WINDING CHART
KVA 1600
CUSTOMER NEA
1600KVA,11000/400V TRANSFORMER GUARANTEED EXPECTED
CORE DIA :- 261 mm. NO LOAD LOSS 2000 W 1970 WATT
CENTER LEG :- 462.5 mm. LOAD LOSS 17000W 16500WATT
WINDOW HT :- 540 mm. IMPEDANCE % 6.25%+/- TOL. 5.90%
TAP SWITCH :- OLTC TAPPING RANGE :- +5% to - 15 % in Steps of 1.25% (16 STEP/17 POSITION)
SL. PARTICULARS DESIGN DATA
1 WINDING L.V.WINDING H.V.WINDING
2 TOTAL TURNS PER PHASE 13 650
3 BARE CONDUCTOR SIZE CU 12X4 6X2.85
4 INSULATION COVERING 0.40 DPC 0.40DPC
5 COVERED CONDUCTOR SIZE CU 12.4X4.4 6.4X3.25
6 CONDUCTOR PLACEMENT 5 W X3 D Single Wire
7 WINDING DIRECTION L→R L→R
8 TYPE OF WINDING Layer Wound LAYER WOUND
9 NO. OF COIL PER TRANSFORMER 3 3
10 NO. OF COIL PER PHASE 1 1
11 TURNS PER COILS PER PHASE 13 650
NO. OF LAYER 2 (1 to 6LAYER ) (7TO 8 LAYER) (9 TO 10LAYER)
TURNS PER LAYER 6.5 66 65 62
INTER LAYER INSULATION 4.0MM PB DUCT 1-5&6-8(3x5MIL), 5-6&8-9(4mmPBD)
TRANSPOSITION ONE CONDUCTOR AT CENTER 9-10-10MILX3
WINDING LENGTH 482 430 424 408
AXIAL LENGTH 498 462
END STRIP 8/70 16+16 19+19 27+27
18 INTERNAL DIAMETER OF COIL 273 360
19 EXTERNAL DIAMETER OF COIL 336 448
20 CLEARANCE BETWEEN COIL -- ---
21 COND.WEIGHT WITH INSULATION IN Kg. 265 kg 382Kg
22 CONDUCTOR LENGTH MTRS 41 MTRX15REEL ----
23 (F)650 T---642---634---626---619---611--603---595---588---580---572---564---557---549--541---533---526 BREAK526----0T(START)
24 END CLEARANCE see assembly details see assembly details
25 NO. OF SPACERS / CIRCLE 10 10
26 RESISTANCE PER PHASE AT 75 DEG. C 0.0004 OHM 1.0OHM
27 I2R AT 75 DEG. C 6400 WATT 7052WATT