Concrete
Concrete
By
William Nickelson
Ruben Jerves
Christopher Motter, co-PI
Adam Phillips, co-PI
for
May 2022
i
Acknowledgments
This report is based on a thesis by William Nickelson in partial fulfillment of the requirements
for a M.S. degree from Washington State University. This research was sponsored by the
State University and by the U.S. Department of Transportation. This support is gratefully
acknowledged. Simpson Strong Tie (SST) is thanked for providing in-kind donations of fiber
reinforced polymer and resin, in addition to installation of the steel jackets used in the test
columns. Nucor is thanked for in-kind donations of Grade 40 reinforcement used in the test
columns. Scott Lewis, Joshah Jennings, Levi Arnold, and Roshan Ghimire are thanked for
Disclaimer
The contents of this report reflect the views of the authors, who are responsible for the facts and
the accuracy of the information presented. This document is disseminated under the sponsorship
of information exchange. The U.S. Government assumes no liability for the contents or use
thereof.
ii
Table of Contents
Acknowledgments........................................................................................................................... ii
Disclaimer ....................................................................................................................................... ii
1. Introduction ................................................................................................................................. 3
2. Literature Review........................................................................................................................ 8
3. Column Testing......................................................................................................................... 12
3.2.2. Load-Deformation....................................................................................................... 52
5. Conclusions ............................................................................................................................... 90
References ..................................................................................................................................... 93
iv
List of Figures
Figure 3.2: General Footing Reinforcement Details (10-#7 Starter Base Depicted) (Dimensions
in Inches)....................................................................................................................................... 15
Figure 3.3: Footing Sleeve Details (10-#7 Starter Bars Depicted) (Dimension in Inches) .......... 16
Figure 3.6: Construction: a) Bracing for Column Concrete Pour, and b) Bracing for Top Block
Concrete Pour................................................................................................................................ 20
First Excursion to Exceed Value, Photo Depicts 7.3 δ/δy Excursion:a) C(CFRP)-4.0-#7(1.3)-
v
0.05, b) C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-
First Excursion to 7.3 δ/δy in the Negative Direction is Depicted. For C(CFRP)-4.0-#7(2.7)-0.05
vi
#5(1.4)-0.05, c) C(CFRP)-4.0-#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-
f) C(CFRP)-4.0-#7(1.3)-0.15 ........................................................................................................ 44
Depiction of the East Face was Available. For C(CFRP)-4.0-#5(1.4)-0.05 Only a Depiction of
the West Face was Available. For C(CFRP)-4.0-#7(1.3)-0.05-EQ Only a Depiction of the West
4.0-#7(1.3)-0.15 ............................................................................................................................ 45
Only a Depiction of the East Face was Available. For C(CFRP)-4.0-#5(1.4)-0.05 Only a
Depiction of the West Face was Available. For C(CFRP)-4.0-#7(1.3)-0.05-EQ Only a Depiction
vii
C(CFRP)-4.0-#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-2X,
f) C(CFRP)-4.0-#7(1.3)-0.15 ........................................................................................................ 47
Figure 3.27. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.05: a) Base Shear, b) Effective
Figure 3.28. Backbone Model Fit for C(CFRP)-4.0-#5(1.4)-0.05: a) Base Shear, b) Effective
Figure 3.29. Backbone Model Fit for C(CFRP)-4.0-#7(2.7)-0.05: a) Base Shear, b) Effective
Figure 3.30. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.05-EQ: a) Base Shear, b) Effective
Figure 3.31. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.05-2X: a) Base Shear, b) Effective
Figure 3.32. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.15: a) Base Shear, b) Effective
#5(1.4)-0.05................................................................................................................................... 69
viii
Figure 3.38. Strain Measured in Longitudinal Reinforcement at Cycle Peaks, C(CFRP)-4.0-
#7(2.7)-0.05................................................................................................................................... 69
#7(1.3)-0.05-EQ ............................................................................................................................ 70
#7(1.3)-0.05-2X ............................................................................................................................ 70
#7(1.3)-0.15................................................................................................................................... 71
f) C(CFRP)-4.0-#7(1.3)-0.15 ........................................................................................................ 73
....................................................................................................................................................... 76
....................................................................................................................................................... 77
e) C(CFRP)-4.0-#7(1.3)-0.15 ........................................................................................................ 80
ix
Figure 4.1. Column Deformation Model ...................................................................................... 83
Figure 4.2. Column Load-Deformation Response for Model and Tests: a) C(CFRP)-4.0-#7(1.3)-
x
List of Tables
Table 2.1: Parameters of Past Tests on Reinforced Concrete Circular Bridge Columns Retrofitted
Table 3.2: Measured Properties of Steel Reinforcement Obtained from Tensile Testing ............ 21
Table 3.3: Footing Concrete Compressive Strength from Cylinder Testing ............................... 22
Table 3.4: Column Concrete Compressive Strength from Cylinder Testing ................................ 23
xi
Executive Summary
Many bridges in the western United States, including those built for the Interstate Highway
System in the 1950s and 1960s, have seismically vulnerable reinforced concrete (RC) columns.
bridges are relied upon as critical lifelines into urban centers after natural disasters. Some states,
including California and Washington, have introduced retrofit programs to enhance the seismic
ductility of vulnerable columns. The retrofit involves wrapping the column with either a
structural steel or fiber reinforced polymer (FRP) jacket, which enhances the deformation
capacity of the column to improve the seismic performance. Previous research on jacketed
This research was focused on characterization of the behavior of FRP jacketed bridge columns
under long-duration earthquakes. Six tests were conducted on cantilever bridge columns with
FRP jackets at the base. The FRP jackets were 0.40” and extended over a height of one column
diameter. The FRP had specified strength of 128-ksi and elastic modulus of 14.2ksi in the
circumferential direction. Test variables for the columns included longitudinal reinforcement
ratio, longitudinal bar diameter, axial load ratio, and loading protocol. All tested columns had
lateral deformation capacity of at least 6% drift, with lateral deformation capacity considered to
occur at 20% strength loss. Axial failure was not achieved in any of the test columns, and the
tests were stopped after multiple cycles at 10% drift. Five of the six test columns were nominally
identical to a set of previously tested columns with FRP jackets. The lateral deformation capacity
1
of each column with an FRP jacket met or exceeded that of the equivalent column with a steel
jacket.
A model was formulated to predict the deformation capacity of FRP jacketed columns. The
model included a column model followed by a fatigue model to estimate bar fracture. The
column was modeled in OpenSees using an elastic beam column element over the height of the
column, with two zero-length bond slip elements at the base. The two elements represented bond
slip of longitudinal reinforcement from the footing and from the jacketed column. The OpenSees
model was run to determine the stress-strain history in the outermost longitudinal reinforcement.
The strain history was used in a fatigue model to predict the drift at fracture of the first
longitudinal bar. The modeling approach was validated to test data from the experimental study.
The model was used to estimate the deformation capacity of FRP jacketed bridge columns.
2
1. Introduction
Significant damage to reinforced concrete bridge columns was observed following the 1971 San
understanding of the design issues, and, in 1983, AASHTO issued new bridge design guidelines
with changes aimed at addressing the issue of nonductile bridge columns in new construction.
The seismic vulnerabilities of pre-1971 bridge columns were again exposed by the 1989 Loma
Prieta, CA (NIST, 1990; EERI, 1990) and 1994 Northridge, CA earthquakes (EERI, 1994;
Buckle, 1994). Based on the damage observed in these earthquakes and research on the topic, it
is clear that there is a need for seismic retrofit of pre-1971 reinforced concrete bridge columns in
areas of high seismicity. Many bridges in the U.S. were constructed prior to 1971, including state
bridges constructed in the 1950s and 1960s as part of the national Interstate Highway System.
These bridges represent important lifelines for cities in the aftermath of a large earthquake.
Deficiencies in pre-1971 reinforced concrete bridge columns include insufficient lap splice
lengths of 20 times the longitudinal reinforcement diameter (i.e., 20db), inadequate shear
strength, and inadequate flexural ductility due to insufficient transverse reinforcement (typically
#4 hoops at 12” hoops) (Chai et al, 1991). Initial research on retrofit of seismically deficient
bridge columns focused on the use of steel jackets (Chai et al, 1991; Priestley et al, 1994a,b), and
this research led to field implementation in Washington and California. For circular columns, the
3
jackets were typically installed by seam welding two half-plates of semi-circular cross-section.
The jackets were oversized, and the gap that was left between the jacket and the column, which
was typically 1-2”, was filled with grout. For rectangular columns, the jackets were elliptical,
and concrete was used to fill the voids between the jacket and the column. If enhancement to
column shear strength was needed to prevent shear failure, the jackets were provided over the
full height of the column. Alternatively, the jackets were provided only in plastic hinge zones
(i.e., at the base of the column for cantilevers, and at the top and the bottom of the column for
fixed-fixed columns) if enhancement to shear strength was not needed. In this case, the jackets
can provide adequate confinement to prevent splice failure of 20db lap splices and to prevent
crushing of concrete. A small gap (~2”) was left between the base of the steel jacket and the
footing in order to avoid contact that would allow load transfer between the footing and the
Recommendations on steel jacket design are provided in the FHWA guidelines (2006) and stem
from research (Chai et al, 1991; Priestley et al, 1994a,b). The recommendations specify the
jacket thickness needed to prevent concrete crushing or splice failure. If these failure modes are
avoided, fatigue failure of longitudinal reinforcement is expected to occur at the gap between the
bottom of the steel jacket and the top of the footing. Chai et al (1991) determined that load
sharing was occurring between the steel jacket and the column, such that the jacket provided an
enhancement to flexural strength. The enhancement to flexural strength limited the spread of
plasticity, and Chai et al (1991) recommended that the zone of plasticity (i.e., plastic hinge
length) could be modeled as being equal to the gap length between the jacket and the footing
plus bond slip of the longitudinal reinforcement into the footing and into the steel jacket.
4
Much of the research on steel jackets was conducted in the 1990s, at a time when steel jackets
were a more cost-efficient option relative to fiber reinforced polymer (FRP). FRP has become
less cost inhibitive with time, and the use of FRP jackets is particularly beneficial in cases where
a steel jacket retrofit may be inadequate. FRP jackets may offer an advantage over steel jackets
by better accommodating the vertical spread of plasticity, which may be achieved by orienting
the FRP fibers in the circumferential direction. The improved spread of plasticity leads to a
larger plastic hinge length. This means that for a given curvature demand at the base of the
column, the FRP jacket accommodates a larger deformation capacity than the steel jacket,
leading to a reduced collapse likelihood in earthquakes. Previous research has not focused on the
behavior of FRP jacketed columns in long duration earthquakes. Existing models to predict the
deformation capacity of FRP jacket retrofitted columns based on fatigue failure of reinforcement
do not exist.
1.2. Objectives
The first objective of the research was to experimentally assess the deformation capacity of FRP
jacketed bridge columns, with properties characteristic of Washington State bridges, subjected to
Cascadia Subduction Zone earthquake demands. The second objective was to formulate a model
to determine the deformation capacity of FRP jacket retrofitted bridge columns. The model was
intended to be suitable for use in nonlinear time history analyses, making it a suitable tool for
analyzing the behavior of FRP jacket retrofitted bridge columns in a given earthquake ground
5
motion. The data needed for model calibration/validation was generated from the experimental
program. Six approximately one-half-scale to two-thirds-scale bridge columns with FRP jacket
retrofits were constructed and tested. The test program was intended to address gaps from
previous studies by including the range of practical parameters that influence column
deformation capacity. A lumped plasticity model for the retrofitted columns was developed and
validated with experimental results. In this model, deformation capacity was based on fatigue
fracture of reinforcement.
Results from testing of FRP jacketed columns were used to provide an assessment of the
deformation capacity of WSDOT bridge columns in Cascadia Subduction Zone earthquakes. The
tests produced a unique dataset for FRP jacketed columns subjected to long duration earthquake
demands that may be used for model calibration/validation. The model formulated in this study
was validated to this data. This model may be used to assess the failure probability of any FRP
jacket retrofitted bridge column for a given earthquake ground motion, making it a useful tool to
aid in the design of FRP retrofits. This study addresses TriDurle research thrust #5: Addressing
natural hazards and extreme disaster events that threaten the durability and service life of
transportation infrastructure.
6
1.4. Report Overview
This report includes five chapters and a list of references. An introduction is provided in Chapter
Chapter 3, which included two subsections. An overview of the experimental program was
provided in the first subsection. This included methods of construction, testing, and material
properties. Test results were provided and discussed in the second subsection. This included a
Chapter 4, which also included two subsections. A description of the column model was
provided in the first subsection, with model validation described in the second subsection. A
summary and list of conclusions are provided in Chapter 5. A list of references follows Chapter
5.
7
2. Literature Review
A number of previous experimental studies have been conducted on circular reinforced concrete
columns with FRP jackets. Xiao and Ma (1997) tested three columns that had longitudinal
reinforcement at the base of the column with lap splice lengths of 20 times the bar diameter. Two
of the three columns were retrofit with FRP jackets prior to testing. The unretrofitted column
failed due to lap splice failure at low ductility. This column was repaired, retrofit with FRP, and
tested again. For all three retrofitted columns, the level of confinement provided by the jackets
was such that bond failure occurred gradually, allowing for ductility demands in the range of
four to six at 20% loss of lateral load-carrying capacity. Xiao and Ma (1997) used the test results
to develop and validate a deformation capacity model that accounted for the influence of
Haroun and Elsanadedy (2005a,b) conducted tests on FRP jacketed circular columns that also
had lap splice lengths of 20 times the longitudinal bar diameter. The jackets used were such that
the reported failure occurred due to concrete crushing or longitudinal bar buckling rather than
bond. Similar failure modes were reported for the tests of Ghosh and Sheikh (2007).
For FRP jacket retrofit of reinforced concrete bridge columns, failure may occur due to concrete
thickness based on the Mander et al (1988) confined concrete model, which is reflected in the
8
FHWA guidelines (2006). It is shown in Section x on column modeling that for cases in which
reinforcement fatigue fracture governs failure, the parameters that impact column deformation
capacity are the neutral axis depth (influenced by the axial load ratio and longitudinal
reinforcement ratio), plastic hinge length (influenced by the longitudinal bar diameter and
column diameter), and the loading history. Systematic variation of these parameters is not
evident from the summary of previous tests provided in Table 1, and the proposed experimental
Previous experimental programs (Xiao and Ma, 1997; Haroun and Elsanadedy, 2005a,b; Ghosh
and Sheikh, 2007; Breña and Schlick, 2007) used loading protocols that were developed using
strike-slip earthquake ground motions (e.g., Krawinkler, 1992). Subduction zone earthquakes
produce longer duration ground motions than strike-slip earthquakes, which results in greater
cumulative plastic deformation in flexure-yielding components and the increased potential for
fatigue failure. The USGS has recently released updated hazard maps that require increased
levels of seismicity for structural design in regions affected by the Cascadia Subduction Zone
(CSZ). These new maps reflect the geologic evidence indicating that the CSZ is capable of
producing M9 megathrust earthquakes at the interface between the Juan de Fuca and North
American plates (Atwater et al. 1995). Such an event has a 10-14% chance of occurring in the
next 50 years (Goldfinger et al. 2012). In an M9 CSZ earthquake, strong ground shaking is
expected in Washington, Oregon, northern California, and Alaska. Due to the lack of an accurate
metric to assess the deformation capacity of FRP jacket retrofitted columns, there is uncertainty
earthquakes. The proposed research will result in the development of a new model that may be
9
used to determine if and when a FRP jacketed bridge column fails under a specific seismic
demand, such as a CSZ-type ground motion. The model will be calibrated/validated using test
data generated through an experimental study on FRP jacketed columns. The tests are expected
to generate a unique dataset for model calibration relative to data that is available from previous
tests. Specifically, the columns will be tested under loading protocols reflective of long-duration
earthquakes. Past experimental studies on RC columns with FRP jackets (Xiao and Ma, 1997;
Haroun and Elsanadedy, 2005a,b; Ghosh and Sheikh, 2007; Breña and Schlick, 2007) have not
the level of FRP confinement used for the test columns in the proposed study will be higher than
that typically used in previous studies. In previous studies, failure typically occurred due to
confinement and increased cycle content for the columns in the proposed study is expected to
produce fatigue failure of reinforcement. Furthermore, direct comparison between steel jackets
and FRP jackets has not been considered in an experimental study that isolates this test variable.
To address this shortcoming, the six FRP jacketed columns tested as part of the proposed
research were identical to a set of six steel jacketed columns tested by the P.I.’s as part of a study
funded by WSDOT.
10
Table 2.1: Parameters of Past Tests on Reinforced Concrete Circular Bridge Columns
Retrofitted with FRP Jackets
Total
Longitudinal Shear Lap Splice
Axial Load Diameter Longitudinal FRP FRP FRP Elastic
Specimen Steel Area/ Span Ratio Length /
Experimental Program Ratio, or Bar Diameter Thickness Ultimate Modulus
Name Gross (M /VD or Longitudinal
P/(Agf'c) Length (inches) (inches) Stress (ksi) (ksi)
Concrete M/VL) Bar Diameter
Area
Xiao and Ma (1997) C2-RT4 0.0195 0.050 24 4 0.75 20 0.5 80 7000
Haroun and Elsanadedy (2005a) CF-R1 0.0195 0.061 24 6 0.75 20 0.028 604 33568
Haroun and Elsanadedy (2005a) CF-R2 0.0195 0.060 24 6 0.75 20 0.028 642 33365
Haroun and Elsanadedy (2005a) CF-R3 0.0195 0.067 24 6 0.75 20 0.449 108 5293
Haroun and Elsanadedy (2005a) CF-R4 0.0195 0.059 24 6 0.75 20 0.067 635 32770
Haroun and Elsanadedy (2005a) CF-R5 0.0195 0.056 24 6 0.75 20 0.5 93 5278
Haroun and Elsanadedy (2005a) CF-R6 0.0195 0.067 24 6 0.75 20 0.327 136 9135
Haroun and Elsanadedy (2005b) CS-R1 0.0195 0.054 24 2 0.75 20 0.028 604 33568
Haroun and Elsanadedy (2005b) CS-R2 0.0195 0.056 24 2 0.75 20 0.028 642 33365
Haroun and Elsanadedy (2005b) CS-R3 0.0195 0.065 24 2 0.75 20 0.406 61 2683
Haroun and Elsanadedy (2005b) CS-R4 0.0195 0.059 24 2 0.75 20 0.047 181 15051
Ghosh and Sheikh (2007) CAF1-2N 0.0172 0.050 14 5.65 0.75 24.67 0.04 148 11458
Ghosh and Sheikh (2007) CAF1-5N 0.0172 0.270 14 5.65 0.75 24.67 0.04 148 11458
Ghosh and Sheikh (2007) CBF1-6N 0.0172 0.050 14 5.65 0.75 24.67 0.04 148 11458
Brena Schlick (2007) CFRP-05 0.0254 0.050 9.5 4.5 0.5 24 0.0065 550 33000
Brena Schlick (2007) KFRP-05 0.0254 0.050 9.5 4.5 0.5 24 0.011 290 17400
Brena Schlick (2007) CFRP-15 0.0254 0.150 9.5 4.5 0.5 24 0.0065 550 33000
Brena Schlick (2007) KFRP-15 0.0254 0.150 9.5 4.5 0.5 24 0.011 290 17400
11
3. Column Testing
3.1. Methodology
Each test specimen consisted of a column, a footing, and a loading head. A test matrix for the six
test columns is provided in Table 3.1, with drawings of the columns provided in Figure 3.1. The
test columns were nominally identical to those tested by McGuiness (2021), except that carbon
fiber reinforced polymer (CFRP) jackets were used in place of steel jackets. The reinforced
concrete column parameters matched those tested by McGuiness (2021), except that C(S)-6.0-
#7(1.3)-0.05, the tallest column in the McGuiness (2021) study, was replaced by a column with
ratio, axial load ratio, and loading protocol. Design parameters among the test columns are
column with CFRP jacket in “C(CFRP)”, with a “4.0” span to depth ratio (H/D = 4.0), using
“#7” longitudinal reinforcement with 1.3% longitudinal reinforcement ratio (As/Ag = 0.013), and
5% axial load ratio (P/(f’cAg) = 0.05). A fully reversed cyclic loading protocol was used for five
More details on the loading protocols are provided in Section 3.6. The columns were tested as
cantilevers, and the column height, H, was the measured distance from the top of footing to the
12
line of action of the applied lateral load. The height of the circular column section was 9” less
than H to facilitate inclusion of the loading head. Column diameter, D, was 24”. All test columns
had nominally identical 1” clear cover, cb, Grade 40 longitudinal and transverse reinforcement,
and #3 hoops with a lap-splice length, lb, of 16” and center-to-center vertical spacing, s, of 8”
splices.
The footing and loading head were consistent with those used in the McGuiness (2021) tests,
with details provided in Figure 3.2 and Figure 3.3. C(CFRP)-4.0-#7(1.3)-0.05-2X, which did not
have an equivalent test in the McGuiness (2021) study, had the same footing as C(CFRP)-4.0-
#7(1.3)-0.05. Voids were provided in the footing using SCH40 PVC pipe, located as shown in
Figure 3.3, to allow the footing to be post-tensioned to the laboratory strong floor and to
facilitate lifting and moving of the test specimens before and after testing.
The CFRP jackets were designed to provide a level of confinement stiffness that was greater than
that provided by the 3/16” steel jackets used in the columns tested by McGuiness (2021). The
specified CFRP modulus of elasticity was 14,200 ksi in the CFRP direction that was oriented
circumferentially around the columns. Five sheets of 0.08” thick CFPR were used, resulting in a
thickness of 0.40”, which provides circumferential stiffness of 14,200 ksi * 0.40” = 5,680 k/in
relative to 29,000 ksi * 0.1875” = 5,437.5 k/in for the steel jacket. The CFRP jackets were used
over the lower 24” inches of the column, which is the column diameter. The steel jackets used in
the columns tested by McGuiness spanned the full circular portion of the column, with the
13
Table 3.1: Test Matrix
Long. #
Loading
Column I.D. Bar Long. 𝐴𝑠 /𝐴𝑔 𝑃/(𝐴𝑔 𝑓𝑐′ ) 𝐻/𝐷
Protocol
Size Bars
14
Figure 3.2: General Footing Reinforcement Details (10-#7 Starter Base Depicted) (Dimensions
in Inches)
15
Figure 3.3: Footing Sleeve Details (10-#7 Starter Bars Depicted) (Dimension in Inches)
Each column was constructed in two pours, with a cold joint at the base of the column.
Formwork consisted of 3/4 CDX plywood, 2” x 4” framing lumber, and tubular forms, made
from heavy cardboard, for the circular portion of the column. Six sets of forms were constructed,
as depicted in Figure 3.4a, to enable pouring from the same load of concrete. Footing
reinforcement cages were tied externally prior to being placed inside the formwork. Column
starter bars were tied to footing reinforcement while located within the column cross-section
16
using plywood drilled holes for the bars. Strain gauges in the footing concrete were wired away
from the footing-column interface. Further description of the strain gauge layout is provided in
Section 3.5. Vertical PVC sleeves were precisely located in the footing to match the pattern in
the strong floor. Formwork heights allowed direct tailgate delivery of ready-mix concrete for the
footing. The cold joint between the footing and subsequent column pour was intentionally
roughened to magnitudes greater than ¼-in. The remaining exposed footing surfaces were
troweled to a smooth uniform finish. Column reinforcement cages where tied horizontally.
After completion of the footing pours, the column cages were rotated into the vertical position,
and affixed to the footing starter bars with contact lap splices of longitudinal reinforcement to
starter bars. Spacers were installed on reinforcement, and column forms were then installed by
lowering from above. Proper vertical alignment of column forms was provided by timber bracing
between the top of the forms to ground level brace points, as depicted in Figure 3.5a. The wires
of strain gauges cast into the column, similar to the footing, were routed away from the footing-
column interface. Top block formwork was supported by the column formwork and at ground
level. Top block transverse reinforcement was tied to column longitudinal reinforcement, and
PVC sleeves were installed within top block formwork, as depicted in Figure 3.6b. Due to
height, the delivery and placement of concrete to the column formwork required the assistance of
a concrete boom truck pump and 12-ft drop hose. Concrete was pumped incrementally, with
periodic pauses to raise the pump hose and facilitate vibratory consolidation of the concrete. The
exposed top surface was trowel finished. After the appropriate cure time, formwork was
17
Several months after column construction, CFRP jackets were installed by a professional team.
Installation began with roughening of the concrete surface, using a grinder, to facilitate bond of
epoxy to concrete. Dust from roughening was removed from the column using acetone. The
CFRP wrap was cut to lengths approximately equal to one circumference of the column plus 12-
inches. The epoxy was mixed in batches due to a 1-hour pot life at 70°F (21°C). After the first
epoxy batch was mixed, an epoxy primer was applied to the columns using a nap roller. CFRP
sheets were hand saturated using plastic trowels. Care was taken to ensure full fiber saturation
without saturation so excessive that the sheet would settle once on the column. After saturating
the fibers, the sheets were wrapped around the column and the plastic hand trowels were used to
remove any entrapped air and excess saturate. The sheet had a lap length of 12-inches, with the
lap intended to provide adequate bond. The seams had additional epoxy applied per manufacturer
specifications. After the first layer, additional layers were applied with the start of the new layer
on the opposite side of the column as the end of the previous layer, such that all seams were
offset. After all 5 layers were applied, an epoxy paste was applied as an outer coating, and the
columns were given at least 72 hours to cure before testing of the first column. A finished jacket
is shown in Figure 3.4. Lacking of bulging in the jacket suggests that epoxy was appropriately
18
Figure 3.4: CFRP Jacket Before Testing for C(CFRP)-4.0-#7(1.3)-0.05
19
Figure 3.6: Construction: a) Bracing for Column Concrete Pour, and b) Bracing for Top Block
Concrete Pour
A batch of #7, #5, and #3 Grade 40 reinforcement was manufactured specifically for this study,
such that all column reinforcement in a given size was from the same heat. Three samples of #5
and #7 column longitudinal reinforcement were tested, with resulting stress-strain plots provided
in Figure 3.7. Values of the resulting yield strength, 𝑓𝑦 , ultimate strength, 𝑓𝑢 , and percent
20
Table 3.2: Measured Properties of Steel Reinforcement Obtained from Tensile Testing
21
3.1.3.2. Concrete
A single concrete supplier and mix design were used for the project. The mix used a 3/8-in
maximum aggregate to reflect 3/4-in maximum aggregate at full-scale. The footings were poured
separately from the columns and loading heads, as described in Section 3.2. 6” x 12” cylinders
were prepared for the footing and the columns, respectively. Cylinders were stored in close
proximity to the specimens. The footing cylinders were tested at 7-days, with the measured
concrete compressive strength provided in Table 3.3. Four cylinders were tested within 3 days of
each column test, and the results are provided in Table 3.4. A clear trend of strength increase
̅′ )
with time is not evident from the data, and the average concrete compressive strength (𝑓𝑐,𝑡𝑒𝑠𝑡
22
Table 3.4: Column Concrete Compressive Strength from Cylinder Testing
unidirectional carbon fabric designed to be laminated with CSS-ES and CSS-UES saturant. It is
specified to have 10% of the strength properties in the minor direction than the major direction.
The major direction was oriented around the circumferences of the columns. Table 3.5 provides
properties for the major direction, as specified in the ICC Report ESR-3404 (ICC ES, 2022).
23
Table 3.5: CFRP Properties in Major Direction
Property Value
Dry Fiber Tensile Strength 670,000 psi
Dry Fiber Tensile Modulus 37,000,000 psi
Dry Fiber Elongation at Break 1.9 %
Dry Fiber Unit Weight 44.0 oz./yd.2
Cured Composite Tensile Strength 128,000 psi
Cured Composite Tensile Modulus 14,200,000 psi
Cured Composite Elongation at Break 0.9 %
Cured Composite Thickness per Layer 0.08 in.
Using the set-up shown in Figure 3.8, tests were conducted in the Simpson Strong-Tie
Experimental Testing Laboratory, which is part of the Composite Materials and Engineering
Center (CMEC) at Washington State University. Prior to testing, the footing block of each test
column was post-tensioned to the laboratory strong floor. A pair of steel channels spanning over
each end of the footing blocks were used to engage more floor anchors. During testing, constant
axial load and cyclic lateral displacement were applied to the test column. Lateral load and
displacement was applied using a servo-controlled hydraulic actuator with 40-in stroke and
capacity of 220-k in tension and 328-k in compression. The lateral actuator was post-tensioned to
the top of the test column and was reacted by the laboratory strong wall. Axial load was applied
using 60-ton hydraulic jack(s) manually controlled by a self-contained hydraulic power unit.
Load was controlled through a pressure regulating valve integral with the power unit and
monitored with 100-k low profile load cell(s). As shown in Figure 3.10, a single jack and load
cell were used for five of the six tests, while three jacks and load cells were used for C(CFRP)-
24
4.0-#7(1.3)-0.05 due to the higher axial load. The application of vertically oriented axial load to
simulate P-delta was a unique feature of this program relative to much of the prior research (e.g.,
Haroun and Elsanadedy, 2005), which used tendons anchored to the strong floor to apply axial
load. Utilizing a roller and swiveling knuckle assembly, as depicted in Figure 3.9, the applied
axial load was able to translate with the top of the column to remain vertical. A steel frame,
comprised of four steel framing columns and three beams, was used to react the applied axial
load and to prevent out of plane movement of the test column. The standard axial load
configuration (5 of 6 tests) is depicted in Figure 3.9. The column with large axial load set-up
configuration required an additional axial load roller and larger capacity clevis assembly.
Additionally, steel plates were added between the test column and loading beam to distribute and
25
b)
a)
𝑃𝑑
Figure 3.8: Test Set-up, = 0.05: a) Schematic, b) Photo
𝐴𝑔 𝑓𝑐′
𝑷𝒅
Figure 3.9: Axial Load Setup, = 𝟎. 𝟎𝟓
𝑨𝒈 𝒇′𝒄
26
3.1.5. Instrumentation
Forces, strains, and displacements were recorded during testing. Five of the six tests used a
single 100-k load cell to measure axial load, while the test column with higher axial load used
three 100-k load cells. Displacement measurements of the column and footing relative to a
stationary reference frame were obtained from linear variable differential transducers (LVDTs)
and string potentiometers at the locations shown in Figure 3.10. Rotation of the footing was
determined based on two vertical sensors located at each end of the footing. LVDTs spanning
between the footing and 0.5-in above the footing were used to measure column sliding in the
horizontal direction and bond slip in the vertical direction. Axial-flexural deformations within
the jacketed region were measured using vertical sensors at the locations shown in Figure 3.13.
To attach LVDTs, ¼-in threaded instrumentation rods were installed into the column core
concrete by drilling approximately ½-inch diameter holes approximately 1” deep into the column
and inserting the threaded instrumentation rods with fast drying epoxy. Post-installed ¼-in
wedge anchors were alternatively used at the footing and loading head and at the relative
measurements bridging the gaps between the footing-column and column-loading head.
For each column, 14 strain gauges were installed on each of the two longitudinal starter bars
located closest to the column ends, as shown in Figure 3.10. As shown in Figure 3.11, the gauges
were located in the column and footing and were arranged symmetrically above and below a
location at ½-inch above the column-footing interface. The gauges were spaced at intervals of
every fourth bar deformation. This arrangement of strain gauges in the anticipated plastic hinge
region was intended to enable collection of data that would quantify the extent of strain
27
penetration into the columns and footings. Installation of each strain gauge required removal of
one bar deformation. Reinforcement bar deformation removal was limited to the surface area
required to adhere a gauge to the bar, which was typically one-half of the circumferential
deformation. The exception was full circumferential removal of the bar deformation at a location
redundant gauge on the opposing side. Strain gauge wires were arranged to exit from the top of
the footing.
28
Figure 3.11: Strain Gauge Reinforcement Layout (Dimensions in Inches)
29
Figure 3.13: LVDT Instrumentation Layout (Dimensions in Inches)
A fully-reversed cyclic loading protocol was used for four of the six test columns, and one test
was conducted using an earthquake loading protocol. These protocols were identical to those
cycles, with three cycles each at 5-k, 10-k, and additional intervals of 10-k prior to the yield drift.
Displacement control was employed thereafter, with six full cycles each at 1.0, 1.25, 1.5, 1.75,
2.0, and 2.5 times the yield drift, followed by two cycles each at 3.0, 3.5, 4.0, 5.0, 6.0, 8,0, 10.0,
12.5, 15.0, 20.0, and 25.0 times the yield drift, or until the test was completed. For cases in
which testing was continued, additional cycles were applied at 25.0 times yield drift, 𝛿𝑦 /𝐻.
30
C(CFRP)-4.0-#7(1.3)-0.05 used a modification of the reversed cyclic protocol that had twice the
number of cycles at each increment. Consistent with the steel jacketed columns tested by
McGuiness (2021), the yield drift was taken as 0.4% for C(S)-4.0-#7(1.3)-0.05, C(S)-4.0-
that consisted of a main-shock and aftershock, as shown in Figure 3.36 with values provided in
Table 3.6 and 3.7, respectively. For displacement-controlled cycles, the drift used to control the
31
Figure 3.15: Earthquake Loading Protocol
# Drift [%] # Drift [%] # Drift [%] # Drift [%] # Drift [%]
1 0.000 71 -2.396 141 -0.445 211 -0.167 281 -0.418
2 -0.011 72 -1.836 142 0.545 212 0.212 282 0.395
3 -0.005 73 -3.165 143 -0.550 213 -0.242 283 -0.333
4 -0.006 74 1.565 144 0.502 214 0.208 284 0.181
5 0.016 75 -0.240 145 -0.542 215 -0.165 285 -0.148
6 -0.003 76 2.746 146 0.468 216 0.099 286 0.249
7 -0.001 77 0.611 147 -0.571 217 -0.035 287 -0.212
8 -0.004 78 2.301 148 0.355 218 0.059 288 0.168
9 -0.002 79 -3.229 149 -0.185 219 -0.141 289 -0.146
10 -0.008 80 -0.268 150 0.252 220 0.140 290 0.179
11 0.000 81 -1.303 151 -0.290 221 -0.066 291 -0.247
12 -0.004 82 0.567 152 0.257 222 0.079 292 0.162
13 0.005 83 -0.468 153 -0.325 223 -0.077 293 -0.187
14 -0.002 84 0.569 154 0.350 224 0.035 294 0.165
15 -0.005 85 -2.447 155 -0.257 225 -0.082 295 -0.190
16 0.000 86 4.087 156 0.145 226 0.135 296 0.146
17 0.000 87 -1.566 157 -0.225 227 -0.232 297 -0.068
18 0.004 88 0.957 158 0.353 228 0.259 298 0.042
19 -0.011 89 -1.340 159 -0.452 229 -0.217 299 -0.118
32
20 -0.005 90 1.496 160 0.455 230 0.141 300 0.080
21 -0.006 91 -1.944 161 -0.442 231 -0.103 301 -0.038
22 0.004 92 2.784 162 0.491 232 0.249 302 0.040
23 0.003 93 -1.460 163 -0.337 233 -0.421 303 -0.060
24 0.004 94 1.911 164 0.276 234 0.376 304 0.044
25 0.004 95 -2.256 165 -0.296 235 -0.304 305 -0.018
26 0.023 96 1.260 166 0.190 236 0.219 306 0.021
27 -0.026 97 -2.155 167 -0.249 237 -0.185 307 -0.077
28 0.044 98 2.183 168 0.139 238 0.174 308 0.140
29 -0.055 99 -2.025 169 -0.033 239 -0.230 309 -0.132
30 0.025 100 1.794 170 0.018 240 0.168 310 0.102
31 -0.021 101 -1.856 171 -0.184 241 -0.082 311 -0.130
32 -0.021 102 1.752 172 0.217 242 0.060 312 0.058
33 -0.039 103 -1.727 173 -0.204 243 -0.127 313 0.008
34 0.119 104 1.510 174 0.187 244 0.136 314 0.011
35 -0.130 105 -0.758 175 -0.256 245 -0.145 315 -0.063
36 0.057 106 0.473 176 0.300 246 0.119 316 0.034
37 -0.004 107 -0.771 177 -0.210 247 -0.127 317 -0.023
38 0.251 108 0.869 178 0.184 248 0.063 318 0.016
39 -0.323 109 -0.852 179 -0.226 249 -0.081 319 -0.016
40 0.073 110 0.672 180 0.213 250 0.071 320 0.072
41 -0.195 111 -0.495 181 -0.221 251 0.000 321 -0.047
42 0.447 112 0.345 182 0.232 252 0.001 322 0.029
43 -0.460 113 -0.433 183 -0.253 253 0.000 323 -0.033
44 0.493 114 0.424 184 0.221 254 0.004 324 0.019
45 -0.593 115 -0.674 185 -0.211 255 -0.023 325 -0.024
46 0.625 116 0.785 186 0.157 256 0.070 326 0.013
47 -0.746 117 -0.541 187 -0.232 257 -0.183 327 -0.018
48 0.980 118 0.384 188 0.216 258 0.170 328 0.008
49 -0.855 119 -0.465 189 -0.132 259 -0.191 329 -0.014
50 1.019 120 0.482 190 0.086 260 0.261 330 0.004
51 -0.659 121 -0.566 191 -0.097 261 -0.340 331 -0.011
52 0.405 122 0.478 192 0.025 262 0.330 332 0.002
53 -0.590 123 -0.340 193 -0.070 263 -0.347 333 -0.009
54 0.930 124 0.021 194 0.087 264 0.373 334 0.000
55 0.924 125 0.011 195 -0.203 265 -0.319
56 0.987 126 0.395 196 0.254 266 0.206
57 -1.095 127 -0.708 197 -0.224 267 -0.223
58 0.841 128 0.714 198 0.192 268 0.310
59 -2.925 129 -0.590 199 -0.117 269 -0.342
60 4.524 130 0.245 200 0.236 270 0.175
33
61 -6.148 131 -0.117 201 -0.284 271 -0.048
62 3.341 132 0.066 202 0.159 272 0.076
63 -2.340 133 -0.045 203 -0.179 273 -0.205
64 1.358 134 -0.036 204 0.183 274 0.251
65 -2.432 135 -0.055 205 -0.310 275 -0.080
66 3.553 136 0.161 206 0.202 276 0.021
67 -1.108 137 -0.453 207 -0.277 277 -0.031
68 -0.795 138 0.468 208 0.310 278 0.058
69 -0.800 139 -0.402 209 -0.181 279 -0.196
70 2.616 140 0.306 210 0.142 280 0.423
34
28 0.333 73 -0.225 118 0.04 163 0.157 208 0
29 -0.309 74 0.235 119 -0.125 164 -0.196
30 0.095 75 -0.169 120 0.145 165 0.143
31 -0.096 76 0.005 121 -0.232 166 -0.146
32 0.317 77 -0.098 122 0.219 167 0.184
33 -0.053 78 0.477 123 -0.117 168 -0.159
34 -0.052 79 -0.169 124 0.142 169 0.11
35 -0.058 80 0.212 125 -0.155 170 -0.139
36 -0.057 81 -0.159 126 0.174 171 0.033
37 -0.157 82 -0.011 127 -0.277 172 -0.078
38 0.369 83 -0.117 128 0.161 173 0.061
39 -0.225 84 0.001 129 -0.175 174 -0.013
40 0.566 85 -0.1 130 0.194 175 0.02
41 -1.321 86 0.105 131 -0.223 176 0.001
42 1.37 87 -0.069 132 0.182 177 0.028
43 -2.02 88 0.198 133 -0.191 178 -0.074
44 1.103 89 -0.328 134 0.151 179 0.071
45 -0.017 90 0.326 135 -0.107 180 -0.085
Photos that show damage at 4 𝛿/𝛿𝑦 , 8 𝛿/𝛿𝑦 , 15 𝛿/𝛿𝑦 , 20 𝛿/𝛿𝑦 , and the completion of testing are
provided in Figure 3.16 and Figure 3.17, Figure 3.18 and Figure 3.19, Figure 3.20 and Figure
3.21, Figure 3.22 and Figure 3.23, and Figure 3.24 and Figure 3.25, respectively. Concrete
crushing was not observed within the jacketed region, indicating that the jackets adequately
confined the concrete. Damage generally concentrated at the top of the footing in the vicinity of
the column, with spalling observed in the footing. Cracking was observed above the jacket.
35
reinforcement buckling were not observed above the jacket. The exception was C(CFRP)-4.0-
characteristic of a plastic hinge, occurred above the jacket. Spalling of concrete was first
observed at the first cycle to 12.5(𝛿/𝛿𝑦 ) in the negative direction, with longitudinal bars visible
occurred, as shown in Figure 3.24.f and Figure 3.25.f, until a state of axial failure was reached
during the final cycle to 15(𝛿/𝛿𝑦 ). Extending the jacket further up the height of the column
The cycles at which footing cracks, horizontal flexural cracks, vertical shear cracks, and spalling
of footing concrete were first observed are provided in Table 3.8. Damage in all tests included
splitting cracks on the top surface of the footing that would propagate down the long sides and
horizontal cracks on the tension face of the column just above the jacket. The horizontal cracks
closed when the load was reversed and would propagate as the test progressed. In cycles after
8𝛿/𝛿𝑦 , horizontal cracks extended up to 64-inches from the column base. The extent of flexural
cracks varied significantly between tests in both severity and how far they propagated up the
column. Flexural cracks began to develop between 30-kip and 3.5 𝛿/𝛿𝑦 for all columns.
C(CFRP)-4.0-#7(1.3)-0.15 is the only column in which flexural cracks developed prior to footing
cracks. The flexural cracks progressed faster in terms of quantity, length, and severity for
C(CFRP)-4.0-#7(1.3)-0.15 with a measured 0.068 inch wide crack at the first cycle to 8𝛿/𝛿𝑦 in
the negative direction (Figure 3.19.f). The flexural cracks continued to grow as the test
progressed, with vertical cracks connecting the horizontal flexural cracks being noticed at the
observed at 12.5 𝛿/𝛿𝑦 , while shear cracks were not observed for C(CFRP)-4.0-#7(1.3)-0.05 and
loading protocol.
Significant torsion was observed for C(CFRP)-4.0-#7(1.3)-0.05-EQ, and test was stopped before
reaching the third cycle at 10% drift, as the base of the column had ratcheted roughly 1.5 inches
out of plane. The Final photos of the column shown in figure 3.9.d, show that the column
scraped off the cover of the footing all the way down to the upper reinforcement as it moved out
of plane.
Footing
Column ID Footing Cracks Flexure Cracks Shear Cracks
Spalling
C(CFRP)-4.0-
5-k (2nd) 2(δ/δy ) (1st) N/A 15(δ/δy ) (1st)
#7(1.3)-0.05
C(CFRP)-4.0-
1(δ/δy ) (1st) 1.25(δ/δy ) (1st) 4(δ/δy ) (1st) 15(δ/δy ) (1st)
#5(1.4)-0.05
C(CFRP)-4.0- 1.75(δ/δy )
3.5(δ/δy ) (2nd) 5(δ/δy ) (1st) 10(δ/δy ) (1st)
#7(2.7)-0.05 (2nd)
C(CFRP)-4.0-
Start of test 1.12(δ/δy ) (1st) N/A 12.5(δ/δy ) (1st)
#7(1.3)-0.05-EQ
C(CFRP)-4.0-
Start of test 30-k (1st) 12.5(δ/δy ) (1st) 10(δ/δy ) (1st)
#7(1.3)-0.05-2X
C(CFRP)-4.0-
1.25(δ/δy ) 40-k (1st) 8(δ/δy ) (2nd) 10(δ/δy ) (1st)
#7(1.3)-0.15
37
a) d)
b) e)
c) f)
38
a) d)
b) e)
c) f)
Figure 3.17. Concrete Damage Above Jacket at 𝟒. 𝟎𝜹/𝜹𝒚 (2.55𝜹/𝜹𝒚 for C(CFRP)-4.0-#7(1.3)-
0.05-EQ) for: a) C(CFRP)-4.0-#7(1.3)-0.05, b) C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-
#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-2X, and f)
C(CFRP)-4.0-#7(1.3)-0.15
39
a) d)
b) e)
c) f)
40
a) d)
b) e)
c) f)
Figure 3.19. Concrete Damage Above Jacket at 𝟖. 𝟎𝜹/𝜹𝒚 (7.3𝜹/𝜹𝒚 for C(CFRP)-4.0-#7(1.3)-
0.05-EQ) for: a) C(CFRP)-4.0-#7(1.3)-0.05, b) C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-
#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-2X, and f)
C(CFRP)-4.0-#7(1.3)-0.15
41
a) d)
b) e)
c) f)
42
a) d)
b) e)
c) f)
43
a) d)
c) e)
d) f)
Figure 3.22. Concrete Damage at Base at 20𝜹/𝜹𝒚 (at 𝟏𝟓𝜹/𝜹𝒚 for C(CFRP)-4.0-#7(1.3)-0.15)
for: a) C(CFRP)-4.0-#7(1.3)-0.05, b) C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-#7(2.7)-0.05,
d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-2X, and f) C(CFRP)-4.0-
#7(1.3)-0.15
44
a) d)
b) e)
c) f)
Figure 3.23. Concrete Damage Above Jacket at 20𝜹/𝜹𝒚 (at 𝟏𝟓𝜹/𝜹𝒚 for C(CFRP)-4.0-#7(1.3)-
0.15) for: a) C(CFRP)-4.0-#7(1.3)-0.05, b) C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-#7(2.7)-
0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-2X, and f) C(CFRP)-4.0-
#7(1.3)-0.15
45
a) d)
b) e)
c) f)
46
a) d)
b) e)
c) f)
Figure 3.25. Concrete Damage Above Jacket at Completion of Testing for: a) C(CFRP)-4.0-
#7(1.3)-0.05, b) C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-#7(2.7)-0.05, d) C(CFRP)-4.0-
#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-2X, and f) C(CFRP)-4.0-#7(1.3)-0.15
47
3.2.1.2 Fatigue Fracture of Longitudinal Reinforcement
In all cases, low-cycle fatigue fracture of longitudinal reinforcement occurred near the footing-
column interface. Concrete cracks that formed at the footing-column interface, as shown in
Figure 3.16, were attributed to longitudinal reinforcement bond slip. The sequence of
reinforcement fractures in each loading direction is provided in Table 3.9 and Table 3.10. For
each of the five tests with fully reversed-cyclic loading, a level of variability is evident in Table
3.9. For C(CFRP)-#7(1.4)-0.05-EQ, the first positive and negative fractures occurred at the same
cycle, despite higher demands in the negative direction during the earthquake and aftershock
protocols. In the columns containing more than one bar fracture, the second fracture occurred in
the same or immediately succeeding excursion. Due to torsional ratcheting at the base, shown in
Figure 3.24.d, testing of C(CFRP)-4.0-#7(1.3)-0.05-EQ was stopped before more than six bars
had fractured. Only one bar fractured for C(CFRP)-4.0-#7(1.3)-0.15 due to plastic hinging above
48
Table 3.9: Sequence of Longitudinal Bar Fractures
Column Name
Bar C(CFRP)- C(CFRP)- C(CFRP)- C(CFRP)- C(CFRP)- C(CFRP)-
Fracture 4.0- #7(1.3)- 4.0-#5(1.4)- 4.0-#7(2.7)- 4.0-#7(1.3)- 4.0-#7(1.3)- 4.0-#7(1.3)-
0.05 0.05 0.05 0.05-EQ 0.05-2X 0.15
@ 4.26% 1st @ 5.22% 1st @ 6.39% @ 4.75% @ -1.62%
1st
to to 2nd to 1st to 2nd to ̶
Pos. (+)
+8.0% +8.0% +7.5% +10.0% +6.0%
@ -5.28% @ -5.02% @ -4.20% @ -4.74% @ -0.22% @ -0.26%
1st
2nd to 2nd to 2nd to 1st to 1st to 1st to
Neg. (–)
-6.0% -6.0% -7.5% -10.0% -6.0% -7.5%
@ 2.10% @ 5.92 % @ 0.83% @ 7.06% @ 5.80%
2nd
2nd to 1st to 1st to 1st to 1st to ̶
Pos. (+)
+8.0% +8.0% +10.0% +10.0% +8.0%
@ -2.18% @ -5.77% @ -6.08% @ -6.82% @ 0.24%
2nd
2nd to 2nd to 2nd to 1st to 3rd to ̶
Neg. (–)
-8.0% -6.0% -7.5% -10.0% -6.0%
@ 7.39% @ 3.00% @ 6.42% @ 1.10 @ 4.61%
3rd
1st to 2nd to 1st to 2nd to 2nd to ̶
Pos. (+)
+10.0% +8.0% +10.0% +10.0% +8.0%
49
@ 7.38% @ 6.46%
6th
N.A. 2nd to 2nd to N.A. N.A. N.A.
Pos. (+)
+8.0% +10.0%
@ -7.25% @ -7.83
6th
N.A. 2nd to 2nd to N.A. N.A. N.A.
Neg. (–)
-8.0% -10.0%
7th @ 7.11% 1st @ 9.89%
Pos. (+) N.A. to 2nd to N.A. N.A. N.A.
+10.0% +10.0%
@ -7.68% @ -7.85%
7th
N.A. 2nd to 6th to N.A. N.A. N.A.
Neg. (–)
-8.0% -10.0%
@ 9.34% @ 0.15%
8th
N.A. 3rd to 4th to N.A. N.A. N.A.
Pos. (+)
+10.0% +10.0%
@ -9.59% @ -9.25%
8th
N.A. 2nd to 7th to N.A. N.A. N.A.
Neg. (–)
-10.0% -10.0%
@ 6.46% @ 8.23%
9th
N.A. 4th to 4th to N.A. N.A. N.A.
Pos. (+)
+10.0% +10.0%
@ -8.03%
9th
N.A. 3rd to ̶ N.A. N.A. N.A.
Neg. (–)
-10.0%
@ 9.01%
10th @ -5.89%
N.A. 4th to N.A. N.A. N.A.
Pos. (+) 5th to +10.0%
+10.0%
10th
N.A. ̶ ̶ N.A. N.A. N.A.
Neg. (–)
50
Table 3.10: Summary of Cycles at which Longitudinal Bars Fractured
51
3.2.2. Load-Deformation
The lateral load-deformation response is provided in Figure 3.26 for all tests. All columns were
incurred damage above the jacketed region, was greater than the other tests. The sequence of
longitudinal bar fractures is indicated on the plots, and the degradation in lateral load resistance
occurred primarily due to bar fractures. P-delta demands also reduced lateral load resistance,
with quantification of P-delta effects provided in Section 3.3. The values for peak shear demand,
𝑉𝑚𝑎𝑥 , normalized peak base moment, 𝑀𝑚𝑎𝑥 /𝑀𝑛 , displacement at peak demand, 𝛿𝑚𝑎𝑥 , and drift
𝛿
at peak demand, ( ) , are provided in Table 3.11 for each test column in both the positive and
𝐻 𝑚𝑎𝑥
where 𝐻 is the height of the column, 𝑃 is the axial load, Δ is the column lateral displacement
measured at the point of lateral load application, and 𝑉𝑚𝑎𝑥 is the maximum shear. As shown in
Table 3.11, 𝑀𝑚𝑎𝑥 /𝑀𝑛 ranged from 1.244 to 1.435 for the six columns and ranged from 1.279 to
1.345 for the four tests with identical loading protocol. 𝑀𝑚𝑎𝑥 /𝑀𝑛 was smallest for C(CFRP)-
strength. 𝑀𝑚𝑎𝑥 /𝑀𝑛 was highest for C(CFRP)-4.0-#7(1.3)-0.05-EQ, likely due to a large cycle
earlier in the cycle sequence than that of the fully reversed cyclic tests. For all tests 𝑀𝑚𝑎𝑥 /𝑀𝑛
was within 4% for both the positive and negative loading directions.
52
Lateral failure was defined to have occurred when the lateral load at a maximum cycle peak first
dropped below 20% of the peak lateral load and did not return to this level during subsequent
cycles. A maximum cycle peak is defined as a cycle peak that had lateral displacement greater
than or equal to any previous peak in that loading direction. The maximum cycle peak prior to
the cycle at which lateral failure occurred in the positive and negative loading direction is
provided in Table 3.12 for each column. All columns reached lateral failure between 12.5 𝛿/𝛿𝑦
and 20.0𝛿/𝛿𝑦 . C(CFRP)-4.0-#7(1.3)-0.05-EQ had the greatest displacement before lateral failure
the greatest difference between the positive and negative loading directions. Both columns had
increased strength in the negative loading direction with a 3.7% of 𝑀𝑛 increase for C(CFRP)-
attributed to asymmetry in the loading cycles of the earthquake protocol. Of the other four tests,
none had greater than a 1% difference in peak moment between the corresponding positive and
The first bar fracture occurred during the excursion at which lateral failure occurred, with the
exception of C(CFRP)-4.0-#7(1.3)-0.15, in which the first bar fractured after lateral failure
occurred and the loss in strength was attributed to the concrete damage described in Section
3.2.1.1. The majority of longitudinal reinforcement fractures occurred during the portion of the
cyclic excursion beyond zero lateral displacement. While some fractures were reported during
53
unloading, they were in the minority, occurring twice for C(CFRP)-4.0-#7(1.3)-0.05-2X and
once for C(CFRP)-4.0-#7(2.7)-0.05. Fractures occurring on the loading excursions typically were
associated with an immediate loss of strength. Fractures occurring on the unloading excursions
54
a) d)
b) e)
c) f)
55
Table 3.11: Peak Demands, Displacements, and Drifts
56
3.2.3 Backbone Modeling
Bilinear backbone models, suitable for implementation into computer software used for
conducting nonlinear time history analyses, were fit to the load-displacement response of each
tested column in both the positive and negative loading direction, as shown in Figure 3.27.a
through Figure 3.32.a for the applied shear demand and Figure 3.27.b through Figure 3.32.b for
an effective shear demand that accounts for P-delta. Effective shear was computed as the base
moment, including P-delta, divided by the column height of 96 inches. The procedure in
ASCE/SEI-41 Section 7.4.3.2.4 (ASCE, 2017) was used for bilinear modeling. Although this
building, it was used for component modeling in this study. The first step in the procedure was
the formulation of a test data backbone, which consisted of a piecewise linear fit to peaks of
initial cycles, defined as any cycle that has a larger displacement that any previous cycle. The
bilinear model was formulated by placing the terminal points at the origin and maximum load.
The first line in the bilinear model intersected the test data backbone at 60% of the yield force.
The yield point, located at the intersection of the lines in the bilinear model, was determined such
that the area under the bilinear model was equal to the area under the test data curve between the
origin and maximum load. Base moment, including P-delta, was used to determine the excursion
From the backbone models, the effective stiffness and post-yield stiffness, Ke and Kp,
respectively, were taken as the slope of the first and second lines of the bilinear model,
57
𝑉𝑦
𝐾𝑒 = (3-2)
𝛿𝑦
𝑉𝑚𝑎𝑥 − 𝑉𝑦
𝐾𝑝 = (3-3)
𝛿𝑚𝑎𝑥 − 𝛿𝑦
where 𝑉𝑦 and 𝛿𝑦 are the base shear and displacement at yielding, respectively, and 𝑉𝑚𝑎𝑥 and
𝛿𝑚𝑎𝑥 are the maximum shear and corresponding displacement, respectively, all determined by
the bilinear backbone modeling procedure. Values of 𝐾𝑒 and 𝐾𝑝 for both the applied shear and
effective shear backbones are provided in Table 3.13 for each of the six test columns in each of
the two loading directions. Assuming all deformation in the cantilever column was due to
𝑉𝑦 𝐻 3 𝐻 3
𝐸𝐼𝑒𝑓𝑓 = = 𝐾 (3-4)
3𝛿𝑦 3 𝑒
where H is the height of the column. Resulting values for (𝐸𝐼)𝑒𝑓𝑓 and (𝐸𝐼)𝑒𝑓𝑓 /(𝐸𝑐 𝐼𝑔 ) are
additionally reported in Table 3.13 where 𝐸𝑐 is the modulus of elasticity of concrete, and 𝐼𝑔 is the
moment of inertia of the gross concrete column section without the CFRP jacket included. The
average tested concrete strength from all column cylinder tests, shown in Table 3.4, was 3.95-
58
ACI 318-19 Section 19.2.2.1. C(CFRP)-4.0-#7(1.3)-0.15 had the largest (𝐸𝐼)𝑒𝑓𝑓 in both
directions, likely attributed to increased concrete strength from the increased axial loads.
C(CFRP)-4.0-#7(1.3)-0.05 had the lowest (𝐸𝐼)𝑒𝑓𝑓 in the positive direction and C(CFRP)-4.0-
#7(1.3)-0.05-EQ had the lowest (𝐸𝐼)𝑒𝑓𝑓 in the negative direction. Since these columns only
differ in loading protocol it is not surprising that their (𝐸𝐼)𝑒𝑓𝑓 values are similar. The three
the positive direction and 0.458 with a COV of 19.7% in the negative direction.
Bilinear models and test data backbones, normalized by lateral load at yielding determined from
the bilinear model fit, are provided in Figure 3.34 and Figure 3.35, respectively. Directional
variability was evident from the asymmetry of (𝐸𝐼)𝑒𝑓𝑓 values for C(CFRP)-4.0-#7(1.3)-0.05,
C(CFRP)-4.0-#7(1.3)-0.15 had the lowest directional variability of the 6 columns with the
negative direction having only 0.03% increase in (𝐸𝐼)𝑒𝑓𝑓 compared to the positive direction.
59
a) b)
Figure 3.27. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.05: a) Base Shear, b) Effective
Base Shear
a) b)
Figure 3.28. Backbone Model Fit for C(CFRP)-4.0-#5(1.4)-0.05: a) Base Shear, b) Effective
Base Shear
60
a) b)
Figure 3.29. Backbone Model Fit for C(CFRP)-4.0-#7(2.7)-0.05: a) Base Shear, b) Effective
Base Shear
a) b)
Figure 3.30. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.05-EQ: a) Base Shear, b) Effective
Base Shear
61
a) b)
Figure 3.31. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.05-2X: a) Base Shear, b) Effective
Base Shear
a) b)
Figure 3.32. Backbone Model Fit for C(CFRP)-4.0-#7(1.3)-0.15: a) Base Shear, b) Effective
Base Shear
62
Figure 3.33. Bilinear Model Backbone Slope Parameters
63
Table 3.13: Stiffness and Strength of Backbone Models
64
Figure 3.34. Normalized Bilinear Backbone Model Plots
65
3.2.4. Effective Secant Stiffness
Effective secant stiffness, 𝐾𝑠𝑒𝑐 , was determined for each initial cycle (i.e., each point on the test
data backbone) as the slope of the line from the origin to that point. Assuming all deformation in
the cantilever column was due to bending, 𝐾𝑠𝑒𝑐 was converted to an effective flexural rigidity,
(EI)sec, as:
𝐾𝑠𝑒𝑐 𝐻 3 𝑉𝐻 3
(𝐸𝐼)𝑠𝑒𝑐 = = (3-6)
3 3𝛿
Plots of 𝐸𝐼𝑠𝑒𝑐 /(𝐸𝐶 𝐼𝑔 ) versus drift with data points connected by lines are provided in Figure
longitudinal reinforcement ratio and higher axial load, respectively, than the other columns,
exhibited greater stiffness at given drift levels. Minor variation was observed between C(CFRP)-
66
Figure 3.36. Effective Secant Stiffness Plots
Measurements obtained from the strain gauges shown in Figure 3.10 and Figure 3.11 were
plotted in Figures 4.22 through Figures 4.26 for initial cycle peaks at various drift levels.
Negative values on the y-axes indicate strain gauges in the footing. Yield strain, 𝜖𝑦 , is shown on
the plots and was determined from the reinforcement stress-strain data provided in Figure 3.7.
During positive loading excursions, the South reinforcement was in tension and the North
67
reinforcement was in compression. Gauges tended to become damaged as testing progressed,
leading to sparser data at increased drift levels. Some gauges malfunctioned before testing
commenced, and these data were omitted. Gauge results for C(CFRP)-4.0-#7(1.3)-0.05 were not
available due issues with gauges. Two gauges were used at 0.05-in above the column-footing
interface, and, when both gauges were functioning, average values were reported.
Generally, strains increased with greater magnitude excursions. Most columns had larger strain
in the tension than compression direction, as expected, and this trend was most prominent for
closer to the column-footing interface. Reinforcement yielding was reached in all columns.
EQ also exhibited reinforcement yielding at the sensor farthest above the column footing
interface. All other columns exhibited at least 80% of the yield strain in one of the sensors at
68
Figure 3.37. Strain Measured in Longitudinal Reinforcement at Cycle Peaks, C(CFRP)-4.0-
#5(1.4)-0.05
71
3.2.6. Column Curvature
Curvature was determined using the vertically oriented LVDTs in the column, shown in Figure
3.13. At each height increment, curvature was determined using the two North-South Sensors,
with plots of the values provided in Figure 3.42. Results were more limited at advanced
deformation levels due to damage interfering with instrumentation. It is evident that curvature
demand concentrated in the lower 6 inches of the columns. However, at a height of 0.5-in, the
deformation is primarily due to bond slip and extension, such that the strain determined from the
LVDTs over the lower 0.5-in is not reflective of true curvature. Column curvatures excluding
data for the lower 0.5-in are provided in Figure 3.43. The calculated yield curvatures shown in
Figure 3.42 and Figure 3.43 were computed using moment-curvature analysis with the steel
reinforcement material properties provided in Table 3.2 and the concrete material properties
provided in Table 3.3. Measured curvature did not exceed calculated yield curvature at locations
more than 4-in above the column-footing interface. The exception was C(CFRP)-4.0-#7(1.3)-
0.15, in which curvature exceeded the calculated yield curvature at 12-in above the column-
footing interface at 2% and greater drift in the positive direction and 4% and greater drift in the
negative direction. It is noted that data was excluded from Figure 3.42 and Figure 3.43 due to
72
Figure 3.42. Measured Curvature: a) C(CFRP)-4.0-#7(1.3)-0.05, b) C(CFRP)-4.0-#5(1.4)-0.05,
c) C(CFRP)-4.0-#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-
2X, f) C(CFRP)-4.0-#7(1.3)-0.15
73
Figure 3.43. Measured Curvature Excluding Bond Slip: a) C(CFRP)-4.0-#7(1.3)-0.05, b)
C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-EQ, e)
C(CFRP)-4.0-#7(1.3)-0.05-2X, f) C(CFRP)-4.0-#7(1.3)-0.15
74
3.2.7. Shear Sliding and Base Rotation
Shear sliding and base twisting were determined using the horizontally oriented sensors spanning
from the footing to the base of the column, with sensor locations shown in Figure 3.12. Plots of
shear sliding and base twisting versus base shear are provided in Figure 3.43 and Figure 3.44,
respectively, with clockwise and counter-clockwise indicating column twist direction relative to
the footing. Data for C(CFRP)-4.0-#7(1.3)-0.05 were omitted due to sensor error. Included data
for all columns were more limited at advanced deformation levels due to damage interfering with
instrumentation. C(CFRP)-4.0-#7(2.7)-0.05 had the most shear sliding of any test, reaching
almost 0.7-in of sliding in both directions. C(CFRP)-4.0-#7(1.3)-0.15 had the least shear sliding
and base rotation, with less than 0.15-in of shear sliding in both directions and a maximum base
twisting rotation of 0.0042 radians in the clockwise direction and 0.0000 radians in the counter
loading direction, while C(CFRP)-4.0-#7(1.3)-0.15 had more shear sliding in the positive loading
positive and negative directions, with 1.92 times as much shear sliding in the negative direction
than in the positive direction. This column had the most base rotation of any of the columns, with
a maximum base twisting rotation of 0.094 radians in the clockwise direction and 0.033 radians
in the counter clockwise direction. The twisting caused out-of-plane translation due to ratcheting,
75
Figure 3.44. Shear Sliding: a) C(CFRP)-4.0-#5(1.4)-0.05, b) C(CFRP)-4.0-#7(2.7)-0.05, c)
C(CFRP)-4.0-#7(1.3)-0.05-EQ, d) C(CFRP)-4.0-#7(1.3)-0.05-2X, e) C(CFRP)-4.0-#7(1.3)-0.15
76
Figure 3.45. Base Rotation: a) C(CFRP)-4.0-#5(1.4)-0.05, b) C(CFRP)-4.0-#7(2.7)-0.05, c)
C(CFRP)-4.0-#7(1.3)-0.05-EQ, d) C(CFRP)-4.0-#7(1.3)-0.05-2X, e) C(CFRP)-4.0-#7(1.3)-0.15
77
3.2.8. Components of Deformation
The components of deformation for the six tests at peaks of initial cycles are provided in Figure
3.45. The components are provided as a percentage of the overall column displacement and drift.
“Flexure in the Jacket” was determined from the curvature over the height of the jacket, using
curvature values shown in Figure 3.42 with constant curvature assumed over the length of the
sensor (i.e., center of rotation at mid-height of the sensor length). This did not include the
curvature in the bottom 0.5-in of the column, which contained bar slip and elongation. The lower
0.5-in of the column, which was included separately in the figure as “Bond Slip/Elongation”,
was determined from the rotation measured over the lower 0.5-in of the column. The shear
sliding described in Section 3.2.7 is included in Figure 3.45 as “shear sliding”. Estimated shear
𝑉ℎ
Δ𝑠ℎ𝑒𝑎𝑟 = (3-8)
(𝐴𝑉 𝐺)𝑒𝑓𝑓
where V is the shear force at the base of the column, h is the height of the column shear span, and
(AvG)eff, is the effective shear rigidity, which was computed using the recommended value in
78
where 𝐸𝑐 is the concrete modulus of elasticity of concrete and 𝐴𝑔 is the gross cross-sectional
area. The “Other” category is the displacement or drift not accounted for by the previously
mentioned components. This includes flexural deformation above the jacket, as well as any
category constitutes everything but shear sliding and estimated shear displacement, due to sensor
error described in Section 3.2.6. Similarly, C(CFRP)-4.0-#7(1.3)-0.05 was omitted due to the
As evident from Figures 4.31.c. through 4.31.e., the majority of the deformation occurred at the
bottom 0.5-in of the column, with shear sliding contributing minimally to the overall
deformation. Shear sliding between -5.6% and 12.7%for all columns. Flexure in the jacket also
contributed minimally to the overall deformation with a minimum contribution of -10.8% and a
contribution of 11.8% across all columns. The majority of the deformation was due to bond
slip/elongation and other sources. The contribution from bond slip and elongation generally
increased as drift increased. An increase in “other” with increase in damage above the jacket was
evident in the negative direction for C(CFRP)-4.0-#7(1.3)-0.15, which failed above the jacket,
79
Figure 3.46. Components of Deformation: a) C(CFRP)-4.0-#5(1.4)-0.05, b) C(CFRP)-4.0-
#7(2.7)-0.05, c) C(CFRP)-4.0-#7(1.3)-0.05-EQ, d) C(CFRP)-4.0-#7(1.3)-0.05-2X,
e) C(CFRP)-4.0-#7(1.3)-0.15
80
4. Column Modeling
4.1. Methodology
Failure of the FRP jacket retrofitted bridge columns was due to low-cycle fatigue fracture of
longitudinal reinforcement. Predicting the drift and cycle at failure for a given column is
existing models for low-cycle fatigue fracture of reinforcement are based on plastic strain history
(Uriz and Mahin, 2008; Huang and Mahin, 2008; Kanvinde, 2004; Padilla-Llano et al., 2018). A
column hinge rotation model was used to formulate a relationship between the strain in the
The column model, shown in Figure 4.1, consisted of a linear elastic line element, a fiber section
element over the 1” clear cover to the footing top reinforcement, and a bond slip element at the
footing column interface and at 1” into the footing. The spread of plasticity into the column was
not modeled, as it was evident from test data in Section 3.2.6 that the spread of plasticity in the
jacketed region was minimal. The use of a fiber section in the concrete cover was intended to
account for the concrete spalling that occurred, as described in Section 3.2.1.1. The bond slip
elements were intended to model strain penetration into the footing and into the jacket. In this
model, the plastic hinge length, Lp, was 1”, which was concrete cover dimension, and plastic
deformation was modeled to occur in the fiber section element and in the two zero-length bond
slip elements. Rotation in the plastic hinge, θp, is related to drift ratio as:
81
(𝛥−𝛥𝑦 ) 𝛥𝑝
𝜃𝑝 = 𝐿𝑝 = 𝐿𝑝 (4-1)
(𝐻+ 2 ) (𝐻+ 2 )
where Δ is the total lateral displacement at the top of the column, Δy is the lateral displacement at
yield, Δp is the plastic lateral displacement, H is the column clear height, and Lp/2 is the height of
the plastic hinge center of rotation below the base of the column. Previous research (Chai et al,
1991) has shown that plastic curvature in steel jacket retrofitted columns concentrates at the base
at the gap between the steel jacket and the foundation. Because Lp is small relative to the height
of the column, plastic hinge rotation may be approximated as plastic drift ratio:
𝛥𝑝 𝛥𝑝 𝛥𝑝
𝜃𝑝 = = 𝐿𝑔𝑎𝑝 ≈ (4-2)
(𝐻−𝐻ℎ𝑖𝑛𝑔𝑒 ) (𝐻− 2 ) 𝐻
Assuming plane section behavior and uniform strain over the height of the fiber section element,
𝜃𝑝 𝛥𝑝 /𝐻 𝛥𝑝 /𝐻
𝜀𝑝,𝑡 = 𝜀𝑠 − 𝜀𝑦 = 𝜙𝑝 (𝑑 − 𝑐) = (𝑑 − 𝑐) ≈ (𝑑 − 𝑐) = (𝑑 − 𝑐) (4-3)
𝐿𝑝 𝐿𝑝 𝐿𝑔𝑎𝑝 +𝐶𝑑𝑏
where εs is the tensile strain in the outermost tensile longitudinal reinforcement, εs is the yield
strain of the outermost tensile longitudinal reinforcement, ϕp is the plastic curvature, d is the
depth to the outermost tensile longitudinal reinforcement, and c is the neutral axis depth.
Similarly, the plastic compression strain in the outermost longitudinal reinforcement, εp,c, is:
82
𝜃𝑝 𝛥𝑝 /𝐻 𝛥𝑝 /𝐻
𝜀𝑝,𝑐 = 𝜀𝑠 − 𝜀𝑦 = 𝜙𝑝 (𝑐 − 𝑑′) = (𝑐 − 𝑑′) ≈ (𝑐 − 𝑑′) = (𝑐 − 𝑑′) (4-4)
𝐿𝑝 𝐿𝑝 𝐿𝑔𝑎𝑝 +𝐶𝑑𝑏
where d’ is the compression strain in the outermost compressive longitudinal reinforcement and
83
The column model was formulated in OpenSees (McKenna, year) as a linear elastic beam
element with a displacement based fiber element of length Lp = 1-in. The model is intended to be
efficient for use in nonlinear time history analyses and enabled the recording of stress and strain
in longitudinal reinforcement. In this manner the strain history in the longitudinal reinforcement
could be directly related to the drift history of the column, without needing to explicitly
The stiffness of the unjacketed column was determined using the method of Elwood and
Eberhard (2009), which accounts for the contribution from flexure, shear, and bond slip as:
𝐻 2 𝜙𝑦
𝛥𝑓𝑙𝑒𝑥𝑢𝑟𝑒 = (4-6)
3
𝐻𝑑𝑏 𝑓𝑦 𝜙𝑦 𝐻𝑑𝑏 𝑓𝑦 𝜙𝑦
𝛥𝑠𝑙𝑖𝑝 = = (4-7)
8𝑢
8(9.6√𝑓𝑐′ )
𝑀𝑦 𝑀𝑦
𝛥𝑠ℎ𝑒𝑎𝑟 = = (0.85𝐷)(0.2𝐸 (4-8)
𝐴𝑣 𝐺𝑒𝑓𝑓 𝑐)
where H is the height of the column, is the yield curvature, db is the diamater of longitudinal
the yield moment, Av is the area of the cross-section resisting shear, D is the diamater of the
column, Geff if the effective shear modulus, and Ec is the modulus of elasticity of concrete. My
was determined from moment-curvature analysis at first yield of reinforcement. For the bond slip
contribution, Zhao and Sritharan (2007) was used in place of Eq. (5-8):
84
1
𝑑𝑏 𝑓𝑦 𝛼
Δ𝑠𝑙𝑖𝑝 = 0.1 [ (2𝛼 + 1)] + 0.013 (4-9)
4√𝑓 ′ 𝑐
where 𝛼 is the parameter used in local bond-slip relation and was taken as 0.4 as done in Zhao
and Sritharan (2007). The increase in stiffness from the FRP jacket was determined using the
approach recommended by Chai et al (1994) for steel jackets, which accounts for the bond
transfer length needed to develop full composite action of the jacket and column. As this was an
FRP jacket, the gap length, 𝐿𝑔𝑎𝑝 , and grout thickness, 𝑡𝑔𝑟𝑜𝑢𝑡 , were both zero. The CFRP jacket
cured composite tensile modulus and tensile strength shown in Table 3.5 were used in place of
the steel jacket elastic modulus and yield strength. Once the stiffness of the column, k, was
determined, it was implemented into the model as the elastic flexural rigidity, (EI)elastic, of the
𝑀𝑦 𝐿𝑔𝑎𝑝 𝐿𝑝 3 𝑀𝑦 𝐿𝑔𝑎𝑝 𝐿𝑝 3
− 2 − 2) −
𝐻 (𝐻 𝐻 (𝐻 2 − 2)
(𝐸𝐼)𝑒𝑙𝑎𝑠𝑡𝑖𝑐 = = (4-10)
3∆𝑒𝑙𝑎𝑠𝑡𝑖𝑐 𝑀𝑦 𝐿𝑔𝑎𝑝
3( − 𝜙𝑦 𝐿𝑝 (𝐻 −
𝐻𝑘 2 ))
where My and ϕy was determined from moment-curvature analysis using the Mander et al (1988)
confined concrete model. This computation of (EI)elastic accounts for the flexibility in the fiber
element based on the displacement at yield due to curvature in the fiber, such that the elastic
stiffness in the model is expected to match the computed value for k at yield.
85
Concrete was modeled using Concrete02 in OpenSees. The Mander et al (1988) model for
confined concrete was used to determine the confined concrete compressive strength, f’cc, and the
strain at which f’cc is reached, εcc. The ultimate concrete stress and strain were modeled as 0.2f’cc
and 5εcc, respectively. λ in the Concrete02 model, which is the ratio between unloading slope and
initial slope, was taken as 0.1.. Reinforcement was modeled using ReinforcingSteel, with the
tangent at initial strain hardening taken as 0.01𝐸𝑠 . Strain hardening was initiated at 𝜀𝑠ℎ and strain
at peak stress was reached at 𝜀𝑢𝑙𝑡 . Reinforcement in the bond-slip elements was modeled with
Bond SP01. Yield slip, 𝑠𝑦 , was computed using Eq. (5-8) from Elwood and Eberhard (2008)
utilizing the yield curvature determined from a moment-curvature analysis of the column not
accounting for confinement. Slip at ultimate strength, 𝑠𝑢 , was taken as 30 times the yield slip,
consistent with Zhao and Sritharan (2007). The values for initial hardening slope in the
monotonic slip versus bar stress response, b, and the pinching factor for the cyclic slip versus bar
The stress-strain response of the outermost longitudinal reinforcement at both ends of the column
was recorded during the OpenSees analysis. The strain history of the reinforcement was then
implemented in an existing low-cycle fatigue model that was used to estimate the point of
fracture of the outermost longitudinal bar based on the accumulated plastic strain. The low-cycle
fatigue model was implemented in Matlab, such that failure was determined through post-
Modeling of low-cycle fatigue was based on the Coffin (1954 and 1971) and Manson (1965)
formulation:
86
−𝑚
𝜀𝑝 = 𝜀0 (2𝑁𝑓 ) (4-11)
where εp is the plastic strain amplitude of each constant amplitude half cycle, ε0 is a material
constant that approximately indicates the plastic strain amplitude at which one half cycle will
cause failure, 2Nf is the number of constant amplitude half cycles to failure, and m is a material
constant that indicates the sensitivity between εi and Nf. Equation (4-11) may be re-arranged to
determine the number of constant amplitude half cycles at εp needed to reach failure:
𝜀𝑝
(−𝑚)−1 log( )
2𝑁𝑓 = 10 𝜀0 (4-12)
2𝑛𝑖
𝐷𝐼 = ∑ (4-13)
2𝑁𝑓
where 2ni is the number of half cycles at a specific value of εp, and 2𝑁𝑓 is determined for that
same value of εp using Equation (4-12). For an individual half cycle, 2ni = 1, such that the
damage of each half cycle is (2Nf)-1. When the accumulation of half-cycles causes the damage
index, DI, to exceed 1.0, fatigue failure occurs. Although rainflow counting is often used to
define full cycles, the use of half-cycles enables the analysis to progress sequentially without a
need for rainflow counting. In this case, a half-cycle is defined to be bounded by two load
reversals, such that the amplitude of a half cycle is one-half of the strain bounded by two load
reversals.
87
4.2. Results and Discussion
The method to compute the stiffness of each column, described in the previous section, was
validated to data from the column tests described in Chapter 4. The stiffness values from the
model and test data are provided in Table 4.1 for each test. The stiffness from test data was
consistent with the values in Table 3.13, which were determined from fitting a backbone model
to test data, as desribed in Section 3.2.3. It is evident from Table 4.1 that the model predicted the
stiffness with a percent error that was less than 25% for all tests. The average percent error was
2.04% in the positive direction (i.e., overprediction of stiffness). Given the level of variability in
stiffness observed in the tests, the use of this method to determine stiffness was deemed
appropriate.
Effective Stiffness
Column Name
Test [kip/in] Model [kip/in] % Error
C-#7(1.3)-0.05 77.5 89.63 15.65
C-#5(1.4)-0.05 95.53 98.19 2.78
C-#7(2.7)-0.05 103.715 115.65 11.51
C-#7(1.3)-0.05-EQ 82.34 89.63 8.85
C-#7(1.3)-0.05-X 92.465 89.63 -3.07
C-#7(1.3)-0.15 131.145 100.34 -23.49
The model was validated to the six columns tested in this study, which were described in Chapter
4. The fit between model and tests is provided in Figure 4.2. The model provided a reasonable fit
to the test data, with the exception of an underestimate of the strength for x and an overestimate
of the level of pinching in the load-deformation hysteresis of x. The model did not capture the
88
the jacketed region. The model prediction of fracture of the first longitudinal bar is indicated in
the figures. The model under predicted fracture for each of the six tests.
a) d)
b) e)
c) f)
Figure 4.2. Column Load-Deformation Response for Model and Tests: a) C(CFRP)-4.0-#7(1.3)-
0.05, b) C(CFRP)-4.0-#5(1.4)-0.05, c) C(CFRP)-4.0-#7(2.7)-0.05, d) C(CFRP)-4.0-#7(1.3)-0.05-
EQ, e) C(CFRP)-4.0-#7(1.3)-0.05-2X, f) C(CFRP)-4.0-#7(1.3)-0.15
89
5. Conclusions
Retrofit of reinforced concrete bridge columns with jackets is a commonly implemented strategy
to increase column ductility in earthquakes. Six FRP jacket retrofitted reinforced concrete bridge
columns were designed, constructed and tested. Five of the six columns were nominally identical
to a set of recently tested steel jacket retrofitted columns. Test variables included bar size of
longitudinal reinforcement, longitudinal reinforcement ratio, axial load ratio, and loading
protocol, with inclusion of a variable amplitude earthquake time history for one of the columns.
These test variables were selected due to the influence on the strain history in the longitudinal
reinforcement, as strength degradation in the test columns was expected to be due to fatigue
fracture of longitudinal reinforcement. The range of values for the test variables was intended to
reflect the range of variation of these parameters in the Washington State DoT inventory.
Using test results from the columns and reinforcement tests, a model was developed to estimate
the load-deformation response and fatigue fracture of longitudinal reinforcement in steel jacket
retrofitted reinforced concrete columns. The model consisted of a linear elastic element with a
plastic hinge at the base. The plastic hinge length included the gap between the bottom of the
steel jacket and the footing as well as additional length to account for bond slip of reinforcement
due to strain penetration into the footing and into the steel jacketed region. Strain history
determined from the model was used in an existing fatigue model to estimate the drift at fatigue
fracture of longitudinal reinforcement. The model was validated with existing test data.
90
The following conclusions on FRP jacket retrofitted reinforced concrete bridge columns were
reached:
Concrete damage is limited to the cover concrete at the top of the footing. Cracking
concentrated at the column-footing interface, and the crack at this location became wide
longitudinal reinforcement. The extent of spalling of cover concrete at the top of the
footing varied for the test columns, with the extent of damage most limited for the
Fracture of the first longitudinal bar in the test columns occurred during cycles at 12.5 or
15.0 times the yield displacement. Axial failure was reached for one of the test columns
upon fracture of the final longitudinal bar. This occurred at 20.0 times the yield
the load-deformation responses of the test columns. Strength degradation was primarily
Peak base moment on the column was larger by as much as 40% for the test column with
variable amplitude earthquake protocol. The largest excursions in the earthquake protocol
were associated with a significant reduction in strength upon the next occurrence of
reaching this drift level, and larger drift in the excursion was associated with a larger
reduction in strength. The level of strength drop observed for this test prior to bar fracture
was not observed in tests with fully reserved cyclic protocols prior to bar fracture, and
91
90% of column deformation was attributable to bond slip of longitudinal reinforcement.
The next greatest contribution was column sliding shear at the footing--column interface.
Flexure and shear deformation in the retrofit columns, beyond the plastic hinge region,
over a distance of 0.5” to 8.0” above the column base was significantly larger than
locations further up in the column. This was indicative of yielding, lack of composite
Lateral failure was defined to have occurred when the lateral load at a maximum cycle
peak first dropped below 20% of the peak lateral load and did not return to this level
during subsequent cycles. A maximum cycle peak is defined as a cycle peak that was
greater than or equal to any previous peak in that loading direction. Lateral failure
corresponded to fracture of the first longitudinal bar. All test columns reached 12.5 to
The predicted stiffness used in the model matched the measured stiffness from the test
columns with a percent error that was less than 25% for all tests and an average percent
92
References
ACI 374.2R-13 (2013). “Guide for Testing Reinforced Concrete Structural Element under
Slowly Applied Simulated Seismic Loads”. American Concrete Institute, Farmington Hills,
Michigan.
ACI 440.2R-17 (2017). “Guide for the Design and Construction of Externally Bonded FRP
Systems for Strengthening Concrete Structures”. American Concrete Institute, Farmington Hills,
Michigan.
Atwater, B. F., Nelson, A. R., Clague, J. J., Carver, G. A., Yamaguchi, D. K., Bobrowsky, P. T.,
Bourgeois, J., Darienzo, M. E., Grant, W. C., Hemphill‐Haley, E., Kelsey, H. M., Jacoby, G. C.,
Nishenko, S. P., Palmer, S. P., Peterson, C. D., and Reinhart, M. A. 1995. “Summary of Coastal
Geologic Evidence for Past Great Earthquakes at the Cascadia Subduction Zone.” Earthquake
Breña, S. F., and Schlick, B. M. (2007). "Hysteretic Behavior of Bridge Columns with FRP
Jacketed Lap Splices Designed for Moderate Ductility Enhancement." Journal of Composites for
Buckle, I.G. (1994). The Northridge, California Earthquake of January 17, 1994: Performance of
Engineering Research, State University of New York at Buffalo, Buffalo, NY, 136 pp.
93
Chai, Y.H., Priestley, M.J.N., and Seible, F. (1991). Seismic Retrofit of Circular Bridge Columns
Chai, Y.H., Priestley, M.J.N., and Seible, F. (1994). Analytical Model for Steel-Jacketed RC
EERI. (1994). Northridge Earthquake January 17, 1994, Preliminary Reconnaissance Report,”
No. 94-01, J. F. Hall, ed., Earthquake Engineering Research Institute, Oakland, Calif., 1994, p.
104.
Federal Highway Administration. (2006). Seismic Retrofitting Manual for Highway Structures:
Fung, G. G., Lebeau, R. J., Klein, E. D., Belvedere, J., and Goldschmidt, A. F. (1971). Field
Investigation of Bridge Damage in the San Fernando Earthquake. Technical Report, Bridge
209 pp.
94
Ghosh, K. K., and Sheikh, S. A. (2007). “Seismic upgrade with carbon fiber-reinforced polymer
of columns containing lap-spliced reinforcing bars.” ACI Structural Journal, 104(2): 227-236.
Goldfinger, C., Nelson, C. H., Morey, A. E., Johnson, J. E., Patton, J. R., Karabanov, E.,
Gutiérrez-Pastor, J., Eriksson, A. T., Gràcia, E., Dunhill, G., Enkin, R. J., Dallimore, A., and
Paleoseismicity of the Cascadia Subduction Zone, U.S. Geological Survey Professional Paper
1661–F, 170 p.
Haroun, M. A., and Elsanadedy, H. M. (2005b). "Fiber-Reinforced Plastic Jackets for Ductility
Enhancement of Reinforced Concrete Bridge Columns with Poor Lap-Splice Detailing". Journal
Huang, Y. and Mahin, S. A. (2010). “Simulating the inelastic seismic behavior of steel braced
frames including the effects of low-cycle fatigue.” PEER Report 2010/104, University of
95
Krawinkler H. (1992). Guidelines for Cyclic Seismic Testing of Components of Steel Structure,
Mander, J.B., Priestley, M.J.N., and Park, R. (1988). Observed Stress-Strain Behavior of
National Institute of Standards and Technology. (1990). Performance of Structures during the
Loma Prieta Earthquake of October 17, 1989. NIST Publication 778, Jan. 1990.
Padilla-Llano, D. A., Hajjar, J.F., Eatherton, M.R., Easterling, S.W., and Schafer, B.W. (2018).
“Cyclic fracture simulation framework for stability and collapse simulation in steel structures,”
Priestley, M. J. N., and Seible, F. (1991). "Seismic assessment and retrofit of bridges." Struct.
Sys. Res. Pro)., Rep. No. SSRP·91/103, University of California at San Diego, Calif.
Priestley, M.J.N., Seible, F., Xiao, Y., and Verma, R. (1994a). Steel Jacket Retrofitting of
96
Priestley, M.J.N., Seible, F., Xiao, Y., and Verma, R. (1994b). Steel Jacket Retrofitting of
Reinforced Concrete Bridge Columns for Enhanced Shear Strength—Part 2: Test Results and
Uriz, P., and Mahin, S.A. (2008). Toward Earthquake-Resistant Design of Concentrically Braced
Steel-Frame Structures. PEER Report 2008/08, Pacific Earthquake Engineering Research Center,
Xiao, Y., and Ma, R. (1997). Seismic Retrofit of RC Circular Columns Using Prefabricated
97