VFD User Manual
VFD User Manual
MH300G 4T 0.75 GB
MH300 series Braking unit
blank no
A B H H1 W D
Single phase 220V
94 150 161 105 135 Ø 1.1 2.3/4.0/7.
MH200G2S0.4/0.7/1.5/2.2GB
4.0 0/9.6
113 172 186 125 164 Ø 1.1 2.3/4.0/7.
MH300G2S0.4/0.7/1.5/2.2GB
5.0 0/9.6
Three phase 380V
94 150 161 105 135 Ø 1.1 2.1/3.8/5.
MH200G4T0.7/1.5/2.2GB
4.0 1
113 172 186 125 164 Ø 1.1 2.1/3.8/5.
MH300G4T0.7/1.5/2.2GB
5.0 1
MH300/200G4T3.7GB/5.5PB 9.0/13
Ø
148 236 248 / 160 183 2.5 13/17
MH300/200G4T5.5GB/7.5PB 5.0
MH300/200G4T7.5GB/11PB 17/25
MH300/200G4T11GB/15PB 25/32
190 305 322 / 208 192 Ø6 6.5
MH300/200G4T15GB/18.5PB 32/37
MH300/200G4T18.5GB/22PB 37/45
MH300/200G4T22GB/30PB 45/60
MH300/200G4T30GB/37PB 60/75
Ø6
MH300/200G4T37GB/45PB
274 465 / 48 315 234 24 75/91
0
MH300/200G4T45GB 91
MH300/200G4T55GB/75PB 112/150
320 530 / 55 360 265 Ø8 41.5
MH300/200G4T75GB/90PB 150/176
5
MH300/200G4T90GB/110PB 176/210
370 600 / 63 410 300 Ø10 56.5
MH300/200G4T110GB/132PB 210/253
0
360 740 76 516 326 Ø10 87 253/304
MH300/200G4T132G/160P
5 304/350
MH300/200G4T160G/180P
MH300/200G4T180G/200P 350/377
390 882 / 91 560 342 Ø10 90
MH300/200G4T200G/220P 377/426
0
MH300/200G4T220G/250P 426/465
470 1310 / 13 535 380 Ø10 185
MH300/200G4T250G/280P 465/520
40
MH300/200G4T280G/315P 520/585
MH300/200G4T315G/355P 585/650
Ø10
545 1563 / 15 600 380 233 650/725
MH300/200G4T355G/400P
MH300/200G4T400G/450P 93 725/750
MH300/200G4T/450G 750
L1、L2 Single-phase power supply input terminals Connect to the single-phase 220
VAC power supply.
R、S、T Three-phase power supply input terminals Connect to the Three-phase 380
VAC power supply.
(+)、(-) Positive and negative terminals of DC bus Common DC bus input point.
(Caution: between CME and COM, OP and +24V without short tab, the user chose connection mode through J10,
J9, the factory default CME and COM, OP and +24V short circuit)
External +24V Provide +24 V power supply to external unit. Generally, it provides
+24V-COM power Supply power supply to DI/DO terminals and external sensors.
Maximum output current: 200 mA
Input terminal of Connect to +24 V by default. When DI1-DI5 need to be driven by
OP external power external signal, OP needs to be connected to external power
supply supply and be disconnected from +24 V.
Mochuan Drives- MH300/200 User Manual
AI1-GND Analog input 1 Input voltage range: 0–10 VDC. Impedance: 22 kΩ
Analog input
interface
J3 Support various types of PG cards: OC,differential, UVW and
PG card interface
resolver.
J7 External
Connect to external operation panel.
operation
panel interface
1: G type (constant torque load); 2: P type (variable torque load e.g. Model
P0-00 G/P type display ●
fan and pump) dependent
Command source 0: Operation panel control (LED off);1: Terminal control (LED on)
P0-02 0 ☆
selection 2: Communication control (LED blinking);
selection
0: Main frequency source X; 1: X and Y operation (operation
relationship determined by ten's digit); 2: Switchover between X and
00 ☆
Y; 3: Switchover between X and "X and Y operation"; 4: Switchover
between Y and "X and Y operation"
P0-12 Frequency upper limit Frequency lower limit (P0-14) to maximum frequency (P0-10) 50.00 Hz ☆
P0-14 Frequency lower limit 0.00 Hz to frequency upper limit (P0-12) 0.00 Hz ☆
Model
P0-15 Carrier frequency 0.5–16.0 kHz ☆
dependent
Carrier frequency
P0-16 adjustment with 0: No; 1: Yes 1 ☆
temperature
Model
P0-17 Acceleration time 1 0.00–650.00s (P0-19 = 2) ☆
dependent
0.0–6500.0s (P0-19 = 1)
Model
P0-18 Deceleration time 1 0–65000s (P0-19 = 0) ☆
dependent
Acceleration/Deceleration
P0-19 0:1s; 1: 0.1s; 2: 0.01s 1 ★
time unit
Frequency offset of
auxiliary frequency
P0-21 0.00 Hz to maximum frequency (P0-10) 0.00 Hz ☆
source for X and
Y operation
Frequency eference
P0-22 1: 0.1 Hz; 2: 0.01 Hz; 2 ★
resolution
Acceleration/Deceleration
P0-25 0: Maximum frequency (P0-10); 1: Set frequency; 2: 100 Hz; 0 ★
time base frequency
Serial communication
P0-28 0: Modbus protocol; 1: Profibus-DP bridge; 2: CANopen bridge 0 ☆
protocol
Model
P1-01 Rated motor power 0.1–1000.0 kW ★
dependent
Model
P1-02 Rated motor voltage 1–2000 V ★
dependent
Function
Parameter Name Setting Range Default Property
Code
Mochuan Drives- MH300/200 User Manual
Model
P1-04 Rated motor frequency 0.01 Hz to maximum frequency ★
dependent
Rated motor rotational Model
P1-05 1–65535 RPM ★
speed dependent
Stator resistance 0.001–65.535 Ω (AC drive power ≤ 55 kW) Model
P1-06 ★
(asynchronous motor) 0.0001–6.5535 Ω (AC drive power > 55 kW) dependent
Rotor resistance 0.001–65.535 Ω (AC drive power ≤ 55 kW) Model
P1-07 ★
(asynchronous motor) 0.0001–6.5535 Ω (AC drive power > 55 kW) dependent
Leakage inductive
0.01–655.35 mH (AC drive power ≤ 55 kW) Model
P1-08 reactance ★
0.001–65.535 mH (AC drive power > 55 kW) dependent
(asynchronous motor)
Mutual inductive
0.1–6553.5 mH (AC drive power ≤ 55 kW) Model
P1-09 reactance ★
0.01–-655.35 mH (AC drive power > 55 kW) dependent
(asynchronous motor)
No-load current 0.01 to P1-03 (AC drive power ≤55 kW) Model
P1-10 ★
(asynchronous motor) 0.1 to P1-03 (AC drive power >55 kW) dependent
mode of P2-10.
Mochuan Drives- MH300/200 User Manual
Excitation adjustment
P2-13 proportional gain 0–20000 2000 ☆
Excitation adjustment
P2-14 integral gain 0–20000 1300 ☆
Torque adjustment
P2-15 proportional gain 0–20000 2000 ☆
Torque adjustment
P2-16 integral gain 0–20000 1300 ☆
Field weakening
Voltage rise time of V/F 0.0–1000.0s It indicates the time for the voltage rising from 0 V to
P3-15 0.0s ☆
separation rated motor voltage.
P4-03 DI4 function selection input of external fault; 34: Frequency modification forbidden 12 ★
35: Reverse PID action direction; 36: External STOP terminal 1
37: Command source switchover terminal 2; 38: PID integral pause;
P4-04 DI5 function selection 13 ★
39: Switchover between main; frequency source X and preset
P4-05 DI6 function selection frequency; 40: Switchover between auxiliary; frequency source Y and 0 ★
preset frequency; 41: Motor selection terminal 1
P4-06 DI7 function selection 42: Motor selection terminal 2; 43: PID parameter switchover 0 ★
44: User-defined fault 1; 45: User-defined fault 2; 46: Speed
P4-07 DI8 function selection control/Torque control switchover; 47: Emergency stop; 48: External 0 ★
Corresponding setting of
P4-14 -100.00%–100.0% 0.0% ☆
AI curve 1 minimum input
Corresponding setting of
P4-16 -100.00%–100.0% 100.0% ☆
AI curve 1 maximum input
Corresponding setting of
P4-19 -100.00%–100.0% 0.0% ☆
AI curve 2 minimum input
Corresponding setting of
P4-21 -100.00%–100.0% 100.0% ☆
AI curve 2 maximum input
Corresponding setting of
P4-24 -100.00%–100.0% 0.0% ☆
AI curve 3 minimum input
Function
Parameter Name Setting Range Default Property
Code
Corresponding setting of
P4-26 -100.00%–100.0% 100.0% ☆
AI curve 3 maximum input
Corresponding setting of
P4-29 -100.00%–100.0% 0.0% ☆
pulse minimum input
Corresponding setting of
P4-31 -100.00%–100.0% 100.0% ☆
pulse maximum input
Setting for AI less than Ten's digit (Setting for AI2 less than minimum input)
P4-34 000 ☆
minimum input
0, 1 (same as AI1)
0, 1 (same as AI1)
Unit's digit (DI1 valid mode): 0: High level valid; 1: Low level valid
P4-38 DI valid mode selection 1 00000 ★
Ten's digit (DI2 valid mode): 0, 1 (same as DI1)
Hundred's digit (DI3 valid mode): 0, 1 (same as DI1)
P5-00 FM terminal output mode 0: Pulse output (FMP); 1: Switch signal output (FMR)
0 ☆
P5-01 FMR function (open- 0: No output; 1: AC drive running; 2: Fault output (stop); ☆
2
collector output terminal) 3: Frequency-level detection; FDT1 output; 4: Frequency reached
5: Zero-speed running (no output at stop); 6: Motor overload
P5-02 Relay function pre-warning; 7: AC drive overload pre-warning; 8: Set count value
(T/A-T/B-T/C) reached; 9: Designated count value reached; 10: Length reached
11: PLC cycle complete; 12: Accumulative running time reached
13: Frequency limited ;14: Torque limited; 15: Ready for RUN
16: AI1 larger than AI2; 17: Frequency upper limit reached
18: Frequency lower limit reached (no output at stop)
2 ☆
19: Under voltage state output; 20: Communication setting
21: Reserved; 22: Reserved; 23: Zero-speed running 2 (having
Extension card relay
P5-03 output at stop); 24: Accumulative power-on time reached 0 ☆
function (P/A-P/B-P/C)
25: Frequency level detection FDT2 output; 26: Frequency 1 reached
27: Frequency 2 reached; 28: Current 1 reached; 29: Current 2
reached; 30: Timing reached; 31: AI1 input limit exceeded; 32: Load
DO1 function selection becoming 0; 33: Reverse running; 34: Zero current state; 35: Module
P5-04 (open-collector output temperature reached; 36: Software current limit exceeded
terminal) 37: Frequency lower limit reached (having output at stop)
1 ☆
38: Alarm output; 39: Motor overheat warning; 40: Current running
time reached; 41: Fault output (There is no output if it is the coast to
Extension card DO2 stopfault and undervoltage occurs.)
P5-05 4 ☆
function
0000–FFFF
Bit00: Running frequency 1 (Hz); Bit01: Set frequency (Hz)
Bit02: Bus voltage (V); Bit03: Output voltage (V)
Bit04: Output current (A); Bit05: Output power (kW)
LED display running
P7-03 Bit06: Output torque (%); Bit07: DI input status 1F ☆
parameters 1
Bit08: DO output status; Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V); ; Bit11: AI3 voltage (V)
Bit12: Count value; ; Bit13: Length value
Bit14: Load speed display; Bit15: PID setting
0000–FFFF
Bit00: PID feedback; Bit01: PLC stage; Bit02: Pulse setting frequency
(kHz); Bit03: Running frequency 2 (Hz); Bit04: Remaining running
time; Bit05: AI1 voltage before; correction (V); Bit06: AI2 voltage
LED display running before; correction (V); Bit07: AI3 voltage; before correction (V); Bit08: 0 ☆
P7-04
parameters 2 Linear speed; Bit09: Current power-on time; (Hour); Bit10: Current 0
running time (Min); Bit11: Pulse setting frequency; (Hz); Bit12:
Communication setting value; Bit13: Encoder feedback speed (Hz)
Bit14: Main frequency X display (Hz); Bit15: Auxiliary frequency Y
display (Hz)
0000–FFFF
Bit00: Set frequency (Hz); Bit01: Bus voltage (V); Bit02: DI input
LED display stop status; Bit03: DO output status; Bit04: AI1 voltage (V); Bit05: AI2
P7-05 33 ☆
parameters voltage (V); Bit06: AI3 voltage (V); Bit07: Count value; Bit08: Length
value; Bit09: PLC stage; Bit10: Load speed; Bit11: PID setting
Bit12: Pulse setting frequency (kHz)
Heatsink temperature of
P7-07 0.0–100.0°C - ●
inverter module
Temporary software
P7-08 - - ●
version
Function
Parameter Name Setting Range Default Property
Code
Accumulative running
P7-09 0–65535 h - ●
time
P7-10 Product number - - ●
Accumulative power-on
P7-13 0–65535 h 0h ●
time
Accumulative power
P7-14 0–65535 kWh - ●
consumption
Group P8: Auxiliary Functions
Frequency jump
P8-11 0.00 Hz to maximum frequency 0.00 Hz ☆
amplitude
Forward/Reverse rotation
P8-12 0.0–3000.0s 0.0s ☆
dead-zone time
Accumulative power-on
P8-16 0–65000 h 0h ☆
time threshold
Accumulative running
P8-17 0–65000 h 0h ☆
time threshold
0: No
P8-18 Startup protection 0 ☆
1: Yes
Frequency detection
P8-19 0.00 Hz to maximum frequency 50.00 Hz ☆
value FDT1)
Frequency detection
P8-20 Hysteresis (FDT 0.0%–100.0% (FDT1 level) 5.0% ☆
hysteresis 1)
Detection range of
P8-21 0.00–100% (maximum frequency) 0.0% ☆
frequency reached
Frequency switchover
point between
P8-25 0.00 Hz to maximum frequency 0.00 Hz ☆
acceleration time 1and
acceleration time 2
Frequency switchover
point between
P8-26 0.00 to maximum frequency 0.00 Hz ☆
deceleration time 1
and deceleration time 2
Frequency detection
P8-28 0.00 to maximum frequency 50.00 Hz ☆
value (FDT2)
Frequency detection
P8-29 0.0%–100.0% (FDT2 level) 5.0% ☆
hysteresis (FDT
hysteresis 2)
Any frequency reaching
P8-30 0.00 Hz to maximum frequency 50.00 Hz ☆
detection value 1
P8-48 Cooling fan control 0: Fan working during running; 1: Fan working continuously; 0 ☆
P8-49 Wakeup frequency Dormant frequency (P8-51) to maximum frequency (P0-10) 0.00 Hz ☆
Overvoltage stall
P9-04 120%–150% 130% ☆
protective voltage
P9-05 Overcurrent stall gain 0–100 20 ☆
Overcurrent stall
P9-06 100%–200% 150% ☆
protective current
Short-circuit to ground 0: Disabled
P9-07 1 ☆
upon power-on 1: Enabled
P9-16 3rd (latest) fault type over-speed; 45: Motor overheat; 51: Initial position fault - ●
Ten's digit (Power input phase loss, Err12): Same as unit's digit 00000 ☆
Hundred's digit (Power output phase loss, Err13): Same as unit's digit 00000 ☆
Thousand's digit (External equipment fault, Err15) : Same as unit's
00000 ☆
digit
Fault protection action Unit's digit (User-defined fault1 Err27),: Same as unit's digit in P9-47
P9-49
selection 3 Ten's digit (User-defined fault 2 Err28),: Same as unit's digit in P9-47
00000 ☆
Same as unit's digit in P9-47
Fault protection action Hundred's digit (Initial position fault, Err51):Same as unit's digit in
P9-50
selection 4 P9-47
00000 ☆
Thousand's digit (Speed feedback fault, Err52):Same as unit's digit in
P9-47
Type of motor
P9-56 0: No temperature sensor; 1: PT100; 2: PT1000; 1 ☆
temperature sensor
Over-speed detection
P9-67 0.0%–50.0% (maximum frequency) 20.0% ☆
value
Over-speed detection
P9-68 0.0–60.0s 1.0s ☆
time
PA-02 PID feedback source 0: AI1; 1: AI2; 2: AI3; 3: AI1 – AI2; 4: Pulse setting (DI5); 0 ☆
5: Communication setting; 6: AI1 + AI2; 7: MAX (|AI1|, |AI2|)
8: MIN (|AI1|, |AI2|)
PA-14 Reserved - - ☆
PA-18 PID parameter 0: No switchover; 1: Switchover via DI;2: Automatic switchover based on s0 ☆
switchover condition Deviation; 3: Automatic switchover based on running frequency
0: Invalid:1: Valid; 00 ☆
PA-28 PID operation at stop 0: No PID operation at stop;1: PID operation at stop; 0 ☆
Swing frequency
Pb-01 0.0%–100.0% 0.0% ☆
amplitude
Jump frequency
Pb-02 0.0%–50.0% 0.0% ☆
amplitude
0: No; 1: Yes 00 ☆
0: 300 BPs; 1: 600 BPs; 2: 1200 BPs; 3: 2400 BPs; 4: 4800 BPs; 5:
9600 BPs; 6: 19200 BPs; 7: 38400 BPs; 8: 57600 BPs; 9: 115200 BPs
Pd-01 Data format 0: No check, data format <8,N,2>;1: Even parity check, data format ; 2: 0 ☆
Odd Parity check, data format<8,O,1>; 3: No check, data format
<8,N,1>
Valid for Modbus <8,E,1>; 2: Odd Parity check, data format <8,O,1>; 3:
No check, data format <8,N,1> Valid for Modbus
Mochuan Drives- MH300/200 User Manual
Pd-05 Modbus protocol Unit's digit: Modbus protocol: 0: Non-standard Modbus protocol; 1: 31 ☆
selection and Standard Modbus protocol
FIBUS-DP data
Ten's digit: PROFIBUS-DP data: 0: PPO1 format: 1: PPO2 format
Format
2: PPO3 format; 3: PPO5 format
PP-01 Restore default settings 0: No operation; 01: Restore factory settings except motor parameters
02: Clear records; 04: Restore user; backup parameters; 501: Back up 0 ★
current user parameters
Parameter 0: Modifiable
PP-04 0 ☆
modification property 1: Not modifiable
in torque control 5: Communication setting; 6: MIN (AI1, AI2); 7: MAX (AI1, AI2)
Acceleration time in
A0-07 0.00–65000s 0.00s ☆
torque control
Deceleration time in
A0-08 0.00–65000s 0.00s ☆
torque control
Compensation 0f ☆
0.0~100.0% 0.0
friction torque at Low
A0-09
speed
Compensation 0f ☆
A0-10 0.0~100.0% 0.0
friction torque at high
speed
Friction compensation ☆
A0-11 0.00~20.00 2.00
switch over frequency
Faults and Solutions The MH300 provides a total of 24 pieces of fault information and protective
functions. After a fault occurs, the AC drive implements the protection function, and displays the fault code on
the operation panel (if the operation panel is available). Before contacting Manufacture for technical support,
you can first determine the fault type,analyze the causes, and perform troubleshooting according to the
following tables. If the fault cannot be rectified, contact the agent or Manufacture. Err22 is the AC drive
hardware over-current or over-voltage signal. In most situations, hardware over-voltage fault causes Err22.
Solutions to the faults of the MH300.
Fault Name Display Fault Name Display