OPC-30GU
DIGITAL PARTS FEEDER
CONTROLLER
USER MANUAL
ORAND CO., LTD
[Table of Contents]
1.Wiring ……………………………………………………………… 3
2.Basic adjustment of Panel ………………………………………… 5
2.1 Names and functions of panel ……………………………… 5
2.2 Operation and Stop …………………………………………… 6
2.3 Frequency setting ………………………………………… 7
2.4 Voltage setting ……………………………………… 7
2.5 ON DELAY, OFF DELAY, SLOW UP, SLOW DOWN time setting …… 7
2.6 Function and setting range of each VR ……………………… 8
3.Operation sequence after the initial connection to
vibrator ………………………… 9
4.Additional functions ………………………………………………… 10
4.1 External input operation/stop control(EXS) ………………… 10
4.2 Over-flow sensor control(SN) …………………………… 10
4.3 External output voltage control(EX_VR: external VR/DC 0~5V) 11
4.4 Operation synchronized output signal (SYNC) ……………… 11
5.Product Specifications …………………………………………… 12
6.Protection and alarm function ……………………………………… 12
·Outline Drawing ……………………………………… 13
·Wiring diagram of Interlock operation of BOWL Feeder and Hopper 14
- 1 -
Precautions
● Do not use this product to parts feeder of piezoelectric method
● Never use this product in a place where there are ignitable materials or
inflammables
There is a risk of an explosion or a fire
● Do not use this product in a place where there are a lot of dust or moisture
This product is not dustproof or waterproof. Particularly, a separate measure
for protection is required in a place where there are a lot of metal powders.
● Do not turn on/off input power frequently.
It may cause a failure by remarkably deteriorating internal electronic
components. Particularly, avoid using the on/off control method on the parts
feeder by intermitting the input power of this product with a magnetic switch
(Relay)(It is necessary to use an external signal control method using an EXS
terminal).
● Do not turn on/off this product in the output part.
It is because the controller is damaged when the driving part is
operated/stopped by inserting the magnetic switch (RELAY) in the output part(It
is necessary to use an external signal control method using an EXS terminal).
● Do not perform welding process on the FEEDER in the state that the driving part
is connected to the controller.
The leak current on welding may damage the controller.
● Do not use the output of the PWM inverter as an input power of this product.
It may cause damage of this product.
● Use this product within rated voltage and rated current of input/output power.
● Do not disassemble, repair and convert this product carelessly.
It may cause damage or malfunction of this product.
● Perform wiring work when power is turned off.
There is a possibility of product damage or an electric shock.
● Connect the ground terminal of the input/output power to the ground necessarily.
It prevents the electric shock in the leakage of electricity and reduce power
noise.
- 2 -
1.Wiring
Wiring between the controller and feeder is roughly shown as below.
OPC-30GU
RUN TRIP
FRQM ONDLY SLUP
FRQS OFDLY SLDN
ON
VOLTAGE
OFF
PARTS FEEDER CONTROLLER
Front cover
< Additional function >
▷ Input terminal
. External operation/stop signal
(+12,EXS, GND)
. Connecting external VR for Voltage
Input power adjustment purpose (EX_VR)
(AC 100V~240V 50~60Hz) ▷ Output terminal
. Operation synchronizing signal(SYNC)
Output power
Overflow Sensor
Bowl/Linear/Hopper Feeder
- 3 -
Internal connector connection shall be carried out in the following order.
① Take off the front cover where outlet of controller's connection cable is located.
② Referring to following figure, connect input/output power and its necessary
additional equipment.
③ Arrange them for the cable so as to come out from the cable outlet of front cover
and attach the taken-off cover.
External input output
power control Built-in/external VR selection jumper
terminal [Page 11] .IN:Built-in VR EX:external VR
.External VR or
0~5V control
FG Frame Ground
EX_VR OUTB Output power terminal
Display Panel . Controlled PWM AC power
OUTA
Connector DISPLAY output
terminal INB
.For Input power terminal
manufacture .220/110V Free Voltage
INA
FUSE
Operation synchronized signal
output signal [Page 11]
.NC,NO contact point output
External input operation/stop signal
terminal [Page 10]
Overflow sensor type Overflow sensor input terminal
(NPN/PNP) setting [Page 10] [Page 10]
.NPN at shipment
As this product is designed for AC100V~240V and FREE - VOLTAGE, it can be
used for input power without mechanical or electrical setting change.
<Notice>
1. When the cover is taken off, isolate the input power necessarily.
2. (FG:Frame Ground) for input and output power terminals shall be connected
necessarily for the prevention of electric short and stable operation.
3. Operation shall be carried out only when the cover is closed completely.
- 4 -
2. Basic adjustment of Panel
2.1 Names and functions of panel
6.TRIP LED
.Lighting on in case of over current
.Flickering in case of over heated
1.RUN LED
.Lighting on in case of run
.In case of stop by external
signal control OPC-30GU
1:10 cycle flickering 7.ON DELAY volume
RUN TRIP .Setting delay time from sensor
.In case of stop by external
sensor control ON to operation start
10:1 cycle control (0.1~10.0Sec, 0.1Sec unit)
2. Frequency major control volume 8.SLOW UP time setting volume
.0.1~3.0Sec, 0.1Sec unit
FRQM ONDLY SLUP
3.Frequency minor control volume 9.SLOW DOWN time setting volume
.0.1~3.0Sec, 0.1Sec unit
FRQS OFDLY SLDN
4.OFF DELAY volume
.Setting delay time from sensor OFF
to operation stop
(0.1~10.0Sec, 0.1Sec unit) ON
10.Voltage adjustment VR
5.Power switch .Used for voltage adjustment
VOLTAGE
OFF
PARTS FEEDER CONTROLLER
- 5 -
2.2 Operation and Stop
1. Locate FRQM VR at right side as a maximum location, and FRQS and VOLTAGE VR at the
interim to turn on switch.
RUN TRIP
◆ Initial status after turning power switch on
.RUN status: In case that external input operation FRQM ONDLY SLUP
VOLTAGE
/stop signal(EXS) is ON(Active)
In case that power switch is turned off FRQS OFDLY SLDN
when running
.STOP status: In cases other than above running conditions
2.By adjusting FRQM and FRQS VR, fix to the resonant frequency where the vibration
can be maximized.
※Please refer to frequency setting method (Page 7).
3. By adjusting voltage with VOLTAGE VR, fix the magnitude of vibration.
※Please refer to voltage setting method (Page 7).
VOLTAGE
4. Repeat procedures of 2~3 shown above to search an optimum point.
5. After completing operation, turn off power switch.
ON
I
O
OFF
◎ If RUN LED lights on, but Parts Feeder is not vibrated, please check followings.
① Is voltage set to be "0" or too low?
→ Set voltage properly.
Adjust with VOLTAGE VR.
② Is frequency deviated from resonant frequency too much?
→ Change frequency to set frequency where strong vibration can be felt.
Adjust with FRQM and FRQS VR.
③ Is it in error status?
→ Take countermeasures against error as per the contents guided by TRIP LED.
- 6 -
2.3 Frequency setting
1.Change frequency with FRQM VR.
◆'FRQM' : if turn left, frequency goes down. FRQM ONDLY SLUP
if turn right, frequency goes up.
FRQS OFDLY SLDN
2. Adjust frequency minutely with FRQS VR.
FRQM ONDLY SLUP
FRQS OFDLY SLDN
2.4 Voltage setting
1.Change voltage with VOLTAGE VR.
◆'VOLTAGE' : if turn left, voltage goes down.
if turn right, voltage goes up.
VOLTAGE
2.5 ON DELAY, OFF DELAY, SLOW UP, SLOW DOWN time setting
1.Change time with ONDLY, OFDLY, SLUP and SLDN VR.
◆'VR' : if turn left, time decreases. FRQM ONDLY SLUP
if turn right, time increases.
FRQS OFDLY SLDN
- 7 -
2.6 Function and setting range of each VR
Default
Setting(VR) Description of functions setting range at
shipment
FRQM □ Frequency adjustment
40~160Hz 160Hz
RFQS □ Frequency minute adjustment
□ Sensor input On Timer(Sensor Control On Timer) 0.1~10.0 Sec
ONDLY .Setting time from input On to operation start (0.1Sec unit)
0.1
□ Sensor input Off Time(Sensor Control Off Timer) 0.1~10.0 Sec
OFDLY .Setting time from input Off to operation stop (0.1Sec unit)
0.1
0.1~3.0 Sec
SLUP □ Slow up(Soft Start) time setting
(0.1Sec unit)
0.1
0.1~3.0 Sec
SLDN □ Slow Down(Soft Stop) time setting
(0.1Sec unit)
0.1
- 8 -
3.Operation sequence after the initial connection to vibrator
This explains the setting flow when operating at the first time after connecting to
the vibrator. For details, please refer to related pages.
1.Adjustment of vibration
point
Fit physical natural frequency of page Adjust FRQM, FRQS VR at the state of
vibrator to electrical driving frequency 7 fixed voltage
so that the greatest vibration can be
made in a same voltage.
2.Adjustment of vibration
amplitude Adjust in an appropriate manner only with
page
Adjust the vibration amplitude so voltage while checking worker's moving speed
7
that moving speed of worker can be
optimized in the resonance frequency.
3.Setting of
.SLOW-UP/DOWN(SOFT-START/STOP) time
additional functions page .ON/OFF delay time of Over flow
10
~11 function
.speed control by external signal,etc
4.Normal operation
- 9 -
4.Additional functions
4.1 External input operation/stop control(EXS)
It is possible to carry out operation/stop control by contact point input or voltage input.
※ When operation is stopped by this function, RUN LED is flickering at 1:10 cycle.
Contact point input OC input voltage input
EX_VR GND GND GND DC 12~24V
EXS EXS EXS
+12 +12 +12
Condition Status
Contact CLOSE RUN
point input OPEN STOP
Voltage +12(24)V RUN
input 0V STOP
4.2 Over-flow sensor control(SN)
Run/temporary stop control due to overflow during operation
◆ Jumper setting : NPN/PNP Jumper Cap position ('NPN' at shipment)
※ When operation is stopped by this function, RUN LED is flickering at 10:1 cycle.
This functions only when EXS control is placed at operation status.
Contact point connection Sensor connection
EX_VR BROWN
+12 +12 DC12~24V
BLUE
GND GND OV
BLACK
SN SN OUT
(*Note)
PSN40-20□□ (*Note)
DN : NPN NO Type
DN2 : NPN NC Type
DP : PNP NO Type
DP2 : PNP NC Type
(*Note)Instance of Autonics proximity sensor
NPN NPN setting(at shipment)
PNP
NPN ◆ Movement Timing Chart
PNP
PNP setting
OVF Sensor Not detected Detected Not detected
Controller Run Stop Run
Jump cap for NPN/PNP setting
OFF Delay ON Delay
- 10 -
4.3 External output voltage control(EX_VR: external VR/DC 0~5V)
Control output voltage by using external VR connection or control voltage of 0~5V
◆ External VR connection control
. In case of external VR connection, voltage control from OP is forbidden automatically.
◆ 0~5V external voltage control
. In case that the impedance of control power is very high when 0V is supplied, it is
recommended to connect the fixed resistance higher than 10KΩ 1/8W as illustrated below.
※As the controller may be damaged when external control voltage exceeds 5V, voltage not higher
than 5V shall be applied.
Built-in/External VR External VR
setting purpose jumper cap Built-in
VR
EX_VR
External VR connection
③ ①
3 ②
2 ②
③
1 ①
10KΩ-B
5051-03 MOLEX
DC 0~5V external voltage control
③
3 V
②
2
1 ① 10K 1/8W
(Recommended) DC 0~5V control voltage
5051-03 MOLEX
4.4 Operation synchronized output signal (SYNC)
Output contact signal according to operation and suspension of controller
.Use it on connected operation between Hopper and Bowl Feeder
Status of Output
controller
Operation CLOSE
EX_VR Suspension OPEN
GND
EXS
+12
SYNC Level
GND
Sensor
SN
Bowl Feeder Hopper Feeder
* Hopper can be moved
only if Bowl Feeder is
Example of connected operation between Hopper and Bowl Feeder
being operated.
- 11 -
5.Product Specifications
Items OPC-30GU Remarks
Rated input
.AC100V~240V 50~60Hz
.Free Voltage
setting method Built-in VR or external VR
Voltage setting range 0V~240V
setting angular resolution 1V
Out setting method Built-in VR
put
Frequenc
y setting range 40~160Hz
setting angular resolution 0.1Hz
Max. allowable current 5A
Driving method PWM type
Control type Full digital control by RISC CPU
External input .on/off control(PLC, etc) by external input
.Dry/Wet contact (12V,24V)
Run stop .Temporary stop/operation at the status of over flow
control
.Dry/Wet contact(12V, 24V)
Control Sensor input .On Delay Timer setting : 0~10.0sec,0.1sec unit
.Off Delay Timer setting: 0~10.0sec,0.1sec unit
.Sensor power : DC12V 100mA
Operation synchronizing
signal 2 terminals output(SYNC)
Soft Start 0.1~3.0 Sec setting(0.1s unit, volume adjustment)
Soft Stop 0.1~3.0 Sec setting(0.1s unit, volume adjustment)
Indication of operation status .Indicated
Operation, external signal control stop, sensor control stop
by lighting on and flickering cycle of RUN LED
Protection function Operation stop and alarm in case of over current, over
Alarm method TRIP LED lighting on, flic
Cooling method Natural air cooling
Surrounding 0 ~ 40℃
Condition temperature
for use Surrounding
humidity 10 ~ 90%
Weight 1.2 Kg
Spec
Dimension 61(W)×115(D)×150(H)
6.Protection and alarm function
This product is designed specifically so that when Error is being occurred due to
carelessness of user or an environmental factor, a protecting function will be operated,
Error Code will be displayed on display window and alarm will sound for protection of
product.
※ Contents of error and its measure according to ERROR CODE shall be as follows.
TRIP LED Contents of error Measures
Flickering □ Over Heat Error .Turn off POWER, remove an overheating factor, wait
.Internal Heat-Sink is overheated certain time for natural cooling
□ Over Current Error
Lighting on .Over Current exceeding its capacity .Turn off POWER, remove an Over Current factor
flows
- 12 -
[Outline Drawing]
61.0
30.5 10.0 115.0
φ5.5
10.0
OPC-30GU
RUN TRIP
FRQM ONDLY SLUP
FRQS OFDLY SLDN
150.0
166.0
180.0
ON
VOLTAGE
OFF
PARTS FEEDER CONTROLLER
- 13 -
[Wiring diagram of Interlock operation of BOWL Feeder and Hopper]
·
Hopper will work only when operating Bowl Feeder.
Level For BOWL FEEDER
Sensor
BOWL FEEDER
FG
OUTB
SYNC OUTA
GND (*Note))INB
OVF EXS
BRN INA AC INPUT
Sensor +12V BLU
100V~240V
GND BLK
SN
OUT-AC
For HOPPER
HOPPER
FG
OUTB
SYNC OUTA
GND INB
EXS INA
BRN AC INPUT
+12V
BLU 100V~240V
GND BLK
SN
(*Note)
OUT-AC
(*Note)Autonics
Example of proximity switch
- 14 -
Product Warranty
Orand Co., Ltd warrantees this product as specified below.
Parts Feeder
Product Name Model No. OPC - 30GU
Controller
Date of Serial No.
Purchase
Service without charge
Services will be given without charge only when the product has been used in
accordance with the conditions, methods and precautions specified in this user
manual and the product has been wrong due to defects in design, material and
manufacturing.
The warrantee period is one year from the date of purchase, and when a separate
warranty period is agreed, the warranty period shall be in compliance with it.
Service with charge
1. Failure due to consumes' fault
● Failures due to consumers' carelessness, disassemble, repair or convert
● Failures due to incorrect usage that differs from the usage condition, usage
method and precautions specified in this user manual
● Failures due to repair by the person who has not been approved as a repair
engineer by Orand Co., Ltd
2. Failure due to natural disaster
● Failures due to fire, earthquake, flood, etc
※ The contents of this user manual may be changed without notice for improvement
of the product function.
Orand Co., Ltd
No.911 2nd Daeryung Posttower
182-13 Guro 3-dong, Guro-gu, Seoul
Tel +82-2-2082-1270~3
FAX +82-2-2082-1274
- 15 -
Orand Co., Ltd
W W W . O R A N D. C O . K R
Address : No.911 2nd Daeryung
Posttower182-13 Guro 3-dong,
Guro-gu, Seoul
TEL : +82-2-2082-1270~3
FAX : +82-2-2082-1274
*The contents of this user manual may be changed without notice for improvement
of the product function.
2008.08 edited