0% found this document useful (0 votes)
21 views1 page

Wai Plant List

The document outlines the specifications and monitoring parameters for various equipment in a wastewater treatment and pyrolysis facility. It includes details on the control systems, power ratings, and parameters such as on/off/trip time and temperature for each unit. Key components include sludge pumps, dosing units, dewatering units, dryers, and aeration blowers, along with their respective monitoring requirements.

Uploaded by

hmsanju5
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views1 page

Wai Plant List

The document outlines the specifications and monitoring parameters for various equipment in a wastewater treatment and pyrolysis facility. It includes details on the control systems, power ratings, and parameters such as on/off/trip time and temperature for each unit. Key components include sludge pumps, dosing units, dewatering units, dryers, and aeration blowers, along with their respective monitoring requirements.

Uploaded by

hmsanju5
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Sl.

No Location Control Specification Parameter to monitor


1 Holding Tank MCB DP Sludge pump 1 Power :1.3kW, 1 Ph On/off/Trip time
2 MCB DP Sludge pump 2 Power :1.3kW, 1 Ph On/off/Trip time
3 MCB DP Sludge pump 3 Power :1.3kW, 1 Ph On/off/Trip time
4 MCB DP Sludge pump 4 Power :1.3kW, 1 Ph On/off/Trip time
5 MCB DP Sludge pump 5 Power :1.3kW, 1 Ph On/off/Trip time

6 Dosing Unit MCB TPN Dosing Pump Power: 0.75kW, 3Ph On/off/Trip time
7 MCB TP Mixer motor Power: 0.75kW, 3Ph On/off/Trip time

8 Dewatering unit MCB DP Flocculation motor Power: 0.75kW, 3Ph On/off/Trip time
9 MCB DP Screw Motor Power: 0.75kW, 3Ph On/off/Trip time
10 MCB DP Filtrate Pump Power :1.3kW, 1 Ph On/off/Trip time
11 Dryer 1 MCB TP /VFD Emerson 0.75kW Wet end auger Power: 0.75kW, 3Ph On/off/Trip time
12 MCB TP /VFD Nidec 0.75kW Biomas Auger Power: 0.75kW, 3Ph
13 MCB TP /VFD Nidec 4kW Dryer fans 1 Power: 2.2kW, 3Ph On/off/Trip time
14 MCB TP /VFD Nidec 4kW Dryer fans 2 Power: 2.2kW, 3Ph On/off/Trip time
15 MCB TP /VFD Emerson 0.75kW Dryer Belt Power: 0.37kW, 3Ph On/off/Trip time
16 MCB TP /VFD Emerson 0.75kW Dry end auger Power: 0.75kW, 3Ph On/off/Trip time
Belt K type Thermocouple Temperature

17 Dryer 2 MCB TP /VFD Delta 0.75k Biomass conveyor Power: 0.75kW, 3Ph On/off/Trip time
18 MCB TP /VFD Delta 0.75k Wet end auger Power: 0.75kW, 3Ph On/off/Trip time
19 MCB TP /VFD Delta 3.7k Dryer fans Power: 2.2kW, 3Ph On/off/Trip time
20 MCB TP /VFD Delta 3.7k Dryer fans Power: 2.2kW, 3Ph On/off/Trip time
21 MCB TP /VFD Delta 0.75k Dryer Belt Power: 0.37kW, 3Ph On/off/Trip time
22 MCB TP /VFD Dry end auger Power: 0.75kW, 3Ph On/off/Trip time
Belt K type Thermocouple Temperature
23 Pyrolysis 1 VFD Emerson 0.25kW Fuel auger 100W, 230V, 3Ph On/off/Trip time
24 VFD Emerson 0.25kW Combustion blower 100W, 230V, 3Ph On/off/Trip time
25 VFD Emerson 0.25kW Char auger 100W, 230V, 3Ph On/off/Trip time
26 Water in K type Thermocouple Temperature
27 Water out K type Thermocouple Temperature
28 Fire K type Thermocouple Temperature
29 Catalyst K type Thermocouple Temperature
30 Stack K type Thermocouple Temperature

31 Pyrolysis 1 VFD Emerson 0.25kW Fuel auger 100W, 230V, 3Ph On/off/Trip time
32 VFD Emerson 0.25kW Combustion blower 100W, 230V, 3Ph On/off/Trip time
33 VFD Emerson 0.25kW Char auger 100W, 230V, 3Ph On/off/Trip time
34 Water in K type Thermocouple Temperature
35 Water out K type Thermocouple Temperature
36 Fire K type Thermocouple Temperature
37 Catalyst K type Thermocouple Temperature
38 Stack K type Thermocouple Temperature

39 WWTP MCB TP Aeration tank Blower 1 Power: 1.1kW, 3Ph On/off/Trip time
40 MCB TP Aeration tank Blower 2 Power: 1.1kW, 3Ph On/off/Trip time
41 MCB TP Aeration tank Blower 3 Power: 1.1kW, 3Ph On/off/Trip time
42 MCB TP Aeration tank Blower 4 Power: 1.1kW, 3Ph On/off/Trip time
43 MCB DP Aeration tank pump Power :1.3kW, 1 Ph On/off/Trip time

44 Tertiary treatment RS 485 Water parameters pH meter pH


45 RS 485 Water parameters Online monitoring system BOD
46 RS 485 Water parameters Online monitoring system COD
47 RS 485 Water parameters Online monitoring system TSS
48 RS 485 Water parameters Electromagnetic Flow meter Flow rate
49 MCB DP Treated water pump Power: 0.75kW, 3Ph On/off/Trip time

50 Incommer panel Incommer panel Multifunction meter kWh, V, A, PF


51 DG panel Multifunction meter DG run time, kWh