T100 Series
Electromechanical Time Switches
Project:
Location:
T100 Series Product Type:
The T100 Series Mechanical Time Switches are heavy-duty switches
that have the highest horsepower ratings in the industry for industrial, Contact/Phone:
commercial and residential applications. Model #:
Features
• Provides direct 24-Hour control of most loads
• Control electrical loads up to 40 Amps
• 1 to 12 ON/OFF operations each day
• Minimum ON/OFF times of 1 hour
• Manual override
• All models equipped with one ON and one OFF tripper
Ratings
Enclosure Type: See table
Knockouts:
Combination 1⁄2"- 3⁄4" nominal knockouts, one on T101R
back and on each side, and two on bottom
Switch Type: See table
Switch Rating: Each Pole
40 Amp Resistive, 120-480 VAC
40 Amp Tungsten, Inductive or 1000 VA Pilot Duty,
120-277 VAC
2 HP (24 FLA) 120 VAC
5 HP (28 FLA) 240 VAC single-phase
Power Input: 3 W Maximum
Operating Temperature: -40°F to 130°F (-40°C to 54°C) T104PCD82
Shipping Weight: Type 1 - 3 lbs. (1.4 kg)
Type 3R - 4 lbs. (1.8 kg)
Warranty: Limited 1 year
T101
Model with Model with Model with Type 3R Model with Switch Clock Hz Amps/ HP
Type 1 Steel Type 3R Steel Plastic Plastic Type 3R Type Motor Volts Pole Rating
Enclosure Enclosure Enclosure Enclosure with
See Through
Cover
T101 T101R T101P T101PCD82 SPST 125 60 40 2
T102 T102R T102P - SPST 208-277 60 40 5
T103 T103R T103P T103PCD82 DPST 125 60 40 2
T104 T104R T104P T104PCD82 DPST 208-277 60 40 5
T104-50 - - - DPST 208-277 50 40 5
T101B** - - - SPST 125 60 40 2
T105 - - - 1NO/1NC* 125 60 40 2
N/A T106R - - 1NO/1NC* 208-277 60 40 5
*Can be wired SPDT
**Separate Clock Motor Terminals
Energy Controls
T100 Series
Specification
The time switch shall be of the 24-Hour dial type, capable of permitting up to 12 ON/OFF operations each day. The time
switch shall provide a minimum ON/OFF time of 1 hour. The time switch shall be powered by ____________ (125)(208-
277) VAC,_________ (50)(60) Hz power supply. The time switch motor shall be a synchronous motor, which shall be
designed to withstand a minimum of 6000 volt transients. The time switch motor shall be connected to the supply
terminals with ring-type connectors and shall not require more than 3 Watts to operate the time switch. The time switch
mechanism shall be a snap-in design to provide ease of mechanism removal from the enclosure. The time switch
enclosure shall be a _______________(Type 1 steel)(Type 3R steel)(Type 3R plastic with see through cover) lockable
enclosure. The time switch enclosure shall provide a minimum of 31 cubic inches of wiring space and provide a non-
removable cover, which shall swing open a full 180 degrees. The time switch shall provide clear terminal identification on
a see-through non-curling terminal insulator. A visual indicator shall be provided in the time switch for inspecting clock
motor operation. The time switch contact blades shall be a one piece design with welded silver alloy contacts and shall
be designed to provide wiping action on contacts during operation to ensure reliable load switching. Terminal
connections shall be made using teeter-type terminal screws to provide secure connections for wire sizes up to #8 AWG.
Switch configuration shall be ______________ (SPST)(DPST) (1NO/1NC) with a switch rating each pole:
• 40 Amp Resistive, 120-480 VAC
• 40 Amp Tungsten, Inductive or 1000 VA Pilot Duty each pole, 120-277 VAC
• 2 HP (24 FLA), 120 VAC
• 5 HP (28 FLA), 240 VAC
The time switch shall be Agency Listed under Clock Operated Switches and shall be Intermatic model ________________
(See Model Numbers Listed).
Diagrams
Clock
Equipment Motor Equipment
Clock
Motor
Ground Ground
Equipment Clock
Motor
A 1 2 Ground
A 1 2
A 1 2 3 4
Neutral*/Line 2**
Neutral 208-277 VAC Neutral
120 VAC Input 120 VAC To
Input Input
Line 1 To Load Loads
Line 1
Line To Load *277V
**208V, 240V Model T103 DPST
Typical Wiring Diagram
Model T102 SPST Jumper
Model T101 SPST
Clock Clock
Equipment Motor Equipment Motor
Clock
Ground Ground
Equipment Motor
Ground A 1 2 3 4 A 1 2 3 4
A 1 2 3 4 208-277 VAC
Input Neutral*/Line 1**
120 VAC Neutral To N.0.
Input To N.0. *277 VAC Line 2
Load
To Line
Load
**208, 240 VAC
Neutral*/Line 1** Load Jumper
208-277 Model T106R (1 NO/1NC) See Note 3
VAC Input Line 2 Model T105 (1 NO/1NC) Jumper NOTES:
See Note 3 1. For Single Pole Normally Open Operation - See Diagram
NOTES:
1. For Single Pole Normally Open Operation - See Diagram 2. For Single Pole Normally Closed operation - move motor lead from Terminal 3
*277VAC to Terminal 2. Connect LINE to Terminal 2 and LOAD to Terminal 1.
2. For Single Pole Normally Closed operation - move motor lead from Terminal 3 3. For Single Pole Double Throw operation - install JUMPER between Terminals 2
**208, 240VAC to Terminal 2. Connect LINE to Terminal 2 and LOAD to Terminal 1.
Model T104 DPST 3. For Single Pole Double Throw operation - install JUMPER between Terminals 2
and 3; Connect LINE to Terminal 2; N.O. LOAD to Terminal 4 and N.C. LOAD to Terminal 1.
Connect COMMON to Terminal A.
and 3; Connect LINE to Terminal 2; N.O. LOAD to Terminal 4 and N.C. LOAD to Terminal 1.
Connect COMMON to Terminal A.
7 ¾" 9 3⁄8 "
[19.69 cm] 9 3⁄8 " [23.81 cm]
[23.81 cm]
3" 3 5⁄8 " 4" [10.16 cm]
5" [7.62 cm] 5 ½" [9.21 cm] 5 ½"
[12.70 cm] [13.97 cm] [13.97 cm]
Type 1 Steel Type 3R Steel Type 3R Plastic
Energy Controls www.intermatic.com