P1 Manuel

The P1-10-35 Control Unit is designed for efficient control of small to medium-sized air compressors, featuring a user-friendly interface with tactile buttons and a backlit LCD display. It includes various functionalities such as pressure control, service countdown timers, and customizable menu settings for operational and configuration parameters. The device supports multiple input and output connections, ensuring compatibility with various sensors and alarms for optimal performance and safety.

Uploaded by

m.cakir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
243 views14 pages

P1 Manuel

The P1-10-35 Control Unit is designed for efficient control of small to medium-sized air compressors, featuring a user-friendly interface with tactile buttons and a backlit LCD display. It includes various functionalities such as pressure control, service countdown timers, and customizable menu settings for operational and configuration parameters. The device supports multiple input and output connections, ensuring compatibility with various sensors and alarms for optimal performance and safety.

Uploaded by

m.cakir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

Compressor PLC P1-10 Control

P1-10-35 Control Unit Programming Elektronik

P1-10-35 Control Unit


Programming
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

The AirMaster P1 has been custom designed and engineered as a cost efficient control solution for small to medium sized rotary, 1
vane and reciprocating air compressors up to 65Bar (950psi).

Interface:

• 6 tactile feedback push button type keys


integrated in to the front overlay design.
• Industrial push button Emergency Stop
Self locking; twist to unlock.
• 95 element custom backlit LCD

Keys:

Start Up or Increment Value

Stop Down or Decrement Value

Reset Enter

Display:

1 2 5 1: Main Display Value 0.1 to 999


o o
2: Main Display Value Units BAR, PSI, C, F
3: User Menu Item Display Value 0.1 to 99999
o o
4: User Menu Item Display Units BAR, PSI, C, F, Hr, LHr

5: Status Symbols Started, Running, Loaded


6
6: Service/Fault Symbols Service, Fault: Alarm/Warning/Trip
3 4

Construction:

Cast Aluminum alloy housing, process black corrosion protective coating and corrosion protected steel rear plate.
IP65 keypad overlay and panel mount sealing.

Mounting:
144 28 10
Front panel mounting (1.0mm to A2 A1

2.5mm plate thickness) with 4 x - + - + C6 C2

M4 clearance holes for front


accessible screw, self-tap,
nut/bolt or rivet type fixings.

Connections:
2 2
0.5mm to 1.5mm CSA wire 96
screw terminals.

Emergency Stop – 2 x 110’ push


fit ‘faston’ connectors R1 R2 R3 R4

Earth Tabs – 2 x 250’ push fit


‘faston’ connectors 4 x M4 clearance 24Vac 0V R1C C

Arthur Cengiz Tan Total Pages 1 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

X01 – Power Supply: 2


Controller: 24Vac +-15%; 50VA @ 50/60Hz

R1C R1 C R2 R3 R4
Di
0Vac
ES

24Vac

24Vac 0Vac

It is recommended the 0Vac power supply is securely bonded to a suitable earth connection.
Polarity of power supply connection to the controller is important.

Emergency Stop (ES) activation is detected on R1C (relay #1 common pin); 24Vac only.

If common 24Vac power supply is used for motor contactor coil energisation the ‘VA’ power supply rating must be increased
accordingly.
Di
Main 24Vac power supply is used for digital input activation (digital inputs are 24Vac detecting).

X02 – Analogue Inputs:


Pin Function
1 A1+ Pressure Sensor + 16VDC
2 A1- Pressure Sensor 4-20mA Signal
3 A2+ Temperature Sensor KTY (NTC 10k, PT100, PT1000)
4 A2- Temperature Sensor 0VDC

X03 – Digital Inputs:


Pin Function ON: 24Vac OFF: 0Vac
- C1 Emergency Stop see Relay Outputs R1C
1 C2 Shutdown Trip Fault (e.g. Motor Fault) OK Shutdown
2 C3 Shutdown Trip Fault (e.g. Oil Filter) OK Shutdown
3 C4 Shutdown Trip Fault (e.g. Separator Element) OK Shutdown
4 C5 Menu Configurable (Default: Alarm) Alarm OK
5 C6 Menu Configurable (Default: Alarm) Alarm OK

ON= > 19.8Vac, OFF = < 1.0Vac


X04 – Relay Outputs:
Pin Function
1 R1C Emergency Stop Detection; Relay #1 Common 24Vac only (<1.0Vac = E.Stop)
2 R1 Load Solenoid
3 C Relay #2, #3 and #4 Common max. 130Vac/dc
4 R2 Main/Line Motor Contactor Coil
5 R3 Start Motor Contactor Coil
6 R4 Delta Motor Contactor Coil

Arthur Cengiz Tan Total Pages 2 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

User Display: 3

Main Display Value; Pressure (bar/psi menu selectable)

o o
Default User Menu Item; Temperature ( C/ F menu selectable)

To view alternative User Menu items press Up or Down

Total Run Hours

Hours Run Onload

Hours Until Service Due (countdown timer based on total run hours)

RS485 Communication Network Address (*only show if RS485 option installed)

If a timer event occurs (run-on, stop, blowdown or auto restart time) the User item display will show the time countdown in
seconds. While a countdown is being displayed normal User items can still be viewed; press Down.

The display will default back to the User Temperature item after a short period of no key activity or after a timer event has completed.

If operating in ‘Pressure Switch Mode’ the main display will show the detected temperature and the default User Menu item will
be total run hours. Pressure is not displayed in pressure switch mode.

Pressure Switch Mode

Status Display:

The operating status is continuously displayed using status symbols.

Standby: The compressor is in a started state but is not running. The compressor will automatically re-start
and load when pressure falls to the lower pressure set point; or a remote load signal.

Running: The compressor is running offload (run-on-time active)

Loaded: The compressor is running onload

Fault Conditions:

If a Fault condition occurs the Fault triangle symbol will switch on steady (Alarm/Warning) or flash (Trip/Shutdown)
The User menu display item will show a ‘Fault Code’ dependant on the fault.

Fault Codes

Arthur Cengiz Tan Total Pages 3 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

Service Due Countdown Timer: 4


If the Service Due countdown timer reaches 0(zero) hours the Service and Alarm symbols will flash and the service Alarm
(Warning) code will be displayed. The alarm code can be reset but the service symbol will remain on the display until the
service due timer is reset; the service hours will continue to decrement in negative hours. The service countdown timer can
be reset, using the menu routine, when the required service has been carried out. Set to any value greater than 0(zero) hours
before reset.

The Service Due countdown timer can be reset to any hours value, dependant on the required service interval. The timer will
countdown dependant on total run hours.

Menu Routine:

Parameters, Values and Options can be adjusted and set using the Menu Routines. There are two menu lists:
1) Operational Menu – Access Code “0009”
2) Configuration Menu – Access Code “0121”

To access a menu stop the compressor first then press the Up and Down buttons simultainiously.
After several seconds the display will show four “0” characters; the first character will flash. Press Up or Down to adjust the first
character to match the first character of the required access code. Press Enter to increment to the second code character.

When all four access code characters have been set, and the last code character is flashing, press Enter. If the
access code is correct for access to one of the two menus the first menu item of the appropriate menu will be displayed. If the access
code is incorrect the display will return to the normal operational display.

To select a menu item for adustement press Up or Down until the menu item is displayed. To adjust an item setting press Enter, the
value or option will flash. Press Up or Down to adjust as required then press Enter to store in memory.

To exit a menu and return to the normal operational display, at any time, press Reset.
Any adjustement that has not be entered to memory will be abandoned and the previous setting maintained.

Arthur Cengiz Tan Total Pages 4 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

Operational Menu: 5
Item Description Range Default
01: 1.Pu Upper Pressure Set point 1 to 68bar 7.0bar
02: 1.PL Lower Pressure Set point 0.8 to 67.8bar 6.8 bar
03: 1.rt Run-On-Time 0 to 600 seconds 300 seconds (5 minutes)
04: 1.bt Blowdown Time 0 to 120 seconds 30 seconds
05: 1.St Stop Time 0 to 30 seconds 10 seconds
06: 1.P- Pressure Display Units bar/psi bar
o o o
07: 1.t- Temperature Display Units C/ F C
08: 1.At Auto Resetart Time 0 to 120 seconds 10 seconds
09: 1.H3 General Service Hours -99999 to 99999 2000 hours
10: 1.H4 Air Filter Service Hours -99999 to 99999 2000 hours
11: 1.H5 Oil Filter Service Time -99999 to 99999 4000 hours
12: 1.H6 Seperator Filter Service Hours -99999 to 99999 4000 hours
13: 1.H7 Oil Change Service Hours -99999 to 99999 4000 hours

Operational Menu Items:

Pressure Control:
The compressor will maintain pressure between the set Pu (Unload Pressure Set Point) and PL (Load Pressure Set Point. When Pressure
reaches the set ‘Pu’ level the compressor will unload. When pressure falls to the ‘PL’ level the compressor will load.

Run-On-Time:
When the compressor unloads the run-on-timer is initiated. If the set run-on-time expires before the compressor loads again the main
motor will stop and the compressor enter the Standby state.

Blowdown Timer:
When the main motor stops the compressor will allow a period of blowdown (the Blowdown Time) before a motor start can be re-
initiated. A motor re-start is inhibited during this time period. This time is intended to allow internal pressure (or sump pressure) to be
vented before a motor start sequence is permitted. Set to 0(zero) seconds if not required.

Stop Time:
When the Stop button is pressed the compressor will unload and the main motor will continue to run for the set Stop Time. This time is
intended to allow internal pressure (or sump pressure) to reduce before the compression element is stopped; preventing potential oil
blow-back through the compression element and air filter. The stop time is initiated from the moment the compressor is unloaded. If
the compressor has been offload for a period of time prior to a stop command the time is automatically reduced accordingly. If the
compressor is stopded after the compressor has been running offload for the stop time, or longer, the compressor is stopped
immediately; no stop time is applied.
Set to 0(zero) seconds if not required.

Auto Restart Time:


The P1 is equipped with low voltage (<19.8Vac) and power failure detection (>40ms). If a power disturbance or failure occures while
the controller is in a Started state (running or in Standby mode) the compressor will be automatically restarted when power is restored.
The controller will display a Power Failure Detected alarm code to indicate this event has occured.
To enable this function select an Auto Restart Time greater than 0(zero) seconds. When power is restored the controller will wait for
the set Auto Restart Time before initiating a motor start sequence. This time is intended as a warning period and/or a method of
stagger starting a number of compressors on the same power supply distribution system.
To disable (inhibit) the Auto Restart function set the time to 0(zero) seconds.

Arthur Cengiz Tan Total Pages 5 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

Configuration Menu: 6
Item Description Range Default
1: 2.Sd Motor Star/Delta Time 0.0 to 20.0 seconds 5.0 seconds
2: 2.Ad Network Address (RS485 option) 1 to 12 1
3: 2.LS Load Source 0=local, 1=RS485 0=local
4: 2.SS Start Source 0=local, 1=RS485 0=local
5: 2.PA High Pressure Alarm Level 1.0 to 68.0bar 7.6bar
6: 2.PF High Pressure Trip Fault Level 0.8 to 67.8bar 8.0bar
o o
7: 2.tA High Temperature Alarm Level 50 to 248 C 110 C
o o
8: 2.tF High Temperature Trip Fault Level 52 to 250 C 120 C
9: 2.d2 Digital Input ‘C2’ configuration
2: Eno - Shutdown Trip @ 24Vac (0Vac=OK)
3: Enc - Shutdown Trip @ 0Vac (24Vac=OK) - default
10: 2.d3 Digital Input ‘C3’ configuration
2: Eno - Shutdown Trip @ 24Vac (0Vac=OK)
3: Enc - Shutdown Trip @ 0Vac (24Vac=OK) - default
11: 2.d4 Digital Input ‘C4’ configuration
2: Eno - Shutdown Trip @ 24Vac (0Vac=OK)
3: Enc - Shutdown Trip @ 0Vac (24Vac=OK) - default
12: 2.d5 Digital Input ‘C5’ configuration
0: Ano - Alarm @ 24Vac (0Vac=OK) - default
1: Anc - Alarm @ 0Vac (24Vac=OK)
2: Eno - Shutdown Trip @ 24Vac (0Vac=OK)
3: Enc - Shutdown Trip @ 0Vac (24Vac=OK)
13: 2.d6 Digital input ‘C6’ configuration
0: Ano - Alarm @ 24Vac (0Vac=OK) - default
1: Anc - Alarm @ 0Vac (24Vac=OK)
2: Eno - Shutdown Trip @ 24Vac (0Vac=OK)
3: Enc - Shutdown Trip @ 0Vac (24Vac=OK)
4: rLu - Remote Load - Unload (24Vac=Load)
5: PSr - Pressure Switch Regulation (24Vac=Load)
6: rSS – Remote Start – Stop (24Vac=Start)

14: 2.Po Pressure sensor ‘offset’ calibration -1.5 to 1.5bar 0.0bar


15: 2.Pr Pressure sensor ‘range’ calibration 0.0 to 105bar 16.0bar
o o
16: 2.tL Low Temperature Load Inhibit 1 to 70 C (0 = disable function) 2.0 C
o o
17: 2.tr Low Temperature Run Inhibit -20 to 10 C -10.0 C
18: 2.r4 Relay 4 Function setting 1 to 12 12
0 0 0
19: 2.FH Fan control ON temperature 50 C … 90 C 85 C
0 0 o
20: 2.FL Fan control OFF temperature 40 C … 85 C 75 C
21: 2.Ft Fan minumum run time 10 s … 180 s 180 s
22: 2.H1 Total Running Hours 0 to 99999 0 hours
23: 2.H2 Loaded Hours 0 to 99999 0 hours
24: 2.C1 User Password 0001 to 9999 0009
25: 2.C2 Fabric Password 0001 to 9999 0121

Configuration Menu Items:

2.Sd - Motor Star/Deta Time:


The number of seconds the main motor will run in Star configuration, during a motor start sequence, before transition to Delta
configuration.

• The Star motor contractor is energised 200ms before the Main motor contactor.
• The Star to Delta contactor transition time is fixed at 50ms.

Arthur Cengiz Tan Total Pages 6 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

2.Ad - Network Address: 7


The RS485 network communication address and the compressor number. Each compressor, connected to the same network, must be
assigned a unique address starting from 1 to the number of compressors on the network system.

RS485 Communications Option


2.LS - Load Source:
1) Compressor will operate using the local set ‘Pu’ and ‘PL’ pressure set points.
2) The compressor will respond to remote RS485 system management pressure control.

Local pressure control (Pu and PL) is automatically resumed if RS485 communications is disrupted or lost. When RS485
communications are resumed, pressure control is automatically reverted back to RS485 control.

2.SS - Start Source:


1) The compressor can be started using the local Start button.
2) The compressor can be started using remote RS485 communications; the local start button is inhibited.

Local and remote Stop functions are always active.

2.d6:rLu - Remote Load/Unload:


The controller can be set to load and unload in responce to a 24Vac signal (derived from the main 24Vac power supply). When this
option is selected the local pressure set points ‘Pu’ and ‘PL’ are ignored. The compressor will load when 24Vac is detected on digital
input C6, and unload when the voltage is removed from C6. This feature is intended for remote pressure switch control or remote
sequence management control.

Local pressure continues to be displayed; high pressure Alarm (Warning) and shutdown Trip settings remain active.

2.d6:PSr - Pressure Switch Mode:


In Pressure Switch Mode the controller will load and unload in responce to a 24Vac signal (derived from the main 24Vac power supply).
When this option is selected the local pressure set points ‘Pu’ and ‘PL’ are ignored. The compressor will load when 24Vac is detected on
digital input C6, and unload when the voltage is removed. This feature is intended for operation from a local pressure switch device
(PS).

A2 A1
- + C6 - - - C2

PS

24Vac Di

The local detected pressure input ‘A1’ is ignored and pressure is not displayed. The main display value will show the detected
Temperature. There is no requirement to connect a 4-20mA pressure sensor to analogue input ‘A1’ in this mode.

A temperature sensor is compulsary in all modes.

The high pressure Alarm (Warning) and shutdown Trip settings are ignored. It is recommended alternative excess pressure
shutdown, utilising a shutdown digital input, is implemented.
Pressure Switch Mode is intended for compressor units that are equipped with a pressure switch but are not equipped with a pressure
sensor.

Arthur Cengiz Tan Total Pages 7 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

2.d6:rSS – Remote Start-Stop Mode: 8


Execution control unit can be programmed remotely. This voltage is used to 24Vac. This control unit can supply voltages. If this feature
is selected to set off the Start button remains. The P1 of the compressor input 24Vac works with C6 and the terminal voltage of the cut
ends with. P1 in the function of the circuit remains in the Stop button. With Stop button stops the compressor.

Arthur Cengiz Tan Total Pages 8 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

2.Po/2.Pr - Pressure Sensor Type: 9


The controller is designed for use with a 4-20mA type pressure sensor that can operate from a 16VDC supply. The ‘range’ of the sensor,
and sensor calibration, can be adjusted using the ‘Po’ (pressure sensor offset) and ‘Pr’ (pressure sensor range) values. As default these
values are set for a 0-16.0bar (0-232psi) sensor.

Wire polarity is important


If a sensor with a different range is used, initially set the ‘Pr’ range value to match the sensor; then calibrate.
For example: for a 0-60bar sensor set the ‘Pr’ range value to 60.0bar.
If the sensor has a non-zero lower pressure limit, -1.0 (minus one) to 15bar for example, initially set the ‘Po’ offset to –1.0 (minus one)
bar and the ‘Pr’ range to 15.0bar; then calibrate.
Pressure Sensor Calibration:

1) Expose the sensor to atmosphere (0.0bar gauge). Adjust the ‘Po’ offset value until the displayed pressure is 0.0bar.
2) Apply a known accurate pressure to the sensor. The pressure can be static or dynamic (changing). Adjust the ‘Pr’ range value
until the displayed pressure matches the applied pressure. The applied pressure can be any value but It is recommended the
pressure be equivalent to, or greater than, normal working pressure to ensure an accurate calibration.

Detected pressure is displayed when the ‘Po’ and Pr’ menu items are selected for adjustment.

The controller will automatically adjust the pressure fault levels, and the pressure set points, to ensure they remain within the
pressure sensor range. Always check and comfirm these values after a pressure sensor ‘offset’ or ‘range’ adjustment.

2.tL - Low Temperature Load Inhibit


If detected temperature is below the set low temperature limit, and a load condition is required, the controller will inhibit the
compressor from loading, and the compressor will run offload, untill temperature increases above the set limit. When this condition
occurs the controller will display an Alarm indication (A3423 Err). The Alarm will self reset when temperature increases above the set
limit. The alarm cannot be manually reset.
To disable this function set to 0(zero).

2.tr - Low Temperature Run Inhibit


If detected temperature is below the set low temperature limit, and a load condition is required, the controller will inhibit a main
motor start, and the compressor will remain in a standby condition, untill temperature increases above the set limit. If a load condition
is still required when temperature increases above the set limit the compressor will automatically start and run. When this condition

Arthur Cengiz Tan Total Pages 9 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

occurs the controller will display an Alarm indication (A3123 Err). The Alarm will self reset when temperature increases above the set 10
limit. The alarm cannot be manually reset. This feature cannot be disabled.

This function will not stop or inhibit a compressor from operating if the main motor is already running; the function only applies when
the main motor is stopped and the controller is required to initiate a motor start sequence.

2.R4 Relay 4 Output Functions:

01 – Alarm De-energized for any active Alarm fault (2.tL and 2.tr value not including)
02 – Shutdown De-energized for any active Shutdown fault (2.tL and 2.tr value not including)
03 – Group Fault De-energized for any active Alarm, Star/Run Inhibit or Shutdown fault
04 – Alarm Service De-Energized for any Alarm fault or Service Due alarm (2.tL and 2.tr value not including)
05 – Service Energized for Service Due alarm only
06 – Heater Energizes if detected temperature falls below set low temperature run inhibit “2.tr”
De-energizes if detected temperature increases above set low temp run inhibit + 2°C
Can be used to energize anti-condensate heater contactor or as low temperature warning auxiliary
output.
07 – Fan Energized in all RUNNING states except ‘motor start’ “2.Sd”
Can be used to energize internal and/or external cooling fan motor contactor
08 – Standby Energized in ‘Standby’ and ‘Blowdown’ states
09 – Running Energized in all RUNNING state conditions
10 – Loaded Energized in all LOADED state conditions
11 – Started Energized in all STARTED state conditions
12 – Fan (temp ctl) Enabled to operate in all RUNNING states except ‘motor start’ If enabled to operate the output will only
energize if delivery temperature exceeds the set ‘Fan High’ temperature setting. If delivery temperature
falls below the set ‘Fan Low’ temperature setting the output will de-energize. Once energized the output
will remain energized for a minimum of the set ‘Fan Minimum Run Time’ regardless of delivery
temperature. Can be used to energize internal and/or external cooling fan motor contactor; the minimum
run time is intended as a means of limiting Fan motor starts-per-hour.
Service Function:
To force the compressor in to an offload condition, regardless of pressure level, press and hold RESET for 5 seconds.

• The lower display will indicate ‘OFF’ (press DOWN to view the temperature or other user menu items)
• The load status symbol will flash (without the delivery arrow)
• The motor run-on-timer is inhibited; the compressor will continue to run indefinantly in an offload condition.

To exit the service function, and resume normal operation, press RESET.
The service function will self cancel if the compressor is stopped; normal operation will resume when the compressor is re-started.

Temperature Sensor:
signal
A2+
The P1 is designed as standard to use a KTY type 0VDC
A2-
temperature sensor. A KTY sensor offers a calibration
o o
temperature range of –32 C to 150 C.

Special builds (on request) can accommodate 10k NTC, PT100 or PT1000 type sensors in instances where a different or higher
o o
temperature range (-50 C to 250 C) is required; reciprocating compressor application for example.

Passwords:
Passwords can be change only with fabric password level.

C1  USER Password default value=0009


C2  FABRIC Password default value=0121

ATTENTION !!!

If any reason passwords are forgotten PLC must be return source.

Arthur Cengiz Tan Total Pages 10 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

RS485 Communications Option: 11


Multi485
The P1 can be factory fitted, or retro-fitted, with an
optional 2-wire RS485 serial communications port. The X06
RS485 option is automatically detected, no menu RS485
adjustments are required.

L2 L1 X06
L1
3 X06 3 1 L1
1 5 2 L2
L2
2 1 RS485
4
X06
2
RS485

RS485

X06
X05

a: Remove the P1 rear cover plate (1).


b: Attach the RS485 PCB (2) to the underside of the P1 rear cover plate using the two screw fixings provided (3); the P1 rear cover plate
is equipped with two mounting holes for this purpose.
c: Connect the RS485 PCB cable (4) to the RS485 PCB socket (5)
d: Connect the second end of the RS485 PCB cable (4) to plug X05 on the P1 PCB (6).

Ensure the RS485 PCB cable plugs are tight and secure.

e: Replace the P1 rear cover plate (1)

Handle with care - ensure the RS485 PCB cable plugs are not pulled from the sockets during this procedure.

Multi485 Protocol:
The port utilises the CMC Multi485 protocol enabling connectivity to a range of system management products, remote
communications monitoring and control options or MODBUS RTU connectivity using a MODBUS Gateway module.

Arthur Cengiz Tan Total Pages 11 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

Fault Codes: 12
Fault conditions are separated in to two categories:

A: Alarm (Warning) – symbol illuminated on steady, the compressor will continue to operate

A:2050 C5 (if set for alarm warning function)


A:2060 C6 (if set for alarm warning function)
A:2118 High Pressure: alarm limit exceeded
A:2128 High Temperature: alarm limit exceeded

A:2816 Power Failure Detected

A:3123 Run Inhibited - temperature is below set low temperature run inhibit limit
(will self reset when temperature increases above the set temperature limit; cannot be manually reset)

A:3423 Load Inhibited - temperature is below set low temperature load inhibit limit
(will self reset when temperature increases above the set temperature limit; cannot be manually reset)

A: 4804 General Service hours time expired, service due (reset countdown timer)
A: 4814 Air filter hour’s time expired, service due (reset countdown timer)
A: 4824 Oil filter hour’s time expired, service due (reset countdown timer)
A: 4834 Air/Oil Separator hours time expired, service due (reset countdown timer)
A: 4844 Oil service hours time expired, service due (reset countdown timer)

E: Shutdown (Trip) – symbol will flash, the compressor will stop.

E:0010 Emergency Stop – 24Vac in not being detected on terminal R1C


E:0020 C2 – fault condition detected on digital input C2
E:0030 C3 – fault condition detected on digital input C3
E:0040 C4 – fault condition detected on digital input C4
E:0050 C5 (if set for shutdown trip function)
E:0060 C6 (if set for shutdown trip function)

E:0115 Pressure Sensor Fault: 4-20mA signal out-of-range (< 3.8mA or > 20.8mA)
E:0119 Excess Pressure: shutdown limit exceeded
o o
E:0125 Temperature Sensor Fault: signal out-of-range (< -50 C or > 250 C)
E:0129 Excess Temperature: shutdown limit exceeded

Arthur Cengiz Tan Total Pages 12 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010
Compressor PLC P1 Control
P1-10-35 Control Unit Programming Elektronik

Mounting Options: 13

131.44

83.44

131.44

83.44

not to scale

Arthur Cengiz Tan Total Pages 13 / 13


File P1-10 Standart Instruction Manual Date 15.03.2010