General technical information
TABLE 2.1 Certified products ratings
R = Resistive / GP = General Purpose / GU = General Use / I = Inductive (cosϕ 0.4) / B = Ballast / NO = NO type
Ratings
Product Type UL file AC/DC “Motor Load” Pilot Duty Open Type Pollution Max
No. Single phase Devices degree Surrounding Air
Temperature
110-120 220-240
34.51 E106390 6 A – 250 Vac (GP) B300 – R300 Yes 2 40 °C
40.31 – 40.51 E81856 10 A – 250 Vac (R) 1/3 Hp (250 V) R300 Yes / 85 °C
40.52 E81856 8 A – 250 Vac (R) 1/6 Hp 1/3 Hp R300 Yes / 85 °C
8 A – 277 Vac (GP) (4.4 FLA) (3.6 FLA)
8 A – 30 Vdc (GP)
40.61 E81856 15 A – 250 Vac (R) ½ Hp (250 V) R300 Yes / 85 °C
40.31 NEW E81856 12 A – 277 Vac (GU) 1/3 Hp ¾ Hp B300 Yes 2 or 3 85 °C
12 A – 30 Vdc (GU) (7.2 FLA) (6.9 FLA)
40.61 NEW E81856 16 A – 277 Vac (GU) 1/3 Hp ¾ Hp B300 Yes 2 or 3 85 °C
16 A 30 Vdc (GU) (AgCdO) (7.2 FLA) (6.9 FLA)
12 A – 30 Vdc (GU)
(AgNi)
40.11 – 40.41 E81856 10 A – 240 Vac (R) / ½ Hp (250 V) / Yes / 70 °C
5 A – 240 Vac (I)
10 A – 250 Vac (GP)
8 A – 24 Vdc
0,5 A – 60 Vdc
0,2 A – 110 Vdc
0,12 A – 250 Vdc
41.31 E81856 12 A – 277 Vac (GU) 1/4 Hp ½ Hp B300 – R300 Yes 2 or 3 40 or 70 °C
12 A – 277 Vac (R) (5.8 FLA) (4.9 FLA) with a minimum
distance among relay
of 5 mm
41.61 E81856 16 A – 277 Vac (GU-R) ¼ Hp ½ Hp B300 – R300 Yes 2 or 3 40 or 70 °C
8 A – 277 Vac (B) (5.8 FLA) (4.9 FLA) with a minimum
distance among relay
of 5 mm
41.52 E81856 8 A – 277 Vac (GU-R) ½ Hp (277 V) B300 Yes 2 or 3 40 or 70 °C
8 A – 30 Vdc (GU; NO) (4.1 FLA ) with a minimum
distance among relay
of 5 mm
43.41 E81856 10 A – 250 Vac ¼ Hp ½ Hp B300 – R300 Yes 2 or 3 40 or 85 °C
(GU-R) (5,8 FLA ) (4.9 FLA)
4 A – 30 Vdc (R)
43.61 E81856 10 A – 250 Vac ¼ Hp ½ Hp B300 – R300 Yes 2 or 3 40 or 85 °C
(GU-R) (AgCdO) (5.8 FLA) (AgCdO) (4.9 FLA) (AgCdO)
16 A – 250 Vac 1/3 Hp ¾ Hp
(GU) (AgNi) (7.2 FLA) (AgNi) (6.9 FLA) (AgNi)
16 A – 250 Vac (R)
(AgCdO)
44.52 E81856 6 A – 277 Vac (R) 1/8 Hp 1/3 Hp / Yes / 85ºC
(3.8 FLA) (3.6 FLA)
44.62 E81856 10 A – 277 Vac (R) ¼ Hp ¾ Hp / Yes / 85ºC
(5.8 FLA) (6.9 FLA)
45.31 E81856 16 A – 277 Vac (GU)(Agni) 1/3 Hp 1 Hp / Yes 2 or 3 105 or 125 °C
(7.2 FLA) (8 FLA) (AgNi)1 Hp with a minimum
(AgNi; NO)1/3 Hp (8 FLA) (AgNi)1 Hp distance among relay
(7.2 FLA) (8 FLA) (AgNi)1 Hp of 10 mm
(AgNi; NO)1/3 Hp (8 FLA) (AgNi)1 Hp
(7.2 FLA) (8 FLA) (AgNi)
(AgNi; NO)1/3 Hp
(7.2 FLA)
(AgNi; NO)1/3 Hp
(7.2 FLA)
16 A – 30 Vdc (AgNi; NO)
(GU)(AgNi)16 A – 30 Vdc
(GU)(AgNi)16 A – 30 Vdc
(GU)(AgNi)16 A – 30 Vdc
(GU)(AgNi)16 A – 30 Vdc
(GU)(AgNi)
45.71 E81856 16 A – 240 Vac (GU) ½ Hp 1 Hp / Yes 2 or 3 105 or 125 °C
16 A – 30 Vdc (GU) (9.8 FLA) (AgCdO) (8 FLA) (AgNi) with a minimum
(AgCdO) 1/3 Hp distance among relay
16 A – 277 Vac (GU) (7.2 FLA) of 10 mm
16 A – 30 Vdc (AgNi; NO)
(NO-GU)
12 A – 30 Vdc
(NC-GU) (AgNi)
45.91 E81856 16 A – 277 Vac (GU)(AgNi) 1/6 Hp ½ Hp / Yes 2 or 3 105 or 125 °C
V-2014, www.findernet.com
(4.4 FLA)1/6 Hp (4.9 FLA)½ Hp with a minimum
(4.4 FLA)1/6 Hp (4.9 FLA)½ Hp distance among relay
(4.4 FLA)1/6 Hp (4.9 FLA)½ Hp of 10 mm
(4.4 FLA) (4.9 FLA)
16 A – 30 Vdc (GU)(AgNi)
46.52 E81856 8 A – 277 Vac (GU) ¼ Hp ½ Hp B300 – R300 Yes 2 or 3 70 °C
6 A – 30 Vdc (R) (5.8 FLA) (4.9 FLA)
V
General technical information
TABLE 2.1 Certified products ratings
R = Resistive / GP = General Purpose / GU = General Use / I = Inductive (cosϕ 0.4) / B = Ballast / NO = NO type
Ratings
Product Type UL file AC/DC “Motor Load” Pilot Duty Open Type Pollution Max
No. Single phase Devices degree Surrounding Air
Temperature
110-120 220-240
46.61 E81856 16 A – 277 Vac 1/3 Hp ¾ Hp B300 – R300 Yes 2 or 3 70 °C
12 A(NO)-10 A (NC) (7.23 FLA) (6.9 FLA) (AgNi)
30 Vdc (AgNi) A300 – R300
10 A(NO)-8 A(NC) (AgSnO2)(AgSnO2)
30 Vdc (AgSnO2)30 Vdc (AgSnO2) (AgSnO2)(AgSnO2)
30 Vdc (AgSnO2)30 Vdc (AgSnO2)
50 E81856 8 A – 277 Vac (GU) 1/3 Hp ½ Hp B300 (NO) Yes 2 or 3 70 °C
8 A – 30 Vdc (GU) (7.2 FLA) (4.9 FLA) with a minimum
(Only NO) (Only NO) distance among relay
of 5 mm
55.X2 – 55.X3 E106390 10 A – 277 Vac (R) 1/3 Hp ¾ Hp R300 Yes / 40 °C
10 A – 24 Vdc (R) (7.2 FLA) (6.9 FLA)
(55.X2)
5 A – 24 Vdc (R)
(55.X3)
55.X4 E106390 7 A – 277 Vac (GP) 1/8 Hp 1/3 Hp R300 Yes / 55 °C
7 A – 30 Vdc (GP) (3.8 FLA) (3.6 FLA)
(Std/Au contact)
5 A – 277 Vac (R)
5 A – 24 Vdc (R)
(AgCdO contact)
56 E81856 12 A – 277 Vac (GU) ½ Hp 1 Hp B300 Yes 2o3 40 or 70 °C
12 A – 30 Vdc (GU) (9.8 FLA) (8 FLA)
(AgNi; NO)
8 A – 30 Vdc (GU)
(AgNi; NC)
12 A – 30 Vdc (GU)
(AgCdO)
10 A – 30 Vdc (GU)
(AgSnO2; NO)(AgSnO2; NO)
8 A – 30 Vdc (GU)
(AgSnO2; NC)(AgSnO2; NC)
60 E81856 10 A – 277 Vac (R) 1/3 Hp 1 Hp B300 Yes / 40 °C
10 A – 30 Vdc (GU) (7.2 FLA) (8 FLA) (AgNi only)
R300
62 E81856 15 A – 277 Vac (GU) ¾ Hp 2 Hp B300 Yes 2 or 3 40 or 70 °C
10 A – 400 Vac (GU) (13.8 FLA) (12 FLA) (AgCdO)
8 A – 480 Vac (GU) 1 Hp R300
15 A – 30 Vdc (GU) (480 Vac - 3 f );
(480 Vac - 3 f )
(2.1 FLA) (NO)
65.31 E81856 20 A – 277 Vac (GU) 3/4 Hp 2 Hp / Yes / 70 °C
65.61 (13.6 FLA) (12.0 FLA)
65.31 NO 30 A – 277 Vac (GU)
65.61 NO
65.31-S 35 A – 277 Vac (GU) / / 85 °C
65.61-S
(DC coil, NO only)
66 E81856 30 A – 277 Vac (GU) 1 Hp 2 Hp / Yes 2 or 3 70 °C
(NO) (16.0 FLA) (12.0 FLA) (NO) with a minimum
distance among relay
10 A – 277 Vac (GU) (AgCdO, NO) of 20 mm
(NC) ½ Hp
24 A – 30 Vdc (GU) (9.8 FLA)
(NO) (AgNi)
30 A – 30 Vdc (GU)
(X6XX type only)
67 E81856 50 A – 277 Vac (GU) / / / Yes 3 85 °C
50 A – 480 Vac (GU) (60 °C - PCB)
(three phases)
70.61 E106390 6 A – 250 Vac (R) / / / Yes 2 50 °C
6 A – 24 Vdc (R)
20 E81856 16 A – 277 Vac (R) ½ Hp / / Yes / 40 °C
1000 W Tung. 120 V (9.8 FLA)
2000 W Tung. 277 V
85.02 – 85.03 E106390 10 A – 277 Vac (R) 1/3 Hp ¾ Hp / Yes / 40 °C
10 A – 24 Vdc (R) (7.2 FLA) (6.9 FLA)
(85.X2)
5 A – 24 Vdc (R)
(85.X3)
85.04 E106390 7 A – 277 Vac (GP) 1/8 Hp 1/3 Hp / Yes / 55 °C
V-2014, www.findernet.com
7 A – 30 Vdc (GP) (3.8 FLA) (3.6 FLA)
7T.81…2301 E337851 10 A – 250 Vac (R) 1 ½ Hp (250 Vac) / Yes 2 –20 / +40 °C
7T.81…2401 (10 FLA)
7T.81…2303 E337851 10 A – 250 Vac (R) 1 ½ Hp (250 Vac) / Yes 2 0 / +60 °C
7T.81…2403 (10 FLA)
86 E106390 / / / / Yes 2 35 or 50 °C
99 E106390 / / / / Yes 2 or 3 50 °C
VI
General technical information
TABLE 2.2 Certified products ratings
R = Resistive / GP = General Purpose / GU = General Use / I = Inductive (cosϕ 0.4) / B = Ballast / NO = NO type
Ratings
Product Type UL file AC/DC “Motor Load” Pilot Duty Open Type Pollution Max
No. Single phase Devices degree Surrounding Air
Temperature
110-120 220-240
22.32 – 22.34 E81856 25 – 277 Vac (GU) 3/4 Hp 2 Hp A300 Yes 2 50 °C
25 A – 30 Vdc (GU) (13.8 FLA / 82.8 LRA) (12 FLA / 72 LRA)
20 A – 277 Vac (B) (AgNi ; NO) (AgNi ; NO)
1/2 Hp 1.5 Hp
(9.8 FLA / 5.8 LRA) (10 FLA / 60 LRA)
(AgSnO2 ; NO) (AgSnO2 ; NO)
Three phase
(22.34 NO only)
3 Hp
(9.6 FLA / 64 LRA)
0.22.33 – 0.22.35 E81856 5 A – 277 Vac (GU) B300 Yes 2 50 °C
72.01 – 72.11 E81856 15 A – 250 Vac (R) ½ Hp (250 Vac) / Yes 2 or 3 50 °C
(4.9 FLA)
77.11 E359047 15 A – 277 Vac (GU-B) ¾ Hp 1 Hp / Yes 2 45 °C
77.31 E359047 30 A – 400 Vac (GU) ¾ Hp 1 Hp / Yes 2 40 °C
30 A – 277 Vac (B) ½ Hp (480 Vac)
80.01-11-21-41-91 E81856 8 A – 250 (R) ½ Hp (250 Vac) / Yes 2 40 °C
(4.9 FLA)
80.61 E81856 8 A – 250 (GU;R) / 1/3 Hp (250 Vac) R300 Yes 2 40 °C
(3.6 FLA)
80.82 E81856 6 A – 250 Vac (GU;R) / / B300 – R300 Yes 2 40 °C
83.X1 – 83.X2 E81856 12 A – 250 Vac (GU) / / / Yes 2 50 °C
83.62 E81856 8 A – 250 Vac (GU) / / / Yes 2 50 °C
7S E172124 6 A – 250 Vac (GU same polarity) / B300 (NO) Yes / 70 °C
6 A – 24 Vdc (GU)
Capacitor start motors
Single phase 230 V AC capacitor start motors have a starting current of
about 120% of the rated current. However, damaging currents can result
from an instantaneous reversal of the direction of rotation. In the first
diagram, high circulating currents can cause severe arcing across the
contact gap, as the changeover contacts make an almost instantaneous
reversal of polarity to the capacitor. Measurements have shown a peak
current of 250 A for a 50 Watt motor, and up to 900 A for a 500 Watt motor.
This inevitably leads to welding of the contacts. Incorrect AC motor reversal: Correct AC motor reversal:
Reversing the direction of such motors should therefore use two relays, Contact is in the intermediate state for Provision of 300 ms “dead break”
as the second diagram shows, whereby in the control to the relay coils a less than 10 ms – insufficient time to time when neither relay contacts are
allow the energy in the capacitor to closed - during which time the capacitor
“dead break” of approximately 300 ms is provided. The delay can either be
dissipate before the electrical connection discharges harmlessly through the motor
provided by another control component such as a Timer, or through the is remade to the opposite polarity. windings.
Microprocessor etc., or by connecting a suitable NTC resistance in series
with each relay coil. Cross interlocking the coil circuits of both relays will
not produce the required delay! Moreover, the use of anti-weld contact
material will not solve the problem.
V-2014, www.findernet.com
VII
General technical information
TABLE 2.3 Certified sockets ratings
Socket type UL ratings CSA ratings Open Pollution Max System Conductors Wire size Terminal
Type degree Surrounding Air Overvoltage to be used (AWG) tightening
Devices (Installation Temperature Category (max torque
environment) peak Voltage
impulse)
90.02/03 10 A 300 V 10 A 300 V 70 °C
(max 20 A Total
Load)
90.14/15 10 A 300 V 10 A 250 V
90.20/21/26/27 10 A 300 V 10 A 250 V
90.82.3 10 A 300 V 10 A 300 V 70 °C 14-20 7.08 lb.in.
stranded (0.8 Nm)
and solid
90.83.3 10 A 300 V 10 A 300 V 65 °C 14-20 7.08 lb.in.
stranded (0.8 Nm)
and solid
92.03 16 A 300 V 10 A 250 V 70 °C 75 °C Cu only 10-24, 7.08 lb.in.
(max 20 A Total stranded (0.8 Nm)
Load) or solid
92.13/33 16 A 300 V 10 A 250 V
93.01/51 6 A 300 V 6 A 250 V 60 °C 75 °C Cu only 14-24,
stranded
or solid
93.02/52 2 x 10 A 300 V (60 °C) 2 x 10 A 300 V (60 °C) Yes 2 60 or 70 °C II (2.5 kV) 75 °C Cu only
2 x 8 A 300 V (70 °C) 2 x 8 A 300 V (70 °C) (CSA)
93.11 6 A 300 V 6 A 300 V 70 °C
93.21 6 A 300 V / Yes 2 70 °C
93.60/65/66/67/68 6 A 300 V (40 °C) 6 A 300 V (40 °C) 40 or 70 °C 75 °C Cu only 14-24,
4 A 300 V (70 °C) 4 A 300 V (70 °C) stranded
or solid
93.61/62/63/64/68 6 A 300 V (40 °C) 6 A 300 V (40 °C) 40 or 70 °C 75 °C Cu only 14-24, 4.43 lb.in.
4 A 300 V (70 °C) 4 A 300 V (70 °C) stranded (0.5 Nm)
or solid
09368141 100 mA 24V 100 mA 24V 70 °C
94.02/03/04 10 A 300 V 10 A 250 V 70 °C 75 °C Cu only 10-24 4.43 lb.in.
(max 20 A Total stranded, (0.5 Nm)
Load) 12-24 solid
94.12/13/14 10 A 300 V 10 A 250 V
(4 pole: 5A 300 V)
94.22/23/24 10 A 300 V 10 A 250 V
94.33/34 10 A 300 V 10 A 250 V
(4 pole: 5A 300 V)
94.54 10 A 300 V Yes 70 °C Copper only 14-18-24
stranded
and solid
94.62/64 10 A 300 V 10 A 250 V
94.72/73/74 10 A 300 V 10 A 250 V
(94.74: max 20 A
Total Load)
94.82 10 A 300 V 10 A 250 V
94.82.3/92.3 10 A 300 V Yes 70 °C
94.84.3/94.3 10 A 300 V Yes 55 °C
94.82.2 10 A 300 V Yes 50 °C
94.84.2 7 A 300 V Yes 50 °C
95.03/05 10 A 300 V 10 A 250 V 70 °C 75 °C Cu only 10-24 4.43 lb.in.
(max 20 A Total stranded, (0.5 Nm)
Load) 12-24 solid
95.13.2/15.2 12 A 300 V 10 A 300 V Yes 70 °C
(max 20 A Total with a minimum
Load) distance of 5 mm
95.55/55.3 10 A 300 V (40 °C) 10 A 300 V (40 °C) Yes 40 or 70 °C 14-24
8 A 300 V (70 °C) 8 A 300 V (70 °C) stranded
and solid
95.23 10 A 300 V 10 A 250 V
95.63/65/75 10 A 300 V 10 A 250 V
95.83.3/85.3/ 12 A 300 V Yes 85 °C 14-18, 7.08 lb. in.
93.3/95.3 stranded (0.8 Nm)
or solid
96.02/04 12 A 300 V (50 °C) 12 A 300 V (50 °C) Yes 50 or 70 °C III (4.0 kV) 60/75 °C Cu only 10-14, 7.08 lb.in.
10 A 300 V (70 °C) 10 A 300 V (70 °C) 75 °C Cu only stranded (0.8 Nm)
(CSA) or solid
96.12/14 12 A 300 V 15A 250 V
96.72/74 15 A 300 V 10 A 250 V
(max 20 A Total
Load)
97.01 16 A 300 V (50 °C) 16 A 300 V (50 °C) Yes 50 or 70 °C 75 °C Cu only
12 A 300 V (70 °C) 12 A 300 V (70 °C) (CSA)
97.02 2x8 A 300 V 2x8 A 300 V Yes 70 °C 75 °C Cu only
(CSA)
97.11 16 A 300 V (50 °C) / Yes 50 or 70 °C
12 A 300 V (70 °C) with a minimum
distance of 5 mm
97.12 2 x 8 A 300 V / Yes 70 °C
V-2014, www.findernet.com
with a minimum
distance of 5 mm
97.51 - 97.51.3 15 A 300 V (40 °C) 15A 300 V (40 °C) Yes 40 or 70 °C 14-24
(2-wires/per pole) 10 A 300 V (70 °C) stranded
10 A 300 V (70 °C) and solid
97.52 - 97.52.3 10 A 300 V (40 °C) 8 A 300 V Yes 70 °C 14-24
8 A 300 V (70 °C) stranded
and solid
VIII