INPUT Location D&D: Main beam 1st Floor @internal support
Design mo 62 kNm fcu 30 N/mm² gc =
ßb 1 fy 460 N/mm² gs =
Span 3000 mm Comp cove 40 mm to main reinforcement
Height, h 400 mm Tens cover 48 mm to main reinforcement
Breadth, b 300 mm Side cover 35 mm to main reinforcement
Tens Ø 16 mm
Comp Ø 16 mm Section locCONTINUOUS SPAN
OUTPUT D&D: Main beam 1st Floor @internal support
d = 400 - 48 - 16/2 = 344.0 mm
(3.4.4.4) K' = 0.156 > K = 0.058 ok .
(3.4.4.4) z = 344.0(0.5 + (0.25 - 0.058/0.9)^½ ) = 320.1 < 326.8 mm
(Fig 3.3) fst = 438.1 N/mm²
As = 1E6 x 62 /320.1 /438.1 = 442 mm² .
PROVIDE 3 T16 tension steel = 603 mm²
(Equn 8) fs = 2/3 x 460 x 442 /603 = 224.8 N/mm²
(Table 3.11Comp mod factor = 1 + 0.390 /(3 + 0.390) = 1.115 < 1.5
(Table 3.10Tens mod factor = 0.55 + (477 - 224.8) /120 /(0.9 + 1.746) = 1.344 < 2
(3.4.6.3) Permissible L/d = 26.0 x 1.115 x 1.344 = 38.966 .
(3.4.6.1) Actual L/d = 3000 /344.0 = 8.721 ok .
. .