0% found this document useful (0 votes)
21 views2 pages

02 16001 04 en

The document provides installation instructions and safety information for the SpaceLogic™ TB-PS-W1 Terminal Base, emphasizing that only qualified personnel should handle the equipment. It includes technical specifications, wiring details, and compliance warnings, particularly regarding electrical shock hazards. Additionally, it contains a California Proposition 65 warning about potential exposure to harmful chemicals.

Uploaded by

Aneta Deliu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views2 pages

02 16001 04 en

The document provides installation instructions and safety information for the SpaceLogic™ TB-PS-W1 Terminal Base, emphasizing that only qualified personnel should handle the equipment. It includes technical specifications, wiring details, and compliance warnings, particularly regarding electrical shock hazards. Additionally, it contains a California Proposition 65 warning about potential exposure to harmful chemicals.

Uploaded by

Aneta Deliu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Installation Sheet 02-16001-04-en, May 2021 | 1

SpaceLogic™ TB-PS-W1
Terminal Base
Regulatory Compliance and Safety Information
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
Carefully read these instructions and all information relevant for this product before trying to install it. See the list of technical literature.
The technical literature and declarations of conformity can be accessed on the Schneider Electric Exchange website, ecobuilding.schneider-
electric.com. Contact your local Schneider Electric sales office for a hard copy of the documentation or for additional information.

Technical Literature
• SpaceLogic Hardware Reference Guide, 04-XX001-XX-en
• EcoStruxure Building Management - Smoke Control System Design Guide, 04-16014-XX-en

Dimensions Overview

Connecting the Next Terminal Base


Installing the Terminal Base
WARNING
HAZARD OF ELECTRIC SHOCK OR EQUIPMENT DAMAGE
Ensure that the module type and the terminal base type match.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.

NOTE: Install the terminal base on a horizontal DIN rail. This


position provides proper cooling air flow through the electronics
module.
02-16001-04-en, May 2021 | 2

I/O Bus Addressing, Power Limits, and Cables Wiring


Recommended screw tightening torque: 0.56 Nm (5 lbf.in)

Terminal Base and Electronics Module


Device Part number

TB-PS-W1 Terminal Base SXWTBPSW110001

PS-24V Power Supply SXWPS24VX10001

S-Cables
Device Part number

S-Cable, 1.5 m, angle SXWSCABLE10002

S-Cable, 0.75 m, angle SXWSCABLE10003

Smoke Control Application Note


Connections The input power terminals are power-limited per UL 864
requirements. For more information on the use of the PS-24V power
supply for a UL 864 smoke control application, see the latest
version of the EcoStruxure Building Management - Smoke Control
System Design Guide (04-16014-XX-en).

Specifications
AC input DC output Mechanical
Nominal voltage Output voltage Ingress protection rating
24 VAC 50/60 Hz 24 V ±1 V IP 20
Recommended transformer rating Output power Plastic flame rating
≥60 VA max. 30 W UL94-5VB
DC input Operation environment Electrical
Nominal voltage Ambient temperature, operating I/O bus power
24 VDC 0 to 50 °C (32 to 122 °F) 24 VDC max. 30 W per I/O bus power
Power consumption Humidity supply, Class 2
max. 40 W Maximum 95 % RH non-condensing Maximum addresses per I/O bus
32

Addendum - California Proposition 65 Warning Statement for California Residents


WARNING: This product can expose you to chemicals including lead which is known to the State of California
to cause cancer and which is known to the State of California to cause birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov

© 2021 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.