 00, 01 (start-stop)
used to request default variation) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
40 1 32-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see note 06 (no range, or all) 17, 28 (index - see note 2)
1) 07, 08 (limited qty)
17, 27, 28 (index)
40 2 16-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
40 3 Short Floating Point Analog Output 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Status 06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
41 1 32-Bit Analog Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 2 16-Bit Analog Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)

370 P64-TM-EN-1
P64 Chapter 16 - Communications

Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Qualifier Codes Function Codes
Description Function Codes (dec) (dec) Qualifier Codes (hex)
Number Number (hex)
41 3 Short Floating Point Analog Output 3 (select) 17, 27, 28 (index) 129 response echo of request
Block 4 (operate)
5 (direct op)
6 (dir. op, noack)
1 1 (read) 07 (limited qty = 1) 129 response 07 (limited qty = 1)
50 (default - see note Time and Date
1)
2 (write) 07 (limited qty = 1)
60 0 Not defined
60 1 Class 0 Data 1 (read) 06 (no range, or all)
60 2 Class 1 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
60 3 Class 2 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
60 4 Class 3 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
70 0 File Event - Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
70 2 File Authentication 29 (authenticate) 5b (free-format) 129 response 5B (free-format)
70 3 File Command 25 (open) 5b (free-format)
27 (delete)
70 4 File Command Status 26 (close) 5b (free-format) 129 response 5B (free-format)
30 (abort)
70 5 File Transfer 1 (read) 5b (free-format) 129 response 5B (free-format)
70 6 File Transfer Status 129 response 5B (free-format)
70 7 File Descriptor 28 (get file info) 5b (free-format) 129 response 5B (free-format)

80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)

No Object (function code only) 13 (cold restart)

No Object (function code only) 14 (warm restart)

No Object (function code only) 23 (delay meas.)

Note:
A Default variation refers to the variation responded to when variation 0 is requested and/or in class 0, 1, 2, or 3 scans.

Note:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded to when a request is sent with qualifiers 17 or
28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded to with qualifiers
00 or 01. For change-event objects, qualifiers 17 or 28 are always responded to.

16.9.3.8.3 DNP3 INTERNAL INDICATIONS


The following table lists the DNP3.0 Internal Indications (IIN) and identifies those that are supported by the device.

P64-TM-EN-1 371
Chapter 16 - Communications P64

The IIN form an information element used to convey the internal states and diagnostic results of a device. This
information can be used by a receiving station to perform error recovery or other suitable functions. The IIN is a two-
octet field that follows the function code in all responses from the device. When a request cannot be processed due
to formatting errors or the requested data is not available, the IIN is always returned with the appropriate bits set.

Bit Indication Description Supported


Octet 1
Set when a request is received with the destination address of the all
stations address (6553510). It is cleared after the next response (even if a
All stations message
0 response to a global request is required). Yes
received
This IIN is used to let the master station know that a "broadcast" message
was received by the relay.
Set when data that has been configured as Class 1 data is ready to be sent
to the master.
1 Class 1 data available Yes
The master station should request this class data from the relay when this
bit is set in a response.
Set when data that has been configured as Class 2 data is ready to be sent
to the master.
2 Class 2 data available Yes
The master station should request this class data from the relay when this
bit is set in a response.
Set when data that has been configured as Class 3 data is ready to be sent
to the master.
3 Class 3 data available Yes
The master station should request this class data from the relay when this
bit is set in a response.
The relay requires time synchronization from the master station (using the
Time-synchronisation Time and Date object).
4 Yes
required This IIN is cleared once the time has been synchronised. It can also be
cleared by explicitly writing a 0 into this bit of the Internal Indication object.
Set when some or all of the relays digital output points (Object 10/12) are in
the Local state. That is, the relays control outputs are NOT accessible
5 Local through the DNP protocol. No
This IIN is clear when the relay is in the Remote state. That is, the relays
control outputs are fully accessible through the DNP protocol.
Set when an abnormal condition exists in the relay. This IIN is only used
6 Device in trouble when the state cannot be described by a combination of one or more of the No
other IIN bits.
Set when the device software application restarts. This IIN is cleared when
7 Device restart the master station explicitly writes a 0 into this bit of the Internal Indications Yes
object.
Octet 2
Function code not
0 The received function code is not implemented within the relay. Yes
implemented
The relay does not have the specified objects or there are no objects
Requested object(s) assigned to the requested class.
1 Yes
unknown This IIN should be used for debugging purposes and usually indicates a
mismatch in device profiles or configuration problems.
Parameters in the qualifier, range or data fields are not valid or out of range.
This is a 'catch-all' for application request formatting errors. It should only
2 Out of range Yes
be used for debugging purposes. This IIN usually indicates configuration
problems.
Event buffer(s), or other application buffers, have overflowed. The master
station should attempt to recover as much data as possible and indicate to
3 Buffer overflow Yes
the user that there may be lost data. The appropriate error recovery
procedures should be initiated by the user.

372 P64-TM-EN-1
P64 Chapter 16 - Communications

Bit Indication Description Supported


The received request was understood but the requested operation is
4 Already executing
already executing.
Set to indicate that the current configuration in the relay is corrupt. The
5 Bad configuration Yes
master station may download another configuration to the relay.
6 Reserved Always returned as zero.
7 Reserved Always returned as zero.

16.9.3.8.4 DNP3 RESPONSE STATUS CODES


When the device processes Control Relay Output Block (Object 12) requests, it returns a set of status codes; one
for each point contained within the original request. The complete list of codes appears in the following table:
Code
Identifier Name Description
Number
0 Success The received request has been accepted, initiated, or queued.
The request has not been accepted because the ‘operate’ message was received after
1 Timeout the arm timer (Select Before Operate) timed out.
The arm timer was started when the select operation for the same point was received.
The request has not been accepted because no previous matching ‘select’ request
2 No select exists. (An ‘operate’ message was sent to activate an output that was not previously
armed with a matching ‘select’ message).
The request has not been accepted because there were formatting errors in the control
3 Format error
request (‘select’, ‘operate’, or ‘direct operate’).
The request has not been accepted because a control operation is not supported for this
4 Not supported
point.
The request has not been accepted because the control queue is full or the point is
5 Already active
already active.
6 Hardware error The request has not been accepted because of control hardware problems.
7 Local The request has not been accepted because local access is in progress.
8 Too many operations The request has not been accepted because too many operations have been requested.
9 Not authorized The request has not been accepted because of insufficient authorisation.
127 Undefined The request not been accepted because of some other undefined reason.

Note:
Code numbers 10 through to 126 are reserved for future use.

16.9.3.8.5 DNP3 CONFIGURATION


To configure the device:
1. Select the CONFIGURATION column and check that the Comms settings cell is set to Visible.
2. Select the COMMUNICATIONS column.
3. Move to the first cell down (RP1 Protocol). Set this to the chosen communication protocol – in this case
DNP3.0.
4. Move down to the next cell (RP1 Address). This cell controls the DNP3.0 address of the IED. Up to 32 IEDs
can be connected to one spur, therefore it is necessary for each IED to have a unique address so that
messages from the master control station are accepted by only one IED. DNP3.0 uses a decimal number
between 1 and 65519 for the Relay Address. It is important that no two IEDs have the same address.

P64-TM-EN-1 373
Chapter 16 - Communications P64

5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six baud rates are
supported by the IED 1200 bps, 2400 bps, 4800 bps, 9600 bps, 19200 bps and 38400 bps. Make sure that
the baud rate selected on the IED is the same as that set on the master station.
6. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames. The
parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on the IED is
the same as that set on the master station.
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
8. Move down to the next cell (RP1 Time Sync). This cell affects the time synchronisation request from the
master by the IED. It can be set to enabled or disabled. If enabled it allows the DNP3.0 master to
synchronise the time on the IED.

16.9.3.8.5.1 DNP3 CONFIGURATOR


A PC support package for DNP3.0 is available as part of the supplied settings application software (MiCOM S1
Agile) to allow configuration of the device's DNP3.0 response. The configuration data is uploaded from the device to
the PC in a block of compressed format data and downloaded in a similar manner after modification. The new
DNP3.0 configuration takes effect after the download is complete. To restore the default configuration at any time,
from the CONFIGURATION column, select the Restore Defaults cell then select All Settings.
In MiCOM S1 Agile, the DNP3.0 data is shown in three main folders, one folder each for the point configuration,
integer scaling and default variation (data format). The point configuration also includes screens for binary inputs,
binary outputs, counters and analogue input configuration.
If the device supports DNP Over Ethernet, the configuration related settings are done in the folder DNP Over
Ethernet.

16.9.4 IEC 61850


This section describes how the IEC 61850 standard is applied to GE Vernova products. It is not a description of the
standard itself. The level at which this section is written assumes that the reader is already familiar with the
IEC 61850 standard.
IEC 61850 is the international standard for Ethernet-based communication in substations. It enables integration of
all protection, control, measurement and monitoring functions within a substation, and additionally provides the
means for interlocking and inter-tripping. It combines the convenience of Ethernet with the security that is so
essential in substations today.
There are two editions of most parts of the IEC 61850 standard; edition 1 and edition 2. This product supports IEC
61850 edition 2 only.

16.9.4.1 BENEFITS OF IEC 61850


The standard provides:
● Standardised models for IEDs and other equipment within the substation
● Standardised communication services (the methods used to access and exchange data)
● Standardised formats for configuration files
● Peer-to-peer communication

The standard adheres to the requirements laid out by the ISO OSI model and therefore provides complete vendor
interoperability and flexibility on the transmission types and protocols used. This includes mapping of data onto

374 P64-TM-EN-1
P64 Chapter 16 - Communications

Ethernet, which is becoming more and more widely used in substations, in favour of RS485. Using Ethernet in the
substation offers many advantages, most significantly including:
● Ethernet allows high-speed data rates (currently 100 Mbps, rather than tens of kbps or less used by most
serial protocols)
● Ethernet provides the possibility to have multiple clients
● Ethernet is an open standard in every-day use
● There is a wide range of Ethernet-compatible products that may be used to supplement the LAN installation
(hubs, bridges, switches)

16.9.4.2 IEC 61850 INTEROPERABILITY


A major benefit of IEC 61850 is interoperability. IEC 61850 standardizes the data model of substation IEDs, which
allows interoperability between products from multiple vendors.
An IEC 61850-compliant device may be interoperable, but this does not mean it is interchangeable. You cannot
simply replace a product from one vendor with that of another without reconfiguration. However, the terminology is
pre-defined and anyone with prior knowledge of IEC 61850 should be able to integrate a new device very quickly
without having to map all of the new data. IEC 61850 brings improved substation communications and
interoperability to the end user, at a lower cost.

16.9.4.3 THE IEC 61850 DATA MODEL


The data model of any IEC 61850 IED can be viewed as a hierarchy of information, whose nomenclature and
categorization is defined and standardized in the IEC 61850 specification.

Data Attributes
stVal q t PhA PhB PhC

Data Objects
Pos A

Logical Nodes: 1 to n
LN1: XCBR LN2: MMXU

Logical Device: IEDs 1 to n

Physical Device (network address)

V01008a

Figure 170: Data model layers in IEC 61850

The levels of this hierarchy can be described as follows:

P64-TM-EN-1 375
Chapter 16 - Communications P64

Data Frame format

Layer Description
Identifies the actual IED within a system. Typically the device’s name or IP address can
Physical Device
be used (for example Feeder_1 or 10.0.0.2.
Identifies groups of related Logical Nodes within the Physical Device. For the MiCOM
Logical Device IEDs, multiple Logical Devices exist, for System (root LD) and various Control,
Measurements, Protection, and Records LDs.
Identifies the major functional areas within the IEC 61850 data model. Either 3 or 6
characters are used as a prefix to define the functional group (wrapper) while the actual
functionality is identified by a 4 character Logical Node name suffixed by an instance
Wrapper/Logical Node Instance
number.
For example, XCBR1 (circuit breaker), MMXU1 (measurements), FrqPTOF2
(overfrequency protection, stage 2).
This next layer is used to identify the type of data you will be presented with. For
Data Object
example, Pos (position) of Logical Node type XCBR.
This is the actual data (measurement value, status, description, etc.). For example, stVal
Data Attribute (status value) indicating actual position of circuit breaker for Data Object type Pos of
Logical Node type XCBR.

16.9.4.4 IEC 61850 IN MICOM IEDS


IEC 61850 is implemented by use of a separate Ethernet board. This Ethernet board manages the majority of the
IEC 61850 implementation and data transfer to avoid any impact on the performance of the protection functions.
To communicate with an IEC 61850 IED on Ethernet, it is necessary only to know its IP address. This can then be
configured into either:
● An IEC 61850 client (or master), for example a bay computer (MiCOM C264)
● An HMI
● An MMS browser, with which the full data model can be retrieved from the IED, without any prior knowledge
of the IED

The IEC 61850 compatible interface standard provides capability for the following:
● Read access to measurements
● Refresh of all measurements at a standard rate.
● Generation of non-buffered and buffered multi-client reports on change of status or measurement
● SNTP time synchronization over an Ethernet link. (This is used to synchronize the IED's internal real time
clock.
● GOOSE peer-to-peer communication
● Disturbance record extraction by IEC 61850 MMS file transfer. The record is extracted as an ASCII format
COMTRADE file

● Controls (Direct and Select Before Operate)

Note:
Setting changes are not supported in the current IEC 61850 implementation. Currently these setting changes are carried out
using the settings application software.

16.9.4.5 IEC 61850 DATA MODEL IMPLEMENTATION


The data model naming adopted in the IEDs has been standardised for consistency. The Logical Nodes are
allocated under Logical Devices, as appropriate.

376 P64-TM-EN-1
P64 Chapter 16 - Communications

The data model is described in the Model Implementation Conformance Statement (MICS) document, which is
available as a separate document.

16.9.4.6 IEC 61850 COMMUNICATION SERVICES IMPLEMENTATION


The IEC 61850 communication services which are implemented in the IEDs are described in the Protocol
Implementation Conformance Statement (PICS) document, which is available as a separate document.

16.9.4.7 IEC 61850 PEER-TO-PEER (GOOSE) COMMUNICATIONS


The implementation of IEC 61850 Generic Object Oriented Substation Event (GOOSE) enables faster
communication between IEDs offering the possibility for a fast and reliable system-wide distribution of input and
output data values. The GOOSE model uses multicast services to deliver event information. Multicast messaging
means that messages are sent to selected devices on the network. The receiving devices can specifically accept
frames from certain devices and discard frames from the other devices. It is also known as a publisher-subscriber
system. When a device detects a change in one of its monitored status points it publishes a new message. Any
device that is interested in the information subscribes to the data it contains.

16.9.4.8 GOOSE MESSAGE VALIDATION


Whenever a new GOOSE message is received its validity is checked before the dataset is decoded and used to
update the Programmable Scheme Logic. As part of the validation process a check is made for state and sequence
number anomalies. If an anomaly is detected, the 'out-of-order' GOOSE message is discarded. When a message is
discarded the last valid message remains active until a new valid GOOSE message is received or its validity period
(TAL) expires.
Out-of-order GOOSE message indicators and reporting are provided to the subscriber via the IEC61850 LGOS
logical node.

16.9.4.9 MAPPING GOOSE MESSAGES TO VIRTUAL INPUTS


Each GOOSE signal contained in a subscribed GOOSE message can be mapped to any of the virtual inputs within
the PSL. The virtual inputs allow the mapping to internal logic functions for protection control, directly to output
contacts or LEDs for monitoring.
An IED can subscribe to all GOOSE messages but only the following data types can be decoded and mapped to a
virtual input:
● BOOLEAN
● BSTR2
● INT16
● INT32
● INT8
● UINT16
● UINT32
● UINT8

16.9.4.10 IEC 61850 GOOSE CONFIGURATION


All GOOSE configuration is performed using the IEC 61850 Configurator tool available in the MiCOM S1 Agile
software application.
All GOOSE publishing configuration can be found under the GOOSE Publishing tab in the configuration editor
window. All GOOSE subscription configuration parameters are under the External Binding tab in the configuration
editor window.
Settings to enable GOOSE signalling and to apply Test Mode are available using the HMI.

P64-TM-EN-1 377
Chapter 16 - Communications P64

16.9.4.11 ETHERNET FUNCTIONALITY


IEC 61850 Associations are unique and made between the client and server. If Ethernet connectivity is lost for any
reason, the associations are lost, and will need to be re-established by the client. The IED has a TCP_KEEPALIVE
function to monitor each association, and terminate any which are no longer active.
The IED allows the re-establishment of associations without disruption of its operation, even after its power has
been removed. As the IED acts as a server in this process, the client must request the association. Uncommitted
settings are cancelled when power is lost, and reports requested by connected clients are reset. The client must re-
enable these when it next creates the new association to the IED.

16.9.4.12 IEC 61850 CONFIGURATION


To configure the device for IEC 61850, it is recommended to use the IEC 61850 IED Configurator, which is part of
the settings application software. You can also configure it with the HMI. To configure IEC61850 edition 2 using the
HMI, you must first enable the IP From HMI setting, after which you can set the media (copper or fibre), IP address,
subnet mask and gateway address.
IEC 61850 allows IEDs to be directly configured from a configuration file. The IED’s system configuration
capabilities are determined from an IED Capability Description file (ICD), supplied with the product. By using ICD
files from the products to be installed, you can design, configure and test (using simulation tools), a substation’s
entire protection scheme before the products are installed into the substation.
To help with this process, the settings application software provides an IEC 61850 Configurator tool, which allows
the pre-configured IEC 61850 configuration file to be imported and transferred to the IED. As well as this, you can
manually create configuration files for all products, based on their original IED capability description (ICD file).
Other features include:
● The extraction of configuration data for viewing and editing.
● A sophisticated error checking sequence to validate the configuration data before sending to the IED.

Note:
Some configuration data is available in the IEC61850 CONFIG. column, allowing read-only access to basic configuration data.

16.9.4.12.1 IEC 61850 CONFIGURATION BANKS


There are two configuration banks:
● Active Configuration Bank
● Inactive Configuration Bank

Any new configuration sent to the IED is automatically stored in the inactive configuration bank, therefore not
immediately affecting the current configuration.
Following an upgrade, the IEC 61850 Configurator tool can be used to transmit a command, which authorises
activation of the new configuration contained in the inactive configuration bank. This is done by switching the active
and inactive configuration banks. The capability of switching the configuration banks is also available using the
IEC61850 CONFIG. column of the HMI.
The SCL Name and Revision attributes of both configuration banks are available in the IEC61850 CONFIG. column
of the HMI.

16.9.4.12.2 IEC 61850 NETWORK CONNECTIVITY


Configuration of the IP parameters and SNTP (Simple Network Time Protocol) time synchronisation parameters is
performed by the IEC 61850 Configurator tool. If these parameters are not available using an SCL (Substation
Configuration Language) file, they must be configured manually.

378 P64-TM-EN-1
P64 Chapter 16 - Communications

Every IP address on the Local Area Network must be unique. Duplicate IP addresses result in conflict and must be
avoided. Most IEDs check for a conflict on every IP configuration change and at power up and they raise an alarm if
an IP conflict is detected.
The IED can be configured to accept data from other networks using the Gateway setting. If multiple networks are
used, the IP addresses must be unique across networks.

16.9.4.13 IEC 61850 EDITION 2


Many parts of the IEC 61850 standard have now been released as the second edition. This offers some significant
enhancements including:
● Improved interoperability
● Many new logical nodes
● Better defined testing; it is now possible to perform off-line testing and simulation of functions

Edition 2 implementation requires use of version 3.8 of the IEC 61850 configurator, which is installed with version
2.0.1 of MiCOM S1 Agile.

16.9.4.13.1 BACKWARD COMPATIBILITY

IEC61850 System - Backward compatibility


An Edition 1 IED can operate with an Edition 2 IEC 61850 system, provided that the Edition 1 IEDs do not subscribe
to GOOSE messages with data objects or data attributes which are only available in Edition 2.
The following figure explains this concept:

Ed2

MMS

IED1 IED2 IED3


C

C C
L/ R

Ed1 Ed1 Ed2

GOOSE

BAY
Ed1 devices in Ed2 system:
 GOOSE OK
 MMS OK
 TOOLS (SCL files) OK V01056
Figure 171: Edition 2 system - backward compatibility

An Edition 2 IED cannot normally operate within an Edition 1 IEC 61850 system. An Edition 2 IED can work for
GOOSE messaging in a mixed system, providing the client is compatible with Edition 2.

P64-TM-EN-1 379
Chapter 16 - Communications P64

Ed1

MMS

IED1 IED2 IED3

C C
L/ R

Ed1 Ed1 Ed2

GOOSE

BAY
Ed1 devices in Ed2 system:
 GOOSE OK
 MMS Not OK
 TOOLS (SCL files) Not OK V01057
Figure 172: Edition 1 system - forward compatibility issues

16.9.4.13.2 EDITION-2 COMMON DATA CLASSES


The following common data classes (CDCs) are new to Edition 2 and therefore should not be used in GOOSE
control blocks in mixed Edition 1 and Edition 2 systems
● Histogram (HST)
● Visible string status (VSS)
● Object reference setting (ORG)
● Controllable enumerated status (ENC)
● Controllable analogue process value (APC)
● Binary controlled analogue process value (BAC)
● Enumerated status setting (ENG)
● Time setting group (TSG)
● Currency setting group (CUG)
● Visible string setting (VSG)
● Curve shape setting (CSG)

Of these, only ENS and ENC types are available from a MiCOM P40 IED when publishing GOOSE messages, so
Data Objects using these Common Data Classes should not be published in mixed Edition 1 and Edition 2 systems.
For compatibility between Edition 1 and Edition 2 IEDs, SCL files using SCL schema version "2.1" must be used.
For a purely Edition 2 system, use the schema version "2007B4".

16.9.5 READ ONLY MODE


With IEC 61850 and Ethernet/Internet communication capabilities, security has become an important issue. For this
reason, all relevant GE Vernova IEDs have been adapted to comply with the latest cyber-security standards.

380 P64-TM-EN-1
P64 Chapter 16 - Communications

In addition to this, a facility is provided which allows you to enable or disable the communication interfaces. This
feature is available for products using Courier, IEC 60870-5-103, or IEC 61850.

16.9.5.1 IEC 60870-5-103 PROTOCOL BLOCKING


If Read-Only Mode is enabled for RP1 or RP2 with IEC 60870-5-103, the following commands are blocked at the
interface:
● Write parameters (=change setting) (private ASDUs)
● General Commands (ASDU20), namely:
○ INF16 auto-recloser on/off
○ INF19 LED reset
○ Private INFs (for example: CB open/close, Control Inputs)
The following commands are still allowed:
● Poll Class 1 (Read spontaneous events)
● Poll Class 2 (Read measurands)
● GI sequence (ASDU7 'Start GI', Poll Class 1)
● Transmission of Disturbance Records sequence (ASDU24, ASDU25, Poll Class 1)
● Time Synchronisation (ASDU6)
● General Commands (ASDU20), namely:
○ INF23 activate characteristic 1
○ INF24 activate characteristic 2
○ INF25 activate characteristic 3
○ INF26 activate characteristic 4

Note:
For IEC 60870-5-103, Read Only Mode function is different from the existing Command block feature.

16.9.5.2 COURIER PROTOCOL BLOCKING


If Read-Only Mode is enabled for RP1 or RP2 with Courier, the following commands are blocked at the interface:
● Write settings
● All controls, including:
○ Reset Indication (Trip LED)
○ Operate Control Inputs
○ CB operations
○ Auto-reclose operations
○ Reset demands
○ Clear event/fault/maintenance/disturbance records
○ Test LEDs & contacts
The following commands are still allowed:
● Read settings, statuses, measurands
● Read records (event, fault, disturbance)
● Time Synchronisation
● Change active setting group

P64-TM-EN-1 381
Chapter 16 - Communications P64

16.9.5.3 IEC 61850 PROTOCOL BLOCKING


If Read-Only Mode is enabled for the Ethernet interfacing with IEC 61850, the following commands are blocked at
the interface:
● All controls, including:
○ Enable/disable protection
○ Operate Control Inputs
○ CB operations (Close/Trip, Lock)
○ Reset LEDs
The following commands are still allowed:
● Read statuses, measurands
● Generate reports
● Extract disturbance records
● Time synchronisation
● Change active setting group

16.9.5.4 READ-ONLY SETTINGS


The following settings are available for enabling or disabling Read Only Mode.
● RP1 Read Only
● RP2 Read Only (only for products that have RP2)
● NIC Read Only (where Ethernet is available)

16.9.5.5 READ-ONLY DDB SIGNALS


The remote read only mode is also available in the PSL using three dedicated DDB signals:
● RP1 Read Only
● RP2 Read Only (only for products that have RP2)
● NIC Read Only (where Ethernet is available)

Using the PSL, these signals can be activated by opto-inputs, Control Inputs and function keys if required.

382 P64-TM-EN-1
P64 Chapter 16 - Communications

16.10 TIME SYNCHRONISATION


In modern protection schemes it is necessary to synchronise the IED's real time clock so that events from different
devices can be time stamped and placed in chronological order. This is achieved in various ways depending on the
chosen options and communication protocols.
● Using the IRIG-B input (if fitted)
● Using the SNTP time protocol (for Ethernet IEC 61850 versions)
● Using IEEE 1588 Precision Time Protocol (PTP)
● By using the time synchronisation functionality inherent in the data protocols
The time synchronisation sources can be configured in a priority order using the Primary Source and Secondary
Source cells in the DATE AND TIME column. If the Primary source becomes unavailable, the Secondary source will
be used, if available.

16.10.1 IRIG-B
IRIG stands for Inter Range Instrumentation Group, which is a standards body responsible for standardising
different time code formats. There are several different formats starting with IRIG-A, followed by IRIG-B and so on.
The letter after the "IRIG" specifies the resolution of the time signal in pulses per second (PPS). IRIG-B, the one
which we use has a resolution of 100 PPS. IRIG-B is used when accurate time-stamping is required.
The following diagram shows a typical GPS time-synchronised substation application. The satellite RF signal is
picked up by a satellite dish and passed on to receiver. The receiver receives the signal and converts it into time
signal suitable for the substation network. IEDs in the substation use this signal to govern their internal clocks and
event recorders.

Signal GPS Satellite GPS

IRIG-B

Receiver IED IED IED


Antenna

V01040

Figure 173: GPS satellite timing signal

The IRIG-B time code signal is a sequence of one second time frames. Each frame is split up into ten 100 mS slots
as follows:
● Time-slot 1: Seconds
● Time-slot 2: Minutes

P64-TM-EN-1 383
Chapter 16 - Communications P64

● Time-slot 3: Hours
● Time-slot 4: Days
● Time-slot 5 and 6: Control functions
● Time-slots 7 to 10: Straight binary time of day

The first four time-slots define the time in BCD (Binary Coded Decimal). Time-slots 5 and 6 are used for control
functions, which control deletion commands and allow different data groupings within the synchronisation strings.
Time-slots 7-10 define the time in SBS (Straight Binary Second of day).

16.10.1.1 IRIG-B IMPLEMENTATION


Depending on the chosen hardware options, the product can be equipped with an IRIG-B input for time
synchronisation purposes. The IRIG-B interface is implemented either on a dedicated board, or together with other
communication functionality such as Ethernet. The IRIG-B connection is presented by a connector is a BNC
connector. IRIG-B signals are usually presented as an RF-modulated signal. The boards support universal IRIG-B,
which means they accept demodulated or modulated IRIG-B.
To set the device to use IRIG-B, use the setting IRIG-B Sync cell in the DATE AND TIME column.
The IRIG-B status can be viewed in the IRIG-B Status cell in the DATE AND TIME column.

16.10.2 SNTP
SNTP is used to synchronise the clocks of computer systems over packet-switched, variable-latency data networks,
such as IP. SNTP can be used as the time synchronisation method for models using IEC 61850 over Ethernet. A
time synchronisation accuracy of within 5 ms is possible.
The device is synchronised by the main SNTP server. This is achieved by entering the IP address of the SNTP
server into the IED using the IEC 61850 Configurator software described in the settings application software
manual. A second server is also configured with a different IP address for backup purposes.
This function issues an alarm when there is a loss of time synchronisation on the SNTP server. This could be
because there is no response or no valid clock signal.
The HMI menu does not contain any configurable settings relating to SNTP, as the only way to configure it is using
the IEC 61850 Configurator. However it is possible to view some parameters in the COMMUNICATIONS column
under the sub-heading SNTP parameters. Here you can view the SNTP server addresses and the SNTP poll rate in
the cells SNTP Server 1, SNTP Server 2 and SNTP Poll rate respectively.
The SNTP time synchronisation status is displayed in the SNTP Status cell in the DATE AND TIME column.

16.10.2.1 LOSS OF SNTP SERVER SIGNAL ALARM


This function issues an alarm when there is a loss of time synchronization on the SNTP server. It is issued when the
SNTP sever has not detected a valid time synchronisation response within its 5 second window. This is because
there is no response or no valid clock. The alarm is mapped to IEC 61850.

16.10.3 IEEE 1588 PRECISION TIME PROTOCOL


The MiCOM P40 modular products support IEEE 1588 Precision Time Protocol (PTP) as a slave-only clock. MiCOM
relays are profile unaware, which means that they will accept synchronisation from any PTP profile. Power Utility
Profile (IEC 61850-9-3) is specifically designed to perform well for substation related applications, with PMU
applications needing the most stringent requirements.
PTP can be used to replace or supplement IRIG-B and SNTP time synchronisation so that the IED can be
synchronised using Ethernet messages from the substation LAN without any additional physical connections being
required.
A dedicated DDB signal (PTP Failure) is provided to indicate failure of PTP.

384 P64-TM-EN-1
P64 Chapter 16 - Communications

16.10.3.1 ACCURACY AND DELAY CALCULATION


A time synchronisation accuracy of within 3 ms is possible. Both peer-to-peer or end-to-end mode delay
measurement can be used.In peer-to-peer mode, delays are measured between each link in the network and are
compensated for. This provides greater accuracy, but requires that every device between the Grand Master and
Slaves supports the peer-to-peer delay measurement.
In end-to-end mode, delays are only measured between each Grand Master and Slave. The advantage of this
mode is that the requirements for the switches on the network are lower; they do not need to independently
calculate delays. The main disadvantage is that more inaccuracy is introduced, because the method assumes that
forward and reverse delays are always the same, which may not always be correct.
When using end-to-end mode, the IED can be connected in a ring or line topology using RSTP or Self Healing
Protocol without any additional Transparent Clocks. But because the IED is a slave-only device, additional
inaccuracy is introduced. The additional error will be less than 1ms for a network of eight devices.

Grand Master

PTP Aware Network

RSTP Network
<8 Hops, so <1ms
additional timing error

V01061a

Figure 174: Timing error using ring or line topology

16.10.3.2 PTP DOMAINS


PTP traffic can be segregated into different domains using Boundary Clocks. These allow different PTP clocks to
share the same network while maintaining independent synchronisation within each grouped set.
The PTP domain number can be configured in MiCOM P40 modular products the using the Domain Number cell in
the DATE AND TIME column. The domain number needs to be configured to match the domain of the local
network.

16.10.4 TIME SYNCHRONISATION USING THE COMMUNICATION PROTOCOLS


All communication protocols have in-built time synchronisation mechanisms. If an external time synchronisation
mechanism such as IRIG-B, SNTP, or IEEE 1588 PTP is not used to synchronise the devices, the time
synchronisation mechanism within the relevant serial protocol is used. The real time is usually defined in the master
station and communicated to the relevant IEDs via one of the rear serial ports using the chosen protocol. It is also
possible to define the time locally using settings in the DATE AND TIME column.

P64-TM-EN-1 385
Chapter 16 - Communications P64

The time synchronisation for each protocol is described in the relevant protocol description section.

386 P64-TM-EN-1
CHAPTER 17

CYBER-SECURITY
Chapter 17 - Cyber-Security P64

17.1 DISCLAIMER
GE Vernova Grid Automation products are digital devices designed to be installed and operated in utility substations
& industrial plant environments and connected to secure private networks. GE Vernova IEDs should not be
connected to the public internet.
GE Vernova strongly recommends that users protect their digital devices using a defense-in-depth strategy which
will protect their products, their network, their systems and interfaces against cyber security threats. This includes,
but is not limited to, placing digital devices inside the control system network security perimeter, deploying and
maintaining access controls, monitoring and intrusion detection, security awareness training, security policies,
network segmentation and firewalls installation, strong and active password management, data encryption, antivirus
and other mitigating applicable technologies.
GE Vernova IEDs are available with standard features, and in some products additional optional software options,
which provide cyber security mechanisms to help users protect against cyber security intrusion. GE Vernova
strongly recommends using all available cyber security options.
For additional details and recommendations on how to protect the GE Vernova IEDs, please see Cyber Security
sections of the manuals. GE Vernova Grid Automation may also provide additional instructions and
recommendations to users from time to time relating to IED and cyber security threats or vulnerabilities.
It is the users' sole responsibility to make sure that all GE Vernova Grid Automation IEDs are installed and operated
considering its cyber security capabilities, security context, and the instructions and recommendations provided to
the user relating to GE Vernova. Users assume all risks and liability associated with damages or losses incurred in
connection with any and all cyber security incidences.
IT IS THE SOLE RESPONSIBILITY OF THE USER TO SECURE THEIR NETWORK AND ASSOCIATED
DEVICES AGAINST CYBER SECURITY INTRUSIONS OR ATTACKS. GE VERNOVA GRID AUTOMATION AND
ITS AFFILIATES ARE NOT LIABLE FOR ANY DAMAGES AND/OR LOSSES ARISING FROM OR RELATED TO
SUCH SECURITY INTRUSION OR ATTACKS.

388 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

17.2 OVERVIEW
In the past, substation networks were traditionally isolated and the protocols and data formats used to transfer
information between devices were often proprietary.
For these reasons, the substation environment was very secure against cyber-attacks. The terms used for this
inherent type of security are:
● Security by isolation (if the substation network is not connected to the outside world, it cannot be accessed
from the outside world).
● Security by obscurity (if the formats and protocols are proprietary, it is very difficult to interpret them).

However, note that these are not recognised defences against attackers.
The increasing sophistication of protection schemes, coupled with the advancement of technology and the desire
for vendor interoperability, has resulted in standardisation of networks and data interchange within substations.
Today, devices within substations use standardised protocols for communication. Furthermore, substations can be
interconnected with open networks, such as the internet or corporate-wide networks, which use standardised
protocols for communication. This introduces a major security risk making the grid vulnerable to cyber-attacks,
which could in turn lead to major electrical outages.
Clearly, there is now a need to secure communication and equipment within substation environments. This chapter
describes the security measures that have been put in place for our range of Intelligent Electronic Devices (IEDs).

Note:
Cyber-security compatible devices do not enforce NERC compliance, they merely facilitate it. It is the responsibility of the user
to ensure that compliance is adhered to as and when necessary.

This chapter contains the following sections:


Disclaimer 388
Overview 389
The Need for Cyber-Security 390
Standards 391
Cyber-Security Implementation 395
Roles and Permissions 396
User Authentication 399
SNMP Configuration 416
Returning The IED To Factory 417
Security Event Management 418

P64-TM-EN-1 389
Chapter 17 - Cyber-Security P64

17.3 THE NEED FOR CYBER-SECURITY


Cyber-security provides protection against unauthorised disclosure, transfer, modification, or destruction of
information or information systems, whether accidental or intentional. To achieve this, there are several security
requirements:
● Confidentiality (preventing unauthorised access to information)
● Integrity (preventing unauthorised modification)
● Availability/Authentication (preventing the denial of service and assuring authorised access to information)
● Non-repudiation (preventing the denial of an action that took place)
● Traceability/Detection (monitoring and logging of activity to detect intrusion and analyse incidents)

The threats to cyber-security may be unintentional (e.g. natural disasters, human error), or intentional (e.g. cyber-
attacks by hackers).
Good cyber-security can be achieved with a range of measures, such as closing down vulnerability loopholes,
implementing adequate security processes and procedures and providing technology to help achieve this.
Examples of vulnerabilities are:
● Indiscretions by personnel (users keep passwords on their computer)
● Bad practice (users do not change default passwords, or everyone uses the same password to access all
substation equipment)
● Bypassing of controls (users turn off security measures)
● Inadequate technology (substation is not firewalled)

Examples of availability issues are:


● Equipment overload, resulting in reduced or no performance
● Expiry of a certificate preventing access to equipment

To help tackle these issues, standards organisations have produced various standards. Compliance with these
standards significantly reduces the threats associated with lack of cyber-security.

390 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

17.4 STANDARDS
There are several standards, which apply to substation cyber-security. The standards currently applicable to Grid
Automation Systems and IEDs are NERC and IEEE1686.

Standard Country Description


NERC CIP (North American Electric Reliability USA Framework for the protection of the grid critical Cyber
Corporation) Assets
BDEW (German Association of Energy and Water Germany Requirements for Secure Control and
Industries) Telecommunication Systems
ANSI ISA 99 USA ICS oriented then Relevant for EPU completing existing
standard and identifying new topics such as patch
management
IEEE 1686 International International Standard for substation IED cyber-security
capabilities
IEC 62351 International Power systems management and associated
information
exchange - Data and communications security
IEC 62443 International Security for industrial automation and control systems

ISO/IEC 27002 International Framework for the protection of the grid critical Cyber
Assets
NIST SP800-53 (National Institute of Standards USA Complete framework for SCADA SP800-82and ICS
and Technology) cyber-security
CPNI Guidelines (Centre for the Protection of UK Clear and valuable good practices for Process Control
National Infrastructure) and SCADA security

17.4.1 NERC COMPLIANCE


The North American Electric Reliability Corporation (NERC) created a set of standards for the protection of critical
infrastructure. These are known as the CIP standards (Critical Infrastructure Protection). These were introduced to
ensure the protection of 'Critical Cyber Assets', which control or have an influence on the reliability of North
America’s electricity generation and distribution systems.
These standards have been compulsory in the USA for several years now. Compliance auditing started in June
2007, and utilities face extremely heavy fines for non-compliance.

NERC CIP standards

CIP Standard Description


CIP-002 Critical Cyber Assets Define and document the Critical Assets and the Critical Cyber Assets
CIP-003 Security Management Controls Define and document the Security Management Controls required to
protect the Critical Cyber Assets
CIP-004 Personnel and Training Define and Document Personnel handling and training required protecting
Critical Cyber Assets
CIP-005 Electronic Security Define and document logical security perimeters where Critical Cyber
Assets reside. Define and document measures to control access points
and monitor electronic access
CIP-006 Physical Security Define and document Physical Security Perimeters within which Critical
Cyber Assets reside

P64-TM-EN-1 391
Chapter 17 - Cyber-Security P64

CIP Standard Description


CIP-007 Systems Security Management Define and document system test procedures, account and password
management, security patch management, system vulnerability, system
logging, change control and configuration required for all Critical Cyber
Assets
CIP-008 Incident Reporting and Response Define and document procedures necessary when Cyber-security
Planning Incidents relating to Critical Cyber Assets are identified
CIP-009 Recovery Plans Define and document Recovery plans for Critical Cyber Assets

17.4.1.1 CIP 002


CIP 002 concerns itself with the identification of:
● Critical assets, such as overhead lines and transformers
● Critical cyber assets, such as IEDs that use routable protocols to communicate outside or inside the
Electronic Security Perimeter; or are accessible by dial-up

Power Utility Responsibilities GE Vernova's Contribution


Create the list of the assets We can help the power utilities to create this asset register automatically.
We can provide audits to list the Cyber assets

17.4.1.2 CIP 003


CIP 003 requires the implementation of a cyber-security policy, with associated documentation, which demonstrates
the management’s commitment and ability to secure its Critical Cyber Assets.
The standard also requires change control practices whereby all entity or vendor-related changes to hardware and
software components are documented and maintained.

Power Utility Responsibilities GE Vernova's Contribution


To create a cyber-security policy We can help the power utilities to have access control to its critical assets by
providing centralized Access control.
We can help the customer with its change control by providing a section in the
documentation where it describes changes affecting the hardware and software.

17.4.1.3 CIP 004


CIP 004 requires that personnel with authorized cyber access or authorized physical access to Critical Cyber
Assets, (including contractors and service vendors), have an appropriate level of training.

Power Utility Responsibilities GE Vernova's Contribution


To provide appropriate training of its personnel We can provide cyber-security training

17.4.1.4 CIP 005


CIP 005 requires the establishment of an Electronic Security Perimeter (ESP), which provides:
● The disabling of ports and services that are not required
● Permanent monitoring and access to logs (24x7x365)
● Vulnerability Assessments (yearly at a minimum)
● Documentation of Network Changes

392 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Power Utility Responsibilities GE Vernova's Contribution


To monitor access to the ESP To disable all ports not used in the IED
To perform the vulnerability assessments To monitor and record all access to the IED
To document network changes

17.4.1.5 CIP 006


CIP 006 states that Physical Security controls, providing perimeter monitoring and logging along with robust access
controls, must be implemented and documented. All cyber assets used for Physical Security are considered critical
and should be treated as such:

Power Utility Responsibilities GE Vernova's Contribution


Provide physical security controls and perimeter monitoring GE Vernova cannot provide additional help with this aspect
Ensure that people who have access to critical cyber assets
don’t have criminal records

17.4.1.6 CIP 007


CIP 007 covers the following points:
● Test procedures
● Ports and services
● Security patch management
● Antivirus
● Account management
● Monitoring

Power Utility Responsibilities GE Vernova's Contribution


To provide an incident response team and have Test procedures, we can provide advice and help on testing.
appropriate processes in place Ports and services, our devices can disable unused ports and services
Security patch management, we can provide assistance
Antivirus, we can provide advise and assistance
Account management, we can provide advice and assistance
Monitoring, our equipment monitors and logs access

17.4.1.7 CIP 008


CIP 008 requires that an incident response plan be developed, including the definition of an incident response team,
their responsibilities and associated procedures.

Power Utility Responsibilities GE Vernova's Contribution

To provide an incident response team and have appropriate


GE Vernova cannot provide additional help with this aspect.
processes in place.

17.4.1.8 CIP 009


CIP 009 states that a disaster recovery plan should be created and tested with annual drills.

Power Utility Responsibilities GE Vernova's Contribution


To implement a recovery plan To provide guidelines on recovery plans and backup/restore documentation

P64-TM-EN-1 393
Chapter 17 - Cyber-Security P64

17.4.2 IEEE 1686-2013


IEEE 1686-2013 is an IEEE Standard for substation IEDs' cyber-security capabilities. It proposes practical and
achievable mechanisms to achieve secure operations.
The following features described in this standard apply:
● Passwords are 8 characters long and can contain upper-case, lower-case, numeric and special characters.
● Passwords are never displayed or transmitted to a user.
● IED functions and features are assigned to different password levels. The assignment is fixed.
● The audit trail is recorded, listing events in the order in which they occur, held in a circular buffer.
● Records contain all defined fields from the standard and record all defined function event types where the
function is supported.
● No password defeat mechanism exists. Instead a secure recovery password scheme is implemented.
● Unused ports (physical and logical) may be disabled.

394 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

17.5 CYBER-SECURITY IMPLEMENTATION


GE Vernova IEDs have always been and will continue to be equipped with state-of-the-art security measures. Due
to the ever-evolving communication technology and new threats to security, this requirement is not static. Hardware
and software security measures are continuously being developed and implemented to mitigate the associated
threats and risks.
MiCOM 5th Generation P40 products provide enhanced security through the following features:
● An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS)
client that is managed centrally, enables user attribution, provides accounting of all user activities, and uses
secure standards based on strong cryptography for authentication and credential protection. In other words,
this option uses a RADIUS.
● Server for user authentication. There is provision for both remote (RADIUS) and local (device) authentication.
● A Role-Based Access Control (RBAC) system in line with IEC 62351-8:2020 that provides a permission
model that allows access to the device operations and configurations based on specific roles and individual
user accounts configured on the AAA server.
● Security event reporting through both proprietary security event log (separate from the main events file) and
the Syslog and SNMP protocols for supporting Security Information Event Management (SIEM) systems for
centralised cybersecurity monitoring.
● Encryption of passwords - stored within the IED, in network messages between the MiCOM S1 Agile software
and the IED, and in network messages between the RADIUS server and the IED (subject to the RADIUS
server configuration).
● Secure firmware upgrade process.

17.5.1 INITIAL SETUP: DEFAULT USERNAMES AND DEFAULT PASSWORDS


The requirements for initial setup of the IED for cyber-security and RBAC will depend on:
1. which interfaces, if any, the cyber-security is required,
2. the intended authentication method, as defined in the setting Auth. Method’ in SECURITY CONFIG column
(see the Authentication Methods section).
When the authentication method is configured as Device Only, there are four pre-defined profiles.

User Name Default Password IEC 62351-8 Roles


ADMIN1 ChangeMe1# SECADM
RBACMNT1 ChangeMe2# RBACMNT
ENGG1 ChangeMe3# ENGINEER
VIEWER1 ChangeMe4# VIEWER

During the first logon, it is Mandatory to change the Default Passwords, and the IED or MiCOM S1 Agile software
will prompt the user to change it. The new password must comply with the strength defined by the Password Policy
setting, detailed in the Password Policy section of this chapter.
When the authentication method is configured as ‘Server + Device’, and authentication using RADIUS is required,
users must be set up on the RADIUS server (see the RADIUS users section). These users are separate from the
pre-defined Device users. RADIUS server information must be configured in the IED to connect to the RADIUS
server(s) for Server authentication (see the RADIUS server settings section). It is recommended that the RADIUS
shared secret be changed from the default (see the RADIUS client-server validation section).

P64-TM-EN-1 395
Chapter 17 - Cyber-Security P64

17.6 ROLES AND PERMISSIONS

17.6.1 ROLES
The P40 Agile products supports all the mandatory pre-defined roles as per IEC 62351-8:2020.

IEC 62351-8 Roles Value


VIEWER 0
OPERATOR 1
ENGINEER 2
INSTALLER 3
SECADM 4
SECAUD 5
RBACMNT 6

Individual user accounts can be configured to have one or more of these roles.
● VIEWER: Can view all values and settings
● OPERATOR: Can view values and perform control operations
● ENGINEER: Can view values, and change settings of the device
● INSTALLER: Specific role required to perform firmware updates
● SECADM: Security Administrator - Can edit/modify Users and roles and configure security settings
● SECAUD: Security Auditor - Can view Security Log files
● RBACMNT: RBAC Management can change role to permission assignment
Only one role of one type is allowed to be logged in at a time from any interface. For example, one Operator can be
logged in but not a second Operator at the same time from any other interface. This prevents subsets of settings
from being changed at the same time.

17.6.2 PERMISSIONS
Authentication and authorization are two different processes. An authenticated user cannot perform any action on
the IED unless a privilege has been explicitly granted to them. This is the concept of “least privileges” access.
Privileges must be granted to users through roles. A role is a collection of privileges, and roles are granted to users.
It is possible to have multiple roles for a user. The privilege/role matrix is stored on the IED. This is known as Role-
Based-Access Control (RBAC).
On successful user authentication, the IED will load the user’s role list. If the user’s role changes, the user must
logout and log back in to exercise his/her privileges.
The table below shows the predefined permissions assignment for the predefined Roles according to IEC
62351-8:2020

Permission
SETTINGGROU
LISTOBJECTS

READVALUES

Role Name
REPORTING

Value
FILEWRITE

FILEMNGT

SECURITY
FILEREAD

CONTROL

(revision = 1)
DATASET

P
CONFIG

<0> VIEWER C C X C1

396 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Permission

SETTINGGROU
LISTOBJECTS

READVALUES
Role Name

REPORTING
Value

FILEWRITE

FILEMNGT

SECURITY
FILEREAD

CONTROL
(revision = 1)

DATASET

P
CONFIG
<1> OPERATOR X X X C1 X X
<2> ENGINEER X X X X X1 X1 X1 X X
<3> INSTALLER X X X X2 X2 X X
<4> SECADM X X X X4 X4 X4 X X
<5> SECAUD X X X X3
<6> RBACMNT X X X X4 X
<7 ...32767> Reserved For future use of IEC defined roles.
<-32768 .. -1> Private Defined by external agreement. Not guaranteed to be inoperable.
C = Conditional read access, clarification of specific data objects may be necessary (e.g., VIEWER may not access security
settings, but process values)
C1 = Conditional read access to files of filetype data
X1 = Access to files of type data and config
X2 = Access to files of type config and firmware (updates)
X3 = Access to files of type audit log
X4 = Access to files of type security (config)

The table below shows the predefined permissions description according to IEC 62351-8:2020

Permission Description
LISTOBJECTS Allows the subject/role to discover what objects are present within an IED by presenting the type and ID
of those objects. If this permission is granted to a subject/role, the object for which the READVALUES
permission has not been granted are not readable. This permission basically relates to all objects defined
in IEC 61850 and allows a query on the existence of the data objects.
READVALUES Allows the subject/role to obtain the values for all or some objects that are present within an IED in
addition to the type and ID. This permission basically relates to all objects defined in IEC 61850 that
provide a value and allows a read action on the actual values of the data objects.
DATASET Allows the subject/role to have full service access (e.g., createDataSet, deleteDataSet) for both persistent
and non-persistent DataSets.
REPORTING Allows the subject/role to use buffered reporting as well as unbuffered reporting. Reporting relates to
buffered and unbuffered report control blocks of a logical node.
FILEREAD Allows the subject/role to perform read actions on file objects.
FILEWRITE Allows the subject/role to perform write actions on file objects. This permission includes the FILEREAD
permission.
CONTROL (group) Allows the subject/role to perform control operations on all or some controllable objects that are present
within an IED. Control services are for instance select or operate and relate to data objects defined in IEC
61850.
CONFIG Allows the subject/role to locally or remotely configure all or some objects that are present within an IED.
This relates to data attributes of the IEC 61850 functional constraints CF, DC and SP.
SETTINGGROUP Allows the subject/role to remotely configure SettingGroup control block. For example, this relates to the
switching between different configured SettingGroups. SettingGroups also contains the IEC 61850
functional constraints SE.
FILEMNGT Allows the subject/role to delete existing files on the IEDS.
SECURITY Allows the subject/role to perform actions on all security related data objects, reportings, logs or files.

P64-TM-EN-1 397
Chapter 17 - Cyber-Security P64

Specific product related permissions are listed in the tables below. Roles are mapped to Access Level definitions: A
cross indicates that specific actions can be done by a user with the role allocated.

Extract Files Role Name


None
File Type VIEWER OPERATOR ENGINEER INSTALLER SECADM SECAUD RBACMNT
Logged
Setting X X X X X
PSL X X
MCL (IEC 61850) X X
DNP3 X X
SLD X X
Events (operational) X X X
Security Events X
Disturbance
X X X
Records

Sending Files Role Name


None
File Type VIEWER OPERATOR ENGINEER INSTALLER SECADM SECAUD RBACMNT
Logged
Setting X X X
PSL X X
MCL (IEC 61850) X X
DNP3 X X
SLD X X
Menu Text X X

398 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

17.7 USER AUTHENTICATION

17.7.1 AUTHENTICATION METHODS


The IED supports Bypass (no authentication), Device authentication and Server authentication.
Authentication
Description User Interface
Method
Bypass Auth. IED does not provide security, any user (Local) can access the IED without Front Panel UI
logging in. IED does not validate user and password. In this case, there is no Front Port (USB port)
need to enter user name and password to login. Bypass can not be enabled (Local interfaces only)
on Rear Port 1, Rear Port 2 and Ethernet Ports.
Device Only IED allows role access using local authentication. Front Panel UI
Front Port (USB port)
Rear Port 1
Rear Port 2
Network Port 1
Network Port 2
Server + Device IED uses RADIUS server authentication to validate the user first. And it Front Panel UI
allows fallback to device authentication if the RADIUS server(s) are Front Port (USB port)
unavailable. Rear Port 1
Rear Port 2
Network Port 1
Network Port 2

If Bypass Auth. is enabled, the IED ignores the Auth. Method setting.
The Auth. Method setting offers the following options for user authentication:
● Server + Device (This is the default setting for IEDs with NIC (Ethernet Board) fitted)
● Device Only (This is the default setting for IEDs without NIC (Ethernet Board) fitted)

Only users with a SECADM role may change the Auth. Method setting. If the SECADM user changes it, the role
remains logged in. Only when the user logs-out is their access-level revoked.

17.7.2 BYPASS
In Bypass Auth. mode, the IED does not provide user authentication - any user can login. IED does not validate
user and password. The bypass security feature provides an easier access, with no authentication and encryption
for situations when this is considered safe. Only users with SECADM role can enable Bypass mode.
There are three modes for authentication bypass:
1. Disabled - no interfaces in Bypass Auth. mode (normal authentication is active)
2. Local - Bypass authentication when using Front Port and Front Panel
3. Front Panel - will bypass authentication Front Panel User Interface

Bypass authentication for


Front Port Front Panel UI
Bypass mode:
Disabled
Local X X
Front Panel X

P64-TM-EN-1 399
Chapter 17 - Cyber-Security P64

The DDB signal Security Bypass is available to indicate that the IED is in Bypass Auth. mode.
The Front Panel UI will display "BYPASSED" at the top of the screen to indicate that the IED is in Bypass Auth.
mode.

17.7.3 LOGIN
A user can only login through the following methods:
● Front Panel User Interface
● Using MiCOM S1 Agile, connected to either the Front Port, Rear Port 1 or 2, or Ethernet Network Port 1 or 2.

17.7.3.1 FRONT PANEL LOGIN


Front panel User Interface supports both Device authentication and Server authentication. The P40 gives the user
the option to enter the user credentials via UI panel. To access the Login window, select the Login text in the top
banner using the arrow keys.

400 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

For both Device authentication or Server authentication, the user can enter any valid username and password
combination. For ease of typing, it is preferable to do login using MiCOM S1 Agile.
After successful log in, a confirmation message is displayed, showing the logged in username at the top of the
screen. For example:

17.7.3.2 LOGIN FAILED


When Authentication fails, a failure message is displayed:

P64-TM-EN-1 401
Chapter 17 - Cyber-Security P64

17.7.3.3 OTHER LOGIN PROMPTS


For cases where the bypass is disabled and the user attempts an action which requires a user login, the Login
Window appears after the error message. This is applicable while changing any setting values or pressing buttons
which require user management - the Function Key, for example.

17.7.3.4 MICOM S1 LOGIN


When the user attempts to login, MiCOM S1 Agile will prompt the user with a login dialog box that contains a
username and password entry fields. For both Device authentication or Server authentication, the user can enter
any valid combination of username and password.

17.7.3.4.1 WARNING BANNER


After successful authentication and authorisation to access the IED, MiCOM S1 Agile will display a security warning
banner to the user.
If I Agree is selected, the integrated authentication and authorisation is completed. Selecting I Disagree causes the
program to close and the login user to logout.
For S1 Agile authentication, this is a pop-up dialog that the user must click to acknowledge.

17.7.4 USER SESSIONS


Only one role of one type is allowed to be logged in at a time from any interface. If the role has been logged in from
one interface, an attempt to login the same role will result in a message being displayed, as below.

402 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Open sessions will be automatically closed by the IED after a configurable session timeout.
The inactivity timer configuration setting defines the period of time that the IED waits in idleness before a logged in
user is automatically logged out.
If there is any data change that does not commit to IED, the data change is discarded when user logged out. If there
is any access that does not finish, the access will fail when user logged out. Front panel will display the default page
when user reaches the defined inactivity time.
If the keypad is inactive for configured UI inactivity timer, the user logout message is displayed and the front panel
user interface reverts to the Viewer access level.
The following settings are available in the SECURITY CONFIG column to support configurable inactivity timers.
● FP InactivTimer
● UI InactivTimer
● NIC Tunl Timeout

User Role
Setting Name Description Min Max Default Units
Required

Attempts Limit Number of failed authentications before the device 0 (lockout 99 3 - SECADM
blocks subsequent authentication attempts for the disabled)
lockout period. A value of 0 means Lockout is disabled.
Lockout Period The period of time in seconds a user is prevented from 1 5940 30 sec SECADM
logging in, after being locked out.

FP FP Inactivity Timer is the time of idleness on Front Port 0 (no 30 10 min SECADM
InactivTimer before a logged in user is automatically logged out and Inactivity
revert the access level to the viewer role Timeout)
UI InactivTimer UI Inactivity Timer is the time of idleness on Front Panel 0 (no 30 10 min SECADM
before a logged in user is automatically logged out and Inactivity
revert the access level to the viewer role Timeout)

P64-TM-EN-1 403
Chapter 17 - Cyber-Security P64

User Role
Setting Name Description Min Max Default Units
Required

NIC Tunl NIC Tunl Timeout is the time of idleness on Ethernet 1 30 5 min SECADM
Timeout Port (NIC) before a logged in user is automatically
logged out and revert the access level to the viewer role

The recommended settings for Attempts Limit is 3 and Lockout Period is 30 sec to discourage brute force
attacks. If the Lockout period is too large, anybody can lockout Device users.
The following settings are available in the COMMUNICATIONS column to configure the inactivity timers for rear
serial ports:
● KBUS InactTmr for RP1, if Courier Protocol is selected
● RP2 InactivTimer for RP2

17.7.5 USER LOCKING POLICY


A local user locking policy is implemented for Device access:
● This user locking policy applies to both Device users.
● The account is unlocked at the first successful login after the Lockout Period
● If the user consecutively fails to login at the configured number of Attempts Limit, the user account will be
locked for the configured Lockout Period
Each user account records how long it has been locked if the account is locked.
Each user account records how many times it has consecutively failed to login. User account failed times include all
interfaces login attempts. For example, if the Attempts Limit setting is 3 and the operator failed to login from front
panel 2 times, and they changed to login from the Courier interface, but failed again, then the Operator would be
locked out.
When the IED is powered on, these Attempts Limit counter resets to zero.
When the user account exceeds the Attempts Limit it is locked for Lockout period, at that time Attempt limit
resets to zero.
The locked user account will be unlocked automatically, after the configured “Lockout Period” is expired.
If the locked account attempts to login the IED from the Front Panel, the unsuccessful login attempt screen is
displayed.

17.7.6 LOGOUT
Each user should Log out after reading or configuring the IED.
The user can only log out from the front panel, if they logged in from the front panel. If the user logged in from S1
Agile, they have to logout from S1 Agile.

17.7.6.1 FRONT PANEL LOGOUT


Go to the top of the banner and select the current logged in User. You may be prompted to log out with the following
display:

404 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

If you confirm, the following screen is displayed for 2 seconds and then the action will be recorded in the security
events file:

If you decide not to log out (i.e. you cancel), the logout screen would be cancelled.

17.7.6.2 MICOM S1 LOGOUT


Right-click on the device name in the System Explorer panel in MiCOM S1 Agile and select Log Off.
In the Log Off confirmation dialog, click Yes. The action will be recorded in the security events file.

P64-TM-EN-1 405
Chapter 17 - Cyber-Security P64

17.7.7 PASSWORD POLICY


Cyber-security requires strong passwords and validation for NERC compliance. The IED will enforce one of two
levels of password strength according to the Password Policy setting.
The NERC password complexity policy requires an alpha-numeric password (for all accesses, front panel, and
network/local port) that meets the following mandatory requirements:
1. Passwords cannot contain the user's account name or parts of the user's full name that exceed two
consecutive characters.
2. Passwords must be at least eight characters in length, but not exceed 16 characters in length.
Strict passwords rules must contain characters from all four categories as shown below:
a. English uppercase characters (A through Z).
b. English lowercase characters (a through z).
c. Numeric (digits 0 through 9).
d. Special non-alphanumeric characters (such as @,!,#,{, but not limited to only those)
Normal password rules: Any 3 out of 4 conditions as in strict password rules.
For Device authentication, the IED will enforce that configured passwords meet these requirements. The user can
select which policies are required by selecting either Strict or Normal in the Password Policy setting under DEVICE
RBAC.

User Role
Setting Name Description Min Max Default Units
Required
Password Policy Selection of whether strict or normal rules apply for Normal Strict Strict - SECADM
device authentication password policy

For Server authentication, the password complexity and user locking policy is defined in the external RADIUS
server.

17.7.8 PASSWORD EXPIRY


For Device authentication users, it is possible to select a configurable time (in days) for the password to be changed
by the user.
Under DEVICE RBAC Settings, select Password Expiry to be Enabled. The setting of Disabled disables the
password expiry check by the IED. If enabled, Max Password Age can be selected, this is in the range of days.

User Role
Setting Name Description Min Max Default Units
Required
Password Expiry Selection of whether Password Expiry is enforced Disabled Enabled Enabled - SECADM
by the IED for device authentication

Max Password Period in days if Password Expiry is enabled, the 30 730 180 days SECADM
Age device passwords need to be changed

When the Max Password Age has been reached and if the user attempts to login using the front panel UI, the
following window will be shown.

406 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

The user will be presented with a screen to save the new password.

17.7.9 CHANGE PASSWORD


All the Device users will need to change the default password at the first logon.
The initial password change can be done either from the front panel User Interface, or from MiCOM S1 Agile using
the Change/Set Password option in the Supervise Device dialog box.

P64-TM-EN-1 407
Chapter 17 - Cyber-Security P64

Any further password change can only be done from MiCOM S1 Agile using the Change/Set Password option in
the Supervise Device dialog box.
Users with SECADM and RBACMNT roles can change the password of any user. Users with other roles can
change only their own password.

Caution:
It is recommended that user passwords are changed periodically.

17.7.10 RADIUS AUTHENTICATION


When the Auth. Method setting is configured as Server + Device, a user must log in with a username and
password that has been predefined on the RADIUS server.
This log in can be performed from any interface, as described in the Login section. The IED will authenticate the
user to the active RADIUS server, over the Ethernet connection.

Groups User
Access Request
User login RADIUS
IED Client
Access
Accept
(User Role)
User RADIUS Server Active Directory

V01100

Figure 175: RADIUS server/client communication

17.7.10.1 RADIUS USERS


For Server authentication, RADIUS users and passwords are created in the RADIUS server (in the Active
Directory), not in the IED.
The username must be from the ASCII Subset of 32 to 122 which includes upper and lower case letters, digits and
several special characters.
Each RADIUS user must have a password that meets the password policy of the Active Directory (not the password
policy of the P40) and have one of the supported roles assigned in the Active Directory.
The number of RADIUS users is not limited by the IED.
RADIUS password changes are done in the Active Directory (after password expiration).

17.7.10.2 RADIUS CLIENT


Two RADIUS servers are supported by the IED in the configuration for redundancy. The IED will try each in
sequence until one responds.
The IED will first try server 1 up to the configured number of retries, leaving a request timeout between each
request. If, after this point there is still no valid answer from server 1, the IED will switch to server 2 and repeat for
up to the configured number of retries.
If the number of retries for the second server is exceeded the IED will fallback to Device authentication. A RADIUS
Server unavailable security event is also logged under this condition.

408 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

The RADIUS implementation supports the following authentication protocols:


● EAP-TTLS-MSCHAP2
● PAP
● EAP-PEAP-MSCHAP2
● PAP EAP-TTLS-PAP (Default)

The RADIUS implementation queries the Role ID vendor attribute and establish the logged in user security context
with that role.

RADIUS Config. Value


Vendor ID 2910
Vendor Attribute 1
Standard Values
VIEWER 0
OPERATOR 1
ENGINEER 2
INSTALLER 3
SECADM 4
SECAUD 5
RBACMNT 6

17.7.10.3 RADIUS SERVER SETTINGS


The following RADIUS server information must be configured in the IED to connect to the RADIUS server(s) for
Server authentication.
Setting User Role
Description Min Max Default Units
Name Required
RADIUS IP address of Server 1. 0.0.0.0 255.255.255.255 0.0.0.0 - SECADM
Pri IP Default value indicates no
Primary RADIUS server is
configured, and so RADIUS
is disabled.
RADIUS IP address of Server 2. 0.0.0.0 255.255.255.255 0.0.0.0 - SECADM
Sec IP Default value indicates no
Secondary RADIUS server
is configured
RADIUS RADIUS authentication port 1 65535 1812 - SECADM
Auth Port
RADIUS Authentication protocol to be EAP-TTLS-MSCHAP2 PAP EAP-TTLS- - SECADM
Security used by RADIUS server PAP PAP
EAP-PEAP-
MSCHAP2
PAP EAP-TTLS-PAP
RADIUS Timeout in seconds between 1 900 2 sec SECADM
Timeout re-transmission requests
RADIUS Number of retries before 1 99 10 - SECADM
Retries giving up
RADIUS Shared Secret used in 1 character 64 characters ChangeMe1# - SECADM
Secret authentication. It is only
displayed as asterisks.

P64-TM-EN-1 409
Chapter 17 - Cyber-Security P64

Setting User Role


Description Min Max Default Units
Name Required
RADIUS NAS-Identifier for RADIUS 1 character 20 characters MiCOM P40 - SECADM
NAS ID

The data cell RADIUS Status indicates the status of the currently-selected RADIUS server. This will display either
Disabled, Server OK, or Failed.

17.7.10.4 RADIUS ACCOUNTING


RADIUS accounting is not supported by the IED. The user can achieve accounting through syslog (see the
SYSLOG section).

17.7.10.5 RADIUS CLIENT-SERVER VALIDATION


Client-server validation is achieved using a shared secret. The IED must be configured with the RADIUS Secret
setting to match the shared secret configured in the RADIUS server. It is recommended (but not enforced) that this
setting meets the P40 password requirements. The device supports RADIUS secret of 1-64 characters.
MiCOM S1 Agile provides an option to save RADIUS Secret to the device. This can be achieved by logging to the
device with a SECADM profile and accessing Supervise Device -> RADIUS Secret.

Note:
It is recommended that the shared secret be changed from the default before using RADIUS authentication.

The IED does not support exchange of CA certificates. The RADIUS server may send a certificate but the IED will
not verify it.

17.7.11 RECOVERY

17.7.11.1 RESTORE TO LOCAL FACTORY DEFAULT


The Restore Defaults setting is available to facilitate NERC CIP compliance requirements for decommissioning
critical cyber devices. Only the Administrator role can change this setting.
The Restore Defaults setting under the CONFIGURATION column is used to restore a setting group to factory
default settings.
0 = No Operation
1 = All Settings
2 = Setting Group 1
3 = Setting Group 2
4 = Setting Group 3
5 = Setting Group 4
To restore the default values to the settings in any setting group, set the Restore Defaults setting to the relevant
Group number. Alternatively, it is possible to set the Restore Defaults setting to All Settings to restore the
default values to all the IEDs settings, not only one setting group.

Note:
Restoring defaults to all settings includes the rear communication port settings, which may result in communication via the
rear port being disrupted if the new (default) settings do not match those of the master station.

410 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Data (events, DR, fault records, protection counters etc) is left untouched. When decommissioning critical cyber
IEDs, users may want to clear all data and events as well.

17.7.11.2 PASSWORD RESET PROCEDURE


If you mislay a devices password (if Administrator forgets their password), the passwords can be reset to default
using a recovery password. To obtain the recovery password you must contact the Contact Centre and supply the
Serial Number and the security code. The Contact Centre will use these items to generate a Recovery Password.
The security code is a 16-character string of uppercase characters. It is a read-only parameter. The device
generates its own security code randomly. A new code is generated under the following conditions:
● On power up
● Whenever settings are set back to default
● On expiry of validity timer (see below)
● When the recovery password is entered

This reset procedure can be only accomplished through front panel exclusively and cannot be done over any other
interface. As soon as the security code is displayed on the front panel User Interface, a validity timer is started. This
validity timer is set to 72 hours and is not configurable. This provides enough time for the Contact Centre to
manually generate and send a recovery password. The Service Level Agreement (SLA) for recovery password
generation is one working day, so 72 hours is sufficient time, even allowing for closure of the Contact Centre over
weekends and bank holidays.
The procedure is:
The security code is displayed on confirmation. The validity timer is then started. The security code can only be
read from the front panel.
This reset procedure can be only accomplished through front panel exclusively and cannot be done over the
Ethernet/serial port, but only when physically present in front of the IED. In the event of losing all passwords (if the
Administrator forgets their password) the user could reset the IED to default passwords, following the procedure
below:
1. User navigates to Security Code cell in SECURITY CONFIG column
2. To prevent accidental reading of the IED Security Code, the cell will initially display a warning message:

PRESS ENTER TO
READ SEC. CODE

3. Press Enter to read the Security Code.


4. User sends an email to the Contact Centre providing the full IED serial number and displayed Security
Code, using a recognisable corporate email account
5. Contact Centre emails the user with the Recovery Password. The recovery password is intended for recovery
only. It is not a replacement password that can be used continually. It can only be used once – for password
recovery.
6. User logs in with the username ADMINISTRATOR and the recovery password in to the Password setting in
SYSTEM DATA column.
7. Then IED will prompt

RESET PASSWORD?
ENTER or CLEAR

P64-TM-EN-1 411
Chapter 17 - Cyber-Security P64

8. Press Enter to continue the reset procedure


9. If the recovery password successfully validates, the default passwords are restored for each access level for
Device authentication.
10. Change Auth. Method setting to Server + Device if applicable.

Note:
Restoring passwords to defaults does not affect any other settings and does not provoke reboot of the IED. The protection
and control functions of the IED are always maintained.

17.7.11.3 ACCESS LEVEL DDBS


The current level of access for each interface is available for use in the Programmable Scheme Logic (PSL) as
these DDB signals:
● HMI Access Lvl 1
● HMI Access Lvl 2
● FPort AccessLvl1
● FPort AccessLvl2
● RPrt1 AccessLvl1
● RPrt1 AccessLvl2
● RPrt2 AccessLvl1
● RPrt2 AccessLvl2

Each pair of DDB signals indicates the access level as follows:


● Level 1 off, Level 2 off = 0
● Level 1 on, Level 2 off = 1
● Level 1 off, Level 2 on = 2
● Level 1 on, Level 2 on = 3

KEY:
HMI = Human Machine Interface
(Front Panel User Interface)
FPort = Front Port
RPrt = Rear Port
Lvl = Level

17.7.12 PORT HARDENING: PHYSICAL PORTS


It is possible to disable unused physical ports. Enabling/Disabling of physical ports can be done either via the Front
Panel or by sending the modified settings to the IED. These settings are under the PORT HARDENING: PHYSICAL
PORTS Section of SECURITY CONFIG column. A user with SECADM role is needed to perform this action. This
action cannot be done via the Supervise Device dialog box using MiCOM S1 Agile.
The following ports can be disabled, depending on the model.
● Front Port (Front Port setting)
● Rear Port 1 (Rear Port 1 setting)
● Rear Port 2 (Rear Port 2 setting)
● Ethernet Network Port 1 (Network Port 1 Setting)
● Ethernet Network Port 2 (Network Port 2 Setting)

412 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

17.7.13 PORT HARDENING: LOGICAL PORTS (PROTOCOLS)


It is possible to disable unused logical ports. Enabling/Disabling of logical ports can be done either via the Front
Panel or via sending the modified settings to the IED. These settings are under the PORT HARDENING: LOGICAL
PORTS Section of the SECURITY CONFIG column. A user with SECADM role is needed to perform this action,
This action cannot be done via the Supervise Device dialog box using MiCOM S1 Agile.
The following NIC protocols can be disabled:
● Courier Tunnel (for S1 Agile remote connection over Ethernet)
● IEC 61850
● SNTP
● PTP
● SNMP
● RADIUS
● SYSLOG

17.7.14 SERVICE (PROTOCOL) MAPPING: ETHERNET NETWORK PORTS 1 AND 2


This section details which of the Ethernet protocols are available on each of Network Port 1 and Network Port 2,
and whether these are configurable or fixed mappings. Settings for the configurable service mappings are under the
PORT HARDENING: SERVICE MAP section of the SECURITY CONFIG column.

Service Network Port 1 Network Port 2 Fixed/Configurable Setting


IEC 61850 No Yes Fixed to NP2.
SNTP No Yes Fixed to NP2.
PTP No Yes Fixed to NP2.
SSH (for S1 Agile) Yes - only one port at a Yes - only one port at a Configurable - NP1 or Courier Tunnel
time time NP2
SNMP Yes - only one port at a Yes - only one port at a Configurable - NP1 or SNMP
time time NP2
RADIUS Yes - only one port at a Yes - only one port at a Configurable - NP1 or RADIUS
time time NP2
Syslog Yes - only one port at a Yes - only one port at a Configurable - NP1 or SYSLOG
time time NP2

17.7.15 SUPERVISE DEVICE DIALOG BOX


Role Name

Supervise Device None


VIEWER OPERATOR ENGINEER INSTALLER SECADM SECAUD RBACMNT
Logged

Active Group X X X

Reset Cell X

Breakers X

Device Address X X X

Date and Time X X X

Bypass Options X

P64-TM-EN-1 413
Chapter 17 - Cyber-Security P64

Role Name

Supervise Device None


VIEWER OPERATOR ENGINEER INSTALLER SECADM SECAUD RBACMNT
Logged

Active MCL Bank X X

Device User
X X
Management
Own Password
X X X X X X X
Change
RADIUS Secret X

SNMP Security X

Clear Records X

Restore Defaults X X

Restore Security
Settings X

SSH Client
Passcode X

17.7.16 SECURE FIRMWARE UPGRADE


IEC 62351-8:2020 has defined a specific INSTALLER Role which can do firmware upgrades on the IEDs. The
default users in the Device Authentication does not have any users with the INSTALLER Role. If a requirement
exists to upgrade the Firmware of the IED, then the following mandatory steps must be taken before starting the
firmware update:
● Using MiCOM S1 Agile, create a new user having the INSTALLER Role
● Using MiCOM S1 Agile, log into the device using the user having the INSTALLER Role. Change the default
password
● Use the Firmware Download Tool and log into the IED, using the newly created user and changed password
● Once these steps are done, the firmware update process can continue.

The device supports Secure Firmware Update. The firmware files are checked for validity prior to updating of the
IED. The main steps in the secure firmware update process are as follows:
● The ‘PX40 Download and Calibration’ firmware tool opens the secure firmware ZIP file and extracts its
contents [Compressed Images and Signatures].
● The ‘PX40 Download and Calibration’ firmware tool transfers the firmware files [Compressed Images and
Signatures] to IED Main CPU Board.
● IED validates the Compressed Images and extracts them.
● After successful validation, only then will the settings be cleared.
● In case of validation failure, IED will display the ERROR CODE and after that, the user can reboot the relay to
its previous state.
● IED updates it Main CPU Board, Co-processor Board and Ethernet Board storage and verifies it.
● Finally, the Main CPU Board initiates an IED reboot.

Key steps in this process will be logged in the security events - see the Security Event Management section of this
chapter for further details.

414 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Any firmware upgrade should be organised through the GE Vernova Grid Automation After Sales Service
departments, or a regional Local Service Centre. The firmware upgrade should normally be performed by GE
Vernova personnel, or by suitably prepared and competent persons after instruction from GE Vernova personnel. A
separate MiCOM P40 firmware download procedure guide is available.

Note:
It is not possible to update the firmware on the IED which is under Bypass mode.

Note:
During the firmware update, only the security events file is retained - all other configuration and record files are erased during
a firmware upgrade.

P64-TM-EN-1 415
Chapter 17 - Cyber-Security P64

17.8 SNMP CONFIGURATION


You configure the SNMP interface using the HMI panel or using the SNMP Security option in the Supervise Device
dialog box by a user with SECADM role. Two different versions are available; SNMPv2c and SNMPv3:
To enable the SNMP interface:
1. Select the SECURITY CONFIG column and scroll to the SNMP PARAMETERS heading
2. You can select either v2C, V3 or both. Selecting None will disable the main processor SNMP interface.

SNMP Trap Configuration


SNMP traps allow for unsolicited reporting between the IED and up to two SNMP managers with unique IP
addresses. The device MIB details what information can be reported using Traps. To configure the SNMP Traps:
1. Move down to the cell Trap Dest. IP 1 and enter the IP address of the first destination SNMP manager.
Setting this cell to 0.0.0.0 disables the first Trap interface.
2. Move down to the cell Trap Dest. IP 2 and enter the IP address of the second destination SNMP manager.
Setting this cell to 0.0.0.0 disables the Second Trap interface.

SNMP V3 Security Configuration


SNMPv3 provides a higher level of security via authentication and privacy protocols. The IED adopts a secure
SNMPv3 implementation with a user-based security model (USM).
Authentication is used to check the identity of users, privacy allows for encryption of SNMP messages. Both are
optional, however you must enable authentication in order to enable privacy. To configure these security options:
1. If SNMPv3 has been enabled, set the Security Level setting. There are three levels; without authentication
and without privacy (noAuthNoPriv), with authentication but without privacy (authNoPriv), and with
authentication and with privacy (authPriv).
2. If Authentication is enabled, use the Auth Protocol setting to select the authentication type. There are two
options: HMAC-MD5-96 or HMAC-SHA-96.
3. Using the Auth Password setting, enter the password (up to 20 characters) to be used by the IED for
authentication.
4. Using the Auth Protocol setting, select one of the two available mechanisms for encryption of messages to
be used by the IED (CBC-DES or CFB-AES128).
5. If privacy is enabled, use the Encrypt Password setting to set the encryption password (up to 20 characters)
that will be used by the IED for encryption.

Note:
When setting the SNMP browser for RBAC compatible relays, the Context Name should be ‘px4x’.

SNMP V2C Security Configuration


SNMPv2c implements authentication between the master and agent using a parameter called the Community
Name. This is effectively the password but it is not encrypted during transmission (this makes it inappropriate for
some scenarios in which case version 3 should be used instead). To configure the SNMP 2c security:
1. If SNMPv2c has been enabled, use the Community Name setting to set the password that will be used by
the IED and SNMP manager for authentication. This may be between one and 8 characters.

416 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

17.9 RETURNING THE IED TO FACTORY


MiCOM P40 5th Generation products provide enhanced security, and there is no mechanism to bypass the
implemented user management. In the event that the IED is returned to the factory for repair or technical analysis,
to facilitate the Engineers gaining access to the configuration and stored records in the IED, it is proposed that the
IED is returned to the factory with one of the following options:
● Bypass enabled on the front port
● A new user with all Roles is created and left with a default password. If the details of this user are passed to
the factory, the IED can be logged in after changing the default password. If the newly created user’s
password has been modified, it will be required that the modified password is provided

P64-TM-EN-1 417
Chapter 17 - Cyber-Security P64

17.10 SECURITY EVENT MANAGEMENT


To implement NERC-compliant cyber-security, a range of security events are logged by the IED in three separate
methods:
● In the Security Events file (security audit log) - a Courier events file that can be extracted and viewed by
MiCOM S1 Agile
● As syslog events
● As SNMP events (traps)

17.10.1 SECURITY EVENTS: COURIER


The P40 supports the IEC 62351-14 format of security event messages. These are logged into a separate security
audio log file named "Security events" that can be extracted and viewed by MiCOM S1 Agile, in addition to the
operational events file. The maximum number of security events is 2048.
IEC
IEC 62443-4 IEC 62351-14 IEC 62351-14 ID /
Event 62351-14 Text Extra Info
Category Mnemonic Private ID
Severity
SECUR_EVT_PW_SE 62443- Info USER_PW_ IEC 62351-14:1.31 User Password
T_NON_COMPLIANT AUDIT_LOG CHANGE_ change failed -
FAIL_POLICY policy check
failed
SECUR_EVT_PW_ 62443- Notice USER_PW_ IEC 62351-14:1.25 User password Interface
MODIFIED CONFIG_CHAN CHANGE_OK changed
GE successfully
SECUR_EVT_PW_ 62443- Notice LOCK_USER_ IEC 62351-14:1.7 User locked - Interface
ENTRY_NOW_ ACCESS_CON WRONG_CR Wrong
BLOCKED TROL credentials
SECUR_EVT_PW_ 62443- Notice - 2910-MiCP40-001 User unlocked Interface
ENTRY_UNBLOCKED ACCESS_CON
TROL
SECUR_EVT_PW_ 62443- Notice - 2910-MiCP40-002 Log-in attempt Interface
ENTERED_WHILE_ ACCESS_CON when user is
BLOCKED TROL locked
SECUR_EVT_INVALID 62443- Notice LOGIN_FAIL_ IEC 62351-14:1.3 Log-in failed - Interface
_PW_ENTERED ACCESS_CON WRONG_ CR Wrong
TROL credentials
SECUR_EVT_PW_ 62443- error LOGIN_FAIL_ IEC 62351-14:1.4 Log-in failed - Interface
TIMED_OUT ACCESS_CON CRED_ credentials
TROL EXPIRE expired.
SECUR_EVT_ 62443- Notice - 2910-MiCP40-004 Recovery Interface
RECOVERY_PW_ ACCESS_CON password entered
ENTERED TROL
SECUR_EVT_IED_SE 62443- Info - 2910-MiCP40-005 Security Code Interface
C_CODE_READ AUDIT_LOG read
SECUR_EVT_IED_SE 62443- Info - 2910-MiCP40-006 Security Code Interface
C_CODE_TMR_ AUDIT_LOG Timer expired
EXPIRED
SECUR_EVT_PORT_ 62443- Notice - 2910-MiCP40-007 Port Disabled Interface
DISABLED CONFIG_CHAN
GE
SECUR_EVT_PORT_ 62443- Notice - 2910-MiCP40-008 Port Enabled Interface, Port
ENABLED CONFIG_CHAN number
GE

418 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

IEC
IEC 62443-4 IEC 62351-14 IEC 62351-14 ID /
Event 62351-14 Text Extra Info
Category Mnemonic Private ID
Severity
SECUR_EVT_PSL_ 62443- Notice - 2910-MiCP40-009 PSL Settings Interface, Port
SETTINGS_ CONFIG_CHAN downloaded to number
DOWNLOADED GE device
SECUR_EVT_DNP_ 62443- Notice - 2910-MiCP40-010 DNP Settings Interface,
SETTINGS_ CONFIG_CHAN downloaded to Group number
DOWNLOADED GE device
SECUR_EVT_TRACE_ 62443- Notice - 2910-MiCP40-011 TRACE Data Interface
DATA_DOWNLOADED CONFIG_CHAN downloaded to
GE device
SECUR_EVT_61850_ 62443- Notice - 2910-MiCP40-012 IEC61850 Config Interface
CONFIG_ CONFIG_CHAN downloaded to
DOWNLOADED GE device
SECUR_EVT_USER_ 62443- Notice - 2910-MiCP40-013 User Curves Interface
CURVES_ CONFIG_CHAN downloaded to
DOWNLOADED GE device
SECUR_EVT_SETTIN 62443- Notice - 2910-MiCP40-014 Setting Group Interface,
G_GRP_ CONFIG_CHAN downloaded to Curve number
DOWNLOADED GE device
SECUR_EVT_DR_ 62443- Notice - 2910-MiCP40-015 DR Settings Interface,
SETTINGS_ CONFIG_CHAN downloaded to Group number
DOWNLOADED GE device
SECUR_EVT_PSL_ 62443- Notice - 2910-MiCP40-016 PSL Settings Interface
SETTINGS_ BACKUP_REST uploaded from
UPLOADED ORE device
SECUR_EVT_DNP_ 62443- Notice - 2910-MiCP40-017 DNP Settings Interface,
SETTINGS_ BACKUP_REST uploaded from Group number
UPLOADED ORE device
SECUR_EVT_TRACE_ 62443- Notice - 2910-MiCP40-018 TRACE Data Interface
DATA_UPLOADED BACKUP_REST uploaded from
ORE device
SECUR_EVT_61850_ 62443- Notice - 2910-MiCP40-019 IEC61850 Config Interface
CONFIG_UPLOADED BACKUP_REST uploaded from
ORE device
SECUR_EVT_USER_ 62443- Notice - 2910-MiCP40-020 User Curves Interface
CURVES_UPLOADED BACKUP_REST uploaded from
ORE device
SECUR_EVT_PSL_ 62443- Notice - 2910-MiCP40-021 PSL Config Interface,
CONFIG_UPLOADED BACKUP_REST uploaded from Curve number
ORE device
SECUR_EVT_ 62443- Notice - 2910-MiCP40-022 Settings Interface,
SETTINGS_ BACKUP_REST uploaded from Group number
UPLOADED ORE device
SECUR_EVT_CS_ 62443- Notice - 2910-MiCP40-023 Control & Support Interface
SETTINGS_CHANGED CONFIG_CHAN settings changed
GE
SECUR_EVT_DR_ 62443- Notice - 2910-MiCP40-024 Disturbance Interface
SETTINGS_CHANGED CONFIG_CHAN Record Settings
GE changed
SECUR_EVT_ 62443- Notice - 2910-MiCP40-025 Setting Group Interface
SETTING_GROUP_ CONFIG_CHAN changed
CHANGED GE

P64-TM-EN-1 419
Chapter 17 - Cyber-Security P64

IEC
IEC 62443-4 IEC 62351-14 IEC 62351-14 ID /
Event 62351-14 Text Extra Info
Category Mnemonic Private ID
Severity
SECUR_EVT_ 62443- Notice - 2910-MiCP40-026 Default Settings Interface,
DEFAULT_SETTINGS_ BACKUP_REST restored Group number
RESTORED ORE
SECUR_EVT_ 62443- Notice - 2910-MiCP40-027 Default User Interface
DEFAULT_USRCURVE BACKUP_REST Curve restored
_ RESTORED ORE
SECUR_EVT_POWER 62443- Notice - 2910-MiCP40-028 Device Powered Interface,
_ON CONTROL_ On Curve number
SYSTEM
SECUR_EVT_RADIUS 62443- warning RBAC_NO_ IEC 62351-8:1.3 RADIUS server Interface
_UNAVAIL AUDIT_LOG RADIUS not available

SECUR_EVT_ 62443- Notice - 2910-MiCP40-030 Active user Interface


SESSION_LIMIT AUDIT_LOG sessions limit
reached
SECUR_EVT_SLD_ 62443- Notice - 2910-MiCP40-031 SLD File Interface
FILE_DOWNLOADED CONFIG_CHAN downloaded to
GE device
SECUR_EVT_SLD_ 62443- Notice - 2910-MiCP40-032 SLD File Interface
FILE_UPLOADED BACKUP_REST uploaded from
ORE device
SECUR_EVT_RBAC_ 62443- Notice LOGIN_OK IEC-62351-14:1.1 Log-in successful Interface
LOGIN ACCESS_CON
TROL
SECUR_EVT_RBAC_ 62443- Notice LOGOUT_ IEC 62351-14:1.8 Log-out (user Interface
LOGOUT ACCESS_CON USER logged out)
TROL
Bypass mode 62443- Notice - 2910-MiCP40-033 Bypass Mode Interface
Activated ACCESS_CON Activated
TROL
Bypass mode 62443- Notice - 2910-MiCP40-034 Bypass Mode Interface
Deactivated ACCESS_CON Deactivated
TROL
SECUR_EVT_RADIUS 62443- Notice - 2910-MiCP40-044 RADIUS Secret Interface
_KEY_CHANGED CONFIG_CHAN Key changed
GE
SECUR_SEC_ 62443- Notice - 2910-MiCP40-041 Security settings Interface
SETTINGS_ BACKUP_REST restored
RESTORED ORE
Switch to Golden 62443- Notice - 2910-MiCP40-045 Device switching Interface
Image AUDIT_LOG to Firmware
update mode
FIRMWARE_ 62443- Notice - 2910-MiCP40-035 Firmware Digital Interface
VALIDATION_ AUDIT_LOG Signature check
SUCCESS successful
FIRMWARE_ 62443- warning - 2910-MiCP40-036 Firmware Digital Interface
VALIDATION_FAIL AUDIT_LOG Signature check
failed
Firmware update 62443- Notice - 2910-MiCP40-046 Firmware update Interface
process started AUDIT_LOG initiated

420 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

IEC
IEC 62443-4 IEC 62351-14 IEC 62351-14 ID /
Event 62351-14 Text Extra Info
Category Mnemonic Private ID
Severity
Fail to receive firmware 62443- Warning - 2910-MiCP40-047 Firmware files Interface
files AUDIT_LOG transfer failed

Fail to update firmware 62443- Warning - 2910-MiCP40-048 Firmware update Interface


AUDIT_LOG failed

Firmware update 62443- Notice - 2910-MiCP40-049 Firmware update Interface,


process success CONFIG_CHAN successful Previous FW
GE version,
Latest FW
version
Serial&Model number 62443- Notice - 2910-MiCP40-050 Serial/Model
update success AUDIT_LOG number update
successful
Serial&Model number 62443- Warning - 2910-MiCP40-051 Serial/Model Interface
update fail AUDIT_LOG number update
failed
NP1 MAC update 62443- Notice - 2910-MiCP40-052 NP1 MAC Interface
success AUDIT_LOG address update
successful
NP1 MAC update fail 62443- Warning - 2910-MiCP40-053 NP1 MAC Interface
AUDIT_LOG address update
failed
NP2 MAC update 62443- Notice - 2910-MiCP40-054 NP2 MAC Interface
success AUDIT_LOG address update
successful
NP2 MAC update fail 62443- Warning - 2910-MiCP40-055 NP2 MAC Interface
AUDIT_LOG address update
failed
Fallback to Device 62443- Warning - 2910-MiCP40-056 Fallback to Interface
Authentication ACCESS_CON Device
TROL Authentication
User logged out due to 62443- Notice LOGOUT_ IEC 62351-14:1.9 Log-out by user Interface
inactivity timeout ACCESS_CON TIMEOUT inactivity
TROL (timeout).
Security events upload 62443- Notice - 2910-MiCP40-042 Security Events Interface
AUDIT_LOG uploaded from
device
SSH Passcode change 62443- Notice - 2910-MiCP40-057 SSH pass code Interface
CONFIG_CHAN change
GE
SSH Client 62443- Warning - 2910-MiCP40-059 Failed client Interface
Authentication Fail ACCESS_CON authentication
TROL
SSH Client 62443- Notice - 2910-MiCP40-058 Successful client Interface
Authentication Success ACCESS_CON authentication
TROL
New User added 62443- Notice USER_ IEC 62351-14:2.15 User account Interface
CONFIG_CHAN ACCNT_ created
GE CREATE_OK successfully.

P64-TM-EN-1 421
Chapter 17 - Cyber-Security P64

IEC
IEC 62443-4 IEC 62351-14 IEC 62351-14 ID /
Event 62351-14 Text Extra Info
Category Mnemonic Private ID
Severity
User deleted 62443- Notice USER_ IEC 62351-14:2.21 User account Interface
CONFIG_CHAN ACCNT_DEL_ deleted
GE OK successfully.
User role change 62443- Notice USER_ IEC 62351-14:2.11 Permission Interface
CONFIG_CHAN PERMISSION_ changed
GE CHANGE_OK successfully.
User name change 62443- Notice - 2910-MiCP40-060 User renamed Interface
CONFIG_CHAN successfully
GE

Where the Interface values in "Extra Info" parameter are: "UI", "FP", "RP1", "RP2", "NET", "HMI".

17.10.2 SECURITY EVENTS: SYSLOG


Security events are also logged to a remote server and are based on Syslog [RFC 5424].
All login and logout attempts from local and central authentication, whether successful or failed, are logged. The
contents of each successful or failed, login and logout security event include a specific username.
The security log cannot be cleared by any of the available roles.
The contents of each login and/or logout security event include the relevant interface. The following interfaces are
supported:

Interface Abbr.
Front Port FP
Rear Port 1 RP1
Rear Port 2 RP2
Network Port 1 or 2 NET
Front Panel UI

The following events are available to be logged to the syslog server:

Security Event SNMP Trap Text

SECUR_EVT_PW_SET_NON_COMPLIANT User Password change failed - policy check failed

SECUR_EVT_PW_MODIFIED User password changed successfully

SECUR_EVT_PW_ENTRY_NOW_BLOCKED User locked – Wrong credentials

SECUR_EVT_PW_ENTRY_UNBLOCKED User unlocked

SECUR_EVT_PW_ENTERED_WHILE_BLOCKED Log-in attempt when user is locked

SECUR_EVT_INVALID_PW_ENTERED Log-in failed - Wrong credentials

SECUR_EVT_PW_TIMED_OUT Log-in failed - credentials expired.

SECUR_EVT_RECOVERY_PW_ENTERED Recovery password entered

SECUR_EVT_IED_SEC_CODE_READ Security Code read

422 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Security Event SNMP Trap Text

SECUR_EVT_IED_SEC_CODE_TMR_EXPIRED Security Code Timer expired

SECUR_EVT_PORT_DISABLED Port Disabled

SECUR_EVT_PORT_ENABLED Port Enabled

SECUR_EVT_PSL_SETTINGS_DOWNLOADED PSL Settings downloaded to device

SECUR_EVT_DNP_SETTINGS_DOWNLOADED DNP Settings downloaded to device

SECUR_EVT_61850_CONFIG_DOWNLOADED IEC61850 Config downloaded to device

SECUR_EVT_USER_CURVES_DOWNLOADED User Curves downloaded to device

SECUR_EVT_SETTING_GRP_DOWNLOADED Setting Group downloaded to device

SECUR_EVT_DR_SETTINGS_DOWNLOADED DR Settings downloaded to device

SECUR_EVT_PSL_SETTINGS_UPLOADED PSL Settings uploaded from device

SECUR_EVT_DNP_SETTINGS_UPLOADED DNP Settings uploaded from device

SECUR_EVT_61850_CONFIG_UPLOADED IEC61850 Config uploaded from device

SECUR_EVT_USER_CURVES_UPLOADED User Curves uploaded from device

SECUR_EVT_PSL_CONFIG_UPLOADED PSL Config uploaded from device

SECUR_EVT_SETTINGS_UPLOADED Settings uploaded from device

SECUR_EVT_CS_SETTINGS_CHANGED Control & Support settings changed

SECUR_EVT_DR_SETTINGS_CHANGED Disturbance Record Settings changed

SECUR_EVT_SETTING_GROUP_CHANGED Setting Group changed

SECUR_EVT_DEFAULT_SETTINGS_RESTORED Default Settings restored

SECUR_EVT_DEFAULT_USRCURVE_RESTORED Default User Curve restored

SECUR_EVT_RADIUS_UNAVAIL RADIUS server not available

SECUR_EVT_SESSION_LIMIT Active user sessions limit reached

SECUR_EVT_SLD_FILE_DOWNLOADED SLD File downloaded to device

SECUR_EVT_SLD_FILE_UPLOADED SLD File uploaded from device

SECUR_EVT_RBAC_LOGIN Log-in successful

SECUR_EVT_RBAC_LOGOUT Log-out (user logged out)

Bypass mode Activated Bypass Mode Activated

Bypass mode Deactivated Bypass Mode Deactivated

P64-TM-EN-1 423
Chapter 17 - Cyber-Security P64

Security Event SNMP Trap Text

RADIUS Secret Key changed RADIUS Secret Key changed

SECUR_EVT_SEC_SETTINGS_RESTORED Security settings restored

Switch to Golden Image Device switching to Firmware update mode

Fallback to Device Authentication Fallback to Device Authentication

User logged out due to inactivity timeout. Log-out by user inactivity (timeout)

Security events upload Security Events uploaded from device

SSH Passcode change SSH pass code change

SSH Client Authentication Fail Failed client authentication

SSH Client Authentication Success Successful client authentication

New User added User account created successfully.

User deleted User account deleted successfully.

User role change Permission changed successfully.

17.10.3 SYSLOG CLIENT


The IED supports security event reporting through the Syslog protocol for supporting Security Information Event
Management (SIEM) systems for centralized cyber security Monitoring over UDP protocol.
The IED is a Syslog client that supports two Syslog servers. The following settings are available in the SECURITY
CONFIG. column.
User Role
Setting Name Description Min Max Default Units
Required
SysLog Pri IP The IP address of the target Syslog 0.0.0.0 223.255.255.254 0.0.0.0 - SECADM
server (Primary)
SysLog Sec IP The IP address of the target Syslog 0.0.0.0 223.255.255.254 0.0.0.0 - SECADM
server (Secondary)
SysLog Port The UDP port number of the target 1 65535 514 - SECADM
Syslog server

17.10.4 SYSLOG FUNCTIONALITY


P40 supports IEC 62351-14 based cyber security event monitoring and is based on Syslog [RFC 5424].
Sample Syslog messages are shown below:

Event Access Method Syslog Message (As from Syslog Server)


IED Powered On UI 5492, 2024-06-12T19:18:28.982Z, 423991K,
GE_RE_P543_______AB0_o, MiCP40_POWER_ON, 2910-MiCP40-028,
notice, IECCTRLSYS, Device Powered On, UI
ADMIN1 Log-in successful FP 5523, 2024-06-12T20:04:26.851Z, 423991K,
GE_RE_P543_______AB0_o, LOGIN_OK, IEC 62351-14:1.1, notice,
IECACCCTRL, ADMIN1, SECAM, Log-in successful, FP

424 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Event Access Method Syslog Message (As from Syslog Server)


SSH Successful client NET 5460, 2024-06-12T18:04:45.359Z, 423991J, GE_RE_P546_______AB0_o,
authentication (S1 Agile) MiCP40_SSH_CLIENT_AUTH_SUCCESS, 2910-MiCP40-058, notice,
IECACCCTRL, Successful client authentication, NET
Firmware update successful FP 5476, 2024-06-12T19:18:19.004Z, 423991K,
GE_RE_P543_______AB0_o, MiCP40_FW_UPDATE_SUCCESS, 2910-
MiCP40-049, notice, IECCONFCHG, Firmware update successful, FP,
P546_______AB0_o to P543_______AB0_o

17.10.5 SECURITY EVENTS: SNMP


Security events can also be sent as SNMP traps to a remote SNMP server. These traps are supported in both V2c
and V3 versions of SNMP. For further information related to the full SNMP interface in P40, refer to the SNMP
section in the COMMUNICATIONS chapter.
The format of the SNMP traps for security events consists of three parts as described below:
"Event Description, Username, Interface"
● Event Description: Short description of the alarm, same as the description present in Security event.
● Username: User associated with the event, provided only when Username is available for the Security event.
● Interface: Interface on which Security event has occurred, same as the interface information present in
Security event.
The following events are available to be logged to the SNMP server:

Security Event SNMP Trap Text

SECUR_EVT_PW_SET_NON_COMPLIANT User Password change failed - policy check failed

SECUR_EVT_PW_MODIFIED User password changed successfully

SECUR_EVT_PW_ENTRY_NOW_BLOCKED User locked – Wrong credentials

SECUR_EVT_PW_ENTRY_UNBLOCKED User unlocked

SECUR_EVT_PW_ENTERED_WHILE_BLOCKED Log-in attempt when user is locked

SECUR_EVT_INVALID_PW_ENTERED Log-in failed - Wrong credentials

SECUR_EVT_PW_TIMED_OUT Log-in failed - credentials expired.

SECUR_EVT_RECOVERY_PW_ENTERED Recovery password entered

SECUR_EVT_IED_SEC_CODE_READ Security Code read

SECUR_EVT_IED_SEC_CODE_TMR_EXPIRED Security Code Timer expired

SECUR_EVT_PORT_DISABLED Port Disabled

SECUR_EVT_PORT_ENABLED Port Enabled

SECUR_EVT_PSL_SETTINGS_DOWNLOADED PSL Settings downloaded to device

SECUR_EVT_DNP_SETTINGS_DOWNLOADED DNP Settings downloaded to device

SECUR_EVT_61850_CONFIG_DOWNLOADED IEC61850 Config downloaded to device

SECUR_EVT_USER_CURVES_DOWNLOADED User Curves downloaded to device

P64-TM-EN-1 425
Chapter 17 - Cyber-Security P64

Security Event SNMP Trap Text

SECUR_EVT_SETTING_GRP_DOWNLOADED Setting Group downloaded to device

SECUR_EVT_DR_SETTINGS_DOWNLOADED DR Settings downloaded to device

SECUR_EVT_PSL_SETTINGS_UPLOADED PSL Settings uploaded from device

SECUR_EVT_DNP_SETTINGS_UPLOADED DNP Settings uploaded from device

SECUR_EVT_61850_CONFIG_UPLOADED IEC61850 Config uploaded from device

SECUR_EVT_USER_CURVES_UPLOADED User Curves uploaded from device

SECUR_EVT_PSL_CONFIG_UPLOADED PSL Config uploaded from device

SECUR_EVT_SETTINGS_UPLOADED Settings uploaded from device

SECUR_EVT_CS_SETTINGS_CHANGED Control & Support settings changed

SECUR_EVT_DR_SETTINGS_CHANGED Disturbance Record Settings changed

SECUR_EVT_SETTING_GROUP_CHANGED Setting Group changed

SECUR_EVT_DEFAULT_SETTINGS_RESTORED Default Settings restored

SECUR_EVT_DEFAULT_USRCURVE_RESTORED Default User Curve restored

SECUR_EVT_POWER_ON Device Powered On

SECUR_EVT_RADIUS_UNAVAIL RADIUS server not available

SECUR_EVT_SESSION_LIMIT Active user sessions limit reached

SECUR_EVT_SLD_FILE_DOWNLOADED SLD File downloaded to device

SECUR_EVT_SLD_FILE_UPLOADED SLD File uploaded from device

SECUR_EVT_RBAC_LOGIN Log-in successful

SECUR_EVT_RBAC_LOGOUT Log-out (user logged out)

Bypass mode Activated Bypass Mode Activated

Bypass mode Deactivated Bypass Mode Deactivated

RADIUS Secret Key changed RADIUS Secret Key changed

SECUR_EVT_SEC_SETTINGS_RESTORED Security settings restored

Switch to Golden Image Device switching to Firmware update mode

Fallback to Device Authentication Fallback to Device Authentication

User logged out due to inactivity timeout. Log-out by user inactivity (timeout)

Security events upload Security Events uploaded from device

426 P64-TM-EN-1
P64 Chapter 17 - Cyber-Security

Security Event SNMP Trap Text

SSH Passcode change SSH pass code change

SSH Client Authentication Fail Failed client authentication

SSH Client Authentication Success Successful client authentication

New User added User account created successfully.

User deleted User account deleted successfully.

User role change Permission changed successfully.

P64-TM-EN-1 427
Chapter 17 - Cyber-Security P64

428 P64-TM-EN-1
CHAPTER 18

INSTALLATION
Chapter 18 - Installation P64

18.1 CHAPTER OVERVIEW


This chapter provides information about installing the product.
This chapter contains the following sections:
Chapter Overview 430
Handling the Goods 431
Mounting the Device 432
Cables and Connectors 435
Case Dimensions 440

430 P64-TM-EN-1
P64 Chapter 18 - Installation

18.2 HANDLING THE GOODS


Our products are of robust construction but require careful treatment before installation on site. This section
discusses the requirements for receiving and unpacking the goods, as well as associated considerations regarding
product care and personal safety.

Caution:
Before lifting or moving the equipment you should be familiar with the Safety
Information chapter of this manual.

18.2.1 RECEIPT OF THE GOODS


On receipt, ensure the correct product has been delivered. Unpack the product immediately to ensure there has
been no external damage in transit. If the product has been damaged, make a claim to the transport contractor and
notify us promptly.
For products not intended for immediate installation, repack them in their original delivery packaging.

18.2.2 UNPACKING THE GOODS


When unpacking and installing the product, take care not to damage any of the parts and make sure that additional
components are not accidentally left in the packing or lost. Do not discard any CDROMs or technical documentation
(where included). These should accompany the unit to its destination substation and put in a dedicated place.
The site should be well lit to aid inspection, clean, dry and reasonably free from dust and excessive vibration. This
particularly applies where installation is being carried out at the same time as construction work.

18.2.3 STORING THE GOODS


If the unit is not installed immediately, store it in a place free from dust and moisture in its original packaging. Keep
any dehumidifier bags included in the packing. The dehumidifier crystals lose their efficiency if the bag is exposed to
ambient conditions. Restore the crystals before replacing it in the carton. Ideally regeneration should be carried out
in a ventilating, circulating oven at about 115°C. Bags should be placed on flat racks and spaced to allow circulation
around them. The time taken for regeneration will depend on the size of the bag. If a ventilating, circulating oven is
not available, when using an ordinary oven, open the door on a regular basis to let out the steam given off by the
regenerating silica gel.
On subsequent unpacking, make sure that any dust on the carton does not fall inside. Avoid storing in locations of
high humidity. In locations of high humidity the packaging may become impregnated with moisture and the
dehumidifier crystals will lose their efficiency.
The device can be stored between –25º to +70ºC for unlimited periods or between -40°C to + 85°C for up to 96
hours (see technical specifications).
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energised state once a year,
for one hour continuously.

18.2.4 DISMANTLING THE GOODS


If you need to dismantle the device, always observe standard ESD (Electrostatic Discharge) precautions. The
minimum precautions to be followed are as follows:
● Use an antistatic wrist band earthed to a suitable earthing point.
● Avoid touching the electronic components and PCBs.

P64-TM-EN-1 431
Chapter 18 - Installation P64

18.3 MOUNTING THE DEVICE


The products are dispatched either individually or as part of a panel or rack assembly.
Individual products are normally supplied with an outline diagram showing the dimensions for panel cut-outs and
hole centres.
The products are designed so the fixing holes in the mounting flanges are only accessible when the access covers
are open.
If you use a P991 or MMLG test block with the product, when viewed from the front, position the test block on the
right-hand side of the associated product. This minimises the wiring between the product and test block, and allows
the correct test block to be easily identified during commissioning and maintenance tests.

18.3.1 FLUSH PANEL MOUNTING


Panel-mounted devices are flush mounted into panels using M4 SEMS Taptite self-tapping screws with captive
3 mm thick washers (also known as a SEMS unit).

Caution:
Do not use conventional self-tapping screws, because they have larger heads and
could damage the faceplate.

Alternatively, you can use tapped holes if the panel has a minimum thickness of 2.5 mm.
For applications where the product needs to be semi-projection or projection mounted, a range of collars are
available.
If several products are mounted in a single cut-out in the panel, mechanically group them horizontally or vertically
into rigid assemblies before mounting in the panel.

Caution:
Do not fasten products with pop rivets because this makes them difficult to remove if
repair becomes necessary.

18.3.2 RACK MOUNTING


Panel-mounted variants can also be rack mounted using single-tier rack frames (our part number FX0021 001), as
shown in the figure below. These frames are designed with dimensions in accordance with IEC 60297 and are
supplied pre-assembled ready to use. On a standard 483 mm (19 inch) rack this enables combinations of case
widths up to a total equivalent of size 80TE to be mounted side by side.
The two horizontal rails of the rack frame have holes drilled at approximately 26 mm intervals. Attach the products
by their mounting flanges using M4 Taptite self-tapping screws with captive 3 mm thick washers (also known as a
SEMS unit).

Caution:
Risk of damage to the front cover molding. Do not use conventional self-tapping
screws, including those supplied for mounting MiDOS products because they have
slightly larger heads.

Once the tier is complete, the frames are fastened into the racks using mounting angles at each end of the tier.

432 P64-TM-EN-1
P64 Chapter 18 - Installation

Figure 176: Rack mounting of products

Products can be mechanically grouped into single tier (4U) or multi-tier arrangements using the rack frame. This
enables schemes using products from different product ranges to be pre-wired together before mounting.
Use blanking plates to fill any empty spaces. The spaces may be used for installing future products or because the
total size is less than 80TE on any tier. Blanking plates can also be used to mount ancillary components. The part
numbers are as follows:

Case size summation Blanking plate part number


5TE GJ2028 001
10TE GJ2028 002
20TE GJ2028 004
40TE GJ2028 008
60TE GJ2028 012

18.3.3 REFURBISHMENT SOLUTIONS


A major advantage of the 5th Generation MiCOM 5th Generation series is the ease in which you can refurbish both
older 5th Generation generation and legacy MBCH/KBCH devices. The P40 5th Generation platform retains form, fit
and function compatibility, compared to older generations, while delivering the latest platform and software. For
example, the 5th Generation line differential protection is fully compatible with all previous 5th Generation versions
and maintains pin to pin refurbishment compatibility.

P64-TM-EN-1 433
Chapter 18 - Installation P64

This allows easy upgrade of the protection system with minimum impact, resulting in only a few minutes of
downtime.
To begin the upgrade:
● Take the order code (CORTEC) of the older relay being removed, typically a blue case relay
● Translate to today’s latest GE Vernova MiCOM model, adding Ethernet options if required
● Order the new 5th Generation P40 relay
● Use the S1 Agile toolsuite to extract settings and logic and convert the settings
● Detach the medium duty terminal blocks from your old device, making sure you leave the wiring attached. It is
recommended the CT/VT terminal blocks on the new IED are used during refurbishment
● Carefully examine the terminal blocks to ensure that no physical damage has occurred since installation
● Attach the terminal blocks and wiring from your old device to the new IED. It is recommended to apply rated
current and voltage to the relay CT/VT inputs during secondary injection testing to check the continuity of the
CT/VT terminal block connections to the relay
● Download your converted files
● Test, then return circuit to service. See the Commissioning Instructions chapter for more information on
testing

Please contact us for assistance.

434 P64-TM-EN-1
P64 Chapter 18 - Installation

18.4 CABLES AND CONNECTORS


This section describes the type of wiring and connections that should be used when installing the device. For pin-
out details please refer to the Hardware Design chapter or the wiring diagrams.

Caution:
Before carrying out any work on the equipment you should be familiar with the Safety
Section and the ratings on the equipment’s rating label.

18.4.1 TERMINAL BLOCKS


The device may use one or more of the terminal block types shown in the following diagram. The terminal blocks
are fastened to the rear panel with screws.
● Heavy duty (HD) terminal blocks for CT and VT circuits
● Medium duty (MD) terminal blocks for the power supply, relay outputs and rear communications port
● MiDOS terminal blocks for CT and VT circuits
● RTD/CLIO terminal block for connection to analogue transducers

Figure 177: Terminal block types

MiCOM products are supplied with sufficient M4 screws for making connections to the rear mounted terminal blocks
using ring terminals, with a recommended maximum of two ring terminals per terminal.
If required, M4 90° crimp ring terminals can be supplied in three different sizes depending on wire size. Each type is
available in bags of 100.
Part number Wire size Insulation color
ZB9124 901 0.25 - 1.65 mm2 (22 – 16 AWG) Red
ZB9124 900 1.04 - 2.63 mm2 (16 – 14 AWG) Blue

P64-TM-EN-1 435
Chapter 18 - Installation P64

Note:
IP2x shields and side cover panels may be fitted to provide IP20 ingress protection for MiCOM terminal blocks. The shields
and covers can be attached during installation or retrofitted to upgrade existing installations. The shields are supplied with four
language fitting instructions, publication number: IP2x-TM-4L-n (where n is the current issue number). For more information,
contact your local sales office or our worldwide Contact Centre.

18.4.2 POWER SUPPLY CONNECTIONS


These should be wired with 1.5 mm PVC insulated multi-stranded copper wire terminated with M4 ring terminals.
The wire should have a minimum voltage rating of 300 V RMS.

Caution:
Protect the auxiliary power supply wiring with a maximum 16 A high rupture capacity
(HRC) type NIT or TIA fuse.

18.4.3 EARTH CONNNECTION


Every device must be connected to the cubicle earthing bar using the M4 earth terminal.

Use a wire size of at least 2.5 mm2 terminated with a ring terminal.

Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring
terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced to 2.63
mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each terminated in a
separate ring terminal.
The wire should have a minimum voltage rating of 300 V RMS.

Note:
To prevent any possibility of electrolytic action between brass or copper ground conductors and the rear panel of the product,
precautions should be taken to isolate them from one another. This could be achieved in several ways, including placing a
nickel-plated or insulating washer between the conductor and the product case, or using tinned ring terminals.

18.4.4 CURRENT TRANSFORMERS


Current transformers would generally be wired with 2.5 mm2 PVC insulated multi-stranded copper wire terminated
with M4 ring terminals.

Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring
terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced to 2.63
mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each terminated in a
separate ring terminal.
The wire should have a minimum voltage rating of 300 V RMS.

Caution:
Current transformer circuits must never be fused.

436 P64-TM-EN-1
P64 Chapter 18 - Installation

Note:
If there are CTs present, spring-loaded shorting contacts ensure that the terminals into which the CTs connect are shorted
before the CT contacts are broken.

Note:
For 5A CT secondaries, we recommend using 2 x 2.5 mm2 PVC insulated multi-stranded copper wire.

18.4.5 VOLTAGE TRANSFORMER CONNECTIONS


Voltage transformers should be wired with 2.5 mm2 PVC insulated multi-stranded copper wire terminated with M4
ring terminals.
The wire should have a minimum voltage rating of 300 V RMS.

18.4.6 WATCHDOG CONNECTIONS


These should be wired with 1 mm PVC insulated multi-stranded copper wire terminated with M4 ring terminals.
The wire should have a minimum voltage rating of 300 V RMS.

18.4.7 EIA(RS)485 AND K-BUS CONNECTIONS


For connecting the EIA(RS485) / K-Bus ports, use 2-core screened cable with a maximum total length of 1000 m or
200 nF total cable capacitance.
To guarantee the performance specifications, you must ensure continuity of the screen, when daisy chaining the
connections.
Two-core screened twisted pair cable should be used. It is important to avoid circulating currents, which can cause
noise and interference, especially when the cable runs between buildings. For this reason, the screen should be
continuous and connected to ground at one end only, normally at the master connection point.
The K-Bus signal is a differential signal and there is no signal ground connection. If a signal ground connection is
present in the bus cable then it must be ignored. At no stage should this be connected to the cable's screen or to
the product’s chassis. This is for both safety and noise reasons.
A typical cable specification would be:
● Each core: 16/0.2 mm2 copper conductors, PVC insulated
● Nominal conductor area: 0.5 mm2 per core
● Screen: Overall braid, PVC sheathed

18.4.8 IRIG-B CONNECTION


The IRIG-B input and BNC connector have a characteristic impedance of 50 ohms. We recommend that
connections between the IRIG-B equipment and the product are made using coaxial cable of type RG59LSF with a
halogen free, fire retardant sheath.

18.4.9 OPTO-INPUT CONNECTIONS


These should be wired with 1 mm2 PVC insulated multi-stranded copper wire terminated with M4 ring terminals.
Each opto-input has a selectable preset ½ cycle filter. This makes the input immune to noise induced on the wiring.
This can, however slow down the response. If you need to switch off the ½ cycle filter, either use double pole
switching on the input, or screened twisted cable on the input circuit.

P64-TM-EN-1 437
Chapter 18 - Installation P64

Caution:
Protect the opto-inputs and their wiring with a maximum 16 A high rupture capacity
(HRC) type NIT or TIA fuse.

18.4.10 OUTPUT RELAY CONNECTIONS


These should be wired with 1 mm PVC insulated multi-stranded copper wire terminated with M4 ring terminals.

18.4.11 ETHERNET METALLIC CONNECTIONS


If the device has a metallic Ethernet connection, it can be connected to either a 10Base-T or a 100Base-TX
Ethernet hub. Due to noise sensitivity, we recommend this type of connection only for short distance connections,
ideally where the products and hubs are in the same cubicle. For increased noise immunity, CAT 6 (category 6) STP
(shielded twisted pair) cable and connectors can be used.
The connector for the Ethernet port is a shielded RJ-45. The pin-out is as follows:
Pin Signal name Signal definition
1 TXP Transmit (positive)
2 TXN Transmit (negative)
3 RXP Receive (positive)
4 - Not used
5 - Not used
6 RXN Receive (negative)
7 - Not used
8 - Not used

18.4.12 ETHERNET FIBRE CONNECTIONS


We recommend the use of fibre-optic connections for permanent connections in a substation environment. The
100 Mbps fibre optic port uses type LC connectors (one for Tx and one for Rx), compatible with 50/125 µm or
62.5/125 µm multimode fibres at 1300 nm wavelength.

18.4.13 USB CONNECTION


The IED has a type B USB socket inside the bottom compartment. A standard USB printer cable (type A one end,
type B the other end) can be used to connect a local PC to the IED. This cable is the same as that used for
connecting a printer to a PC.

18.4.14 RTD CONNECTIONS


Resistance Temperature Detector (RTD) inputs use screw clamp connectors. The connection block is situated at
the rear of the IED. It can accept wire sizes from 0.1 mm2 to 1.5 mm2. The connections between the IED and the
RTDs must be made using a screened 3-core cable with a total resistance less than 10 Ω. The cable should have a
minimum voltage rating of 300 V RMS.
A 3-core cable should be used even for 2-wire RTD applications, as it allows for the cable’s resistance to be
removed from the overall resistance measurement. In such cases the third wire is connected to the second wire at
the point where the cable is joined to the RTD.
The screen of each cable must only be earthed (grounded) at one end, preferably at the IED end and must be
continuous. Multiple earthing (grounding) of the screen can cause circulating current to flow along the screen. This
induces noise and is also unsafe.

438 P64-TM-EN-1
P64 Chapter 18 - Installation

You should minimize the noise pick-up in the RTD cables by keeping them close to earthed (grounded) metal
casings and avoid areas of high electromagnetic and radio interference. The RTD cables should not be run adjacent
to or in the same conduit as other high voltage or current cables.
A typical cable specification would be:
● Each core: 7/0.2 mm copper conductors heat resistant PVC insulated
● Nominal conductor area: 0.22 mm2 per core
● Screen: Nickel-plated copper wire braid heat resistant PVC sheathed

The following extract may be useful in defining cable recommendations for the RTDs:
Noise pick up by cables can be categorized into three types:
● Resistive
● Capacitive
● Inductive
Resistive coupling requires an electrical connection to the noise source. Assuming the wire and cable insulation are
in good condition and the junctions are clean, this can be dismissed. Capacitive coupling requires sufficient
capacitance to the noise source. This is a function of the dielectric strength between the signal cable on the noise
source and the power of the noise source. Inductive coupling occurs when the signal cable is adjacent to a wire
carrying the noise or it is exposed to a radiated EMF.
Standard screened cable is normally used to protect against capacitively-coupled noise. However for this to be
effective, the screen should only be bonded to the system ground at one point. Otherwise a current could flow and
the noise would be coupled into the signal wires of the cable. There are different types of screening available, but
the most commonly used are aluminium foil wrap, or tin-copper braid. Foil screens are good for low to medium
frequencies and braid is good for high frequencies. High-fidelity screen cables provide both types.
Protection against inductive coupling requires careful cable routing and magnetic shielding. The latter can be
achieved with steel-armoured cable and steel cable trays. The cable armour must be grounded at both ends so the
EMF of the induced current cancels the field of the noise source and shields the cables conductors from it.
However, the system ground must be designed such that it does not bridge two isolated ground systems. This could
be hazardous and defeat the objectives of the original grounding design. The cable should be laid in the cable trays
as close as possible to the metal of the tray. Under no circumstance should any power cable be in or near to the
tray. Power cables should only cross the signal cables at 90 degrees and never be adjacent to them.
Both the capacitive and inductive screens must be contiguous from the RTD probes to the IED terminals. The best
types of cable are those provided by the RTD manufacturers. These are usually three conductors, known as a triad,
which are screened with foil. Such triad cables are available in armoured forms as well as multi-triad armoured
forms.

18.4.15 CLIO CONNECTIONS


Current Loop Inputs and Outputs (CLIO) use screw clamp connectors. The connection block is situated at the rear
of the IED. It can accept wire sizes from 0.1 mm2 to 1.5 mm2. We recommend screened cable, and it should have a
minimum voltage rating of 300 V RMS.

P64-TM-EN-1 439
Chapter 18 - Installation P64

18.5 CASE DIMENSIONS


Not all products are available in all case sizes.

440 P64-TM-EN-1
P64 Chapter 18 - Installation

18.5.1 CASE DIMENSIONS 40TE


Flush mounting panel.
Panel cut-out details

200 A = Clearance holes


B = Mounting holes
8 off holes Dia.3.4
23.3 155.4

AB BA

168
159

AB BA

10.35 181.3
202
240
Incl. wiring
FRONT VIEW

177 157.5
max.

206 27 SIDE VIEW

Sealing strip

177
(4U)

483 (19" RACK)

Note: If mounting plate is required use flush mounting cut-out dimensions All dimensions in mm.
V01484

Figure 178: 40TE case dimensions

P64-TM-EN-1 441
Chapter 18 - Installation P64

18.5.2 CASE DIMENSIONS 60TE


303.5
FLUSH MOUNTING PANEL CUT-OUT DETAIL

23.25 116.55 142.45 12 OFF HOLES 3.4

159 168

10.3 155.4 129.5 4.5

305.5

240 INCL. WIRING


FRONT VIEW

157.5 MAX
177

309.6 27 SIDE VIEW

MOUNTING SCREWS: M4 x 12 SEM UNIT STEEL THREAD FORMING SCREWS


TERMINAL SCREWS: M4 x 7 BRASS CHEESE HEAD SCREWS WITH LOCKING V01485
WASHERS PROVIDED.

Figure 179: 60TE case dimensions

442 P64-TM-EN-1
P64 Chapter 18 - Installation

18.5.3 CASE DIMENSIONS 80TE


FLUSH MOUNTED PANEL CUT-OUT DETAILS
407.1 74.95 116.55 142.45

159 168

222

62 155.4 129.5 4.5

408.9

240 incl wiring

177 157.5
max

27 SIDE VIEW
413.2
FRONT VIEW

MOUNTING SCREWS: M4 x 12 SEM UNIT STEEL THREAD FORMING SCREWS


TERMINAL SCREWS: M4 x 7 BRASS CHEESE HEAD SCREWS WITH LOCKING V01486
WASHERS PROVIDED.

Figure 180: 80TE case dimensions

P64-TM-EN-1 443
Chapter 18 - Installation P64

444 P64-TM-EN-1
CHAPTER 19

COMMISSIONING INSTRUCTIONS
Chapter 19 - Commissioning Instructions P64

19.1 CHAPTER OVERVIEW


This chapter contains the following sections:
Chapter Overview 446
General Guidelines 447
Commissioning Test Menu 448
Commissioning Equipment 451
Product Checks 453
Setting Checks 463
IEC 61850 Edition 2 Testing 465
Checking the Differential Element 470
Protection Timing Checks 474
Onload Checks 476
Final Checks 478

446 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.2 GENERAL GUIDELINES


GE Vernova IEDs are self-checking devices and will raise an alarm in the unlikely event of a failure. This is why the
commissioning tests are less extensive than those for non-numeric electronic devices or electro-mechanical relays.
To commission the devices, you (the commissioning engineer) do not need to test every function. You need only
verify that the hardware is functioning correctly and that the application-specific software settings have been
applied. You can check the settings by extracting them using the settings application software, or by means of the
front panel interface (HMI panel).
The menu language is user-selectable, so you can change it for commissioning purposes if required.

Note:
Remember to restore the language setting to the customer’s preferred language on completion.

Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or Safety Guide SFTY/4LM as well as the ratings on
the equipment’s rating label.

Warning:
With the exception of the CT shorting contacts check, do not disassemble the
device during commissioning.

P64-TM-EN-1 447
Chapter 19 - Commissioning Instructions P64

19.3 COMMISSIONING TEST MENU


The IED provides several test facilities under the COMMISSION TESTS menu heading. There are menu cells that
allow you to monitor the status of the opto-inputs, output relay contacts, internal Digital Data Bus (DDB) signals and
user-programmable LEDs. This section describes these commissioning test facilities.

19.3.1 OPTO I/P STATUS CELL (OPTO-INPUT STATUS)


This cell can be used to monitor the status of the opto-inputs while they are sequentially energised with a suitable
DC voltage. The cell is a binary string that displays the status of the opto-inputs where '1' means energised and '0'
means de-energised. If you move the cursor along the binary numbers, the corresponding label text is displayed for
each logic input.

19.3.2 RELAY O/P STATUS CELL (RELAY OUTPUT STATUS)


This cell can be used to monitor the status of the relay outputs. The cell is a binary string that displays the status of
the relay outputs where '1' means energised and '0' means de-energised. If you move the cursor along the binary
numbers, the corresponding label text is displayed for each relay output.
The cell indicates the status of the output relays when the IED is in service. You can check for relay damage by
comparing the status of the output contacts with their associated bits.

Note:
When the Test Mode cell is set to Contacts Blocked, the relay output status indicates which contacts would operate if the
IED was in-service. It does not show the actual status of the output relays, as they are blocked.

19.3.3 TEST MODE CELL


This cell allows you to perform secondary injection testing. It also lets you test the output contacts directly by
applying menu-controlled test signals.
To go into test mode, select the Test Mode option in the Test Mode cell. This takes the IED out of service causing
an alarm condition to be recorded and the Out of Service LED to illuminate. This also freezes any information
stored in the CB CONDITION column. In IEC 60870-5-103 versions, it changes the Cause of Transmission (COT) to
Test Mode.
In Test Mode, the output contacts are still active. To disable the output contacts you must select the Contacts
Blocked option.
Once testing is complete, return the device back into service by setting the Test Mode Cell back to Disabled.

Caution:
When the cell is in Test Mode, the Scheme Logic still drives the output relays,
which could result in tripping of circuit breakers. To avoid this, set the Test Mode
cell to Contacts Blocked.

Note:
Test mode and Contacts Blocked mode can also be selected by energising an opto-input mapped to the Test Mode
signal, and the Contact Block signal respectively.

448 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.3.4 TEST PATTERN CELL


The Test Pattern cell is used to select the output relay contacts to be tested when the Contact Test cell is set to
Apply Test. The cell has a binary string with one bit for each user-configurable output contact, which can be set
to '1' to operate the output and '0' to not operate it.

19.3.5 CONTACT TEST CELL


When the Apply Test command in this cell is issued, the contacts set for operation change state. Once the test
has been applied, the command text on the LCD will change to No Operation and the contacts will remain in the
Test state until reset by issuing the Remove Test command. The command text on the LCD will show No
Operation after the Remove Test command has been issued.

Note:
When the Test Mode cell is set to Contacts Blocked the Relay O/P Status cell does not show the current status of the
output relays and therefore cannot be used to confirm operation of the output relays. Therefore it will be necessary to monitor
the state of each contact in turn.

19.3.6 TEST LEDS CELL


When the Apply Test command in this cell is issued, the user-programmable LEDs illuminate for approximately 2
seconds before switching off, and the command text on the LCD reverts to No Operation.

19.3.7 RED AND GREEN LED STATUS CELLS


These cells contain binary strings that indicate which of the user-programmable red and green LEDs are illuminated
when accessing from a remote location. A '1' indicates that a particular LED is illuminated.

Note:
When the status in both Red LED Status and Green LED Status cells is ‘1’, this indicates the LEDs illumination is yellow.

19.3.8 PSL VERIFICIATION

19.3.8.1 TEST PORT STATUS CELL


This cell displays the status of the DDB signals that have been allocated in the Monitor Bit cells. If you move the
cursor along the binary numbers, the corresponding DDB signal text string is displayed for each monitor bit.
By using this cell with suitable monitor bit settings, the state of the DDB signals can be displayed as various
operating conditions or sequences are applied to the IED. This allows you to test the Programmable Scheme Logic
(PSL).

19.3.8.2 MONITOR BIT 1 TO 8 CELLS


The eight Monitor Bit cells allows you to select eight DDB signals that can be observed in the Test Port Status cell
or downloaded via the front port.
Each Monitor Bit cell can be assigned to a particular DDB signal. You set it by entering the required DDB signal
number from the list of available DDB signals.
The pins of the monitor/download port used for monitor bits are as follows:
Monitor Bit 1 2 3 4 5 6 7 8
Monitor/Download Port Pin 11 12 15 13 20 21 23 24

P64-TM-EN-1 449
Chapter 19 - Commissioning Instructions P64

The signal ground is available on pins 18, 19, 22 and 25.

Caution:
The monitor/download port is not electrically isolated against induced voltages on
the communications channel. It should therefore only be used for local
communications.

450 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.4 COMMISSIONING EQUIPMENT


Specialist test equipment is required to commission this product. We recognise three classes of equipment for
commissioning :
● Recommended
● Essential
● Advisory

Recommended equipment constitutes equipment that is both necessary, and sufficient, to verify correct
performance of the principal protection functions.
Essential equipment represents the minimum necessary to check that the product includes the basic expected
protection functions and that they operate within limits.
Advisory equipment represents equipment that is needed to verify satisfactory operation of features that may be
unused, or supplementary, or which may, for example, be integral to a distributed control/automation scheme.
Operation of such features may, perhaps, be more appropriately verified as part of a customer defined
commissioning requirement, or as part of a system-level commissioning regime.

19.4.1 RECOMMENDED COMMISSIONING EQUIPMENT


The minimum recommended equipment is a multifunctional three-phase AC current and voltage injection test set
featuring :
● Controlled three-phase AC current and voltage sources,
● Transient (dynamic) switching between pre-fault and post-fault conditions (to generate delta conditions),
● Dynamic impedance state sequencer (capable of sequencing through 4 impedance states),
● Integrated or separate variable DC supply (0 - 250 V)
● Integrated or separate AC and DC measurement capabilities (0-440V AC, 0-250V DC)
● Integrated and/or separate timer,
● Integrated and/or separate test switches.

In addition, you will need :


● A portable computer, installed with appropriate software to liaise with the equipment under test (EUT).
Typically this software will be proprietary to the product’s manufacturer (for example MiCOM S1 Agile).
● Suitable electrical test leads.
● Electronic or brushless insulation tester with a DC output not exceeding 500 V
● Continuity tester
● Verified application-specific settings files

19.4.2 ESSENTIAL COMMISSIONING EQUIPMENT


As an absolute minimum, the following equipment is required:
● AC current source coupled with AC voltage source
● Variable DC supply (0 - 250V)
● Multimeter capable of measuring AC and DC current and voltage (0-440V AC, 0-250V DC)
● Timer
● Test switches
● Suitable electrical test leads
● Continuity tester

P64-TM-EN-1 451
Chapter 19 - Commissioning Instructions P64

19.4.3 ADVISORY TEST EQUIPMENT


Advisory test equipment may be required for extended commissioning procedures:
● Current clamp meter
● Multi-finger test plug:
○ P992 for test block type P991
○ MMLB for test block type MMLG blocks
● Electronic or brushless insulation tester with a DC output not exceeding 500 V
● KITZ K-Bus - EIA(RS)232 protocol converter for testing EIA(RS)485 K-Bus port
● EIA(RS)485 to EIA(RS)232 converter for testing EIA(RS)485 Courier/MODBUS/IEC60870-5-103/DNP3 port
● A portable printer (for printing a setting record from the portable PC) and or writeable, detachable memory
device
● Phase angle meter
● Phase rotation meter
● Fibre-optic power meter.
● Fibre optic test leads (minimum 2). 10m minimum length, multimode 50/125 µm or 62.5µm terminated with
BFOC (ST) 2.5 connectors for testing the fibre-optic RP1 port

452 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.5 PRODUCT CHECKS


These product checks are designed to ensure that the device has not been physically damaged prior to
commissioning, is functioning correctly and that all input quantity measurements are within the stated tolerances.
If the application-specific settings have been applied to the IED prior to commissioning, you should make a copy of
the settings. This will allow you to restore them at a later date if necessary. This can be done by:
● Obtaining a setting file from the customer.
● Extracting the settings from the IED itself, using a portable PC with appropriate setting software.

If the customer has changed the password that prevents unauthorised changes to some of the settings, either the
revised password should be provided, or the original password restored before testing.

Note:
If the password has been lost, a recovery password can be obtained from GE Vernova.

19.5.1 PRODUCT CHECKS WITH THE IED DE-ENERGISED

Warning:
The following group of tests should be carried out without the auxiliary supply
being applied to the IED and, if applicable, with the trip circuit isolated.

The current and voltage transformer connections must be isolated from the IED for these checks. If a P991 test
block is provided, the required isolation can be achieved by inserting test plug type P992. This open circuits all
wiring routed through the test block.
Before inserting the test plug, you should check the scheme diagram to ensure that this will not cause damage or a
safety hazard (the test block may, for example, be associated with protection current transformer circuits). The
sockets in the test plug, which correspond to the current transformer secondary windings, must be linked before the
test plug is inserted into the test block.

Warning:
Never open-circuit the secondary circuit of a current transformer since the high
voltage produced may be lethal and could damage insulation.

If a test block is not provided, the voltage transformer supply to the IED should be isolated by means of the panel
links or connecting blocks. The line current transformers should be short-circuited and disconnected from the IED
terminals. Where means of isolating the auxiliary supply and trip circuit (for example isolation links, fuses and MCB)
are provided, these should be used. If this is not possible, the wiring to these circuits must be disconnected and the
exposed ends suitably terminated to prevent them from being a safety hazard.

19.5.1.1 VISUAL INSPECTION

P64-TM-EN-1 453
Chapter 19 - Commissioning Instructions P64

Warning:
Check the rating information under the top access cover on the front of the IED.

Warning:
Check that the IED being tested is correct for the line or circuit.

Warning:
Record the circuit reference and system details.

Warning:
Check the CT secondary current rating and record the CT tap which is in use.

Carefully examine the IED to see that no physical damage has occurred since installation.
Ensure that the case earthing connections (bottom left-hand corner at the rear of the IED case) are used to connect
the IED to a local earth bar using an adequate conductor.

19.5.1.2 CURRENT TRANSFORMER SHORTING CONTACTS


Check the current transformer shorting contacts to ensure that they close when the heavy-duty terminal block is
disconnected from the current input board.
The heavy-duty terminal blocks are fastened to the rear panel using four crosshead screws. These are located two
at the top and two at the bottom.

Note:
Use a magnetic bladed screwdriver to minimise the risk of the screws being left in the terminal block or lost.

Pull the terminal block away from the rear of the case and check with a continuity tester that all the shorting
switches being used are closed.

19.5.1.3 INSULATION
Insulation resistance tests are only necessary during commissioning if explicitly requested.
Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation tester at a DC
voltage not exceeding 500 V. Terminals of the same circuits should be temporarily connected together.
The insulation resistance should be greater than 100 MW at 500 V.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the IED.

19.5.1.4 EXTERNAL WIRING

Caution:
Check that the external wiring is correct according to the relevant IED and scheme
diagrams. Ensure that phasing/phase rotation appears to be as expected.

19.5.1.5 WATCHDOG CONTACTS


Using a continuity tester, check that the Watchdog contacts are in the following states:

454 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

Terminals Contact State with Product De-energised


11 - 12 on power supply board Closed
13 - 14 on power supply board Open

19.5.1.6 POWER SUPPLY


Depending on its nominal supply rating, the IED can be operated from either a DC only or an AC/DC auxiliary
supply. The incoming voltage must be within the operating range specified below.
Without energising the IED measure the auxiliary supply to ensure it is within the operating range.
Nominal supply rating Nominal Supply Rating
DC Operating Range AC Operating Range
DC AC RMS
24 - 54 V N/A 19 to 65 V N/A
48 - 125 V 30 - 100 V 37 to 150 V 24 - 110 V
110 - 250 V 100 - 240 V 87 to 300 V 80 to 265 V

Note:
The IED can withstand an AC ripple of up to 15% of the upper rated voltage on the DC auxiliary supply.

Warning:
Do not energise the IED or interface unit using the battery charger with the battery
disconnected as this can irreparably damage the power supply circuitry.

Caution:
Energise the IED only if the auxiliary supply is within the specified operating
ranges. If a test block is provided, it may be necessary to link across the front of
the test plug to connect the auxiliary supply to the IED.

19.5.2 PXXX_CI_PRODUCTCHECKSENERGISED

Warning:
The current and voltage transformer connections must remain isolated from the
IED for these checks. The trip circuit should also remain isolated to prevent
accidental operation of the associated circuit breaker.

The following group of tests verifies that the IED hardware and software is functioning correctly and should be
carried out with the supply applied to the IED.

19.5.2.1 WATCHDOG CONTACTS


Using a continuity tester, check that the Watchdog contacts are in the following states when energised and healthy.

Terminals Contact State with Product Energised


11 - 12 on power supply board Open
13 - 14 on power supply board Closed

P64-TM-EN-1 455
Chapter 19 - Commissioning Instructions P64

19.5.2.2 TEST GRAPHICAL HMI


The Graphical HMI is designed to operate in a wide range of substation ambient temperatures. For this purpose, the
IEDs have an LCD Brightness setting. The brightness is factory pre-set, but it may be necessary to adjust the
contrast to give the best in-service display.
To change the contrast, you can increment or decrement the LCD Brightness cell in the CONFIGURATION
column.

Caution:
Before applying a brightness setting, make sure that it will not make the display so
light or dark that the menu text becomes unreadable. It is possible to restore the
visibility of a display by downloading a setting file, and setting the LCD Brightness
within the typical range of 7 - 11.

19.5.2.3 DATE AND TIME


The date and time is stored in memory, which is backed up by a supercapacitor.
The method for setting the date and time depends on whether an IRIG-B signal is being used or not. The IRIG-B
signal will override the time, day and month settings, but not the initial year setting. For this reason, you must
ensure you set the correct year, even if the device is using IRIG-B to maintain the internal clock.
You set the Date and Time by one of the following methods:
● Using the front panel to set the Date and Time cells respectively
● By sending a courier command to the Date/Time cell (Courier reference 0801)

Note:
If the auxiliary supply fails, the time and date will be maintained by the supercapacitor. Therefore, when the auxiliary supply is
restored, you should not have to set the time and date again. To test this, remove the IRIG-B signal, and then remove the
auxiliary supply. Leave the device de-energised for approximately 30 seconds. On re energisation, the time should be correct.

When using IRIG-B to maintain the clock, the IED must first be connected to the satellite clock equipment (usually
an RT430), which should be energised and functioning.
1. Set the IRIG-B Sync cell in the DATE AND TIME column to Enabled.
2. Ensure the IED is receiving the IRIG-B signal by checking that cell IRIG-B Status reads Active.
3. Once the IRIG-B signal is active, adjust the time offset of the universal co coordinated time (satellite clock
time) on the satellite clock equipment so that local time is displayed.
4. Check that the time, date and month are correct in the Date/Time cell. The IRIG-B signal does not contain the
current year so it will need to be set manually in this cell.
5. Reconnect the IRIG-B signal.
If the time and date is not being maintained by an IRIG-B signal, ensure that the IRIG-B Sync cell in the DATE AND
TIME column is set to Disabled.
1. Set the date and time to the correct local time and date using Date/Time cell or using the serial protocol.

19.5.2.4 TEST LEDS


On power-up, all LEDs should first flash yellow. Following this, the green "Healthy" LED should illuminate indicating
that the device is healthy.
The IED's non-volatile memory stores the states of the alarm, the trip, and the user-programmable LED indicators (if
configured to latch). These indicators may also illuminate when the auxiliary supply is applied.

456 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

If any of these LEDs are ON then they should be reset before proceeding with further testing. If the LEDs
successfully reset (the LED goes off), no testing is needed for that LED because it is obviously operational.

19.5.2.5 TEST ALARM AND OUT-OF-SERVICE LEDS


The alarm and out of service LEDs can be tested using the COMMISSION TESTS menu column.
1. Set the Test Mode cell to Contacts Blocked.
2. Check that the out of service LED illuminates continuously and the alarm LED flashes.
It is not necessary to return the Test Mode cell to Disabled at this stage because the test mode will be required
for later tests.

19.5.2.6 TEST TRIP LED


The trip LED can be tested by initiating a manual circuit breaker trip. However, the trip LED will operate during the
setting checks performed later. Therefore no further testing of the trip LED is required at this stage.

19.5.2.7 TEST USER-PROGRAMMABLE LEDS


To test these LEDs, set the Test LEDs cell to Apply Test. Check that all user-programmable LEDs illuminate.

19.5.2.8 TEST OPTO-INPUTS


This test checks that all the opto-inputs on the IED are functioning correctly.
The opto-inputs should be energised one at a time. For terminal numbers, please see the external connection
diagrams in the "Wiring Diagrams" chapter. Ensuring correct polarity, connect the supply voltage to the appropriate
terminals for the input being tested.
The status of each opto-input can be viewed using either the Opto I/P Status cell in the SYSTEM DATA column, or
the Opto I/P Status cell in the COMMISSION TESTS column.
A '1' indicates an energised input and a '0' indicates a de-energised input. When each opto-input is energised, one
of the characters on the bottom line of the display changes to indicate the new state of the input.

19.5.2.9 TEST OUTPUT RELAYS


This test checks that all the output relays are functioning correctly.
1. Ensure that the IED is still in test mode by viewing the Test Mode cell in the COMMISSION TESTS column.
Ensure that it is set to Contacts Blocked.
2. The output relays should be energised one at a time. To select output relay 1 for testing, set the Test Pattern
cell as appropriate.
3. Connect a continuity tester across the terminals corresponding to output relay 1 as shown in the external
connection diagram.
4. To operate the output relay set the Contact Test cell to Apply Test.
5. Check the operation with the continuity tester.
6. Measure the resistance of the contacts in the closed state.
7. Reset the output relay by setting the Contact Test cell to Remove Test.
8. Repeat the test for the remaining output relays.
9. Return the IED to service by setting the Test Mode cell in the COMMISSION TESTS menu to Disabled.

19.5.2.10 RTD INPUTS


This test checks that all the RTD inputs are functioning correctly, if the RTD board is fitted.

P64-TM-EN-1 457
Chapter 19 - Commissioning Instructions P64

Please refer to the wiring diagrams for details of the terminal connections.
1. You should connect a 100 ohm resistor across each RTD in turn. The resistor needs to have a very small
tolerance (0.1%). You must connect the RTD common return terminal to the correct RTD input, otherwise the
device will report an RTD error.
2. Check that the corresponding temperature displayed in the MEASUREMENTS 3 column of the menu is 0°C
+/-2°C. This range takes into account the 0.1% resistor tolerance and device accuracy of +/-1°C. If a resistor
of lower accuracy is used during testing, the acceptable setting range needs to be increased.

19.5.2.11 CURRENT LOOP OUTPUTS


This test checks that all the current loop outputs are functioning correctly, if the board is fitted.
Please refer to the wiring diagrams for details of the terminal connections. Note that for the current loop outputs, the
physical connection of the 1 mA output is different from that of the other types.
1. Enable the current loop output to be tested.
2. Note the current loop output type (CLO Type) for the application.
3. Note the current loop output parameter (CLO Parameter)
4. Note the current loop output minimum and maximum settings (CLO Minimum and CLO Maximum)
5. Apply the appropriate analog input quantity to match the CLO Parameter at a value equal to (CLO maximum
+ CLO minimum)/2. The current loop output should be at 50% of its maximum rated output.
6. Using a precision resistive current shunt and a high-resolution voltmeter, check that the current loop output is
at 50% of its maximum rated output according to the range as follows:
0.5 mA (0 to 1 mA CLO)
5 mA (0 to 10 mA CLO)
10 mA (0 to 20, 4 to 20 mA CLO)
7. The accuracy should be within +/-0.5% of full scale + meter accuracy.

19.5.2.12 CURRENT LOOP INPUTS


This test checks that all the current loop inputs are functioning correctly, if the board is fitted.
Please refer to the wiring diagrams for details of the terminal connections. Note that for the current loop inputs, the
physical connection of the 1 mA input is different from that of the other types.
You can use an accurate DC current source to apply various current levels to the current loop inputs. One approach
to this is to use a current loop output as a DC current sources. If you stimulate the current loop output by applying
an appropriate signal to the input to which it has been assigned with the CLO Parameter setting, you will get an
appropriate DC signal if the output is enabled.
1. Enable the current loop input to be tested.
2. Note the CLIx minimum and maximum settings and the CLIx Input type for the application.
3. Apply a DC current to the current loop input at 50% of the CLI input maximum range, 0.5 mA (0 to 1 mA CLI),
5 mA (0 to 10 mA CLI) or 10 mA (0 to 20, 4 to 20 mA CLI).
4. Check the accuracy of the current loop input using the CLIO Input 1/2/3/4 cells in the MEASUREMENTS 3
column. The display should show (CLIx maximum + CLIx minimum)/2 +/-1% full scale accuracy.

19.5.2.13 TEST SERIAL COMMUNICATION PORT RP1


You need only perform this test if the IED is to be accessed from a remote location with a permanent serial
connection to the communications port. The scope of this test does not extend to verifying operation with connected
equipment beyond any supplied protocol converter. It verifies operation of the rear communication port (and if
applicable the protocol converter) and varies according to the protocol fitted.

458 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.5.2.13.1 CHECK PHYSICAL CONNECTIVITY


The rear communication port RP1 is presented on terminals 16, 17 and 18 of the power supply terminal block.
Screened twisted pair cable is used to make a connection to the port. The cable screen should be connected to pin
16 and pins 17 and 18 are for the communication signal:

Figure 181: RP1 physical connection

For K-Bus applications, pins 17 and 18 are not polarity sensitive and it does not matter which way round the wires
are connected. EIA(RS)485 is polarity sensitive, so you must ensure the wires are connected the correct way round
(pin 18 is positive, pin 17 is negative).
If K-Bus is being used, a Kitz protocol converter (KITZ101, KITZ102 OR KITZ201) will have been installed to
convert the K-Bus signals into RS232. Likewise, if RS485 is being used, an RS485-RS232 converter will have been
installed. In the case where a protocol converter is being used, a laptop PC running appropriate software (such as
MiCOM S1 Agile) can be connected to the incoming side of the protocol converter. An example for K-bus to RS232
conversion is shown below. RS485 to RS232 would follow the same principle, only using a RS485-RS232
converter. Most modern laptops have USB ports, so it is likely you will also require a RS232 to USB converter too.

P64-TM-EN-1 459
Chapter 19 - Commissioning Instructions P64

Figure 182: Remote communication using K-bus

Fibre Connection
Some models have an optional fibre optic communications port fitted (on a separate communications board). The
communications port to be used is selected by setting the Physical Link cell in the COMMUNICATIONS column, the
values being Copper or K-Bus for the RS485/K-bus port and Fibre Optic for the fibre optic port.

19.5.2.13.2 CHECK LOGICAL CONNECTIVITY


The logical connectivity depends on the chosen data protocol, but the principles of testing remain the same for all
protocol variants:
1. Ensure that the communications baud rate and parity settings in the application software are set the same as
those on the protocol converter.
2. For Courier models, ensure that you have set the correct RP1 address
3. Check that communications can be established with this IED using the portable PC/Master Station.

19.5.2.14 TEST SERIAL COMMUNICATION PORT RP2


RP2 is an optional second serial port board providing additional serial connectivity. It provides two 9-pin D-type
serial port connectors SK4 and SK5. Both ports are configured as DTE (Date Terminal Equipment) ports. That
means they can be connected to communications equipment such as a modem with a straight-through cable.
SK4 can be configured as an EIA(RS232), EIA(RS485), or K-Bus connection for Courier protocol only, whilst SK5 is
fixed to EIA(RS)232 for InterMiCOM signalling only.
It is not the intention of this test to verify the operation of the complete communication link between the IED and the
remote location, just the IED's rear communication port and, if applicable, the protocol converter.

460 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

The only checks that need to be made are as follows:


1. Set the RP2 Port Config cell in the COMMUNICATIONS column to the required physical protocol; (K-Bus,
EIA(RS)485, or EIA(RS)232.
2. Set the IED's Courier address to the correct value (it must be between 1 and 254).

19.5.2.15 TEST ETHERNET COMMUNICATION


For products that employ Ethernet communications, we recommend that testing be limited to a visual check that the
correct ports are fitted and that there is no sign of physical damage.
If there is no board fitted or the board is faulty, a NIC link alarm will be raised (providing this option has been set in
the NIC Link Report cell in the COMMUNICATIONS column).

19.5.3 SECONDARY INJECTION TESTS


Secondary injection testing is carried out to verify the integrity of the VT and CT readings. All devices leave the
factory set for operation at a system frequency of 50 Hz. If operation at 60 Hz is required, you must set this in the
Frequency cell in the SYSTEM DATA column.
The PMU must be installed and connected to a 1pps fibre optic synchronising signal and a demodulated IRIG-B
signal, provided by a device such as a REASON RT430.
Connect the current and voltage outputs of the test set to the appropriate terminals of the first voltage and current
channel and apply nominal voltage and current with the current lagging the voltage by 90 degrees.

19.5.3.1 TEST CURRENT INPUTS


This test verifies that the current measurement inputs are configured correctly.
1. Using secondary injection test equipment such as an Omicron, apply and measure nominal rated current to
each CT in turn.
2. Check its magnitude using a multi-meter or test set readout. Check this value against the value displayed on
the HMI panel (usually in MEASUREMENTS 1 column).
3. Record the displayed value. The measured current values will either be in primary or secondary Amperes. If
the Local Values cell in the MEASURE’T SETUP column is set to Primary, the values displayed should be
equal to the applied current multiplied by the corresponding current transformer ratio (set in the CT AND VT
RATIOS column). If the Local Values cell is set to Secondary, the value displayed should be equal to the
applied current.

Note:
If a PC connected to the IED using the rear communications port is being used to display the measured current, the process
will be similar. However, the setting of the Remote Values cell in the MEASURE’T SETUP column will determine whether the
displayed values are in primary or secondary Amperes.

The measurement accuracy of the IED is +/- 1%. However, an additional allowance must be made for the accuracy
of the test equipment being used.

P64-TM-EN-1 461
Chapter 19 - Commissioning Instructions P64

19.5.3.1.1 CHECK POLARITY OF THREE-PHASE CTS


This test checks the polarity of all three-phase CTs associated with a winding.
1. Apply the same current to phases A, B, and C, phase displaced as for a balanced 3-phase set with standard
ABC phase rotation (phase A = 0°, phase B = -120°, phase C = +120°).
2. Starting from CT input 1, apply the balanced current and check the measured residual current in the relevant
cell. This will be IN-TN1 Deriv Mag, IN-TN2 Deriv Mag, or IN-TN3 Deriv Mag depending on the transformer
winding to which the current input is assigned.
3. The residual current measured should be less than 0.05 p.u. If high residual current is measured, one or
more of the CT circuits for the end concerned may have a problem (for example, an inverted connection).
Repeat the same test on the rest of the CT inputs.

19.5.3.2 TEST VOLTAGE INPUTS


This test verifies that the voltage measurement inputs are configured correctly.
1. Using secondary injection test equipment, apply and measure the rated voltage to each voltage transformer
input in turn.
2. Check its magnitude using a multimeter or test set readout. Check this value against the value displayed on
the HMI panel (usually in MEASUREMENTS 1 column).
3. Record the value displayed. The measured voltage values will either be in primary or secondary Volts. If the
Local Values cell in the MEASURE’T SETUP column is set to Primary, the values displayed should be
equal to the applied voltage multiplied by the corresponding voltage transformer ratio (set in the CT AND VT
RATIOS column). If the Local Values cell is set to Secondary, the value displayed should be equal to the
applied voltage.

Note:
If a PC connected to the IED using the rear communications port is being used to display the measured current, the process
will be similar. However, the setting of the Remote Values cell in the MEASURE’T SETUP column will determine whether the
displayed values are in primary or secondary Amperes.

The measurement accuracy of the IED is +/- 1%. However, an additional allowance must be made for the accuracy
of the test equipment being used.

462 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.6 SETTING CHECKS


The setting checks ensure that all of the application-specific settings (both the IED’s function and Programmable
Scheme Logic settings) have been correctly applied.

Note:
If applicable, the trip circuit should remain isolated during these checks to prevent accidental operation of the associated
circuit breaker.

19.6.1 APPLY APPLICATION-SPECIFIC SETTINGS


There are two different methods of applying the settings to the IED
● Transferring settings to the IED from a pre-prepared setting file using MiCOM S1 Agile
● Enter the settings manually using the IED’s front panel HMI

19.6.1.1 TRANSFERRING SETTINGS FROM A SETTINGS FILE


This is the preferred method for transferring function settings. It is much faster and there is a lower margin for error.
1. Connect a PC running the Settings Application Software to the IED's front port, or a rear Ethernet port.
Alternatively connect to the rear Courier communications port, using a KITZ protocol converter if necessary.
2. Power on the IED
3. Enter the IP address of the device if it is Ethernet enabled
4. Right-click the appropriate device name in the System Explorer pane and select Send
5. In the Send to dialog select the setting files and click Send

Note:
The device name may not already exist in the system shown in System Explorer. In this case, perform a Quick Connect to
the IED, then manually add the settings file to the device name in the system. Refer to the Settings Application Software help
for details of how to do this.

19.6.1.2 ENTERING SETTINGS USING THE HMI


1. Starting at the default display, press the Down cursor key to show the first column heading.
2. Use the horizontal cursor keys to select the required column heading.
3. Use the vertical cursor keys to view the setting data in the column.
4. To return to the column header, either press the Up cursor key for a second or so, or press the Cancel key
once. It is only possible to move across columns at the column heading level.
5. To return to the default display, press the Up cursor key or the Cancel key from any of the column headings. If
you use the auto-repeat function of the Up cursor key, you cannot go straight to the default display from one
of the column cells because the auto-repeat stops at the column heading.
6. To change the value of a setting, go to the relevant cell in the menu, then press the Enter key to change the
cell value. A flashing cursor on the LCD shows that the value can be changed. You may be prompted for a
password first.
7. To change the setting value, press the vertical cursor keys. If the setting to be changed is a binary value or a
text string, select the required bit or character to be changed using the left and right cursor keys.

P64-TM-EN-1 463
Chapter 19 - Commissioning Instructions P64

8. Press the Enter key to confirm the new setting value or the Clear key to discard it. The new setting is
automatically discarded if it is not confirmed within 15 seconds.
9. For protection group settings and disturbance recorder settings, the changes must be confirmed before they
are used. When all required changes have been entered, return to the column heading level and press the
down cursor key. Before returning to the default display, the following prompt appears.

Update settings?
ENTER or CLEAR

10. Press the Enter key to accept the new settings or press the Clear key to discard the new settings.

Note:
If the menu time-out occurs before the setting changes have been confirmed, the setting values are also discarded.
Control and support settings are updated immediately after they are entered, without the Update settings prompt.
It is not possible to change the PSL using the IED’s front panel HMI.

Caution:
Where the installation needs application-specific PSL, the relevant .psl files, must
be transferred to the IED, for each and every setting group that will be used. If you
do not do this, the factory default PSL will still be resident. This may have severe
operational and safety consequences.

464 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.7 IEC 61850 EDITION 2 TESTING

19.7.1 USING IEC 61850 EDITION 2 TEST MODES


In a conventional substation, functionality typically resides in a single device. It is usually easy to physically isolate
these functions, as the hardwired connects can simply be removed. Within a digital substation architecture however,
functions may be distributed across many devices. This makes isolation of these functions difficult, because there
are no physical wires that can be disconnected on a Ethernet network. Logical isolation of the various functions is
therefore necessary.
With devices that support IEC 61850 Edition 2, it is possible to use a test mode to conduct online testing, which
helps with the situation. The advantages of this are as follows:
● The device can be placed into a test mode, which can disable the relay outputs when testing the device with
test input signals.
● Specific protection and control functions can be logically isolated.
● GOOSE messages can be tagged so that receiving devices can recognise they are test signals.
● An IED receiving simulated GOOSE or Sampled Value messages from test devices can differentiate these
from normal process messages, and be configured to respond appropriately.

19.7.1.1 IED TEST MODE BEHAVIOUR


Test modes define how the device responds to test messages, and whether the relay outputs are activated or not.
You can select the mode of operation by:
● Using the front panel HMI, with the setting IED Test Mode under the COMMISSION TESTS column.
● Using an IEC 61850 control service to System/LLN0.Mod
● Using an opto-input via PSL with the signal Block Contacts

The following table summarises the IED behaviour under the different modes:
IED Test Mode Setting Result
Disabled Normal IED behaviour
Protection remains enabled
Output from the device is still active
Test IEC 61850 message output has the 'quality' parameter set to 'test'
The device only responds to IEC61850 MMS messages from the client with the 'test'
flag set
Protection remains enabled
Output from the device is disabled
Contacts Blocked IEC 61850 message output has quality set to ‘test’
The device only responds to IEC 61850 MMS messages from the client with the 'test'
flag set

Setting the Test or Contacts Blocked mode puts the whole IED into test mode. The IEC 61850 data object Beh in all
Logical Nodes (except LPHD and any protection Logical Nodes that have Beh = 5 (off) due to the function being
disabled) will be set to 3 (test) or 4 (test/blocked) as applicable.

19.7.1.2 SAMPLED VALUE TEST MODE BEHAVIOUR


The SV Test Mode defines how the device responds to test sampled value messages. You can select the mode of
operation by using the front panel HMI, with the setting SV Test Mode under the IEC 61850-9.2LE column.
The following table summarises the behaviour for sampled values under the different modes:

P64-TM-EN-1 465
Chapter 19 - Commissioning Instructions P64

SV Test Mode Setting Result


Normal IED behaviour
All sampled value data frames received with an IEC 61850 Test quality bit set are
Disabled treated as invalid
The IED will display the measurement values for sampled values with the Simulated
flag set but the protection elements within the IED will be blocked
All sampled value data frames received are treated as good, no matter if they have an
Enabled
IEC 61850-9-2 Simulated flag set or not

19.7.2 SIMULATED INPUT BEHAVIOUR


Simulated GOOSE messages and sampled value streams can be used during testing.
The Subscriber Sim setting in the COMMISSION TESTS column controls whether a device listens to simulated
signals or to real ones. An IEC 61850 control service to System/LPHD.Sim can also be used to change this value.
The device may be presented with both real signals and test signals. An internal state machine is used to control
how the device switches between signals:
● The IED will continue subscribing to the ‘real’ GOOSE1 (in green) until it receives the first simulated GOOSE
1 (in red). This will initiate subscription changeover.
● After changeover to this new state, the IED will continue to subscribe to the simulated GOOSE 1 message (in
red). Even if this simulated GOOSE 1 message disappears, the real GOOSE 1 message (in green) will still
not be processed. This means all Virtual Inputs derived from the GOOSE 1 message will go to their default
state.
● The only way to bring the IED out of this state is to set the Subscriber Sim setting back to False. The IED
will then immediately stop processing the simulated messages and start processing real messages again.
● During above steps, IED1 will continuously process the real GOOSE 2 and GOOSE 3 messages as normal
because it has not received any simulated messages for these that would initiate a changeover.
The process is represented in the following figure:

LPHD1

Sim stVal=true Beh stVal=on


Simulated GOOSE 1 messages
Simulation bit goes TRUE

Real GOOSE 1 messages


Simulation bit was FALSE

Incoming data
processed
Real GOOSE 2 messages

Real GOOSE 3 messages

Reception buffer

V01058

Figure 183: Simulated input behaviour

466 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.7.3 TESTING EXAMPLES


These examples show how you test the IED with and without simulated values. Depending on the IED Test Mode, it
may respond by operating plant (for example by tripping the circuit breaker) or it may not operate plant.

19.7.3.1 TEST PROCEDURE FOR REAL VALUES


This procedure is for testing with real values without operating plant.
1. Set device into 'Contacts Blocked' Mode
Select COMMISSION TESTS ® IED Test Mode ® Contacts Blocked
2. Confirm new behaviour has been enabled
View COMMISSION TESTS ® IED Mod/Beh, and check that it shows Test-blocked
3. Set device into Simulation Listening Mode
Select COMMISSION TESTS ® Subscriber Sim = Disabled
4. If using sampled values set the sampled values test mode
Select IEC 61850-9.2LE ® SV Test Mode ® Disabled
5. Inject real signals using a test device connected to the merging units. The device will continue to listen to
‘real’ GOOSE messages and ignore simulated messages received.
6. Verify function based on test signal outputs
Binary outputs (e.g. CB trips) will not operate. All transmitted GOOSE and MMS data items will be tagged
with the 'quality' parameter set to 'test', so that the receiver understands that they have been issued by a
device under test and can respond accordingly. This is summarised in the following diagram

Fully digital bay Hardwired


CB control

Station/Process Bus
q = test No output

Yard Yard

SC MU1 Switchgear

MU1 MU1

Test Test
Device Device
V01062

Figure 184: Test example 1

P64-TM-EN-1 467
Chapter 19 - Commissioning Instructions P64

19.7.3.2 TEST PROCEDURE FOR SIMULATED VALUES - NO PLANT


This procedure is for testing with simulated values without operating plant.
1. Set device into 'Contacts Blocked' Mode
Select COMMISSION TESTS ® IED Test Mode ® Contacts Blocked
2. Confirm new behaviour has been enabled
View COMMISSION TESTS ® IED Mod/Beh, and check that it shows test-blocked
3. Set device into Simulation Listening Mode
Select COMMISSION TESTS ® Subscriber Sim = Enabled
4. If using sampled values set the sampled values test mode
Select IEC 61850-9.2LE ® SV Test Mode ® Enabled
5. Inject simulated signals using a test device connected to the Ethernet network. The device will continue to
listen to ‘real’ GOOSE messages until a simulated message is received. Once the simulated messages are
received, the corresponding ‘real’ messages are ignored until the device is taken out of test mode. Each
message is treated separately, but sampled values are considered as a single message.
6. Verify function based on test signal outputs
Binary outputs (e.g. CB trips) will not operate. All transmitted GOOSE and MMS data items will be tagged
with the 'quality' parameter set to 'test', so that the receiver understands that they have been issued by a
device under test and can respond accordingly. This is summarised in the following diagram

Fully digital bay Hardwired


CB control

Station/Process Bus
Simulated q = test No output
values

Yard Yard
Test
Device SC MU1 Switchgear

MU1 MU1
V01063
Figure 185: Test example 2

19.7.3.3 TEST PROCEDURE FOR SIMULATED VALUES - WITH PLANT


This procedure is for testing with simulated values with operating plant.
1. Set device into 'Contacts Blocked' Mode
Select COMMISSION TESTS ® IED Test Mode ® Test
2. Confirm new behaviour has been enabled
View COMMISSION TESTS ® IED Mod/Beh, and check that it shows Test

468 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

3. Set device into Simulation Listening Mode


Select COMMISSION TESTS ® Subscriber Sim = Enabled
4. If using sampled values set the sampled values test mode
Select IEC 61850-9.2LE ® SV Test Mode ® Enabled
5. Inject simulated signals using a test device connected to the Ethernet network.
The device will continue to listen to ‘real’ GOOSE messages until a simulated message is received. Once the
simulated messages are received, the corresponding ‘real’ messages are ignored until the device is taken out
of IED test mode. Each message is treated separately, but sampled values are considered as a single
message.
6. Verify function based on test signal outputs.
Binary outputs (e.g. CB trips) will operate as normal. All transmitted GOOSE and MMS data items will be
tagged with the 'quality' parameter set to 'test', so that the receiver understands that they have been issued
by a device under test and can respond accordingly. This is summarised in the following diagram:

Fully digital bay Hardwired


CB control

Station/Process Bus
Simulated q = test Trip output
values

Yard Yard
Test
Device SC MU1 Switchgear

MU1 MU1

V01064
Figure 186: Test example 3

19.7.3.4 CONTACT TEST


The Apply Test command in this cell is used to change the state of the contacts set for operation.
If the device has been put into 'Contact Blocked' mode using an input signal (via the Block Contacts DDB signal)
then the Apply Test command will not execute. This is to prevent a device that has been blocked by an external
process having its contacts operated by a local operator using the HMI.
If the Block Contacts DDB is not set and the Apply Test command in this cell is issued, contacts change state and
the command text on the LCD changes to No Operation. The contacts remain in the Test state until reset by
issuing the Remove Test command. The command text on the LCD shows No Operation after the Remove Test
command has been issued.

Note:
When the IED Test Mode cell is set to Contacts Blocked, the Relay O/P Status cell does not show the current status of the
output relays so cannot be used to confirm operation of the output relays. Therefore it is necessary to monitor the state of
each contact in turn.

P64-TM-EN-1 469
Chapter 19 - Commissioning Instructions P64

19.8 CHECKING THE DIFFERENTIAL ELEMENT


Testing of the differential element during commissioning is not necessary unless explicitly requested.
To avoid spurious operation of any other protection elements, all protection elements except the transformer
differential protection should be disabled for the duration of the differential element tests. This is done in the
product’s CONFIGURATION column. Make a note of which elements need to be re-enabled after testing.
The following tests demonstrate correct operation of the differential protection. Testing should be performed on
individual current inputs of each phase and on each winding, but note that the timing test should only be performed
on the high voltage winding. Testing the low-set element is sufficient to test the correct operation of the differential
protection.
Using a suitable current injection method, slowly increase the current from 0 Amps and note the pick-up value at
which the element operates. Reduce the current slowly and note the drop-off value at which it resets. Check that the
pick-up and drop-off are within the range shown in the table below.
Current level
Pick-up 0.90 x In to 1.1 x In
Drop-off 0.90 x pick-up to 1 x pick-up

where In = Is1/(amplitude matching factor)


and Is1 is the low set setting which can be found in the Is1 cell in the DIFF PROTECTION column.
The amplitude matching factor is used to compensate for a mismatch in currents due to the line side current
transformer ratios. There is one amplitude matching factor for the high-voltage side, one for the low-voltage side
and one for the tertiary-voltage side. You will find these in the SYSTEM CONFIG column. Use the appropriate
amplitude matching factor to calculate the required injection current. This depends on whether it is being injected
into the HV, LV, or TV current transformer inputs.
1. Whilst connected to the HV windings, connect the output contacts for the low set differential protection
function to trip the test set and also to stop a timer.
2. Configure the test set so that when the current is applied, the timer starts.
3. Inject 5x In into the HV CT input.
4. Check that the element operates within the range of 30 ms to 35 ms and record the time.

Note:
If this test has been successfully performed there is no need to carry out the tests described in the protection timing checks
section.

19.8.1 USING THE OMICRON ADVANCED MODULE


In software versions 05 and onwards, transient bias can be disabled or enabled. In software version 06 onwards,
the CT Saturation function was separated from the No gap function.

Testing Differential Operating Characteristics


When testing the differential operating characteristic, it is important to first disable transient bias. The CT saturation
and No Gap settings may be either disabled or enabled. An example is shown below:

470 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

V01503

Figure 187: Operating Characteristic Diagram

Testing Differential Tripping Time Characteristics


When testing the differential tripping time characteristic, transient bias, CT saturation and No Gap settings may be
either disabled or enabled. An example is shown below:

P64-TM-EN-1 471
Chapter 19 - Commissioning Instructions P64

V01504

Figure 188: Trip Time Test Plane

Testing Harmonic Restraint


When testing 2nd or 5th harmonic restraint, transient bias may be either enabled or disabled, but the CT Saturation
and No Gap settings must be disabled. This is because harmonic blocking is used to unblock the protection during
normal energization of the transformer, while No Gap Detection and CT Saturation Detection is used to unblock the
protection during an internal fault. An example is shown below:

472 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

Harmonic Restraint Test Plane


Idiff/In [In]

I2f/Idiff [%]
V01505

Figure 189: Harmonic Restraint Test Plane

P64-TM-EN-1 473
Chapter 19 - Commissioning Instructions P64

19.9 PROTECTION TIMING CHECKS


There is no need to check every protection function. Only one protection function needs to be checked as the
purpose is to verify the timing on the processor is functioning correctly.

19.9.1 BYPASSING THE ALL POLE DEAD BLOCKING CONDITION


Some protection functions and control functions are blocked when all poles are dead. When these conditions are
met, an All Poles Dead signal is asserted, blocking the said conditions. If you wish to test these these elements
during commissioning, you must bypass this blocking condition. You can do this by modifying the default PSL,
placing a NOT gate between the CB1 Closed signal and opto-input 7, so that when this input is not energised, CB1
is assumed to be closed.

19.9.2 OVERCURRENT CHECK


If the overcurrent protection function is being used, test the overcurrent protection for stage 1.
1. Check for any possible dependency conditions and simulate as appropriate.
2. In the CONFIGURATION column, disable all protection elements other than the one being tested.
3. Make a note of which elements need to be re-enabled after testing.
4. Connect the test circuit.
5. Perform the test.
6. Check the operating time.

19.9.3 CONNECTING THE TEST CIRCUIT


1. Use the PSL to determine which output relay will operate when an overcurrent trip occurs.
2. Use the output relay assigned to Trip Output A.
3. Use the PSL to map the protection stage under test directly to an output relay.

Note:
If using the default PSL, use output relay 3 as this is already mapped to the DDB signal Trip Command Out.

4. Connect the output relay so that its operation will trip the test set and stop the timer.
5. Connect the current output of the test set to the A-phase current transformer input.
If the I>1 Directional cell in the OVERCURRENT column is set to Directional Fwd, the current should
flow out of terminal 2. If set to Directional Rev, it should flow into terminal 2.
If the I>1 Directional cell in the OVERCURRENT column has been set to Directional Fwd or
Directional Rev, the rated voltage should be applied to terminals 20 and 21.
6. Ensure that the timer starts when the current is applied.

Note:
If the timer does not stop when the current is applied and stage 1 has been set for directional operation, the connections may
be incorrect for the direction of operation set. Try again with the current connections reversed.

474 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

19.9.4 PERFORMING THE TEST


1. Ensure that the timer is reset.
2. Apply a current of twice the setting shown in the I>1 Current Set cell in the OVERCURRENT column.
3. Note the time displayed when the timer stops.
4. Check that the red trip LED has illuminated.

19.9.5 CHECK THE OPERATING TIME


Check that the operating time recorded by the timer is within the range shown below.
For all characteristics, allowance must be made for the accuracy of the test equipment being used.

Operating Time at Twice Current Setting and Time Multiplier/Time Dial Setting of 1.0
Characteristic
Nominal (seconds) Range (seconds)
DT I>1 Time Delay setting Setting ±2%
IEC S Inverse 10.03 9.53 - 10.53
IEC V Inverse 13.50 12.83 - 14.18
IEC E Inverse 26.67 24.67 - 28.67
UK LT Inverse 120.00 114.00 - 126.00
IEEE M Inverse 3.8 3.61 - 4.0
IEEE V Inverse 7.03 6.68 - 7.38
IEEE E Inverse 9.50 9.02 - 9.97
US Inverse 2.16 2.05 - 2.27
US ST Inverse 12.12 11.51 - 12.73

Note:
With the exception of the definite time characteristic, the operating times given are for a Time Multiplier Setting (TMS) or Time
Dial Setting (TDS) of 1. For other values of TMS or TDS, the values need to be modified accordingly.
For definite time and inverse characteristics there is an additional delay of up to 0.02 second and 0.08 second respectively.
You may need to add this the IED's acceptable range of operating times.

Caution:
On completion of the tests, you must restore all settings to customer
specifications.

P64-TM-EN-1 475
Chapter 19 - Commissioning Instructions P64

19.10 ONLOAD CHECKS

Warning:
Onload checks are potentially very dangerous and may only be carried out by
qualified and authorised personnel.

Onload checks can only be carried out if there are no restrictions preventing the energisation of the plant, and the
other devices in the group have already been commissioned.
Remove all test leads and temporary shorting links, then replace any external wiring that has been removed to allow
testing.

Warning:
If any external wiring has been disconnected for the commissioning process,
replace it in accordance with the relevant external connection or scheme diagram.

19.10.1 CONFIRM CURRENT CONNECTIONS


1. Measure the current transformer secondary values for each input either by:
a. reading from the device's HMI panel (providing it has first been verified by a secondary injection test)
b. using a current clamp meter
2. Check that the current transformer polarities are correct by measuring the phase angle between the current
and voltage, either against a phase meter already installed on site and known to be correct or by determining
the direction of power flow by contacting the system control centre.
3. Ensure the current flowing in the neutral circuit of the current transformers is negligible.
If the Local Values cell is set to Secondary, the values displayed should be equal to the applied secondary
voltage. The values should be within 1% of the applied secondary voltages. However, an additional allowance must
be made for the accuracy of the test equipment being used.
If the Local Values cell is set to Primary, the values displayed should be equal to the applied secondary voltage
multiplied the corresponding voltage transformer ratio set in the CT & VT RATIOS column. The values should be
within 1% of the expected values, plus an additional allowance for the accuracy of the test equipment being used.

19.10.2 CONFIRM VOLTAGE CONNECTIONS


1. Using a multimeter, measure the voltage transformer secondary voltages to ensure they are correctly rated.
2. Check that the system phase rotation is correct using a phase rotation meter.
3. Compare the values of the secondary phase voltages with the measured voltage magnitude values, which
can be found in the MEASUREMENTS 1 menu column.

Cell in MEASUREMENTS 1 Column Corresponding VT Ratio in CT/VT RATIOS Column


VAB MAGNITUDE
VBC MAGNITUDE
VCA MAGNITUDE
Main VT Primary / Main VT Sec'y
VAN MAGNITUDE
VBN MAGNITUDE
VCN MAGNITUDE
If the Local Values cell is set to Secondary, the values displayed should be equal to the applied secondary
voltage. The values should be within 1% of the applied secondary voltages. However, an additional allowance must
be made for the accuracy of the test equipment being used.

476 P64-TM-EN-1
P64 Chapter 19 - Commissioning Instructions

If the Local Values cell is set to Primary, the values displayed should be equal to the applied secondary voltage
multiplied the corresponding voltage transformer ratio set in the CT & VT RATIOS column. The values should be
within 1% of the expected values, plus an additional allowance for the accuracy of the test equipment being used.

19.10.3 ON-LOAD DIRECTIONAL TEST


This test ensures that directional overcurrent and fault locator functions have the correct forward/reverse response
to fault and load conditions. For this test you must first know the actual direction of power flow on the system. If you
do not already know this you must determine it using adjacent instrumentation or protection already in-service.
● For load current flowing in the Forward direction (power export to the remote line end), the cells A Phase
Watts HV, A Phase Watts LV , and A Phase Watts TV in the MEASUREMENTS 2 column should show
positive power signing.
● For load current flowing in the Reverse direction (power import from the remote line end), the cells A Phase
Watts LV in the MEASUREMENTS 2 column should show negative power signing.

Note:
This check applies only for Measurement Modes 0 (default), and 2. This should be checked in the MEASURE’T. SETUP
column (Measurement Mode = 0 or 2). If measurement modes 1 or 3 are used, the expected power flow signing would be
opposite to that shown above.

In the event of any uncertainty, check the phase angle of the phase currents with respect to their phase voltage.

P64-TM-EN-1 477
Chapter 19 - Commissioning Instructions P64

19.11 FINAL CHECKS


1. Remove all test leads and temporary shorting leads.
2. If you have had to disconnect any of the external wiring in order to perform the wiring verification tests,
replace all wiring, fuses and links in accordance with the relevant external connection or scheme diagram.
3. The settings applied should be carefully checked against the required application-specific settings to ensure
that they are correct, and have not been mistakenly altered during testing.
4. Ensure that all protection elements required have been set to Enabled in the CONFIGURATION column.
5. Ensure that the IED has been restored to service by checking that the Test Mode cell in the COMMISSION
TESTS column is set to Disabled.
6. If the IED is in a new installation or the circuit breaker has just been maintained, the circuit breaker
maintenance and current counters should be zero. These counters can be reset using the Reset All Values
cell. If the required access level is not active, the device will prompt for a password to be entered so that the
setting change can be made.
7. If the menu language has been changed to allow accurate testing it should be restored to the customer’s
preferred language.
8. If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the cover so that the
protection is put into service.
9. Ensure that all event records, fault records, disturbance records, alarms and LEDs and communications
statistics have been reset.

Note:
Remember to restore the language setting to the customer’s preferred language on completion.

478 P64-TM-EN-1
CHAPTER 20

MAINTENANCE AND
TROUBLESHOOTING
Chapter 20 - Maintenance and Troubleshooting P64

20.1 CHAPTER OVERVIEW


The Maintenance and Troubleshooting chapter provides details of how to maintain and troubleshoot products based
on the Px4x and P40Agile platforms. Always follow the warning signs in this chapter. Failure to do so may result
injury or defective equipment.

Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on the
equipment’s rating label.

The troubleshooting part of the chapter allows an error condition on the IED to be identified so that appropriate
corrective action can be taken.
If the device develops a fault, it is usually possible to identify which module needs replacing. It is not possible to
perform an on-site repair to a faulty module.
If you return a faulty unit or module to the manufacturer or one of their approved service centres, you should include
a completed copy of the Repair or Modification Return Authorization (RMA) form.
This chapter contains the following sections:
Chapter Overview 480
Maintenance 481
Troubleshooting 489

480 P64-TM-EN-1
P64 Chapter 20 - Maintenance and Troubleshooting

20.2 MAINTENANCE

20.2.1 MAINTENANCE CHECKS


In view of the critical nature of the application, GE Vernova products should be checked at regular intervals to
confirm they are operating correctly. GE Vernova products are designed for a life in excess of 20 years.
The devices are self-supervising and so require less maintenance than earlier designs of protection devices. Most
problems will result in an alarm, indicating that remedial action should be taken. However, some periodic tests
should be carried out to ensure that they are functioning correctly and that the external wiring is intact. It is the
responsibility of the customer to define the interval between maintenance periods. If your organisation has a
Preventative Maintenance Policy, the recommended product checks should be included in the regular program.
Maintenance periods depend on many factors, such as:
● The operating environment
● The accessibility of the site
● The amount of available manpower
● The importance of the installation in the power system
● The consequences of failure

Although some functionality checks can be performed from a remote location, these are predominantly restricted to
checking that the unit is measuring the applied currents and voltages accurately, and checking the circuit breaker
maintenance counters. For this reason, maintenance checks should also be performed locally at the substation.

Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on the
equipment’s rating label.

20.2.1.1 ALARMS
First check the alarm status LED to see if any alarm conditions exist. If so, press the Read key repeatedly to step
through the alarms.
After dealing with any problems, clear the alarms. This will clear the relevant LEDs.

20.2.1.2 OPTO-ISOLATORS
Check the opto-inputs by repeating the commissioning test detailed in the Commissioning chapter.

20.2.1.3 OUTPUT RELAYS


Check the output relays by repeating the commissioning test detailed in the Commissioning chapter.

20.2.1.4 MEASUREMENT ACCURACY


If the power system is energised, the measured values can be compared with known system values to check that
they are in the expected range. If they are within a set range, this indicates that the A/D conversion and the
calculations are being performed correctly. Suitable test methods can be found in Commissioning chapter.
Alternatively, the measured values can be checked against known values injected into the device using the test
block, (if fitted) or injected directly into the device's terminals. Suitable test methods can be found in the
Commissioning chapter. These tests will prove the calibration accuracy is being maintained.

P64-TM-EN-1 481
Chapter 20 - Maintenance and Troubleshooting P64

20.2.2 REPLACING THE DEVICE


If your product should develop a fault while in service, depending on the nature of the fault, the watchdog contacts
will change state and an alarm condition will be flagged. In the case of a fault, you can replace either the complete
device or just the faulty PCB, identified by the in-built diagnostic software.
If possible you should replace the complete device, as this reduces the chance of damage due to electrostatic
discharge and also eliminates the risk of fitting an incompatible replacement PCB. However, we understand it may
be difficult to remove an installed product and you may be forced to replace the faulty PCB on-site. The case and
rear terminal blocks are designed to allow removal of the complete device, without disconnecting the scheme
wiring.

Caution:
Replacing PCBs requires the correct on-site environment (clean and dry) as well as
suitably trained personnel.

Caution:
If the repair is not performed by an approved service centre, the warranty will be
invalidated.

Caution:
Before carrying out any work on the equipment, you should be familiar with the
contents of the Safety Information section of this guide or the Safety Guide SFTY/
4LM, as well as the ratings on the equipment’s rating label. This should ensure that
no damage is caused by incorrect handling of the electronic components.

Warning:
Before working at the rear of the device, isolate all voltage and current supplying it.

Note:
The current transformer inputs are equipped with integral shorting switches which will close for safety reasons, when the
terminal block is removed.

To replace the complete device:


1. Carefully disconnect the cables not connected to the terminal blocks (e.g. IRIG-B, fibre optic cables, earth),
as appropriate, from the rear of the device.
2. Remove the terminal block screws using a magnetic screwdriver to minimise the risk of losing the screws or
leaving them in the terminal block.
3. Without exerting excessive force or damaging the scheme wiring, pull the terminal blocks away from their
internal connectors.
4. Remove the terminal block screws that fasten the device to the panel and rack. These are the screws with
the larger diameter heads that are accessible when the access covers are fitted and open.
5. Withdraw the device from the panel and rack. Take care, as the device will be heavy due to the internal
transformers.
6. To reinstall the device, follow the above instructions in reverse, ensuring that each terminal block is relocated
in the correct position and the chassis ground, IRIG-B and fibre optic connections are replaced. The terminal
blocks are labelled alphabetically with ‘A’ on the left hand side when viewed from the rear.
Once the device has been reinstalled, it should be re-commissioned as set out in the Commissioning chapter.

482 P64-TM-EN-1
P64 Chapter 20 - Maintenance and Troubleshooting

Caution:
If the top and bottom access covers have been removed, some more screws with
smaller diameter heads are made accessible. Do NOT remove these screws, as they
secure the front panel to the device.

Note:
There are four possible types of terminal block: RTD/CLIO input, heavy duty, medium duty, and MiDOS. The terminal blocks
are fastened to the rear panel with slotted or cross-head screws depending on the type of terminal block. Not all terminal
block types are present on all products.

Figure 190: Possible terminal block types

20.2.3 REPAIRING THE DEVICE


If your product should develop a fault while in service, depending on the nature of the fault, the watchdog contacts
will change state and an alarm condition will be flagged. In the case of a fault, either the complete unit or just the
faulty PCB, identified by the in-built diagnostic software, should be replaced.
Replacement of printed circuit boards and other internal components must be undertaken by approved Service
Centres. Failure to obtain the authorization of after-sales engineers prior to commencing work may invalidate the
product warranty.
We recommend that you entrust any repairs to Automation Support teams, which are available world-wide.

20.2.4 REMOVING THE FRONT PANEL

Warning:
Before removing the front panel to replace a PCB, you must first remove the auxiliary
power supply and wait 5 seconds for the internal capacitors to discharge. You should
also isolate voltage and current transformer connections and trip circuit.

P64-TM-EN-1 483
Chapter 20 - Maintenance and Troubleshooting P64

Caution:
Before removing the front panel, you should be familiar with the contents of the
Safety Information section of this guide or the Safety Guide SFTY/4LM, as well as the
ratings on the equipment’s rating label.

To remove the front panel:


1. Open the top and bottom access covers. You must open the hinged access covers by more than 90° before
they can be removed.
2. If fitted, remove the transparent secondary front cover.
3. Apply outward pressure to the middle of the access covers to bow them and disengage the hinge lug, so the
access cover can be removed. The screws that fasten the front panel to the case are now accessible.
4. Undo and remove the screws. The 40TE case has four cross-head screws fastening the front panel to the
case, one in each corner, in recessed holes. The 60TE/80TE cases have an additional two screws, one
midway along each of the top and bottom edges of the front plate.
5. When the screws have been removed, pull the complete front panel forward to separate it from the metal
case. The front panel is connected to the rest of the circuitry by a 64-way ribbon cable.
6. The ribbon cable is fastened to the front panel using an IDC connector; a socket on the cable and a plug with
locking latches on the front panel. Gently push the two locking latches outwards which eject the connector
socket slightly. Remove the socket from the plug to disconnect the front panel.

Caution:
Do not remove the screws with the larger diameter heads which are accessible when
the access covers are fitted and open. These screws hold the relay in its mounting
(panel or cubicle).

Caution:
The internal circuitry is now exposed and is not protected against electrostatic
discharge and dust ingress. Therefore ESD precautions and clean working conditions
must be maintained at all times.

20.2.5 REPLACING PCBS


1. To replace any of the PCBs, first remove the front panel.
2. Once the front panel has been removed, the PCBs are accessible. The numbers above the case outline
identify the guide slot reference for each printed circuit board. Each printed circuit board has a label stating
the corresponding guide slot number to ensure correct relocation after removal. To serve as a reminder of the
slot numbering there is a label on the rear of the front panel metallic screen.
3. Remove the 64-way ribbon cable from the PCB that needs replacing
4. Remove the PCB in accordance with the board-specific instructions detailed later in this section.

Note:
To ensure compatibility, always replace a faulty PCB with one of an identical part number.

20.2.5.1 REPLACING THE MAIN PROCESSOR BOARD


The main processor board is situated in the front panel. This board contains application-specific settings in its non-
volatile memory. You may wish to take a backup copy of these settings. This could save time in the re-
commissioning process.

484 P64-TM-EN-1
P64 Chapter 20 - Maintenance and Troubleshooting

To replace the main processor board:


1. Remove front panel.
2. Place the front panel with the user interface face down and remove the six screws from the metallic screen,
as shown in the figure below. Remove the metal plate.
3. Remove the screws that hold the main processor board in position.
4. Carefully disconnect the ribbon cable. Take care as this could easily be damaged by excessive twisting.
5. Replace the main processor board
6. Reassemble the front panel using the reverse procedure. Make sure the ribbon cable is reconnected to the
main processor board and that all eight screws are refitted.
7. Refit the front panel.
8. Refit and close the access covers then press the hinge assistance T-pieces so they click back into the front
panel moulding.
9. Once the unit has been reassembled, carry out the standard commissioning procedure as defined in the
Commissioning chapter.

Note:
After replacing the main processor board, all the settings required for the application need to be re-entered. This may be done
either manually or by downloading a settings file.

V01601

Figure 191: Front panel assembly

20.2.5.2 REPLACEMENT OF COMMUNICATIONS BOARDS


Most products will have at least one communications board of some sort fitted. There are several different boards
available offering various functionality, depending on the application. Some products may even be fitted with two
boards of different types.
To replace a faulty communications board:
1. Remove front panel.
2. Disconnect all connections at the rear.
3. The board is secured in the relay case by two screws, one at the top and another at the bottom. Remove
these screws carefully as they are not captive in the rear panel.
4. Gently pull the communications board forward and out of the case.
5. Before fitting the replacement PCB check that the number on the round label next to the front edge of the
PCB matches the slot number into which it will be fitted. If the slot number is missing or incorrect, write the
correct slot number on the label.

P64-TM-EN-1 485
Chapter 20 - Maintenance and Troubleshooting P64

6. Fit the replacement PCB carefully into the correct slot. Make sure it is pushed fully back and that the securing
screws are refitted.
7. Reconnect all connections at the rear.
8. Refit the front panel.
9. Refit and close the access covers then press the hinge assistance T-pieces so they click back into the front
panel moulding.
10. Once the unit has been reassembled, commission it according to the Commissioning chapter.

20.2.5.3 REPLACEMENT OF THE INPUT MODULE


Depending on the product, the input module consists of two or three boards fastened together and is contained
within a metal housing. One board contains the transformers and one contains the analogue to digital conversion
and processing electronics. Some devices have an additional auxiliary transformer contained on a third board.
To replace an input module:
1. Remove front panel.
2. The module is secured in the case by two screws on its right-hand side, accessible from the front, as shown
below. Move these screws carefully as they are not captive in the front plate of the module.
3. On the right-hand side of the module there is a small metal tab which brings out a handle (on some modules
there is also a tab on the left). Grasp the handle(s) and pull the module firmly forward, away from the rear
terminal blocks. A reasonable amount of force is needed due to the friction between the contacts of the
terminal blocks.
4. Remove the module from the case. The module may be heavy, because it contains the input voltage and
current transformers.
5. Slot in the replacement module and push it fully back onto the rear terminal blocks. To check that the module
is fully inserted, make sure the v-shaped cut-out in the bottom plate of the case is fully visible.
6. Refit the securing screws.
7. Refit the front panel.
8. Refit and close the access covers then press the hinge assistance T-pieces so they click back into the front
panel moulding.
9. Once the unit has been reassembled, commission it according to the Commissioning chapter.

Caution:
With non-mounted IEDs, the case needs to be held firmly while the module is
withdrawn. Withdraw the input module with care as it suddenly comes loose once the
friction of the terminal blocks is overcome.

Note:
If individual boards within the input module are replaced, recalibration will be necessary. We therefore recommend
replacement of the complete module to avoid on-site recalibration.

20.2.5.4 REPLACEMENT OF THE POWER SUPPLY BOARD

Caution:
Before removing the front panel, you should be familiar with the contents of the
Safety Information section of this guide or the Safety Guide SFTY/4LM, as well as the
ratings on the equipment’s rating label.

486 P64-TM-EN-1
P64 Chapter 20 - Maintenance and Troubleshooting

The power supply board is fastened to an output relay board with push fit nylon pillars. This doubled-up board is
secured on the extreme left hand side, looking from the front of the unit.
1. Remove front panel.
2. Pull the power supply module forward, away from the rear terminal blocks and out of the case. A reasonable
amount of force is needed due to the friction between the contacts of the terminal blocks.
3. Separate the boards by pulling them apart carefully. The power supply board is the one with two large
electrolytic capacitors.
4. Before reassembling the module, check that the number on the round label next to the front edge of the PCB
matches the slot number into which it will be fitted. If the slot number is missing or incorrect, write the correct
slot number on the label
5. Reassemble the module with a replacement PCB. Push the inter-board connectors firmly together. Fit the
four push fit nylon pillars securely in their respective holes in each PCB.
6. Slot the power supply module back into the housing. Push it fully back onto the rear terminal blocks.
7. Refit the front panel.
8. Refit and close the access covers then press the hinge assistance T-pieces so they click back into the front
panel moulding.
9. Once the unit has been reassembled, commission it according to the Commissioning chapter.

20.2.5.5 REPLACEMENT OF THE I/O BOARDS


There are several different types of I/O boards, which can be used, depending on the product and application.
Some boards have opto-inputs, some have relay outputs and others have a mixture of both.
1. Remove front panel.
2. Gently pull the board forward and out of the case
3. If replacing the I/O board, make sure the setting of the link above IDC connector on the replacement board is
the same as the one being replaced.
4. Before fitting the replacement board check the number on the round label next to the front edge of the board
matches the slot number into which it will be fitted. If the slot number is missing or incorrect, write the correct
slot number on the label.
5. Carefully slide the replacement board into the appropriate slot, ensuring that it is pushed fully back onto the
rear terminal blocks.
6. Refit the front panel.
7. Refit and close the access covers then press at the hinge assistance T-pieces so they click back into the front
panel moulding.
8. Once the unit has been reassembled, commission it according to the Commissioning chapter.

20.2.6 RECALIBRATION
Recalibration is not needed when a PCB is replaced, unless it is one of the boards in the input module. If any of the
boards in the input module is replaced, the unit must be recalibrated.
Although recalibration is needed when a board inside the input module is replaced, it is not needed if the input
module is replaced in its entirety.
Although it is possible to carry out recalibration on site, this requires special test equipment and software. We
therefore recommend that the work be carried out by the manufacturer, or entrusted to an approved service centre.

20.2.7 SUPERCAPACITOR DISCHARGED


The supercapacitor maintains charge for two weeks with the IED de-energised. When first energising the IED after
this time there may be a SuperCap Alarm due to the supercapacitor voltage dropping below a pre-defined

P64-TM-EN-1 487
Chapter 20 - Maintenance and Troubleshooting P64

threshold. The SuperCap Alarm will clear after approximately 30 minutes of IED being energised, and once cleared
there will be enough charge in the supercapacitor to maintain the RTC.

Note:
The Real Time Clock will be reset if the supercapacitor is fully discharged.

20.2.8 CLEANING

Warning:
Before cleaning the device, ensure that all AC and DC supplies and transformer
connections are isolated, to prevent any chance of an electric shock while cleaning.

Only clean the equipment with a lint-free cloth dampened with clean water. Do not use detergents, solvents or
abrasive cleaners as they may damage the product's surfaces and leave a conductive residue.

488 P64-TM-EN-1
P64 Chapter 20 - Maintenance and Troubleshooting

20.3 TROUBLESHOOTING

20.3.1 SELF-DIAGNOSTIC SOFTWARE


The device includes several self-monitoring functions to check the operation of its hardware and software while in
service. If there is a problem with the hardware or software, it should be able to detect and report the problem, and
attempt to resolve the problem by performing a reboot. In this case, the device would be out of service for a short
time, during which the ‘Healthy’ LED on the front of the device is switched OFF and the watchdog contact at the
rear is ON. If the restart fails to resolve the problem, the unit takes itself permanently out of service; the ‘Healthy’
LED stays OFF and watchdog contact stays ON.
If a problem is detected by the self-monitoring functions, the device attempts to store a maintenance record to allow
the nature of the problem to be communicated to the user.
The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is performed on boot-
up, and secondly a continuous self-checking operation, which checks the operation of the critical functions whilst it
is in service.

20.3.2 POWER-UP ERRORS


If the IED does not appear to power up, use the following to determine whether the fault is in the external wiring,
auxiliary fuse, IED power supply module or IED front panel.

Test Check Action


1 Measure the auxiliary voltage on terminals 1 If the auxiliary voltage is correct, go to test 2. Otherwise check the
and 2. Verify the voltage level and polarity wiring and fuses in the auxiliary supply.
against the rating label on the front.
Terminal 1 is –dc, 2 is +dc
2 Check the LEDs and LCD backlight switch on at If the LEDs and LCD backlight switch on, or the contact closes and
power-up. Also check the N/O (normally open) no error code is displayed, the error is probably on the main
watchdog contact for closing. processor board in the front panel.
If the LEDs and LCD backlight do not switch on and the contact
does not close, go to test 3.
3 Check the output (nominally 48 V DC). If there is no field voltage, the fault is probably in the IED power
supply module.

20.3.3 ERROR MESSAGE OR CODE ON POWER-UP


The IED performs a self-test during power-up. If it detects an error, a message appears on the LCD and the power-
up sequence stops. If the error occurs when the IED application software is running, a maintenance record is
created and the device reboots.

Test Check Action


1 Is an error message or code permanently displayed If the IED locks up and displays an error code permanently, go
during power up? to test 2.
If the IED prompts for user input, go to test 4.
If the IED reboots automatically, go to test 5.
2 Record displayed error, and then remove and re- Record whether the same error code is displayed when the IED
apply IED auxiliary supply. is rebooted. If no error code is displayed, contact the local
service centre stating the error code and IED information. If the
same code is displayed, go to test 3.

P64-TM-EN-1 489
Chapter 20 - Maintenance and Troubleshooting P64

Test Check Action


3 Error Code Identification These messages indicate that a problem has been detected on
The following text messages (in English) are the IED’s main processor board in the front panel.
displayed if a fundamental problem is detected,
preventing the system from booting:
Bus Fail – address lines
SRAM Fail – data lines
FLASH Fail format error
FLASH Fail checksum
Code Verify Fail
The following hex error codes relate to errors
detected in specific IED modules:

3.1 0c140005/0c0d0000 Input Module (including opto-isolated inputs)


3.2 0c140006/0c0e0000 Output IED boards
3.3 The last four digits provide details on the actual Other error codes relate to hardware or software problems on
error. the main processor board. Contact GE Vernova with details of
the problem for a full analysis.

4 The IED displays a message for corrupt settings and The power-up tests have detected corrupted IED settings.
prompts for the default values to be restored for the Restore the default settings to allow the power-up to complete,
affected settings. and then reapply the application-specific settings.

5 The IED resets when the power-up is complete. A Error 0x0E080000, programmable scheme logic error due to
record error code is displayed excessive execution time. If the IED powers up successfully,
check the programmable logic for feedback paths.
Other error codes relate to software errors on the main
processor board.

20.3.4 OUT OF SERVICE LED ON AT POWER-UP

Test Check Action


1 Using the IED menu, confirm the Commission If the setting is Enabled, disable the test mode and make sure the
Test or Test Mode setting is Enabled. If it is not Out of Service LED is OFF.
Enabled, go to test 2.
2 Select the VIEW RECORDS column then view Check for the H/W Verify Fail maintenance record. This indicates a
the last maintenance record from the menu. discrepancy between the IED model number and the hardware.
Examine the Maint Data; cell. This indicates the causes of the
failure using bit fields:
Bit Meaning
0 The application type field in the model number does not
match the software ID
1 The application field in the model number does not match
the software ID
2 The variant 1 field in the model number does not match the
software ID
3 The variant 2 field in the model number does not match the
software ID
4 The protocol field in the model number does not match the
software ID

490 P64-TM-EN-1
P64 Chapter 20 - Maintenance and Troubleshooting

Test Check Action


5 The language field in the model number does not match the
software ID
6 The VT type field in the model number is incorrect (110 V
VTs fitted)
7 The VT type field in the model number is incorrect (440 V
VTs fitted)
8 The VT type field in the model number is incorrect (no VTs
fitted)

20.3.5 ERROR CODE DURING OPERATION


The IED performs continuous self-checking. If the IED detects an error it displays an error message, logs a
maintenance record and after a short delay resets itself. A permanent problem (for example due to a hardware fault)
is usually detected in the power-up sequence. In this case the IED displays an error code and halts. If the problem
was transient, the IED reboots correctly and continues operation. By examining the maintenance record logged, the
nature of the detected fault can be determined.

20.3.6 MAL-OPERATION DURING TESTING

20.3.6.1 FAILURE OF OUTPUT CONTACTS


An apparent failure of the relay output contacts can be caused by the configuration. Perform the following tests to
identify the real cause of the failure. The self-tests verify that the coils of the output relay contacts have been
energized. An error is displayed if there is a fault in the output relay board.

Test Check Action


1 Is the Out of Service LED ON? If this LED is ON, the relay may be in test mode or the protection
has been disabled due to a hardware verify error.
2 Examine the Contact status in the Commissioning If the relevant bits of the contact status are operated, go to test
section of the menu. 4; if not, go to test 3.
3 Examine the fault record or use the test port to If the protection element does not operate, check the test is
check the protection element is operating correctly. correctly applied.
If the protection element operates, check the programmable
logic to make sure the protection element is correctly mapped to
the contacts.
4 Using the Commissioning or Test mode function, If the output relay operates, the problem must be in the external
apply a test pattern to the relevant relay output wiring to the relay. If the output relay does not operate the output
contacts. Consult the correct external connection relay contacts may have failed (the self-tests verify that the relay
diagram and use a continuity tester at the rear of coil is being energized). Ensure the closed resistance is not too
the relay to check the relay output contacts high for the continuity tester to detect.
operate.

20.3.6.2 FAILURE OF OPTO-INPUTS


The opto-isolated inputs are mapped onto the IED's internal DDB signals using the programmable scheme logic. If
an input is not recognised by the scheme logic, use the Opto I/P Status cell in the COMMISSION TESTS column to
check whether the problem is in the opto-input itself, or the mapping of its signal to the scheme logic functions.

P64-TM-EN-1 491
Chapter 20 - Maintenance and Troubleshooting P64

If the device does not correctly read the opto-input state, test the applied signal. Verify the connections to the opto-
input using the wiring diagram and the nominal voltage settings in the OPTO CONFIG column. To do this:
1. Select the nominal voltage for all opto-inputs by selecting one of the five standard ratings in the Global
Nominal V cell.
2. Select Custom to set each opto-input individually to a nominal voltage.
3. Using a voltmeter, check that the voltage on its input terminals is greater than the minimum pick-up level (See
the Technical Specifications chapter for opto pick-up levels).
If the signal is correctly applied, this indicates failure of an opto-input, which may be situated on standalone opto-
input board, or on an opto-input board that is part of the input module. Separate opto-input boards can simply be
replaced. If, however, the faulty opto-input board is part of the input module, the complete input module should be
replaced. This is because the analogue input module cannot be individually replaced without dismantling the
module and recalibration of the IED.

20.3.6.3 INCORRECT ANALOGUE SIGNALS


If the measured analogue quantities do not seem correct, use the measurement function to determine the type of
problem. The measurements can be configured in primary or secondary terms.
1. Compare the displayed measured values with the actual magnitudes at the terminals.
2. Check the correct terminals are used.
3. Check the CT and VT ratios set are correct.
4. Check the phase displacement to confirm the inputs are correctly connected.

20.3.7 PSL EDITOR TROUBLESHOOTING


A failure to open a connection could be due to one or more of the following:
● The IED address is not valid (this address is always 1 for the front port)
● Password in not valid
● Communication set-up (COM port, Baud rate, or Framing) is not correct
● Transaction values are not suitable for the IED or the type of connection
● The connection cable is not wired correctly or broken
● The option switches on any protocol converter used may be incorrectly set

20.3.7.1 DIAGRAM RECONSTRUCTION


Although a scheme can be extracted from an IED, a facility is provided to recover a scheme if the original file is
unobtainable.
A recovered scheme is logically correct but much of the original graphical information is lost. Many signals are
drawn in a vertical line down the left side of the canvas. Links are drawn orthogonally using the shortest path from A
to B. Any annotation added to the original diagram such as titles and notes are lost.
Sometimes a gate type does not appear as expected. For example, a single-input AND gate in the original scheme
appears as an OR gate when uploaded. Programmable gates with an inputs-to-trigger value of 1 also appear as OR
gates

20.3.7.2 PSL VERSION CHECK


The PSL is saved with a version reference, time stamp and CRC check (Cyclic Redundancy Check). This gives a
visual check whether the default PSL is in place or whether a new application has been downloaded.

492 P64-TM-EN-1
P64 Chapter 20 - Maintenance and Troubleshooting

20.3.8 REPAIR AND MODIFICATION PROCEDURE


Please follow these steps to return an Automation product to us:
1. Get the Repair and Modification Return Authorization (RMA) form
An electronic version of the RMA form is available from the following:
GA.support@gevernova.com
2. Fill in the RMA form
Fill in only the white part of the form.
Please ensure that all fields marked (M) are completed such as:
○ Equipment model
○ Model No. and Serial No.
○ Description of failure or modification required (please be specific)
○ Value for customs (in case the product requires export)
○ Delivery and invoice addresses
○ Contact details
3. Send the RMA form to your local contact
For a list of local service contacts worldwide, email us at:
GA.support@gevernova.com
4. The local service contact provides the shipping information
Your local service contact provides you with all the information needed to ship the product:
○ Pricing details
○ RMA number

○ Repair centre address

If required, an acceptance of the quote must be delivered before going to the next stage.
5. Send the product to the repair centre
○ Address the shipment to the repair centre specified by your local contact
○ Make sure all items are packaged in an anti-static bag and foam protection
○ Make sure a copy of the import invoice is attached with the returned unit
○ Make sure a copy of the RMA form is attached with the returned unit
○ E-mail or fax a copy of the import invoice and airway bill document to your local contact.

P64-TM-EN-1 493
Chapter 20 - Maintenance and Troubleshooting P64

494 P64-TM-EN-1
CHAPTER 21

TECHNICAL SPECIFICATIONS
Chapter 21 - Technical Specifications P64

21.1 CHAPTER OVERVIEW


This chapter describes the technical specifications of the product.
This chapter contains the following sections:
Chapter Overview 496
Interfaces 497
Performance of Transformer Differential Protection and Monitoring Functions 501
Performance of Current Protection Functions 504
Performance of Voltage Protection Functions 507
Performance of Frequency Protection Functions 509
Performance of Monitoring and Control Functions 510
Measurements and Recording 512
Ratings 514
Input/Output Connections 517
Mechanical Specifications 519
Type Tests 520
Environmental Conditions 521
Electromagnetic Compatibility 522

496 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.2 INTERFACES

21.2.1 GRAPHICAL HMI

Graphical HMI
Screen size 4.0" diagonal
Display format 480 x 480 Dots
Number of colour 16.7M
Dimensions 77 mm (H) x 80 mm (V) x 2.3 mm (D)
Active area 71.86 mm (H) x 70.18 mm (V)
Display mode Transmissive/normally black
Viewing direction All round
Backlight type LED, white
Operating temperature -30°C ~ + 85°C
Storage temperature -40°C ~ + 90°C

21.2.2 FRONT USB PORT

Front USB port


Use For local connection to laptop for configuration purposes and firmware downloads
Connector USB type B
Isolation Isolation to ELV level
Constraints Maximum cable length 5 m

21.2.3 REAR SERIAL PORT 1

Rear serial port 1 (RP1)


Use For SCADA communications (multi-drop)
Standard EIA(RS)485, K-bus
Connector General purpose block, M4 screws (2 wire)
Cable Screened twisted pair (STP)
Supported Protocols * Courier, IEC-60870-5-103, DNP3.0
Isolation Isolation to SELV level
Constraints Maximum cable length 1000 m

21.2.4 FIBRE REAR SERIAL PORT 1

Optional fibre rear serial port (RP1)


Main Use Serial SCADA communications over fibre
Connector IEC 874-10 BFOC 2.5 –(ST®) (1 each for Tx and Rx)
Fibre type Multimode 50/125 µm or 62.5/125 µm
Supported Protocols Courier, IEC870-5-103, DNP 3.0
Wavelength 850 nm

P64-TM-EN-1 497
Chapter 21 - Technical Specifications P64

21.2.5 REAR SERIAL PORT 2

Optional rear serial port (RP2)


Use For SCADA communications (multi-drop)
Standard EIA(RS)485, K-bus, EIA(RS)232
Designation SK4
Connector 9 pin D-type female connector
Cable Screened twisted pair (STP)
Supported Protocols Courier
Isolation Isolation to SELV level
Constraints Maximum cable length 1000 m for RS485 and K-bus, 15 m for RS232

21.2.6 OPTIONAL REAR SERIAL PORT (SK5)

Optional rear serial port for teleprotection


Use For teleprotection in distance products
Standard EIA(RS)232
Designation SK5
Connector 9 pin D-type female connector
Cable Screened twisted pair (STP)
Supported Protocols InterMiCOM (IM)
Isolation Isolation to SELV level
Constraints Maximum cable length 15 m

21.2.7 IRIG-B (DEMODULATED)

IRIG-B Interface (Demodulated)


Use External clock synchronisation signal
Standard IRIG 200-98 format B00X
Connector BNC
Cable type 50 ohm coaxial
Isolation Isolation to SELV level
Input signal TTL level
Input impedance 10 k ohm at dc
Accuracy +/- 1 ms

21.2.8 IRIG-B (MODULATED)

IRIG-B Interface (Modulated)


Use External clock synchronisation signal
Standard IRIG 200-98 format B12X
Connector BNC
Cable type 50 ohm coaxial
Isolation Isolation to SELV level

498 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

IRIG-B Interface (Modulated)


Input signal peak to peak, 200 mV to 20 mV
Input impedance 6 k ohm at 1000 Hz
Accuracy +/- 1 ms

21.2.9 REAR ETHERNET PORT COPPER

Rear Ethernet Port Using CAT 5/6/7 Wiring


Main Use Substation Ethernet communications
Standard IEEE 802.3 10BaseT/100BaseTX
Connector RJ45
Cable type Screened twisted pair (STP)
Isolation 1.5 kV
Supported Protocols Courier (tunnelled), IEC 61850, PTP, SNTP, SNMP, RADIUS, syslog
PRP (Parallel Redundancy Protocol)
HSR (High-availability Seamless Redundancy)
Redundancy Protocols Supported
RSTP (Rapid Spanning Tree Protocol)
Failover
Constraints Maximum cable length 100 m

21.2.10 REAR ETHERNET PORT FIBRE

Rear Ethernet Port Using Fibre-optic Cabling


Main Use Substation Ethernet communications
Connector IEC 874-10 BFOC 2.5 - (LC®) (1 each for Tx and Rx)
Standard IEEE 802.3 100 BaseFX
Fibre type Multimode 50/125 µm (OM2 or OM3) or 62.5/125 µm (OM1)
Supported Protocols Courier (tunnelled), IEC 61850, PTP, SNTP, SNMP, RADIUS, syslog
PRP (Parallel Redundancy Protocol)
HSR (High-availability Seamless Redundancy)
Redundancy Protocols Supported
RSTP (Rapid Spanning Tree Protocol)
Failover
Wavelength 1310 nm

21.2.10.1 100 BASE FX RECEIVER CHARACTERISTICS

Parameter Sym Min. Typ. Max. Unit


Input Optical Power Minimum at
PIN Min. (W) -31.0 -12.0 dBm avg.
Window Edge
Input Optical Power Minimum at
PIN Min. (C) -34.5 -31.8 Bm avg.
Eye Center
Input Optical Power Maximum PIN Max. -14 -11.8 dBm avg.

Conditions: TA = 0°C to 70°C

P64-TM-EN-1 499
Chapter 21 - Technical Specifications P64

21.2.10.2 100 BASE FX TRANSMITTER CHARACTERISTICS

Parameter Sym Min. Typ. Max. Unit


Output Optical Power BOL 62.5/125 µm PO -20 -17.0 -14.0 dBm avg.
NA = 0.275 Fibre EOL
Output Optical Power BOL 50/125 µm PO -24.0 -21.0 -17.0 dBm avg.
NA = 0.20 Fibre EOL
Optical Extinction Ratio ER 10 dB
Output Optical Power at Logic "0" State PO(off) -45 dBm avg.

Conditions: TA = 0°C to 70°C

500 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.3 PERFORMANCE OF TRANSFORMER DIFFERENTIAL


PROTECTION AND MONITORING FUNCTIONS

21.3.1 TRANSFORMER DIFFERENTIAL PROTECTION

Accuracy
Pick-up Formula +/-5% or 20 mA, whichever is greater
Drop-off 0.95 x formula +/- 5% or 20 mA, whichever is greater
Pick-up and drop-off repeatability < 1%
Low set differential element operate time (High Break
< 33 ms (currents applied at 1.2x pickup level or higher)
contact)
Low set differential element operate time (Standard
< 36 ms (currents applied at 1.2x pickup level or higher)
Contact)
High set 1 differential element operate time
< 15 ms (currents applied at 2x pickup level or higher)
(Transient Bias disabled)
High set 2 differential element operate time
< 25 ms (currents applied at 2x pickup level or higher)
(High Break contact)
< 33 ms, whichever is greater (currents applied at 1.2x pickup level
DT operate time (High Break contact)
or higher
< 36 ms, whichever is greater (currents applied at 1.2x pickup level
DT operate time (Standard contact)
or higher
Operate time repeatability < 2 ms
Disengagement time < 15 ms
2nd harmonic blocking pick-up Setting +/-5% of setting or 20 mA, whichever is greater
2nd harmonic blocking drop-off 0.95 x setting +/-5% or 20 mA, whichever is greater
5th harmonic blocking pick-up Setting +/-5% of setting or 20 mA, whichever is greater
5th harmonic blocking drop-off 0.95 x setting +/-5% or 20 mA, whichever is greater

Note:
Transformer differential protection operating times are with the Diff Protection - Phase Comparison setting Disabled.

21.3.2 MATCHING FACTORS

Matching factor for typical setting


CT Type Max. sensitivity Permitted Matching Factor range
Is1 = 0.2 pu
Standard 43 mA 0.05 - 15 4.65
Sensitive 13 mA 0.05 - 20 15.38

21.3.3 CIRCUITRY FAULT ALARM

Pick-up Formula +/- 5% (for Is-cctfail > 0.05 pu)


Drop-off 0.95 x formula +/- 5% or 20 mA, whichever is greater

P64-TM-EN-1 501
Chapter 21 - Technical Specifications P64

Pick-up and drop-off repeatability < 4%


DT operate < 26 ms (currents applied at 2.5x pickup level or higher)
Operate time repeatability < 8 ms
Disengagement time < 26 ms
Timer +/- 2% or 50 ms, whichever is greater

21.3.4 THROUGH FAULT MONITORING

Overcurrent pick-up Setting +/-5% or 50 mA, whichever greater


Overcurrent drop-off 0.95 x setting +/- 5% or 50 mA, whichever is greater
Heating pickup (I2t) Setting +/-2% or 5 A2s, whichever greater

21.3.5 THERMAL OVERLOAD

Accuracy
Hot Spot pick-up Expected pick-up time +/-5% or 50 ms, whichever greater.
(Expected pick-up time is the time required to reach the temperature
setting)
Hot Spot operate DT +/-5% or <= 50 ms, whichever greater
Top Oil pick-up Expected pick-up time +/-5% or 50 ms, whichever greater
Top Oil operate DT +/-5% or <= 50 ms, whichever greater
Repeatability < 2.5%

21.3.6 TRANSFORMER AND LOSS OF LIFE

Loss of Life
FAA > pick-up Formula: +/-5%
Loss of life > pick-up Expected pick-up current +/-5%
Repeatability < 2.5%
FAA > DT ±5% or 200 ms, whichever is greater

21.3.7 LOW IMPEDANCE RESTRICTED EARTH FAULT

Pick-up Formula +/-5% or 20 mA, whichever is greater


Drop-off 0.9 x formula +/- 5% or 20 mA, whichever is greater
Pick-up and drop-off repeatability < 5%
Operate time < 30 ms (currents applied at 3x pickup level or higher)
Operate time repeatability < 5 ms
Disengagement time < 30 ms

502 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.3.8 HIGH IMPEDANCE RESTRICTED EARTH FAULT

Pick-up Formula +/-5% or 20 mA, whichever is greater


Drop-off 0.9 x formula +/- 5% or 20 mA, whichever is greater
Pick-up and drop-off repeatability < 5%
Operate time < 30 ms
Operate time repeatability < 5 ms
Disengagement time < 30 ms

P64-TM-EN-1 503
Chapter 21 - Technical Specifications P64

21.4 PERFORMANCE OF CURRENT PROTECTION FUNCTIONS

21.4.1 TRANSIENT OVERREACH AND OVERSHOOT

Accuracy
Additional tolerance due to increasing X/R ratios +/-5% over the X/R ratio of 1 to 120
Overshoot of overcurrent elements < 40 ms
Disengagement time < 30 ms

21.4.2 THREE-PHASE OVERCURRENT PROTECTION

Accuracy
IDMT pick-up 1.05 x Setting +/-5% or 20 mA, whichever is greater
DT pick-up Setting +/-5% or 20 mA, whichever is greater
Drop-off (IDMT and DT) 0.95 x setting +/-5% or 20 mA, whichever is greater
IDMT operate +/-5% of expected operating time or 40 ms, whichever is greater
IEEE reset +/-5% or 50 ms, whichever is greater
DT operate +/-2% of setting or 50 ms, whichever is greater
DT reset Setting +/-5%
Characteristic UK IEC 60255-3 1998
Characteristic US IEEE C37.112 1996

21.4.2.1 THREE-PHASE OVERCURRENT DIRECTIONAL PARAMETERS

Accuracy
Directional boundary pickup (RCA +/-90%) +/-2°
Directional boundary hysteresis < 3°
Directional boundary repeatability <1%
Directional voltage pick-up +/-5% or 50 mV, whichever is greater
Directional voltage drop-off 0.95 x setting +/-5% or 50 mV, whichever is greater
Directional voltage repeatability <3%

21.4.3 VOLTAGE DEPENDENT OVERCURRENT PROTECTION

Accuracy
Voltage threshold pick-up Setting +/- 5%
Voltage threshold drop-off 1.05 x setting +/- 5%
Current threshold pick-up Formula +/- 5% or 50 mA, whichever is greater
Current threshold drop-off 0.95 x formula +/- 5% or 50 mA, whichever is greater

Note:
Reference conditions: IDMT accuracy = +/- 5% or 50 ms for M value above 1.1

504 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.4.4 EARTH FAULT PROTECTION

Accuracy
IDMT pick-up 1.05 x Setting +/-5% or 20 mA, whichever is greater
DT pick-up Setting +/-5%, or 20 mA, whichever is greater
Measured drop-off (IDMT and DT) 0.95 x setting +/-5% or 20 mA, whichever is greater
Derived drop-off (IDMT and DT) 0.9 x setting +/-5% or 20 mA, whichever is greater
IDMT Operate +/-5% or 40 ms, whichever is greater*
IEEE reset +/-5% or 40 ms, whichever is greater
Pick-up and drop-off repeatability < 2%
DT operate time +/-2% or 50 ms, whichever is greater
DT reset time +/- 5%

Note:
Reference conditions: TMS = 1, TD = 1, IN> = 1A, operating range = 2-16In

21.4.4.1 EARTH FAULT DIRECTIONAL PARAMETERS

Measured and Derived


Vpol pick-up Vpol +/-5% or 50 mV, whichever is greater
Vpol drop-off 0.95 x Vpol +/-5% or 50 mV, whichever is greater
Directional boundary pickup (RCA +/-90%) +/- 2°
Directional boundary hysteresis < 1°
Directional boundary repeatability < 1%

21.4.5 NEGATIVE SEQUENCE OVERCURRENT PROTECTION

Pick-up (IDMT and DT) Setting +/-5% or 20 mA, whichever is greater


Drop-off (IDMT and DT) 0.95 x Setting +/-5% or 20 mA, whichever is greater
Pick-up and drop-off repeatability < 1%
Disengagement time < 35 ms
DT operate +/- 2% or 60 ms, whichever is greater
Operate time repeatability < 6 ms

21.4.5.1 NPSOC DIRECTIONAL PARAMETERS

Directional boundary pick-up (RCA +/-90%) +/-2°


Directional boundary hysteresis < 2°
Directional boundary repeatability < 2%
Vpol pickup Setting +/-5% or 50 mV, whichever is greater
Vpol drop-off 0,95 x setting +/-5% or 50 mV, whichever is greater

P64-TM-EN-1 505
Chapter 21 - Technical Specifications P64

21.4.6 CIRCUIT BREAKER FAIL PROTECTION

I< Pick-up 1.1 X setting +/- 5% or 20 mA, whichever is greater


I< Drop-off Setting +/- 5% or 20 mA, whichever is greater
Timers +/- 2% or 50 ms, whichever is greater
Reset time < 15 ms (fully offset current waveform considered)

506 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.5 PERFORMANCE OF VOLTAGE PROTECTION FUNCTIONS

21.5.1 UNDERVOLTAGE PROTECTION (P643/5)

Pick-up (IDMT and DT) Setting +/- 5%


Drop-off (IDMT and DT) 1.02 x Setting +/-5%
Operate (IDMT and DT) +/- 2% or 50 ms, whichever is greater
Reset < 50 ms
Repeatability < 1%

21.5.2 OVERVOLTAGE PROTECTION

Pick-up (IDMT and DT) Setting +/- 5%


Drop-off (IDMT and DT) 0.98 x Setting +/-5%
Operate (IDMT and DT) +/- 2% or 50 ms, whichever is greater
Reset < 50 ms
Repeatability < 1%

21.5.3 RESIDUAL OVERVOLTAGE PROTECTION (P643/5)

Pick-up (IDMT and DT) Setting +/- 5% or 50 mV, whichever is greater


Drop-off (IDMT and DT) 0.95 x Setting +/-5%
IDMT operate +/- 2% or 55 ms, whichever is greater
DT operate +/- 2% or 70 ms or whichever is greater
Reset time < 50 ms
Disengagement time < 35 ms
Pick-up and drop-off repeatability <1%
Timer repeatability < 10 ms

21.5.4 NEGATIVE SEQUENCE VOLTAGE PROTECTION

DT Pick-up Setting +/- 5%


DT Drop-off 0.95 x Setting +/-5%
+/- 2% or 50 ms, whichever is greater (accelerated mode)
DT operate
+/- 2% or 60 ms, whichever is greater (normal mode)
Disengagement time <35 ms
Operating time Repeatability < 5 ms
Operating threshold repeatability < 1%

P64-TM-EN-1 507
Chapter 21 - Technical Specifications P64

Note:
Reference conditions: IDMT accuracy = +/- 5% or 50 ms for M value above 1.1

508 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.6 PERFORMANCE OF FREQUENCY PROTECTION FUNCTIONS

21.6.1 OVERFREQUENCY PROTECTION

Pick-up Setting +/- 10 mHz


Drop-off Setting -25 mHz +/- 10 mHz
+/- 2% or 70 ms, whichever is greater (excluding frequency
DT operate
tracking time delay)
Repeatability < 1%

21.6.2 UNDERFREQUENCY PROTECTION

Pick-up Setting +/- 10 mHz


Drop-off Setting +25 mHz +/- 10 mHz
+/- 2% or 70 ms, whichever is greater (excluding frequency
DT Operate
tracking time delay)
Repeatability < 1%

21.6.3 OVERFLUXING PROTECTION

Pick-up Setting +/- 5%


Drop-off Setting -2% +/- 5%
Repeatability (operating threshold) < 1%
IDMT operate +/- 5% or 50 ms, whichever is greater
DT operate +/- 2% or 50 ms, whichever is greater
Instantaneous operation < 50 ms
Disengagement time < 50 ms
Repeatability (operating times) < 10 ms
V / Hz measurement +/- 1%
Reset time +/- 2% or 50 ms, whichever is greater

Note:
Reference conditions: IDMT accuracy = +/- 5% or 50 ms for M value above 1.1

P64-TM-EN-1 509
Chapter 21 - Technical Specifications P64

21.7 PERFORMANCE OF MONITORING AND CONTROL FUNCTIONS

21.7.1 VOLTAGE TRANSFORMER SUPERVISION

VTS I> pick-up Setting +/- 5% or 50 mA, whichever is greater


VTS I> drop-off 0.9 x Setting +/- 5% or 50 mA, whichever is greater
VTS I2> pick-up Setting +/- 5% or 50 mA, whichever is greater
VTS I> drop-off 0.95 x Setting +/- 5% or 50 mA, whichever is greater
VTS V< pick-up (P642) 70V +/- 5%
VTS V< pick-up (P643/5) 10V +/- 5%
VTS V< drop-off (P642) 95V +/- 5%
VTS V< drop-off (P643/5) 30V +/- 5%
VTS V2> pick-up (P642/3/5) 10V +/- 5%
VTS V2> drop-off (P642/3/5) 9.5V +/- 5%
Fast block operation < 25 ms
Fast block reset < 30 ms
Time delay Setting +/- 2% or 50 ms, whichever is greater
Pick-up and drop-off repeatability < 1%

21.7.2 CURRENT TRANSFORMER SUPERVISION

CTS I1 pick-up ratio Setting +/- 5% or 20 mA, whichever is greater


CTS I2/I1>1 pick-up ratio 0.95 x Setting +/- 5% or 20 mA, whichever is greater
CTS I2/I1>2 pick-up ratio 1.05 x setting +/- 5% or 20 mA, whichever is greater
CTS I1 drop-off ratio 0.95 x setting +/-5% or 20 mA, whichever is greater
CTS I2/I1>1 drop-off ratio Setting +/-5% or 20 mA, whichever is greater
CTS I2/I1>2 drop-off ratio Setting +/-5% or 20 mA, whichever is greater
Pick-up and drop-off repeatability < 3%
Time delay operation Setting +/-2% or 50 ms, whichever is greater
CTS terminal block operation < 25 ms
CTS differential block operation < 30 ms
CTS reset time < 25 ms
CTS disengagement time < 30 ms

21.7.3 POLE DEAD PROTECTION

Current pick-up 50 mA +/- 20 mA


Current drop-off 55 mA +/- 20 mA
Voltage pick-up 10V +/- 5%

510 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

Voltage drop-off 30V +/- 5%


DT operate < 50 ms

21.7.4 PSL TIMERS

Output conditioner timer Setting ±2% or 50 ms, whichever is greater


Dwell conditioner timer Setting ±2% or 50 ms, whichever is greater
Pulse conditioner timer Setting ±2% or 50 ms, whichever is greater

P64-TM-EN-1 511
Chapter 21 - Technical Specifications P64

21.8 MEASUREMENTS AND RECORDING

21.8.1 GENERAL

General Measurement Accuracy


General measurement accuracy Typically +/- 1%, but +/- 0.5% between 0.2 - 2 In/Vn
Phase 0° to 360° +/- 0.5%
Current (0.05 to 3 In) +/- 1.0% of reading, or 4mA (1A input), or 20mA (5A input)
Voltage (0.05 to 2 Vn) +/- 1.0% of reading
Frequency (45 to 65 Hz) +/- 0.025 Hz
Power (W) (0.2 to 2 Vn and 0.05 to 3 In) +/- 5.0% of reading at unity power factor
Reactive power (Vars) (0.2 to 2 Vn and 0.05 to 3 In) +/- 5.0% of reading at zero power factor
Apparent power (VA) (0.2 to 2 Vn and 0.05 to 3 In) +/- 5.0% of reading
Energy (Wh) (0.2 to 2 Vn and 0.2 to 3 In) +/- 5.0% of reading at unity power factor
Energy (Varh) (0.2 to 2 Vn and 0.2 to 3In) +/- 5.0% of reading at zero power factor

21.8.2 DISTURBANCE RECORDS

Disturbance Records Measurement Accuracy


Minimum record duration 0.1 s
Maximum record duration 10.5 s
Minimum number of records at 10.5 seconds 100
Magnitude and relative phases accuracy +/- 5% of applied quantities
Duration accuracy +/- 2%
Trigger position accuracy +/- 2% (minimum Trigger 100 ms)

21.8.3 EVENT, FAULT AND MAINTENANCE RECORDS

Event, Fault & Maintenance Records


Record location Flash memory
Viewing method Front panel display or Settings Application Software
Extraction method Extracted via USB, RP1, RP2, NIC (Ethernet) port
Number of event records Up to 5000 time tagged event records (newest overwrites oldest)
Number of fault records Up to 100
Number of maintenance records Up to 10
Event time stamp resolution 1 ms

21.8.4 RESISTIVE TEMPERATURE DETECTORS

Accuracy
Pick-up: Setting ±1°C

512 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

Accuracy
Drop-off: (Setting -1°C)
Operating time: ±2% or <3 s

P64-TM-EN-1 513
Chapter 21 - Technical Specifications P64

21.9 RATINGS

21.9.1 AC MEASURING INPUTS

AC Measuring Inputs
Nominal frequency 50 Hz or 60 Hz (settable)
Operating range 45 to 65 Hz
Phase rotation ABC or CBA

21.9.2 CURRENT TRANSFORMER INPUTS


AC Current Inputs
Nominal current (In) 1A or 5A
Nominal burden per phase < 0.2 VA at In
20 A (continuous operation)
AC current thermal withstand (5A input) 150 A (for 10 s)
500 A (for 1 s)
4 A (continuous operation)
AC current thermal withstand (1A input) 30 A (for 10 s)
100 A (for 1 s)
Standard: Linear up to 64 × In (non-offset AC current)
Linearity
Sensitive: Linear up to 2 × In (non-offset AC current)

21.9.3 VOLTAGE TRANSFORMER INPUTS

AC Voltage Inputs
Version 100 V to 120 V (ph-ph) 380 V to 480 V (ph-ph)
< 0.003 VA @ Vn (ph-n); Vn < 120/Ö3 V < 0.02 VA @ Vn (ph-n); Vn < 440/3Ö V
(ph-n) (ph-n)
Nominal burden per VT input *1
< 0.01 VA @ Vn (ph-n); Vn < 240/Ö3 V < 0.07 VA @ Vn (ph-n); Vn < 880/3Ö V
(ph-n) (ph-n)
Linearity for each VT input Linear up to 200 Vac rms Linear up to 800 Vac rms
Continuous rating for each VT input 240 Vac rms 880 Vac rms
10 seconds rating for each VT input 312 Vac rms 1144 Vac rms

Note:
Reference Conditions: *1 = Overfrequency operating range 50/60 Hz and over temperature range 20° +/- 5° C.

514 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.9.4 AUXILIARY SUPPLY VOLTAGE

CORTEC option (DC only)


24 to 48 V DC
CORTEC option (rated for AC or DC operation)
48 to 110 V DC
Nominal operating range
40 to 100 V AC rms
CORTEC option (rated for AC or DC operation)
110 to 250 V DC
100 to 240 V AC rms
CORTEC option (DC only)
19 to 65 V DC
CORTEC option (rated for AC or DC operation)
37 to 150 V DC
Maximum operating range
32 to 110 V AC rms
CORTEC option (rated for AC or DC operation)
87 to 300 V DC
80 to 265 V AC rms
Frequency range for AC supply 45 to 65 Hz
Ripple <15% for a DC supply (compliant with IEC 60255-26:2013)
Power up time < 11 seconds

21.9.5 NOMINAL BURDEN

Quiescent burden 11.2 W or 22 VA


2nd rear communications port 1.25 W or 2.5 VA
Each relay output burden 0.13 W or 0.25 VA per output relay
Each opto-input burden (24 – 27 V) 0.065 W or 0.13 VA max
Each opto-input burden (30 – 34 V) 0.065 W or 0.13 VA max
Each opto-input burden (48 – 54 V) 0.125 W or 0.25 VA max
Each opto-input burden (110 – 125 V) 0.36 W or 0.72 VA max
Each opto-input burden (220 – 250 V) 0.9 W or 1.8 VA max

21.9.6 POWER SUPPLY INTERRUPTION

Standard IEC 60255-26:2013 (DC and AC)


20 ms at 24 V (half and full load)
24-48V DC SUPPLY
50 ms at 36 V (half and full load)
100% interruption without de-energising
100 ms at 48 V (half and full load)
20 ms at 37V (half and full load)
50 ms at 60 V (half and full load)
48-110V DC SUPPLY
100 ms at 72 V (half load)
100% interruption without de-energising
100 ms at 85 V (full load)
200 ms at 110 V (half and full load)

P64-TM-EN-1 515
Chapter 21 - Technical Specifications P64

20 ms at 87 V (half load)
50 ms at 110 V (half load)
50 ms at 98 V (full load)
110-250V DC SUPPLY
100 ms at 160 V (half load)
100% interruption without de-energising
100 ms at 135 V (full load)
200 ms at 210 V (half load)
200 ms at 174 V (full load)
40-100V AC SUPPLY 50 ms at 32 V (half load)
100% voltage dip without de-energising 10 ms at 32 V (full load)
100-240V AC SUPPLY
50 ms at 80 V (full and half load)
100% voltage dip without de-energising

Note:
Maximum loading = all inputs/outputs energised.

Note:
Quiescent or 1/2 loading = 1/2 of all inputs/outputs energised.

21.9.7 SUPERCAPACITOR

Discharge time >14 days

516 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.10 INPUT/OUTPUT CONNECTIONS

21.10.1 ISOLATED DIGITAL INPUTS

Opto-isolated digital inputs (opto-inputs)


Compliance ESI 48-4
Rated nominal voltage 24 to 250 V dc
Operating range 19 to 265 V dc
Withstand 300 V dc
Recognition time with half-cycle ac
< 2 ms
immunity filter removed
Recognition time with filter on < 12 ms

21.10.1.1 NOMINAL PICKUP AND RESET THRESHOLDS

Nominal battery
Logic levels: 60-80% DO/PU Logic Levels: 50-70% DO/PU
voltage
24/27 V Logic 0 < 16.2V, Logic 1 > 19.2V Logic 0 <12V, Logic 1 > 16.8V
30/34 Logic 0 < 20.4V, Logic 1 > 24V Logic 0 < 15V, Logic 1 > 21V
48/54 Logic 0 < 32.4V, Logic 1 > 38.4V Logic 0 < 24V, Logic 1 > 33.6V
110/125 Logic 0 < 75V, Logic 1 > 88V Logic 0 < 55.V, Logic 1 > 77V
220/250 Logic 0 < 150V, Logic 1 > 176V Logic 0 < 110V, Logic 1 > 154V

Note:
Filter is required to make the opto-inputs immune to induced AC voltages.

In addition to the above thresholds, some models of this product provide the following threshold levels for FSK
applications:
● For 220/250 voltage inputs: Logic 0 < 145V, Logic 1 > 165V

21.10.2 STANDARD OUTPUT CONTACTS

Compliance In accordance with IEC 60255-1:2009


Use General purpose relay outputs for signalling, tripping and alarming
Rated voltage 300 V
Maximum continuous current 10 A
30 A for 3 s
Short duration withstand carry
250 A for 30 ms
Make and break, dc resistive 50 W
Make and break, dc inductive 62.5 W (L/R = 50 ms)
Make and break, ac resistive 2500 VA resistive (cos phi = unity)
Make and break, ac inductive 2500 VA inductive (cos phi = 0.7)
Make and carry, dc resistive 30 A for 3 s, 10000 operations (subject to a maximum load of 7500W))

P64-TM-EN-1 517
Chapter 21 - Technical Specifications P64

4 A for 1.5 s, 10000 operations (subject to the above limit for make and break, dc
Make, carry and break, dc resistive
resistive load)
0.5 A for 1 s, 10000 operations (subject to the above limit for make and break, dc
Make, carry and break, dc inductive
inductive load)
Make, carry and break ac resistive 30 A for 200 ms, 2000 operations (subject to the above limits)
Make, carry and break ac inductive 10 A for 1.5 s, 10000 operations (subject to the above limits)
Loaded contact 10000 operations min.
Unloaded contact 100000 operations min.
Operate time < 5 ms
Reset time < 10 ms

21.10.3 HIGH BREAK OUTPUT CONTACTS

Compliance In accordance with IEC 60255-1:2009


Use For applications requiring high rupture capacity
Rated voltage 300 V
Maximum continuous current 10 A DC
30 A DC for 3 s
Short duration withstand carry
250 A for 30 ms
Make and break, dc resistive 7500 W
Make and break, dc inductive 2500 W (L/R = 50 ms)
Make and carry, dc resistive 30 A for 3 s, 10000 operations (subject to the above limits)
30 A for 3 s, 5000 operations (subject to the above limit for make and break, dc
resistive load)
Make, carry and break, dc resistive
30 A for 200 ms, 10000 operations (subject to the above limit for make and break,
dc resistive load)
10 A for 40 ms, 10000 operations (subject to the above limit for make and break,
dc inductive load)
Make, carry and break, dc inductive
10 A for 20 ms (250V, 4 shots per second, subject to the above limit for make and
break, dc inductive load)
Loaded contact 10,000 operations minimum.
Unloaded contact 100,000 operations minimum.
Operate time < 0.2 ms
Reset time < 8 ms
MOV Protection Maximum voltage 330 V DC

21.10.4 WATCHDOG CONTACTS

Use Non-programmable contacts for relay healthy/relay fail indication


Breaking capacity, dc resistive 30 W
Breaking capacity, dc inductive 15 W (L/R = 40 ms)
Breaking capacity, ac inductive 375 VA inductive (cos phi = 0.7)

518 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.11 MECHANICAL SPECIFICATIONS

21.11.1 PHYSICAL PARAMETERS

40TE
Case Types* 60TE
80TE
Weight (40TE case) 7 kg – 8 kg (depending on chosen options)
Weight (60TE case) 9 kg – 12 kg (depending on chosen options)
Weight (80TE case) 13 kg - 16 kg (depending on chosen options)
Dimensions in mm (w x h x l) (40TE case) W: 206.0 mm H: 177.0 mm D: 243.1 mm
Dimensions in mm (w x h x l) (60TE case) W: 309.6 mm H: 177.0 mm D: 243.1 mm
Dimensions in mm (w x h x l) (80TE case) W 413.2 mm H 177.0 mm D 243.1 mm
Mounting Panel, rack, or retrofit

Note:
*Case size is product dependent.

21.11.2 ENCLOSURE PROTECTION

Against dust and dripping water (front face) IP52 as per IEC 60529:1989/A2:2013
Protection against dust (whole case) IP50 as per IEC 60529:1989/A2:2013
Protection for sides of the case (safety) IP30 as per IEC 60529:1989/A2:2013
Protection for rear of the case (safety) IP10 as per IEC 60529:1989/A2:2013

21.11.3 MECHANICAL ROBUSTNESS

Vibration test per EN 60255-21-1:1998 Response: class 2, Endurance: class 2


Shock response: class 2, Shock withstand: class 1, Bump
Shock and bump immunity per EN 60255-21-2:1988
withstand: class 1
Seismic test per EN 60255-21-3: 1993 Class 2

21.11.4 TRANSIT PACKAGING PERFORMANCE

Primary packaging carton protection ISTA 1C


Vibration tests 3 orientations, 7 Hz, amplitude 5.3 mm, acceleration 1.05g
10 drops from 610 mm height on multiple carton faces, edges and
Drop tests
corners

P64-TM-EN-1 519
Chapter 21 - Technical Specifications P64

21.12 TYPE TESTS

21.12.1 INSULATION

Compliance IEC 60255-27: 2013


Insulation resistance > 100 M ohm at 500 V DC (Using only electronic/brushless insulation tester)

21.12.2 CREEPAGE DISTANCES AND CLEARANCES

Compliance IEC 60255-27: 2013


Pollution degree 3
Overvoltage category lll
Impulse test voltage (not RJ45) 5 kV
Impulse test voltage (RJ45) 1 kV

21.12.3 HIGH VOLTAGE (DIELECTRIC) WITHSTAND

IEC Compliance IEC 60255-27: 2013


Between all independent circuits 2 kV ac rms for 1 minute
Between independent circuits and protective earth conductor terminal 2 kV ac rms for 1 minute
Between all case terminals and the case earth 2 kV ac rms for 1 minute
Across open watchdog contacts 1 kV ac rms for 1 minute
Across open contacts of changeover output relays 1 kV ac rms for 1 minute
Between all RJ45 contacts and protective earth 1 kV ac rms for 1 minute
Between all screw-type EIA(RS)485 contacts and protective earth 1 kV ac rms for 1 minute
ANSI/IEEE Compliance ANSI/IEEE C37.90-2005
Across open contacts of normally open output relays 1.5 kV ac rms for 1 minute
Across open contacts of normally open changeover output relays 1 kV ac rms for 1 minute
Across open watchdog contacts 1 kV ac rms for 1 minute

21.12.4 IMPULSE VOLTAGE WITHSTAND TEST

Compliance IEC 60255-27: 2013


Between all independent circuits Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5 J
Between terminals of all independent circuits Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5 J
Between all independent circuits and protective earth
Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5 J
conductor terminal

Note:
Exceptions are communications ports and normally-open output contacts, where applicable.

520 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.13 ENVIRONMENTAL CONDITIONS

21.13.1 AMBIENT TEMPERATURE RANGE

Compliance IEC 60255-27: 2013


Test Method IEC 60068-2-1:2007 and IEC 60068-2-2 2007
Operating temperature range -25°C to +55°C (continuous)
Storage and transit temperature range -25°C to +70°C (continuous)

21.13.2 TEMPERATURE ENDURANCE TEST

Temperature Endurance Test


Test Method IEC 60068-2-1: 2007 and 60068-2-2: 2007
-40°C (96 hours)
Operating temperature range
+70°C (96 hours)
-40°C (96 hours)
Storage and transit temperature range
+70°C (96 hours)

21.13.3 AMBIENT HUMIDITY RANGE

Compliance IEC 60068-2-78: 2012 and IEC 60068-2-30: 2005


Durability 56 days at 93% relative humidity and +40°C
Damp heat cyclic six (12 + 12) hour cycles, 93% RH, +25 to +55°C

21.13.4 CORROSIVE ENVIRONMENTS

Compliance, Industrial corrosive environment/poor IEC 60068-2-42: 2003, IEC 60068-2-43: 2003, IEC 60068-2-52:
environmental control 1996
21 days exposure to elevated concentrations (25ppm) of SO2 at
Sulphur Dioxide, IEC 60068-2-42: 2003
75% relative humidity and +25°C
21 days exposure to elevated concentrations (10ppm) of H2S at
Hydrogen Sulphide, IEC 60068-2-43: 2003
75% relative humidity and +25°C
Salt mist, IEC 60068-2-52: 1996 7 days, KB severity 3

P64-TM-EN-1 521
Chapter 21 - Technical Specifications P64

21.14 ELECTROMAGNETIC COMPATIBILITY

21.14.1 1 MHZ BURST HIGH FREQUENCY DISTURBANCE TEST

Compliance IEC 60255-26:2013


Common-mode test voltage (level 3) 2.5 kV
Differential test voltage (level 3) 1.0 kV

21.14.2 DAMPED OSCILLATORY TEST

Compliance EN61000-4-18: 2011: Level 3, 100 kHz and 1 MHz. Level 4: 3 MHz,
10 MHz and 30 MHz, IEC 60255-26:2013
Common-mode test voltage (level 3) 2.5 kV
Common-mode test voltage (level 4) 4.0 kV
Differential mode test voltage 1.0 kV

21.14.3 IMMUNITY TO ELECTROSTATIC DISCHARGE

Compliance IEC 60255-26:2013, IEC 61000-4-2:2009


Class 4 Condition 15 kV discharge in air to user interface, display, and exposed metalwork
Class 3 Condition 8 kV discharge in air to all communication ports

21.14.4 ELECTRICAL FAST TRANSIENT OR BURST REQUIREMENTS

Compliance IEC 60255-26:2013, IEC 61000-4-4:2012


Applied to communication inputs Amplitude: 2 kV, burst frequency 5 kHz and 100 KHz (level 4)
Applied to power supply and all other inputs
Amplitude: 4 kV, burst frequency 5 kHz and 100 KHz (level 4)
except for communication inputs

21.14.5 SURGE WITHSTAND CAPABILITY

Compliance IEEE/ANSI C37.90.1: 2012


4 kV fast transient and 2.5 kV oscillatory applied common mode and differential mode
Condition 1
to opto inputs, output relays, CTs, VTs, power supply
4 kV fast transient and 2.5 kV oscillatory applied common mode to communications,
Condition 2
IRIG-B

522 P64-TM-EN-1
P64 Chapter 21 - Technical Specifications

21.14.6 SURGE IMMUNITY TEST

Compliance IEC 60255-26:2013, IEC 61000-4-5:2014+AMD1:2017


Pulse duration Time to half-value: 1.2/50 µs
Between all groups and protective earth conductor terminal Amplitude 4 kV
Between terminals of each group (excluding communications ports,
Amplitude 2 kV
where applicable)

21.14.7 IMMUNITY TO RADIATED ELECTROMAGNETIC ENERGY

Compliance IEC 60255-26:2013, IEC 61000-4-3:2006 + A2:2010


Frequency band 80 MHz to 3.0 GHz
Spot tests at 80, 160, 380, 450, 900, 1850, 2150 MHz
Test field strength 10 V/m
Test using AM 1 kHz @ 80%
Compliance IEEE/ANSI C37.90.2: 2004
Frequency band 80 MHz to 1 GHz
Spot tests at 80, 160, 380, 450 MHz
Waveform 1 kHz @ 80% am and pulse modulated
Field strength 35 V/m

21.14.8 RADIATED IMMUNITY FROM DIGITAL COMMUNICATIONS

Compliance IEC 61000-4-3:2006 + A2:2010


Frequency bands 800 to 960 MHz, 1.4 to 2.0 GHz
Test field strength 30 V/m
Test using AM 1 kHz / 80%

21.14.9 RADIATED IMMUNITY FROM DIGITAL RADIO TELEPHONES

Compliance IEC 60255-26:2013, IEC 61000-4-3:2006 + A2:2010


Frequency bands 900 MHz and 1.89 GHz
Test field strength 10 V/m

21.14.10 IMMUNITY TO CONDUCTED DISTURBANCES INDUCED BY RADIO


FREQUENCY FIELDS

Compliance IEC 60255-26:2013, IEC 61000-4-6:2013 Level 3


Frequency bands 150 kHz to 80 MHz

P64-TM-EN-1 523
Chapter 21 - Technical Specifications P64

Test disturbance voltage 10 V rms


Test using AM 1 kHz @ 80%
Spot tests 27 MHz and 68 MHz

21.14.11 MAGNETIC FIELD IMMUNITY

IEC 61000-4-8:2009 Level 5


Compliance IEC 61000-4-9:2016 Level 5
IEC 61000-4-10:2016 Level 5
IEC 61000-4-8 test 100 A/m applied continuously, 1000 A/m applied for 3 s
IEC 61000-4-9 test 1000 A/m applied in all planes
100 A/m applied in all planes at 100 kHz/1 MHz with a burst duration of 2
IEC 61000-4-10 test
seconds

21.14.12 CONDUCTED EMISSIONS

Compliance IEC 60255-26:2013, EN 55032: 2015+A1:2020


Power supply test 1 0.15 - 0.5 MHz, 79 dBµV (quasi peak) 66 dBµV (average)
Power supply test 2 0.5 – 30 MHz, 73 dBµV (quasi peak) 60 dBµV (average)
RJ45 test 1 (where applicable) 0.15 - 0.5 MHz, 97 dBµV (quasi peak) 84 dBµV (average)
RJ45 test 2 (where applicable) 0.5 – 30 MHz, 87 dBµV (quasi peak) 74 dBµV (average)

21.14.13 RADIATED EMISSIONS

Compliance IEC 60255-26:2013


Test 1 30 – 230 MHz, 40 dBµV/m at 10 m measurement distance
Test 2 230 – 1 GHz, 47 dBµV/m at 10 m measurement distance
Test 3 1 – 2 GHz, 76 dBµV/m at 10 m measurement distance

21.14.14 POWER FREQUENCY

Compliance IEC 60255-26:2013


Opto-inputs (Compliance is achieved using the opto-input 300 V common-mode (Class A)
filter) 150 V differential mode (Class A)

Note:
Compliance is achieved using the opto-input filter.

524 P64-TM-EN-1
APPENDIX A

ORDERING OPTIONS
Appendix A - Ordering Options P64

526 P64-TM-EN-1
P64 Appendix A - Ordering Options

CORTEC Order Code Matrix 1-3 4 5 6 7 8 9 10 11 12-13 14 15


Transformer Protection P64 AB
2 End: 2 Winding Transformer 2
3 End: 3 Winding Transformer 3
5 End: 3 Winding Transformer 5
Nominal Auxiliary Supply Voltage
24-54 Vdc 7
48-125 Vdc (40-100 Vac) 8
110-250 Vdc (100-240 Vac) 9
CT and VT Ratings CT/Hardware Opt. Compatibility
HV-LV In = 1A/5A, Vn = (100/120V) (xCT/1VT) Standard CT P642 = 8, P643 = 12, P645 = 18 1
HV-LV In = 1A/5A, Vn = (100/120V) (xCT/4VT) Standard CT (8 CT & 2VT for P642) P642 = 8, P643 = 12, P645 = 18 2
HV-LV In = 1A/5A, Vn = (100/120V) (xCT/1VT) Sensitive CT (P643/5 Only) P643 = 12, P645 = 18 3
HV-LV In = 1A/5A, Vn = (100/120V) (xCT/4VT) Sensitive CT (P643/5 Only) P643 = 12, P645 = 18 4
Hardware Options
Standard - 1 x RS485 rear serial communications port provided with all ordering options (Courier, -103, DNP3 ready) 1
With additional IRIG-B (Modulated) 2
With additional IRIG-B (Modulated) & Serial Fibre Optic comms 4
Single Ethernet 1 LC Duplex port + Universal IRIG-B + 1588 + 1 RJ45 Maintenance Port U
Redundant Ethernet PRP/HSR/RSTP/Failover 2 LC Duplex port + IEC870-103 Serial Fibre ST ports + Universal IRIG-B + 1588 + 1 RJ45 Maintenance Port V
Redundant Ethernet PRP/HSR/RSTP/Failover 2 RJ45 + Universal IRIG-B + 1588 + 1 RJ45 Maintenance Port W
Redundant Ethernet PRP/HSR/RSTP/Failover 2 LC Duplex ports + Universal IRIG-B + 1588 + 1 RJ45 Maintenance Port Y
Input/Output Options Case Size Compatibility
8 inputs, 8 outputs 40TE, 60TE B
12 inputs, 12 outputs 60TE E
16 inputs, 16 outputs 60TE H
16 inputs, 16 outputs + 4 High-Speed High-Break 60TE, 80TE J
16 inputs, 21 outputs 60TE, 80TE K
16 inputs, 24 outputs 60TE, 80TE L
20 inputs, 20 outputs 60TE, 80TE P
24 inputs, 16 outputs 60TE, 80TE S
24 inputs, 16 outputs + 8 High-Speed High-Break 80TE T
24 inputs, 24 outputs 80TE U
24 inputs, 32 outputs 80TE V
32 inputs, 24 outputs 80TE 1
32 inputs, 32 outputs 80TE 2
40 inputs, 24 outputs 80TE 4
48 inputs, 16 outputs 80TE 7
Product Specific Options
RTD A
CLIO B
RTD + CLIO C
None X
Case Size and Mounting Product Compatibility
80TE Case - Flush/Panel Mounting with Harsh Env. Coating, with USB Port and 10 Function Keys P642, P643, P645 S
80TE Case - 19" Rack Mounting with Harsh Env. Coating, with USB Port and 10 Function Keys 40TE P642, P643, P645 T
Case - Flush/Panel Mounting with Harsh Env. Coating, with USB Port, without Function Keys 60TE P642 U
Case - Flush/Panel Mounting with Harsh Env. Coating, with USB Port and 10 Function Keys P642, P643 V
Product Features
Standard Version X
Software Version
Enhanced cybersecurity, concurrent protocols, 5000 events, 100 fault records, 1050s oscillography AB
Customer-Specific Additions
Standard version 0
Customer-specific configuration/options A
Hardware Version
5th Generation Hardware, Graphical Colour HMI with High Performance Processing Q

P64-TM-EN-1 527
Appendix A - Ordering Options P64

528 P64-TM-EN-1
APPENDIX B

SETTINGS AND SIGNALS


Appendix B - Settings and Signals P64

Tables, containing a full list of settings for each model, are provided in a separate Excel file attached as an
embedded resource. To access the spreadsheet file, click on the button below.

Note:
An Open File dialogue box may open with a warning message about potential harm from programs, macros or viruses. The
file supplied does not contain any harmful content, and may be safely opened.

Settings and Signals

530 P64-TM-EN-1
APPENDIX C

WIRING DIAGRAMS
Appendix C - Wiring Diagrams P64

532 P64-TM-EN-1
Appendix C - Wiring Diagrams P64

CORTEC Product Specific Drawing-


Model Input/Output Options and Case Size Compatibility Issue
Option* Option Sheet
Comms Options MiCOM Px40 Platform 10Px4001-1 N
All - -
10Px4001-2 A
I/O Option B X (8 I/P & 8 O/P) (40TE) 10P64201-1 L
High Z REF for 2 bias input transformer differential 10P64201-2 H
same principle applies to wire High Z REF for T2
I/O Option B A - RTD (8 I/P & 8 O/P + RTD) (40TE) 10P64202-1 K
I/O Option B B - CLIO (8 I/P & 8 O/P + CLIO) (40TE) 10P64203-1 K
I/O Option B A - RTD (8 I/P & 8 O/P) (60TE) 10P64217-1
B - CLIO High Z REF for 2 bias input transformer differential 10P64217-2 B
X same principle applies to wire High Z REF for T2
I/O Option E A - RTD (12 I/P & 12 O/P) (60TE) 10P64226-1
B - CLIO High Z REF for 2 bias input transformer differential 10P64226-2 B
X same principle applies to wire High Z REF for T2
I/O Option H X (16 I/P & 16 O/P) (60TE) 10P64233-1
High Z REF for 2 bias input transformer differential 10P64233-2 B
same principle applies to wire High Z REF for T2
I/O Option J A - RTD (16 I/P & 16 O/P + 4 High-Speed High-Break) (80TE) 10P64237-1
B - CLIO High Z REF for 2 bias input transformer differential 10P64237-2 B
C - RTD + CLIO same principle applies to wire High Z REF for T2
X
I/O Option K A - RTD (16 I/P & 21 O/P) (80TE) 10P64241-1
B - CLIO High Z REF for 2 bias input transformer differential 10P64241-2 B
C - RTD + CLIO same principle applies to wire High Z REF for T2
P642 X
I/O Option L A - RTD (16 I/P & 24 O/P) (80TE) 10P64245-1
B - CLIO High Z REF for 2 bias input transformer differential 10P64245-2 B
C - RTD + CLIO same principle applies to wire High Z REF for T2
X
I/O Option P A - RTD (20 I/P & 20 O/P) (80TE) 10P64249-1
B - CLIO High Z REF for 2 bias input transformer differential 10P64249-2 B
C - RTD + CLIO same principle applies to wire High Z REF for T2
X
I/O Option S A - RTD (24 I/P & 16 O/P) (80TE) 10P64257-1
B - CLIO High Z REF for 2 bias input transformer differential 10P64257-2
C - RTD + CLIO same principle applies to wire High Z REF for T2 B
X

I/O Option T B - CLIO (24 I/P & 16 O/P + 8 High-Speed High-Break) (80TE) 10P64258-1
High Z REF for 2 bias input transformer differential C
10P64258-2
same principle applies to wire High Z REF for T2
I/O Option U A - RTD (24 I/P & 24 O/P) (80TE) 10P64259-1
B - CLIO High Z REF for 2 bias input transformer differential B
X 10P64259-2
same principle applies to wire High Z REF for T2
I/O Option V X (24 I/P & 32 O/P) (80TE) 10P64262-1
High Z REF for 2 bias input transformer differential B
10P64262-2
same principle applies to wire High Z REF for T2

I/O Option H X (16 I/P & 16 O/P) (60TE) 10P64301-1 G


10P64301-2 J
High Z REF for 3 bias input transformer differential 10P64301-3 E
same principle applies to wire High Z REF for T2 & T3
P643
I/O Option H A - RTD (16 I/P & 16 O/P + RTD) (60TE) 10P64302-1 G
10P64302-2 J
I/O Option H B - CLIO (16 I/P & 16 O/P + CLIO) (60TE) 10P64303-1 H
10P64303-2 J

P64-TM-EN-1 533
P64 Appendix C - Wiring Diagrams

CORTEC Product Specific Drawing-


Model Input/Output Options and Case Size Compatibility Issue
Option* Option Sheet
I/O Option J X (16 I/P & 16 O/P + 4 High-Speed High-Break) (60TE) 10P64306-1 G
10P64306-2 J
I/O Option J A - RTD (16 I/P & 16 O/P + 4 High-Speed High-Break) (80TE) 10P64330-1 A
B - CLIO 10P64330-2
C - RTD + CLIO
X
I/O Option K X (16 I/P & 21 O/P) (60TE) 10P64322-1
A
10P64322-2
I/O Option K A - RTD (16 I/P & 21 O/P) (80TE) 10P64335-1 A
B - CLIO 10P64335-2
C - RTD + CLIO
X
I/O Option L X (16 I/P & 24 O/P) (60TE) 10P64305-1 G
10P64305-2 J
I/O Option L A - RTD (16 I/P & 24 O/P) (80TE) 10P64339-1 A
B - CLIO 10P64339-2
C - RTD + CLIO
X
I/O Option P X (20 I/P & 20 O/P) (60TE) 10P64345-1 A
10P64345-2
I/O Option P A - RTD (20 I/P & 20 O/P) (80TE) 10P64342-1 A
B - CLIO 10P64342-2
C - RTD + CLIO
X
P643 I/O Option S X (24 I/P & 16 O/P) (60TE) 10P64304-1 H
10P64304-2 J
I/O Option S A - RTD (24 I/P & 16 O/P) (80TE) 10P64362-1 A
B - CLIO 10P64362-2
C - RTD + CLIO
X
I/O Option T A - RTD (24 I/P & 16 O/P + 8 High-Speed High-Break) (80TE) 10P64363-1 A
B - CLIO 10P64363-2
X
I/O Option U A - RTD (24 I/P & 24 O/P) (80TE) 10P64352-1 A
B - CLIO 10P64352-2
C - RTD + CLIO
X
I/O Option V A - RTD (24 I/P & 32 O/P) (80TE) 10P64353-1 A
B - CLIO 10P64353-2
X
I/O Option 1 A - RTD (32 I/P & 24 O/P) (80TE) 10P64374-1 A
B - CLIO 10P64374-2
X
I/O Option 2 B - CLIO (32 I/P & 32 O/P) (80TE) 10P64377-1 A
10P64377-2
I/O Option 4 B - CLIO (40 I/P & 24 O/P) (80TE) 10P64355-1 A
10P64355-2
I/O Option 7 B - CLIO (48 I/P & 16 O/P) (80TE) 10P64356-1 A
10P64356-2

I/O Option H X (16 I/P & 16 O/P) (60TE) 10P64501-1 F


10P64501-2 K
High Z REF for 5 bias input transformer differential 10P64501-3 H
P645 same principle applies to wire High Z REF for T2, T3,
T4 & T5
I/O Option H A - RTD (16 I/P & 16 O/P + RTD) (60TE) 10P64502-1 F
10P64502-2 J

534 P64-TM-EN-1
Appendix C - Wiring Diagrams P64

CORTEC Product Specific Drawing-


Model Input/Output Options and Case Size Compatibility Issue
Option* Option Sheet
I/O Option H B - CLIO (16 I/P & 16 O/P + CLIO) (60TE) 10P64503-1 F
10P64503-2 J
I/O Option J X (16 I/P & 16 O/P + 4 High-Speed High-Break) (60TE) 10P64528-1
A
10P64528-2
I/O Option J A - RTD (16 I/P & 16 O/P + 4 High-Speed High-Break) (80TE) 10P64538-1 A
B - CLIO 10P64538-2
C - RTD + CLIO
X
I/O Option K X (16 I/P & 21 O/P) (60TE) 10P64529-1 A
10P64529-2
I/O Option K A - RTD (16 I/P & 21 O/P) (80TE) 10P64542-1 A
B - CLIO 10P64542-2
C - RTD + CLIO
X
I/O Option L X (16 I/P & 24 O/P) (60TE) 10P64505-1 F
10P64505-2 J
I/O Option L A - RTD (16 I/P & 24 O/P) (80TE) 10P64546-1 A
B - CLIO 10P64546-2
C - RTD + CLIO
X
I/O Option P X (20 I/P & 20 O/P) (60TE) 10P64530-1 A
10P64530-2
I/O Option P A - RTD (20 I/P & 20 O/P) (80TE) 10P64550-1 A
B - CLIO 10P64550-2
C - RTD + CLIO
P645 X
I/O Option S X (24 I/P & 16 O/P) (60TE) 10P64504-1 F
10P64504-2 J
I/O Option S A - RTD (24 I/P & 16 O/P) (80TE) 10P64558-1 A
B - CLIO 10P64558-2
C - RTD + CLIO
X
I/O Option T A - RTD (24 I/P & 16 O/P + 8 High-Speed High-Break) (80TE) 10P64559-1 A
B - CLIO 10P64559-2
X
I/O Option U A - RTD (24 I/P & 24 O/P) (80TE) 10P64565-1 A
B - CLIO 10P64565-2
C - RTD + CLIO
X
I/O Option V A - RTD (24 I/P & 32 O/P) (80TE) 10P64566-1 A
B - CLIO 10P64566-2
X
I/O Option 1 A - RTD (32 I/P & 24 O/P) (80TE) 10P64573-1 A
B - CLIO 10P64573-2
X
I/O Option 2 B - CLIO (32 I/P & 32 O/P) (80TE) 10P64576-1 A
10P64576-2
I/O Option 4 B - CLIO (40 I/P & 24 O/P) (80TE) 10P64577-1 A
10P64577-2
I/O Option 7 B - CLIO (48 I/P & 16 O/P) (80TE) 10P64578-1 A
10P64578-2
* When selecting the applicable wiring diagram(s), refer to appropriate model’s CORTEC.

P64-TM-EN-1 535
Issue: Revision: Title:
EXTERNAL CONNECTION DIAGRAM:
N SHEET 2 ADDED. CID008142.
COMMS OPTIONS MICOM Px40 PLATFORM
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 17/07/2024 Name: S WOOTTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1 C
UK Grid Solutions Ltd

Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10PX4001 Next
Sht: 2
St Leonards Building,
Harry Kerr Drive,
Stafford.
ST16 1WT, UK.
IRIG-B INPUT IRIG-B INPUT IRIG-B INPUT IRIG-B INPUT

NP2B NP2B
NP2A 1 TX+
1 20 2 TX- 1 20
RP1 TX
TxFault 2 19 3 RX+ TxFault 2 19 FIBRE OPTIC
TxDisable 3 18 4 TxDisable 3 18 COMMUNICATION
MOD-DEF2 4 17 5 MOD-DEF2 4 17 RP1 RX

MOD-DEF1 5 16 VccTx 6 RX- MOD-DEF1 5 16 VccTx


MOD-DEF0 6 15 VccRx 7 MOD-DEF0 6 15 VccRx NP2B
RateSelect 7 14 8 RateSelect 7 14
1 20
MDLLOS 8 13 RJ45 MDLLOS 8 13
TxFault 2 19
9 12 9 12
NP2A TxDisable 3 18
10 11 1 TX+ 10 11
MOD-DEF2 4 17
2 TX-
MOD-DEF1 5 16 VccTx
3 RX+
NP2A MOD-DEF0 6 15 VccRx
4
NP1 1 20 RateSelect 7 14
1 TX+ 5
TxFault 2 19 MDLLOS 8 13
2 TX- 6 RX-
TxDisable 3 18 9 12
3 RX+ 7
MOD-DEF2 4 17 10 11
4 8
MOD-DEF1 5 16 VccTx
5 RJ45
MOD-DEF0 6 15 VccRx NP2A
6 RX-
NP1 RateSelect 7 14
7 1 TX+ 1 20
MDLLOS 8 13
8 2 TX- TxFault 2 19
9 12
3 RX+ TxDisable 3 18
RJ45
10 11
4 MOD-DEF2 4 17
5 MOD-DEF1 5 16 VccTx
6 RX- NP1 MOD-DEF0 6 15 VccRx
1 TX+
7 RateSelect 7 14
2 TX-
8 MDLLOS 8 13
3 RX+
RJ45 9 12
4
10 11
5
6 RX-
7 NP1
1 TX+
8
2 TX-
RJ45 3 RX+
4
5
6 RX-
7
8
RJ45

COMBINED ETHERNET COMBINED ETHERNET COMBINED ETHERNET COMBINED ETHERNET


LOW COST OPTION COPPER STATION FIBRE STATION FIBRE STATION AND FIBRE SERIAL

Issue: Revision: Title:


INITIAL ISSUE. CID008142 EXTERNAL CONNECTION DIAGRAM
A COMMS OPTIONS MICOM Px40
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 27/06/2024 Name: S WOOTTON Sht: 2
10PX4001
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
T1 C24 NOTE 3
A (1) n
C23
a MiCOM P642 (PART)
b c
C26
C3
B (1) F11
WATCHDOG
C25 VFLUX CONTACT F12
C4 F13
C28 WATCHDOG
CONTACT F14
C (1) E1
D1 -
C27 RELAY 1 E2
D2 OPTO 1
+ E3
T2 C18
D3 RELAY 2 E4
-
A (2) OPTO 2 E5
D4
+
C17 RELAY 3 E6
D5 - E7
C20 D6 OPTO 3
+ RELAY 4 E8
B (2) D7 E9
-
C19 D8 OPTO 4 RELAY 5 E10
+
D9 E11
C22 -
OPTO 5 RELAY 6 E12
C (2) D10
+ E13
D11 -
C21 E14
OPTO 6 RELAY 7
D12 E15
+
D13 E16
GROUNDED WYE -
NEUTRAL TAILS D14 OPTO 7 E17
+ RELAY 8
E18
HV LV D15
-
NOTE 4 D16 OPTO 8
NOTE 2 +
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17
-
TN2 C14 SEE DRAWING EIA485/
P1 S1
10Px4001 KBUS NOTES:
P2 S2 Y (LV) F18
+ PORT
C13 F16 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
SCN
P1 S1 TN1 C16
* F1 (b) TERMINAL.
Y (HV) -
AC OR DC
F2 x AUX SUPPLY (c) PIN TERMINAL (P.C.B. TYPE)
C15 +

2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.


3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).

CASE 4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.


EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
L CID006234 Outlines updated to GE Format
DIFFERENTIAL (8 I/P & 8 O/P) WITH 1 POLE VT INPUT (40TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg
GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
No:
10P64201 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 C24 NOTE 3
A (1) n
C23
a
MiCOM P642 (PART)
b c
C26
C3
B (1) F11
WATCHDOG
C25 VFLUX CONTACT F12
C4 F13
C28 WATCHDOG
CONTACT F14
C (1) E1
D1 -
C27 RELAY 1 E2
D2 OPTO 1
+ E3
T2 C18
D3 RELAY 2 E4
-
A (2) OPTO 2 E5
D4
+
C17 RELAY 3 E6
D5 - E7
C20 D6 OPTO 3
+ RELAY 4 E8
B (2) D7 E9
-
C19 D8 OPTO 4 RELAY 5 E10
+
D9 E11
C22 -
OPTO 5 RELAY 6 E12
C (2) D10
+ E13
D11 -
C21 E14
OPTO 6 RELAY 7
D12 E15
+
GROUNDED WYE D13 E16
-
NEUTRAL TAILS D14 OPTO 7 E17
+ RELAY 8
E18
HV LV D15 -
NOTE 4 D16 OPTO 8
NOTE 2 +
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17
-
NOTES:
P1 S1 TN2 C14 SEE DRAWING EIA485/
10Px4001 KBUS
P2 S2 Y (LV) F18 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
+ PORT
C13 F16
R ST TN1
SCN (b) TERMINAL.
P1 S1 C16
* F1 (c) PIN TERMINAL (P.C.B. TYPE)
Y (HV) -
AC OR DC
F2 x AUX SUPPLY
C15 + 2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
METROSIL (USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


EXT CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF SAME
H CID006234 Outlines updated to GE Format
PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg
GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 2

Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
No:
10P64201 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
T1 C24 NOTE 3
A (1) n
C23 MiCOM P642 (PART)
a b c
C26
C3
B (1) F11
WATCHDOG
C25 VFLUX CONTACT F12
B1
C4 F13
C28 WATCHDOG B2 RTD 1
CONTACT F14
C (1) B3
E1
D1 - B4
C27 RELAY 1 E2
D2 OPTO 1 B5 RTD 2
+ E3
T2 C18 B6
D3 RELAY 2 E4
- B7
A (2) OPTO 2 E5
D4
+ B8 RTD 3
C17 RELAY 3 E6
D5 - B9
E7
C20 D6 OPTO 3
+ RELAY 4 E8
B (2) D7 E9
-
C19 D8 OPTO 4 RELAY 5 E10 B28
+ RTD 10
E11 B29
C22 D9 -
RELAY 6 E12 B30
D10 OPTO 5
C (2) + E13
D11 -
C21 E14
OPTO 6 RELAY 7
D12 E15
+
GROUNDED WYE D13 - E16
NEUTRAL TAILS D14 OPTO 7 E17
+ RELAY 8
E18
HV LV D15 -
NOTE 4 D16 OPTO 8
NOTE 2 +
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17
-
NOTES:
TN2 C14 SEE DRAWING EIA485/
P1 S1
10Px4001 KBUS
P2 S2 Y (LV) F18
+ PORT 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
C13 F16
SCN (b) TERMINAL.
P1 S1 TN1 C16
* F1 (c)
Y (HV) - PIN TERMINAL (P.C.B. TYPE)
AC OR DC
F2 x AUX SUPPLY
C15 + 2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format
EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
K DIFFERENTIAL (8 I/P & 8 O/P + RTD) WITH 1 POLE VT INPUT (40TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1

Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
No:
10P64202 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED B1
20mA
TRANSFORMER MiCOM P642 (PART) N B2
T1 C24 NOTE 3 1mA OUTPUT 1
B3
A (1) n
B5
C23 20mA
F11 B6
a b c WATCHDOG 1mA OUTPUT 2
C26 F12
CONTACT B7
C3 F13
B (1) B9
WATCHDOG 20mA
CONTACT F14
C25 VFLUX B10
E1 1mA OUTPUT 3
C4
C28 RELAY 1 E2 B11

C (1) E3 B13
20mA
D1 RELAY 2 E4 B14
C27 - 1mA OUTPUT 4
D2 OPTO 1 E5
+ B15
T2 C18
D3
RELAY 3 E6 CLIO
- B16
A (2) E7 20mA CURRENT LOOP
D4 OPTO 2
+ RELAY 4 E8 B17 INPUTS & OUTPUTS
C17 1mA INPUT 1
D5 B18 NOTE 5
- E9
C20 D6 OPTO 3 RELAY 5 E10
+ B20
20mA
B (2) D7 E11
- B21
RELAY 6 E12 1mA INPUT 2
C19 D8 OPTO 4
+ B22
E13
C22 D9 - B24
E14 20mA
OPTO 5 RELAY 7
C (2) D10 E15 B25
+ 1mA INPUT 3
D11 E16 B26
C21 -
D12 OPTO 6 E17
+ RELAY 8 B28
E18 20mA
GROUNDED WYE D13 - B29
1mA INPUT 4
NEUTRAL TAILS D14 OPTO 7
+ B30
HV LV D15 -
NOTE 4 D16 OPTO 8 MiCOM P642 (PART)
NOTE 2 +
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17 NOTES:
-
TN2 C14 SEE DRAWING EIA485/
P1 S1 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
10Px4001 KBUS
P2 S2 Y (LV) F18
+ PORT
C13 F16 (b) TERMINAL.
SCN
P1 S1 TN1 C16 (c) PIN TERMINAL (P.C.B. TYPE)
* F1
Y (HV) -
AC OR DC 2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
F2 x AUX SUPPLY
C15 +
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
5. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title: EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER


K CID006234 Outlines updated to GE Format
DIFFERENTIAL (8 I/P & 8 O/P + CLIO) WITH 1 POLE VT INPUT (40TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg
GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1

Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
No:
10P64203 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
MiCOM P642 (PART)
E1
TRANSFORMER MiCOM P642 (PART) N
E2 T1 C24 NOTE 3
J11 B1
E3 A (1) n WATCHDOG
J12
CONTACT B2 RTD 1
E4 C23 J13
WATCHDOG B3
E5 a b c CONTACT J14 B4
C26
E6 H1 B5 RTD 2
C3
B (1) RELAY 1 H2
E7 B6
C25 VFLUX H3 B7
E8 RELAY 2 H4 OPTIONAL
C4 B8 RTD 3
C28
E9 H5 B9
C (1) RELAY 3 H6
E10
D1 -
E12 C27 H7
D2 OPTO 1 RELAY 4
+ H8
T2 C18 B28
D3 H9
- B29 RTD 10
E11 A (2) OPTO 2 RELAY 5 H10
D4 B30
E14 +
C17 H11
D5 - RELAY 6 H12
C20 D6 OPTO 3
E13 + H13
E16 B (2) D7 H14
- RELAY 7
C19 D8 OPTO 4 H15
+ B1
20mA
D9 H16
NOT USED E15 C22 - B2
H17 1mA OUTPUT 1
E18 D10 OPTO 5 RELAY 8
C (2) + B3
H18
D11 - B5
C21 20mA
D12 OPTO 6
E17 + B6
1mA OUTPUT 2
E20 D13
GROUNDED WYE - B7
NEUTRAL TAILS D14 OPTO 7
+ B9
20mA
E19 HV LV D15 B10
- 1mA OUTPUT 3
E22 OPTO 8
NOTE 4 D16 B11
NOTE 2 +
COMMS
D17 B13
COMMON 20mA
E21 D18 CONNECTION B14
E24 1mA OUTPUT 4
P2 S2 B15
J17 CLIO
- B16
E23 20mA CURRENT LOOP
E26 TN2 C14 SEE DRAWING EIA485/ B17 INPUTS & OUTPUTS
P1 S1 1mA INPUT 1
10Px4001 KBUS (OPTIONAL)
P2 S2 Y (LV) J18 B18
+ PORT
E25 C13 J16 B20
20mA
E28 SCN B21
P1 S1 TN1 C16 1mA INPUT 2
* J1 B22
Y (HV) -
AC OR DC
E27 J2 x AUX SUPPLY B24
C15 + 20mA
B25
1mA INPUT 3
B26
NOTES:
B28
20mA
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. B29
1mA INPUT 4
CASE
EARTH B30
(b) TERMINAL.

(c) PIN TERMINAL (P.C.B. TYPE)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (8 I/P & 8 O/P) WITH 1 POLE VT INPUT (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 01/05/2024 Name: S WOOTTON Sht: 1
10P64217
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
E1 PHASE ROTATION
E2 PROTECTED
E3 TRANSFORMER N MiCOM P642 (PART)
T1 C24 NOTE 3
E4 n
A (1)
E5 J11 B1
C23 WATCHDOG
CONTACT J12 B2 RTD 1
E6 a b c J13
C26 B3
E7 WATCHDOG
C3 CONTACT J14 B4
E8 B (1)
H1 B5 RTD 2
E9 C25 VFLUX RELAY 1 H2 B6
C4 H3
E10 C28 B7
RELAY 2 H4 OPTIONAL
E12 C (1) B8 RTD 3
H5 B9
D1 -
C27 RELAY 3 H6
D2 OPTO 1
E11 T2 C18 + H7
E14 D3 RELAY 4 H8
- B28
A (2) OPTO 2
D4 H9
+ B29 RTD 10
C17 RELAY 5 H10
E13 D5 - B30
E16 C20 OPTO 3 H11
D6
+ RELAY 6 H12
B (2) D7 - H13
NOT USED E15 C19 D8 OPTO 4
+ H14
E18 RELAY 7
C22 D9 - H15 B1
OPTO 5 20mA
D10 H16
C (2) + B2
E17 H17 1mA OUTPUT 1
D11 - RELAY 8 B3
E20 C21 H18
D12 OPTO 6
+ B5
20mA
GROUNDED WYE D13 - B6
E19 1mA OUTPUT 2
NEUTRAL TAILS D14 OPTO 7
E22 + B7
HV LV D15 - B9
20mA
NOTE 4 D16 OPTO 8
E21 NOTE 2 + B10
COMMS 1mA OUTPUT 3
E24 D17 B11
COMMON
D18 CONNECTION B13
20mA
E23 P2 S2 B14
1mA OUTPUT 4
E26 F17 B15
-
TN2 SEE DRAWING
CLIO
P1 S1 C14 EIA485/ B16
10Px4001 20mA CURRENT LOOP
E25 KBUS
P2 S2 Y (LV) F18 B17 INPUTS & OUTPUTS
+ PORT 1mA INPUT 1
E28 (OPTIONAL)
C13 F16 B18
R ST TN1
SCN B20
P1 S1 C16 20mA
E27 * F1 B21
Y (HV) - 1mA INPUT 2
AC OR DC
F2 x AUX SUPPLY B22
C15 +
B24
20mA
B25
METROSIL 1mA INPUT 3
B26
NOTES:
B28
20mA
CASE
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. EARTH B29
1mA INPUT 4
B30
(b) TERMINAL.

(c) PIN TERMINAL (P.C.B. TYPE) POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
*
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 01/05/2024 Name: S WOOTTON Sht: 2
10P64217
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
E1 PROTECTED
E2
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 C24 NOTE 3
E3 n
A (1)
E4 J11 B1
C23 WATCHDOG
E5 CONTACT J12
a b c B2 RTD 1
C26 J13
E6 WATCHDOG B3
C3 J14
B (1) CONTACT B4
E7
H1 B5 RTD 2
C25 VFLUX
E8 RELAY 1 H2
C4 B6
E9 C28 H3 B7
C (1) RELAY 2 H4 OPTIONAL
E10 B8 RTD 3
D1 H5 B9
E12 C27 -
OPTO 1 RELAY 3 H6
D2
T2 C18 +
H7
D3 -
E11 A (2) RELAY 4 H8
D4 OPTO 2 B28
E14 + H9
C17 B29 RTD 10
D5 - RELAY 5 H10
B30
C20 D6 OPTO 3 H11
E13 +
E16 B (2) RELAY 6 H12
D7 -
OPTO 4 H13
C19 D8
+ H14
NOT USED E15 D9 RELAY 7
C22 - H15
E18 B1
D10 OPTO 5 20mA
C (2) + H16
B2
D11 H17 1mA OUTPUT 1
C21 - RELAY 8 B3
E17 D12 OPTO 6 H18
E20 + B5
D13 G9 20mA
GROUNDED WYE - B6
NEUTRAL TAILS OPTO 7 RELAY 9 G10 1mA OUTPUT 2
D14
+ B7
E19 G11
HV LV D15 -
E22 RELAY 10 G12 B9
NOTE 4 D16 OPTO 8 20mA
NOTE 2 + G13 B10
COMMS 1mA OUTPUT 3
D17 G14
E21 COMMON RELAY 11 B11
E24 D18 CONNECTION G15
B13
P2 S2 G16 20mA
G17 B14
J17 RELAY 12 1mA OUTPUT 4
E23 - B15
G18
E26
P1 S1 TN2 C14 SEE DRAWING EIA485/ CLIO
10Px4001 B16
KBUS G1 20mA CURRENT LOOP
P2 S2 Y (LV) J18 -
+ PORT B17 INPUTS & OUTPUTS
OPTO 9 G2 1mA INPUT 1
E25 C13 J16 + (OPTIONAL)
B18
E28 SCN G3
- B20
P1 S1 TN1 C16 OPTO 10 20mA
* G4
J1 + B21
Y (HV) - 1mA INPUT 2
E27 AC OR DC G5
J2 x AUX SUPPLY - B22
C15 + OPTO 11 G6
+ B24
NOTES: G7 20mA
-
B25
OPTO 12 G8 1mA INPUT 3
+ B26
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
B28
CASE 20mA
(b) TERMINAL. EARTH B29
1mA INPUT 4
(c) PIN TERMINAL (P.C.B. TYPE) B30

2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.


* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER


Issue: Revision: Title:
CID008334. NOT USED TERMNIALS ADDED.
B DIFFERENTIAL (12 I/P & 12 O/P) WITH 1 POLE VT INPUT (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 03/05/2024 Name: S WOOTTON Sht: 1
10P64226
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
E1 T1 C24 NOTE 3 MiCOM P642 (PART)
E2 A (1) n
E3 C23 J11 B1
WATCHDOG
E4 a b c CONTACT J12 B2 RTD 1
C26
J13 B3
E5 C3 WATCHDOG
B (1) J14
CONTACT B4
E6
C25 VFLUX H1 B5 RTD 2
E7 C4 RELAY 1 H2
C28 B6
E8 H3 B7
C (1) RELAY 2 H4 OPTIONAL
E9 B8 RTD 3
D1 - H5
C27 B9
E10 OPTO 1
D2 RELAY 3 H6
T2 C18 +
E12
D3 H7
-
A (2) OPTO 2 RELAY 4 H8
D4 B28
+
E11 C17 H9
D5 B29 RTD 10
E14 - RELAY 5 H10
C20 D6 OPTO 3 B30
+ H11
B (2) D7 RELAY 6 H12
-
E13 OPTO 4
C19 D8 H13
E16 +
D9 H14
C22 - RELAY 7
OPTO 5 H15 B1
C (2) D10 20mA
NOT USED E15 + H16
D11 B2
E18 C21 - H17 1mA OUTPUT 1
OPTO 6 RELAY 8 B3
D12 H18
+
D13 B5
E17 GROUNDED WYE - G9 20mA
E20 NEUTRAL TAILS D14 OPTO 7 RELAY 9 B6
+ G10 1mA OUTPUT 2
D15 G11 B7
HV LV -
OPTO 8 RELAY 10 G12 B9
E19 NOTE 4 D16 20mA
NOTE 2 +
E22 COMMS G13 B10
D17 1mA OUTPUT 3
COMMON G14
D18 RELAY 11 B11
CONNECTION G15
E21 P2 S2 B13
G16 20mA
E24 B14
J17 G17 1mA OUTPUT 4
- RELAY 12
G18 B15
P1 S1 TN2 C14 SEE DRAWING EIA485/ CLIO
E23 10Px4001 KBUS B16
E26 P2 S2 Y (LV) J18 G1 20mA CURRENT LOOP
+ PORT - B17 INPUTS & OUTPUTS
C13 J16 OPTO 9 G2 1mA INPUT 1
+ (OPTIONAL)
B18
R ST TN1
SCN
G3
E25 P1 S1 C16 - B20
E28 * J1 OPTO 10 G4 20mA
Y (HV) - + B21
AC OR DC 1mA INPUT 2
J2 x AUX SUPPLY - G5
C15 + B22
E27 OPTO 11 G6
+ B24
G7 20mA
METROSIL - B25
OPTO 12 G8 1mA INPUT 3
+ B26
NOTES: CASE B28
EARTH 20mA
B29
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. 1mA INPUT 4
B30

(b) TERMINAL. POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


*
(c) PIN TERMINAL (P.C.B. TYPE)

2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.


3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 03/05/2024 Name: S WOOTTON Sht: 2
10P64226
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
E1 PHASE ROTATION
E2 PROTECTED
E3
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 C24 NOTE 3
E4 n
A (1)
E5
C23 B1 J11
-
E6 a b c OPTO 9 WATCHDOG
C26 B2 J12 CONTACT
+
E7 J13
C3 B3
B (1) - WATCHDOG
E8 OPTO 10 J14 CONTACT
B4
C25 VFLUX + H1
E9
C4 - B5 RELAY 1
C28 H2
E10 OPTO 11 B6 H3
E12 +
C (1)
B7 H4 RELAY 2
-
C27 D1 OPTO 12 H5
- B8
OPTO 1 + RELAY 3
E11 T2 C18 D2 H6
+ B9
E14 - H7
A (2) D3 - OPTO 13 B10 RELAY 4
OPTO 2 + H8
D4
C17 + B11 H9
E13 -
D5 - OPTO 14 RELAY 5
E16 C20 B12 H10
OPTO 3 +
D6 H11
+ B13
B (2) -
D7 OPTO 15 H12 RELAY 6
- B14
NOT USED E15 C19 OPTO 4 + H13
D8
E18 + B15
C22 - H14
D9 OPTO 16 RELAY 7
- B16 H15
OPTO 5 +
C (2) D10
E17 + B17 H16
C21 D11 COMMON H17
E20 - B18 RELAY 8
CONNECTION
D12 OPTO 6 H18
+
GROUNDED WYE D13 G1
E19 -
NEUTRAL TAILS OPTO 7 G2 RELAY 9
E22 D14
+
HV LV G3
D15 - G4 RELAY 10
NOTE 2 NOTE 4 D16 OPTO 8
E21 COMMS + G5
E24 D17 G6 RELAY 11
COMMON
D18 CONNECTION G7
P2 S2 G8 RELAY 12
E23
E26 J17 G9
-
G10 RELAY 13
TN2 C14 SEE DRAWING EIA485/
P1 S1
10Px4001 KBUS G11
E25 P2 S2 Y (LV) J18 RELAY 14
+ PORT G12
E28
C13 J16 G13
SCN G14
P1 S1 TN1 C16 RELAY 15
E27 * J1
G15
Y (HV) - G16
AC OR DC
J2 x AUX SUPPLY G17
C15 + RELAY 16
NOTES: G18

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.

(b) TERMINAL. CASE


EARTH
(c) PIN TERMINAL (P.C.B. TYPE)

2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.


3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
Issue: Revision: Title:
CID008334. NOT USED TERMINALS ADDED.. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (16 I/P & 16 O/P WITH 1 POLE VT INPUT (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 07/05/2024 Name: S WOOTTON Sht: 1
10P64233
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
E1
PROTECTED
E2 TRANSFORMER N
T1 C24 NOTE 3 MiCOM P642 (PART)
E3
A (1) n
E4
C23 B1
E5 - J11
a b c OPTO 9 J12
WATCHDOG
E6 C26 B2 CONTACT
+
C3 B3 J13
E7 B (1) - WATCHDOG
OPTO 10 J14 CONTACT
E8 C25 B4
VFLUX + H1
E9 C4 - B5 RELAY 1
C28 H2
OPTO 11 B6
E10 + H3
C (1)
E12 B7 H4 RELAY 2
D1 - -
C27
OPTO 1 OPTO 12 B8 H5
D2 +
T2 C18 + H6 RELAY 3
E11 D3 - B9
- H7
E14 A (2) OPTO 2 OPTO 13 B10
D4 + H8 RELAY 4
+
C17 B11
D5 - H9
-
E13 C20 OPTO 3 OPTO 14 B12 H10 RELAY 5
D6 +
E16 +
B13 H11
B (2) D7 -
- H12 RELAY 6
OPTO 4 OPTO 15 B14
C19 D8 + H13
+
NOT USED E15 B15
C22 D9 - - H14
E18 OPTO 16 RELAY 7
D10 OPTO 5 B16 H15
C (2) + +
D11 B17 H16
E17 C21 - COMMON
OPTO 6 B18 H17
D12 CONNECTION RELAY 8
E20 + H18
GROUNDED WYE D13 - G1
NEUTRAL TAILS D14 OPTO 7
E19 + G2 RELAY 9
E22 HV LV D15 - G3
NOTE 4 D16 OPTO 8 G4 RELAY 10
NOTE 2 +
COMMS G5
E21 D17
COMMON G6 RELAY 11
E24 D18 CONNECTION G7
P2 S2 G8 RELAY 12
E23 J17 G9
-
E26 G10 RELAY 13
P1 S1 TN2 C14 SEE DRAWING EIA485/
10Px4001 KBUS G11
P2 S2 Y (LV) J18
+ PORT G12 RELAY 14
E25
E28 C13 J16 G13
R ST TN1
SCN
G14
P1 S1 C16 RELAY 15
* J1 G15
E27 Y (HV) -
AC OR DC G16
J2 x AUX SUPPLY
C15 + G17
RELAY 16
G18
METROSIL

NOTES: CASE
EARTH
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.

(b) TERMINAL. POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


*
(c) PIN TERMINAL (P.C.B. TYPE)

2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.


3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY).
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
Issue: Revision: Title:
CID008334. NOT USED TERMINALS ADDED. EXT CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2
2
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 03/05/2024 Name: S WOOTTON Sht:

10P64233
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
-
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
F1
F2 D23 H1 M11
-
a b c OPTO 9 WATCHDOG
F3 D26 H2 M12 CONTACT
+
D3 H3 M13
F4 B (1) - WATCHDOG
OPTO 10 M14 CONTACT
F5 H4
D25 VFLUX + L1
F6 D4 - H5 RELAY 1
D28 L2
OPTO 11 H6
F7 + L3
C (1)
F8 H7 L4 RELAY 2
-
D27 E1 OPTO 12 L5
F9 - H8
OPTO 1 + RELAY 3
T2 D18 E2 L6
F10 + H9
- L7
A (2) E3 - OPTO 13
F12 H10 RELAY 4
OPTO 2 + L8
E4
D17 + H11 L9
-
E5 - OPTO 14 RELAY 5
F11 D20 H12 L10
OPTO 3 +
F14
E6 L11
+ H13
B (2) -
E7 OPTO 15 L12 RELAY 6
- H14
D19 OPTO 4 + L13
E8
F13 + H15
D22 - L14
F16 E9 OPTO 16 RELAY 7
- H16 L15
OPTO 5 +
C (2) E10
+ H17 L16
NOT USED D21 E11 COMMON L17
F15 - H18 RELAY 8
CONNECTION
F18 E12 OPTO 6 L18
+
GROUNDED WYE E13 K1
-
NEUTRAL TAILS OPTO 7 K2 RELAY 9
F17 E14
+
F20 HV LV K3
E15 - C1
20mA K4 RELAY 10
NOTE 2 NOTE 4 E16 OPTO 8
COMMS + C2 K5
OUTPUT 1 1mA
F19 E17 C3 K6 RELAY 11
F22 COMMON
E18 CONNECTION C5 K7
20mA
P2 S2 K8 RELAY 12
C6
M17 OUTPUT 2 1mA K9
F21 - C7
F24 K10 RELAY 13
TN2 D14 SEE DRAWING EIA485/
P1 S1 C9
10Px4001 KBUS 20mA K11
P2 S2 Y (LV) M18 C10 RELAY 14
+ PORT K12
F23 OUTPUT 3 1mA
D13 M16 C11 K13
F26
SCN K14
TN1 D16 C13 RELAY 15
P1 S1 20mA
* M1 C14
K15
F25 Y (HV) - OUTPUT 4 1mA K16
AC OR DC
F28 M2 x AUX SUPPLY C15 K17
D15 + CLIO RELAY 16
NOTES: C16 K18
CURRENT LOOP 20mA
F27 INPUTS & OUTPUTS C17
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. INPUT 1 1mA J3
(OPTIONAL) -
C18
RELAY 17
C20 J4
(b) TERMINAL. 20mA +
C21 J7
INPUT 2 1mA -
(c) PIN TERMINAL (P.C.B. TYPE)
C22 RELAY 18
J8
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. C24 + HIGH BREAK
20mA
C25 J11 - CONTACTS
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. INPUT 3 1mA
(USED BY V/Hz W2 PROTECTION ONLY). C26 RELAY 19
J12
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. +
C28
20mA J15
C29 -
INPUT 4 1mA RELAY 20
CASE C30 J16
EARTH +
B1
RTD 1 B2
B3
B4
RTD 2 B5
B6
B7
RTD 3 B8
OPTIONAL
B9

B28
RTD 10 B29
B30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER DIFFERENTIAL
B (16 I/P & 16 O/P + 4 HIGH-SPEED HIGH-BREAK) WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 1
10P64237
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 - H1 M11
OPTO 9 WATCHDOG
a b c +
H2 M12 CONTACT
D26
H3 M13
D3 - WATCHDOG
B (1) M14
F1 OPTO 10 H4 CONTACT
D25
+ L1
F2 VFLUX
- H5 RELAY 1
D4 L2
F3 D28 OPTO 11 H6
+ L3
F4 C (1) H7 L4 RELAY 2
-
E1 - OPTO 12 L5
F5 D27 H8
OPTO 1 + RELAY 3
E2 L6
F6 T2 D18 + H9
- L7
E3 - OPTO 13
F7 H10
A (2) OPTO 2 + L8 RELAY 4
E4
F8 + H11 L9
D17 -
E5 - OPTO 14
F9 H12 L10 RELAY 5
D20 OPTO 3 +
E6 L11
F10 + H13
B (2) - RELAY 6
F12 E7 - OPTO 15 L12
H14
D19 OPTO 4 + L13
E8
+ H15
- L14
D22 E9 - OPTO 16 RELAY 7
F11 H16 L15
OPTO 5 +
F14 C (2) E10
+ H17 L16
E11 - COMMON L17
D21 H18 RELAY 8
OPTO 6 CONNECTION
F13 E12 L18
+
F16 E13 K1
GROUNDED WYE -
NEUTRAL TAILS E14 OPTO 7 K2 RELAY 9
+
K3
NOT USED F15 HV LV E15 - B1
F18
20mA K4 RELAY 10
NOTE 4 E16 OPTO 8
NOTE 2 + B2 K5
COMMS OUTPUT 1 1mA
E17 B3 K6 RELAY 11
F17
COMMON
E18 CONNECTION B5 K7
F20 20mA
P2 S2 K8 RELAY 12
B6
OUTPUT 2 1mA K9
M17 B7
- RELAY 13
F19 K10
F22 P1 S1 TN2 D14 SEE DRAWING EIA485/ 20mA
B9 K11
10Px4001 KBUS
P2 S2 Y (LV) M18 B10 K12 RELAY 14
+ PORT OUTPUT 3 1mA
B11 K13
F21 D13 M16
R ST SCN K14
F24 B13 RELAY 15
P1 S1 TN1 D16 20mA K15
* M1 OUTPUT 4 1mA
B14
K16
Y (HV) -
AC OR DC B15
F23 M2 x AUX SUPPLY K17
F26
D15 + CLIO RELAY 16
B16 K18
CURRENT LOOP 20mA
INPUTS & OUTPUTS B17
METROSIL (OPTIONAL)
INPUT 1 1mA J3 -
F25 B18
RELAY 17
F28 B20 J4
20mA +
NOTES:
B21 J7
INPUT 2 1mA -
F27 B22
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. RELAY 18
J8
B24 + HIGH BREAK
20mA
(b) TERMINAL. B25 J11 - CONTACTS
INPUT 3 1mA
B26 RELAY 19
(c) PIN TERMINAL (P.C.B. TYPE) J12
+
B28
20mA J15
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. -
B29
INPUT 4 1mA RELAY 20
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. B30 J16
(USED BY V/Hz W2 PROTECTION ONLY). +

4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.


C1
RTD 1 C2
C3
C4
RTD 2 C5
C6
C7
OPTIONAL RTD 3 C8
C9

C28
CASE RTD 10 C29
EARTH
C30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 2
10P64237
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 H1 M11
-
a b c OPTO 9 WATCHDOG
D26 H2 M12 CONTACT
+
D3 H3 M13
B (1) - WATCHDOG
OPTO 10 M14 CONTACT
H4
D25 VFLUX + L1
D4 - H5 RELAY 1
D28 L2
F1 OPTO 11 H6
+ L3
C (1) RELAY 2
F2 H7 L4
-
F3 D27 E1 OPTO 12 L5
- H8
OPTO 1 + RELAY 3
F4 T2 D18 E2 L6
+ H9
- L7
F5 A (2) E3 - OPTO 13 H10
OPTO 2 + RELAY 4 L8
F6 E4
D17 + H11 L9
-
F7 E5 - OPTO 14
D20 H12 L10
OPTO 3 +
F8 E6 L11
+ H13 RELAY 5
B (2) -
E7 OPTO 15 L12
F9 - H14
D19 OPTO 4 + L13
F10 E8
+ H15
- RELAY 6 L14
D22 E9
F12 - OPTO 16 H16 L15
OPTO 5 +
C (2) E10
+ H17 L16
D21 E11 COMMON L17
F11 - CONNECTION H18 RELAY 7
F14 E12 OPTO 6 L18
+
GROUNDED WYE E13 K1
- RELAY 8
NEUTRAL TAILS OPTO 7 K2
F13 E14
+ K3
F16 HV LV E15 20mA
C1 RELAY 9
- K4
NOTE 2 NOTE 4 E16 OPTO 8 C2
COMMS + OUTPUT 1 1mA K5
NOT USED F15 E17 C3 RELAY 10 K6
F18 COMMON C5 K7
E18 CONNECTION 20mA
P2 S2 RELAY 11 K8
C6
OUTPUT 2 1mA K9
F17 M17 C7
-
K10
F20 SEE DRAWING
P1 S1 TN2 D14 EIA485/ C9 K11
10Px4001 20mA RELAY 12
KBUS
P2 S2 Y (LV) M18 C10 K12
+ PORT OUTPUT 3 1mA
F19 C11 K13
D13 M16
F22 SCN K14
C13 RELAY 13
P1 S1 TN1 D16 20mA K15
* M1 OUTPUT 4 1mA
C14
K16
F21 Y (HV) -
AC OR DC
M2 x AUX SUPPLY C15 K17
F24 D15 + CLIO RELAY 14
NOTES: C16 K18
CURRENT LOOP 20mA
INPUTS & OUTPUTS C17 J1
F23 INPUT 1 1mA
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. (OPTIONAL) RELAY 15 J2
F26 C18
J3
C20 RELAY 16
(b) TERMINAL. 20mA J4
F25 C21 J5
INPUT 2 1mA
F28 (c) PIN TERMINAL (P.C.B. TYPE) C22 RELAY 17 J6
C24 J7
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. 20mA
RELAY 18 J8
F27 C25
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. INPUT 3 1mA J9
(USED BY V/Hz W2 PROTECTION ONLY). C26
J10
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. C28 J11
20mA RELAY 19
C29 J12
INPUT 4 1mA
C30 J13
RELAY 20 J14
J15
B1 J16
RTD 1 B2 RELAY 21 J17
B3 J18

B4
RTD 2 B5
B6
OPTIONAL B7
RTD 3 B8
B9

B28
CASE
EARTH RTD 10 B29
B30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (16 I/P & 21 O/P) WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 1
10P64241
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 D24 NOTE 3 MiCOM P642 (PART)
A (1) n
D23
H1 M11
a b c -
WATCHDOG
D26 OPTO 9 M12
H2 CONTACT
D3 +
B (1) H3 M13
- WATCHDOG
D25 OPTO 10 M14 CONTACT
F1 VFLUX H4
+ L1
D4
F2 D28 H5 RELAY 1
- L2
F3 OPTO 11 H6
C (1) + L3
F4 E1 H7 RELAY 2 L4
D27 - -
E2 OPTO 1 OPTO 12 L5
F5 + H8
T2 D18 + RELAY 3 L6
F6 E3 - H9
A (2) - L7
E4 OPTO 2 OPTO 13
F7 + H10
D17 + RELAY 4 L8
F8 E5 - H11 L9
-
D20 E6 OPTO 3 OPTO 14
F9 + H12 L10
+
F10 B (2) E7 H13 RELAY 5 L11
- -
D19 E8 OPTO 4 OPTO 15 L12
F12 + H14
+ L13
D22 E9 - H15
- RELAY 6 L14
E10 OPTO 5 OPTO 16
F11 C (2) + H16 L15
+
F14 E11 H17 L16
D21 -
E12 OPTO 6 COMMON L17
+ CONNECTION H18 RELAY 7
L18
F13 GROUNDED WYE E13 -
F16 OPTO 7 K1
NEUTRAL TAILS E14
+ RELAY 8 K2
HV LV E15 - K3
NOT USED F15 OPTO 8 C1 RELAY 9
NOTE 4 E16 20mA K4
NOTE 2 +
F18 COMMS C2
E17 OUTPUT 1 1mA K5
COMMON C3 RELAY 10 K6
E18 CONNECTION
F17 C5 K7
P2 S2 20mA
F20 RELAY 11 K8
M17 C6
- OUTPUT 2 1mA K9
C7
P1 S1 TN2 D14 SEE DRAWING EIA485/ K10
F19 10Px4001 C9
KBUS 20mA RELAY 12 K11
F22 P2 S2 Y (LV) M18
+ PORT C10 K12
OUTPUT 3 1mA
D13 M16 K13
C11
F21
R ST TN1
SCN
K14
P1 S1 D16 C13 RELAY 13
F24 * M1
20mA K15
Y (HV) - C14
AC OR DC OUTPUT 4 1mA K16
M2 x AUX SUPPLY
D15 + C15 K17
F23 CLIO RELAY 14
K18
F26 C16
CURRENT LOOP 20mA
METROSIL INPUTS & OUTPUTS C17 J1
(OPTIONAL) INPUT 1 1mA RELAY 15
C18 J2
F25 J3
F28 NOTES: C20 RELAY 16
20mA J4
C21 J5
INPUT 2 1mA
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. RELAY 17
F27 C22 J6
C24 J7
(b) TERMINAL. 20mA
RELAY 18 J8
C25
INPUT 3 1mA J9
(c) PIN TERMINAL (P.C.B. TYPE) C26
J10
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. C28 J11
20mA RELAY 19
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. C29 J12
INPUT 4 1mA
(USED BY V/Hz W2 PROTECTION ONLY). C30 J13
RELAY 20 J14
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
J15
B1 J16
RTD 1 B2 J17
RELAY 21
B3 J18
B4
RTD 2 B5
B6
B7
OPTIONAL
RTD 3 B8
B9

CASE B28
EARTH
RTD 10 B29
B30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 2
10P64241
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No: C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 H1 M11
-
a b c OPTO 9 WATCHDOG
D26 H2 M12 CONTACT
+
D3 H3 M13
B (1) - WATCHDOG
F1 OPTO 10 M14 CONTACT
H4
F2 D25 VFLUX + L1
D4 - H5 RELAY 1
F3 D28 L2
OPTO 11 H6
+ L3
F4 C (1)
H7 L4 RELAY 2
-
F5 D27 E1 OPTO 12 L5
- H8
F6 OPTO 1 + RELAY 3
T2 D18 E2 L6
+ H9
- L7
F7 E3 OPTO 13
A (2) - H10
OPTO 2 + L8 RELAY 4
F8 E4
D17 + H11 L9
-
F9 E5 OPTO 14
- H12 L10 RELAY 5
D20 OPTO 3 +
F10 E6 L11
+ H13
B (2) -
F12 E7 L12 RELAY 6
- OPTO 15 H14
D19 OPTO 4 + L13
E8
+ H15
D22 - L14
F11 E9 OPTO 16 RELAY 7
- H16 L15
F14 OPTO 5 +
C (2) E10
+ H17 L16
D21 E11 COMMON L17
- CONNECTION H18 RELAY 8
F13 E12 OPTO 6 L18
F16 +
GROUNDED WYE E13 K1
-
NEUTRAL TAILS OPTO 7 K2 RELAY 9
E14
+ C1
NOT USED F15 HV LV 20mA K3
E15 -
F18 C2 K4 RELAY 10
NOTE 2 NOTE 4 E16 OPTO 8 OUTPUT 1 1mA
COMMS + C3 K5
E17 K6 RELAY 11
F17 COMMON C5
E18 20mA K7
F20 CONNECTION
P2 S2 C6 RELAY 12
OUTPUT 2 1mA K8
M17 C7 K9
-
F19 C9 K10 RELAY 13
F22 TN2 D14 SEE DRAWING EIA485/ 20mA
P1 S1 K11
10Px4001 KBUS C10
P2 S2 Y (LV) M18 OUTPUT 3 1mA RELAY 14
+ PORT K12
C11
F21 D13 M16 K13
SCN C13 K14
F24 20mA
P1 S1 TN1 D16 RELAY 15
C14
* M1 OUTPUT 4 1mA K15
Y (HV) - C15 K16
AC OR DC
F23
D15 M2
+
x AUX SUPPLY CLIO K17
F26 C16 RELAY 16
NOTES: CURRENT LOOP 20mA
K18
INPUTS & OUTPUTS C17
INPUT 1 1mA J1
(OPTIONAL)
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. C18 RELAY 17
F25 J2
F28 C20 J3
20mA
(b) TERMINAL. C21 J4 RELAY 18
INPUT 2 1mA
C22 J5
F27 (c) PIN TERMINAL (P.C.B. TYPE)
J6 RELAY 19
C24
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. 20mA J7
C25 RELAY 20
INPUT 3 1mA J8
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C26 J9
(USED BY V/Hz W2 PROTECTION ONLY).
C28 J10 RELAY 21
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. 20mA
C29 J11
INPUT 4 1mA RELAY 22
J12
C30
J13
J14
B1 RELAY 23
J15
RTD 1 B2 J16
B3 J17
B4 RELAY 24
J18
RTD 2 B5
B6
B7
OPTIONAL RTD 3 B8
B9

B28
CASE RTD 10 B29
EARTH B30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (16 I/P & 24 O/P) WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 1
10P64245
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 D24 NOTE 3 MiCOM P642 (PART)
A (1) n
D23
H1 M11
a b c -
WATCHDOG
D26 OPTO 9 M12
F1 H2 CONTACT
D3 +
F2 B (1) H3 M13
- WATCHDOG
D25 OPTO 10 M14 CONTACT
F3 VFLUX H4
+ L1
D4
F4 D28 - H5 RELAY 1
L2
F5 OPTO 11 H6
C (1) + L3
F6 E1 - H7 L4 RELAY 2
D27 -
E2 OPTO 1 OPTO 12 L5
F7 + H8
T2 D18 +
L6 RELAY 3
F8 E3 - H9
A (2) - L7
E4 OPTO 2 OPTO 13
F9 + H10 RELAY 4
D17 + L8
F10 E5 - H11 L9
-
D20 E6 OPTO 3 OPTO 14 RELAY 5
F12 + H12 L10
+
B (2) E7 H13 L11
- -
OPTO 4 OPTO 15 L12 RELAY 6
D19 E8 H14
F11 + + L13
F14 D22 E9 H15
- - L14
E10 OPTO 5 OPTO 16 RELAY 7
C (2) + H16 L15
+
F13 E11 - H17 L16
D21
F16 E12 OPTO 6 COMMON L17
+ CONNECTION H18 RELAY 8
E13 L18
GROUNDED WYE -
NOT USED F15 NEUTRAL TAILS E14 OPTO 7 K1
+ RELAY 9
F18 K2
HV LV E15 - C1 K3
OPTO 8 20mA
NOTE 4 E16 K4 RELAY 10
NOTE 2 + C2
F17 COMMS OUTPUT 1 1mA
E17 K5
F20 C3
COMMON RELAY 11
E18 CONNECTION K6
C5
20mA K7
P2 S2
F19 C6 RELAY 12
OUTPUT 2 1mA K8
M17
F22 - C7 K9
P1 S1 TN2 D14 SEE DRAWING EIA485/ C9 K10 RELAY 13
10Px4001 KBUS 20mA
P2 S2 Y (LV) M18 C10 K11
F21 + PORT OUTPUT 3 1mA
F24 K12 RELAY 14
D13 M16 C11
K13
R ST TN1
SCN
C13
P1 S1 D16 20mA K14
* RELAY 15
F23 M1 C14 K15
Y (HV) - OUTPUT 4 1mA
F26 AC OR DC
M2 x AUX SUPPLY C15 K16
D15 +
CLIO CLIO K17
C16 RELAY 16
CURRENT LOOP 20mA
F25 K18
INPUTS & OUTPUTS C17
F28 METROSIL (OPTIONAL) INPUT 1 1mA J1
C18 RELAY 17
J2
C20 J3
F27 NOTES: 20mA
C21 J4 RELAY 18
INPUT 2 1mA
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. C22 J5
J6 RELAY 19
C24
20mA J7
(b) TERMINAL. C25
INPUT 3 1mA J8 RELAY 20
(c) PIN TERMINAL (P.C.B. TYPE) C26 J9
C28 J10 RELAY 21
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. 20mA
C29 J11
INPUT 4 1mA RELAY 22
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. J12
C30
(USED BY V/Hz W2 PROTECTION ONLY). J13
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. J14
RELAY 23
J15
B1
J16
RTD 1 B2
J17
B3 RELAY 24
J18
B4
RTD 2 B5
B6
OPTIONAL B7
RTD 3 B8
B9

B28
CASE RTD 10 B29
EARTH
B30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/02024 Name: S WOOTTON Sht: 2
10P64245
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 H1 M11
-
a b c OPTO 9 WATCHDOG
D26 H2 M12 CONTACT
+
D3 H3 M13
B (1) - WATCHDOG
OPTO 10 M14 CONTACT
H4
D25 VFLUX + L1
D4 - H5 RELAY 1
D28 L2
OPTO 11 H6
+ L3
C (1)
H7 L4 RELAY 2
-
D27 E1 OPTO 12 L5
- H8
OPTO 1 + RELAY 3
T2 D18 E2 L6
+ H9
- L7
A (2) E3 - OPTO 13 H10 RELAY 4
OPTO 2 + L8
E4
D17 + H11 L9
-
E5 - OPTO 14 RELAY 5
D20 H12 L10
OPTO 3 +
E6 L11
F1 + H13
B (2) -
E7 OPTO 15 L12 RELAY 6
- H14
F2 D19 OPTO 4 + L13
E8
F3 + H15
D22 - L14
E9 OPTO 16 RELAY 7
F4 - H16 L15
OPTO 5 +
C (2) E10
F5 + H17 L16
D21 E11 COMMON L17
- CONNECTION H18 RELAY 8
F6 OPTO 6
E12 L18
F7 + J1
GROUNDED WYE E13 - K1
- OPTO 17
F8 NEUTRAL TAILS OPTO 7 J2 K2 RELAY 9
E14 +
F9 +
HV LV J3 K3
E15 - -
F10 OPTO 18 K4 RELAY 10
NOTE 4 OPTO 8 J4
NOTE 2 E16 +
F12 COMMS + K5
E17 J5
- K6 RELAY 11
COMMON OPTO 19 J6
E18 CONNECTION + K7
F11 P2 S2 J7 K8 RELAY 12
F14 M17 -
- OPTO 20 K9
J8
+ K10 RELAY 13
TN2 D14 SEE DRAWING EIA485/
P1 S1 K11
F13 10Px4001 KBUS
P2 S2 Y (LV) M18 B1 RELAY 14
F16 + PORT K12
D13 M16 RTD 1 B2 K13
SCN B3 K14
NOT USED F15 P1 S1 TN1 D16 RELAY 15
* B4 K15
F18 M1 -
Y (HV) RTD 2 B5 K16
AC OR DC
M2 x AUX SUPPLY B6 K17
D15 + RELAY 16
F17 NOTES: B7 K18
F20 OPTIONAL RTD 3 B8 J9
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. B9 RELAY 17
J10
F19 J11
F22
(b) TERMINAL. J12 RELAY 18
B28 J13
(c) PIN TERMINAL (P.C.B. TYPE)
RTD 10 B29 J14 RELAY 19
F21 B30
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. J15
F24
J16
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY). C1 J17
20mA RELAY 20
F23 J18
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. C2
F26 OUTPUT 1 1mA
C3
C5
F25 20mA
F28 C6
OUTPUT 2 1mA
C7
C9
F27 20mA
C10
OUTPUT 3 1mA
C11
C13
20mA
C14
OUTPUT 4 1mA
C15
CLIO
C16
CURRENT LOOP 20mA
INPUTS & OUTPUTS C17
INPUT 1 1mA
(OPTIONAL)
C18
C20
20mA
C21
INPUT 2 1mA
C22
C24
20mA
C25
INPUT 3 1mA
C26
C28
20mA
C29
INPUT 4 1mA
C30

CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (20 I/P & 20 O/P) WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 1
10P64249
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 D24 NOTE 3 MiCOM P642 (PART)
A (1) n
D23
- H1 M11
a b c OPTO 9 WATCHDOG
D26 H2 M12 CONTACT
+
D3 M13
B (1) H3
- WATCHDOG
OPTO 10 M14 CONTACT
D25 VFLUX H4
+ L1
D4 H5
D28 - L2 RELAY 1
OPTO 11 H6
C (1) + L3
E1 H7 L4 RELAY 2
D27 - -
F1 E2 OPTO 1 OPTO 12 H8 L5
T2 D18 + + RELAY 3
L6
F2 E3 H9
- - L7
A (2) OPTO 2 OPTO 13
F3 E4 H10 RELAY 4
+ + L8
D17
F4 E5 H11 L9
- -
F5 D20 E6 OPTO 3 OPTO 14 H12 L10 RELAY 5
+ +
F6 B (2) E7 H13 L11
- - RELAY 6
OPTO 4 OPTO 15 L12
F7 D19 E8 H14
+ + L13
F8 D22 E9 - H15 L14
-
OPTO 5 OPTO 16 RELAY 7
F9 E10 H16 L15
C (2) + +
F10 E11 H17 L16
D21 -
OPTO 6 COMMON L17
F12 E12 CONNECTION H18 RELAY 8
+
L18
GROUNDED WYE E13 - J1
OPTO 7 - K1
F11 NEUTRAL TAILS E14
+ OPTO 17 J2 K2 RELAY 9
F14 +
HV LV E15 - K3
J3
E16 OPTO 8 - RELAY 10
NOTE 2 NOTE 4 + OPTO 18 K4
J4
F13 COMMS +
E17 K5
F16 COMMON J5
- K6 RELAY 11
E18 CONNECTION OPTO 19 J6 K7
P2 S2 +
J7 K8 RELAY 12
NOT USED F15 M17
- -
F18 OPTO 20 K9
J8
P1 S1 TN2 D14 SEE DRAWING EIA485/ + K10 RELAY 13
10Px4001 KBUS K11
P2 S2 Y (LV) M18
F17 + PORT RELAY 14
B1 K12
F20 D13 M16 RTD 1 B2 K13
R ST TN1
SCN
B3 K14
P1 S1 D16 RELAY 15
F19 * M1 B4 K15
Y (HV) -
F22 AC OR DC RTD 2 B5 K16
M2 x AUX SUPPLY
D15 + B6 K17
RELAY 16
B7 K18
F21
F24
METROSIL OPTIONAL RTD 3 B8 J9
B9 J10 RELAY 17
J11
NOTES:
F23 J12 RELAY 18
F26 B28 J13
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
RTD 10 B29 J14 RELAY 19
F25 B30 J15
(b) TERMINAL.
F28 J16
(c) PIN TERMINAL (P.C.B. TYPE) C1 J17
20mA RELAY 20
J18
F27 C2
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. OUTPUT 1 1mA
C3
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY). C5
20mA
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. C6
OUTPUT 2 1mA
C7
C9
20mA
C10
OUTPUT 3 1mA
C11
C13
20mA
C14
OUTPUT 4 1mA
C15
CLIO
C16
CURRENT LOOP 20mA
INPUTS & OUTPUTS C17
INPUT 1 1mA
(OPTIONAL)
C18
C20
20mA
C21
INPUT 2 1mA
C22
C24
20mA
C25
INPUT 3 1mA
C26
C28
20mA
C29
INPUT 4 1mA
C30
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 2
10P64249
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 H1 M11
-
a b c OPTO 9 WATCHDOG
D26 H2 M12 CONTACT
+
D3 H3 M13
B (1) - WATCHDOG
OPTO 10 M14 CONTACT
H4
D25 VFLUX + L1
D4 - H5 RELAY 1
D28 L2
OPTO 11 H6
+ L3
C (1)
H7 L4 RELAY 2
-
D27 E1 OPTO 12 L5
- H8
OPTO 1 + RELAY 3
T2 D18 E2 L6
+ H9
- L7
A (2) E3 - OPTO 13
F1 H10 RELAY 4
OPTO 2 + L8
E4
F2 D17 + H11 L9
-
E5 - OPTO 14 RELAY 5
F3 D20 H12 L10
OPTO 3 +
E6 L11
F4 + H13
B (2) -
E7 OPTO 15 L12 RELAY 6
F5 - H14
D19 OPTO 4 + L13
E8
F6 + H15
D22 - L14
E9 OPTO 16 RELAY 7
F7 - H16 L15
OPTO 5 +
C (2) E10
F8 + H17 L16
D21 E11 COMMON L17
F9 - CONNECTION H18 RELAY 8
E12 OPTO 6 L18
F10 + J1
GROUNDED WYE E13 - K1
F12 - OPTO 17 J2
NEUTRAL TAILS OPTO 7 + K2 RELAY 9
E14
+ J3
HV LV - K3
E15 -
F11 OPTO 18 J4 K4 RELAY 10
NOTE 2 NOTE 4 E16 OPTO 8 +
F14 COMMS + J5 K5
E17 -
OPTO 19 K6 RELAY 11
COMMON J6
E18 + K7
F13 CONNECTION
P2 S2 - J7 RELAY 12
K8
F16 OPTO 20
M17 J8 K9
- +
J9 K10 RELAY 13
TN2 D14 SEE DRAWING EIA485/ -
NOT USED F15 P1 S1 OPTO 21
10Px4001 KBUS J10 K11
F18 P2 S2 Y (LV) M18 +
+ PORT K12 RELAY 14
- J11
D13 M16 K13
OPTO 22 J12
SCN + K14
F17 TN1 D16 RELAY 15
P1 S1 J13
F20 * M1 - K15
Y (HV) - OPTO 23 J14 K16
AC OR DC +
M2 x AUX SUPPLY K17
D15 + J15
F19 - RELAY 16
NOTES: K18
OPTO 24 J16
F22 +
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. J17
COMMON
F21 CONNECTION J18
F24 (b) TERMINAL.

(c) PIN TERMINAL (P.C.B. TYPE)


C1
F23 20mA B1
F26 2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. C2 B2 RTD 1
OUTPUT 1 1mA
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. C3 B3
(USED BY V/Hz W2 PROTECTION ONLY). B4
F25 C5
20mA
F28 4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. B5 RTD 2
C6
OUTPUT 2 1mA B6
C7
B7
F27 C9 B8 RTD 3 OPTIONAL
20mA
C10 B9
OUTPUT 3 1mA
C11
C13
20mA
B28
C14
OUTPUT 4 1mA B29 RTD 10
C15 B30
CLIO
C16
CURRENT LOOP 20mA
INPUTS & OUTPUTS C17
INPUT 1 1mA
(OPTIONAL)
C18
C20
20mA
C21
INPUT 2 1mA
C22
C24
20mA
C25
INPUT 3 1mA
C26
C28
20mA
C29
INPUT 4 1mA
C30
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (24 I/P & 16 O/P) WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 1
10P64257
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 D24 NOTE 3 MiCOM P642 (PART)
A (1) n
D23
a H1 M11
b -
WATCHDOG
D26 OPTO 9 H2 M12 CONTACT
D3 +
B (1) H3 M13
- WATCHDOG
D25 OPTO 10 M14 CONTACT
VFLUX H4
+ L1
D4
D28 - H5 RELAY 1
L2
OPTO 11 H6
C (1) + L3
E1 - H7 L4 RELAY 2
D27 -
E2 OPTO 1 OPTO 12 L5
+ H8
T2 D18 +
L6 RELAY 3
E3 - H9
F1 A (2) - L7
E4 OPTO 2 OPTO 13
+ H10 RELAY 4
F2 D17 + L8
E5 - H11
- L9
F3 D20 OPTO 3
E6 OPTO 14 H12 L10 RELAY 5
+ +
F4 B (2) E7 H13 L11
- -
F5 OPTO 4 L12 RELAY 6
D19 E8 OPTO 15 H14
+ +
F6 L13
D22 E9 - H15
F7 - L14
E10 OPTO 5 OPTO 16 RELAY 7
C (2) + H16 L15
F8 +
E11 - H17 L16
D21
F9 OPTO 6 COMMON L17
E12 H18
+ CONNECTION RELAY 8
F10 L18
GROUNDED WYE E13 -
- J1
F12 OPTO 7 K1
NEUTRAL TAILS E14
+ OPTO 17 J2 RELAY 9
+ K2
HV LV E15 -
- J3 K3
F11 E16 OPTO 8
NOTE 2 NOTE 4 + OPTO 18 J4 K4 RELAY 10
F14 COMMS +
E17 K5
COMMON - J5
E18 OPTO 19 K6 RELAY 11
CONNECTION J6
F13 + K7
F16 P2 S2
- J7 RELAY 12
K8
M17 OPTO 20
- J8 K9
+
NOT USED F15 P1 S1 TN2 D14 SEE DRAWING EIA485/ J9 K10 RELAY 13
10Px4001 KBUS -
F18 P2 S2 Y (LV) M18 OPTO 21 J10 K11
+ PORT +
K12 RELAY 14
D13 M16 - J11
K13
F17 R ST TN1
SCN OPTO 22 J12
P1 S1 D16 + K14
F20 * RELAY 15
M1 - J13 K15
Y (HV) -
AC OR DC OPTO 23
M2 x AUX SUPPLY J14 K16
D15 + +
F19 J15 K17
- RELAY 16
F22 K18
OPTO 24 J16
METROSIL +
J17
F21 COMMON
CONNECTION J18
F24 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


F23 C1
F26 20mA B1
(b) TERMINAL. C2 B2 RTD 1
OUTPUT 1 1mA
C3 B3
F25 (c) PIN TERMINAL (P.C.B. TYPE)
C5 B4
F28 20mA
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. B5 RTD 2
C6
OUTPUT 2 1mA B6
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. C7
F27 (USED BY V/Hz W2 PROTECTION ONLY). B7
C9 B8 RTD 3
20mA OPTIONAL
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C10 B9
OUTPUT 3 1mA
C11
C13
20mA
B28
C14
OUTPUT 4 1mA B29 RTD 10
C15 B30
CLIO
C16
CURRENT LOOP 20mA
INPUTS & OUTPUTS C17
(OPTIONAL) INPUT 1 1mA
C18
C20
20mA
C21
INPUT 2 1mA
C22
C24
20mA
C25
INPUT 3 1mA
C26
C28
20mA
C29
INPUT 4 1mA
CASE C30
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 2
10P64257
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 C1 M11
-
a b c OPTO 9 WATCHDOG
D26 C2 M12 CONTACT
+
D3 C3 M13
B (1) - WATCHDOG
OPTO 10 M14 CONTACT
C4
D25 VFLUX + L1
D4 - C5 RELAY 1
D28 L2
OPTO 11 C6
+ L3
C (1)
C7 L4 RELAY 2
-
D27 E1 - OPTO 12 L5
F1 C8
OPTO 1 + RELAY 3
T2 D18 E2 L6
F2 + C9
- L7
A (2) E3 - OPTO 13
F3 C10 RELAY 4
OPTO 2 + L8
E4
F4 D17 + C11 L9
-
E5 - OPTO 14 RELAY 5
F5 D20 C12 L10
OPTO 3 +
E6 L11
F6 + C13
B (2) -
E7 OPTO 15 L12 RELAY 6
- C14
F7 D19 OPTO 4 + L13
E8
F8 + C15
D22 - L14
E9 OPTO 16 RELAY 7
- C16 L15
F9 OPTO 5 +
C (2) E10
+ C17 L16
F10
D21 E11 COMMON L17
F12 - CONNECTION C18 RELAY 8
E12 OPTO 6 L18
+ B1
GROUNDED WYE E13 - K1
- OPTO 17 B2
F11 NEUTRAL TAILS OPTO 7 + K2 RELAY 9
E14
F14 + B3
HV LV - K3
E15 - OPTO 18 B4 K4 RELAY 10
NOTE 2 NOTE 4 E16 OPTO 8 +
F13 COMMS + B5 K5
E17 -
F16 OPTO 19 K6 RELAY 11
COMMON B6
E18 + K7
CONNECTION
P2 S2 - B7 RELAY 12
K8
NOT USED F15 OPTO 20 B8
M17 + K9
F18 -
B9 K10 RELAY 13
TN2 D14 SEE DRAWING EIA485/ -
P1 S1 OPTO 21
10Px4001 KBUS B10 K11
P2 S2 Y (LV) M18 +
F17 + PORT K12 RELAY 14
- B11
F20 D13 M16 K13
OPTO 22 B12
SCN + K14
P1 S1 TN1 D16 RELAY 15
B13
F19 * M1 - K15
Y (HV) - OPTO 23 B14 K16
F22 AC OR DC +
M2 x AUX SUPPLY K17
D15 + B15
- RELAY 16
NOTES: K18
OPTO 24 B16
F21 +
F24 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. B17 J3 -
COMMON
CONNECTION B18 RELAY 17
J4
F23 (b) TERMINAL. +
F26 J7 -
(c) PIN TERMINAL (P.C.B. TYPE)
RELAY 18
J8
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. + HIGH BREAK
F25
J11 - CONTACTS
F28 3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
(USED BY V/Hz W2 PROTECTION ONLY). RELAY 19
J12
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. +
F27
J15 -
RELAY 20
J16
+
H3 -
RELAY 21
H4
+
H7 -
RELAY 22
H8
+ HIGH BREAK
H11 - CONTACTS
RELAY 23
H12
+
H15 -
RELAY 24
H16
CASE +
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
C DIFFERENTIAL (16 I/P & 16 O/P + 8 HS HB) WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 07/05/2024 Name: S WOOTTON Sht: 1
10P64258
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 D24 NOTE 3 MiCOM P642 (PART)
A (1) n
D23
- C1 M11
a b OPTO 9 WATCHDOG
D26 C2 M12 CONTACT
+
D3 M13
B (1) C3 WATCHDOG
-
OPTO 10 M14 CONTACT
D25 VFLUX C4
+ L1
D4 C5
D28 - L2 RELAY 1
OPTO 11 C6
C (1) + L3
E1 C7 L4 RELAY 2
D27 - -
OPTO 1 OPTO 12 C8 L5
E2 +
T2 D18 + L6 RELAY 3
F1 E3 C9
- - L7
F2 A (2) OPTO 2 OPTO 13
E4 C10 RELAY 4
+ + L8
F3 D17
E5 - C11 L9
-
F4 D20 E6 OPTO 3 OPTO 14 C12 L10 RELAY 5
+ +
F5 B (2) C13 L11
E7 - -
OPTO 15 L12 RELAY 6
F6 D19 E8 OPTO 4 C14
+ + L13
F7 E9 C15
D22 - - L14
OPTO 5 OPTO 16 RELAY 7
F8 E10 C16 L15
C (2) + +
F9 E11 C17 L16
D21 - COMMON
F10 OPTO 6 C18 L17
E12 CONNECTION RELAY 8
+ L18
F12 E13 B1
GROUNDED WYE - - K1
NEUTRAL TAILS E14 OPTO 7 OPTO 17 B2
+ + K2 RELAY 9
F11 E15 B3
HV LV - - K3
F14 OPTO 8 OPTO 18
NOTE 4 E16 B4 K4 RELAY 10
NOTE 2 + +
COMMS K5
E17 B5
COMMON -
F13 OPTO 19 K6 RELAY 11
E18 CONNECTION B6
F16 + K7
P2 S2 B7
- K8 RELAY 12
M17 OPTO 20 B8
- + K9
NOT USED F15
F18 P1 S1 TN2 D14 SEE DRAWING EIA485/ - B9 K10 RELAY 13
10Px4001 KBUS OPTO 21 K11
Y (LV) M18 B10
P2 S2 + PORT +
K12 RELAY 14
D13 - B11
F17 M16 K13
F20 R ST SCN OPTO 22 B12
P1 S1 TN1 D16 + K14
RELAY 15
* M1 - B13 K15
Y (HV) -
AC OR DC OPTO 23 B14 K16
F19 M2 x AUX SUPPLY +
F22 D15 + K17
- B15 RELAY 16
OPTO 24 K18
B16
METROSIL +
F21 B17 J3 -
F24 COMMON
CONNECTION B18 RELAY 17
NOTES: J4
+
F23 J7 -
F26 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
RELAY 18
J8
+ HIGH BREAK
(b) TERMINAL.
J11 - CONTACTS
F25
F28 (c) PIN TERMINAL (P.C.B. TYPE) RELAY 19
J12
+
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
J15 -
F27
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. RELAY 20
(USED BY V/Hz W2 PROTECTION ONLY). J16
+
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
H3 -
RELAY 21
H4
+
H7 -
RELAY 22
H8
+ HIGH BREAK
H11 - CONTACTS
RELAY 23
H12
+
H15 -
RELAY 24
H16
+

CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXT CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
C SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 08/05/2024 Name: S WOOTTON Sht: 2
10P64258
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 H1 M11
-
a b c OPTO 9 WATCHDOG
D26 H2 M12 CONTACT
+
D3 H3 M13
B (1) - WATCHDOG
OPTO 10 M14 CONTACT
H4
D25 VFLUX + L1
D4 - H5 RELAY 1
D28 L2
OPTO 11 H6
+ L3
C (1)
H7 L4 RELAY 2
-
D27 E1 OPTO 12 L5
- H8
OPTO 1 + RELAY 3
F1 T2 D18 E2 L6
+ H9
- L7
F2 A (2) E3 - OPTO 13 H10 RELAY 4
OPTO 2 + L8
F3 E4
D17 + H11 L9
-
F4 E5 - OPTO 14 RELAY 5
D20 H12 L10
OPTO 3 +
F5 E6 L11
+ H13
B (2) -
E7 OPTO 15 L12 RELAY 6
F6 - H14
D19 OPTO 4 + L13
F7 E8
+ H15
D22 - L14
E9 OPTO 16 RELAY 7
F8 - H16 L15
OPTO 5 +
C (2) E10
F9 + H17 L16
D21 E11 COMMON L17
F10 - H18 RELAY 8
CONNECTION
E12 OPTO 6 L18
F12 +
- C1
GROUNDED WYE E13 OPTO 17
K1
- C2
NEUTRAL TAILS OPTO 7 + K2 RELAY 9
E14
F11 + C3
HV LV - K3
F14 E15 - OPTO 18 C4 K4 RELAY 10
NOTE 2 NOTE 4 E16 OPTO 8 +
COMMS + C5 K5
E17 -
F13 OPTO 19 K6 RELAY 11
COMMON C6
F16 E18 + K7
CONNECTION
P2 S2 - C7 RELAY 12
K8
OPTO 20 C8
M17 + K9
NOT USED F15 -
F18 C9 K10 RELAY 13
TN2 D14 SEE DRAWING EIA485/ -
P1 S1 OPTO 21 K11
10Px4001 KBUS C10
P2 S2 Y (LV) M18 +
+ PORT K12 RELAY 14
- C11
F17 D13 M16 K13
F20 OPTO 22 C12
SCN + K14
P1 S1 TN1 D16 RELAY 15
C13
* M1 - K15
Y (HV) - OPTO 23 C14 K16
F19 AC OR DC +
M2 x AUX SUPPLY K17
F22 D15 + C15
- RELAY 16
NOTES: K18
OPTO 24 C16
+ J1
F21 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. C17
J2 RELAY 17
F24 COMMON
CONNECTION C18 J3
(b) TERMINAL. J4 RELAY 18
F23 J5
(c) PIN TERMINAL (P.C.B. TYPE) B1
F26 20mA J6 RELAY 19
B2 J7
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. OUTPUT 1 1mA
B3 J8 RELAY 20
F25 3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
F28 (USED BY V/Hz W2 PROTECTION ONLY). B5 J9
20mA
J10 RELAY 21
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. B6
OUTPUT 2 1mA J11
F27 B7
J12 RELAY 22
B9 J13
20mA
B10 J14
OUTPUT 3 1mA RELAY 23
B11 J15
J16
B13
20mA J17
B14 RELAY 24
OUTPUT 4 1mA J18
B15
CLIO B1
B16
CURRENT LOOP 20mA
B2 RTD 1
INPUTS & OUTPUTS B17
INPUT 1 1mA B3
(OPTIONAL)
B18
B4
B20 B5 RTD 2
20mA
B21 B6
INPUT 2 1mA
B22 B7
B8 RTD 3 OPTIONAL
B24
20mA B9
B25
INPUT 3 1mA
B26
B28 B28
20mA
CASE B29 B29 RTD 10
INPUT 4 1mA
EARTH B30
B30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (24 I/P & 24 O/P WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 1
10P64259
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 D24 NOTE 3 MiCOM P642 (PART)
A (1) n
D23 H1 M11
-
a b OPTO 9 H2 M12
WATCHDOG
D26 + CONTACT
D3 H3 M13
B (1) - WATCHDOG
OPTO 10 M14 CONTACT
D25 H4
VFLUX + L1
D4 - H5 RELAY 1
D28 L2
OPTO 11 H6
+ L3
C (1)
H7 L4 RELAY 2
E1 - -
D27 OPTO 12 L5
E2 OPTO 1 H8
+ + RELAY 3
T2 D18 H9
L6
E3 - - L7
F1 A (2) OPTO 2 OPTO 13 H10
E4 + L8 RELAY 4
+
F2 D17 H11
E5 - L9
-
F3 D20 OPTO 3 OPTO 14 H12 L10 RELAY 5
E6 +
+ L11
F4 H13
B (2) E7 -
- L12 RELAY 6
F5 OPTO 4 OPTO 15 H14
D19 E8 + L13
+
F6 H15
D22 E9 - - L14
F7 OPTO 16 RELAY 7
E10 OPTO 5 H16 L15
C (2) + +
F8 H17 L16
E11 -
F9 D21 COMMON L17
E12 OPTO 6 CONNECTION H18 RELAY 8
+ L18
F10
E13 - C1
F12
GROUNDED WYE - K1
OPTO 7 OPTO 17 C2
NEUTRAL TAILS E14
+ + K2 RELAY 9
E15 C3 K3
HV LV - -
F11 OPTO 8 OPTO 18 C4 K4 RELAY 10
NOTE 4 E16 +
F14 NOTE 2 +
COMMS C5 K5
E17 -
COMMON OPTO 19 K6 RELAY 11
E18 CONNECTION C6
+ K7
F13
P2 S2 - C7 RELAY 12
F16 K8
M17 OPTO 20 C8
- + K9
C9 K10 RELAY 13
NOT USED F15 P1 S1 TN2 D14 SEE DRAWING EIA485/ -
10Px4001 KBUS OPTO 21 C10 K11
F18 Y (LV) M18 +
P2 S2 + PORT K12 RELAY 14
- C11
D13 M16 K13
OPTO 22 C12
F17 R ST TN1
SCN + K14
P1 S1 D16 RELAY 15
F20 C13
* M1 - K15
Y (HV) - OPTO 23
AC OR DC C14 K16
M2 x AUX SUPPLY +
D15 + C15 K17
F19 - RELAY 16
F22 OPTO 24 K18
C16
+ J1
METROSIL C17
J2 RELAY 17
COMMON
F21 CONNECTION C18 J3
F24 NOTES: J4 RELAY 18
J5
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. B1 RELAY 19
F23 20mA J6
F26 B2 J7
OUTPUT 1 1mA
(b) TERMINAL. B3 J8 RELAY 20
B5 J9
F25 (c) PIN TERMINAL (P.C.B. TYPE) 20mA
J10 RELAY 21
F28 B6
OUTPUT 2 1mA J11
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
B7
J12 RELAY 22
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. B9
F27 20mA J13
(USED BY V/Hz W2 PROTECTION ONLY).
B10 J14
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. OUTPUT 3 1mA RELAY 23
B11 J15
J16
B13
20mA J17
B14 RELAY 24
OUTPUT 4 1mA J18
B15
CLIO B1
B16
CURRENT LOOP 20mA
B2 RTD 1
INPUTS & OUTPUTS B17
INPUT 1 1mA B3
(OPTIONAL)
B18
B4
B20 B5 RTD 2
20mA
B21 B6
INPUT 2 1mA
B22 B7
B8 RTD 3 OPTIONAL
B24
20mA B9
B25
INPUT 3 1mA
B26
B28 B28
20mA
CASE B29 B29 RTD 10
EARTH INPUT 4 1mA
B30
B30

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 2
10P64259
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
MiCOM P642 (PART)
T1 D24 NOTE 3
A (1) n
D23 C1 M11
-
a b c OPTO 9 WATCHDOG
D26 C2 M12 CONTACT
+
D3 C3 M13
F1 B (1) - WATCHDOG
OPTO 10 M14 CONTACT
F2 C4
D25 VFLUX + L1
F3 D4 - C5 RELAY 1
D28 L2
OPTO 11 C6
F4 + L3
C (1)
F5 C7 L4 RELAY 2
-
D27 E1 OPTO 12 L5
F6 - C8
OPTO 1 + RELAY 3
T2 D18 E2 L6
F7 + C9
- L7
A (2) E3 - OPTO 13
F8 C10 RELAY 4
OPTO 2 + L8
E4
F9 D17 + C11 L9
-
E5 - OPTO 14 RELAY 5
F10 D20 C12 L10
OPTO 3 +
E6 L11
F12 + C13
B (2) -
E7 OPTO 15 L12 RELAY 6
- C14
D19 OPTO 4 + L13
E8
F11 + C15
- L14
D22 E9 RELAY 7
F14 - OPTO 16 C16
+ L15
C (2) E10 OPTO 5
+ C17 L16
D21 E11 COMMON L17
F13 - CONNECTION C18 RELAY 8
F16 E12 OPTO 6 L18
+ B1
GROUNDED WYE E13 - K1
- OPTO 17 B2
NEUTRAL TAILS OPTO 7 + K2 RELAY 9
NOT USED F15 E14
+ B3
F18 HV LV - K3
E15 - OPTO 18 B4 K4 RELAY 10
NOTE 2 NOTE 4 E16 OPTO 8 +
COMMS + B5 K5
F17 E17 -
OPTO 19 K6 RELAY 11
F20 COMMON B6
E18 + K7
CONNECTION
P2 S2 - B7 RELAY 12
K8
OPTO 20 B8
F19 M17 + K9
-
F22 B9 K10 RELAY 13
TN2 D14 SEE DRAWING EIA485/ -
P1 S1 OPTO 21 K11
10Px4001 KBUS B10
P2 S2 Y (LV) M18 +
+ PORT K12 RELAY 14
F21 - B11
D13 M16 K13
F24 OPTO 22 B12
SCN + K14
P1 S1 TN1 D16 RELAY 15
B13
* M1 - K15
F23 Y (HV) - OPTO 23 B14 K16
AC OR DC +
F26 M2 x AUX SUPPLY K17
D15 + B15
- RELAY 16
NOTES: K18
OPTO 24 B16
+ J1
F25 B17
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT. J2 RELAY 17
F28 COMMON
CONNECTION B18 J3
(b) TERMINAL. J4 RELAY 18
F27 J5
(c) PIN TERMINAL (P.C.B. TYPE) H1 J6 RELAY 19
H2 RELAY 25 J7
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
H3 J8 RELAY 20
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. H4 RELAY 26
(USED BY V/Hz W2 PROTECTION ONLY). J9
H5 J10 RELAY 21
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. H6 RELAY 27
J11
H7 J12 RELAY 22
H8 RELAY 28 J13
H9 J14
RELAY 23
H10 RELAY 29
J15
H11 J16
H12 RELAY 30 J17
H13 RELAY 24
J18
H14
RELAY 31
H15
H16
CASE
EARTH H17
RELAY 32
H18

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. EXTERNAL CONNECTION DIAGRAM: 2 BIAS INPUT TRANSFORMER
B DIFFERENTIAL (24 I/P & 32 O/P) WITH 1 POLE VT INPUT (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 1
10P64262
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER N
T1 D24 NOTE 3 MiCOM P642 (PART)
A (1) n
D23
a b - C1 M11
D26 OPTO 9 WATCHDOG
C2 M12 CONTACT
D3 +
B (1) M13
F1 - C3 WATCHDOG
D25 OPTO 10 M14 CONTACT
F2 VFLUX C4
+ L1
D4
F3 D28 C5 RELAY 1
- L2
C (1) OPTO 11 C6
F4 + L3
E1 - C7 L4 RELAY 2
F5 D27 -
E2 OPTO 1 OPTO 12 L5
+ C8
F6 T2 D18 +
L6 RELAY 3
E3 - C9
F7 A (2) - L7
E4 OPTO 2 OPTO 13
F8 + C10 RELAY 4
D17 + L8
E5 - C11
F9 - L9
D20 E6 OPTO 3 OPTO 14
+ C12 L10 RELAY 5
F10 +
B (2) E7 L11
F12 - - C13
D19 E8 OPTO 4 OPTO 15 L12 RELAY 6
+ C14
+ L13
D22 E9 - C15
F11 - L14
E10 OPTO 5 OPTO 16 RELAY 7
F14 C (2) + C16 L15
+
E11 - C17 L16
D21
E12 OPTO 6 COMMON L17
F13 + CONNECTION C18 RELAY 8
F16 E13 L18
GROUNDED WYE - B1
OPTO 7 - K1
NEUTRAL TAILS E14
+ OPTO 17 B2 RELAY 9
+ K2
NOT USED F15 HV LV E15 -
- B3 K3
F18 NOTE 4 E16 OPTO 8
NOTE 2 + OPTO 18 B4 K4 RELAY 10
COMMS +
E17 K5
COMMON - B5
F17 E18 CONNECTION OPTO 19 K6 RELAY 11
B6
F20 + K7
P2 S2
- B7 RELAY 12
M17 K8
- OPTO 20 B8
+ K9
F19
P1 S1 TN2 D14 SEE DRAWING EIA485/ B9 K10 RELAY 13
F22 10Px4001 -
KBUS
P2 S2 Y (LV) M18 OPTO 21 B10 K11
+ PORT +
K12 RELAY 14
D13 M16 B11
F21 - K13
F24 R ST TN1
SCN OPTO 22 B12
P1 S1 D16 + K14
* M1 B13
RELAY 15
Y (HV) - - K15
AC OR DC OPTO 23
F23 M2 x AUX SUPPLY B14 K16
D15 + +
F26 B15 K17
- RELAY 16
OPTO 24 K18
METROSIL B16
+ J1
F25 B17
J2 RELAY 17
F28 COMMON
CONNECTION B18 J3
NOTES:
J4 RELAY 18
F27 J5
1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
H1 J6 RELAY 19
H2 RELAY 25 J7
(b) TERMINAL.
H3 J8 RELAY 20
(c) PIN TERMINAL (P.C.B. TYPE) H4 RELAY 26 J9
H5 J10 RELAY 21
2. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS. H6 RELAY 27
J11
3. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR. H7 J12 RELAY 22
(USED BY V/Hz W2 PROTECTION ONLY). H8 RELAY 28 J13
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001. H9 J14
RELAY 23
H10 RELAY 29 J15
H11 J16
H12 RELAY 30 J17
H13 RELAY 24
J18
H14
RELAY 31
H15
H16
CASE H17
EARTH RELAY 32
H18

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID008334. NOT USED TERMINALS ADDED. CONN DIAG:HIGH Z REF FOR 2 BIAS I/P TRANSFORMER DIFF
B SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 (80TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/05/2024 Name: S WOOTTON Sht: 2
10P64262
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1

C C C C C B
C B A PHASE ROTATION

MiCOM P643 (PART)


T2 T1
C24 D1 -
A (1) D2 OPTO 1 J11
+ WATCHDOG
C23 D3 CONTACT J12
-
OPTO 2 J13
C26 D4 WATCHDOG
+ J14
CONTACT
B (1) D5 - H1
D6 OPTO 3
C25 + RELAY 1 H2
D7 - H3
C28
D8 OPTO 4 RELAY 2 H4
C (1) +
H5
D9 -
NOTE 2 C27 RELAY 3 H6
D10 OPTO 5
T2 + H7
C18 D11 - RELAY 4 H8
P2 A (2) D12 OPTO 6 H9
+
S2 C17 RELAY 5 H10
D13 -
OPTO 7 H11
C20 D14
+ RELAY 6 H12
S1 B (2) D15 - H13
D16 OPTO 8
P1 C19 + H14
RELAY 7
D17 H15
C22 COMMON
D18 H16
CONNECTION
C (2) H17
F1 - RELAY 8
C21 H18
F2 OPTO 9
T3 +
E24 G1
F3 - RELAY 9 G2 NOTE 7
A (3) F4 OPTO 10 COMMS
+ G3
E23 F5 RELAY 10 G4
-
F6 OPTO 11 G5 J17
E26 + -
RELAY 11 G6 SEE DRAWING
B (3) F7 - EIA485/
G7 10Px4001 KBUS
TN2 F8 OPTO 12 J18
E25 + RELAY 12 G8 + PORT
F9 - G9 J16
E28
F10 OPTO 13 RELAY 13 SCN
+ G10
C (3)
TN1 F11 -
G11 * J1
E27 -
OPTO 14 RELAY 14 G12 AC OR DC
F12 J2 x AUX SUPPLY
+ +
G13
F13 - G14
F14 OPTO 15 RELAY 15
+ G15
F15 - G16
F16 OPTO 16 G17
+ RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
G DIFFERENTIAL (16 I/O & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64301 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
C12 TN3
S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) S2 P2 (USED BY V/Hz W2 PROTECTION ONLY).

C11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


C14 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1
S1 P1
Y (HV)
C15

Issue: Revision: Title:


EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER DIFFERENTIAL
J CID006234 Outlines updated to GE Format
(16 I/O & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 2 GE VERNOVA

Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64301 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2
A A
P2 P1 * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1 J11 MiCOM P643 (PART)
WATCHDOG
C C C C C B CONTACT J12
C B A PHASE ROTATION J13
WATCHDOG
CONTACT J14
H1
T2 T1 C24 D1 RELAY 1 H2
-
A (1) D2 OPTO 1 H3
+ RELAY 2 H4
C23 D3 - H5
D4 OPTO 2
C26 + RELAY 3 H6
B (1) D5 - H7
D6 OPTO 3 RELAY 4 H8
C25 +
D7 H9
C28 - RELAY 5
OPTO 4 H10
D8
C (1) + H11
D9 - RELAY 6 H12
C27 OPTO 5
D10 H13
+
T2 C18 D11 H14
- RELAY 7
P2 A (2) D12 OPTO 6 H15
+ H16
S2 C17 D13 - H17
D14 OPTO 7 RELAY 8
C20 + H18
S1 B (2) D15 - G1
D16 OPTO 8
P1 C19 + RELAY 9 G2 NOTE 7
D17 G3 COMMS
C22 COMMON
D18 RELAY 10 G4
CONNECTION
C (2) G5 J17
F1 -
- RELAY 11 G6
C21 SEE DRAWING EIA485/
F2 OPTO 9
+ G7 10Px4001 KBUS
T3 E24 F3 RELAY 12
J18
+ PORT
- G8
A (3) F4 OPTO 10 G9 J16
+ SCN
E23 F5 RELAY 13 G10
-
F6 OPTO 11 G11 * J1
E26 + -
RELAY 14 G12 AC OR DC
F7 J2 x AUX SUPPLY
B (3) - G13 +
F8 OPTO 12
GROUNDED WYE E25 + G14
RELAY 15
NEUTRAL TAILS F9 - G15
E28
F10 OPTO 13 G16
+
HV LV TV C (3) G17
F11 - RELAY 16
E27 G18
P2 S2 F12 OPTO 14
+
F13 -
NOTES: 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
F14 OPTO 15
+
P1 S1 TN3 C12 F15 (b) TERMINAL.
P2 S2 -
Y (TV) F16 OPTO 16
+ (c) PIN TERMINAL (P.C.B. TYPE)
C11 F17
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
COMMON
P1 S1 TN2 C14 F18 CONNECTION IS ALWAYS AN HV WINDING CONNECTION.
P2 S2 3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
Y (LV)
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C13 (USED BY V/Hz W2 PROTECTION ONLY).
RST 5. (x2) DENOTES WINDINGS ENERGISED VIA TWO CT SETS. THE RELAY SOFTWARE
P1 S1 TN1 C16
SUMMATES A VIRTUAL WINDING CURRENT FROM THE TWO BIAS INPUTS.
Y (HV) 6. TV INPUTS ARE NOT MANDATORY IF THE TERTIARY HAS NO LOAD.
C15 7. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
CASE 8. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
EARTH MiCOM P643 (PART)
METROSIL 9. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
10. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG:HIGH Z REF FOR 3 BIAS I/P TRANSFORMER DIFF
E SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2 &T3.
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 3
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64301 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1

C C C C C B
C B A PHASE ROTATION

MiCOM P643 (PART)


T2 T1 C24 D1 -
A (1) D2 OPTO 1 J11
+ WATCHDOG
C23 D3 CONTACT J12
- B1
OPTO 2 J13
C26 D4 WATCHDOG
+ J14 B2 RTD 1
CONTACT
B (1) D5 - B3
H1
D6 OPTO 3 B4
C25 + RELAY 1 H2
D7 H3 B5 RTD 2
C28 -
OPTO 4 RELAY 2 H4 B6
D8
C (1) + B7
H5
D9 -
NOTE 2 C27 RELAY 3 H6 B8 RTD 3
D10 OPTO 5
+ H7 B9
T2 C18 D11 - RELAY 4 H8
P2 A (2) D12 OPTO 6 H9
+
S2 C17 RELAY 5 H10 B28
D13 -
H11 B29 RTD 10
D14 OPTO 7
C20 + B30
RELAY 6 H12
S1 B (2) D15 - H13
D16 OPTO 8
P1 C19 + H14
RELAY 7
D17 H15
C22 COMMON
D18 H16
CONNECTION
C (2) H17
F1 - RELAY 8
C21 H18 NOTE 7
F2 OPTO 9 COMMS
+
T3 E24 G1
F3 - RELAY 9 G2
A (3) F4 OPTO 10
+ G3
E23 F5 RELAY 10 G4
-
F6 OPTO 11 G5 J17
E26 + -
RELAY 11 G6 SEE DRAWING
B (3) F7 - EIA485/
G7 10Px4001 KBUS
F8 OPTO 12 J18
E25 + RELAY 12 G8 + PORT
F9 - G9 J16
E28
F10 OPTO 13 RELAY 13 SCN
+ G10
C (3)
F11 -
G11 * J1
E27 -
OPTO 14 RELAY 14 G12 AC OR DC
F12 J2 x AUX SUPPLY
+ +
G13
F13 - G14
F14 OPTO 15 RELAY 15
+ G15
F15 - G16
F16 OPTO 16 G17
+ RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
G DIFFERENTIAL (16 I/O & 16 O/P + RTD) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64302 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

C12 TN3 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


S1 P1
(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
C14 TN2
S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1
S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (16 I/O & 16 O/P + RTD) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg C
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 2 UK Grid Solutions Ltd
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64302 Next
Sht:
-
St Leonards Building
Harry Kerr Drive, Stafford.
ST16 1WT, UK
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1 MiCOM P643 (PART)
B1
C C C C C B 20mA
PHASE ROTATION B2
C B A 1mA OUTPUT 1
B3
B5
T2 T1 C24 20mA
D1 - B6
J11 1mA OUTPUT 2
A (1) D2 OPTO 1 WATCHDOG
+ J12 B7
CONTACT
C23 D3 - J13 B9
WATCHDOG 20mA
D4 OPTO 2 J14
C26 + CONTACT B10
1mA OUTPUT 3
B (1) D5 H1
- B11
OPTO 3 RELAY 1 H2
C25 D6 B13
+ 20mA
H3
D7 - B14
C28 RELAY 2 H4 1mA OUTPUT 4
D8 OPTO 4
+ H5 B15
C (1) CLIO
D9 RELAY 3 H6 B16
NOTE 2 - 20mA
C27 OPTO 5 CURRENT LOOP
D10 H7
+ B17 INPUTS & OUTPUTS
T2 C18 RELAY 4 H8 1mA INPUT 1
D11 B18 NOTE 11
-
P2 A (2) OPTO 6 H9
D12 B20
+ RELAY 5 H10 20mA
S2 C17 D13 - H11 B21
OPTO 7 1mA INPUT 2
C20 D14 RELAY 6 H12 B22
+
S1 D15 H13
B (2) - B24
OPTO 8 H14 20mA
C19 D16 RELAY 7 B25
P1 + 1mA INPUT 3
H15
D17 B26
C22 COMMON H16
D18 CONNECTION H17 B28
C (2) RELAY 8 20mA
F1 - H18 B29
C21 1mA INPUT 4
F2 OPTO 9
+ G1 B30
T3 E24 RELAY 9
F3 - G2
A (3) F4 OPTO 10 G3
+
RELAY 10 G4 NOTE 7
E23 F5 - COMMS
G5
F6 OPTO 11
E26 + RELAY 11 G6
F7 J17
B (3) - G7 -
F8 OPTO 12 RELAY 12 G8 SEE DRAWING
E25 + EIA485/
G9 10Px4001 KBUS
F9 - J18
E28 RELAY 13 + PORT
OPTO 13 G10
F10
C (3) + G11 J16
F11 SCN
- RELAY 14 G12
E27 OPTO 14
F12
+ G13 * J1 -
F13 G14 AC OR DC
- RELAY 15 J2 x AUX SUPPLY
OPTO 15 G15 +
F14
+
G16
F15 -
OPTO 16 G17
F16 RELAY 16
+ G18
SEE SHEET 2 FOR NOTES F17
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
H DIFFERENTIAL (16 I/O & 16 O/P + CLIO) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64303 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
TN3 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C12 S1 P1
(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
TN2
C14 S1 P1 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
TN1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
C16 S1 P1
FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (16 I/O & 16 O/P + CLIO) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64303 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION

MiCOM P643 (PART)


T2 T1
C24 D1 -
A (1) D2 OPTO 1 J11
+ WATCHDOG
C23 D3 CONTACT J12
-
OPTO 2 J13
C26 D4 WATCHDOG
+ J14
CONTACT B3
B (1) D5 - -
H1
D6 OPTO 3 RELAY 17
C25 + RELAY 1 H2
B4
D7 H3 +
C28 -
OPTO 4 RELAY 2 H4 B7 -
D8
C (1) +
H5 RELAY 18
D9 - B8
NOTE 2 C27 RELAY 3 H6 +
D10 OPTO 5 HIGH BREAK
T2 + H7 B11 - CONTACTS
C18 D11 - RELAY 4 H8 RELAY 19
P2 A (2) D12 OPTO 6 H9 B12
+ +
S2 C17 RELAY 5 H10
D13 B15 -
-
OPTO 7 H11
C20 D14 RELAY 20
+ RELAY 6 H12 B16
D15 +
S1 B (2) - H13
D16 OPTO 8
P1 C19 + H14
RELAY 7
D17 H15
C22 COMMON
D18 H16
CONNECTION
C (2) H17
F1 - RELAY 8
C21 H18 NOTE 7
F2 OPTO 9 COMMS
+
T3 E24 G1
F3 - RELAY 9 G2
A (3) F4 OPTO 10
+ G3
E23 F5 RELAY 10 G4
-
F6 OPTO 11 G5 J17
E26 + -
RELAY 11 G6 SEE DRAWING
B (3) F7 - EIA485/
G7 10Px4001 KBUS
F8 OPTO 12 J18
E25 + RELAY 12 G8 + PORT
F9 - G9 J16
E28
F10 OPTO 13 RELAY 13 SCN
+ G10
C (3)
F11 -
G11 * J1
E27 -
OPTO 14 RELAY 14 G12 AC OR DC
F12 J2 x AUX SUPPLY
+ +
G13
F13 - G14
F14 OPTO 15 RELAY 15
+ G15
F15 - G16
F16 OPTO 16 G17
+ RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
G DIFFERENTIAL (16 I/P 20 O/P) WITH 4 POLE VT INPUT (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64306 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
C12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
C11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

C14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) S2 P2 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (16 I/P 20 O/P) WITH 4 POLE VT INPUT (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64306 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION
T2 T1 D24 E1 -
MiCOM P643 (PART)
A (1) E2 OPTO 1 M11 C1
+ WATCHDOG 20mA
D23 E3 CONTACT M12 C2
- 1mA OUTPUT 1
OPTO 2 M13
D26 E4 WATCHDOG C3
+ M14
CONTACT
B (1) E5 C5
- L1 20mA
E6 OPTO 3 C6
D25 + RELAY 1 L2 1mA OUTPUT 2
E7 L3 C7
D28 -
E8 OPTO 4 RELAY 2 L4 C9
C (1) + 20mA
L5
E9 C10
NOTE 2 - RELAY 3 L6 1mA OUTPUT 3
D27 OPTO 5
E10 C11
+ L7
T2 D18 E11 RELAY 4 L8 C13
- 20mA
P2 A (2) E12 OPTO 6 L9 C14
+ 1mA OUTPUT 4
S2 D17 RELAY 5 L10
E13 C15
- CLIO
OPTO 7 L11
D20 E14 C16
+ RELAY 6 L12 20mA CURRENT LOOP
S1 B (2) E15 C17 INPUTS & OUTPUTS
- L13 1mA INPUT 1
OPTO 8 (OPTIONAL)
D19 E16 L14 C18
P1 + RELAY 7
E17 L15 C20
D22 20mA
COMMON L16
E18 CONNECTION C21
C (2) 1mA INPUT 2
L17
G1 RELAY 8 C22
- L18
D21
G2 OPTO 9 C24
+ 20mA
T3 F24 K1
G3 C25
- RELAY 9 K2 1mA INPUT 3
A (3) G4 OPTO 10 C26
+ K3
F23 G5 RELAY 10 K4 C28
- 20mA
G6 OPTO 11 K5 C29
F26 + 1mA INPUT 4
RELAY 11 K6 C30
B (3) G7 -
OPTO 12 K7
F25 G8
+ RELAY 12 K8 B1
G9 - K9
F28 B2 RTD 1
G10 OPTO 13 RELAY 13 K10
C (3) + B3
G11 K11
- B4
F27 OPTO 14 RELAY 14 K12
G12 B5 RTD 2
+
K13
G13 B6
- K14
OPTO 15 RELAY 15 B7
G14 K15 OPTIONAL
+ B8 RTD 3
G15 - K16
B9
G16 OPTO 16 K17
+ RELAY 16
SEE SHEET 2 FOR NOTES G17 K18
COMMON
G18 CONNECTION B28
B29 RTD 10
J3 B30
-
RELAY 17
J4 NOTE 7
+
COMMS
- J7
RELAY 18
J8
HIGH BREAK +
CONTACTS - J11
M17
-
RELAY 19
J12 SEE DRAWING EIA485/
+
10Px4001 KBUS
J15 M18
- + PORT
RELAY 20 M16
J16 SCN
+
* M1 -
AC OR DC
M2 x AUX SUPPLY
+
CASE
EARTH
MiCOM P643 (PART)
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
Issue: Revision: Title:
CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 31/01/2023 Name: S WOOTTON Sht: 1
10P64330
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (16I/16O+4 HB) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 05/05/2023 Name: S WOOTTON Sht: 2
10P64330
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1 MiCOM P643 (PART)
C C C C C B J11
PHASE ROTATION WATCHDOG
C B A CONTACT J12
J13
WATCHDOG
CONTACT J14
T2 T1 C24 D1 -
A (1) D2 OPTO 1
+
C23 D3 -
D4 OPTO 2
C26 + H1 B1
B (1) D5 - RELAY 1 RELAY 15
H2 B2
D6 OPTO 3
C25 + H3 B3
D7 RELAY 2 H4 B4 RELAY 16
C28 -
D8 OPTO 4 H5 B5
C (1) + RELAY 3 RELAY 17
H6 B6
D9 -
NOTE 2 C27 OPTO 5 H7 B7
D10
+ H8 B8
T2 C18 RELAY 4 RELAY 18
D11 - H9 B9
P2 A (2) D12 OPTO 6 H10 B10
+
S2 C17 H11 B11
D13 - RELAY 5 RELAY 19
OPTO 7 H12 B12
C20 D14
+ H13 B13
S1 B (2) D15 -
RELAY 6 H14 B14 RELAY 20
D16 OPTO 8
P1 C19 + H15 B15
D17 H16 B16
C22 COMMON
D18 RELAY 7 H17 B17 RELAY 21
CONNECTION
C (2) H18 B18
F1 -
C21
F2 OPTO 9
+ G1
T3 E24 RELAY 8
F3 - G2
A (3) F4 OPTO 10 G3
+
RELAY 9 G4 NOTE 7
E23 F5 - COMMS
OPTO 11 G5
E26 F6
+ RELAY 10 G6
F7 J17
B (3) - G7 -
F8 OPTO 12 SEE DRAWING
E25 + RELAY 11 G8 EIA485/
10Px4001 KBUS
F9 G9 J18
E28 - + PORT
F10 OPTO 13 G10
C (3) + J16
RELAY 12 G11 SCN
F11 -
E27 G12
OPTO 14
F12
+ G13 * J1 -
F13 AC OR DC
- RELAY 13 G14 J2 x AUX SUPPLY
OPTO 15 +
F14 G15
+
F15 G16
-
OPTO 16 RELAY 14 G17
F16
+ G18
SEE SHEET 2 FOR NOTES F17
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (16 I/P & 21 O/P) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 26/1/2023 Name: S WOOTTON Sht: 1
10P64322
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
C12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
C11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

C14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CICD007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (16 I/P & 21 O/P) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 26/04/2023 Name: S WOOTTON Sht: 2
10P64322
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
P1 P2 P2 P1
A A
PROTECTED
T3 B TRANSFORMER B T1
C C
C B A
T2 D24

D23

D26

D25

D28

NOTE 2 D27

D18
P2
S2 D17

D20
S1

P1 D19

D22

D21

F24

F23

F26

F25

F28

F27

SEE SHEET 2 FOR NOTES

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 01/03/2023 Name: S WOOTTON Sht: 1
10P64335
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (16I/21O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/06/2023 Name: S WOOTTON Sht: 2
10P64335
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION

T1
MiCOM P643 (PART)
T2 C24 D1 -
A (1) D2 OPTO 1 J11
+ WATCHDOG
C23 D3 CONTACT J12
-
OPTO 2 J13 B1
C26 D4 WATCHDOG
+ J14 B2 RELAY 17
CONTACT
B (1) D5 - H1 B3
D6 OPTO 3 RELAY 18
C25 + RELAY 1 H2 B4
D7 - H3 B5
C28 RELAY 19
D8 OPTO 4 RELAY 2 H4 B6
C (1) +
H5 B7
D9 -
NOTE 2 C27 RELAY 3 H6 B8 RELAY 20
D10 OPTO 5
T2 + H7 B9
C18 D11 - RELAY 4 H8 B10 RELAY 21
P2 A (2) D12 OPTO 6 H9 B11
+
S2 C17 RELAY 5 H10 B12 RELAY 22
D13 -
OPTO 7 H11 B13
C20 D14
+ RELAY 6 H12 B14
D15 RELAY 23
S1 B (2) - H13 B15
D16 OPTO 8
P1 C19 + H14 B16
RELAY 7
D17 H15 B17
C22 RELAY 24
COMMON H16 B18
D18 CONNECTION
C (2) H17
F1 - RELAY 8
C21 H18
F2 OPTO 9
T3 +
E24 G1
F3 NOTE 7
- RELAY 9 G2
A (3) OPTO 10 COMMS
F4 G3
+
E23 F5 RELAY 10 G4
-
F6 OPTO 11 G5 J17
E26 + -
RELAY 11 G6 SEE DRAWING
B (3) F7 - EIA485/
G7 10Px4001 KBUS
F8 OPTO 12 J18
E25 + RELAY 12 G8 + PORT
F9 - G9 J16
E28
F10 OPTO 13 RELAY 13 SCN
+ G10
C (3)
F11 -
G11 * J1
E27 -
OPTO 14 RELAY 14 G12 AC OR DC
F12 J2 x AUX SUPPLY
+ +
G13
F13 - G14
F14 OPTO 15 RELAY 15
+ G15
F15 - G16
F16 OPTO 16 G17
+ RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
G DIFFERENTIAL (16 I/O & 24 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64305 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.

GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.

TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)


NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
IS ALWAYS AN HV WINDING CONNECTION.
S2 P2
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C12 TN3 S1 P1 (USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
C14 TN2 S1 P1 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
Y (LV) S2 P2
C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.

C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
J Drg
DIFFERENTIAL (16 I/O & 24 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64305 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
FINISH :- A
S1 S2
A
PROTECTED
A NEXT
S2
STAGE
S1
:- A

T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION
T2 T1 D24 E1 -
MiCOM P643 (PART)
A (1) E2 OPTO 1 M11
+ WATCHDOG
D23 E3 CONTACT M12 B1
-
OPTO 2 M13 B2 RTD 1
D26 E4 WATCHDOG
+ M14
CONTACT B3
B (1) E5 - L1 B4
E6 OPTO 3
D25 + RELAY 1 L2 B5 RTD 2
E7 - L3 B6
D28
E8 OPTO 4 RELAY 2 L4 B7
C (1) + OPTIONAL
L5 B8 RTD 3
E9 -
NOTE 2 D27 RELAY 3 L6 B9
E10 OPTO 5
+ L7
T2 D18 E11 - RELAY 4 L8
P2 A (2) E12 OPTO 6 L9
+ B28
S2 D17 RELAY 5 L10
E13 - B29 RTD 10
OPTO 7 L11 B30
D20 E14
+ RELAY 6 L12
S1 B (2) E15 C1
- L13 20mA
E16 OPTO 8 C2
P1 D19 + L14 1mA OUTPUT 1
RELAY 7
E17 L15 C3
D22 COMMON
E18 L16 C5
CONNECTION 20mA
C (2) L17
G1 RELAY 8 C6
- L18 1mA OUTPUT 2
D21
G2 OPTO 9 C7
+
T3 F24 K1
G3 C9
- RELAY 9 K2 20mA
A (3) G4 OPTO 10 C10
+ K3 1mA OUTPUT 3
F23 G5 RELAY 10 K4 C11
-
G6 OPTO 11 K5 C13
F26 + 20mA
RELAY 11 K6
B (3) G7 C14
- 1mA OUTPUT 4
OPTO 12 K7
F25 G8 C15
+ RELAY 12 K8 CLIO
G9 C16
F28 - K9 20mA CURRENT LOOP
G10 OPTO 13 RELAY 13 K10 C17 INPUTS & OUTPUTS
C (3) + 1mA INPUT 1
(OPTIONAL)
G11 K11 C18
-
F27 OPTO 14 RELAY 14 K12
G12 C20
+ 20mA
K13
G13 C21
- K14 1mA INPUT 2
G14 OPTO 15 RELAY 15 C22
+ K15
G15 K16 C24
- 20mA
G16 OPTO 16 K17 C25
+ RELAY 16 1mA INPUT 3
SEE SHEET 2 FOR NOTES G17 K18 C26
COMMON
G18 CONNECTION J1 C28
20mA
RELAY 17 J2 C29
1mA INPUT 4
J3
C30
RELAY 18 J4
J5
RELAY 19 J6
J7 NOTE 7
J8 COMMS
RELAY 20
J9
RELAY 21 J10
J11
RELAY 22 J12 M17
-
J13
SEE DRAWING EIA485/
J14 10Px4001
RELAY 23 KBUS
J15 M18
+ PORT
J16 M16
J17 SCN
RELAY 24
J18
* M1 -
AC OR DC
M2 x AUX SUPPLY
+
CASE
EARTH
MiCOM P643 (PART)
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
Issue: Revision: Title:
CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/03/2023 Name: S WOOTTON Sht: 1
10P64339
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (16I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 05/06/2023 Name: S WOOTTON Sht: 2
10P64339
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
FINISH :- P1 P2
NEXT STAGE
P2
:- P1
A
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION

MiCOM P643 (PART)


T2 T1
C24 D1 -
A (1) D2 OPTO 1 J11
+ WATCHDOG
C23 D3 CONTACT J12
-
OPTO 2 J13
C26 D4 WATCHDOG
+ J14
CONTACT
B (1) D5 - H1
D6 OPTO 3
C25 + RELAY 1 H2
D7 - H3
C28
D8 OPTO 4 RELAY 2 H4
C (1) +
H5
D9 -
NOTE 2 C27 RELAY 3 H6
D10 OPTO 5
T2 + H7
C18 D11 - RELAY 4 H8
P2 A (2) D12 OPTO 6 H9
+
S2 C17 RELAY 5 H10
D13 -
OPTO 7 H11
C20 D14
+ RELAY 6 H12
S1 B (2) D15 - H13
D16 OPTO 8
P1 C19 + H14
RELAY 7
D17 H15
C22 COMMON
D18 H16
CONNECTION
C (2) H17
F1 - RELAY 8
C21 H18 NOTE 7
F2 OPTO 9 COMMS
+
T3 E24 G1
F3 - RELAY 9 G2
A (3) F4 OPTO 10
+ G3
E23 F5 RELAY 10 G4
-
F6 OPTO 11 G5 J17
E26 + -
RELAY 11 G6 SEE DRAWING
B (3) F7 - EIA485/
G7 10Px4001 KBUS
F8 OPTO 12 J18
E25 + RELAY 12 G8 + PORT
F9 - G9 J16
E28
F10 OPTO 13 RELAY 13 SCN
+ G10
C (3)
F11 -
G11 * J1
E27 RELAY 14 -
OPTO 14 G12 AC OR DC
F12 J2 x AUX SUPPLY
+ +
G13
F13 - G14
F14 OPTO 15 RELAY 15
+ G15
F15 - G16
F16 OPTO 16 G17
+ RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON B9
F18 CONNECTION
RELAY 17 B10
B1 - B11
B2 OPTO 17 RELAY 18
+ B12
B3 - B13
B4 OPTO 18 B14
+ RELAY 19
B5 B15
-
OPTO 19 B16
B6
+ B17
B7 RELAY 20
- B18
B8 OPTO 12
+
CASE
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (20I/20O) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 03/03/2023 Name: S WOOTTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
Sht: 1
10P64345
No:
C
UK Grid Solutions Ltd
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall St Leonards Building,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next Harry Kerr Drive,
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
C12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
C11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

C14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (20I/20O) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 18/04/2023 Name: S WOOTTON Sht: 2
10P64345
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
FINISHA :- A
PROTECTED
A NEXT STAGE :- A
S1 S2 S2 S1
T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION
T2 T1 D24 E1 -
MiCOM P643 (PART)
B1
A (1) E2 OPTO 1 M11
+ WATCHDOG B2 RTD 1
D23 E3 CONTACT M12
- B3
OPTO 2 M13
D26 E4 WATCHDOG B4
+ M14
CONTACT B5 RTD 2
B (1) E5 - L1
OPTO 3 B6
D25 E6 RELAY 1 L2
+ B7
E7 - L3
D28 B8 RTD 3
OPTO 4 RELAY 2 L4 OPTIONAL
E8 B9
C (1) +
L5
E9 -
NOTE 2 D27 RELAY 3 L6
E10 OPTO 5
+ L7
T2 D18 B28
E11 - RELAY 4 L8
P2 OPTO 6 B29 RTD 10
A (2) E12 L9
+ B30
S2 D17 RELAY 5 L10
E13 -
OPTO 7 L11
D20 E14 C1
+ RELAY 6 L12 20mA
S1 B (2) E15 - C2
L13 1mA OUTPUT 1
E16 OPTO 8 C3
P1 D19 + L14
RELAY 7
E17 L15 C5
D22 COMMON 20mA
E18 L16 C6
CONNECTION 1mA OUTPUT 2
C (2) L17
G1 - RELAY 8 C7
D21 L18
G2 OPTO 9 C9
+ 20mA
T3 F24 K1
G3 - C10
RELAY 9 K2 1mA OUTPUT 3
A (3) G4 OPTO 10 C11
+ K3
F23 G5 RELAY 10 K4 C13
- 20mA
G6 OPTO 11 K5 C14
F26 + 1mA OUTPUT 4
RELAY 11 K6
B (3) G7 - C15
OPTO 12 K7 CLIO
F25 G8 C16
+ RELAY 12 K8 20mA CURRENT LOOP
G9 - K9 C17 INPUTS & OUTPUTS
F28 1mA INPUT 1
OPTO 13 (OPTIONAL)
G10 RELAY 13 K10 C18
C (3) +
G11 K11 C20
- 20mA
F27 OPTO 14 RELAY 14 K12
G12 C21
+ 1mA INPUT 2
K13
G13 - C22
K14
G14 OPTO 15 RELAY 15 C24
+ K15 20mA
G15 - K16 C25
1mA INPUT 3
G16 OPTO 16 K17 C26
+ RELAY 16
G17 K18 C28
COMMON 20mA
J9
G18 CONNECTION C29
RELAY 17 J10 1mA INPUT 4
J1 - C30
J11
SEE SHEET 2 FOR NOTES OPTO 17
J2 RELAY 18 J12
+
J3 J13
-
J4 OPTO 18 J14
+ RELAY 19 NOTE 7
J15 COMMS
J5 - J16
J6 OPTO 19
+ J17 M17
RELAY 20 -
J7 - J18
OPTO 20 SEE DRAWING EIA485/
J8 10Px4001
+ KBUS
M18
+ PORT
M16
SCN

* M1 -
AC OR DC
M2 x AUX SUPPLY
+

CASE
EARTH
MiCOM P643 (PART)
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
Issue: Revision: Title:
CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 27/06/2023 Name: S WOOTTON Sht: 1
10P64342
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFF WITH 4 POLE VT INPUTS (20I/20O)) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 27/06/2023 Name: S WOOTTON Sht: 2
10P64342
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1

C C C C C B
C B A PHASE ROTATION

T1
MiCOM P643 (PART)
T2 C24 D1 -
A (1) D2 OPTO 1 J11 B1
+ WATCHDOG -
C23 D3 CONTACT J12 B2 OPTO 17
- +
OPTO 2 J13
C26 D4 WATCHDOG B3
+ J14 -
CONTACT OPTO 18
B (1) D5 - B4
H1 +
D6 OPTO 3 B5
C25 + RELAY 1 H2 -
D7 H3 B6 OPTO 19
C28 - +
D8 OPTO 4 RELAY 2 H4 B7
C (1) + -
H5 OPTO 20
D9 - B8
NOTE 2 C27 RELAY 3 H6 +
D10 OPTO 5 B9
T2 + H7 -
C18 D11 B10 OPTO 21
- RELAY 4 H8 +
P2 A (2) D12 OPTO 6 H9 B11
+ -
S2 C17 RELAY 5 H10 OPTO 22
D13 - B12
+
OPTO 7 H11
C20 D14 B13
+ RELAY 6 H12 -
D15 B14 OPTO 23
S1 B (2) - H13 +
D16 OPTO 8 B15
P1 C19 + H14 -
RELAY 7
D17 H15 B16 OPTO 24
C22 +
COMMON H16
D18 CONNECTION B17
C (2) H17 COMMON
F1 - RELAY 8 B18 CONNECTION
C21 H18
F2 OPTO 9
+
T3 E24 G1
F3 - RELAY 9 G2
A (3) F4 OPTO 10 NOTE 7
+ G3 COMMS
E23 F5 RELAY 10 G4
-
F6 OPTO 11 G5 J17
E26 + -
RELAY 11 G6
B (3) F7 - SEE DRAWING
G7 EIA485/
F8 OPTO 12 10Px4001 KBUS
E25 + RELAY 12 G8 J18
+ PORT
F9 - G9
E28 J16
F10 OPTO 13 RELAY 13 G10 SCN
C (3) +
F11 G11
E27
-
RELAY 14
* J1
F12 OPTO 14 G12 -
+ AC OR DC
G13 J2 x AUX SUPPLY
F13 +
- G14
F14 OPTO 15 RELAY 15
+ G15
F15 - G16
F16 OPTO 16 G17
+ RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
H DIFFERENTIAL (24 I/O & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64304 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.

TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)


NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

C12 TN3 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


S1 P1
(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
C14 TN2
S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 3 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (24 I/O & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64304 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION
T2 T1 D24 E1 -
MiCOM P643 (PART)
A (1) E2 OPTO 1 M11
+ WATCHDOG
D23 M12 B1
E3 - CONTACT
M13 B2 RTD 1
E4 OPTO 2
D26 + WATCHDOG B3
CONTACT M14
B (1) E5 - B4
L1
E6 OPTO 3 B5 RTD 2
D25 + RELAY 1 L2
E7 L3 B6
D28 -
OPTO 4 RELAY 2 L4 B7
E8
C (1) + B8 RTD 3 OPTIONAL
L5
E9 -
NOTE 2 D27 RELAY 3 L6 B9
E10 OPTO 5
+ L7
T2 D18 E11 - RELAY 4 L8
P2 A (2) E12 OPTO 6 L9 B28
+
S2 D17 RELAY 5 L10 B29 RTD 10
E13 -
OPTO 7 L11 B30
D20 E14
+ RELAY 6 L12
S1 B (2) E15 - L13
E16 OPTO 8
P1 D19 + L14 C1
RELAY 7 20mA
E17 L15 C2
D22 COMMON 1mA OUTPUT 1
E18 L16
CONNECTION C3
C (2) L17
G1 - RELAY 8 C5
D21 L18 20mA
G2 OPTO 9
+ C6
T3 F24 K1 1mA OUTPUT 2
G3 - C7
RELAY 9 K2
A (3) G4 OPTO 10
+ K3 C9
20mA
F23 G5 RELAY 10 K4
- C10
OPTO 11 1mA OUTPUT 3
F26 G6 K5
+ C11
RELAY 11 K6
B (3) G7 - C13
OPTO 12 K7 20mA
F25 G8 C14
+ RELAY 12 K8 1mA OUTPUT 4
G9 - K9 C15
F28
G10 OPTO 13 RELAY 13 K10
CLIO
+ C16
C (3) 20mA CURRENT LOOP
G11 K11 INPUTS & OUTPUTS
- C17
F27 OPTO 14 RELAY 14 K12 1mA INPUT 1 (OPTIONAL)
G12 C18
+
K13
G13 - C20
K14 20mA
G14 OPTO 15 RELAY 15
+ K15 C21
1mA INPUT 2
G15 - K16 C22
G16 OPTO 16 K17
+ RELAY 16 C24
K18 20mA
SEE SHEET 2 FOR NOTES G17 C25
COMMON 1mA INPUT 3
G18 CONNECTION C26
H1 - C28
20mA
H2 OPTO 17
+ C29
1mA INPUT 4
H3 - C30
H4 OPTO 18
+
H5 -
H6 OPTO 19
+ NOTE 7
H7 - COMMS
H8 OPTO 20
+
H9 -
H10 OPTO 21
+
M17
H11 -
-
H12 OPTO 22 SEE DRAWING EIA485/
+ 10Px4001 KBUS
H13 M18
- + PORT
H14 OPTO 23 M16
+
SCN
H15 -
H16 OPTO 24 * M1
+ -
AC OR DC
H17 M2 x AUX SUPPLY
COMMON +
H18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
Issue: Revision: Title:
CID007575. INTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/07/2023 Name: S WOOTTON Sht: 1
10P64362
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (24I/16O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 06/07/2023 Name: S WOOTTON Sht: 2
10P64362
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd: S SWAIN
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1
C C C C C B
C B A PHASE ROTATION
T2 T1 D24 E1 -
MiCOM P643 (PART)
A (1) E2 OPTO 1 M11
+ WATCHDOG
D23 E3 CONTACT M12 B1
-
OPTO 2 M13 B2 RTD 1
D26 E4 WATCHDOG
+ M14
CONTACT B3
B (1) E5 - L1 B4
E6 OPTO 3
D25 + RELAY 1 L2 B5 RTD 2
E7 L3 B6
D28 -
E8 OPTO 4 RELAY 2 L4 B7
C (1) + OPTIONAL
L5 B8 RTD 3
E9 -
NOTE 2 D27 RELAY 3 L6 B9
E10 OPTO 5
+ L7
T2 D18 E11 - RELAY 4 L8
P2 A (2) E12 OPTO 6 L9
+ B28
S2 D17 RELAY 5 L10
E13 - B29 RTD 10
OPTO 7 L11 B30
D20 E14
+ RELAY 6 L12
S1 B (2) E15 B1
- L13 20mA
E16 OPTO 8 B2
P1 D19 + L14 1mA OUTPUT 1
RELAY 7
E17 L15 B3
D22 COMMON
E18 L16 B5
CONNECTION 20mA
C (2) L17
G1 RELAY 8 B6
- L18 1mA OUTPUT 2
D21
G2 OPTO 9 B7
+
T3 F24 K1
G3 B9
- RELAY 9 K2 20mA
A (3) G4 OPTO 10 B10
+ K3 1mA OUTPUT 3
F23 G5 RELAY 10 K4 B11
-
G6 OPTO 11 K5 B13
F26 + 20mA
RELAY 11 K6
B (3) G7 B14
- 1mA OUTPUT 4
OPTO 12 K7
F25 G8 B15
+ RELAY 12 K8 CLIO
G9 B16
F28 - K9 20mA CURRENT LOOP
G10 OPTO 13 RELAY 13 K10 B17 INPUTS & OUTPUTS
C (3) + 1mA INPUT 1
(OPTIONAL)
G11 K11 B18
-
F27 OPTO 14 RELAY 14 K12
G12 B20
+ 20mA
K13
G13 B21
- K14 1mA INPUT 2
G14 OPTO 15 RELAY 15 B22
+ K15
G15 K16 B24
- 20mA
G16 OPTO 16 K17 B25
+ RELAY 16 1mA INPUT 3
SEE SHEET 2 FOR NOTES G17 K18 B26
COMMON
G18 CONNECTION B28
J3 20mA
-
H1 B29
- RELAY 17 1mA INPUT 4
H2 OPTO 17 J4 B30
+ +
H3 - J7
-
H4 OPTO 18
+ RELAY 18
J8
H5 HIGH BREAK +
-
H6 OPTO 19 CONTACTS - J11
+
H7 RELAY 19
- J12
OPTO 20 +
H8
+ J15
H9 -
-
OPTO 21 RELAY 20
H10 J16
+ +
H11 - NOTE 7
OPTO 22 COMMS
H12
+
H13 - C3
-
H14 OPTO 23 RELAY 21
+
C4
H15 +
- M17
OPTO 24 C7 -
H16 -
+ SEE DRAWING
RELAY 22 EIA485/
H17 C8 10Px4001 KBUS
COMMON HIGH BREAK + M18
H18 + PORT
CONNECTION CONTACTS C11
- M16
RELAY 23 SCN
C12
+
* M1
C15 -
- AC OR DC
M2 x AUX SUPPLY
RELAY 24 +
C16
CASE +
EARTH
MiCOM P643 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


Issue: Revision: Title:
CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (24I/16O + 8 HB RELAYS) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 24/07/2023 Name: S WOOTTON Sht: 1 UK Grid Solutions Ltd

10P64363
C
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No: St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (24I/16O + 8 HB RELAYS) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 24/07/2023 Name: S WOOTTON Sht: 2 UK Grid Solutions Ltd

10P64363
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
C
No: St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
FINISH :- NEXT STAGE :-
P1 P2 P2 P1
A A
PROTECTED
T3 B TRANSFORMER B T1
C C
C B A
T2 D24

D23

D26

D25

D28

NOTE 2 D27

D18
P2
S2 D17

D20
S1

P1 D19

D22

D21

F24

F23

F26

F25

F28

F27

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24 I/P & 24 O/P) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 15/03/2023 Name: S WOOTTON Sht: 1
10P64352
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24 I/P & 24 O/P) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 20/04/2023 Name: S WOOTTON Sht: 2
10P64352
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
P1 P2 P2 P1
A A
FINISH :- B
NEXT STAGE
PROTECTED
B
:-
T3 TRANSFORMER T1
C C
C B A
T2 D24

D23

D26

D25

D28

NOTE 2 D27

D18
P2
S2 D17

D20
S1

P1 D19

D22

D21

F24

F23

F26

F25

F28

F27

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24 I/P & 32 O/P) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 15/08/2023 Name: S WOOTTON Sht: 1
10P64353
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24 I/P & 32 O/P) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 21/04/2023 Name: S WOOTTON Sht: 2
10P64353
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
P1 P2 P2 P1
A A
FINISH :- T3 B
NEXT STAGE
PROTECTED
B
TRANSFORMER
:- T1
C C
C B A
T2 D24

D23

D26

D25

D28

NOTE 2 D27

D18
P2
S2 D17

D20
S1

P1 D19

D22

D21

F24

F23

F26

F25

F28

F27

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 14/08/2023 Name: S WOOTTON Sht: 1
10P64374
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
FINISH :- NEXT STAGE :-

A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 14/08/2023 Name: S WOOTTON Sht: 2
10P64374
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
P1 P2 P2 P1
A
FINISH :- NEXT
B
STAGEAB :-
PROTECTED
T3 TRANSFORMER T1
C C
C B A
T2 D24

D23

D26

D25

D28

NOTE 2 D27

D18
P2
S2 D17

D20
S1

P1 D19

D22

D21

F24

F23

F26

F25

F28

F27

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/32O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 14/08/2023 Name: S WOOTTON Sht: 1
10P64377
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
FINISH :- NEXT STAGE :-
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/32O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 14/08/2023 Name: S WOOTTON Sht: 2
10P64377
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
P1 P2 P2 P1
A A
FINISH :- B
PROTECTED NEXT
B
STAGE :-
T3 TRANSFORMER T1
C C
C B A
T2 D24

D23

D26

D25

D28

NOTE 2 D27

D18
P2
S2 D17

D20
S1

P1 D19

D22

D21

F24

F23

F26

F25

F28

F27

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (40I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 16/03/2023 Name: S WOOTTON Sht: 1
10P64355
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (40I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 24/04/2023 Name: S WOOTTON Sht: 2
10P64355
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
P1 P2 P2 P1
A
FINISH :- NEXT
B
STAGEAB :-
PROTECTED
T3 TRANSFORMER T1
C C
C B A
T2 D24

D23

D26

D25

D28

NOTE 2 D27

D18
P2
S2 D17

D20
S1

P1 D19

D22

D21

F24

F23

F26

F25

F28

F27

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (48I/16O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 16/03/2023 Name: S WOOTTON Sht: 1
10P64356
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P643 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) (USED BY V/Hz W2 PROTECTION ONLY).
S2 P2
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

D14 TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
Y (HV)
D15

Issue: Revision: Title:


CID007575. INTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 3 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (48I/16O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 24/04/2023 Name: S WOOTTON Sht: 2
10P64356
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T4 T3 T2 T1
C24
A (1)
C23

C26
B (1)
D1 MiCOM P645 (PART)
C25 -
D2 OPTO 1
C28 +
D3 J11
- WATCHDOG
C (1) OPTO 2 J12
D4 CONTACT
+ J13
NOTE 2 C27
D5 - WATCHDOG
T2 CONTACT J14
C18 D6 OPTO 3
+ H1
P2 A (2) D7 RELAY 1 H2
-
S2 C17 D8 OPTO 4 H3
+
RELAY 2 H4
C20 D9 -
OPTO 5 H5
S1 D10
B (2) + RELAY 3 H6
D11 - H7
P1 C19
D12 OPTO 6 RELAY 4 H8
C22 +
D13 H9
-
C (2) OPTO 7 RELAY 5 H10
D14
+ H11
C21
D15 - RELAY 6 H12
T3 E24 OPTO 8
D16 H13
+
P2 A (3) D17 H14
COMMON RELAY 7
S2 E23 D18 H15
CONNECTION
H16
E26 F1 - H17
F2 OPTO 9 RELAY 8
S1 B (3) + H18
F3 -
P1 E25 G1
F4 OPTO 10
+ RELAY 9 G2
E28
F5 - G3
C (3) OPTO 11
F6 RELAY 10 G4
+
E27 G5 NOTE 7
F7 -
T4 RELAY 11 COMMS
E18 OPTO 12 G6
F8
+ G7
P2 A (4) F9 - RELAY 12 G8
S2 E17 F10 OPTO 13
+ G9
F11 RELAY 13 G10
E20 - J17
-
F12 OPTO 14 G11
S1 B (4) + SEE DRAWING
RELAY 14 G12 EIA485/
F13 - 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 + PORT
E22 + G14
RELAY 15 J16
F15 - G15 SCN
C (4) OPTO 16
F16 G16
+ *
E21 G17 J1 -
F17 RELAY 16 AC OR DC
T5 E12
COMMON G18 J2 x AUX SUPPLY
F18 CONNECTION +
A (5)
E11

E14
B (5)
E13

E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH

SEE SHEET 2 FOR NOTES MiCOM P645 (PART)

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
F DIFFERENTIAL (16 I/P & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64501 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c
C2 C2 VA
a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1.
(a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.

GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.

TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)


NOTE 3 2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
IS ALWAYS AN HV WINDING CONNECTION.
S2 P2
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C12 TN3 S1 P1 (USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
C14 TN2 S1 P1 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).

C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.

C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
K DIFFERENTIAL (16 I/P & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64501 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1
J11 MiCOM P645 (PART)
C C C C B WATCHDOG
CONTACT J12
C B A C B A C B A PHASE ROTATION
J13
WATCHDOG
CONTACT J14
T4 T3 T2 T1 C24 D1
H1
- RELAY 1 H2
A (1) D2 OPTO 1
+ H3
C23 D3 RELAY 2 H4
-
C26 D4 OPTO 2 H5
+ RELAY 3 H6
B (1) D5 - H7
D6 OPTO 3
C25 + RELAY 4 H8
D7 - H9
C28
D8 OPTO 4 RELAY 5 H10
C (1) +
D9 H11
C27 -
RELAY 6 H12
1 2 D10
+
OPTO 5

TO R ST T2 C18
H13
D11 - H14
P2 A (2) OPTO 6 RELAY 7
D12 H15
+
S2 C17 D13 H16
-
C20 D14 OPTO 7 H17 NOTE 5
+ RELAY 8
H18 COMMS
S1 B (2) D15 -
D16 OPTO 8 G1
P1 C19 + RELAY 9 G2
D17
C22 COMMON G3
D18 CONNECTION RELAY 10
C (2) G4 J17
F1 -
- G5
C21 SEE DRAWING
F2 OPTO 9 RELAY 11 G6 EIA485/
+ 10Px4001. KBUS
T3 E24 F3 G7 J18
+
- PORT
P2 OPTO 10 RELAY 12 G8
A (3) F4 J16
+ G9 SCN
S2
E23 F5 - RELAY 13 G10
F6 OPTO 11
G11
* J1
E26 + -
AC OR DC
S1 F7 RELAY 14 G12 J2 x AUX SUPPLY
B (3) - +
F8 OPTO 12 G13
P1 E25 +
G14
F9 RELAY 15
- G15
E28 OPTO 13
F10 G16
+
C (3) F11 - G17
RELAY 16
E27 F12 OPTO 14 G18
+
T4 E18 F13 -
P2 OPTO 15
A (4) F14
+ * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
S2
E17 F15 - NOTES:
F16 OPTO 16
E20 + GROUNDED WYE
F17
S1 COMMON NEUTRAL TAILS 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
B (4)
F18 CONNECTION
P1 E19 TV LV HV
(b) TERMINAL.
E22 NOTE 3
(c) PIN TERMINAL (P.C.B. TYPE)
C (4) S2 P2
E21 2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
IS ALWAYS AN HV WINDING CONNECTION.
T5 E12 TN3
C12 S1 P1 3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
A (5)
Y (TV) S2 P2 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
E11 (USED BY V/Hz W2 PROTECTION ONLY).
C11
E14 TN2 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C14 S1 P1
B (5) 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
Y (LV) S2 P2
E13 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
C13 1 2
E16 RST (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C16 TN1 S1 P1
C (5) 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
Y (HV)
E15
C15

MiCOM P645 (PART) CASE METROSIL


EARTH

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG:HIGH Z REF FOR 5 BIAS I/P TRANSFORMER DIFF.
H SAME PRINCIPAL APPLIES TO WIRE HIGH Z REF FOR T2,T3,T4,T5
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 3
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64501 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T4 T3 T2 T1 C24
A (1)
C23

C26
B (1)
D1 MiCOM P645 (PART)
C25 -
D2 OPTO 1
C28 +
D3 J11
- WATCHDOG
C (1) OPTO 2 J12
D4 CONTACT
+ J13
NOTE 2 C27
D5 - WATCHDOG
CONTACT J14 B1
T2 C18 OPTO 3
D6 H1 B2 RTD 1
+
P2 A (2) D7 RELAY 1 H2 B3
-
S2 C17 D8 OPTO 4 H3 B4
+
RELAY 2 H4 B5 RTD 2
C20 D9 -
OPTO 5 H5 B6
S1 D10
B (2) + RELAY 3 H6 B7
D11 - H7 B8 RTD 3
P1 C19
D12 OPTO 6 RELAY 4 H8 B9
C22 +
D13 H9
-
C (2) OPTO 7 RELAY 5 H10
D14
+ H11
C21 B28
D15 - RELAY 6 H12 B29 RTD 10
T3 E24 D16 OPTO 8
+ H13 B30
P2 A (3) D17 H14
COMMON RELAY 7
S2 E23 D18 H15
CONNECTION
H16
E26 F1 - H17
F2 OPTO 9 RELAY 8
S1 B (3) + H18
F3 -
P1 E25 G1
F4 OPTO 10
+ RELAY 9 G2
E28
F5 - G3
C (3) OPTO 11
F6 RELAY 10 G4
+
E27 G5 NOTE 7
F7 -
RELAY 11 COMMS
T4 E18 OPTO 12 G6
F8
+ G7
P2 A (4) F9 - RELAY 12 G8
S2 E17 F10 OPTO 13
+ G9
F11 RELAY 13 G10
E20 - J17
-
F12 OPTO 14 G11
S1 B (4) + SEE DRAWING
RELAY 14 G12 EIA485/
F13 - 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 + PORT
E22 + G14
RELAY 15 J16
F15 - G15 SCN
C (4) OPTO 16
F16 G16
+ *
E21 G17 J1 -
F17 RELAY 16 AC OR DC
T5 E12
COMMON G18 J2 x AUX SUPPLY
F18 CONNECTION +
A (5)
E11

E14
B (5)
E13 CASE
EARTH
E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH

SEE SHEET 2 FOR NOTES MiCOM P645 (PART)

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
F DIFFERENTIAL (16 I/P & 16 O/P + RTD) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1 GE VERNOVA

Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64502 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

C12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
C14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (16 I/P & 16 O/P + RTD) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64502 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T4 T3 T2 T1
C24
A (1)
C23

C26
B (1)
MiCOM P645 (PART)
D1 -
C25 B1
D2 OPTO 1 20mA
C28
+ B2
D3 J11 1mA OUTPUT 1
- WATCHDOG B3
C (1) OPTO 2 CONTACT J12
D4
+ J13 B5
NOTE 2 C27 WATCHDOG 20mA
D5 - J14
T2 CONTACT B6
C18 D6 OPTO 3 1mA OUTPUT 2
+ H1
B7
P2 A (2) D7 RELAY 1 H2
- B9
S2 D8 OPTO 4 H3 20mA
C17 + RELAY 2 H4 B10
D9 1mA OUTPUT 3
C20 - H5 B11
D10 OPTO 5
S1 B (2) + RELAY 3 H6 B13
D11 20mA
- H7
P1 C19 B14
D12 OPTO 6 RELAY 4 H8 1mA OUTPUT 4
C22
+ B15
D13 H9 CLIO
- RELAY 5 B16
C (2) OPTO 7 H10 20mA CURRENT LOOP
D14
+ H11 B17 INPUTS & OUTPUTS
C21 1mA INPUT 1
D15 - RELAY 6 H12 NOTE 11
B18
T3 E24 OPTO 8
D16 H13
+ B20
P2 A (3) D17 H14 20mA
RELAY 7 B21
S2 COMMON H15 1mA INPUT 2
E23 D18 CONNECTION
H16 B22
E26 F1 - H17 B24
F2 OPTO 9 RELAY 8 20mA
S1 B (3) + H18 B25
F3 1mA INPUT 3
P1 E25 - G1 B26
F4 OPTO 10
+ RELAY 9 G2
E28 B28
F5 20mA
- G3
C (3) B29
F6 OPTO 11 RELAY 10 G4 1mA INPUT 4
+ B30
E27 G5
F7 - RELAY 11 G6
T4 E18 F8 OPTO 12
+ G7
P2 A (4) F9 NOTE 7
- RELAY 12 G8 COMMS
S2 E17 F10 OPTO 13 G9
+
F11 RELAY 13 G10
E20 - J17
-
OPTO 14 G11
S1 F12 SEE DRAWING
B (4) + RELAY 14 G12 EIA485/
F13 10Px4001. KBUS
P1 E19 - G13 J18
OPTO 15 + PORT
F14 G14
E22
+ RELAY 15 J16
F15 - G15 SCN
C (4) OPTO 16 G16
F16
E21
+
G17
* J1
F17 -
RELAY 16 AC OR DC
COMMON G18 J2 x AUX SUPPLY
T5 E12 F18 +
CONNECTION
A (5)
E11

E14
B (5)
E13

E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH

SEE SHEET 2 FOR NOTES MiCOM P645 (PART)

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
F GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION
DIFFERENTIAL (16 I/P & 16 O/P + CLIO) WITH 4 POLE VT INPUTS (60TE)
Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64503 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c
C2 C2 VA
a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.

GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.

TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)


NOTE 3 2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
IS ALWAYS AN HV WINDING CONNECTION.
S2 P2
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C12 TN3 S1 P1 (USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
C14 TN2 S1 P1 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
S2 P2
C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
C16 TN1 S1 P1 FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (16 I/P & 16 O/P + CLIO) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON Sht: 2
Date: Chkd:
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64503 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T4 T3 T2 T1
C24
A (1)
C23

C26
B (1)
D1 MiCOM P645 (PART)
C25 -
D2 OPTO 1
C28
+
D3 J11
- WATCHDOG B3
C (1) OPTO 2 J12 -
D4 CONTACT
+ J13 RELAY 17
NOTE 2 C27
D5 WATCHDOG B4
- J14 +
T2 OPTO 3 CONTACT
C18 D6 B7
+ H1 -
P2 A (2) D7 RELAY 1 H2 RELAY 18
-
S2 OPTO 4 H3 B8
C17 D8 + HIGH BREAK
+
RELAY 2 H4 B11 CONTACTS
C20 D9 -
-
OPTO 5 H5 RELAY 19
S1 D10
B (2) + RELAY 3 H6 B12
+
D11 - H7
P1 C19 B15
OPTO 6 -
D12 RELAY 4 H8
C22 + RELAY 20
D13 H9 B16
- +
C (2) OPTO 7 RELAY 5 H10
D14
+ H11
C21
D15 - RELAY 6 H12
T3 E24 OPTO 8
D16 H13
+
P2 A (3) D17 H14
COMMON RELAY 7
S2 E23 D18 H15
CONNECTION
H16
E26 F1 - H17
F2 OPTO 9 RELAY 8
S1 B (3) + H18
F3 -
P1 E25 G1
F4 OPTO 10
+ RELAY 9 G2
E28
F5 - G3
C (3) OPTO 11
F6 RELAY 10 G4
+
E27 G5 NOTE 7
F7 -
T4 RELAY 11 COMMS
E18 OPTO 12 G6
F8
+ G7
P2 A (4) F9 - RELAY 12 G8
S2 E17 F10 OPTO 13
+ G9
F11 RELAY 13 G10
E20 - J17
-
F12 OPTO 14 G11
S1 B (4) + SEE DRAWING
RELAY 14 G12 EIA485/
F13 - 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 + PORT
E22 + G14
RELAY 15 J16
F15 - G15 SCN
C (4) OPTO 16
F16 G16
E21
+
G17
* J1
F17 -
RELAY 16 AC OR DC
T5 E12
COMMON G18 J2 x AUX SUPPLY
F18 CONNECTION +
A (5)
E11

E14
B (5)
E13

E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH

SEE SHEET 2 FOR NOTES MiCOM P645 (PART)


Issue: Revision: Title:
CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (16I/16O + 4 HB RELAYS) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 07/09/2023 Name: S WOOTTON Sht: 1
10P64528
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c
C2 C2 VA
a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3 NOTES:

1.
(a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.

GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.

TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)


NOTE 3 2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
IS ALWAYS AN HV WINDING CONNECTION.
S2 P2
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C12 TN3 S1 P1 (USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
C14 TN2 S1 P1 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).

C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.

C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (16I/16O + 4 HB RELAYS) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 07/09/2023 Name: S WOOTTON Sht: 2
10P64528
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1 E1 -
C C C C B E2 OPTO 1 M11
+ WATCHDOG B1
C B A C B A C B A PHASE ROTATION M12
E3 - CONTACT B2 RTD 1
OPTO 2 M13
E4 WATCHDOG B3
+ M14
T1 CONTACT B4
T4 T3 T2 D24 E5 - L1
OPTO 3 B5 RTD 2
A (1) E6 RELAY 1 L2
+ B6
D23 E7 - L3
B7
E8 OPTO 4 RELAY 2 L4 OPTIONAL
D26 + B8 RTD 3
L5
E9 B9
B (1) - RELAY 3 L6
E10 OPTO 5
D25 + L7
E11 - RELAY 4 L8
D28 OPTO 6 B28
E12 L9
+ B29 RTD 10
C (1) RELAY 5 L10
E13 - B30
NOTE 2 D27 OPTO 7 L11
E14
+ RELAY 6 L12
T2
D18 E15 - L13
OPTO 8 C1
P2 A (2) E16 L14 20mA
+ RELAY 7 C2
S2 D17 E17 L15 1mA OUTPUT 1
COMMON L16 C3
E18 CONNECTION
D20 C5
L17 20mA
G1 - RELAY 8
S1 B (2) L18 C6
G2 OPTO 9 1mA OUTPUT 2
D19 +
K1 C7
G3 - RELAY 9 K2 C9
D22 OPTO 10 20mA
G4 K3
+
C (2) C10
G5 RELAY 10 K4 1mA OUTPUT 3
-
D21 OPTO 11 C11
G6 K5
+
T3 RELAY 11 K6 C13
F24 G7 20mA
-
OPTO 12 K7 C14
P2 A (3) G8 1mA OUTPUT 4
+ RELAY 12 K8 C15 CLIO
S2 F23 G9 - K9
OPTO 13 C16 CURRENT LOOP
G10 RELAY 13 K10 20mA
F26 + INPUTS & OUTPUTS
C17
G11 K11 1mA INPUT 1 (OPTIONAL)
S1 B (3) -
OPTO 14 RELAY 14 K12 C18
G12
F25 +
K13 C20
G13 20mA
- K14
F28 OPTO 15 RELAY 15 C21
G14 1mA INPUT 2
+ K15
C (3) C22
G15 - K16
F27 OPTO 16 C24
G16 K17 20mA
+ RELAY 16
T4 K18 C25
F18 G17 1mA INPUT 3
COMMON C26
P2 A (4) G18 CONNECTION
C28
S2 F17 20mA
C29
- J3 1mA INPUT 4
F20 C30
RELAY 17
S1 B (4) J4
+
F19 J7
-
F22 RELAY 18
J8
C (4) HIGH BREAK +
NOTE 7
CONTACTS - J11 COMMS
F21
RELAY 19
T5 F12 J12
+ M17
-
A (5) - J15
SEE DRAWING EIA485/
F11 RELAY 20 10Px4001 KBUS
J16 M18
+ + PORT
F14 M16
B (5) SCN

F13 * M1 -
AC OR DC
F16 M2 x AUX SUPPLY
+
C (5)
F15
CASE
EARTH
SEE SHEET 2 FOR NOTES
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 19/09/2023 Name: S WOOTTON Sht: 1
10P64538
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF WITH 4 POLE VT INPUTS (16I/20O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 18/09/2023 Name: S WOOTTON Sht: 2
10P64538
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T4 T3 T2 T1
C24 MiCOM P645 (PART)
B1 J11
A (1) WATCHDOG
RELAY 15 B2 J12 CONTACT
C23 B3 J13
WATCHDOG
RELAY 16 B4 J14 CONTACT
C26
B5 H1
B (1) RELAY 17 B6 H2 RELAY 1
D1 -
C25 B7
OPTO 1 H3
D2
C28 + RELAY 18 B8 H4 RELAY 2
D3 - B9 H5
C (1) OPTO 2
D4 B10 H6 RELAY 3
+
NOTE 2 C27 B11
D5 RELAY 19 H7
-
T2 OPTO 3 B12 H8
C18 D6 RELAY 4
+ B13 H9
A (2) D7 - B14 H10
S2 OPTO 4 RELAY 20
C17 D8 B15
+ H11 RELAY 5
C20 D9 B16 H12
-
D10 OPTO 5 B17 H13
S1 B (2) + RELAY 21
B18 H14
D11 - RELAY 6
C19
OPTO 6 H15
D12
C22 + H16
D13 - H17 RELAY 7
C (2) OPTO 7
D14 H18
+
C21
D15 G1
-
T3 E24 OPTO 8 G2 RELAY 8
D16
+
G3
A (3) D17
COMMON G4 RELAY 9
S2 E23 D18 CONNECTION G5
E26 F1 G6 RELAY 10
-
F2 OPTO 9 G7
S1 B (3) +
F3 G8 RELAY 11
E25 -
OPTO 10 G9
F4
E28 + G10
F5 - G11 RELAY 12
C (3) OPTO 11
F6 G12
+
E27
F7 G13
-
T4 E18 OPTO 12 G14
F8 RELAY 13
+
G15
A (4) F9 - G16
S2 E17 F10 OPTO 13
+ G17 RELAY 14
E20 F11 - G18
F12 OPTO 14
S1 B (4) +
F13 -
E19
F14 OPTO 15
E22 +
F15 NOTE 7
-
C (4) OPTO 16 COMMS
F16
+
E21
F17
T5 COMMON
E12 F18 CONNECTION
A (5)
J17
E11 -
SEE DRAWING EIA485/
E14 10Px4001. KBUS
J18
+ PORT
B (5)
J16
E13 SCN
E16 * J1 -
C (5) AC OR DC
J2 x AUX SUPPLY
CASE +
E15 EARTH

SEE SHEET 2 FOR NOTES MiCOM P645 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


Issue: Revision: Title:
CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (16I/21O) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 07/09/2023 Name: S WOOTTON Sht: 1
10P64529
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)

S2 P2 2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1


IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
I Y (TV) S2 P2 (USED BY V/Hz W2 PROTECTION ONLY).
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D14 TN2 S1 P1 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
I Y (LV) S2 P2 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
D13 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
I Y (HV)
FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (16I/16O) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 07/09/2023 Name: S WOOTTON Sht: 2
10P64529
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
C
UK Grid Solutions Ltd
No: St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1 E1 -
C C C C B E2 OPTO 1 M11 B1
+ WATCHDOG
C B A C B A C B A PHASE ROTATION M12 B2 RTD 1
E3 - CONTACT
OPTO 2 M13 B3
E4 WATCHDOG
+ M14 B4
T1 CONTACT
T4 T3 T2 D24 E5 - L1 B5 RTD 2
A (1) E6 OPTO 3 RELAY 1
+ L2 B6
D23 E7 - L3 B7
OPTO 4 RELAY 2 L4 B8 RTD 3 OPTIONAL
E8
D26 +
L5 B9
E9 -
B (1) RELAY 3 L6
E10 OPTO 5
D25 + L7
E11 - L8 B28
D28 RELAY 4
E12 OPTO 6 L9 RTD 10
+ B29
C (1) L10 B30
E13 -
NOTE 2 D27 OPTO 7 RELAY 5 L11
E14
+ L12
T2
D18 E15 - L13
P2 A (2) E16 OPTO 8
+ RELAY 6 L14
S2 D17 E17 L15
COMMON C1
L16 20mA
E18 CONNECTION
D20 C2
RELAY 7 L17 1mA OUTPUT 1
G1 -
S1 B (2) L18 C3
G2 OPTO 9
D19 + K1 C5
P1 20mA
G3 - RELAY 8 K2
D22
C6
OPTO 10 1mA OUTPUT 2
G4 K3
+ C7
C (2) RELAY 9 K4
G5 - C9
D21 OPTO 11 K5 20mA
G6
+ RELAY 10 K6 C10
T3 1mA OUTPUT 3
F24 G7 - K7 C11
P2 A (3) G8 OPTO 12
+ RELAY 11 K8 C13
S2 20mA
F23 G9 - K9
C14
OPTO 13 K10 1mA OUTPUT 4
G10
F26 + C15
G11 RELAY 12 K11 CLIO
S1 B (3) - C16
OPTO 14 K12 20mA CURRENT LOOP
G12
F25 + K13 C17 INPUTS & OUTPUTS
P1 1mA INPUT 1
G13 - K14 (OPTIONAL)
F28 RELAY 13 C18
G14 OPTO 15 K15
+ C20
C (3) K16 20mA
G15 - C21
F27 OPTO 16 K17 1mA INPUT 2
G16 RELAY 14
+ K18 C22
T4
F18 G17
COMMON J1 C24
20mA
P2 A (4) G18 CONNECTION RELAY 15 J2 C25
S2 1mA INPUT 3
F17 J3
C26
RELAY 16 J4
F20 C28
J5 20mA
S1 B (4) RELAY 17 J6 C29
1mA INPUT 4
P1 F19 J7 C30

RELAY 18 J8
F22
J9
C (4) J10 NOTE 7
COMMS
F21 RELAY 19 J11
T5 J12
F12 M17
J13 -
A (5) J14 SEE DRAWING
RELAY 20 EIA485/
J15 10Px4001 KBUS
F11 M18
+ PORT
J16
F14 M16
RELAY 21 J17
SCN
B (5) J18
F13 * M1 -
AC OR DC
F16 M2 x AUX SUPPLY
+
C (5)
F15
CASE
EARTH
SEE SHEET 2 FOR NOTES
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFERENTIAL. WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 19/09/2023 Name: S WOOTTON Sht: 1
10P64542
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (16I/21O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 19/09/2023 Name: S WOOTTON Sht: 2
10P64542
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T1
T4 T3 T2 C24
A (1)
C23

C26
B (1)
D1 MiCOM P645 (PART)
C25 -
D2 OPTO 1
C28 +
D3 J11
- WATCHDOG
C (1) OPTO 2 J12
D4 CONTACT
+ J13
NOTE 2 C27
D5 - WATCHDOG
T2 CONTACT J14
C18 D6 OPTO 3
+ H1 B1
P2 A (2) D7 RELAY 1 H2 B2 RELAY 17
-
S2 C17 D8 OPTO 4 H3 B3
+
RELAY 2 H4 B4 RELAY 18
C20 D9 -
OPTO 5 H5 B5
S1 D10
B (2) + RELAY 3 H6 B6 RELAY 19
D11 - H7 B7
P1 C19
D12 OPTO 6 RELAY 4 H8 B8 RELAY 20
C22 +
D13 H9 B9
-
C (2) OPTO 7 RELAY 5 H10 B10 RELAY 21
D14
+ H11 B11
C21
D15 - RELAY 6 H12 B12 RELAY 22
T3 OPTO 8
E24 D16
+ H13 B13
P2 A (3) D17 H14 B14
COMMON RELAY 7 RELAY 23
S2 E23 D18 H15 B15
CONNECTION
H16 B16
E26 F1 - H17 B17
F2 OPTO 9 RELAY 8 RELAY 24
S1 B (3) + H18 B18
F3 -
P1 E25 G1
F4 OPTO 10
+ RELAY 9 G2
E28
F5 - G3
C (3) OPTO 11
F6 RELAY 10 G4
+
E27 G5
F7 -
T4 RELAY 11 G6
E18 F8 OPTO 12 NOTE 7
+ G7 COMMS
P2 A (4) F9 - RELAY 12 G8
S2 E17 F10 OPTO 13
+ G9
F11 RELAY 13 G10
E20 - J17
-
F12 OPTO 14 G11
S1 B (4) + SEE DRAWING
RELAY 14 G12 EIA485/
F13 - 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 + PORT
E22 + G14
RELAY 15 J16
F15 - G15 SCN
C (4) OPTO 16
F16 G16
E21
+
G17
* J1
F17 -
RELAY 16 AC OR DC
T5
E12
COMMON G18 J2 x AUX SUPPLY
F18 CONNECTION +
A (5)
E11

E14
B (5)
E13

E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH

SEE SHEET 2 FOR NOTES MiCOM P645 (PART)

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
F DIFFERENTIAL (16 I/P & 24 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON Sht: 1
10P64505
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
C
UK Grid Solutions Ltd
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next St Leonards Building, Harry Kerr Drive,
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford. ST16 1WT, UK.
A A

B B A

C C B
A B C A B C
C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c
C2 VA
C2 a b c

C1
C1

C4 VB
C4 VB

OPTIONAL
C3
NOTE 6 C3

E2 VC
E2 VC

NOTE 8
E1 VN
E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3
NOTES:

GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)

S2 P2 2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS.T1


IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
C12 TN3 S1 P1
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) S2 P2 (USED BY V/Hz W2 PROTECTION ONLY).
C11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
C14 TN2 S1 P1 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
Y (LV) S2 P2 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
C13 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (16 I/P & 24 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64505 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1 E1 -
C C C C B E2 OPTO 1 M11 B1
+ WATCHDOG
C B A C B A C B A PHASE ROTATION M12 B2 RTD 1
E3 - CONTACT
OPTO 2 M13 B3
E4 WATCHDOG
+ M14 B4
T1 CONTACT
T4 T3 T2 D24 E5 - L1 B5 RTD 2
A (1) E6 OPTO 3
+ RELAY 1 L2 B6
D23 E7 L3 B7 OPTIONAL
-
E8 OPTO 4 RELAY 2 L4 B8 RTD 3
D26 +
L5 B9
E9 -
B (1) RELAY 3 L6
E10 OPTO 5
D25 + L7
E11 - RELAY 4 L8 B28
D28 OPTO 6
E12 L9 B29 RTD 10
+
C (1) RELAY 5 L10 B30
E13 -
NOTE 2 D27 OPTO 7 L11
E14
+ RELAY 6 L12
T2
D18 E15 - L13
P2 A (2) E16 OPTO 8
+ L14
RELAY 7
S2 D17 E17 L15 C1
20mA
COMMON L16 C2
E18 CONNECTION 1mA OUTPUT 1
D20
L17 C3
G1 - RELAY 8
S1 B (2) L18
G2 OPTO 9 C5
+ 20mA
P1 D19 K1
G3 C6
- RELAY 9 K2 1mA OUTPUT 2
D22 OPTO 10 C7
G4 K3
+
C (2) C9
G5 - RELAY 10 K4 20mA
D21 G6 OPTO 11 K5 C10
+ 1mA OUTPUT 3
T3 RELAY 11 K6 C11
F24 G7 -
OPTO 12 K7 C13
P2 A (3) G8 20mA
+ RELAY 12 K8
S2 F23 G9 C14
- K9 1mA OUTPUT 4
G10 OPTO 13 RELAY 13 C15
F26 + K10 CLIO
G11 K11 C16 CURRENT LOOP
S1 B (3) - 20mA
OPTO 14 RELAY 14 K12 C17 INPUTS & OUTPUTS
G12 1mA INPUT 1
F25 + (OPTIONAL)
P1 K13 C18
G13 -
F28 K14
G14 OPTO 15 RELAY 15 C20
+ K15 20mA
C (3) C21
G15 - K16 1mA INPUT 2
F27 G16 OPTO 16 K17 C22
+ RELAY 16
T4 K18 C24
F18 G17 20mA
COMMON C25
P2 A (4) G18 CONNECTION J1 1mA INPUT 3
S2 RELAY 17 J2 C26
F17
J3 C28
F20 RELAY 18 J4 20mA
C29
S1 B (4) J5 1mA INPUT 4
RELAY 19 J6 C30
P1 F19
J7
F22 RELAY 20 J8
NOTE 7
C (4) J9 COMMS
RELAY 21 J10
F21
J11 M17
T5 F12 RELAY 22 -
J12
SEE DRAWING EIA485/
A (5) J13
10Px4001 KBUS
J14 M18
F11 RELAY 23 + PORT
J15
M16
F14 J16 SCN
B (5) J17
RELAY 24
J18
* M1 -
F13 AC OR DC
M2 x AUX SUPPLY
+
F16
C (5)
CASE
F15 EARTH

SEE SHEET 2 FOR NOTES


* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 19/09/2023 Name: S WOOTTON Sht: 1
10P64546
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (16I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 19/09/2023 Name: S WOOTTON Sht: 2
10P64546
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T4 T3 T2 T1
C24
A (1)
C23

C26
B (1)
D1 MiCOM P645 (PART)
C25 -
D2 OPTO 1
C28
+
D3 J11
- WATCHDOG
C (1) OPTO 2 J12
D4 CONTACT
+ J13
NOTE 2 C27
D5 - WATCHDOG
T2 CONTACT J14
C18 D6 OPTO 3
+ H1
P2 A (2) D7 RELAY 1 H2
-
S2 C17 D8 OPTO 4 H3
+
RELAY 2 H4
C20 D9 -
OPTO 5 H5
S1 D10
B (2) + RELAY 3 H6
D11 - H7
P1 C19
D12 OPTO 6 RELAY 4 H8
C22 +
D13 H9
-
C (2) OPTO 7 RELAY 5 H10
D14
+ H11
C21
D15 - RELAY 6 H12
T3 E24 OPTO 8
D16 H13
+
P2 A (3) D17 H14
COMMON RELAY 7
S2 E23 D18 H15
CONNECTION
H16
E26 F1 - H17
F2 OPTO 9 RELAY 8
S1 B (3) + H18
F3 -
P1 E25 G1
F4 OPTO 10
+ RELAY 9 G2
E28
F5 - G3
C (3) OPTO 11
F6 RELAY 10 G4
+
E27 G5 NOTE 7
F7 -
T4 RELAY 11 COMMS
E18 OPTO 12 G6
F8
+ G7
P2 A (4) F9 - RELAY 12 G8
S2 E17 F10 OPTO 13
+ G9
F11 RELAY 13 G10
E20 - J17
-
F12 OPTO 14 G11
S1 B (4) + SEE DRAWING
RELAY 14 G12 EIA485/
F13 - 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 + PORT
E22 + G14
RELAY 15 J16
F15 - G15 SCN
C (4) OPTO 16
F16 G16
+ *
E21 G17 J1 -
F17 RELAY 16 AC OR DC
T5 E12
COMMON G18 J2 x AUX SUPPLY
F18 CONNECTION +
B9
A (5) B1 - RELAY 17 B10
E11 B2 OPTO 17
+ B11
B3 - RELAY 18 B12
E14
B4 OPTO 18 B13
B (5) +
B5 B14
- RELAY 19
E13 B15
B6 OPTO 19
+ B16
E16
B7 - B17
C (5) OPTO 20 RELAY 20
B8 B18
+
E15

SEE SHEET 2 FOR NOTES

CASE
EARTH

MiCOM P645 (PART)

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (20I/20O) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 07/09/2023 Name: S WOOTTON Sht: 1
10P64530
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3
NOTES:

GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)

S2 P2 2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1


IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
D12 TN3 S1 P1
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
I Y (TV) S2 P2 (USED BY V/Hz W2 PROTECTION ONLY).
D11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D14 TN2 S1 P1 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
I Y (LV) S2 P2 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
D13 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1
9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
I Y (HV)
FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.
D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (20I/20O) 60TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 11/10/2023 Name: S WOOTTON Sht: 2
10P64530
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1 E1 -
C C C C B E2 OPTO 1 M11
+ WATCHDOG B1
C B A C B A C B A PHASE ROTATION M12
E3 - CONTACT
B2 RTD 1
OPTO 2 M13
E4 WATCHDOG B3
+ M14
T1 CONTACT
T4 T3 T2 D24 E5 B4
- L1
A (1) E6 OPTO 3 B5 RTD 2
+ RELAY 1 L2
B6
D23 E7 L3
- B7
E8 OPTO 4 RELAY 2 L4 OPTIONAL
D26 + B8 RTD 3
L5
E9 - B9
B (1) RELAY 3 L6
E10 OPTO 5
D25 + L7
E11 - RELAY 4 L8
D28 OPTO 6 B28
E12 L9
+ B29 RTD 10
C (1) RELAY 5 L10
E13 - B30
NOTE 2 D27 OPTO 7 L11
E14
+ RELAY 6 L12
T2 C1
D18 E15 20mA
- L13
OPTO 8 C2
P2 A (2) E16 L14 1mA OUTPUT 1
+ RELAY 7
S2
C3
D17 E17 L15
COMMON L16 C5
E18 CONNECTION 20mA
D20
L17 C6
G1 RELAY 8 1mA OUTPUT 2
S1 B (2) - L18
OPTO 9 C7
G2
D19 +
P1 K1 C9
G3 20mA
- RELAY 9 K2
D22 OPTO 10 C10
G4 1mA OUTPUT 3
+ K3
C (2) C11
G5 - RELAY 10 K4
D21 OPTO 11 C13
G6 K5 20mA
+
T3 RELAY 11 K6 C14
F24 G7 1mA OUTPUT 4
-
OPTO 12 K7 C15 CLIO
P2 A (3) G8
+ RELAY 12 K8
S2
C16 CURRENT LOOP
F23 G9 20mA
- K9 INPUTS & OUTPUTS
OPTO 13 C17
G10 RELAY 13 K10 1mA INPUT 1 (OPTIONAL)
F26 +
C18
G11 K11
S1 B (3) -
OPTO 14 RELAY 14 K12 C20
G12 20mA
F25 +
P1 K13 C21
G13 1mA INPUT 2
- K14
F28 OPTO 15 RELAY 15 C22
G14 K15
+
C (3) C24
G15 K16 20mA
-
F27 OPTO 16 C25
G16 K17 1mA INPUT 3
+ RELAY 16
T4 K18 C26
F18 G17
COMMON J9 C28
P2 A (4) G18 CONNECTION 20mA
RELAY 17 J10 C29
S2 F17 J1 1mA INPUT 4
- J11
OPTO 17 C30
J2 RELAY 18 J12
F20 +
J3 - J13
S1 B (4)
J4 OPTO 18 J14
+ RELAY 19 NOTE 7
P1 F19 J15 COMMS
J5 -
F22 J16
J6 OPTO 19
+ J17 M17
C (4) RELAY 20 -
J7 - J18
SEE DRAWING EIA485/
F21 J8 OPTO 20
+ 10Px4001 KBUS
T5 M18
F12 + PORT
M16
A (5)
SCN
F11
* M1 -
F14 AC OR DC
M2 x AUX SUPPLY
B (5)
+

F13

F16
C (5)
F15
CASE
EARTH
SEE SHEET 2 FOR NOTES
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 20/09/2023 Name: S WOOTTON Sht: 1
10P64550
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (20I/20O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 20/09/2023 Name: S WOOTTON Sht: 2
10P64550
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1
C C C C B
C B A C B A C B A PHASE ROTATION

T1
T4 T3 T2 C24
A (1)
C23

C26
B (1)
D1 MiCOM P645 (PART)
C25 -
D2 OPTO 1
C28 +
D3 J11
- WATCHDOG
C (1) OPTO 2 J12
D4 CONTACT
+ J13
NOTE 2 C27
D5 - WATCHDOG B1
T2 CONTACT J14 -
C18 D6 OPTO 3 OPTO 17
+ H1 B2
+
P2 A (2) D7 RELAY 1 H2
- B3 -
S2 C17 D8 OPTO 4 H3 OPTO 18
+ B4
RELAY 2 H4 +
C20 D9 - B5
H5 -
D10 OPTO 5 OPTO 19
S1 B (2) + RELAY 3 H6 B6
+
D11 - H7 B7
P1 C19 -
D12 OPTO 6 RELAY 4 H8 OPTO 20
+ B8
C22 +
D13 H9
- B9 -
C (2) OPTO 7 RELAY 5 H10
D14 B10 OPTO 21
+ H11 +
C21
D15 - B11
RELAY 6 H12 -
T3 E24 OPTO 8
D16 H13 B12 OPTO 22
+ +
P2 A (3) D17 H14
RELAY 7 B13 -
S2 COMMON
E23 D18 CONNECTION H15 OPTO 23
B14
H16 +
E26 F1 - B15
H17 -
F2 OPTO 9 RELAY 8 OPTO 24
S1 B (3) + H18 B16
+
F3 - B17
P1 E25 G1
F4 OPTO 10 COMMON
+ RELAY 9 G2 B18 CONNECTION
E28
F5 - G3
C (3) OPTO 11
F6 RELAY 10 G4
+
E27 G5
F7 -
T4 OPTO 12 RELAY 11 G6 NOTE 7
E18 F8
+ G7 COMMS
P2 A (4) F9 - RELAY 12 G8
S2 E17 F10 OPTO 13
+ G9
F11 RELAY 13 G10
E20 - J17
-
F12 OPTO 14 G11
S1 B (4) + SEE DRAWING
RELAY 14 G12 EIA485/
F13 - 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 + PORT
E22 + G14
RELAY 15 J16
F15 - G15 SCN
C (4) OPTO 16
F16 G16
+ *
E21 G17 J1 -
F17 RELAY 16 AC OR DC
T5 E12
COMMON G18 J2 x AUX SUPPLY
F18 CONNECTION +
A (5)
E11

E14
B (5)
E13

E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH

SEE SHEET 2 FOR NOTES MiCOM P645 (PART)

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
F DIFFERENTIAL (24 I/P & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that Sht: 1
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64504 Next
Sht: 2
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
C2 C2 a b c

C1 C1

C4 VB C4 VB

OPTIONAL
C3 C3
NOTE 6

E2 VC E2 VC

NOTE 8
E1 VN E1 VN

E4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


E3
NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
(c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
S2 P2
IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
C12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
Y (TV) S2 P2 (USED BY V/Hz W2 PROTECTION ONLY).
C11 5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

TN2 6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.


C14 S1 P1
Y (LV) 7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
S2 P2
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
C13
8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: 5 BIAS INPUT TRANSFORMER
J DIFFERENTIAL (24 I/P & 16 O/P) WITH 4 POLE VT INPUTS (60TE)
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 4/30/2020 Name: S.J.BURTON This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that
Sht: 2
Date: Chkd:
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
No:
10P64504 Next
Sht:
-
C
UK Grid Solutions Ltd
St Leonards Building, Harry Kerr Drive,
Stafford. ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1 E1 -
C C C C B E2 OPTO 1 M11
+ WATCHDOG B1
C B A C B A C B A PHASE ROTATION M12
E3 - CONTACT B2 RTD 1
OPTO 2 M13 B3
E4 WATCHDOG
+ M14
T1 CONTACT B4
T4 T3 T2 D24 E5 - L1 B5 RTD 2
A (1) E6 OPTO 3
+ RELAY 1 L2 B6
D23 E7 L3 B7
-
E8 OPTO 4 RELAY 2 L4 B8 RTD 3 OPTIONAL
D26 +
L5 B9
E9 -
B (1) RELAY 3 L6
E10 OPTO 5
D25 + L7
E11 - RELAY 4 L8
D28 B28
E12 OPTO 6 L9
+ B29 RTD 10
C (1) RELAY 5 L10
E13 - B30
NOTE 2 D27 OPTO 7 L11
E14
+ RELAY 6 L12
T2
D18 E15 - L13
P2 A (2) E16 OPTO 8
+ L14
RELAY 7
S2 D17 E17 L15 C1
COMMON 20mA
E18 L16
D20 CONNECTION C2
L17 1mA OUTPUT 1
G1 - RELAY 8 C3
S1 B (2) L18
G2 OPTO 9
+ C5
P1 D19 K1 20mA
G3 - C6
RELAY 9 K2 1mA OUTPUT 2
D22 OPTO 10
G4 K3 C7
+
C (2)
G5 - RELAY 10 K4 C9
20mA
D21 G6 OPTO 11 K5
+ C10
T3 RELAY 11 1mA OUTPUT 3
F24 G7 K6
- C11
OPTO 12 K7
P2 A (3) G8 C13
+ RELAY 12 K8 20mA
S2 F23 G9 C14
- K9 1mA OUTPUT 4
G10 OPTO 13 RELAY 13 K10
F26 + C15 CLIO
G11 K11 C16 CURRENT LOOP
S1 B (3) - 20mA
OPTO 14 RELAY 14 K12 INPUTS & OUTPUTS
G12 C17
F25 + 1mA INPUT 1 (OPTIONAL)
P1 K13
G13 - C18
F28 K14
G14 OPTO 15 RELAY 15
+ K15 C20
C (3) 20mA
G15 - K16 C21
1mA INPUT 2
F27 G16 OPTO 16 K17
+ RELAY 16 C22
T4 K18
F18 G17 C24
COMMON 20mA
P2 A (4) G18 CONNECTION C25
1mA INPUT 3
S2 F17 H1 C26
-
H2 OPTO 17 C28
F20 + 20mA
S1 H3 - C29
B (4) 1mA INPUT 4
H4 OPTO 18
+ C30
P1 F19
H5 -
F22 OPTO 19
H6
+
C (4)
H7 -
F21 OPTO 20 NOTE 7
H8
+ COMMS
T5 F12 H9 -
A (5) H10 OPTO 21
+ M17
-
F11 H11 - SEE DRAWING EIA485/
H12 OPTO 22 10Px4001 KBUS
F14 + M18
+ PORT
H13 -
B (5)
OPTO 23 M16
H14 SCN
F13 +
H15
F16
- * M1
H16 OPTO 24 -
+ AC OR DC
C (5) M2 x AUX SUPPLY
H17 +
F15 COMMON
H18 CONNECTION CASE
EARTH
SEE SHEET 2 FOR NOTES
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 26/09/2023 Name: S WOOTTON Sht: 1
10P64558
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (24I/16O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 26/09/2023 Name: S WOOTTON Sht: 2
10P64558
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1 M11
B PROTECTED TRANSFORMER B B E1 WATCHDOG
T5 T1 - CONTACT M12
C C C C B E2 OPTO 1 M13
+ B1
PHASE ROTATION WATCHDOG
C B A C B A C B A E3 M14 B2 RTD 1
- CONTACT
OPTO 2 L1 B3
E4
+ RELAY 1 L2
T1 B4
T4 T3 T2 D24 E5 - L3 B5 RTD 2
A (1) E6 OPTO 3
+ RELAY 2 L4 B6
D23 E7 - L5 B7
E8 OPTO 4 RELAY 3 L6 B8 RTD 3 OPTIONAL
D26 +
L7 B9
E9 -
B (1) RELAY 4 L8
E10 OPTO 5
D25 + L9
E11 - RELAY 5 L10
D28 B28
E12 OPTO 6 L11
+ B29 RTD 10
C (1) RELAY 6 L12
E13 - B30
NOTE 2 D27 OPTO 7 L13
E14
+ L14
T2 RELAY 7
D18 E15 - L15
P2 A (2) E16 OPTO 8
+ L16
S2 D17 E17 L17 B1
COMMON RELAY 8 20mA
E18 L18
D20 CONNECTION B2
1mA OUTPUT 1
G1 K1 B3
S1 B (2) -
G2 OPTO 9 RELAY 9 K2
+ B5
P1 D19 K3 20mA
G3 - B6
D22 RELAY 10 K4 1mA OUTPUT 2
G4 OPTO 10
+ K5 B7
C (2)
G5 - RELAY 11 K6 B9
20mA
D21 G6 OPTO 11 K7
+ B10
T3 1mA OUTPUT 3
F24 G7 RELAY 12 K8
- B11
OPTO 12 K9
P2 A (3) G8 B13
+ RELAY 13 K10 20mA
S2 F23 G9 B14
- K11 1mA OUTPUT 4
G10 OPTO 13 RELAY 14
F26 + K12 B15 CLIO
G11 K13 B16 CURRENT LOOP
S1 B (3) - 20mA
G12 OPTO 14 K14 INPUTS & OUTPUTS
+ RELAY 15 B17
P1 F25 K15 1mA INPUT 1 (OPTIONAL)
G13 - B18
F28 K16
G14 OPTO 15
+ K17 B20
C (3) RELAY 16 20mA
G15 - K18 B21
1mA INPUT 2
F27 G16 OPTO 16
+ J3 B22
T4 -
F18 G17 B24
COMMON RELAY 17 20mA
P2 A (4) G18 J4
CONNECTION + B25
1mA INPUT 3
S2 F17 H1 - J7 B26
-
H2 OPTO 17 RELAY 18 B28
F20 + J8 20mA
H3 HIGH BREAK +
S1 B (4) - B29
CONTACTS J11 1mA INPUT 4
H4 OPTO 18 -
+ B30
P1 F19 RELAY 19
H5 - J12
F22 +
H6 OPTO 19
+ - J15
C (4)
H7 - RELAY 20
F21 OPTO 20 J16 NOTE 7
H8 + COMMS
+
T5 F12 H9 - B3
-
A (5) H10 OPTO 21 RELAY 21 M17
+ B4 -
+
F11 H11 SEE DRAWING EIA485/
- B7
OPTO 22 - 10Px4001 KBUS
F14 H12 M18
+ RELAY 22 + PORT
H13 - B8
B (5) HIGH BREAK + M16
H14 OPTO 23 B11 SCN
F13 + CONTACTS -
H15 - RELAY 23 * M1
F16 B12 -
H16 OPTO 24 + AC OR DC
+ M2 x AUX SUPPLY
C (5) B15 +
H17 -
F15 COMMON RELAY 24
H18 CONNECTION B16
+
SEE SHEET 2 FOR NOTES

CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 26/09/2023 Name: S WOOTTON Sht: 1
10P64559
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 26/09/2023 Name: S WOOTTON Sht: 2
10P64559
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1 M11
B PROTECTED TRANSFORMER B B E1 WATCHDOG
T5 T1 - CONTACT M12 B1
C C C C B E2 OPTO 1 M13 B2 RTD 1
+ WATCHDOG
C B A C B A C B A PHASE ROTATION M14 B3
E3 - CONTACT
OPTO 2 L1 B4
E4
+ RELAY 1 L2 B5 RTD 2
T1
T4 T3 T2 D24 E5 - L3 B6
A (1) E6 OPTO 3
+ RELAY 2 L4 B7
OPTIONAL
D23 E7 - L5 B8 RTD 3
E8 OPTO 4 RELAY 3 L6 B9
D26 +
L7
E9 -
B (1) RELAY 4 L8
E10 OPTO 5
D25 + L9 B28
E11 - RELAY 5 L10 RTD 10
B29
D28 OPTO 6
E12 L11 B30
+
C (1) RELAY 6 L12
E13 -
NOTE 2 D27 OPTO 7 L13
E14
+ L14
T2 RELAY 7
D18 E15 - L15
P2 A (2) E16 OPTO 8
+ L16
C1
S2 D17 E17 L17 20mA
COMMON RELAY 8 C2
E18 L18 1mA OUTPUT 1
D20 CONNECTION
C3
G1 K1
S1 B (2) -
RELAY 9 K2 C5
G2 OPTO 9 20mA
D19 +
P1 K3 C6
G3 1mA OUTPUT 2
- RELAY 10 K4
D22 OPTO 10 C7
G4
+ K5
C (2) C9
G5 RELAY 11 K6 20mA
-
D21 OPTO 11 C10
G6 K7 1mA OUTPUT 3
+
T3 RELAY 12 K8 C11
F24 G7 -
OPTO 12 K9 C13
P2 A (3) G8 20mA
+ RELAY 13 K10 C14
S2 F23 G9 1mA OUTPUT 4
- K11
OPTO 13 C15 CLIO
G10 RELAY 14 K12
F26 +
C16 CURRENT LOOP
G11 K13 20mA
S1 B (3) - INPUTS & OUTPUTS
OPTO 14 K14 C17
G12 RELAY 15 1mA INPUT 1 (OPTIONAL)
F25 +
P1 K15 C18
G13 -
F28 K16 C20
G14 OPTO 15 20mA
+ K17
C (3) RELAY 16 C21
G15 K18 1mA INPUT 2
-
F27 OPTO 16 C22
G16
+ J1
T4 C24
F18 G17 RELAY 17 J2 20mA
COMMON C25
P2 A (4) G18 CONNECTION J3 1mA INPUT 3
RELAY 18 J4 C26
S2 F17 H1 - C28
OPTO 17 J5 20mA
F20 H2
+ RELAY 19 J6 C29
H3 1mA INPUT 4
S1 B (4) - J7 C30
H4 OPTO 18 RELAY 20
F19 + J8
P1
H5 J9
-
F22 OPTO 19 RELAY 21 J10
H6
+
C (4) J11
H7 - RELAY 22 J12 NOTE 7
F21 OPTO 20
H8 J13 COMMS
+
T5 F12 H9 - J14
RELAY 23
A (5) H10 OPTO 21 J15 M17
+ -
F11 H11 J16 SEE DRAWING
- EIA485/
OPTO 22 J17 10Px4001 KBUS
H12 RELAY 24 M18
F14 + J18 + PORT
H13 -
B (5) M16
H14 OPTO 23 SCN
F13 +
H15 - * M1
F16 -
H16 OPTO 24 AC OR DC
+ M2 x AUX SUPPLY
C (5) +
H17
F15 COMMON
H18 CONNECTION

SEE SHEET 2 FOR NOTES

CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INMTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 27/09/2023 Name: S WOOTTON Sht: 1
10P64565
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INTIAL ISISUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFF. WITH 4 POLE VT INPUTS (24I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 27/09/2023 Name: S WOOTTON Sht: 2
10P64565
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1 M11
B PROTECTED TRANSFORMER B B E1 WATCHDOG
T5 T1 - CONTACT M12 C1
C C C C B E2 OPTO 1 M13 C2 RTD 1
+ WATCHDOG
C B A C B A C B A PHASE ROTATION M14 C3
E3 - CONTACT
OPTO 2 L1 C4
E4
+ RELAY 1 L2 C5 RTD 2
T1
T4 T3 T2 D24 E5 - L3 C6
A (1) E6 OPTO 3
+ RELAY 2 L4 C7
OPTIONAL
D23 E7 - L5 C8 RTD 3
E8 OPTO 4 RELAY 3 L6 C9
D26 +
L7
E9 -
B (1) RELAY 4 L8
E10 OPTO 5
D25 + L9 C28
E11 - RELAY 5 L10 RTD 10
C29
D28 OPTO 6
E12 L11 C30
+
C (1) RELAY 6 L12
E13 -
NOTE 2 D27 OPTO 7 L13
E14
+ L14
T2 RELAY 7
D18 E15 - L15
P2 A (2) E16 OPTO 8
+ L16
C1
S2 D17 E17 L17 20mA
COMMON RELAY 8 C2
E18 L18 1mA OUTPUT 1
D20 CONNECTION
C3
G1 K1
S1 B (2) -
OPTO 9 RELAY 9 K2 C5
G2 20mA
D19 +
P1 K3 C6
G3 1mA OUTPUT 2
- RELAY 10 K4
D22 OPTO 10 C7
G4
+ K5
C (2) C9
G5 RELAY 11 K6 20mA
-
D21 OPTO 11 C10
G6 K7 1mA OUTPUT 3
+
T3 RELAY 12 K8 C11
F24 G7 -
OPTO 12 K9 C13
P2 A (3) G8 20mA
+ RELAY 13 K10 C14
S2 F23 G9 1mA OUTPUT 4
- K11
OPTO 13 C15 CLIO
G10 RELAY 14 K12
F26 +
C16 CURRENT LOOP
G11 K13 20mA
S1 B (3) - INPUTS & OUTPUTS
OPTO 14 K14 C17
G12 RELAY 15 1mA INPUT 1 (OPTIONAL)
F25 +
P1 K15 C18
G13 -
F28 K16 C20
G14 OPTO 15 20mA
+ K17
C (3) RELAY 16 C21
G15 K18 1mA INPUT 2
-
F27 OPTO 16 C22
G16
+ J1
T4 C24
F18 G17 RELAY 17 J2 20mA
COMMON C25
P2 A (4) G18 CONNECTION J3 1mA INPUT 3
RELAY 18 J4 C26
S2 F17 H1 - C28
OPTO 17 J5 20mA
F20 H2
+ RELAY 19 J6 C29
H3 1mA INPUT 4
S1 B (4) - J7 C30
H4 OPTO 18 RELAY 20
F19 + J8
P1
H5 J9
-
F22 OPTO 19 RELAY 21 J10
H6
+
C (4) J11
H7 - RELAY 22 J12
F21 OPTO 20
H8 J13
+
T5 F12 H9 - J14
RELAY 23
A (5) H10 OPTO 21 J15
+
F11 H11 J16
-
OPTO 22 J17
H12 RELAY 24
F14 + J18
H13 -
B (5)
OPTO 23 B1
H14
F13 + RELAY 25 B2
H15 -
F16 B3
H16 OPTO 24
+ RELAY 26 B4
C (5)
H17 B5
F15 COMMON RELAY 27
H18 B6
CONNECTION
B7
SEE SHEET 2 FOR NOTES RELAY 28 B8
B9
RELAY 29 B10 NOTE 7
B11 COMMS
RELAY 30 B12
B13 M17
-
B14 SEE DRAWING
RELAY 31 EIA485/
B15 10Px4001 KBUS
M18
B16 + PORT
B17 M16
RELAY 32
B18 SCN

* M1 -
AC OR DC
M2 x AUX SUPPLY
+
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INTIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24I/32O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 27/09/2023 Name: S WOOTTON Sht: 1
10P64566
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INTIAL ISSUE EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (24I/32O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 27/09/2023 Name: S WOOTTON Sht: 2
10P64566
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1 E1 M11
- WATCHDOG
OPTO 1 M12 B1
C C C C B E2 CONTACT
+ M13 B2 RTD 1
C B A C B A C B A PHASE ROTATION
E3 - WATCHDOG B3
CONTACT M14
E4 OPTO 2 B4
+ L1
T1
T4 T3 T2 D24 E5 RELAY 1 L2 B5 RTD 2
-
OPTO 3 L3 B6
A (1) E6
+ B7
RELAY 2 L4
D23 E7 - OPTIONAL
L5 B8 RTD 3
E8 OPTO 4
D26 + RELAY 3 L6 B9
E9 - L7
B (1)
E10 OPTO 5 RELAY 4
+ L8
D25
E11 L9 B28
-
D28 OPTO 6 RELAY 5 L10 B29 RTD 10
E12
+ L11 B30
C (1)
E13 - RELAY 6 L12
NOTE 2 D27 OPTO 7
E14 L13
+
T2 B1
D18 E15 L14 20mA
- RELAY 7
OPTO 8 B2
P2 A (2) E16 L15 1mA OUTPUT 1
+
L16 B3
S2 D17 E17
COMMON L17 B5
E18 CONNECTION RELAY 8 20mA
D20 L18 B6
G1 1mA OUTPUT 2
S1 B (2) - K1
OPTO 9 B7
G2 RELAY 9
D19 + K2
P1 B9
G3 K3 20mA
-
D22 OPTO 10 B10
G4 RELAY 10 K4 1mA OUTPUT 3
+
C (2) K5 B11
G5 -
D21 OPTO 11 RELAY 11 K6 B13
G6 20mA
+ K7
T3 B14
F24 G7 1mA OUTPUT 4
- RELAY 12 K8
OPTO 12 B15 CLIO
P2 A (3) G8 K9
+
B16 CURRENT LOOP
S2 F23 G9 RELAY 13 K10 20mA
- INPUTS & OUTPUTS
OPTO 13 K11 B17
G10 1mA INPUT 1 (OPTIONAL)
F26 +
RELAY 14 K12 B18
G11 -
S1 B (3) K13 B20
G12 OPTO 14 20mA
F25 + K14
P1 RELAY 15 B21
G13 K15 1mA INPUT 2
-
F28 OPTO 15 B22
G14 K16
+
C (3) K17 B24
G15 20mA
- RELAY 16
F27 OPTO 16 K18 B25
G16 1mA INPUT 3
+
T4 B26
F18 G17 J1
COMMON RELAY 17 J2 B28
P2 A (4) G18 CONNECTION 20mA
J3 B29
S2 F17 H1 1mA INPUT 4
- RELAY 18 J4 B30
H2 OPTO 17
F20 + J5
H3 RELAY 19 J6
S1 B (4) -
H4 OPTO 18 J7
P1 F19 +
RELAY 20 J8
H5 -
F22 J9
H6 OPTO 19
+ RELAY 21 J10
C (4)
H7 - J11
F21 OPTO 20 RELAY 22
H8 J12
+
T5 F12 H9 J13
-
OPTO 21 J14
A (5) H10 RELAY 23
+ J15
F11 H11 - J16
H12 OPTO 22
F14 + J17
RELAY 24
H13 J18
B (5) -
H14 OPTO 23
F13 +
H15 - C1
F16 -
H16 OPTO 24 OPTO 25
+ C2
C (5) +
H17 C3
F15 COMMON -
H18 CONNECTION OPTO 26 C4
+
SEE SHEET 2 FOR NOTES - C5
OPTO 27 C6
+
- C7
OPTO 28 C8
+
- C9
OPTO 29 C10
+ NOTE 7
C11 COMMS
-
OPTO 30 C12
+ M17
-
- C13
SEE DRAWING EIA485/
OPTO 31 C14
+ 10Px4001 KBUS
M18
C15 + PORT
-
OPTO 32 C16 M16
+ SCN
C17
COMMON * M1
CONNECTION C18 -
AC OR DC
M2 x AUX SUPPLY
+

CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WIOOTTON Sht: 1
10P64573
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WOOTTON Sht: 2
10P64573
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1 E1 M11 J1
- WATCHDOG
C C C C B E2 OPTO 1 CONTACT M12 J2 RELAY 17
+ M13
C B A C B A C B A PHASE ROTATION J3
E3 - WATCHDOG
CONTACT M14 J4 RELAY 18
E4 OPTO 2
+ L1 J5
T1
T4 T3 T2 D24 E5 RELAY 1 L2 J6 RELAY 19
-
A (1) E6 OPTO 3 L3 J7
+
RELAY 2 L4 J8 RELAY 20
D23 E7 -
OPTO 4 L5 J9
E8
D26 + RELAY 3 L6 J10 RELAY 21
E9 - L7
B (1) J11
E10 OPTO 5 RELAY 4
+ L8 J12 RELAY 22
D25
E11 L9 J13
-
D28 OPTO 6 RELAY 5 L10 J14
E12 RELAY 23
+ L11
C (1) J15
E13 - RELAY 6 L12 J16
NOTE 2 D27 OPTO 7
E14 L13
+ J17
T2 RELAY 24
D18 E15 L14 J18
- RELAY 7
P2 A (2) E16 OPTO 8 L15
+ H1
S2 L16
D17 E17 H2 RELAY 25
COMMON L17
E18 CONNECTION RELAY 8 H3
D20 L18
G1 H4 RELAY 26
S1 B (2) - K1
OPTO 9 H5
G2 RELAY 9 K2
D19 + H6 RELAY 27
P1
G3 K3
- H7
D22 OPTO 10 RELAY 10 K4
G4 H8 RELAY 28
+
C (2) K5
G5 - H9
RELAY 11 K6
D21 G6 OPTO 11 H10 RELAY 29
+ K7
T3 H11
F24 G7 RELAY 12 K8
- H12 RELAY 30
P2 A (3) G8 OPTO 12 K9
+ H13
S2 RELAY 13 K10
F23 G9 - H14
K11 RELAY 31
G10 OPTO 13 H15
F26 + RELAY 14 K12
G11 H16
S1 B (3) - K13
OPTO 14 H17
G12 K14 RELAY 32
F25 + RELAY 15 H18
P1
G13 K15
-
F28 OPTO 15 K16
G14
+
C (3) K17
G15 RELAY 16
- K18
F27 G16 OPTO 16
+
T4
F18 G17
COMMON
P2 A (4) G18 CONNECTION
- B1
S2 F17 C1 - OPTO 25 B2
OPTO 17 +
F20 C2
+ B3
-
S1 C3 - OPTO 26
B (4) B4
OPTO 18 +
C4
P1 F19 + B5
-
C5 - OPTO 27
F22 B6
OPTO 19 +
C6
+ B7
C (4) -
C7 - OPTO 28 B8
F21 OPTO 20 +
C8
+ B9
T5 -
F12 C9 - OPTO 29 B10 NOTE 7
OPTO 21 +
A (5) C10 COMMS
+ B11
-
F11 C11 - OPTO 30 B12
OPTO 22 + M17
F14 C12 -
+ B13
- SEE DRAWING
C13 - OPTO 31 EIA485/
B (5) B14 10Px4001
OPTO 23 + KBUS
C14 M18
F13 + B15 + PORT
-
C15 - OPTO 32 M16
F16 B16
OPTO 24 + SCN
C16
+ B17
C (5)
C17 COMMON * M1
COMMON CONNECTION B18 -
F15 AC OR DC
C18 CONNECTION M2 x AUX SUPPLY
+
SEE SHEET 2 FOR NOTES
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/32O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WOOTTON Sht: 1
10P64576
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (32I/32O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WOOTTON Sht: 2
10P64576
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5
B PROTECTED TRANSFORMER B B T1 E1 C1
- -
C C C C B E2 OPTO 1 M11 C2 OPTO 25
+ WATCHDOG +
C B A C B A C B A PHASE ROTATION M12
E3 - CONTACT C3 -
OPTO 2 M13 OPTO 26
E4 WATCHDOG C4
T1 + M14 +
T4 T3 T2 CONTACT
D24 E5 C5
- L1 -
A (1) E6 OPTO 3 C6 OPTO 27
+ RELAY 1 L2 +
D23 E7 L3 C7
- -
E8 OPTO 4 RELAY 2 L4 C8 OPTO 28
D26 + +
L5
E9 - C9 -
B (1) RELAY 3 L6
E10 OPTO 5 C10 OPTO 29
D25 + L7 +
E11 - RELAY 4 L8 C11 -
D28 OPTO 6 OPTO 30
E12 L9 C12
+ +
C (1) RELAY 5 L10
E13 - C13 -
NOTE 2 D27 OPTO 7 L11 OPTO 31
E14 C14
T2 + RELAY 6 L12 +
D18 E15 C15
- L13 -
P2 A (2) E16 OPTO 8 C16 OPTO 32
+ L14 +
RELAY 7
S2 D17 E17 L15 C17
COMMON L16 COMMON
E18 CONNECTION C18 CONNECTION
D20
L17
G1 - RELAY 8 B1 -
S1 B (2) L18
G2 OPTO 9 B2 OPTO 33
D19 + +
P1 K1
G3 - B3 -
RELAY 9 K2
D22 OPTO 10 OPTO 34
G4 K3 B4
+ +
C (2)
G5 - RELAY 10 K4 B5 -
D21 G6 OPTO 11 K5 B6 OPTO 35
+ +
T3 RELAY 11 K6
F24 G7 B7
- -
OPTO 12 K7 OPTO 36
P2 A (3) G8 B8
+ RELAY 12 K8 +
S2 F23 G9 B9
- K9 -
G10 OPTO 13 RELAY 13 K10 B10 OPTO 37
F26 + +
G11 K11 B11
S1 B (3) - -
OPTO 14 RELAY 14 K12 OPTO 38
G12 B12
F25 + +
P1 K13
G13 - B13 -
F28 K14
G14 OPTO 15 RELAY 15 B14 OPTO 39
+ K15 +
C (3)
G15 - K16 B15 -
F27 G16 OPTO 16 K17 B16 OPTO 40
T4 + RELAY 16 +
F18 G17 K18 B17
COMMON J1 COMMON
P2 A (4) G18 CONNECTION B18 CONNECTION
RELAY 17 J2
S2 F17 H1 - J3
H2 OPTO 17
F20 + RELAY 18 J4
H3 - J5
S1 B (4)
OPTO 18 RELAY 19 NOTE 7
H4 J6
F19 + COMMS
P1 J7
H5 -
F22 OPTO 19 RELAY 20 J8
H6
+ J9
C (4)
H7 - RELAY 21 M17
J10 -
F21 H8 OPTO 20
+ J11 SEE DRAWING
T5 EIA485/
F12 H9 RELAY 22 J12 10Px4001
- KBUS
M18
H10 OPTO 21 J13 + PORT
A (5) +
J14 M16
F11 H11 RELAY 23 SCN
- J15
H12 OPTO 22
F14 + J16 * M1
H13 J17 -
B (5) - AC OR DC
RELAY 24 M2 x AUX SUPPLY
H14 OPTO 23 J18 +
F13 +
H15 -
F16 OPTO 24
H16
+
C (5)
H17
F15 COMMON
H18 CONNECTION CASE
EARTH
SEE SHEET 2 FOR NOTES
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
Issue: Revision: Title:
CID007575. INITAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (40I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WOOTTON Sht: 1
10P64577
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL.ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (40I/24O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WOOTTON Sht: 2
10P64577
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
A
P1 P2 P2 P1
A A A MiCOM P645 (PART) MiCOM P645 (PART)
S1 S2 S2 S1
T5 B PROTECTED TRANSFORMER B B T1 E1 J1
- -
C C C C B E2 OPTO 1 M11 J2 OPTO 25
+ WATCHDOG +
C B A C B A C B A PHASE ROTATION M12
E3 - CONTACT J3 -
OPTO 2 M13 OPTO 26
E4 WATCHDOG J4
T1 + M14 +
T4 T3 T2 CONTACT
D24 E5 J5
- L1 -
A (1) E6 OPTO 3 J6 OPTO 27
+ RELAY 1 L2 +
D23 E7 - L3 J7 -
E8 OPTO 4 RELAY 2 L4 J8 OPTO 28
D26 + +
L5
E9 - J9 -
B (1) RELAY 3 L6
E10 OPTO 5 J10 OPTO 29
D25 + L7 +
E11 - RELAY 4 L8 J11 -
D28 OPTO 6 OPTO 30
E12 L9 J12
+ +
C (1) RELAY 5 L10
E13 - J13 -
NOTE 2 D27 OPTO 7 L11 OPTO 31
E14 J14
T2 + RELAY 6 L12 +
D18 E15 J15
- L13 -
P2 A (2) E16 OPTO 8 J16 OPTO 32
+ L14 +
RELAY 7
S2 D17 E17 L15 J17
COMMON L16 COMMON
E18 CONNECTION J18 CONNECTION
D20
L17
G1 - RELAY 8 C1 -
S1 B (2) L18
G2 OPTO 9 C2 OPTO 33
D19 + +
P1 K1
G3 - C3 -
RELAY 9 K2
D22 OPTO 10 OPTO 34
G4 K3 C4
+ +
C (2)
G5 - RELAY 10 K4 C5 -
D21 G6 OPTO 11 K5 C6 OPTO 35
+ +
T3 RELAY 11 K6
F24 G7 C7
- -
OPTO 12 K7 OPTO 36
P2 A (3) G8 C8
+ RELAY 12 K8 +
S2 F23 G9 C9
- K9 -
G10 OPTO 13 RELAY 13 K10 C10 OPTO 37
F26 + +
G11 K11 C11
S1 B (3) - -
OPTO 14 RELAY 14 K12 OPTO 38
G12 C12
F25 + +
P1 K13
G13 - C13 -
F28 K14
G14 OPTO 15 RELAY 15 C14 OPTO 39
+ K15 +
C (3)
G15 - K16 C15 -
F27 G16 OPTO 16 K17 C16 OPTO 40
T4 + RELAY 16 +
F18 G17 K18 C17
COMMON COMMON
P2 A (4) G18 CONNECTION B1 C18 CONNECTION
-
S2 F17 H1 OPTO 41 B2
- +
H2 OPTO 17
F20 + - B3
H3 OPTO 42 B4
S1 B (4) - +
H4 OPTO 18
+ - B5
P1 F19
H5 OPTO 43 B6 NOTE 7
- + COMMS
F22 OPTO 19
H6 B7
+ -
C (4) OPTO 44
H7 - B8
+
F21 H8 OPTO 20
+ - B9
T5 M17
F12 H9 OPTO 45 -
- B10
+ SEE DRAWING
A (5) H10 OPTO 21 EIA485/
+ - B11 10Px4001 KBUS
OPTO 46 M18
F11 H11 - B12 + PORT
+
H12 OPTO 22 M16
F14 + - B13
SCN
H13 OPTO 47 B14
B (5) - +
H14 OPTO 23 * M1
+ - B15 -
F13 AC OR DC
H15 OPTO 48 B16 M2 x AUX SUPPLY
- + +
F16 OPTO 24
H16 B17
+
C (5) COMMON
H17 B18
COMMON CONNECTION
F15 H18 CONNECTION

SEE SHEET 2 FOR NOTES CASE


EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


Issue: Revision: Title:
CID007575. INITIAL ISSUE EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (48I/16O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WOOTTON Sht: 1
10P64578
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may Next
Date: Chkd: be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK. Sht: 2 Stafford.
ST16 1WT, UK.
A A
A
B B
B
C C
A B C A B C C
A B C

MiCOM P645 (PART) N N


NOTE 7 NOTE 4
n n

VA
a b c a b c VA
D2 D2 a b c

D1 D1

D4 VB D4 VB

OPTIONAL
D3 D3
NOTE 6

F2 VC F2 VC

NOTE 8
F1 VN F1 VN

F4

VFLUX VEE CONNECTED VTs (ALTERNATIVE)


F3 NOTES:

1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.


GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
TV LV HV (c) PIN TERMINAL (P.C.B. TYPE)
NOTE 3
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. BIAS INPUT 1
S2 P2 IS ALWAYS AN HV WINDING CONNECTION.
3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.

D12 TN3 S1 P1 4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.


(USED BY V/Hz W2 PROTECTION ONLY).
Y (TV) S2 P2
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
D11
6. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
D14 TN2 S1 P1
7. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
Y (LV) S2 P2 (USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
Y (HV) FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.

D15

Issue: Revision: Title:


CID007575. INITIAL ISSUE. EXTERNAL CONNECTION DIAGRAM 5 BIAS INPUT TRANSFORMER
A DIFFERENTIAL WITH 4 POLE VT INPUTS (48I/16O) 80TE
GE Vernova PROPRIETARY AND CONFIDENTIAL INFORMATION Drg GE VERNOVA
Date: 02/10/2023 Name: S WOOTTON Sht: 2
10P64578
This document is the property of GE Vernova and contains proprietary information of GE Vernova. This document is loaned on the express condition that No:
C
UK Grid Solutions Ltd
St Leonards Building,
neither it nor the information contained therein shall be disclosed to others without the express written consent of GE Vernova, and that the information shall
Harry Kerr Drive,
Date: Chkd:
be used by the recipient only as approved expressly by GE Vernova. This document shall be returned to GE Vernova upon its request. This document may
be subject to certain restrictions under U.S. export control laws and regulations. © GE Vernova, GE VERNOVA CONFIDENTIAL UNPUBLISHED WORK.
Next - Stafford.
Sht: ST16 1WT, UK.
APPENDIX D

VERSION HISTORY
Appendix D - Version History P64

648 P64-TM-EN-1
1 HARDWARE AND SOFTWARE VERSION HISTORY

S/W S/W
H/W Original Technical
Version Version Description of Changes S1 Compatibility Documentation
Version Date of Issue
Major Minor

First release of MiCOM 5th Generation transformer protection. Relay models:


P642/3/5 are released based on software 91. The main changes in this new
hardware and software release are as follows:
 A 10x performance increase in processing power over the previous Generation (4th
Gen)
 Colour graphical HMI available as standard, and with native USB support. It
includes 1 configurable page, for SLD, measurements and status signals
 Any model can be ordered in the 3 size cases: 40TE (W 203.2 mm or 8”), 60TE
(W 304.8 mm or 12”) or 80TE (W 406.4 mm or 16”), with a variation in the number
of I/O
 PRP, HSR and RSTP supported in the same order option
 CyberSentry IEC 62351-8
 5000 Events, 100 Faults, 1050s Oscillography and 128 Digital Signals
 Compliance to IEC 61850 Edition 2.1
 Support for IEC 61850 Substitution - data points for status and measurement can MiCOM S1 Agile v3.0.1
AB - Q August 2024 be substituted P64-TM-EN-1
or later
 Time Synchronization modelled in new LN LTIM/LTMS
 Support for Alarm Handling new LN CALH
 Ethernet port link status via new LN LCCH and new DDBs
 Top-down engineering - configuration of P40 including GOOSE from SCD file
 Configurable RCB name and GCB name
 Multi-level control, new DO MltLev - select local or remote for control. To comply
to local and remote requirements
 Secure Event Logging aligned to IEC 62351-14 - separate audit log for security
operations and Syslog updated to align with IEC 62351-14
 Implementation of secure SSH (Secure Shell) communication to the relay from S1
Agile for configuration over Ethernet
 New Ethernet board - 1-2 Station Bus ports + Engineering port (CORTEC Hardware
Option U/V/W/Y)
 Increased execution speed for REF. Trip time improved from 45 to 30ms at 2xIs
2 SOFTWARE VERSION COMPATIBILITY

IED S/W
Setting File Version Menu Text File Version*8 PSL File Version
Version

AB AB AB AB

Notes:
*1: Compatible except for Disturbance recorder digital channel selection
*2: Additional functionality added such that setting files from earlier software versions will need additional settings to be made
*3: Compatible except for Disturbance recorder digital channel selection & settings for additional functionality will be missing
*4: Compatible except for the Disturbance recorder digital channel selection and the distance settings
*5: Compatible except for Disturbance recorder digital channel selection & the setting file contains a large number of Distance setting which will each produce an error on
download
*6: Additional DDBs were added such that PSL files from earlier software versions will not be able to access them
*7: Additional DDB for the Distance protection will not be included
*8: Menu text remains compatible within each software version but is NOT compatible across different versions
© 2025 GE Vernova. All rights reserved. Information contained in this document is indicative only. No representation or
warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend
on the technical and commercial circumstances. It is provided without liability and is subject to change without notice.
Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

You might also like