MS-QZ Unit A: Instruction Manual
MS-QZ Unit A: Instruction Manual
Attention!
Please ensure that this instruction manual is
made available to end users and the personnel
responsible for maintenance.
JNEE-SI-0905-D
MS-QZ UNIT A
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
MS-QZ UNIT A
INTRODUCTION
Thank you for adopting Mitsubishi's Low-volt CDL (Control Center Data Link System) Transmission Master
Station.
Before using this product, carefully read this manual and fully understand the functions, performance and operation
methods so as to ensure correct usage.
Safety Guide
■ Before installation, operation, maintenance and inspection, carefully read this section to gain a full
understanding of the equipment, safety issues and other important concerns.
■ For handling of Mitsubishi motor control panels, safety precautions are classified into three groups: DANGER,
CAUTION, and REQUEST.
CAUTION
Directions labeled with may also lead to serious accidents depending on the situation.
CAUTION
(Reference
section)
● When installing the MS-QZ in the following environment, please contact us in the Section 2.1
planning stage.
(1) Place where the ambient temperature of the MS-QZ is 0℃ or less, or 55℃ or
over.
(2) Location where the humidity is high enough for condensation or freezing.
(3) Place with intensive vibration and impact.
(4) Location exposed to dust, corrosive gas (G2 class, ISA Specifications), saline
matter, and lamp black.
(5) Location which is exposed direct sunlight, rain or drops of water.
● The current capacity value obtained from the rough calculating formula is the result Section 2.4
of calculating a consumption current of the I/F circuit.
Ensure a power capacity that provides a proper margin to the calculated value during
the system design, considering impedance etc. of the transmission line.
● When turning on the power for the slave station, check the status of the output All sections in
information. Chapter 5
Some programs may cause malfunction (sudden starting).
● Output processing is executed even during address error or parameter error on the All sections in
slave station. Chapter 5
Even during non-connection or communication errors, output processing is continued.
Take safety measures for some programs, such as output clear at the above errors.
● If the master or slave station detects a bus low status by its self-diagnosis function Section 6.1
(at single fault), it will separate the bus.
†When several LSZ slave stations are placed on the same base unit (LSZ-B), all
the slave stations are separated. Therefore, be careful during the system design.
● When the output of the slave station is opened by its self-diagnosis function Section 6.3
(transmission stop = fault), check the setting of this unit and the specifications
of the slave station.
†During system design, note that some settings are unsupported or fixed depending
on the specification of a slave station.
● Replace the transmission power supply with a new one on a regular basis. Section 7.2
If its life expires, the transmission system will stop.
For details about replacement timing, contact the power supply manufacturer.
CAUTION
(Reference
section)
● Warranty and maintenance periods. -
Refer to the follows about them:
(1) The warranty period shall be for one (1) year after delivery to a designated
location.
(2) After the end of the one (1) year warranty period, maintenance shall be available
at cost to the customer, even within the recommended renewal period (described
below). Cause investigation, repair, replacement, and recovery services
shall also be available at cost to the customer, regardless of the cause of
any failure.
(3) The maintenance period shall be for seven (7) years after Mitsubishi Electric
announces the termination of production of the product. Note, however, that
if, before the end of the maintenance period, any required parts are
discontinued or undergo specification changes, Mitsubishi Electric shall
consider using alternative parts whenever possible if such parts are
obtainable but that in this and certain other circumstances, there may be
situations in which Mitsubishi Electric is not able to provide maintenance.
(4) During the maintenance period, Mitsubishi Electric shall offer repair services
only. Mitsubishi Electric cannot newly manufacture a replacement product or
replace the existing one with a new one.
● Scope of warranty. -
If, during the warranty period, a defect or failure is found in this product for a
reason attributable to Mitsubishi Electric, Mitsubishi Electric shall supply the
necessary replacement part(s) or replace or repair the defective portion free of
charge at the location where the product was purchased or to which it was delivered.
This is the sole responsibility that Mitsubishi Electric shall assume for any such
defect or failure. The defect or failure shall be excluded from the scope of this
warranty if it falls under any of the following:
(1) The product has not been used in accordance with the instructions, conditions,
or environments described in the catalogue, instruction manual, or
specifications, or it has been used improperly.
(2) The cause of the defect or failure is not with the purchased or delivered
product.
(3) The cause is an alteration or repair, made by other than Mitsubishi Electric,
that was made after purchase or delivery.
(4) The cause is attributable to a phenomenon that could not be foreseen with science
and technology put into practice at the time of purchase or upon the signing
of the agreement.
(5) If this product is incorporated into the customer’s device, the damage could
have been avoided if the customer’s device had been equipped with the
functions, structures, and so on that it would have if it followed generally
accepted practices in the industry.
(6) Our product is put to a use other than that for which it was intended.
(7) The cause is a natural or other disaster not attributable to Mitsubishi
Electric.
The term “warranty,” as used here, refers to the warranty of the product itself.
Any damage or loss resulting from a defect or failure of the product shall be excluded
from the scope of the warranty.
REQUEST
(Reference
section)
● Carry out periodic inspection. Section 7.2
Note that the equipment may not function properly unless the periodic inspection is
performed.
● The product's expected life (not guaranteed life) is 10 years.
The product's expected life is 10 years for normal use. Replace it with new one before
its life expires. If used past its life, it may not function normally.
(If the annual average of the panel ambient temperature exceeds 25℃ and the annual
average of the in-panel temperature exceeds 40℃, its life will be reduced. If using
it in an environment exceeding these temperatures, consult us in the planning stage.)
MS-QZ UNIT A
CONTENTS
Chapter 1 Overview 1- 1
1.1 Type name of this unit 1- 1
1.2 Configuration of this unit 1- 1
1.3 Outline of data communications in this unit 1- 1
1.4 Restricted combination with PLC 1- 2
1.5 Restricted combination with CDL terminal station (slave station) 1- 2
Chapter 4 External Shape of This Unit and Names of Parts of This Unit 4- 1
4.1 External shape of this unit 4- 1
4.2 Setting switches 4- 2
4.3 LED display 4- 3
Chapter 8 Troubleshooting 8- 1
8.1 Flow for unit malfunction 8- 1
8.2 Flow for system malfunction 8- 5
Chapter 9 Programming 9- 1
9.1 Setting of parameters 9- 2
9.2 Normal communication (input/output) 9- 4
9.3 Exclusive communication 1 (general-purpose: transient input/output) 9- 7
9.4 Exclusive communication 2 (general-purpose: transient output) 9- 9
9.5 Exclusive communication 3 (general-purpose: transient input) 9-10
9.6 Exclusive communication 4 (general-purpose: transient input) 9-12
MS-QZ UNIT A
Chapter 10 Example of Program Preparation 10- 1
10.1 System configuration 10- 1
10.2 Program flowchart 10- 1
10.3 Example of program 10- 2
Appendix
Appendix 1 Slave Station Input/Output Information Appendix 1-1
Appendix 2 Operation of This Unit by PLC Manipulation Appendix 2-1
Appendix 3 Product Information Appendix 3-1
1. Overview
MS-QZ UNIT A
Chapter 1 Overview
This unit is a master station unit for CDL transmission that is placed on an I/O slot for the MELSEC-Q sequencer
(hereinafter referred to as PLC: Programmable Logic Controller).
[Configuration]
P
o
w
e C T B
r P h a
s U i s
u s e
p u u u
p n n n
l i i i
y t t t
u
n
i
t
CPU
I/O signal
Interface with CDL equipment
transmission
bus
Sequencer CPU
CDL equipment
Readout of and
write in buffer
memory
Buffer
memory
Transmission
power supply
1-1
1. Overview
MS-QZ UNIT A
1.4 Restricted combination with PLC
This section describes the systems to be applied.
1.4.1 Units to be applied and the number of units that can be placed
The number of these units that can be placed in combination with the PLC (mainly CPU unit) is limited.
Combinations other than those in the following table have not been confirmed. Contact us concerning the
combinations.
Type name of CPU unit Allowable placement number (maximum) Remarks
Q02CPU
Q02HCPU
Can be placed only
Q06HCPU 64
in the Q mode (Note)
Q12HCPU
Q25HCPU
Q00JCPU
Q00CPU Not supported -
Q01CPU
(Note) Refer to user's manuals for CPU units to be used (function description and program basics).
1-2
2. Product Specifications
MS-QZ UNIT A
Chapter 2 Product Specifications
This chapter describes the product specifications of this unit.
Noise simulator that has a noise voltage of 1500V.P.P. (Place a noise filter on the
Noise tolerance
primary side of the power unit), a noise width of 1us, and a noise frequency of 25 to
60Hz
1500VAC per 1 min. between all AC terminals and earth (power supply unit)
Withstand voltage 500VAC per 1 min. between all DC terminals and earth (each CDL transmission bus of this
unit)
Insulation 5MΩ or more between all AC terminals and earth at a 500VDC insulation tester (excluding
resistance error contacts)
Atmosphere for Shall not have corrosive gas and be extremely dusty.
running
Cooling method Self-cooled
Consumption VA 5VDC 0.35A
I/O occupation 32 points (special function unit)
number
When installing the MS-QZ in the following environment, please contact us in the planning stage.
! CAUTION (1) Place where the ambient temperature of the MS-QZ is 0℃ or less, or 55℃ or over.
(2) Location where the humidity is high enough for condensation or freezing.
(3) Place with intensive vibration and impact.
(4) Location exposed to dust, corrosive gas (G2 class, ISA Specifications), saline matter, and
lamp black.
(5) Location which is exposed direct sunlight, rain or drops of water.
2-1
2. Product Specifications
MS-QZ UNIT A
communicated stations
Transmission Current Twisted pair cable KV,KHV,CPEE 0.75 to 2.0mm2 (AWG 14 to 18, φ1.0 to 1.6)
medium Optical Quartz glass GI50/125 optical fiber
Maximum Current 2000m (depending on cable sizes and the number of connected stations)
transmission Optical 2000m (Quartz glass GI optical fiber)
distance
(Note 1)
Topology Bus method
Transmission speed 9600bps
Electrical
condition
2-2
2. Product Specifications
MS-QZ UNIT A
・ Classification of transmission
line and node maximum length ・Overall transmission system maximum distance
Classification of Node maximum Overall transmission system maximum
Condition
transmission line length distance
Basic system 2000m
AWG18 76
100m (Without using a repeater or † Inclusion of CDL-Z and V makes
(0.75mm2, φ1.0mm) N optical converter) 1500m
2000×(N+1)m
AWG16 128
100m Transmission system with N † Inclusion of CDL-Z and V makes
(1.25mm2, φ1.3mm) N units of repeater 1500×(N+1)m
(N: 1 to 4) Max. 10000m
AWG14 200
100m † Inclusion of CDL-Z and V makes
(2.0 mm2, φ1.6mm) N 6000m
Transmission system using 2000m
an optical converter † Quartz glass GI optical fiber
† N: Node
・In the 4-wire system, N indicates the number of connected stations.
・In the 2-wire system, N indicates the number of connected nodes minus the minimum of the numbers of
nodes connected at the individual points.
[Example] In the 2-wire system, where 16 stations, 24 stations and 24 stations are intensively placed
to the three locations, respectively, N = 64 – 16 = 48 is available.
† (Connected station of node) ≦ 64
2-3
2. Product Specifications
MS-QZ UNIT A
[Example] When using a AWG16 (1.25mm2, φ1.3mm) transmission line
N=n-n/2
LS LS LS
PW Master station PW
LS LS
2-4
2. Product Specifications
MS-QZ UNIT A
PW PW
Master
RPG
station
n1 units n2 units n3 units n4 units
PW:Transmission power
supply 24VDC
(n1+n2+n3+n4) <= 64 units
RPG:Bus repeater
For the distances for (n1+n2) and (n3+n4), refer to
the table in the previous page.
2-5
2. Product Specifications
MS-QZ UNIT A
(2) Wiring
In the transmission power supply, connect 24VDC (+) to the power line (P), and 24VDC (G) to the neutral
line (N).
・The current capacity value obtained from the rough calculating formula is the result
! CAUTION of calculating a consumption current of the I/F circuit.
Ensure a power capacity that provides a proper margin to the calculated value during
the system design, considering impedance etc. of the transmission line.
2-6
3. System Configuration
MS-QZ UNIT A
Chapter 3 System Configuration
This chapter describes system configuration.
Transmission bus
3-1
3. System Configuration
MS-QZ UNIT A
MELSECNET/H
[A system] [B system]
Power supply unit
MELSECNET
CPU unit
CPU unit
A B
Extension cable
Power supply unit
3-2
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
Chapter 4 External Shape of This Unit and Names of Parts of This Unit
27.4mm 104.5mm
MS-QZ
1 5
25.0mm
RUN■ ■C-RUN 2 6
LED display SD■ ■C-ERR 3 7
RD■ ■Q.CPU 4 8
Name plate of UNIT A
unit type name
SW1
Setting switch
SW2
MS-QZ
14.5mm
The terminal and fixing screws of the unit within the following torque range.
Screw position Fastening torque range
Terminal screw for terminal block (M4) 82 to 111N・cm
Unit fixing screw (normally not required) (M3) (Note) 36 to 48N・cm
(Note) The unit can be easily fixed to a base unit by a hook on the upper part of the unit.
However, it is recommended that the unit should be fixed with the unit fixing screw in a place subject
to strong vibration or impact.
(2) For installation environment, refer to the user's manual for a CPU unit that will be used.
4-1
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
4.2 Setting switches
This section describes setting switches in this unit.
Setting Content
0 Slave station overall display/error display
1 Slave station overall display/error display
2 Slave station communication status display 01h to 08h
3 Slave station communication status display 09h to 10h
4 Slave station communication status display 11h to 18h
5 Slave station communication status display 19h to 20h
6 Slave station communication status display 21h to 28h
7 Slave station communication status display 29h to 30h
8 Slave station communication status display 31h to 38h
9 Slave station communication status display 39h to 40h
A Unit setting display (Note)
B Communicated slave station count display (Note)
C I/O assignment X00 to X07 display (Note)
D I/O assignment X08 to X0F display (Note)
E I/O assignment Y10 to Y17 display (Note)
F I/O assignment Y18 to Y1F display (Note)
(Note) If SW1 becomes the same as SW2 at power activation, execute the test function.
Content
Setting
At startup of this unit At stop of link to PC
0 Retention Retention
1 OFF Retention
2 Retention OFF
3 OFF OFF
Selection of
4 Retention Retention
slave station
5 Retention Retention
power setting
6 Retention Retention
7 Retention Retention
8 Retention Retention
9 Retention Retention
A Display test (Note)
B Setting test (Note)
C Selection test Hardware test (Note)
D item I/O operation test (Note)
E CDL transmission test (sending function) (Note)
F CDL transmission test (receiving function) (Note)
(Note) Only if SW1 is the same as SW2 at power activation, execute the test function.
(Even if SW1 is the same as SW2 after startup of this unit, the test function will not
be executed.)
For details about the test function, refer to the section 6.4.
If SW2 is determined to be one of A to F when the test function is not executed, it will
be the same as 0.
4-2
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
4.3 LED display
This section describes LED display of this unit.
MS-QZ
1 5
RUN■ ■C-RUN 2 6
SD■ ■C-ERR. 3 7
RD■ ■Q.CPU 4 8
UNIT A
4-3
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
4-4
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
4-5
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
4-6
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
4-7
4. External Shape of This Unit and Names of Parts of This Unit
MS-QZ UNIT A
4-8
5.Data Link with PLC
MS-QZ UNIT A
Chapter 5 Data Link with PLC
CPU
I/O signal
CDL equipment
Readout of and
write in
buffer memory
Buffer
memory
Transmission
power supply
(2) Device
A buffer memory access command (FROM/TO) of the PLC will be used.
Only access to a device fixed for each item enables data sending and receiving.
・ Device range …… K0000 to K2025
(Caution) Due to that inputs/outputs of the devices are fixed for different items, do not gain access
to the following device areas.
・ Execution of TO command to device area of FROM
・ Execution of FROM command to device area of TO
・ Execution of buffer access command to device area that is not used
5-1
5.Data Link with PLC
MS-QZ UNIT A
5.2 I/O assignment
This section describes the assignment of I/O signals in this unit.
n will be determined based on the I/O assignment of PLC and the placement position in this unit.
5-2
5.Data Link with PLC
MS-QZ UNIT A
5-3
5.Data Link with PLC
MS-QZ UNIT A
5-4
5.Data Link with PLC
MS-QZ UNIT A
Subsequent examples of buffer memory data show a case where the following slave stations are connected.
5-5
5.Data Link with PLC
MS-QZ UNIT A
・ One slave station occupies 5 words independently of connection to slave stations, and the devices are
fixed in the order of slave station addresses.
・ The devices are stored, starting from the lowest byte.
・ For the interpretation of data of each device, refer to the instruction manual for a slave station to
be used.
・ In the case of communication error of a slave station, the applicable device is retained. (It cannot be
forcedly written because of being overwritten.)
・ Only at the startup of this unit, all devices are cleared. (Zero clear)
5-6
5.Data Link with PLC
MS-QZ UNIT A
5.4.4 Error information 1 word
This information contains an error status flag of this unit.
Device b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
K0325 Slave station address with address error * 0 * * * * * *
5-7
5.Data Link with PLC
MS-QZ UNIT A
5.4.6 Setting information 8 words × 64 slave stations = 512 words
This information contains setting data from EMC.
5-8
5.Data Link with PLC
MS-QZ UNIT A
5-9
5.Data Link with PLC
MS-QZ UNIT A
5-10
5.Data Link with PLC
MS-QZ UNIT A
EMC-A, or EMC-B.
5-11
5.Data Link with PLC
MS-QZ UNIT A
5.4.10 Command report information 2 words × 64 slave stations = 128 words
This information contains command report data from a slave station.
・ An LSZ-MRU slave station stores data only when a command code is "98h", "99h", "C7h", "C8h", "CAh", and
"CBh", and also the code. (A B/NET recognition code "FFh" is neglected.)
First word Code
Second word
5-12
5.Data Link with PLC
MS-QZ UNIT A
5-13
5.Data Link with PLC
MS-QZ UNIT A
・When turning on the power for the slave station, check the status of the output
! CAUTION information.
Some programs may cause malfunction (sudden starting).
・Output processing is executed even during address error or parameter error on
the slave station. Even during non-connection or communication errors, output
processing is continued. Take safety measures for some programs, such as output
clear at the above errors.
5-14
5.Data Link with PLC
MS-QZ UNIT A
5.4.14 Command request information 1 bit × 64 slave stations = 4 words
This information contains the relevant station number flag that executes a command request to a slave station.
Device b15 B14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
K1828 10h 0Fh 0Eh 0Dh 0Ch 0Bh 0Ah 09h 08h 07h 06h 05h 04h 03h 02h 01h
K1829 20h 1Fh 1Eh 1Dh 1Ch 1Bh 1Ah 19h 18h 17h 16h 15h 14h 13h 12h 11h
K1830 30h 2Fh 2Eh 2Dh 2Ch 2Bh 2Ah 29h 28h 27h 26h 25h 24h 23h 22h 21h
K1831 40h 3Fh 3Eh 3Dh 3Ch 3Bh 3Ah 39h 38h 37h 36h 35h 34h 33h 32h 31h
・ One slave station occupies 1 bit independently of connection to slave stations, and the devices are fixed
in the order of slave station addresses.
・ Set "1" to the relevant station number bit in a slave station requesting a command.
・ If "OFF→ON" is provided to exclusive communication request (Y(n+1)2), sending processing is executed.
Hence, it is necessary to complete writing command request information and command output information
in a buffer memory device until turning the exclusive communication request (Y(n+1)2) ON.
・ If receiving (response from a slave station) processing is completed, exclusive communication completed
(Xn2) becomes "OFF→ON".
2) When upper bytes are 00h (except when lower code is 02h), it sends (request) to a slave station 1-byte
command output data with B/NET recognition code. A range of data is 0040h to 00FFh.
5-15
5.Data Link with PLC
MS-QZ UNIT A
First word 00h Code
3) In the case of upper bytes other than 00h, it sends (request) to a slave station 2-byte command output
data with B/NET recognition code. A range of data is 0140h to FFFFh.
First word Code (upper) Code (lower)
5-16
5.Data Link with PLC
MS-QZ UNIT A
5-17
6. Self-Diagnosis Function
MS-QZ UNIT A
Chapter 6 Self-Diagnosis Function
This chapter describes the self-diagnosis function of this unit.
(1) Functionality
・ This function monitors a low-level retention time of a signal line S on a transmission bus in the
inside of this unit, determines an error when the status of the signal line does not recover within
a determination time (200ms to 500ms) (during continuation of fault), and separates this unit from
the transmission bus by relay contact.
This unit
Fault
(separation) Transmission
bus
Fault
(separation)
・If the master or slave station detects a bus low status by its self-diagnosis function
! CAUTION (at single fault), it will separate the bus.
† When several LSZ slave stations are placed on the same base unit (LSZ-B), all the slave
stations are separated. Therefore, be careful during the system design.
6-1
6. Self-Diagnosis Function
MS-QZ UNIT A
(1) Functionality
・ This function monitors a stopping time for a linking status between the PLC and this unit (without the
execution of FROM/TO command), determines an error when the linking status does not recover within a
determination time (10 seconds) (during continuation of fault), and opens an output to the slave station
(initialization). Linking stop that is caused by "STOP" of the PLC is also determined to be an error.
・ Immediately after the determination of the error, it sends cleared (00h) output data to a slave station.
The station opens the output by cleared data. Output open is executed for all slave stations (a range
of mode 1 execution is 01h to 40h of slave station address).
・This unit detects an error of the communication function of the PLC from the stop of the linking status
in (1). At the occurrence of an error, the execution of FROM/TO command is stopped to enable the start
of the output open function through the PLC's program.
Also, be careful to the error detection and output open functions of the slave station.
Slave station
(Fault cause) Fault (output open)
・ Fault on PLC (CPU unit etc.)
・ For the faults of upper controllers and buses, a program is required in the PLC.
6-2
6. Self-Diagnosis Function
MS-QZ UNIT A
6.3 Error detection and output open functions of slave station (restrictions at the application of this unit)
A slave station provides the error detection and output open functions of this unit.
The functions minimize the effect on the system in the PLC, between the PLC and this unit, and from this unit's
single fault (internal fault) to transmission stop.
(Point) When selecting a determination time 7s, restrict a range of slave stations to 01h to 20h (up
to 32 stations) before applying the time.
→For the restriction of the range of slave stations, refer to the section 5.4.18.
(1) Functionality
・The slave station monitors a stopping time for a linking status between this unit and the slave station
(without the execution of transmission from this unit). It determines an error when the linking status
does not recover within a determination time (during continuation of fault), and open the output
(initialization).
Under "STOP" of the PLC, this unit does not stop the linking.
・In the determination time, the selection of "7s" and "15s" or "Arbitrary setting of 7 to 160s" and "time
fixed" depends on slave stations (refer to the following table). For details of the determination time,
refer to the instruction manual for a slave station to be used.
Example of slave station Setting of time for detection of no response from master station
LS-44GSX, -08GSX, etc. 7s fixed
LSZ-44, -80, -08, EMC-Z, -A, etc. OFF, 7s, and 15s
EMC-B etc. OFF, and 7s to 160s
H-A7CDL etc. OFF, 5s, 7s, 15s, 20s, 25s, 30s, 40s, 50s, 60s, and 160s
・Immediately after the determination of the error, the slave station clears (resets) its internal output
data. The station opens the output by clear. The determination time is selected by the slave station by
setting of this unit, as shown below. Be careful to the application of a slave station without selection
(with time fixed).
・When not requiring the function, set the slave station to not select the function, or adopt a slave station
without the function.
Slave station
(Fault cause)
・ Power discontinuity of this unit Fault (output open)
・ Fault of this unit Depending on the specifications
・ Fault of CDL bus etc. and setting of slave station
6-3
6. Self-Diagnosis Function
MS-QZ UNIT A
・ When the output of the slave station is opened by its self-diagnosis function
! CAUTION (transmission stop = fault), check the setting of this unit and the specifications
of the slave station.
† During system design, note that some settings are unsupported or fixed depending on
the specification of a slave station.
6-4
6. Self-Diagnosis Function
MS-QZ UNIT A
(2) Functionality
The function has the following 6 test items.
① Display test
② Setting test
③ Hardware test
④ I/O operation test
⑤ CDL transmission test (sending function)
⑥ CDL transmission test (receiving function)
6-5
6. Self-Diagnosis Function
MS-QZ UNIT A
6.4.3 Hardware test
The operation of parts in the interior of this unit is tested.
(1) Testing step
Step 1: Restart this unit with SW2="C" and SW1="C".
(2) Test content
Represent the results of the test for the operation of the parts in LED display. When the result of the
test is abnormal, the relevant LED display turns off.
・ RAM1 : Check of reading and writing to internal work memory (RAM)
・ RAM2 : Check of reading and writing to internal shared memory (RAM)
・ Transmission: Check of access to internal transmission CPU
・ ROM : Check of sum to internal program (ROM)
・ SW3 : Check of unit setting (SW3) ✝ The LED display represents binary numbers of positive
logic.
Status 8 7 6 5 4 3 2 1
display
Tested parts SW3 ROM Transmission RAM2 RAM1
(3) Check items
Visually check that the results of testing are normal (lighting of the (relevant LED) display). If the
unit setting is "0", it is normal.
6-6
6. Self-Diagnosis Function
MS-QZ UNIT A
6-7
6. Self-Diagnosis Function
MS-QZ UNIT A
6-8
7. Maintenance and Inspection
MS-QZ UNIT A
Chapter 7 Maintenance and Inspection
This chapter describes the items that should be daily or periodically inspected, so that users can operate
this unit in a normal and best condition at any time.
・Replace the transmission power supply with a new one on a regular basis.
! CAUTION If its life expires, the transmission system will stop.
For details about replacement timing, contact the power supply manufacturer.
7-1
8.Troubleshooting
MS-QZ UNIT A
Chapter 8 Troubleshooting
This chapter describes the investigation of causes of various errors generated by the use of this unit,
and easy actions for the errors.
For the content related to the PLC, refer to troubleshooting in the CPU user's manual.
8-1
8.Troubleshooting
MS-QZ UNIT A
[RUN]turns off
No
Is power supplied? Supply control power
(Power supply unit)
No Yes
Does [RUN] turn on?
No
8-2
8.Troubleshooting
MS-QZ UNIT A
[Q.CPU]turns off
Yes
No Yes
Does [Q.CPU] blink?
Yes
No Yes
Does [Q.CPU] blink?
10msec order
(Point)
[Q.CPU] displays directly the status of execution of the FROM/TO command. The status can be judged on the
basis of lighting or blinking of [Q.CPU].
As [Q.CPU] turns on at the command execution, the status cannot be visually determined when a command
execution interval is excessively long.
8-3
8.Troubleshooting
MS-QZ UNIT A
[SD]turns off
Yes
Does[RD]turn off? Flow when [RD] turns off
No
No
Does[C-ERR.]turn off? Flow for system malfunction
ー
Yes
Is it possible to Yes
execute load control by
the CPU unit?
No
[RD]turns off
No
Does[C-ERR.]turn off? Flow for system malfunction
Yes
Is the transmission No
power supplied
(24VDC)?
Turn the transmission power on (review)
Yes
Yes No
Does [RD] turn off?
Yes
Is it possible to
execute load control by
the CPU unit?
No
8-4
8.Troubleshooting
MS-QZ UNIT A
[C-RUN]turns off
No
Does[C-ERR.]turn off?
Flow for system malfunction
Yes
Is it possible to Yes
execute load control by
the CPU unit?
No
8-5
8.Troubleshooting
MS-QZ UNIT A
No (Lighting)
Serious fault
Does [C-ERR.] blink?
8-6
8.Troubleshooting
MS-QZ UNIT A
Yes No
Does address error
continue?
(Note) It takes a time to release
the error.
Yes
Does [3] turn on by SW=D Master station redundant address error †
in status LED display?
†Redundant master stations on the CDL
transmission bus
No
The master station is redundant.
Turn the system power off and reconfirm the wiring.
Yes
Does transmission error Confirm the transmission bus
occur?
Yes (Unit Fault)
Yes No
Does address error
continue?
(Note) It takes a time to
H/W fault of this unit release the error.
(Point)
The sub-slave address error cannot be confirmed in status LED display. Check the content of the error based
on error and attribute information.
8-7
8.Troubleshooting
MS-QZ UNIT A
No
Does parameter error
continue?
(Note) It takes a time to release the
Yes error.
Yes No
Does parameter error
continue?
(Note) It takes a time to release the
H/W fault of this unit error.
8-8
8.Troubleshooting
MS-QZ UNIT A
No
Yes
The error is detected if the absence of slave stations
available for communication on the transmission bus
continues for 15 seconds.
Yes No
Does slave station
absence error continue?
8-9
8.Troubleshooting
MS-QZ UNIT A
No
Check that the S-N voltage is about 12V.
(Voltage range: About 10 to 13V)
Yes No
Does transmission bus
error continue?
8-10
8.Troubleshooting
MS-QZ UNIT A
Is 24VDC output of No (Output deterioration due to the end of the supply's useful life)
transmission power supply
normal?
Yes
No
Is the P-N wiring normal? Check the P-N voltage
Yes No
Does transmission
power error continue?
8-11
9. Programming
MS-QZ UNIT A
Chapter 9 Programming
This chapter describes basic programming for this unit.
The chapter includes the following communication programs.
Each time chart describes direct and refresh methods of input/output control in the PLC.
(Point) The refresh method requires a processing time twice the direct one.
A scanning time by the PLC is increased if the execution of buffer memory access command (FROM/TO) from the
PLC is segmentalized.
The increase of the scanning time affects a data refresh cycle between the PLC and this unit.
Devices of this unit are collectively assigned per the same data. Hence, perform batch data processing.
9-1
9. Programming
MS-QZ UNIT A
Processing ・Setting of operating environment of this unit (information on connected slave stations
content and the maximum number of slave stations for communication)
† The operating environment and system configuration of this unit shall be always checked
to prevent an accident that results from on-line modification.
However, slave stations that are not communicated (power disconnection etc.) shall be
neglected.
Processing ・At startup of the system
timing ・Transfer and modification of equipment, change of connected slave station, and change of
address
Unless parameters are not set at the startup of the system, Unit READY (X08), or control running permission
flag will not turn ON.
(After the setting of the parameters, Unit READY (X08) will turn ON at the completion of check against the
system information.)
(†) When the parameters are set, Unit READY (X08) turns ON regardless of the presence or absence of a parameter
error.
It is needed that control sending should not be provided to avoid error control sending at the occurrence
of the parameter error.
Parameter setting
9-2
9. Programming
MS-QZ UNIT A
READY(X08)
t1 t2
READY(X08)
Setting time≒1s
[Remarks]- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・The details of CDL setting errors can be confirmed in LED display and devices.
・For recovery means at the occurrence of setting error, refer to the section 8.2.
・After the correction of a mistaken setting value, a setting request is made again to complete the correction
of mistaken setting of the program. →Manual recovery
・After the change of a mistaken connected slave station to a correct slave station, setting error turns
OFF at communication recognition. →Automatic recover
・After changing a mistaken slave station address to a correct one, restart the slave station.
→Manual recovery
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
9-3
9. Programming
MS-QZ UNIT A
Input information
[Remarks]- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・A receiving/transfer cycle is affected by a scanning time of the PLC. Minimize the time as much as possible
by programming reducing the time or by the selection in the PLC (CPU processing speed-up).
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
9-4
9. Programming
MS-QZ UNIT A
│ <入力,子局交信,運転,エラー情報
< Read input/slave station communication/running/error information読込 > >│
│ X0000 X000F X0008 X0006 │
├─┤ ├───┤/├───┤ ├─┬─┤ ├─┬──────────────────[FROMP H0 K0 R**** K326 ]┤
│ MS-QZ Hardware Unit │ FROM │ Input │
│ READY fault │ command │ information │
READY 01H station
│ │ permission │ │
│ │ │ │
│ │ └────────────────────────────────────[SET Y0016 ]┤
│ │ FROM │
│ │ command │
completed
│ │ │
│ │ X0006 │
│ └─┤/├──────────────────────────────────────[RST Y0016 ]┤
│ FROM command FROM │
│ permission command │
completed
・Data in the PLC is described by R (file register), but there are no problems in the use of other registers.
・Ensure to enter Unit READY (X08) conditions for program execution, and do it by pulse processing.
[Remarks]- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・Change the number of data or delete the command for processing and data not to be used.
However, I/O processing (X/Y) for each command completed is required.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
9-5
9. Programming
MS-QZ UNIT A
READY (X08) ON
FROM command
permission (X06)
FROMP FROMP FROMP
FROM command
completed (Y16) t1 t2 t1 t2 t1 t2 t1 t2
TO command
permission (X07)
TOP TOP
TO command
completed (Y17) t1 t2 t1 t2 t1 t2 t1
Receiving/transfer cycle
READY (X08) ON
FROM command
permission (X06) FROMP FROMP FROMP
FROM command
completed (Y16) t1×2 t2 t1×2 t2 t1×2 t2 t1×2 t2
TO command
permission (X07) TOP TOP
TO command
completed (Y17) t1×2 t2 t1×2 t2 t1×2 t2 t1×2
Receiving/transfer cycle
9-6
9. Programming
MS-QZ UNIT A
Processing ・Receiving (FROM)/transfer (TO) of transient input/output data on the request of the PLC
content [Transfer]
(1) The PLC transfers (TO) command request/output information at arbitrary timing.
(2) This unit monitors the presence or absence of each command request information, and
sends the command output information to the slave station if requested.
(3) The slave station receives command output information and processes the data based
on the specifications of the slave station.
[Receiving]
(1) The slave station sends command response (setting and running history) information
as a response to the receiving of the command output information.
(2) This unit stores received data in command response (setting and running history)
information designated regardless of the change of the received data.
If the slave station's response to the request of the PLC is completed, it makes
exclusive communication completed (X02) ON.
(3) The PLC confirms exclusive communication completed (X02), and receives command response
(setting and running history) information.
Processing ・After confirming "ON" of Unit READY (X08) in the PLC that represents running permission
timing ・Arbitrary timing from the PLC
② Confirmation of response
Execute data analysis after confirming the presence or absence of a response from the relevant station.
Unless the presence or absence of the response is confirmed, old data (undefined data) may be mistakenly
processed.
The confirmation of the following devices enables the determination of "request", "request status"
and "response status".
・Request : Command request information ("1=Request found")
・Request status: Attribute information b11 ("0=Request completed" and "1=Sending error"†)
†In the case of sending error, a timeout time (10s) for response wait does not
occur due to the absence of the response.
・Response status: Command result information ("0=Normal response completed) and "1=No response
(timeout time (10s)†)
9-7
9. Programming
MS-QZ UNIT A
† In the case of no response, request it again after confirming "request
restriction", "request" and "request status".
[Remarks]- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・A slave station that responds to the request is restricted to a CDL-Z slave station. CDL-V slave stations
are not supported.
・Basically confirm the result of the execution, using the relevant bit of the command result information.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
9-8
9. Programming
MS-QZ UNIT A
・Data in the PLC is described by R (file register), but there are no problems in the use of other registers.
・Perform the request when exclusive communication completed (X02) is OFF.
・Ensure to enter Unit READY (X08) conditions for program execution, and do it by pulse processing.
READY(X08) ON
FROMP
Exclusive communication
request (Y12)
TOP
Exclusive communication
completed
t1 t2=Response wait time=10s max
(X02)
[Response time]
This unit starts a response check after the completion of a request.
Usually, the response is returned to the relevant stations (during a given cycle). Consequently, a
response wait does not occur.
However, the response may be delayed, depending on traffic jams or the specifications of the slave
station.
Unless all responses to the request are collected within 10s after the start of the response check,
the request will be forcedly terminated due to the timeout.
9-9
9. Programming
MS-QZ UNIT A
9.4 Exclusive communication 2 (general-purpose: transient output)
Transient data (simultaneous transmission (command code "86h") is sent from and received by this unit on the
request of the PLC.
Confirm "ON" of Unit READY signal X08 in the PLC that represents running permission before executing the receiving
and sending of the data.
[Remarks]- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・A slave station that responds to that responds the request is restricted to a CDL-Z slave station. CDL-V
slave stations are not supported.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・Data in the PLC is described by R (file register), but there are no problems in the use of other registers.
・Perform the request when simultaneous transmission completed (X03) is OFF.
・Ensure to enter Unit READY (X08) conditions for program execution, and do it by pulse processing.
9-10
9. Programming
MS-QZ UNIT A
(4) Time chart
The time chart based on the item of (3) is shown below.
READY(X08) ON
Simultaneous transmission
sending request (Y13)
TOP
Simultaneous transmission
completed (X03)
t1
9-11
9. Programming
MS-QZ UNIT A
9.5 Exclusive communication 3 (general purpose : transient input←Only setting of EMC-Z, EMC-A and EMC-B)
Transient data (setting from EMC (command code "C0h")) is sent from and received by this unit on the request
of the EMC.
Confirm "ON" of Unit READY signal X08 in the PLC that represents running permission before executing the receiving
and sending of the data.
(2) Report
Execute data analysis after confirming the presence or absence of a report from the relevant station.
If the presence or absence of the report is not confirmed, old data may be mistakenly processed.
[Remarks]- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・Slave stations that respond to the request are restricted to EMC-Z, EMC-A and EMC-B.
・Confirm the report at the relevant bit for setting status information, and perform an analysis of the change
content on the program.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・Data in the PLC is described by R (file register), but there are no problems in the use of other registers.
・The change confirmation is described by pulse cut processing of status signal, but there are no problems
in the use of a pulse signal.
・Ensure to enter Unit READY (X08) conditions for program execution, and do it by pulse processing.
9-12
9. Programming
MS-QZ UNIT A
READY(X08) ON
Change reception Change reception
Setting change
request (X04) FROMP FROMP
Processing cycle
READY(X08) ON
Change reception Change reception
Setting change
request (X04) FROMP FROMP
Change reception
Setting change
t2 t1×2 t2 t1×2 possible
confirmation (Y14)
Processing cycle
9-13
9. Programming
MS-QZ UNIT A
9.6 Exclusive communication 4 (general-purpose: transient input)
Transient data (except setting from EMC (command code "C0h")) is sent from and received by this unit on the
request of the slave station.
Confirm "ON" of Unit READY signal X08 in the PLC that represents running permission before executing the receiving
and sending of the data.
Processing ・Receiving (FROM) of transient data on the request of the slave station
content In the case of unprocessed (STOP) by the PLC, the relevant area is overwritten.
[Receiving]
(1) The slave station sends (report) transient data at the change of its internal data.
(2) This unit stores the data in command report information regardless of the change of
received data. In this case, it recognizes the received data as report, set the relevant
station (command status information), and provides ON to command setting change request
(X05) to the PLC.
(3) The PLC confirms command change request (X05) and receives (FROM) the command report
information.
Processing ・After confirming "ON" of Unit READY (X08) in the PLC that represents running permission
timing ・Arbitrary timing from the slave station
(2) Report
Execute data analysis after confirming the presence or absence of a report from the relevant station.
If the presence or absence of the report is not confirmed, old data may be mistakenly processed.
[Remarks]- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・Slave stations that respond to the request are restricted to EMC-Z, EMC-A and EMC-B.
・Confirm the report at the relevant bit for setting status information, and perform an analysis of the change
content on the program.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
・Data in the PLC is described by R (file register), but there are no problems in the use of other registers.
・The change confirmation is described by pulse cut processing of status signal, but there are no problems
in the use of a pulse signal.
・Ensure to enter Unit READY (X08) conditions for program execution, and do it by pulse processing.
9-14
9. Programming
MS-QZ UNIT A
READY(X08) ON
Change reception Change reception
Command change
request (X05) FROMP FROMP
Command change Change reception
confirmation (Y15) t2 t1 t2 t1 possible
Processing cycle
READY(X08) ON
Change reception Change reception
Command change
request (X05) FROMP FROMP
Processing cycle
9-15
10. Example of Program Preparation
MS-QZ UNIT A
Chapter 10 Example of Program Preparation
This chapter describes an example of program preparation for the PLC to this unit.
CPU unit
Transmission
Transmission bus
power supply
(24VDC)
START
OFF SM402
Startup of PLC or
STOP→RUN of PLC
Setting of communication
control
Parameter setting
Normal communication
(input/output)
END
10-1
10. Example of Program Preparation
MS-QZ UNIT A
10.3 Example of program
This section describes an example of program based on the program flowchart.
RST Y16
TO command completed
SET Y17
X07
RST Y17
10-2
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
0 0 0 0 D04 D03 D02 D01 - - - - DI4 DI3 DI2 DI1
② LS-08 (GSX)
Output information (Master station→Slave station) Input information (Slave station→Master station)
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
D08 D07 D06 D05 D04 D03 D02 D01 - - - - - - - -
③ LS-80 (GS)
Output information (Master station→Slave station) Input information (Slave station→Master station)
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
0 0 0 0 0 0 0 0 DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1
④ LS-AI (GS)
Output information (Master station→Slave station) Input information (Slave station→Master station)
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b0
0 0 0 0 0 0 0 0 Analog quantity: 0 to 255
⑤ LS-AO (GSX)
Output information (Master station→Slave station) Input information (Slave station→Master station)
<<DATA1>> <<DATA1>>
b7 b0 b7 b6 b5 b4 b3 b2 b1 b0
Analog quantity: 0 to 255 - - - - - - - -
Appendix 1-1
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b2 b1 b0
Reve Norm
Main circuit current value rse al
D07 D06 D05 0 D04 D03 D02 D01 rota
Fault
rota
(0 to 124%)
tion tion
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b2 b1 b0
Reve Norm
rse al
D07 D06 D05 0 D04 D03 D02 D01 INT PF OCI/UC OC GF
rota
Fault
rota
tion tion
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b2 b1 b0
Main circuit current value (0 to
D07 D06 D05 0 D04 D03 D02 D01 Fault Running
126%)
・ Set each transmission mode for EMC-VB by 'SW2' in the main body.
・ The combination with transmission option unit enables transmission.
・ The combination with output option unit enables D03 to D07 control.
The signal location for D04 depends on the settings of option units.
Appendix 1-2
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
0 0 0 0 0 0 0 0 DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b0
- - - - - - - - Analog quantity: 0 to 255
Appendix 1-3
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
- - - - - - - - DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1
<<DATA2>> <<DATA2>> T* is a test signal for test mode.
b15 b14 b13 b12 b11 b10 b9 b8 b15 b14 b13 b12 b11 b10 b9 b8
- - - - - - - - T8 T7 T6 T5 T4 T3 T2 T1
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b0
- - - - - - - - Analog quantity of channel 1: 0 to 255
<<DATA2>> <<DATA2>>
b15 b14 b13 b12 b11 b10 b9 b8 b15 b8
- - - - - - - - Analog quantity of channel 2: 0 to 255
Appendix 1-4
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
⑥ LSZ-160
Output information (Master station→Slave station) Input information (Slave station→Master station)
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
- - - - - - - - DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1
<<DATA2>> <<DATA2>>
b15 b14 b13 b12 b11 b10 b9 b8 b15 b14 b13 b12 b11 b10 b9 b8
- - - - - - - - DI16 DI15 DI14 DI13 DI12 DI11 DI10 DI9
⑦ LSZ-016
Output information (Master station→Slave station) Input information (Slave station→Master station)
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
- - - - - - - - IN8 IN7 IN6 IN5 IN4 IN3 IN2 IN1
<<DATA2>> <<DATA2>>
b15 b14 b13 b12 b11 b10 b9 b8 b15 b14 b13 b12 b11 b10 b9 b8
- - - - - - - - IN16 IN15 IN14 IN13 IN12 IN11 IN10 IN9
Appendix 1-5
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
Appendix 1-6
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
Appendix 1-7
Appendix 1 Slave Station Input/Output Information
MS-QZ UNIT A
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0
X27 X26 X25 X24 X23 X22 X21 X20 Y47 Y46 Y45 Y44 Y43 Y42 Y41 Y40
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b2 b1 b0
Main circuit current value
X27 X26 X25 X24 X23 X22 X21 X20 Y42 Y41 Y40
(0 to 124%)
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b2 b1 b0
Main circuit current value (0 to
X27 X26 X25 X24 X23 X22 X21 X20 Y41 Y40
126%)
<<DATA1>> <<DATA1>>
b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b2 b1 b0
Main circuit current value
X27 X26 X25 X24 X23 X22 X21 X20 Y42 Y43 Y40
(0 to 124%)
Appendix 1-8
Appendix 2 Operation of This Unit by PLC Mainpulation
MS-QZ UNIT A
(1) "Power activation" by the operation of PLC
This unit restarts at power activation (including short interruption). Consequently, the operation of
the PLC is disabled for about 15s.
(Point) A time required from a restart to the operable state is about 15s.
During the time, the PLC becomes "control disabled". Be careful to power supply at the
application.
This unit is restarted to execute the setting of slave station output at startup
The setting of SW2 (including system configuration) enables the output of slave station to become all
open (OFF) at the startup of this unit.
(Point) It makes the output all-open immediately before the operable state after a restart. However,
the output is retained otherwise when it is latched in the slave station (loaded side).
When it is controlled only with the output of the slave station (without latching mechanism),
and the load cannot be stopped at the startup, select "retention" by the setting of SW2.
Appendix 2-1
Appendix 3 Product Information
MS-QZ UNIT A
Product Notes
sub-code
A (Not shipped.)
B LSZ-MRU and H-A7CDL cannot be set to slave stations.
If they are connected to this unit, it will not function properly.
C~ LSZ-MRU and H-A7CDL can be set to slave stations.
Appendix 3-1