Technical Documentation
Technical Documentation
Cooling Water
Collection Tank
Drawings:
Equipment:
3) Qualitrol - Liquid Level Control Gages Technical Information (en)
Attention:
All equipment is stated in English language (en).
1) Drawing No.: 36003-01-3001 Cooling Water Collection
Tank
12100-13-01 Sign plate
2) 36001-07-50 Technical Specification
4)
5)
PipeCon as
6)
7)
8)
9)
10)
11)
12)
Technical Specification
36001-07-50-0
Surface treatment.
Leak test: All welding and connections to be leak tested with air pressure, 0,1 bar and brushing
with soapy water.
PipeCon as
Edit. 0 Page 1/2
Technical Specification
36001-07-50-0
QC – documentation: Workshop test sheet.
Final documentation:
Final documentation will consist of
PipeCon as
Edit. 0 Page 2/2
6 “Liquid Level Control Gages
Prevent
problems
long life, 6” Liquid Level
Control Gages
high reliability,
low price
Qualitrol Liquid Level Control Gages actuate two switches, if included, at
are designed to provide level control the pre-selected levels.
for machinery, day tanks, storage vessels
and most any equipment requiring The Qualitrol magnetic gage design
liquid level control. Models are permits the complete sealing of the
available for top- or side-mounting in liquid inside the vessel from the dial
vessels with pressure up to 25 psig. switching assembly, outside. This
eliminates fire hazards, loss of product,
A gage can provide the following incorrect level reading or equipment
functions: downtime due to broken glass or
Low level alarm or control leaking seals, bellows, or diaphragms.
High level alarm or control
Indicate level at all times
Qualitrol Liquid Level Control Gages cost less than separate instruments
performing similar functions. Installation costs are also reduced by
mounting only one rather than several controls.
Design simplicity and ruggedness coupled with long life snap switches
provide long term reliability—to minimize costly maintenance and
equipment downtime.
Switching versatility Switching can be supplied for various liquid levels. Large differential
levels, up to 140° of float travel, can also be controlled. Switches can
be preset to within 2° of dial reading.
Snap switches are rated at 10 AMPS, 125-150 VAC; 1/8 AMP, 250
VCD; 1/4 AMP, 125 VDC, Inductive.
Ease of use High visibility dials can be custom lettered or selected from standard
designs. Standard dials are calibrated a full 280° for gear-driven gages
and 140° for lever-driven models. To provide monitoring at maximum
distances, large characters are placed on a contrasting background.
Standard scratch resistant glass lens gives clear visibility without
distortion, even when viewed at an angle.
Standard dial layouts are for use on a square-sided vessel with the gage
mounted at the center of the liquid to be measured.
Options available Gages with switches are supplied with 12” long, “flying” leads. Optional
quick connect, sealed, weatherproof, electrical connectors, with
neoprene-jacketed flexible control cable, are available.
The standard units are supplied with black and white dials, as shown,
but for unusual applications special printing is possible.
Model Selection and Installation
switches
Cutaway view of typical 6”
gear drive gage with switches
float
float rod
* Dimension shown is maximum liquid level that the specific gage will monitor.
Consult the factory for any variation you may require.
**Gage supplied with 3. #16 AWG, 12” long “flying” leads.
Dimensions
Lever drive
Gear drive Lever drive
4 1/2” 2 3/16”
full 7 1/8” 4 1/4”
140° max.
travel
20°
stop
empty
Note: all dimensions are for reference and
1/2” clearance are subject to change
bottom of tank
H
full
1/2 Gear drive high alarm
1/4 3/4
0 F
C
full J D
E
tank
20° stop 140° max. A
travel
low alarm
empty
empty F empty
1/2” clearance G
bottom of tank
B
Note: maximum of 2 SPDT switches are available
MAX
9
G DA L-0 26 -6 2
LIQUID
+25°C LEVEL
MIN
QU
AL I
T RO L COR P . FA I
RP
O RT
NY
U
.S
.A
Connector
Nut Style
(refer to device wiring
Bezel Type Lens Material
& connector styles)
o Permanent (std.)
o Tempered Glass
o Removable
o Polycarbonate
(requires Outdoor, Vented) External Wiring
o Snap-On w/ Test Feature (refer to device wiring & connector styles)
(requires Outdoor, Vented) o Polycarbonate
o Cable o 16 Ga. SOW-A/SO (Std.)
o Other (consult factory)
o Flying o 16 Ga. TEW (Std.)
Leads o 16 Ga. TEF
o 14 Ga. TEW
o None
o Connector
Note: Not all option combinations are available, Parts Only
please consult factory.
Length of Cable or Flying Leads
o Inches o Meters
Specify 6" increments Can be specified to 0.1 m
Length
Connector Orientation
o At 3 o'clock (requires Outdoor, Sealed)
o At 6 o'clock (std.)
min/max length
Application/Float Rod Style in inches [mm]
o Roller (for Bladder bags, U.S. Style) 27.0 [686] / 105.0 [2667]
o Straight (for Straight Float Rods) 6.0 [152] / 42.0 [1067]
o G-Roller (for Bladder Bags, Euro Style) 11.8 [300] / 98.4 [2500]
minimum A,B,C,D
Gear Ratio angular separation
o 2:1 Recommended for float travel > 45 degrees 6°
o 3:1 Non-Standard 4°
o 4:1 Recommended for float travel 45 degrees 3°
Data Type *use minus sign (-) for angles or oil levels below horizontal c/l
Radius Data Input and plus sign (+) for angles or oil levels above horizontal c/l
o Angles
Given from o Inches Can be o Millimeters Specify Max Angle/Level *A = 20°C/25°C Angle/Level
(required) (required except when ordering *C =
Horizontal Center Line specified to .10" increments in 1 mm increments flange assembly only)
o Oil Levels Min Angle/Level Optional Grad Angle/Level
Length = (required) *B = D must be between C & B *D =
Given from (optional 4th graduation mark)
Horizontal Center Line Note : If radius is specified in mm, then ROLLER/ Notes: (A-B) x (Gear Ratio) must be between 45° and 270° inclusive.
(Same Units as Radius)
G-ROLLER float rod hardware will be metric. Maintain minimum A,B,C,D angular separation per Gear Ratio table.
Gear Drive Flange Mounting Styles (in inches unless otherwise noted) Flange Construction
o 45E31 45° 3.125 Ø.28 2.75 O.D. x 2.13 I.D. x .13 x .06 DP. #10-32 o STD o HEAVY DUTY Support Tube Flange
o 45E32 45° 3.125 Ø.34 2.75 O.D. x 2.13 I.D. x .06 DP. #10-32 o STD Length (inches/mm) Construction
o 45E33 45° 3.125 Ø.34 2.75 O.D. x 2.13 I.D. x .13 x .06 DP. #10-32 o STD o HEAVY DUTY o 2.17 / 55MM
o 45E34 45° 3.125 Ø.34 2.63 O.D. x 1.75 I.D. x .08 DP. #10-32 o STD o 2.50 / 63MM STD Only
o 45E41 45° 4.000 Ø.44 3.38 O.D. x 2.63 I.D. x .06 DP. #10-32 o STD o 2.76 / 70MM
o 45E42 45° 4.000 Ø.44 N/A #10-32 o STD o 3.15 / 80MM
o 45E43 45° 4.000 Ø.44 3.38 O.D. x 2.63 I.D. x .13 x .09 DP. #10-32 o STD o HEAVY DUTY o 3.58 / 91MM
o 45E44 45° 4.000 Ø.44 3.38 O.D. x 2.63 I.D. x .09 DP. #10-32 o STD o 3.94 / 100MM
o 45E45 45° 4.750 Ø.56 4.00 O.D. x 3.12 I.D. x .12 DP. #10-32 o STD STD or
o 4.25 / 108MM
o 45E51 45° 5.000 Ø.34 3.81 O.D. x 3.31 I.D. x .13 DP. #10-32 o STD o HEAVY DUTY HEAVY DUTY
o 4.92 / 125MM
o 90E31 90° 3.125 Ø.34 2.75 O.D. x 2.13 I.D. x .06 DP. #10-32 o STD o 5.25 / 133MM
o 90E32 90° 3.125 Ø.28 2.75 O.D. x 2.13 I.D. x .06 DP. #10-32 o STD o HEAVY DUTY o 5.91 / 150MM
o 90E33 90° 3.125 Ø.28 N/A #10-32 o STD o 6.38 / 162MM
o 90E34 90° 3.125 Ø.34 2.75 O.D. x 2.13 I.D. x .13 x .06 DP. #10-32 o STD HEAVY DUTY
o 7.87 / 200MM
o 90E35 90° 3.125 Ø.34 2.63 O.D. x 1.75 I.D. x .08 DP. #10-32 o STD Only
o 10.4 / 265MM
o 45M41 45° 4.000 Ø13MM N/A M5 o STD o HEAVY DUTY o 11.5 / 292MM
o 45M42 45° 4.000 Ø7MM 87MM O.D. x 72.4MM I.D. x 4.3MM DP. M5 o STD o HEAVY DUTY
FLANGE
OPTION
B.C. HOLE GASKET GROOVE CASE MOUNTING Mounting Angle
o 0 (Horizontal)
o -15 degrees
o -30 degrees
o -45 degrees
HOLE o Other
ORIENTATION
2 0
5
2
2
I N
I N
B A
L
- M A X M
- M A X M
L
I
+25°C +20°C +25°C +25°C
A
-
-
6 W
6 W
D 6 W
D 6 W
D
MIN NY
U
.S
.A
MIN NY
U
. S
.A
LO NY
U
.S
.A
BAJO NY
U
.S
.A
T RT RT T
QU OR QU O QU O QU OR
AL I RP AL I RP AL I RP AL I RP
TRO L FA I T ROL FA I T ROL FA I T ROL FA I
CO R P . C OR P . C OR P . COR P .
+25°C +25°C
T
Q
Q
/
/
A A
U
U
5
5
L 2 L 2
I N I
T I T A
R R B
O M O
L X L L
C A C A
OR - M OR -
P W P W
. . 6
FA D 6 FA D
I RP I RP
O RT O RT
NY U .S .A NY U . S .A
STANDARD NUT
CONDUIT ADAPTOR