Concrete Prelim
Concrete Prelim
AGGREGATES
Fine aggregates - pass through sieve #4
Coarse aggregates - retained by sieve #4
• Nominal max size - 1/5 narrowest dimension, 1/3 depth of slab, 3/4 clear spacing
WATER
• must be potable
STEEL REINFORCEMENT
• shall be deformed, plain reinforcement shall be for spirals or prestressing
• welding shall conform to Structural Welding Code - Reinforcing Steel
DEFORMED REINFORCEMENT
• ASTM A615M - resisting member
• ASTM A706M - resisting earthquake
• ASTM A1035 - spiral reinforcement
• ASTM A184M - bar mats
PLAIN REINFORCEMENTS FOR SPIRAL
• ASTM A615M, bars
• ASTM A706M, bars
• ASTM A82M, wires
. Proportioning & Mixing Of Concrete
• shall be proportioned to provide workability, consistency, resistance, and strength.
• Ready-mixed concrete shall be mixed and delivered (ASTM C94M & ASTM C685M)'
• Job-mixed concrete - shall be mixed continuous for at least 1 - 1/2 (ASTM C94M)
ADMIXTURE - used as an ingredient of concrete and added to concrete before or during its mixing.
Conveying, Placing, Compacting, Curing
• conveyed from mixer to place of final deposit by methods that will prevent separation
• CONVEYING- shall be capable of providing a supply of concrete at site
• PLACING- shall be deposited as nearly as practicable in its final position
• defined by its boundaries or predetermined joints, except as permitted by SECTION 406.4
• COMPACTING- thoroughly consolidated by suitable means during placement
• CURING- shall be maintained above 10 degrees Celsius; except when cured SECTION 405.12.3
• ACCELERATED CURING- curing by high-pressure steam; may be employed to accelerate strength; shall provide
a compressive strength at the load stage
Design of Formwork
• forms shall result in a final structure that conforms to shape; shall be substantial and sufficiently tight to prevent
leakage of mortar; shall be properly braced or tied.
Considerations:
1. Rate and method of placing concrete
2. Construction loads
3. Special form
Removal of Forms, Shores and Reshoring
• forms shall be removed in such a manner as not to impair safety and serviceability of the structure
• REMOVAL OF SHORES & RESHORING (SECTION 406.2.2.1 - 406.2.2.3) - shall apply to slabs
and beams
• Contractor shall develop a procedure and schedule for removal of shores
1. Structural analysis and concrete strength data used in planning and implementing form removal
2. No construction loads shall be supported on
3. Sufficient strength shall be demonstrated by structural analysis considering proposed loads
Conduits and Pipes Embedded in Concrete
• Conduits & pipes of aluminum shall not be embedded in structural concrete unless effectively coated or covered to
prevent
• shall not be larger in outside dimension than 1/3
• Not exposed to rusting; not thinner than standard schedule 40 steel pipe
• nominal inside diameter not over 50 mm and are spaced not less than 3 diameters on centers
Conduits and Pipes Embedded in Concrete
• shall be so fabricated and installed that cutting, bending or displacement of reinforcement from its proper location will not be required
Construction Joints
• shall be cleaned and laitance removed immediately before new concrete is placed
• Shall be made for transfer of shear and other forces through construction joints (SECTION 411.8.9)
• Shall be located within the middle third of spans of slabs, beams, and girders.
Tests, Quality Control, Inspection
• shall be made in accordance with the standards (SECTION 403.9)
• For 2 years after completion of the project or as required by implementing agency an preserved by the engineer for that purpose
Sampling
• elapsed time shall not exceed 15 min
• Transport the individual samples to the place where fresh concrete tests are to be performed; shall be combined and remixed with a shovel
• obtained these portions within the time limit specified in section 4
Procedure
• the size of samples shall be dictated by the maximum aggregate size
• NOTE 2 should normally be performed as the concrete is delivered from the mixer
• NOTE 4 the containers may have to be supported above the subgrade
Tests of Materials
• take samples by whichever of the procedures described in 5.2.1. - 5.2.3 most applicable under the given conditions
1. Concrete Strength in Compression - typically measured by its Compressive strength denoted as fc’
• Typical Values (25-40 MPa)
forde
P = maximum applied load
L = length of the span
b = width of the beam
d = depth of the beam
10 mm
-
↑ 10mm
D 200 mm
d 200 mm ↑ 12 mm - 12 mm
• 407.6.3 - shall be bent cold welded five fabric used in slabs not exceeding 3m in span
• 407.6.4 - welding of crossing bars shall not be permitted for assembly
• 407.7 SPACING LIMITS FOR REINFORCEMENT
• 407.7.1 - shall be db but not less than 25 mm. Section 403.4.2
• 407.7.2 - placed in two or more layers, upper layers shall be placed directly above bars in the bottom layer with clear distance between
layers less than 25 mm.
• 407.7.3 - shall not be less than 1.5 db or less than 40 mm.
• 407.7.4 - shall apply also to the clear distance between a contact lap splice
• 407.7.5 - shall not be spaced farther apart than three times the wall or slab thickness, nor farther than 450 mm
• 407.7.6 BUNDLED BARS
• 407.7.6.1 - shall be limited to four bars in one bundle
• 407.7.6.2 - shall be enclosed within stirrups or ties
• 407.7.6.3 - larger than 36 mm shall not be bundled in beams
• 407.7.6.4 - shall terminate at different points with at least 40db stagger
• 407.7.6.5 - shall be treated as a single bar of a diameter from the equivalent total area
• 407.7.7 PRESTRESSING TENDONS AND DUCTS
• 407.7.7.1 -closer vertical spacing and binding of tendons shall be permitted in the middle portion of a span
• 407.7.7.2 - to prevent the tendons from breaking through the duct.
• 407.8 CONCRETE PROTECTION FOR REINFORCEMENT
• 407.8.1 CAST-IN PLACE CONCRETE (NONPRESTRESSED)
• MINIMUM COVER
1. Concrete cast permanently exposed to earth —————75mm
2. Concrete exposed to earth or weather——————50mm
3. Concrete not exposed to weather ——————40mm
a. SLABS, WALLS, JOINTS
42 mm3 58mm bars ————— 40mm
36 mm
3 smaller —————20mm
b. TIES, STIRRUPS, SPIRALS ————40mm
c. SHELLS, FOLDED PLATE MEMBERS
20mm bar larger
—————20mm
16 mm bar . MW200 or MD 200 wire and smaller —————12mm
• 407.8.2 PRECAST CONCRETE (MANUFACTURED UNDER PLANT CONTROL CONDITIONS)
• MINIMUM COVER
1. Concrete cast permanently exposed to earth —————75mm
a. WALL PANELS
4) Imm bar3 58 mmbars —————40mm
36 bar and smaller MV200 or MD 200 ———20mm
b. O. THER MEMBERS
42358 larger than 40mm 50mm
20
Prestressing tendons 40mm and smaller mm
20 mm bar b larger 15 mm
c. Epoxy-coated————72db •
•
407.11.5.5 - four directions into a column
407.11.5.6 - placed in the top of columns or pedestals
d. Plain coated with standard stirrups—————48db • 407.13 SHRINKAGE & TEMPERATURE REINFORCEMENT
• 407.13.1 - shall be provided in structural slabs where the flexural extends in one direction only.
e. Epoxy-coated with standard stirrups—————48db • 407.13.1.2 - temperature restrained
• 407.13.2.1 - area of shrinkage
1. Slabs where grade 280 and 530 deformed bars are used ————— 0.0020
2. Slabs where grade 415 deformed bars or welded wire fabric ——————— 0.0018
3. Slabs with yield stress exceeding 415 MPa at a yield strain of 0.35% —————— 0.0018x415fy
CHAPTER 2
MINIMUM DESIGN LOADS
NSCP 2010
Static force procedure
v
WADS
R =
r (A 15) 74
-
.
8kPa DL
Minimum
5Ca
2 .
v =
LL
P not exceed 100%
# 23 1 .
/I +
,
WL Measures using mg
(
See section 207 for design wind loads
SEISMICL
mi ZON
OTHER &
See section 206.7 for ponding loads
See section w08 for earthquake loads
2015 version has different formula
Wihi(v)
See section 206.9.3 for impact loads-
Fi
wind +Go
=
1.2D + 1.0E+f1 L
O.9D+1.6W+1.6H
0.9D+1.0E+1.6H
where: f1 = 1.0 for floors in places of public assembly, for live loads in
excess of 4.8 kPa, and for garage live load
= 0.5 for other live loads
203.3.2 Other Loads SECTION 205 LIVE LOADS
Where P is to be considered in design; factored as 1.2P. Live loads shall be the maximum loads expected by the intended
203.4 Load Combinations Using Allowable Stress Design use; shall be less than the loads required by this section.
203.4.1 Basic Load Combinations 205.2 Critical Distribution of Live Loads
shall resist the most critical effects resulting from the following shall be designed using the loading conditions, which would cause
combinations of loads: maximum shear and bending moments.
D+F
D+H+F+L+T 205.3 Floor Live Loads
D + H + F + (Lr or R) shall be designed for the unit live loads; shall be taken as the
D+ H + F +0.75[L + T + (Lr or R)]
D + H + F + (W or E/1.4) minimum live loads of horizontal projection; shall be assumed for
No increase in allowable stresses shall be used with these uses that creates or accommodates similar loadings.
load combinations • the actual live load will be greater than the value shown in
203.4.2 Alternate Basic Load Combinations Table 205-1; shall be used in the design of such buildings or
using these alternate basic load combinations, a one-third increase portions thereof; shall be made for machine and apparatus
shall be permitted in allowable stresses for all combinations, including loads.
W or E. 205.3.2 Distribution of Uniform Floor Loads
D + H + F + 0. 7 s[ L + Lr + ( W or E/1.4)] consideration may be limited to full dead load on all spans in; full
0.60D+W+H
0.60D + E/1.4+H live load on adjacent spans and alternate spans.
D + L+ Lr (or R) 205.3.3 Concentrated Loads
D+L+W
D +L+ E/1.4 designed to support safely the uniformly
203.4.3 Other Loads • shall be made in areas where vehicles are used for
Where P is to be considered in design, each applicable concentrated loads, L, consisting of two or more loads spaced
load shall be added to the combinations 1.5 m nominally on center without uniform live loads. Each load
203.5 Special Seismic Load Combinations shall be 40% of the gross weight of the maximum size vehicle
shall be used as specifically required by Section 208, or by Chapters to be accommodated.
3- 7. • Parking garages shall have a floor system designed not less
1.2D+f1L+1.0Em than 9 kN acting on an area of 0.015 m^2 without uniform
0.9D± 1.0Em
live loads.
where:
205.3.4 Special Loads
f 1 = 1.0 for floors in places of public assembly, for live
shall be made for the special vertical and lateral loads as set forth
loads in excess of 4.8 kPa. and for garage live load.
in Table 205-2.
= 0.5 for other live loads
Em = the maximum effect of horizontal and vertical forces
Section Properties by
I
↓
I
① NA
①
-1 ,
bf he
14 Y d+
b
-
:
② d tw 2
ye
wee
Ay behotdtw =
Yule
:
I /RL
tw
② Locate Neutral Axis
A = LW
Y Ay Teg Adh
FogLw3 beh(d + )
Flexure/Bending
dth
* zAy
d tw
=
+
behf(d +
He
(4) atw))
+
hb by
tod
3
5
:
Ma solve
for i
Aty :
[Hiy :
<
Iy Ic =
,
+Ad
y
=
[Ay behe(d -) + d+ w()
+
At behf + dow
Problem 1
1200mm Y Ay
I /
bfhf (d +)
+
/ AREAS :
100 ① ①
/ ① 1200 (100)
② 300(800)
= 120,000
=
240000
800 + 0 =
850
100
)
(1200)/800 + : 102X10
800 ② w()
ATOTAL 360000
② d+
:
/
800-400
300450
I
450 Ay 198x10"
:
Z
?
T =
Ad
Tag byhs [y .
-
y]
Thebe 198x103
100
/1200)[850 550]" · = 1 . 08x10"
in (1200) (100)" = 100 N03 =
360008 dtw[j . ]
4x109
z two
Y 550
800(300) [530 800 5 .
=
:
·
3
12800x10 10.
in (300)(000) Ad 1 62
=
= x
.
+
=
d
y,
100
=
800 +
2
Y ,
=
850mm
Yz
=
y
-
-
=
550-800
2
Ye =
150mm
↑
,
u
,
500//
on a
1000
I
- 1
,
12
I I
150
30
A, 10 (100)
200'lsoI
= -
100 , ,
An :
190(12) :
1800
Ap =
2800
X
,
:
75 y , :30
Xv
: 75 42 : 6
I
Y
*
·
A :
80 (10) =
800
He =
20 (250) :
5000
As 15 (280) 4200
:
:
At =
10000
L 3
ommi
↑To
at
X =
90
y
=
125
⑤
#188 + 140 =
240
7.5 235- X 149 mm
25
=
+
Ex = Ad +
800 (59 75)2
.
= 20 .
42x104 mm
4
250
Ive
= + 5000 /144 75-125)
.
=
33 .
94x18"mmY
5
Ex = + 4700(164 .
75 -
242 .
5)
= 52 .
83 x100mmY
Ix = EEX
IX =
107 .
19x10"mont
500mm
150mm A,
- -
150mm 150mm
1000 mm
-14
Az
As zomm
A Y Ay
D 500 (10) 388 187 75 x10
.
6
② 200 (650) en
Ex
370, 00
EAY 491 .
22
,
Ay
d 8 78
50-y
= = .
da 3525 5 -
=
33 78.
FLEXURE/BEAM UNCRACKED SECTION ANALYSIS
b
Ec =
0 003
. fa
FOR RECTANGULAR SECTION
3
NA
le
# I TbD
:
o . bdc
Moment
As
⑧
T
I
Hi
fet
SECTION MODULUS
f- Mc ,
M Banding Stress
f fr
1
Y Internal will going to resist external
*
If the external moment is higher than
the internal moment = failure
* Limiting stress ——— Rupture Stress
Ex fr
fe
* The rebar won’t act
AJ E =
-
Me
j =
J
E
AG
9ae
C
=
Ke
k E
=
L = 3m
Mmax
8
goo mm Mmax =
jwI ; W
=
As Mr =
Mmax
convertIm 17 12 x
.
100 =
t (w)(3)
fe
:
Mc ;
M
:
fe W
=
15 .
22
KN/m
fo
=
fr :
0 7 .
21 : 3 21 .
MPa
c
=
400 :
200
1 :
it [200(400)3]
I =
1066 67 x10 "mm2 .
M = fr5 =
3 .
21(1066 67x10 .
C 200
Mr =
17 .
12 x 103
CRACKED SECTION - SLD
WORKING STRESS DESIGN
* The one who takes an action is the rebar
1b , 1 b Er SE
-
W
↓ 1/
Id
le
Moment
NA
⑨
A
d d /
jd
A nAS
-
1/ Es
1
d
ve e r r r r r r r r y
fet
1111111
M * Triangular because in the Neutral Axis there’s no value of C
Es
N
=
M-Cjd Tjd =
Fa
jd d -
Me
=
f = - steel ratio
j =
1 -
E
f= Ad
Locate NA solve K Internal Moment
EMA = Ax + Bx + C =
0 COMPRESSION
* fa
:
0 .
45jc
B2 4AC
kd(kd) nAs(d-kd)
X BE 0 5 fa
M Cjd
= -
= .
b
=
=
-
24 allowable suggested
c =
42bd" nAsd-nAskd
:
K : ·
In I
(en)
-o
half
2 =
M Efckjdb
42bd + nAsk-nAj k (n =
(fn)2 + 29
= -
=
0 TENSION
1-
2 bd M- Tid
=
2
+ nbdk -
nfdb =
0
3
T
Ass
-
+ Ink-fn =
0
for strength of steel
fo
=
0 6
.
Fy
= As fojd
M
M =
pbdfs'jd
*
M If , jbd
=
SINGLY REINFORCED CONCRETE SECTION (CRACKED)
b
↓ 1 Er fa =
j 1
led
,
↓
Compression concrete
d Id
Ma Cjd volume of triangle prism
gMoment
=
&
NA
d kd
Ag
8 T
d Y Es
Mc = fakdbid
Strain
fs/ 2
Mc :
Efekjbd
4d - d-kd /d foln-feldfold
:
LetR Efekj
:
Eg Es Mc =
Rbd Lowest safe moment
K
f 2 fr :
Tension Steel
da
:
Ms Tid
K
:
Mc :
Asfsid
I
K =
14 fe
nfc
Ab 201mm :
fc’ = 21 MPa
fy = 228 MPa Read # of bars - 5 .
44pcs
W =
15 KN/m
use 6 #16 Bars
.
-
80
-
6 00 2 00
/200
. .
40
30
2 773
.
2 667
.
Mmax 53 34 -
-
50
d 410
=
6 #16
I I
Required Section : d
/20
fe"0 15fc'
Mmax
9 45 MPa Sa
bd2
.
: .
used 2b increase do
:
or
Es
H=
Ea A
b 26" Mmax =
=
533433 1ax
&, ,
Eg
.
Encore
.
4b 33 19x100 mm
=
.
3
b
=
201 45 . mm
!
McRbd 2b 2202 45
d = = .
R =
Efek ; d =
404 90mm .
J
Try 200x410 OK
nice
mm
Mmax
j= 1 - As =
j d
=
410 mm
Esjd
0
j 1
391
.
=
-
= 0 87
53 34
.
=
-
?
:
1093 11mm
2
.
R =
fckj 136 80 8. .
110
R= 9 450 8
. .
= 607 MPa
PROBLEM: Find the moment capacity of the section shown
GIVEN:
fc = 9.45 MPa
fs = 136.80 MPa
n = 9.3 Transformed section
200mm
/b 200
=
/ I Is
,
d = 410 T NA
/
6 As
/
410 -
X
As =
6- #16 :
1206 mm ? FOR STEEL :
Locate the NA ; EMA =O r fs = 136 80 .
Mira
bx(z =
nAs 410 n= modulus strength ratio
x
dX
-
c =
: . ·
.
244 43mm
.
C= 400 165 -
57 =
.
.
2004 =
9 3 1206410-X
.
Mg : fo I
3/1206410
2
100 x =
9 . ·
9 3 1206 X
.
nC
06410 =
8
.
. .
- . .
=
-
165 5 .
mm 9 3244 43
.
.
d X
Ms 54X10N
-
58 mm
-
= .
4 10 -
165 57 . =
244 43mm .
Ms Mc
from f :
M ; M: S Use Mcapacity :
Mc
I Fog + Ad
= Neglect
Yebx+bx(x) + *g + NA (410
Moap 55 52 KN
x)
m
.
= .
F :
,
-
+ 9 31206
. .
1 =
972 . 69x10" mm4
FOR CONCRETE
fc = 9 45 MPa.
c = X
Mc : fF
C
9 45972 .
.
69x106
=
165 57 .
Mc : 55 .
52 x10"N -
mm
-
-100 &
X
-
I
la 1x2
600
700 -
X Ag 6 #20:
/ /
I you
Stresses/Bending Moment
↑ r2 =
314 15(b) =
1884 96 As
M ; Me-fc
.
.
5 =
nAs =
1884960 mm? SsT
Ms =
nC
CONC :
EMA NA O
300 x + 1000 300100
-
x 50 = nAs 700 ·
x
Me-fe ; =x
E
488 83x18"N
150x* + 70000 d
=
- mm
.
18849 6700- X
.
A
X 50- : .
STEEL :
X =
149 94mm .
100mm A
SsT
Ms =
i 2 700
= 149
.
94 = -
X
= :
74 97 mm
. &
X .
124(E)
X = X -
50 = 149 94.50
.
: 99 .
10 D
700 X =
700 149 94 :
550 86mm (D)
-
- .
.
SOLVING FOR I
I =
FaG + Ada
2 2
Ms Ma Under Reinforcement
Iz 300x1 + 100100" : + 700100X +As
-x) Moment :
+ 900 x x
, 700 Safe
Mcap 24x10"N
100) is + 700100)/2"t 153
"
i
= -
mm
300(A
.
=
+ 700 + 300 (A
°
I =
6797 84x10 - E