Kidde Fire Systems
Component Description
Stackable Electric Control Head Kits
Effective: April 2023
with Control Head Monitor K-85-3002 Rev AD
FEATURES
• UL Listed, ULC Listed, and FM Approved for use with systems listed in the Table, “COMPATIBILITY”, on page 2.
P/N: 85-486500-010
ORDER INFORMATION
Part Number Description
85-486500-010 Kit, Includes:
• Electrical Control Head, 24 VDC, Stackable, (Ex. Proof), P/N: 82-486500-010
• Control Head Monitor, P/N 85-100000-100
(for more information, see data sheet K-85-3000)
• Lever Operated Control Head, P/N WK-870652-000
(for more information, see data sheet K-85-6005)
Note: This kit is UL listed and FM Approved.
85-486500-020 Kit, Includes:
• Electrical Control Head, 24 VDC, Stackable, (Ex. Proof), P/N: 82-486500-010
• Control Head Monitor, P/N 85-100000-100
(for more information, see data sheet K-85-3000)
Note: This kit is UL listed but Not FM Approved.
Note: Both kits are not suitable for 600/900/1100 lb ECS Cylinders, ADS Cylinders, Nitrogen drivers, Nitrogen pilot cylinders,
and FE-13 Cylinders.
2.90"
1.25-18 UNEF-2A
CONNECTION
1/2"-14 NPT
CONDUIT
CONNECTION
ELECTRIC CONTROL HEAD, PART
NO. 486500-01 IS RATED FOR USE
IN HAZARDOUS (CLASSIFIED)
LOCATIONS CLASS 1, DIV. l,
GROUPS C, D AND CLASS ll, DIV. ll, 5.28"
GROUPS E, F, G BETWEEN
-40F AND 140F. USE CONDUIT
SEAL WITHIN 18 IN. (45cm) OF
THIS DEVICE. (3) 18 AWG-LEADS
18" LONG
SWIVEL NUT
1.25-18 UNEF-2B
CONNECTION
Note: This control head is polarized. Improper wiring will result in failure of this device to operate.
Electric control head, P/N: 82-486500-010, is designed for installation directly on 487 Series Halon and
Kidde Fire Systems ECS™ agent valves only to a maximum size of 350 lbs. This control head must not be
installed on any other type of halon or agent cylinder valve, nitrogen valve, carbon dioxide cylinder valve,
WARNING FE-13TM cylinder valve or Stop (Directional) valve. Installation of this control head to any other device (e.g.,
pressure operated control head) will result in failure of device to operate.
MATERIAL SPECIFICATIONS
Body: Brass Voltage: 24 VDC
Current: 0.2A Continuous Draw
1
Figure 1. Electric Control Head Kit (P/N 85-486500-010)
COMPATIBILITY
Series DIOM P/N Supplement P/N Approval
Kidde Fire Systems ECS-500™ System* 06-237585-001 N/A UL, ULC, FM
Kidde Fire Systems ECS™ 360 for use with Fluoroketone Fire Suppression Agents* 06-236553-001 N/A UL, ULC, FM
Kidde Fire Systems ECS™ 360 with HFC-227ea Agent* 06-236115-001 06-236115-003 UL, ULC, FM
Kidde Fire Systems Modular ECS™ 360 with HFC-227ea Agent* 06-236116-001 06-236116-002 UL, ULC, FM
*For Cylinders up to 350 lbs. maximum
Note: Agency listings also apply the Fenwal Engineered Fire Suppression Systems, when the Control Head Monitor is used on these legacy prod-
uct lines.
EXPORT INFORMATION (USA)
Jurisdiction: EAR
Classification: EAR99
This document contains technical data subject to the EAR.
All trademarks are the property of their respective owners.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. believes this data to be accurate, but it is published and presented without any guarantee
or warranty whatsoever. KIDDE-FENWAL, INC. assumes no responsibility for the product's suitability for a particular application. The fire suppression system design,
installation, maintenance, service and troubleshooting must be performed by trained, authorized Kidde Fire Systems distributors for the product to work correctly.
If you need more information on this product, or if you have a particular problem or question, contact:
KIDDE-FENWAL, INC., Ashland, MA 01721 USA, Telephone: (508) 881-2000.
2 Kidde Fire Systems
400 Main Street
Ashland, MA 01721
K-85-3002 Rev AD Ph: 508.881.2000
Fax: 508.881.8920
©2023 Carrier kiddefiresystems.com