Product data sheet 3RM1001-1AA04
MOTOR STARTER 3RM1 SIRIUS DIRECT STARTER 500
V,
0,1-0,5 A,
24 V DC SCREW-TYPE CONNECTION SYSTEM
General technical data:
product designation Motor starter
Design of the product with electronic overload protection
Protection class IP IP20
Suitability for use / device connector 3ZY12 Yes
Installation altitude / at a height over sea level / maximum m 4,000
Ambient temperature
• during operating °C -25 … +60
• during transport °C -40 … +70
• during storage °C -40 … +70
Resistance against shock 6g / 11 ms
Resistance against vibration 1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz
Impulse voltage resistance / rated value kV 6
Conductor-bound parasitic coupling conductor-conductor 1 kV
SURGE / according to IEC 61000-4-5
Conductor-bound parasitic coupling BURST / according to IEC 2 kV / 5 kHz
61000-4-4
Conducted interference as high-frequency radiation according 10 V
to IEC 61000-4-6
Electrostatic discharge / according to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
3RM1001-1AA04 subject to modifications
Page 1/ 4 02/05/2013 © Copyright Siemens AG 2013
Field-bound HF-interference emission / according to CISPR11 Class B for the domestic, business and commercial
environments
Conductor-bound HF-interference emission / according to Class B for the domestic, business and commercial
CISPR11 environments
Insulation voltage / rated value V 600
Safety:
Safety device type / according to IEC 61508-2 Type B
Main circuit:
Operating voltage / rated value / maximum V 500
Operating frequency
•1 Hz 50
•2 Hz 60
Operating current / at 400 V / for AC / rated value A 0.5
Minimum load in % of l_M % 20
Active power loss / typical W 0.02
Adjustable response current
• of the current-dependent overload release A 0.1 … 0.5
Service power / for three-phase servomotors / at 400 V
• at 50 Hz kW 0 … 0.12
Control circuit:
Type of voltage / of the controlled supply voltage DC
Control supply voltage / 1
• for DC / rated value V 24
Operating range factor control supply voltage rated value
• for DC 0.8 … 1.25
Control current A 0.08
Input voltage / at the digital input / with signal <1>
• for DC V 19.2 … 30
Input current / at the digital input / for signal <1> / typical A 0.01
Installation/mounting/dimensions:
mounting position vertical, horizontal
Width mm 22.5
Height mm 100
Depth mm 141.6
Connections:
Design of the electrical connection
• for main current circuit screw-type terminals
3RM1001-1AA04 subject to modifications
Page 2/ 4 02/05/2013 © Copyright Siemens AG 2013
• for auxiliary and control current circuit screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
• solid 1x (0.2 ... 4 mm²), 2x (0.2 ... 2.5 mm²)
• finely stranded
• with conductor end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 2.5 mm²)
• for AWG conductors 1x (20 ... 12), 2x (20 ... 14)
Type of the connectable conductor cross-section
• for auxiliary contacts
• finely stranded
• with conductor end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1 mm²)
• for AWG conductors 1x (20 ... 14), 2x (20 ... 16)
Certificates/approvals:
General Product Approval Declaration of Test Certificates
Conformity
Type Test
Certificates/Test
Report
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
Cax online generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RM1001-1AA04/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RM1001-1AA04
3RM1001-1AA04 subject to modifications
Page 3/ 4 02/05/2013 © Copyright Siemens AG 2013
last change: Feb 4, 2013
3RM1001-1AA04 subject to modifications
Page 4/ 4 02/05/2013 © Copyright Siemens AG 2013