0% found this document useful (0 votes)
239 views57 pages

Innova 6 10K User Manual Draft

The user manual for the Innova 6-10K Tower Online UPS provides essential safety, installation, operation, and maintenance instructions for the device. It details specifications, features, and troubleshooting guidelines to ensure proper usage and reliability of the UPS. The manual emphasizes the importance of qualified personnel for installation and servicing to prevent hazards associated with electrical equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
239 views57 pages

Innova 6 10K User Manual Draft

The user manual for the Innova 6-10K Tower Online UPS provides essential safety, installation, operation, and maintenance instructions for the device. It details specifications, features, and troubleshooting guidelines to ensure proper usage and reliability of the UPS. The manual emphasizes the importance of qualified personnel for installation and servicing to prevent hazards associated with electrical equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 57

USER MANUAL

ONLINE UPS
INNOVA 6-10K TOWER
NOTE:
1. Safety and EMC Instructions .............................................................. 1
1.1 Installation........................................................................................ 1
1.2 Operation ......................................................................................... 2
1.3 Maintenance, servicing and faults................................................... 2
1.4 Transport ......................................................................................... 3
1.5 Storage ............................................................................................ 3
1.6 Standards ........................................................................................ 4
2. Description of Commonly Used Symbols ......................................... 5
3. Introduction .......................................................................................... 6
3.1 Feature ............................................................................................ 6
3.2 Electrical specifications ................................................................... 7
3.3 Operating Environment ................................................................... 8
3.4 Typical backup time (Typical values at 25°C in minutes)................ 9
3.5 Dimensions and weights ................................................................. 9
4. Installation .......................................................................................... 12
4.1 Moving to the installation site ........................................................ 12
4.2 Unpacking and inspection ............................................................. 12
4.3 Input and output power wires and protective earth ground
installation............................................................................................ 13
4.4 Operating procedure for connecting with the external battery...... 17
4.5 EPO Connection............................................................................ 18
5. Operation............................................................................................. 19
5.1 Display Panel................................................................................. 19
5.2 Operating mode............................................................................. 22
5.3 Turning on and Turning off UPS.................................................... 28
5.4 LCD operation ............................................................................... 29
6. Special function.................................................................................. 40
6.1 HE function .................................................................................... 40
6.2 Converter function ......................................................................... 41
6.3 Parallel function ............................................................................. 41
7. Trouble Shooting................................................................................ 47
7.1 Trouble Shooting According To Warning Indication ...................... 47
7.2 Trouble Shooting According To Fault Indication............................ 49
7.3 Trouble Shooting In Else Cases.................................................... 50
8. Battery Maintenance .......................................................................... 51
9. Communication Port.......................................................................... 52
9.1 USB Interface ................................................................................ 52
9.2 Dry contact Interface ..................................................................... 52
9.3 Intelligent slot................................................................................. 52
10. Software ............................................................................................ 53
1. Safety and EMC Instructions
Please read carefully the following user manual and the
safety instructions before installing the unit or using the
unit!

1.1 Installation

★ This is permanently connected equipment, and it must be


installed by qualified maintenance personnel.
★ Condensation may occur if the UPS is moved directly from a
cold to a warm environment. The UPS must be absolutely dry
before being installed. Please allow an acclimatization time of at
least two hours.
★ Do not install the UPS near water or in damp environment.
★ Do not install the UPS where it would be exposed to direct
sunlight or near heat.
★ Do not connect appliances or items of equipment which would
overload the UPS (e.g. laser printers, etc) to the UPS output.
★ Place cables in such a way that no one can step on or trip over
them.
★ Connect UPS with the earth reliably before connecting to the
building wiring terminal, and external battery source must also
be earthed.
★ An integral single emergency switching device which prevents
further supply to the load by the UPS in any mode of operation
should be provided in the building wiring installation.
★ An appropriate disconnect device as short-circuit backup
protection should be provided in the building wiring installation.
★ The equipment is powered by two sources: the mains source,
the internal battery or the external battery source.

1
★ With the installation of the equipment, the sum of the leakage
current of the UPS and the connected load does not exceed 5%
of rated value of input current.
★ Do not block ventilation openings in the UPS’s housing. Ensure
allow at least 50cm of space on front and rear of the UPS.

1.2 Operation

★ Do not disconnect the mains cable on the UPS or the building


wiring terminals during operation since this would remove the
protective earth from the UPS and all connected loads.
★ The UPS output terminal block may still be electrically lived
even if the UPS is not connected to the building wiring terminal,
for there is internal current source (batteries).
★ In order to fully disconnect the UPS, first turn the input breaker
in the “OFF” position, then disconnect the mains lead.
★ Indiscriminate operation of switches may cause output loss or
damage to equipment. Refer to instruction before conducting
any control.
★ While the UPSs work as a parallel system, the external parallel
cable should be reinforced insulation.
★ Ensure that no liquid or other foreign objects can enter the UPS.

1.3 Maintenance, servicing and faults

★ Do not remove the enclosure since the UPS operates with


hazardous voltages. It is to be serviced only by qualified
maintenance personnel.
★ Caution - risk of electric shock. Even after the unit is
disconnected from the mains power supply (building wiring
terminal), components inside the UPS are still connected to the
battery which are potentially dangerous.

2
★ Before carrying out any kind of service and/or maintenance,
isolate UPS and disconnect the batteries. Verify that no current
is present and no hazardous voltage exists in the capacitor or
BUS capacitor.
★ Batteries must be replaced only by qualified personnel.
★ Batteries have a high short-circuit current and pose a risk of
shock. Take all precautionary measures specified below and
any other necessary measures when working with batteries:
- remove all jewellery, wristwatches, rings and other metal
objects
- use only tools with insulated grips and handles.
★ When changing batteries, replace with the same quantity and
the same type of batteries.
★ Do not attempt to dispose of batteries by burning them. It could
cause explosion.
★ Do not open or destroy batteries. Effluent electrolyte can cause
injury to the skin and eyes. It may be toxic.
★ Replace the fuse only by a fuse of the same type and of the
same spec in order to avoid fire hazards.

1.4 Transport

★ Please transport the UPS only in the original packaging to


protect against shock and impact.

1.5 Storage

★ The UPS must be stockpiled in the room where it is ventilated


and dry.

3
1.6 Standards

* Safety

IEC/EN 62040-1-1

* EMI

Conducted Emission..........................:IEC/EN 62040-2 Category C3

Radiated Emission.............................:IEC/EN 62040-2 Category C3

* EMS

ESD...................................................:IEC/EN 61000-4-2 Level 3

RS.....................................................:IEC/EN 61000-4-3 Level 3

EFT....................................................:IEC/EN 61000-4-4 Level 4

SURGE..............................................:IEC/EN 61000-4-5 Level 4

CS……………………………………...:IEC/EN 61000-4-6 Level 3

MS……………………………………..: IEC/EN 61000-4-8 Level 3

Voltage Dips……………………….....: IEC/EN 61000-4-11

Low Frequency Signals.....................:IEC/EN 61000-2-2


Warning: This is a product for cmmercial and industrial application in the
second environment-installation restrictions or additional measures may be
needed to prevente disturbances.

4
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is
advisable to familiarize yourself with them and understand their
meaning:

5
3. Introduction
This On-Line series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically
for computer equipments, communication servers, and data centers.
The double-converter principle eliminates all mains power
disturbances. A rectifier converts the alternating current from the utility
power to direct current. On the basis of this DC voltage, the inverter
generates an AC sinusoidal voltage, which constantly supplies the
loads. In the event of power failure, the maintenance-free batteries
power the inverter.
This manual covers the UPS listed as follows. Please confirm whether
it is the model you intend to purchase by performing a visual inspection
of the Model No. on the rear panel of the UPS.

Model No. Type Model No. Type


6K 6KS Extended backup
Standard
10K 10KS time
“S” Model: Extended backup time

3.1 Feature

This series UPS is a new generation of UPS, which provides the


outstanding reliability, and most cost-performance ratio in the industrial.
Following benefit the product has:
 True online double-conversion technology with high power
density, utility frequency independence, and generator
compatibility.
 Output power factor is 0.9, perfect output sine waveform,
suitable almost all critical equipment.
 High input power factor >0.99, overall high efficiency >0.92,
save power and wiring expense for user. Low input current
distortion, avoid power pollution.
6
 Outstanding adaptability to the worst mains input condition.
Extra wide input voltage, frequency range and waveform, avoid
excessive dissipating limited battery energy.
 Internal charger could be up to 4Amps to decrease recharging
time of battery. Optional external large charging current charger
which is up to 12Amps could be supplied.
 N+X parallel redundancy to increase the reliability and flexibility.
Number of parallel operating UPS is up to 4.
 HE mode with high efficiency >0.96, save power expense for
user.
 Input or output ISO transformer compatibility.
 Start-able without battery.

3.2 Electrical specifications

INPUT
Model No. 6K(S) 10K(S)

Phase Single
Voltage 176~276VAC

Frequency (45~55)/(54~66) Hz

Current(A)
THDI < 5% @ full load
Power Factor > 0.99 @ full load

OUTPUT

Model No. 6K(S) 10K(S)

Power rating 6kVA/5.4kW 10kVA/9kW

Voltage 208*/220/230/240× 1 ( 士 1%)VAC


Frequency ( )
50/60× 1±0.1 Hz (Battery mode)

Wave form sinusoidal


7
Load type PF 0.5~1, lagging
< 2% @ full linear load
THDV
<5% @ full non linear load
In Line mode**:
10 min 105~125%
1 min 125~150%
10 s >150%
Overload 1s >170%
In Battery mode:
2 min 105~125%
30 s 125~150%
1s >150%
*Derating to 90% when the output voltage is adjusted to 208VAC.
**The overload capacity should be derated in Line mode while the circumstance
temperature is larger than 35 degree.

BATTERIES
Model No. 6K 10K
Internal BAT
20×12V 7Ah 20×12V 9Ah
number and type
Current of external
30Amax 50Amax
BAT pack

3.3 Operating Environment

Operating Temperature 0 oC to 45 oC

Operating humidity < 95%

Altitude < 1000m*

Storage temperature -15 oC to 50 oC

*The load capacity should be derated 1% every 100m heightened on the basis
of 1000m.

8
3.4 Typical backup time (Typical values at 25°C in minutes)

Model No. 100 % Load 50 % Load

6K 5 ?

10K 5 ?

3.5 Dimensions and weights

Dimensions W×H×D Net Weight


Model No.
(mm) (kg)

6K 260 x 708 x 550 89

6KS 260 x 708 x 550 34

10K 260 x 708 x 550 92

10KS 260 x 708 x 550 37

9
Fig. 3-1 Front view of 6K(S)/10K(S)

10
6K(S) 10K(S)
Fig. 3-2 Back View of 6K(S)/10K(S)

11
4. Installation
The system may be installed and wired only by qualified
electricians in accordance with applicable safety regulations!

When installing the electrical wiring, please note the nominal


amperage of your incoming feeder.

4.1 Moving to the installation site

The Innova series UPS has wheels making it easy to move the UPS
to the installation site after it has been unpacked. However, if the
receiving area is far from the installation site, it is recommended to
move the UPS by using a pallet jack or a truck before unpacking the
UPS.

4.2 Unpacking and inspection

1. At the installation site, the utmost care shall be taken when


removing the packaging in order to avoid damaging the equipment.
Cut the plastic poly-straps around the shipping container and
remove the corrugated carton and the PS foam on the top of the
UPS. With one or two people on each side of the UPS, lift the UPS
out of the pallet.
Warning: the plastic poly-straps around the shipping container
are under tension. While cutting, don’t face to them, they will
spring back and may cause eye injury.

The shipping materials are recyclable. After unpacking,


save them for later use or dispose of them appropriately.

12
2. Check all packaging materials to ensure that no items are missing.
The shipping package contains:
● A UPS
● A user manual
● A communication cable
● A parallel cable
● A parallel port cover plate
● Terminal connectors 12pcs

3. Inspect the appearance of the UPS to see if there is any damage


during transportation. Do not turn on the unit and notify the carrier
and dealer immediately if there is any damage or lacking of some
parts.

4.3 Input and output power wires and protective earth


ground installation

4.3.1 Notes for installation

1) The UPS must be installed in a location with good ventilation,


far away from water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not
blocked. Allow at least 0.5m of space on each side.

3) Condensation to water drops may occur if the UPS is unpacked


in a very low temperature environment. In this case it is
necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of
electric shock.

4) The additional side mounting brackets optional accessory can )
be fixed to obtain grater stability of the UPS enclosure. See Fig.
4-5.

13
Fig. 4-5 Additional stability
4.3.2 Installation

For safety, please cut off the mains power switch before
installation!
Use cable cross section and protective device specification
Model 6k 10k
Protective earthing conductor
4mm2 (10AWG) 10 mm2 (6AWG)
Min cross section
Input L, N, G
Min conductor cross section 4mm2 (10AWG) 10 mm2 (6AWG)
Input breaker 50A/250VAC 80A/250VAC
Input fuse 60A/250VAC 90A/250AC
Output L,N,
4mm2 (10AWG) 10 mm2 (6AWG)
Min conductor cross section
External Battery Cabinet
Positive Pole(+), Negative pole(-),
4mm2 (10AWG) 10 mm2 (6AWG)
Neutral Pole
Min conductor cross section
External Battery Cabinet Fuse
in Positive Pole(+), Negative pole(-), 60A/240VDC 90A/240VDC
Neutral Pole

14
External Battery Cabinet Breaker
in Positive Pole(+), Negative pole(-), 60A/240VDC 90A/240VDC
Neutral Pole
Backfeed protection device A 2-pole disconnection device with
80A/250VAC, less than 15s break
time and min. 1.4mm clearance
should be used in final installation for
backfeed protection.
Torque for fixing above terminals 3.95~4.97Nm
(35~44 1b in)

2) No matter the UPS is connected to the utility power or not, the


output of the UPS may be electrically live. The parts inside the
unit may still have hazardous voltage after turning off the UPS.
To make the UPS have no output, power off the UPS, and then
cut off the utility power supply, wait the UPS shut down
completely.
3) Open the terminal block cover located on the rear panel of UPS,
please refer to the appearance diagram.
4) For 6KVA UPS, it is recommended to select the UL1015
10AWG/4mm 2 or other insulated wire which complies with AWG
Standard for the UPS input and output wirings.

5) For 10KVA UPS, it is recommended to select the UL1015


6AWG/10mm 2 or other insulated wire which complies with AWG
Standard for the UPS input and output wirings.
6) Ensure the capacity of mains power supply. Do not use the wall
receptacle as the input power source for the UPS, as its rated
current is less than the UPS’s maximum input current.
Otherwise the receptacle may be burned and destroyed.
7) The protective earth ground wire should be installed first
according to the following diagram. It is better to use green wire
or green wire with yellow ribbon wire.

15
8) Connect other input and output wires to the corresponding input
and output terminals according to the following diagram.
9) It is recommended to use the accessorial terminal connectors
which can be compacted on the wires tightly, to ensure the
connection between the wires and the terminal block is reliable.

Fig. 4-6 Input and output Terminal Block wiring diagram


Important notes: If the UPS is used in single mode, JP1 and JP2
must be connected. If the UPS is used in parallel mode, the Jumper
between JP1 and JP2 must be removed.

10) Install an output breaker between the output terminal of UPS


and the load, and the breaker should with leakage current
protective function if necessary.

11) Turn off all the loads first before connecting the load with the
UPS, then perform the connection and finally turn on the loads
one by one.
12) After completing the installation, check all the wires is
connected correctly and tightly.
13) Suggest charging the batteries for 8 hours before use. After
installation, turn on the mains power switch and turn the input
breaker in the “ON” position, the UPS will charge the batteries
automatically. It can also use the UPS immediately without
charging the batteries, but the backup time may be less than the
standard value.
16
14) If it is necessary to connect the inductance load such as a
monitor or a laser printer to the UPS, the start-up power should
be used for calculating the capacity of the UPS, as its start-up
power consumption is too big to make the UPS which capacity
is small fail easily.

4.4 Operating procedure for connecting with the external


battery

1. The nominal DC voltage of external battery pack is 240VDC. Each


battery pack consists of 20 pieces of 12V maintenance free
batteries in series. To achieve longer backup time, it is possible to
connect multi-battery packs, but the principle of “same voltage,
same type” should be strictly followed.
2. For 6KVA, select the UL1015 10AWG/4mm 2 respectively or other
insulated wire which complies with AWG Standard for the UPS
battery wirings.

3. For 10KVA, select the UL1015 6AWG/10mm2 respectively or other


insulated wire which complies with AWG Standard for the UPS
battery wirings.
4. The external battery pack must be independent for each UPS. It is
forbidden that two UPSs use same external battery pack.
5. The procedure of installing battery pack should be complied with
strictly. Otherwise it may encounter the hazardous of electric
shock.

1) Ensure the UPS is not powered on and the mains input


breaker is set in the “OFF” position.
2) A DC breaker must be installed between the external battery
pack and the UPS. The capacity of breaker must be not less
than the data specified in the general specification.

17
3) Set the external battery pack breaker in “OFF” position and
connect the 20 pieces of batteries in series.
4) Connect the external battery pack to the battery terminals.
Check the polarity of connection is correct.
5) Set the breaker of the battery pack in the “ON” position.
6) Set the mains input breaker in the “ON” position, the UPS
would power on and start to charge the battery pack.

4.5 EPO Connection


4.5.1 Introduction
Emergency power off function which the UPS supplies is, when the
emergency occurs, such as the failure of load, the UPS can cut off
the output at once by operating the EPO port manually.
4.5.2 The connection
Normally the EPO connector is closed with a wire on the rear panel,
which is supplied in the accessory. Once the connector is open, the
UPS would stop the output and enter EPO status.

Enable the EPO status Disable the EPO status


Fig. 4-7 Default EPO status
To recover to normal status, first EPO connector should be closed,
and enter LCD menu (illustrated in the chapter of 5.5.5) to clear
EPO status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
The polarity of connector could be inversed by setting in LCD menu
in the chapter of 5.5.7. Contact your local distributor for further
information before modifying the settings.
18
5. Operation
5.1 Display Panel

The UPS has a four-button dot matric LCD with dual color backlight.
Standard back-light is used to light up the display with white text and
a blue background. When the UPS has a critical alarm, the
backlight changes the text to dark amber and the background to
amber. Besides the LCD, the UPS has four colorized LEDs to
provide more convenient information.

Fig. 5-1 Control Panel


Table 5-1 Control Button Functions

The Button Funtion Illustration


When the unit is no power and has connected
Power on with battery, press this button for >100ms&<1s to
power on
When the unit is powered on and is in Bypass
Turn on
mode, press this button for >1s to turn on
When the unit has been turned on, press this
Turn off
button for >1s to turn off
When the unit is in fault mode, press this button
Clear fault
for >1s to stop alarm and clear fault

19
When displaying default UPS status summary
Enter main
screen, press this button for >1s to enter the
menu
main menu tree
Press this button for >1s to exit the present menu
Exit main
to default system status display menu without
menu
executing a command or changing a setting
Press this button for >100ms&<1s to scroll up the
Scroll up
menu option

Press this button for >100ms&<1s to scroll down


Scroll down
the menu option

Press this button for >100ms&<1s to select the


Enter next
present menu option, or enter next menu, but do
menu tree
not change any setting
Press this button for >100ms&<1s to select the
Select one
present menu option, or enter next menu, but do
menu option
not change any setting
Confirm the
Press this button for >1s to confirm the edited
present
options and change the setting
setting

Table 5-2 LED definition


UPS state Normal LED Battery LED Bypass LED Fault LED
(Green) (Yellow) (Yellow) (Red)
Bypass mode
with no output
★ ↑
Bypass mode
● ↑
with output
Turning on △ △ △ △
Line mode ● ↑
Battery mode ● ● ↑
HE mode ● ● ↑
Battery test mode △ △ △ △
Fault mode ↑ ●
Warning mode ↑ ↑ ↑ ★

20
Note:
●: Lightened constantly

△: #1-#4 Lightened circularly

★: Flashing

↑: Depended on the fault/warning status or other status


Table 5-3 Alarm definition
UPS condition Buzzer status
Fault active Continuous
Warning active Beep every second
Battery output Beep every 4 seconds
Bypass output Beep every 2 minutes

The UPS provides useful information about UPS itself, load status,
events, measurements, identification, and settings through the front
panel display.
During powering on, the LCD would display the Welcome logo for
several seconds and then enter to the default page which shows the
UPS status summary.
The display automatically returns to the default UPS status
summary screen when no button has been pressed for 15 minutes.
On the UPS status summary screen it provides the following
information:
 Status summary, including mode and load
 Notice or alarm status, if any are present
 Battery status, including status and charge level

21
Fig. 5-2 The default LCD display
The more detailed operation of LCD is illustrated in the chapter of 5.5.

5.2 Operating mode

The different graphic symbol could be displayed corresponding to


current operating mode or status.
5.2.1 Line mode
The example of LCD display in Line mode is shown in the following
diagram.

Fig. 5-3 Line mode

22
5.2.2 Battery mode
The example of LCD display in battery mode is shown in the
following diagram.

Fig. 5-4 Battery mode


When the UPS is running in battery mode, the buzzer beeps once
every 4 seconds. If the button on the front panel is pressed for more
than 1 second again, the buzzer will stop beeping (in silence mode).
5.2.3 Bypass with output
The LCD display in bypass mode with output is shown in the
following diagram. The UPS does not have the backup function
when it is in bypass mode. The power used by the load is supplied
from the utility power via internal filter. The UPS will beep once
every 2 minutes in bypass mode.

Fig. 5-5 Bypass mode with output

23
5.2.4 Bypass without output
The LCD display in bypass mode without output is shown in the
following diagram.

Fig. 5-6 Bypass mode without output

5.2.5 HE mode (High Efficiency mode)


It is also called economy mode.
After the UPS is turned on, the power used by the load is supplied
from the utility power via internal filter while the utility power is in
normal range, so the high efficiency could be gained in the HE mode.
Once the mains is loss or abnormal, the UPS would transfer to Line
mode or Battery mode and the load is supplied continuously.

Fig. 5-7 HE mode


1) The function could be enabled through the LCD setting or the
software (Winpower, etc.).

24
2) It is attention that the transfer time of UPS output from HE
mode to battery mode is about 10ms. But it is still too long for
some sensitive load.
5.2.6 Converter mode
In converter mode, the UPS would free run with fixed output
frequency (50Hz or 60Hz). Once the mains is loss or abnormal, the
UPS would transfer to battery mode and the load is supplied
continuously.

Fig. 5-8 Converter mode

1) The function could be enabled through the LCD setting or the


software (Winpower, etc.).
2) The load should be derating to 60% in converter mode.

5.2.7 Warning
When the warning occurs, it illustrates that there are some
abnormal problems during the operation of UPS. Normally the
problems are not fatal and the UPS continues working, but they
should be paid attention to, or the UPS may fail.
The detailed warning table is shown in chapter of 7.

25
Fig. 5-9 Warning

5.2.8 Fault
When the fault occurs, it illustrates that some fatal problems
happened, the UPS would directly cut off the output or transfer to
bypass, and keep alarming. The backlight of LCD would also turn to
red.
The detailed fault table is shown in chapter of 7.

Fig. 5-10 Fault

5.2.9 Other status


When the UPS is overload, the alarm will beep twice every second.
Some unnecessary loads should be get rid of one by one to
decrease the loads connected to the UPS less than 90% of its
nominal power capacity.

26
Fig. 5-11 Overload

While doing the battery test, LEDs would be lighted circularly, and
the symbol of battery test would be shown on the display.

Fig. 5-12 Battery test

And if the battery status detected is “bad battery detected” or


“battery disconnected”, the symbol of battery failure would be shown
and UPS would alarm.

Fig. 5-13 Battery fails

27
5.3 Turning on and Turning off UPS
Attention: The UPS could only be turning on while connecting with the
utility at the first time.
Attention: Please switch off the connected loads first before turning
on the UPS, and switch on the loads one by one after the UPS is
turned on. Switch off all of the connected loads before turning off the
UPS.
5.3.1 Turning on UPS with utility
1) Check all the connection is correct. Check the breaker of
external battery pack is in “ON” position.
2) Set input breaker in “ON” position. At this time the fan begins to
rotate, LCD will show “WELCOME”. Then LCD will show the
default UPS status summary screen after UPS finishing
self-test.
3) By pressing button continuously for more than 1 second,
the buzzer will beep for 1s, UPS starts to turn on.
4) A few seconds later, the UPS turns into Line mode. If the utility
power is abnormal, the UPS will transfer to Battery mode
without output interruption of the UPS.
5.3.2 Turning on UPS without utility
1) Check all the connection is correct. Check the breaker of
external battery pack is in “ON” position.
2) By pressing button continuously for more than 100ms, the
UPS would be powered on. At this time the fan begins to rotate,
LCD will show “WELCOME”. Then LCD will show the default
UPS status summary screen after UPS finishing self-test.
3) By pressing button continuously for more than 1 second,
the buzzer will beep for 1s, UPS starts to turn on.
4) A few seconds later, the UPS turns into Battery mode. If the
utility power comes back, the UPS will transfer to Line mode
without output interruption of the UPS.
28
5.3.3 Turning off UPS with utility
1) To turn off the inverter of UPS by pressing button
continuously for more than 1 seconds and the buzzer will beep
for 1s. The UPS will turn into Bypass mode at once.
2) When completing the above action, UPS output voltage is still
present. In order to cut off the UPS output, simply cut off the
utility power supply. A few seconds later, LCD display shuts
down and no output voltage is available from the UPS output
terminal.
5.3.4 Turning off UPS without utility
1) To power off the UPS by pressing button continuously for
more than 1 second, and the buzzer will beep once. The UPS
will cut off the output at once.
2) A few seconds later, LCD shuts down and no voltage is
available from the UPS output.

5.4 LCD operation

Except the default UPS status summary screen, the user could get
more useful information about UPS current status, detailed various
measurements, old events which ever occurred, UPS own
identification, and could change the settings to fit the user own
requirements, optimize the function of UPS.
5.4.1 The main menu
In the default UPS status summary screen, when pressing or
<1s, the detailed information about alarm, the parallel system,
battery would be shown.
In the default UPS status summary screen, when pressing >1s,
the display would enter main menu tree.
The main menu tree includes six branches: UPS status menu, event
log menu, measurement menu, control menu, identification menu,
setting menu.

29
Fig. 5-14 Main menu tree

5.4.2 The UPS status menu


By pressing on the menu of “UPS status”, the display would
enter the next UPS status menu tree.
The content of UPS status menu tree is same as the default UPS
status summary menu.
By pressing >1s, the display would return the last main menu
tree.

30
Fig. 5-15 UPS status menu tree

5.4.3 The event log menu


By pressing on the menu of “Event log”, the display would enter
the next event menu tree.
All the old event, alarm and fault have been recorded here. The
information includes the illustration, the event code, and the
operating time of UPS when the event happened. By press or
<1s, all the event could be displayed one by one.
The max number of record is 50, when the number is larger than 50,
the oldest one would be changed to the newest information.
By pressing >1s, the display would return the last main menu
tree.

31
Fig. 5-16 Event menu tree

5.4.4 The measurement menu


By pressing on the menu of “Measurement”, the display would
enter the next measurement menu tree.
A lot of detailed useful information could be checked here, Ex. the
output voltage and frequency, the output current, the load capacity,
the input voltage and frequency, etc.
By pressing >1s, the display would return the last main menu
tree.

32
Main menu tree

UPS status Measurement menu tree

Ambient Temperature DC Bus


29.1 ºC 83.4 ºF 226.3V 225.9V
Event log

By press >1s
Output Battery
Measurement
By press <1s
850W 1130VA 228.2V 100%

By press or <1s
... Output
Input
24.9A 75% 220.4V 60.0Hz

Output

220.4V 60.0Hz

Fig. 5-17 Measurement menu tree

5.4.5 The control menu


By pressing on the menu of “Control”, the display would enter
the next control menu tree.
1) Single UPS turn off: is one command to turn off one UPS which
is operated currently in a parallel system, and other UPSs
continue working to supply the load in the parallel system.
2) Single UPS battery test: is one command to control one UPS
which is operated currently in a parallel system to do the battery
test singly, and other UPSs do not do the battery test.
3) Parallel UPS battery test: is one command to control all UPS in
a parallel system to do the battery test at the same time.
4) Clear EPO status: once EPO status is enabled, the UPS output
would be cut off. To recover to normal status, first EPO
connector should be closed, and enter this menu to clear EPO
33
status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
5) Reset error status: when fault occurs, UPS would keep in Fault
mode and alarm. To recover to normal status, enter this menu
to reset error status, then UPS would stop alarm and recover to
Bypass mode. And the reason of fault should be checked and
deleted before UPS is turned on again by manual operation.
6) Restore factory settings: all the settings would be recover to
default factory settings. It could only be done in Bypass mode.

Fig. 5-18 Control menu tree

Example: clear EPO status

34
Fig. 5-19 clear EPO status

5.4.6 The identification menu


By press on the menu of “Identification”, the display would enter
the next identification menu tree.
The identification information includes UPS serial number, firmware
serial number, model type, would be shown here.
By press >1s, the display would return the last main menu tree.

35
Fig. 5-20 Identification menu tree

5.4.7 The setting menu


Please contact your local distributor for further information before
using the settings. Some settings would change the specification,
and some settings would enable or disable some functions. The
unsuitable option set by user may result in potential failures or
protecting function loss, even directly damage the load, battery or
UPS.
The most of settings could only be done while UPS is in Bypass
mode.

36
Setting menu tree

Control commands
Battery quantity
from serial port
<20>
<enabled>

Main menu tree


Clear event log EPO input polarity
... Total events: 50 <open>

LCD contrast HE voltage high limit


Identification <+0> <+10%>
Password: AAAA

USER By press or <1s


By press >1s
User password HE voltage low limit
Setting <disabled> <-10%>
By press <1s

Audio Alarm Enable HE frequency high limit

<enabled> <+10%>

Output voltage HE frequency low limit

<230V> <-10%>

Bypass frequency low


Output frequency
limit
<autosensing>
<-10%>

Bypass frequency high


Power strategy
limit
<normal>
<+10%>

Bypass voltage high


Start on battery
limit
<enabled>
<264V>

Bypass voltage low


Site wiring fault alarm
limit
<disabled>
<176V>

Automatic battery test


Inv short clearance
period
<enabled>
<7>

Auto Restart AutoBypass

<enabled> <enabled>

Fig. 5-21 Setting menu tree

37
By press on the menu of “Identification”, the display would enter
the next setting menu tree if “User password” is disabled. If “User
password” is enabled, the user should enter the password by press
, , and , then enter the next setting menu tree.

Table 5-1
Submenu item Optional Values Default value
Rated output voltage 208/220/230/240V 230V
Output frequency autosensing/50/60Hz autosensing
Power strategy* normal/high efficiency/ converter normal
Start on battery enabled/disabled enabled
AutoBypass enabled/disabled enabled
Auto Restart Function enabled/disabled enabled
Bypass voltage low limit 176~205V 176V
Bypass voltage high limit 235~276V 264V
Bypass frequency High limit 70Hz 70Hz
Bypass frequency Low limit 40Hz 40Hz
HE frequency High Limit +5% ~+10% +5%
HE frequency Low Limit -5% ~-10% -5%
HE voltage High limit +1% ~+10% +5%
HE voltage Low limit -1% ~-10% -5%
Inv short clearance enabled/disabled disabled
Site wiring fault alarm enabled/disabled enabled
Audio alarm enable enabled/disabled enabled
EPO input polarity open/close open
Automatic battery test period 0-31days 7days
Battery quantity** 19/20/21 20
Clear event log
LCD contrast -5~+5 0

*Read the chapter of 6.1 and 6.2, before using high efficiency or converter function.
**Ensure the real battery quantity is same as the setting, or the batteries would be
damaged permanently.

38
Example: set rated output voltage value

Fig. 5-22 Set rated output voltage value

39
6. Special function
The series UPS has some special functions, which could satisfy
some special application of user. And the functions have own
features, please contact your local distributor for further information
before using the function.

6.1 HE function

6.1.1 Brief introduction of HE function


If HE function is set to enable, after the UPS is turned on, the power
used by the load is directly supplied from the utility power via
internal filter while the utility power is in normal range, so the high
efficiency could be gained in HE mode. It is also called economy
mode. Once the mains is loss or abnormal, the UPS would transfer
to Line mode or Battery mode and the load is supplied continuously.
The great virtue is overall high efficiency >0.96 of UPS, to save
power for user.
But the disadvantage is 1) the load can not be protected as well as
in Line mode, for the load is directly supplied from the utility; 2) the
transfer time of UPS output from HE mode to Battery mode is about
10ms.
So the function is not suitable to some sensitive loads, and the
region where the utility power is unstable.

6.1.2 Set the function


The function could be enabled through the LCD setting in Bypass
mode.
Enter the power strategy setting menu by following chapter of 5.5.7.

40
6.2 Converter function

6.2.1 Brief introduction of Converter function


In converter mode, the UPS would free run with fixed output
frequency (50Hz or 60Hz). Once the mains is loss or abnormal, the
UPS would transfer to Battery mode and the load is supplied
continuously.
The great virtue is the output frequency is fixed, which is required by
some very sensitive loads.
But the disadvantage is the load capacity of UPS should be derating
to 60% in converter mode.
6.2.2 Set the function
The function could be enabled through the LCD setting in Bypass
mode.
Enter the power strategy setting menu by following chapter of 5.5.7.

6.3 Parallel function

6.3.1 Brief introduction of the redundancy

N+X is currently the most reliable power supply structure. N


represents the minimum UPS number that the total load needs, X
represents the redundant UPS number, i.e. the fault UPS number
that the system can handle simultaneously. When the X is larger, the
reliability of the power system is higher. For occasions where
reliability is highly depended on, N+X is the optimal mode.

As long as the UPS is equipped with parallel cables, up to 4 UPSs


can be connected in parallel to realize output power sharing and
power redundancy.

41
6.3.2 Parallel installation and operation
How to install a new parallel UPS system:

1) Before installing a new parallel UPS system, user need to


prepare the input and output wires, the output breaker, and the
parallel cable.
2) Users need to use a standard 25-pin communication cable,
which should have 25 cores, corresponding stitches and shield,
as the UPS parallel cable. The length of the parallel cable is
appropriate to be less than 3m. And there is one standard
parallel cable in the accessories of every UPS.
3) Remove the cover plate of the parallel port on the UPS,
connect each UPS one by one with the parallel cable, and
re-screw the Parallel port cover which is supplied in the
accessories.
4) Strictly follow the chapter of 4, the wiring requirement of single
UPS to perform the wiring of each UPS.
5) Connect the output wires of each UPS to an output breaker
panel.
6) Disconnect the Jumper on JP1 and JP2 of the terminal block
first, and connect each output breaker to a main output breaker
and then to the loads.
7) Each UPS need an independent battery pack.
8) Please refer to the wiring diagram in the following diagram.
9) The distance between the UPSs in parallel and the breaker
panel is required to be less than 20 meters. The difference
between the wires of input and output of the UPSs is required to
be less than 20%.

42
O/P Ground

Fig. 6-1 Input and output Terminal Block wiring diagram


Main
UPS#1 UPS#2 O/P Breaker
O/P Breaker O/P Breaker

43
Main
I/P Breaker
I/P Ground
TO UTILITY

Main mechanical or static switch

Main I/P Breaker

Main O/P Breaker

TO LOAD

Fig. 6-2 Parallel System Installation Diagram

10) Do not switch on the output breaker of each UPS, switch on the
input breaker of the each UPS, the UPS should work in bypass
with output, observe their display to check if there are any
warning or fault information, measure the output voltage of
each UPS separately to check if the voltage difference between
them is less than 1V. If the difference is more than 1V, check
the wiring.
11) Press the button of one UPS, each UPS would start to turn
on, all the UPSs would transfer to the INV mode together.
Measure the output voltage of each UPS separately to check if
the voltage difference between them is less than 0.5V. If the
difference is more than 0.5V, the UPSs need to be regulated.
12) Press the button of one UPS, each UPS would start to turn
off and transfer to the Bypass mode, switch on the output
breaker of each UPS to parallel all the output of UPSs together.
44
13) Press the button of one UPS, each UPS would start to turn
on, after turning on, the UPSs should work parallel in the Line
mode.

How to join a new UPS to a parallel system:


1) First the parallel system must be installed one main
maintenance mechanical switch or static switch.
2) Ensure the bypass is normal and the bypass setting is “enable”,
remove the cover plate of maintenance switch on the rear panel
of each UPS, the UPS system would transfer to bypass
automatically, set the own maintenance switch of each UPS
from “UPS” to “BPS”.
3) Set the main maintenance switch or static switch from “UPS” to
“BPS”, switch off the main output breaker, and the UPSs would
shut down.
4) Ensure the UPSs shut down totally, set the UPS own
maintenance switch from “BPS” to “UPS” and screw the
maintenance cover plate back again. Reinstall the new UPS
parallel system by following step 1) to 12) of last chapter -
“install a new parallel UPS system”.
5) Set the main maintenance switch or static switch from “BPS” to
“UPS”, Press the button of one UPS, each UPS would start
to turn on, after turning on, the UPSs should work parallel in the
Line mode.

How to remove a single UPS from a parallel system:


1) First the parallel system must be installed one main
maintenance mechanical switch or static switch.
2) Ensure the bypass is normal and the bypass setting is “enable”,
remove the cover plate of maintenance switch on the rear panel
of each UPS, the UPS system would transfer to bypass
automatically, set the own maintenance switch of each UPS
from “UPS” to “BPS”.
45
3) Set the main maintenance switch or static switch from “UPS” to
“BPS”, switch off the main output breaker, and the UPSs would
shut down.
4) Ensure the UPSs shut down totally, set the UPS own
maintenance switch from “BPS” to “UPS” and screw the
maintenance cover plate back again. Remove the wanted UPS
and reinstall the new UPS parallel system by following step 1)
to 12) of last chapter - “install a new parallel UPS system”.
5) If the removed UPS or the remained UPS will be used in a
stand-alone mode, then JP1 and JP2 on the terminal block
should be connected with a short connection wire.
6) Set the main maintenance switch or static switch from “BPS” to
“UPS”, Press the button of one UPS, each UPS would start
to turn on, after turning on, the UPSs should work parallel in the
Line mode.

46
7. Trouble Shooting
If the UPS system does not operate correctly, first check the operating
information on the LCD display.
Please attempt to solve the problem using the table below. If the
problem still persists, consult your dealer.

7.1 Trouble Shooting According To Warning Indication

Problem Displayed Possible cause Remedy


Read EEPROM Error UPS internal fault Consult dealer.
Emergency Power Off EPO connector is Check the EPO connector
open status
On Maintain Bypass Maintain bypass Check the maintain bypass
switch is open switch status

Site Wiring Fault Phase and neutral Reverse mains power wiring.
conductor at input of
UPS system are
reversed
Battery Disconnected Battery pack is not Do the battery test to confirm.
connected correctly
Check the battery bank is
connected to the UPS.

Check the battery breaker is


turn on.
Low Battery Warning Battery voltage is low When audible alarm sounding
every second, battery is almost
empty.
Output Overload Overload Check the loads and remove
some non-critical loads.

Check if some loads are failed.


Fan Failure Fan abnormal Check if the fan is running
normally.
Charger Failure The charge fails Consult dealer.
47
Battery DC Over Voltage Battery voltage is Check if the battery quantity is
higher than normal right.
value
Over Charge Battery is over The UPS would transfer to
charged battery mode automatically, and
after the Battery voltage is
normal and the mains is normal,
the UPS would retransfer to
Line mode automatically again.
Model Pin Error UPS internal fault Consult dealer.
Ambient Over The ambient Check the environment
Temperature temperature is too ventilation.
high
Heatsink Over Inside temperature of Check the ventilation of UPS
Temperature Warning UPS is too high and the ambient temperature.
NTC abnormal UPS internal fault Consult dealer.
Communication cable The parallel cable is Check the parallel cable.
male disconnected disconnected
Communication cable The parallel cable is Check the parallel cable.
female disconnected disconnected
Parallel Battery The battery packs of Check if all the battery pack is
Connection Different some UPSs are connected.
disconnected
Parallel input different The mains input of Check the building wiring and
some UPSs is input cable.
disconnected Check if the input breaker is
closed.
Ensure the UPSs are
connected to same input
source.
Parallel Power strategy There are different The UPSs with different power
setting different power strategy setting strategy setting (Ex. one Line
in parallel system mode and one Converter mode)
are forbidden to parallel.
Parallel rated power There are different The UPSs with different
capacity setting different UPSs in parallel capacity (Ex. one 6KVA and
system one 10KVA) are forbidden to
parallel.

48
Parallel in HE mode HE function is HE function is forbidden in
enabled in parallel parallel system.
system
Parallel load unbalance UPS internal fault Consult dealer.

7.2 Trouble Shooting According To Fault Indication

Problem Displayed Possible cause Remedy


Inverter Overload Fault Overload Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Bypass Overload Fault Overload Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Output Short Circuit Output short circuit Remove all the loads. Turn off
the UPS.
Check if UPS output and loads
is short circuit.
Ensure short circuit is removed
before turning on again.
Heatsink Over Inside temperature of Check the ventilation of UPS
Temperature Fault UPS is too high and the ambient temperature.
Bus Over Voltage UPS internal fault Consult dealer.
Bus Under Voltage UPS internal fault Consult dealer.
Bus Unbalance UPS internal fault Consult dealer.
Bus short UPS internal fault Consult dealer.
Bus Softstart Failed UPS internal fault Consult dealer.
Inverter Over Voltage UPS internal fault Consult dealer.
Inverter Under Voltage UPS internal fault Consult dealer.
Inverter Softstart Failed UPS internal fault Consult dealer.
Negative Power Fault The load is pure Remove some non-critical
inductive and loads.
capacitive Bypass supplies the load first,
ensure there is no overload,
then turn on UPS.

49
Fatal EEPROM Fault UPS internal fault Consult dealer.
Cable male and female The parallel cable is Check the parallel cable.
disconnected fault disconnected

7.3 Trouble Shooting In Else Cases

Problem Possible cause Remedy


No indication, no No input voltage Check the building wiring and
warning tone even input cable.
though system is Check if the input breaker is
connected to mains closed.
power supply
BYPASS LED light up Inverter not switched Press On-Switch “I” to turn on
even though the power on UPS.
supply is available
BATTERY LED lights Input voltage and/or Check input power source.
up, and audible alarm frequency are out of Check the building wiring and
sounding every 1 beep tolerance input cable.
in every 4 seconds Check if the input breaker is
closed.
Emergency supply Batteries not fully Charge the batteries for at least
period shorter than charged / batteries 12 hours and then check
nominal value defect capacity.

Please have the following information at hand before calling the


After-Sales Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. LCD/LED display information, Buzzer alarm status
4. Utility power condition, load type and capacity, environment temperature,
ventilation condition
5. The information (battery capacity, quantity) of external battery pack if the
UPS is “S” model
6. Other information for complete description of the problem

50
8. Battery Maintenance
Battery replacement should be performed by qualified personnel.
 This series UPS only requires minimal maintenance. The
battery used for standard models are value regulated sealed
lead-acid maintenance free battery. These models require
minimal repairs. The only requirement is to charge the UPS
regularly in order to maximize the expected life of the battery.
When being connected to the utility power, whether the UPS is
turned on or not, the UPS keeps charging the batteries and
also offers the protective function of overcharging and
over-discharging.
 The UPS should be charged once every 4 to 6 months if it has
not been used for a long time.
 In the regions of hot climates, the battery should be charged
and discharged every 2 months. The standard charging time
should be at least 12 hours.
 Under normal conditions, the battery life lasts 3 to 5 years. In
case if the battery is found not in good condition, earlier
replacement should be made.
 Replace batteries with the same number and same type of
batteries.
 Do not replace the battery individually. All the batteries should
be replaced at the same time following the instructions of the
battery supplier.
 If the battery service life (3~5 years at 25°C ambient
temperature) has been exceeded, the batteries must be
replaced.

51
9. Communication Port
9.1 USB Interface

The USB port is compliance with USB 1.1 protocol for its communication
software.

9.2 Dry contact Interface


This series UPS has independent dry contact interface. Please contact
your local distributor for details. The following is the pin assignment and
description of DB-9 connector.
Pin # Description I/O Pin # Description I/O
1 UPS Fail Output 6 Bypass Output
2 Summary Alarm Output 7 Battery Low Output
3 GND Input 8 UPS ON Output
4 Remote Shutdown Input 9 Line Loss Output
5 Common Input

9.3 Intelligent slot

This series is equipped with an intelligent slot for Webpower (optional


accessory) or other optional card to achieve remote management of the
UPS through internet / intranet. Please contact your local distributor for
further information.

52
10. Software
Free Software Download – WinPower
WinPower is a UPS monitoring software, which provides user-friendly
interface to monitor and control UPS. This unique software provides
safely auto shutdown for multi-computer systems while power failure.
With this software, users can monitor and control any UPS on the same
LAN, which communicated with local computer through RS232 or USB
protocol, no matter how far from the UPSs.

Installation procedure:
1. Go to the website:
http://www.ups-software-download.com/winpower.htm
2. Choose the operation system you need and follow the instruction
described on the website to download the software.
3. When downloading all required files from the internet, enter the serial
No: 511C1-01220-0100-478DF2A to install the software.
When the computer restarts, the WinPower software will appear as a
green plug icon located in the system tray, near the clock.
53
614-09910-00
54

You might also like