Installation Sheet 02-16002-04-en, May 2021 | 1
SpaceLogic™ PS-24V
Power Supply
Regulatory Compliance and Safety Information
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
Carefully read these instructions and all information relevant for this product before trying to install it. See the list of technical literature.
The technical literature and declarations of conformity can be accessed on the Schneider Electric Exchange website, ecobuilding.schneider-
electric.com. Contact your local Schneider Electric sales office for a hard copy of the documentation or for additional information.
Technical Literature
• SpaceLogic Hardware Reference Guide, 04-XX001-XX-en
• EcoStruxure Building Management - Smoke Control System Design Guide, 04-16014-XX-en
Dimensions
Installing the Module Labeling the Module
WARNING
HAZARD OF ELECTRIC SHOCK OR EQUIPMENT DAMAGE
Install only the module type that is indicated on the label on the
terminal base backplane.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.
02-16002-04-en, May 2021 | 2
Smoke Control Application Note Electronics Module and Terminal Base
The input power terminals are power-limited per UL 864 Device Part number
requirements. For more information on the use of the PS-24V power
supply for a UL 864 smoke control application, see the latest PS-24V Power Supply SXWPS24VX10001
version of the EcoStruxure Building Management - Smoke Control
System Design Guide (04-16014-XX-en). TB-PS-W1 Terminal Base SXWTBPSW110001
Specifications
AC input DC output Mechanical
Nominal voltage Output voltage Ingress protection rating
24 VAC 50/60 Hz 24 V ±1 V IP 20
Recommended transformer rating Output power Plastic flame rating
≥60 VA max. 30 W UL94-5VB
DC input Operation environment Electrical
Nominal voltage Ambient temperature, operating I/O bus power
24 VDC 0 to 50 °C (32 to 122 °F) 24 VDC max. 30 W per I/O bus power
Power consumption Humidity supply, Class 2
max. 40 W Maximum 95 % RH non-condensing Maximum addresses per I/O bus
32
Addendum - California Proposition 65 Warning Statement for California Residents
WARNING: This product can expose you to chemicals including lead which is known to the State of California
to cause cancer and which is known to the State of California to cause birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov
© 2021 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
www.se.com/buildings